Plans (3)
GENERAL NOTES AERIAL VIEW OFFICE COPY E D CODE AND STANDARDS h 1.ALL WORK SHALL COMPLY WITH 2017 OREGON ELECTRIC SPECIALTY CODE(OESC),2019 OREGON T STRUCTURAL SPECIALTY CODE,2017 OREGON RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCAL x'r; "'' BLUFAWLN BUILDING AND ELECTRICAL CODES. CITY OF TIGARD 2.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. 1VO171O�1 SITE NOTES/OSHA REGULATION Orem,UT 84097 1.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 800.377.4480 2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM. WWW.BLUERAVENSOLAR.COM 3.THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS. 4.ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND CONFIDENTIAL-THE INFORMATION THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT � ' HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE 5.N0,OF SHINGLE LAYERS:1 THE BUILDING OR STRUCTURE. 4 „c a EXCEPT BLUE RAVEN SOLAR NOR a q . �„,- �, , w, SHALL IT BE DISCLOSED IN WHOLE OR SOLAR CONTRACTOR r IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT 1.MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. low IN CONNECTION WITH THE SALE AND 2.IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER 7 3 OF THE RESPECTIVE EQUIPMENT, THE MANUFACTURER'S INSTALLATION REQUIREMENTS. WITHOUT THE WRITTEN PERMISSION 3.AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF OF BLUE RAVEN SOLAR LLC. STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. 4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. , 5.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A x1 II �'". '' . t` k SUITABLE SEALING COMPOUND. C E RT I F I E D 6,DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. +�- a � #' � n � 7.ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W1 SUITABLE WIRING CLIPS 8.MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT ; _ w * i PV INSTALLATION AVAILABLE. ` k PROFESSIONAL 9.ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AC Scott Gurney PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS,AND , #PV-011719-015866 CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND �,; - LISTED FOR THE APPLICATION PER NEC 690.4(8). t 10.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. CONTRACTOR:>I s $ � 11.TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED) ;+ Q B RS FIELD OPS IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS. 7•"f 385-498-6700 EQUIPMENT LOCATIONS 1 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT „- .x WILL BE PROVIDED AS PER SECTION NEC 110.26. 2.EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31(A)AND NEC TABLE 310.15(B). 3.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. Z 4,ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. 0 PROJECT INFORMATION: CTTY CSF TIGARD Q N E EMEWED FO CODE t:O1VIPLIA � NUMBER OF STORIES: 2 O r- LI.I CONDUIT RUN: Interior ),J�rovcd' [ ] LL N ECOBEE QTY: 1 Z o Fn LIGHT BULB QTY: 18C. [ ' D O p r PV METER: Not Required Perniit #: v%s Zb2 cn SIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX w �� CO O w v Address: [�sS SW — 2 o � N ROOF TYPE (1) INFORMATION: -- -- WIND SPEED: 100 MPH CONSTRUCTION -V-B PV1 -COVER SHEET Approved plan; O W C } ROOF TYPE: Comp Shingle Siiitc ##: li GROUND SNOW LOAD: 40 Ib/ftz ZONING: RESIDENTIAL PV2 SITE PLAN shall be on 'ob Si ' c~n � N Y FRAMING TYPE: Rafter Date: to SHEATHING TYPE: PLYWOO13 EXPOSURE FACTOR: C PV3 - ROOF PLAN V 0 0 STANDOFF: SFM Infinity Flashkit SEISMIC DESIGN CATEGORY: D PV4 - STRUCTURAL RACKING: Unirac SFM Infinity @48" OC Portrait/48" OC Landscape PV5 - ELECTRICAL 3-LINE DIAGRAM DRAWING BY PV6 - ELECTRICAL CALCULATIONS SCOPE OF WORK NUMBER OF ATTACHMENTS: 50 PV7 -WARNING LABELS AND LOCATIONS Enphase Energy ROOF TYPE (2) INFORMATION (IFAPPLICABLE): INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM AND ANY (ALL OTHER SHEETS AS REQUIRED) 'SEE PV4.2 NECESSARY ADDITIONAL WORK NEEDED FOR INSTALLATION. SS - PRODUCT SPEC. SHEETS PLOT DATE October 18, 2021 SYSTEM TO BE INSTALLED INFORMATION: VALIDITY OF PERMIT UTILITY COMPANY: PROJECT NUMBER: SYSTEM SIZE: 7.6 kW DC THE ISSUANCE OF A PERMIT LIABILIT4 Portland General Electric (PGE) 410289 BASED ON CONSTRUCTION The City Of Tigard and its SHEET NAME: MODULE TYPE: (19) REC Solar REC400AA Pure DOCUMENTS AND OTHER employees shall not be INVERTER TYPE: Enphase IQ7PLUS-72-2-US DATA SHALL NOT PREVENT COVER SHEET MONITORING: Enphase IQ Combiner 3 X-IQ-AM 1-240-3 THE CODE OFFICIAL FROM responsible for discrepancies PERMIT ISSUER: whl-h appear herein. Cit of Tigard OFFICE �r REVISION: PAGE NUMBER mai REQUIRING THE CORRECTION �` Y g i OF ERRORS.ORSC 105.4 0 PV 1 LEGEND iHF cci-,ii JUNCTION BOX cwTv;Fi--,,rrr vat BU-1 E- RAVE N ojl V'4UTILITY METER 0 �-- 1403 N.Research way U--v "I MAIN SERVICE PANEL Orem,UT 84097 Jay - -v ;%I MSP 800.377.4480 LEL U. OAC AC DISCONNECT WWW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR LOAD CENTER IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT FL C� IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION SUB SUBPANEL OF BLUE RAVEN SOLAR LLC. PV PV METER /N/A B�C TS TRANSFER SWITCH CERTIFIED PV INSTALLATION FIRE SETBACK PROFESSIONAL Scott Gurney #PV-01 1719-015866 Lij TRENCHING CONTRACTOR: 4-j U) PROPERTY LINE BRS FIELD OPS = 00 0 385-498-6700 LL SCALE: 3/32" = V-0" 0 0 z LO 0 0 0 cr T— F- ILL C\j C\j cc 0 LLN z 0 — 0) U) W cc Cf) T— Uj 0 W 0 Ci) 0 MSPI >- Al I = w f 0 CB CZ LO DRAWING BY: Enphase Energy PLOT DATE: October 18, 2021 PROJECT NUMBER: 410289 SHEET NAME: 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER SITE PLAN 2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A REVISION: PAGE NUMBER: ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) 0 PV2 LEGEND 0 JUNCTION BOX pL�� RAVEN�/�E!1�` BLUE SKYLIGHT S UTILITY METER 1403 N.Research Way MSP MAIN SERVICE PANEL Orem,UT 84097 800.377.4480 MP3 OAC AC DISCONNECT WWW BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION #OF MODULES: 4 HEREIN CONTAINED SHALL NOT BE 9 MP2 CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE AZIMUTH: 269 PITCH: 26 EXCEPT BLUE RAVEN SOLAR NOR #OF MODULES: 3 SHALL IT BE DISCLOSED IN WHOLE OR AZIMUTH: 89 ❑ LOAD CENTER IN PART TO OTHERS OUTSIDE TSRF: 69°% c�V, LC RECIPIENTS ORGANIZATION,EXCEPT AREA: 290 ft.2 PITCH: 26 IN CONNECTION WITH THE SALE AND TSRF: 72% USE OF THE RESPECTIVE EQUIPMENT, 2 SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION AREA: 330 ft. OF BLUE RAVEN SOLAR LLC. SKYLIGHT �f PV PV METER NABCEP TS TRANSFER SWITCH CERTIFIED PV INSTALLATION W FIRE SETBACK PROFESSIONAL Scott Gurney Z #PV-011719-015866 0 TRENCHING = CONTRACTOR: 1' LL. PROPERTY LINE BRS FIELD OPS 1 0 I 385-498-6700 SCALE: 1/8" = 1'-0" Z _ O LL o MP4 # OF MODULES: 5 Q N AZIMUTH: 270 MP1 N PITCH: 26 # OF MODULES: 7 r- Lii TSRF: 77% AZIMUTH: 90 0 N AREA: 245 ft.2 PITCH: 26 Z O N TSRF: 78% — cin Q) AREA: 252 ft.2 W N oo 0 W U n np -0 N 0 O MSP' Lo C M U � � � SKYLIGHT CB A POINT OF INTERCONNECTION DRAWING BY Enphase Energy UNDERGROUND SERVICE LINE PLOT DATE: October 18, 2021 PROJECT NUMBER 410289 SHEET NAME: 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER ROOF PLAN 2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A REVISION PAGE NUMBER: ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) 0 PV3 STRUCTURAL INFORMATION: STRUCTURAL NOTES: PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5" SPLICE ROOF TYPE (1): 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER 2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER p ROOF TYPE: Comp Shingle THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN BLUE RAVEN SHEATHING TYPE: PLYWOOD FRAMING TYPE: Rafter 3 FT. OF A ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) 1403 N.Research Way FRAMING SIZE: 2X8 Q 24" OCRafters 0324"O.0 23 --48" MAX. -- - LANDSCAPE Orem,UT 84097 — �- - CEILING JOIST SIZE: 2x8 @ 24" OC MAX. 800.377.4480 STANDOFF: SFM Infinity Flashkit W W W,BLUERAVENSOLAR.COM RACKING: Unirac SFM Infinity PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5" SPLICE CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE 48" OC Portrait/48" OC Landscape USED FOR THE BENEFIT OF ANYONE NUMBER OF ATTACHMENTS: 50 EXCEPT BLUE RAVEN SOLAR NOR n:, f ,1,r , tri SHALL IT BE DISCLOSED IN WHOLE OR N PART TO OTHERS OUTSIDE PV MODULE COUNT: 19 Modules RECIPIENTS ORGANIZATION,EXCEPT TOTAL ARRAY AREA: 332.7 ft2 (1 7.51 ft2/panel) IN CONNECTION WITH THE SALE ANDUSE OF THE RESPECTIVE EQUIPMENT, TOTAL ROOF AREA: 2369 ft2 23" WITHOUT THE WRITTEN PERMISSION ARRAY/ROOF AREA: 14%( NOTE:LISTED NUMBER OF ATTACHMENT POINTS ARE AN ESTIMATE ONLY AND MAY VARY y ATT A 48" MAX. PORTRAIT OF BLUE RAVEN SOLAR LLC. ARRAY WEIGHT: 950 lbs (50 lbs/panel) MAX.ATTACHMENT SPACING_ FRONT VIEW -RACKING ATTACHMENTS TO BE STAGGERED DISTRIBUTED LOAD: 2.86 lbs/ft2 BASED ON FIELD CONDITIONS.MAXIMUM ATTACHMENT SPACING TO BE FOLLOWED PER C BY SHIFTING EACH SUBSEQUENT ROW OF ' NA�, POINT LOAD: 19 lbs/attachment ENGINEER OF RECORD SPECIFICATIONS. SCALE: 3/4" - V-0" ATTACHMENTS OVER ONE RAFTER. CERTIFIED UNIRAC SFM INFINITY UNIRAC SFM MICRORAIL/SPLICE A PV INSTALLATION PV MODULE PROFESSIONAL — — r Scott Gurney REC SOLAR REC400AA PURE #PV-011719-015866 PV MODULE B PORTRAIT CONTRACTOR: ®� UNIRAC SFM SLIDER � - B 85 IE OPS ROOF STRUCTURE -6700 (E) ROOF MODULE--- O SHEATHING FLASHING ' ----- -- -B A �- .. (1) 5/16" STAINLESS STEEL LAG BOLT �- ; LANDSCAPE Z WITH 2-1/2" MIN. EMBEDMENT �_ 0 AND FLAT WASHER 2%" MIN. EMBED. � 26° - --1 -- WIDTH Q N c A MIDDLE/TOP STANDOFF DETAIL ATTACHMENT SPACING- SIDE VIEW Z o N SCALE: 3" - 1' 0" (E) BUILDING STRUCTURE D _ 0 Fn - SCALE: 1/2" = V-0" r cc M U REC SOLAR REC400AA PURE M � C) PV MODULE Q N iLO N CZ � o V UNIRAC SFM TRIMRAIL FLASHING DRAWING BY: UNIRAC SFM SLIDER AND Enphase Energy TRIMRAIL ROOF ATTACHMENT (E) ROOF - SHEATHING PLOT DATE October 18, 2021 (1) 5/16" STAINLESS STEEL LAG BOLT �1 PROJECT NUMBER: WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER410289 21/2" MIN. EMBED. SHEET NAME: STRUCTURAL B BOTTOM STANDOFF DETAIL REVISION PAGE NUMBER: SCALE: 3" = V-0" (E) BUILDING STRUCTURE 0 PV4 m 10 AWG THHNITK"-Z CU.BLACK 4 11 210 AAC (2) 10 A"THH, 7,CU.,BLACK M) MAX 12.1 A At W J Uv_ff WIN" (1) 10 AWG TII,114Ntt"WN-2.CU,,GREEN jfGQ soul M" 12-1 A ;11)12-2tC-FR,'THt4N1THL WN- CV MAX 12.1 AAC X 15 (1) 10 AWG THMNIT14WN-4 CU-,RED 112) 240 v Aic 3 121 10 AWG THNNI I HN-2,CU_RED 1L2) "0 VAC 240 V il) 6 AWG BAR[,CU IIECt 1, 240 V AC (1) 10 AWG THWIT"WN-2,CU,,WHIn IN) 11) 10 AWG THW4frNWN-2,CU,GREEN(ECK) 1 (11 3/4 INCH EMT EXTERIOR 111 -3/4 INCH EM7 Emilio 1147TRIl l7 EXTERIBLUE RAVEN DESIGNER NOTES: ELECTRICAL NOTES: 1403 N.Research Way Orem,UT 84097 LOAD SIDE BREAKER IN MSP. INTERIOR POI. ALL CONDUIT TO BE RAN AT LEAST 7/8 IN.ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. 800.377.4480 WWW.BLU ERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE (19) REC Solar REC400AA Pure RECIPIENTS ORGANIZATION,EXCEPT UL 1703 COMPLIANT IN CONNECTION WITH THE SALE AND (E)200A MAIN SERVICE PANEL ENPHASE IQ COMBINER 3USE OF THE RESPECTIVE EQUIPMENT, (E)200A/2P MAIN BREAKER (SOLAR LOAD ONLY) (19) Enphase 107PLUS-72-2-US WITHOUT THE WRITTEN PERMISSION 4"xWx4"PVC JB-1 EZ SOLAR UL 1741 COMPLIANT OF BLUE RAVEN SOLAR LLC. (E) PV AC DISCONNECT JUNCTION BOX JUNCTION BOX (E)200A 2P NON-FUSED (N)20A/2P LOCKABLE,VISIBLE OPEN CIRCUIT OF L, A A, 11-1 AFJB-17LI A F— N 30A,240V,2-POLE L2 I 1_2 I L2 1 10 MODULES //NA B C�FP (E)LOADS 2GLC ...LGLC BREAKER TO BE LOCATED CERTIFIEDj AT OPPOSITE END OF BUSSING 4N 9 FROM MAIN BREAKER 2 1 (N)30A/2P PV INSTALLATION L L2 L2 I F-1 (1 PROFESSIONAL I A - 1_1 A _j (N)20A/2P ILI AFjB_111 n F_ CIRCUIT OF N N 72 4 L2 1_2 — Scott Gurney EGC -EGC- fGic"El C §09 MODULES r---------------------------------------- a #PV-01 1719-015866 120/240 VAC (3 CONTRACTOR: 60HZ 1 PHASE BRS FIELD OPS TO UTILITY i 385-498-6700 GRID (E)GROUNDING 0 ELECTRODE(S) C\I C\j 0 Lii LL N Z 0 0) cc co 0 LU W C/) J 0 U) C: cl, in f Cl) LO CZ LO Cfl 0 a- DRAWING BY: Enphase Energy PLOT DATE: 6 October 18, 2021 0 INTERCONNECTION NOTES PROJECT NUMBER: 705.12(B)(3)THE FOLLOWING METHOD(S) SHALL BE USED TO DETERMINE THE RATINGS OF BUSBARS: (2)WHERE TWO SOURCES, 410289 ONE A PRIMARY POWER SOURCE AND THE OTHER ANOTHER POWER SHEET NAME: SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE lr ELECTRICAL POWER-SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF J THE OVERCURRENT DEVICE PROTECTING THE BUS BAR SHALL NOT REVISION: PAGE NUMBER: EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR. UTILITY COMPANY: Portland General Electric (PGE) PERMIT ISSUER: City of Tigard 0 PV5 MODULE SPECIFICATIONS REC Solar REC400AA Pure DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX-SHORT CIRCUIT CURRRENT(ISC)= 12.1 A AC MODULE VOC 4R.8 V DC STATE Oregon JUNCTION BOX(1) MAX-CURRENT(ISC X125) 154 AAC MODULE VMP 42.1 V DC CITY Portland CONDUCTOR(TC-ER,COPPER(9(rC))m 12 AWG BLUE RAVEN MODULE IMP 9.51 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A MODULE ISC 10.3 A DC ASHRAE EXTREME LOW TEMP(*C) .6 AMB,TEMP.AMP.CORRECTION= 32 0.96 VOC CORRECTION -0,24 %1*C ASHRAE 2%AVG, HIGH TEMP(-Cl 321 ADJUSTED AMP.- 29.8 > 15,a 1403 N.Research WayOrem,LIT 84097 VMP CORRECTION -0.26 %/T JUNCTION BOX TO MAX.SHORT CIRCUIT CUARRENT(ISC}m 12.1 AAC 800.377.4480 SERIES FUSE RATING 25 ADC, SYSTEM ELECTRICAL SPECIFICATIONS CIR I CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT PSC X1.25)= 15A A AC WWW.BLUERAVENSOLAR.COM CONDUCTOR(UF B,COPPER(60-0- 16 10 AWG CONFIDENTIAL-THE INFORMATION DC POWER RATING PER CIRCUIT(STC) 40( CONDUCTOR RATING= 16 30 A HEREIN CONTAINED SHALL NOT BE AD).MODULE VOC @ ASHRAE LOW TEMP S2.4 V DC NUMBER OF MODULES PER MPPT U AD).MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 371 V DC I TOTAL MODULE NUMBER 19 MODULES CONDUIT FILL DERATE m 2 1 USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR MICROINVERTER SPECIFICATIONS Enphase I Q7+Microinverters STC RATING OF ARRAY 7wow Fx AMB,TEMP.AMP.CORRECTION= 32 0,96 SHALL IT BE DISCLOSED IN WHOLE OR POWER POINTTRACKING(MDPT)MINIMAX 22 - 60 V DC AC CURRENT @ MAX POWER POINT 0 MP) 12A 10�9 IN PART TO OTHERS OUTSIDE ADJUSTED AMP.= 28.8 > 15�I RECIPIENTS ORGANIZATION,EXCEPT MAXIMUM INPUT VOLTAGE 60 VDC MAX.CURRENT(IMP X 125) 15.125 13,6125 JUNCTION BOX TO MAX.SHORT CIRCUIT CURFIRENT(ISC)- 12.1 AACIN CONNECTION WITH THE SALE AND I USE OF THE RESPECTIVE EQUIPMENT, MAXIMUM DC SHORT CIRCUIT CURRENT 15 ADC OCPD CURRENT RATING PER CIRCUIT 20 20 - COMBINER BOX(3) MAX.CURRENT(ISC X1,25)- 15 -1 A AC WITHOUT THE WRITTEN PERMISSION MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB,ARRAY AC CURRENT(IMP) 210 CONDUCTOR(UF-B,COPPER(6WC))= 20 10 AWG OF BLUE RAVEN SOLAR LLC. MAXIMUM OUTPUT CURRENT 121 A AC MAX.ARRAY AC POWER 5510W AC CONDUCTOR RATING= 20 30 A AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 4 0,8 XN'ABCEP MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. VRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION- 32 1196 CEC WEIGHTED EFFICIENCY 97 % VRISE SEC. I(MICRO TO JBOX) 36 12 Cu. 1.45 241A5 0.61% ADJUSTED AMP.- 23,04 > V- CERTIFIED VRM SEC.2 OBOX TO COMBINER BOX) 65 10 Cu. 2.00 242.00 0.83% COMBINER BOX TO INVERTER RATED AMPS= 23.0 AAC PV INSTALLATION AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 10 10 Cu. 0.58 240.58 014% MAIN PV OCPD(15) MAX,CURRENT(RATED AMPS X1.25)= 28.74 AAC PROFESSIONAL NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 4.04 24404 CONDUCTOR(THWN-2,COPPER(75-C TERM:))- 30 10 AWG Scott Gurney NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 30 3S A #PV-01 1719-015866 MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690-54) CONDUIT FILL DERATE z 3 1 CONTRACTOR: MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 23.0 A AC AM8,TEMP.AMP.CORRECTION= 32 0,96 BRS FIELD OPS MAXIMUM OCPD RATING FOR AC MODULE 20 A AC INOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP. 33.6 > 28.7 385-498-6700 GROUNDING NOTES WIRING &CONDUIT NOTES :E 1 A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690,47]AND[NEC 250.50-60]SHALL BE 1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 PROVIDED. PER [NEC 690.47], THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE 2,THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED cc THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF 0 0) Lij PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL C: N SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE z 0 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. 0) C/) COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND cc T_ 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS W L7CC) 0 UJI PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED. 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. 0 CCCf) CAI MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE G >- 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE N _"e Lo in MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(13)(3)(A)],&[NEC 310.15(B)(3)(C)]. m Cz LO 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL C 0 GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNrTHWN-2 INSULATED, 90'C RATED, DRAWING BY: 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS, Enphase Energy MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION DAMAGE). 13,VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) October 18, 2021 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR Ll-BLACK, PHASE B OR L2-RED, PROJECT NUMBER: ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWNrTHWN-2 AND MAY BE USED INSIDE 410289 CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] **USE-2 IS AVAILABLE AS UV WHITE REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME: FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15]. ELEC CALCS 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. VISION: PAGE NUMBER: REVISION: 0 PV6 STANDARD LABELS ADDITIONAL LABELS LABEL WARNING /►\ WARNING PER ANEENTPLAQUE ORDIRECTORY DENOTING THE LABEL 1 L LOCATION OF ALL ELECTRIC POWER SOURCE 1403 N.Research Way ELECTRIC SHOCK HAZARD MAIN DISTRIBUTION UTILITY DISCONNECTS) DISCONNECTING MEANS ON OR IN THE PREMISES FOR PV SYSTEM DISCONNECTING MEANS WHERE THE SHALL BE INSTALLED AT EACH SERVICE EQUIPMENT Orem,UT 84097 TERMINALS ON THE LINE AND LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE POWER TO THIS BUILDING IS ALSO SUPPLIED LOCATION AND AL THE LOCATION OPEN POSITION. 690.13 B FROM A ROOF MOUNTED SOLAR ARRAY WITH (S)OF THE SYSTEM [NECI ( )1 800.377.4480 LOAD SIDES MAY BE ENERGIZED A RAPID SHUTDOWN DISCONNECTING MEANS DISCONNECT(S)FOR ALL ELECTRIC POWER WWW.BLUERAVENSOLAR.COM IN THE OPEN POSITION GROUPED AND LABELED WITHIN LINE OF SITE PRODUCTION SOURCES CAPABLE OF BEING AND 10 FT OF THIS LOCATION INTERCONNECTED.[2017 NEC 705.10] CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE _ USED FOR THE BENEFIT OF ANYONE PHOTOVOLTAIC WARNING LABEL 9 EXCEPT BLUE RAVEN SOLAR NOR I PERMANENT PLAQUE OR DIRECTORY DENOTING THE SHALL IT BE DISCLOSED IN WHOLE OR LABEL 2 LOCATION OF ALL ELECTRIC POWER SOURCE IN PART TO OTHERS OUTSIDE A A SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT POWER TO THIS BUILDING IS ALSO DISCONNECTING MEANS ON OR IN THE PREMISES RECIPIENTS ORGANIZATION,EXCEPT THE DISCONNECTING MEANS AS A POWER SOURCE SHALL BE INSTALLED AT EACH SERVICE EQUIPMENT IN CONNECTION WITH THE SALE AND RATED AC OUTPUT CURRENT 22,99 AAND WITH THE RATED AC OUTPUT CURRENT AND THE SUPPLIED FROM MAIN DISTRIBUTION LOCATION AND AT THE LOCATIONUSE OF THE RESPECTIVE EQUIPMENT,S)OF THE SYSTEM WITHOUT THE WRITTEN PERMISSION NOMINAL OPERATING AC VOLTAGE.[NEC 690.54] UTILITY DISCONNECT LOCATED DISCONNECT(S)FOR ALL ELECTRIC POWER OF BLUE RAVEN SOLAR LLC. NOMINAL OPERATING AC VOLTAGE 240 V PRODUCTION SOURCES CAPABLE OF BEING INTERCONNECTED.[2017NEC705.10] __-- -------__-- NABCEP M• r KING LABELED I WARNING PERMANENT PLAQUE OR DIRECTORY TO BE CERTIFIED LABEL 3 LOCATED AT MAIN SERVICE EQUIPMENT DENOTING _ DUAL POWER SUPPLY IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL POWER TO THIS BUILDING IS ALSO SUPPLIED THE LOCATION OF THE RAPID SHUTDOWN SYSTEM PV INSTALLATION ANYWHERE THAT IS POWERED BY BOTH THE UTILITY DISCONNECTING MEANS IF SOLAR ARRAY RAPID AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL FROM A ROOF MOUNTED SOLAR ARRAY.SOLAR SHUTDOWN DISCONNECTING SWITCH IS NOT PROFESSIONAL SOURCES: UTILITY GRID AND AND SUBPANELS.(NEC 705.12(B)(3)] ARRAY RAPID SHUTDOWN DISCONNECT IS GROUPED AND WITHIN LINE OF SITE OF MAIN Scott Gurney PV SOLAR ELECTRIC SYSTEM LOCATED OUTSIDE NEXT TO THE UTILITY METER. SERVICE DISCONNECTING MEANS. #PV-011719-015866 (2017 NEC 705.10 AND 690.56(C)(1)] CONTRACTOR: —"-- BRS FIELD OPS WA R N IN G / WARNING 385-498-6700 POWER SOURCE OUTPUT CONNECTION LABEL 4 ' LABEL 11 APPLY TO THE DISTRIBUTION EQUIPMENT ADJACENT PHOTOVOLTAIC SYSTEM PERMANENT PLAQUE OR DIRECTORY TO BE DO NOT RELOCATE TO THE BACK-FED BREAKER FROM THE POWER COMBINER PANEL LOCATED AT AC COMBINER PANEL.[NEC 110.21(B)] THIS OVERCURRENT SOURCE.[NEC 705.12(B)(2)] DEVICE DO NOT ADD LOADS Z WARNING -WARNING: PHOTOVOLTAICLABEL 12 O LAT EXPOSED RACEWAYS,CABLE TRAYS,COVERS AND F POWER SOURCE ENCLOSURES OF JUNCTION BOXES,AND OTHER a WIRING METHODS.(NEC 690.31(G)(3&4)] C (V THIS EQUIPMENT FED BY MULTIPLE LABEL5 cc G CV SOURCES.TOTAL RATING OF ALL APPLY TO THE PV COMBINER BOX SUBPANEL LI.I OVERCURRENT DEVICES,EXCLUDING (NEC 705.12(3)(3)] UTILITY MAIN (IF INTERCONNECTION AC PV PV COMBINER U.0 N MAIN SUPPLY OVERCURRENT METER SERVICE PANEL IS MADE HERE) DISCONNECT METER BOX Z 0 N DEVICE,SHALL NOT EXCEED — AMPACITY OF BUSBAR. O OO O O O OO O O W 00 0 W U 0 p -0 N p O 2 W C: SOLAR PV SYSTEM EQUIPPED LABEL s O O O O O O O N Y n T N f WITH RAPID SHUTDOWN BUILDINGS WITH PV SYSTEMS SHALL HAVE A O 11 CZ LO PERMANENT LABEL LOCATED AT EACH SERVICE 4 IFR 4 9 9 OR PLACARD � TURN RAPID SHUTDOWN EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS O O O V C IS USED SWITCH TO THE 'OFFIOARE CONNECTED OR AT AN APPROVED READILY �,,,aFiec,ac sHur DOWN PV SYSTEM wreeus VISIBLE LOCATION AND SHALL INDICATE THE LOCATION DRAWING BY:O OR 10 SAND REDUCE HOCK HAZARD OF RAPID SHUTDOWN INITIATION DEVICES. 8 IN THE ARRAY [NEC 690.56(C)] OR PLACARD Enphase Energy PLOT DATE: RAPID • LABEL 7 October 18, 2021 SWITCH FOR SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT • r r SWITCH[NEC 690.56(C)(2)] PROJECT NUMBER: SYSTEM 410289 LABELING NOTES SHEET NAME: 1)LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE EXACT LABELS REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. "ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL 2)LABELING REQUIREMENTS BASED ON THE 2017&2020 NEC CODE,OSHA STANDARD 19010.145,ANSIZ535. REPRESENTATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED REVISION PAGE NUMBER: 3)LATEST BASED BE FSUTHEREQDREMENTS OF THE YTOWITAHJ. MAY VARY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON 3 LINE 4)LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL NOT BE HANDWRITTEN[NEC 110.21] DIAGRAM. 3 LINE DIAGRAM ON PV5 TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. 0 I—p V7 Data Sheet Enphase IQ 7 and IQ 7+ Microinverters Noe Enphase Microinverters BLUE RAVEN INPUT DATA(DC) IQ7 60 2 US IQ7PLUS-72 2-US Region:AMERICAS .__. Commonly used module pairings' 235 W-350 W+ 235 W 440 W+ Module compatibility 60-cell/120 half-cell PV modules 60-cell/120 half-cell and 72- Only cell/144 half-cell PV modules 1403 N RESEARCH WAY,BUILDING J Maximum input DC voltage 48 V 60 V OREM,UT 84097 Peak power tracking voltage 27 V-37 V 27V-45V 800-377-4480 Operating range 16 V-48 V 16V-60V WWW.BLUERAVENSOLAR.COM Min/Max start voltage 22 V/48 V 22 V/60 V CONFIDENTIAL-THE INFORMATION The high-powered smart grid-ready Max DC short circuit current(module Isc) 15 A 15 A HEREIN CONTAINED SHALL NOT BE Enphase Overvoltage class DC port II 11 USED FOR THE BENEFIT OF Enphase IQ 7 MicroTMand Enphase IQ 7+ MicroTMI ANYONE EXCEPT BLUE RAVEN p P DC port backfeed current 0 A 0 A SOLAR NOR SHALL IT BE Q7 and IQ 7+ dramatically simplify the installation process while PV array configuration 1 x 1 ungrounded array;No additio ial DC side protection required; DISCLOSED IN WHOLE OR IN PART AC side protection requires max 2 per branch circuit TO OTHERS OUTSIDE RECIPIENTS achieving the highest system efficiency. ORGANIZATION,EXCEPT IN Microinverters OUTPUT DATA(AC) IQ7 Microinverter IQ7+Microinverter CONNECTION WITH THE SALE AND Part of the Enphase IQSystem,the IQ 7 and Peak output power 250 VA 295 VA USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE Maximum continuous output power 240 VA 290 VA WRITTEN PERMISSION OF BLUE IQ7+Microinverters integrate with the Enphase Nominal(L-L)voltage/range2 240V/ 208V/ 240V/ 208V/ RAVEN SOLAR LLC. IQ EnvoyT° Enphase 10 Battery7and the Enphase 211-264 V 183-229 V 211-264 V 183229 V Maximum continuous output current 1.0 A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V) Enlighten'" monitoring and analysis software. Nominal frequency 60 Hz 60 Hz NABCEP IQ Series Microinverters extend the reliability Extended frequency range 47-68 Hz 47-68 Hz CERTIFIED ACshort circuit fault current over 3 cycles 5.8 Arms 5.8 Arms standards set forth by previous generations and Maximum units per 20 A(L-L)branch circuit3 16(240 VAC) 13(208 VAC) 13(240 VAC) 11 (208 VAC) PV INSTALLATION undergo over a million hours of power-on testing, Overvoltage class AC port III Ill PROFESSIONAL AC port backfeed current 18 mA 18 mA Scott Gurney enabling Enphase to provide an industry-leading Power factor setting 1.0 1.0 #PV-01 1719-015866 warranty Of Up to 25 years. Power factor(adjustable) 0.85 leading...0.85 lagging 0.85 leading...0.85 lagging CONTRACTOR: EFFICIENCY @240 V @208 V @240 V @208 V BRS FIELD OPS Peak efficiency 97.6% 97.6 /° ° ° 97.5% 97.3% 385.498.6700 CEC weighted efficiency 97.0% 97.0% 97.0% 97.0% MECHANICAL DATA Ambient temperature range -40°C to+65°C Easy to Install Relative humidity range 4%to 100%(condensing) Connector type MC4(or Amphenol H4 UTX with additional Q-D005 adapter) • Lightweight and simple Dimensions(HXWXD) 212 mm x 175 mm x 30.2 mm(without bracket) • Faster installation with improved,lighter two-wire cabling Weight 1.08 kg(2.38 lbs) • Built-in rapid shutdown compliant(NEC2014&2017) Cooling Natural convection-No fans Approved for wet locations Yes Pollution degree PD3 Productive and Reliable Enclosure Class II double-insulated,corrosion resistant polymeric enclosure • Optimized for high powered 60-cell/120 half-cell and 72- Environmental category/UV exposure rating NEMA Type 6/outdoor cell/144 half-cell`modules FEATURES • More than a million hours of testing Cammunication Power Line Communication(PLC) • Gass II double-insulated enclosure Monitoring Enlighten Manager and MyEnlighten monitoring options. Both options require installation of an Enphase IQ Envoy. • UL listed Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break disconnect required by NEC 690. Smart Grid Read Compliance CA Rule 21 (UL 1741-SA) Ready UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO.107.1-01 • Complies with advanced grid support,voltage and This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014,NEC frequency ride-through requirements 2017,and NEC 2020 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, • Remotely updates to respond to changing for AC and DC conductors,when installed according manufacturers instructions. grid requirements Configurable for varying grid profiles • Meets CA Rule 21 (UL 1741-SA) 1.No enforced DC/AC ratio.See the compatibility calculator at htt s l/enphase.com/en-us/support/module-cQmpatibility. The IQ7+Micro is required to support 72-cell/144 half-cell modules. 2.Nominal voltage range can be extended beyond nominal it required bythe utility. 3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. SHEET NAME To learn more about Enphase offerings,visit enphase.com ENPHASE. To learn more about Enphase offerings,visit enphase.com ENPHASE. SPEC SHEET©2020 Enphase Energy.All rights reserved Enphase,the Enphase logo,Enphase IQ 7,Enphase IQ 7+,Enphase IQ Battery, %w.✓ Enphase Enlighten,Enphase IQ Envoy,and other trademarks or service names are the trademarks of Enphase Energy,Inc.Data subject to change 2020-08-12 PAGE NUMBER REVISION SS 0 Data Sheet Enphase IQ Combi ner 3 Enphase Networking MODEL NUMBER _.___ _ _.___ v_ ._.v_ _W_______ __ _ _. _.___w w... 13LU E RAVEN IQCombiner 3 IQCombiner 3 with Enphase IQEnvoyT"printed circuit board for integrated revenue grade PV X-IQ-AM1-240-3 production metering(ANSI C12.20+/-0.5%)and optional*consumption monitoring(+/-2.5%). ACCESSORI ES and REPLACEMENT PARTS(not included,order separately) Enphase Mobile Connect'" 1403 N RESEARCH WAY,BUILDING J CELLMODEM-03(4G/12-year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 OREM,UT 84097 CELLMODEM-01 (3G/5-year data plan) microinverters.(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin Islands, CELLMODEM-M1(4G based LTE-M/5-year data plan) where there is adequate cellular service in the installation area.) 800-377-4480 Consumption Monitoring*CT Split core current transformers enable whole home consumption metering(+/-2.5%). WWW.BLUERAVENSOLAR.COM Enphase The Enphase IQ Combiner 3TKNith Enphase CT-200-SPLIT CONFIDENTIAL-THE INFORMATION *consumption monitoring is required for Enphase Storage Systems HEREIN CONTAINED SHALL NOT BE IQ EnvoyTmconsolidates interconnection Wireless USB adapter Installed at the IQ Envoy.For communications with Enphase Encharge'"storage and Enphase USED FOR THE BENEFIT OF 1 Q Combiner 3 COMMS-KIT-01 Enpower'"smart switch.Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner"' ANYONE EXCEPT BLUE RAVEN and allows redundant wireless communication with Enchar a and En Older. SOLAR NOR SHALL IT BE equipment into a single enclosure and g p DISCLOSED IN WHOLE OR IN PART Circuit Breakers Supports Eaton BR210,BR215,BR220,BR230,BR240,BR250,and BR260 circuit breakers. TO OTHERS OUTSIDE RECIPIENTS (X 14AM 1-240-3) streamlines PV and storage installations by BRK-10A-2-240 Circuit breaker,2 pole,10A,Eaton BR210 ORGANIZATION,EXCEPT IN BRK-15A-2-240 Circuit breaker,2 pole,15A,Eaton BR215 CONNECTION WITH THE SALE AND BRK-20A-2P-240 Circuit breaker,2 pole,20A,Eaton BR220 USE OF THE RESPECTIVE providing a consistent, pre-wired solution for EQUIPMENT,WITHOUT THE EPLC-01 Power line carrier(communication bridge pair),quantity-one pair WRITTEN PERMISSION OF BLUE residential applications. It offers u to four RAVEN SOLAR LLC. pp p XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 3(required for EPLC-01) 2-pole input circuits and Eaton BRseries XA-ENV-PCBA-3 Replacement IQ Envoy printed circuit board(PCB)for Combiner 3 ELECTRICAL SPECIFICATIONS NABCEP busbar assembly. Rating Continuous duty CERTIFIED System voltage 120/240 VAC,60 Hz PV INSTALLATION PROFESSIONAL Eaton BR series busbar rating 125 A Scott Gurney Max.continuous current rating(output to grid) 65A #PV-011719-015866 Max.fuse/circuit rating(output) 90 A CONTRACTOR: Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) BRS FIELD OPS 385.498.6700 Smart Max.continuous current rating(input from PV) 64 A • Includes IQ Envoy for communication Max.total branch circuit breaker rating(input) 80A of distributed generation/90A with IQ Envoy breaker included and control Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy • Flexible networking supports Wi-Ft, MECHANICAL DATA +� Ethernet,or cellular r� F Dimensions(WxHxD) 49.5 x 37.5 x 16.8 cm(19.5'x 14.75' x 6.63").Height Is 21.06"(53.5 cm with mounting brackets). Optional AC receptacle available for PLC Weight 7.5 kg(16.5 lbs) 'i bridge Ambient temperature range -400 C to+460 C(-400 to 1150 F) • Provides production metering and optional f Cooling Natural convection,plus heat shield consumption monitoring ` Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction Wire sizes • 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors Simple • 60 A breaker branch input: 4 to 1/0 AWG copper conductors • Main lug combined output: 10 to 2/0 AWG copper conductors • Reduced size from previous combiner Neutral and ground: 14 to 1/0 copper conductors Always follow local code requirements for conductor sizing. it11 II� • Centered mounting brackets support single t Altitude To 2000 meters(6,560 feet) stud mounting � INTERNET CONNECTION OPTIONS • Supports back and side conduit entry � Up to four 2-pole branch circuits for 240 VAC Integrated Wi-Fi 802.11b/g/n plug-in breakers(not included) Ethernet Optional,802 3,Cat5E(or Cat 6)UTP Ethernet cable (not included) • 80 A total PV or storage branch circuits Cellular Optional,CELLMODEM-01 (3G)or CELLMODEM-03(4G)or CELLMODEM-M1(4G based LTE-M) (not included) COMPLIANCE Reliable Compliance,Combiner UL 1741, CAN/CSA C22.2 No.107.1,47 CFR,Part 15,Class B,ICES 003 Production metering:ANSI C12.20 accuracy class 0.5(PV production) • Durable NRTL-certified NEMA type Compliance,IQEnvoy UL 60601-1/CANCSA 22.2 No.61010-1 3R enclosure U� • Five-year limited warranty • UL listed To learn more about Enphase offerings,visit enphase.com SHEET"AME LISTED 02018 Enphase Energy.At rights reserved.Enphase,the Enphase logo,IQCombiner 3,and other trademarks or service names are the SPEC SHEET ' 2r9tg of Enphase Energy,Inc.E N P HE N P H A S E.PAGE NUMBER REVISION To learn more about Enphase offerings,visit enphase.com 0 SS 0 BLIP RAVEN Rrrr" PRODUCT SPEEIFICATION5 SOLARS MOST TRUSTED 1403 N RESEARCH WAY,BUILDING J OREM,UT 84097 mi 800-377-4480 f---- 821±2s n1.7±0.11 CERTIFICATIONS WWW,BLUERAVENSOLAR.COM 28P.11 -� 901[35.5] 460[18.1] IEC61215:2016,IEC 61730:2016,UL 61730 CONFIDENTIAL-THE INFORMATION -- --- IEC 62804 PID HEREIN CONTAINED SHALL NOT BE 153.7[6.05] USED FOR THE BENEFIT OF EC 61701 Salt Mist 1100[43.31+ ANYONE EXCEPT BLUE RAVEN *� IEC 62716 Ammonia Resistance� SOLAR NOR SHALL IT BE Q+ j UL EC 6127802 DrnhpeC[ass2 DISCLOSED IN WHOLE OR IN PART Type �oto.z TO OTHERS OUTSIDE RECIPIENTS [0.24±0.011 _ Dynamic Mechanical Load 77 IEC 6121522016 Hailstone(35mm) ORGANIZAWITHT THE CEPT N 1 _ Y CONNECTION WITH THE SALE AND ' � c M IEC 62321 Lead-free acctoRoHSEU863/2015 USE OF THE RESPECTIVE 15014001:2004,15090012015,OHSA518001:20071EC62941 EQUIPMENT,WITHOUT THE 0- ♦ WRITTEN PERMISSION OF BLUE 10.4OVE (` -` RAVEN SOLAR LLC. [0.43±3±0.01] o - - YRetdr � 2o.s±o.s � 1200[47.21 - WARRANTY [0.8±0.02] • Standard RECProTru5t NABCEP t 53.7[6.051 Installed by an REC Certified r -- SolarPofessional Ne Yes Yes CERTIFIED y • 22.5[0.91 671±3[26.4+0.12] System Size All c25 kW 25 500 kW 45[1.81 PV INSTALLATION X30[1.21 Product Warranty(yrs) zo 25 zs PROFESSIONAL ' 'r Measurements in mm lin] 't Power Warranty(yrs) 25 25 25 r bn Scott Gurney GENERALDATA Labor Warranty(yrs) 0 ZS 1D #PV-01 1719-015866 Power n Year 1 98% ECheterojunction cells Celltype: 13wthlead-fee,gapless technology Connectors: StaubliMC4PVinBacccorCdanccewiitthEC62852 Annual Degradation 0.25% 02% 98% % 0.25% CONTRACTOR: 6 strings of 22 cells in series IP68only when connected PowerinYear25 92% 92% 92% BRS FIELD OPS • A.� • • • .._.._ -... _ _ _..... 0.13 in(3.2 mm)so lar glass with 12 AWG(4mm2)PVwire.43+471[1(1.1+L2m) See warranty documents for details.Conditions apply 385.498.6700 Glass Cable: anti reflection surface treatment accordance with EN 50618 MAXIMUM RATINGS Backsheet: Highly resistantpolymer(black) Dimensions: 71.7x40x1Zin(1821x1016x30mm) ,•_,. = Operational temperature: •40...+185°FHO-..+85°C) Frame: Anodized aluminum(black) Weight: 45 lbs(20.S kg) Maximum system voltage: 1000V Junction box: Origin Made in Singapore 3-part, Maximum testload(front): +7000Pa(146lbs/sq ft)' m ® - accordancewithlEC6279Q Maximum test load(rear): 4000Pa(835lbs/sq ft)' m REC ALPHCX Max renes fuse rating 25 A ELECTRICAL DATA Product Code:RECxxxAA Pure Maxreversecurrent 25A Power Output P,gx(WpJ 385 390 395 400 405 " 1. __. _.._.._.___.. ..._. _.. 'See installation manual for mounting instructions Watt Class Sorting-(W) 0/+5 0/+5 0/+5 0/+5 0/+5 Designload=Testload/1.5(safetyfactor) PUR a Nomina',PowerVoltage-V_(V) 41.2 41.5 41.8 421 42A TEMPERATURE RATINGS' F Nominal Power Current _P(A) 9.35 940 9.45 951 9.56 Nominal ModuleOperatingTemperature 44°C(±2°C) a _._..._.. _.__.. -. _._1 rn ry° Ln Open Circuit Voltage Vor(V) 48.5 48.6 487 488 48.9 Temperature coefficient ofP�,,,: 026%/°C PR®DUCT _JPEDREATI - _ _ ._ � Short Circuit Current-Isc(A) 10.10 1015 1020 1025 1030 TemperaturecoeffiaentofVoc: -0.24%/°C >- � Power Density(W/sq ft) 19.3 19.6 19.8 20.1 20.3 Temperature coefficient oflsc: 0.04%/°C Panel Efficiency(%) 20.8 21.1 21.3 21.6 21.9 'The temperature coefficients stated are linear values • -- - - ---- LOW LIGHT BEHAVIOUR o Power Output-PMAX(Wp) 293 297 301 305 309 m -- Typica(Iowirradiance performance ofmodule atSTC: > F Nominal Power Voltage-V_(V) 38.8 39.1 39.4 39.7 40.0 g Nominal Power Current-IMPP(A) 7.55 7.59 763 768 7.72 r Open Circuit Voltage-Voc(V) 45.7 45.8 459 46.0 46.1 6 - ShortCircuitCurrent-Isc(A) 8.16 8.20 8.24 8.28 8.32 W a 'T-w`zr Values at standard test conditions(STC:air mass AM15,irradiance10.75W/sgft0000 W/rr>Tl temperaturese onaproduction 'ty spread with a tolerance of P V�&1.±3%within one watt class.Nominal module operating temperature(NMOT:air mass AM 1.5,irradiance - n m m - °. 800W/m',temperature WF(20°C),windspeed 33 ft/s(1m/s)`Where root indicates the nominal power class(P.)at STC above, lrrad[ e(W/m2) / , _ Founded in 1996.REC Group is an international pioneering solar energy REC Fjam company dedicated to empowering consumers with clean,affordable solar power.As Solar's Most Trusted.REC is committed to high quality, www.ret rou com 20.3 �/FT innovation,and a low carbon footprint in the solar materials and solar g P "' _ •' , panels it manufactures. Headquartered in Norway with operational 1. '�. •�•>n'"` headquarters in Singapore,REC also has regional hubs in NorthAmerica, • �. • �� • Europe,and Asia-Pacific. or SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0 BLUE RAVEN Product data she;,--" DU221 RB Characteristics 01del,!jq_and SIMPRInq 1,�,L 1403 N.Research Way Safety switch, general duty, non fusible, 30A, _q�L I Orem,UT 84097 C; WICO-D&DU SWNIIEMA311R.WMA 2 poles, 3 hp, 240 VAC, NEMA 3R, bolt-on DiSCOmt Schedule DEIA 800.377.4480 provision GTIN 007$MI490M WWW.BLUERAVENSOLAR.COM -Nb I r-.I cr I f I unA�,npkg CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE Product avaitablidy Stock-Normailly stocked in distributton facility Pig weghiltil-bis) 4.65 th(US)(2.11 kgs USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR Relluirnabililly yes SHALL IT BE DISCLOSED IN WHOLE OR CounOyofongm MX IN PART TO OTHERS OUTSIDE 70 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, Packing Units WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. Pnco*: 177,00 USD Ur4 Type of Packap I PCE Paida"I Height 5-40 in(13-7116 on) p*dia"I wK" 780 In(19,812 cm) NABCEP %90 in M.146 cim) CAR CERTIFIED Number of Units r Package 2 5 PV INSTALLATION Padtage 2 WOONIt 24.60 fb(LIS)(11.156 kg) PROFESSIONAL Package 2 Height lii_k_;(_274320n) Scott Gurney #PV-01 1719-015866 Package width 10M In(28,6?an) J1, Package 2 Length 23 80 n 160 452 cm) CONTRACTOR: LIrat_TVp&_*fPsd"&3 PAL BRS FIELD OPS Number at Units in Pad"*3 M 385-498-6700 Package W*Kft 814.00 th(US)(369-224 kg) Package 3 V*Xm 40.00 in(101,15 cm) Package 3 Lerhgth 46.00 in(121.92 cm) Product Single Throw Safety Switch ctimart RaWq 30A 7 Offer Sustainability CeAft3bom UL Ilialled file E2875 S�inabl�aw sutus Green Premium product Encllost"Rating NEMA 3R is cwomie proposibort 65 WARNING.-This product can expose you to chemicals, W mcluding:LOand I'3d 00topourds wtw-h is known to the State ofCalftm to cause cancer and bKth defects or ottiu-teproductive.herrn For Disoonnect Type Non-fusible disconnect swirtch aw*oforriwion go to www.P65WarrA)p,ca.gov None REACh Regulation jM_b�tN Tsurface ype REACh free of SVHC Yes Number of Poles 2 "nit _00r-4,_*_ comp Eieatrical Connection Lugo, GKO"duty Tabic heavy metal Volta"R*" 240 V AC Mercury fir" Yes Wine Sine AWCT 14_-AWG4-6 copper AWG 12...AWG 6 ahiftrikon Ro14S exemption information Chona RoHSRegulaborr Pro-active Chir%a RoKS decliaration(out of Chirm RoHS legal suipe) Complementary Environmew"Diesdowre, 77' Shod-clecuit wiflutarid 200 kA PVC free mw*vium Not"Power R" 3 hp 240 V AC 60 Hz I phase NEC 430,52 Tightening torque 30 Ibf in(139 N ml 0 00 0,02 in"r2.08 13.3 mml)l AING 14.AWG 6) Contractual Warranty Height 9.63 in(244-60 nun) Warm 1ti months VVkKh 7.79 in(1196,86 mm) Depth 3.75 In(n25 ffvn) 1--r.W3 to A tao.lb*xed-dw**dh K"wDcw dwhbutrr Of rokwkw ke**.0 Pro" SHEET NAME: nt 2 SPEC SHEETS REVISION: PAGE NUMBER 0 SS BLUE RAVEN SaIaDeck FLASHED PV ROOF-MOUNT COMBINER/ENCLOSURE f. 1403 N RESEARCH WAY,BUILDING J OREM,UT 84097 Basic Features 800-377-4480 • Stamped Seamless Construction WWW.BLUERAVENSOLAR COM • 18 Gauge Galvanized Steel CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE Powder Coated Surfaces USED FOR THE BENEFIT OF Flashes into the roof deck E ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE 3 Roof deck knockouts .5", .75", 1 DISCLOSED IN WHOLE OR IN PART # 6 Centeringent dimples or lexit � �q�i.r����`�I TO OTHERS OUTSIDE RECIPIENTS p ry ORGANIZATION,EXCEPT IN fittings O( conduit CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE 2 Position Ground lug installed EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF BLUE Mounting Hardware Included RAVEN SOLAR LLC. SclaL;eck.htodcz SD 078�3 F� �if'1 r 1 SolaDeck UL50 Type 3R Enclosures CERTIFIED PV INSTALLATION Available Models ONAL Model SO 0783-13" fixed Din Rail) PROS ESS cott ney Model SO 0786-(6„slotted Din Rall) #PV-011719-015866 CONTRACTOR: BRS FIELD OPS 385.498.6700 SolaDeck UL 1741 Combiner/Enclosures Models SD 0783-41 and So 0786 41 are labeled and ETL listed UL,STD 1741 according to the UL STD 1741 for photovoltaic combiner enclosures. Max Rated-60OVDC, 120AMPS Model SD 0783µ41 3"Fixed [din Rail fastened using Nurlock System —Typical System Configuration 4- Din Rail Mounted Fuse Holders 60OVDC 30 AMP 1-Power Distribution Block 600VOC 175AMP 1-Bus Bar with UL lug Model SD 0786-41 6-Slatted Din Rail fastened using steel studs —Typical System Configuration 4-Din Rail Mounted Fuse Holders 600VOC 30 AMP 4-Din Rail Mounted Terminal Blocks Bus Bans with UL lug "Fuse holders and terminal blocks added in the field roust be UL fisted or tecg ntzed and met 600 vVC 30 AMP 11 OC fad fuse .600VV 5dO AMP `AUC for fall mounted terminal Clocks and 600 V 175 AMP 9DC for Power Distribution Blocks Use Copper Store conductors Cover is trlmzned to Allow MI SO 078341,wired with Model so 0786.41,wired with Ourlduit or Pittings..base:s Din Rad maootmildd fuse hokders, Dan Rail mounted fuse holders,. center airI for fMt ng bus bar and power dmtriI terminal t7lodcs and bus bars_ locations black SHEET NAME RSTC Enterprises, Inc • 2219 Heirristead Roan •Eau Chare. W1 54703 SPEC SHEET For product information call 1(866) 367-7782 PAGE NUMBER REVISION SS 0 Nor- BLUE RAVEN SYSTEM BONDING & GROUNDING ' ff� I SFM thAML ' 1403Orem,UT 84097Vay 800.377.4480 I MICRORAIL8 INSTALLATION GUIDE I PAGE WWW.BLUERAVENSOLAR.COM —'____________________________ --e_---_____----__---_—_—_------- _———_———————————— "----------' """""""" CONFIDENTIAL THE INFORMATION _ _.: _ _ _._ __ snit» HEREIN CONTAINED SHALL NOT BE i, USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR 4 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE --„ RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND s USE OF THE RESPECTIVE EQUIPMENT, z WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. NABCEP I CERTIFIED - i PV INSTALLATION PROFESSIONAL Scott Gumey — E-W BONDING PATH: #Pv-011719-015866 I E-W module to module bonding is accomplished CONTRACTOR: I'; with 2 pre-installed banding pins which engage BRS FIELD OPS 385-498-6700 on the secure side of the MicrorailTM and splice. 14 N-S BONDING PATH: N-S module to module bonding is accomplished with bonding clamp with 2 integral bonding pins. r0er oo t l ernate €�etho p'ie,^'€�,'. ..` r;..-"+;y f...S1�ti.' €_- �#�c,rrstait{3-a=d iva{. tQl`4"C--�t�i the i SUN BLUE RAVEN UL NaL I FUME 3 N.Research Way CODE COMPLIANCE NOTES ' 14 Orem,UT 84097 1SFMICROUIL" ALLATION GUIDE 'I PAGE WWW.BLU800.377.4480 ERAVENSOLAR.COM _________________________________r_-_- ------_r____-_-_-_-_ SYSTEM �ry/� �ry -__-___--_-_-_-_--_'___-__-____-________-_________----___s__-__--___---'____ CONFIDENTIAL-THE INF RMATI N LEVEL FIRE C�SII`I TION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE Cq ,{ t EXCEPT BLUE RAVEN SOLAR NOR The system fire class rating requires installation in the manner specified in the performance is inherent in the SFM design and no additional mitigation measures SHALL IT BE DISCLOSED IN WHOLE OR x IN PART TO OTHERS OUTSIDE SUNFRAME MICRORAIL SFM Installation Guide.SFM has been Classified to are re uired.The fire classification ratingis valid for an roof itch.There is no IN CI CONNECTION ION WITH THE ORGANIZATION, D (SFM) � 7 �'" IN CONNECTION WITH THE SALE AND the system level fire portion of UL 1703. This UL 1703 classification has been required minimum or maximum height limitation above the roof deck to maintain WITHOUT THEWRITT N EQUIPMENT, WITHOUT THE WRITTEN PERMISSION incorporated into the UL 2703 product Certification. SFM has achieved Class A, the Class A,B & C fire rating for SFM.SUNFRAME MICRORAIL"1 components shall OF BLUE RAVEN SOLAR LLC. B & C system level performance for low slope & steep sloped roofs when used be mounted over a fire resistant roof covering rated for the application. in conjunction with type 1 and type 2 modules.Class A, B & C system level fire NABCEP CERTIFIED Module Type Roof Slope _ System level Fire Rating Microrail Direction Module Orientation Mitigation Required PV INSTALLATION Type 1 and Type 2 L Stee Slope ow Slope Class A, B & C East- est Landscape OR Portrait None Required PROFESSIONAL Yp yp p & LSl p p WLp Scott Gumey #PV-011719-015866 CONTRACTOR: UL2703 TEST MODULES '`" BRS FIELD OPS See page *S"far a list of modules that were electrically and mechanically tested 385-498-6700 or qualified with the SUNFRAME MICRORAIL(SFM) components outlined within _ this Installation Guide. • Maximum Area of Module = 22.3 sgft • UL2703 Design Load Ratings: a) Downward Pressure - 113 PSF 5400 Pa b} Upward Pressure - 50 PSF / 2400 Pa 0 C) [down-Slope Load - 30 PSF / 1400 Pa • Tested Loads: a) Downward Pressure - 170 PSF / 8000 Pa b) Upward Pressure - 7S PSF / 3500 Pa C) p Mown-Sia e Load - 4S PSF / 2100 Pa ry` ' 0000, • Maximum Span = 6ft • Use with a maximum over current protection device OCPD of 30A • System conforms to UL Std 2703,certified to LTR AE-001-2012 • Rated for a design load of 2400 Pa / 5400 Pa with 24 inch span LABEL MARKINGS • • System fire class rating: See installation instructions for installation w� requirements to achieve a specified system fire class rating with Unirac . � • Unirac SUNFRAME MICRORAIL111 is listed to UL 2703. i } • ALL splices within a system are shipped with marking indicating date " Mmuip _�a... ..,, _ SHEET NAME and location of manufacture. ' SPEC SHEETS REVISION: PAGE NUMBER: 0 SS SUN BLUE RAVEN TESTEDCERTIFIEDFUMEMODULELIST ' M 1403 N.Research Way f Orem,UT 84097 MICRORAIL '° � GUIDE PACE WWW.BLU800.377.4480 ERAVENSOLAR.COM ____ ____�__�_______��r�����_______�__ __________ ' "'""'"""'"""""""INSTA " - 'I- CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR Marfrftrre Module Mlodd/swift Ut! ' Module Madel/Series j Man> re Module Mom/Series SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT HIB/HIH/HPB/HPH-xxxM IN CONNECTION WITH THE SALE AND AtL'GP-Series y iarlsol TD-AN3,'I O- N'I: I LR4-60 C USE OF THE RESPECTIVE EQUIPMENT, I CElSM6612P,CHSM6612P/FiV,CHSM6612M, US-ANL UD-ANI LR4-T2(HIH/HPH)-xxxM WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. ( 60�?2�1 8 72P Series LR6.60(8P/HBD/HE8D)•xxxM(30MM) Astronergy CHSM6612M/Hw:CHSM6610M(BL)(BF)/(HF), NetleAe 36M,60M, CHSM72M HC HT60 I56(M)(NOV)(-f), LR6-60(8K)(Pf)(HP89H1PH)-xxxM(35mm) �BCCE Ffi sot8# tEtGLRf-60(8K)(PE)(PB{PF)xxXM(4}nm) AXN6M610TAXN6P610T, HT 72-156(MM 7CERTIFIED 1 Auxin M1 LR6-72(BP){HBD)(Hl8D)-xxxM(30mm) AXN6M612T&AXN6P612T HyurWai KG,MG,TG,RI,RG,Ti,Ml,HI KI Series N `- - -- - LR6-72(HV)(OK)(PE)(PFO(PB)(HPH)-xxxM PV INSTALLATION AXlblacirpremium 60(35mm), ; K IT,rr-HE 1T SE Series PROFESSIONAL (35mm) Scott Gumey AXlpower 60(35mm), Japan Solar JPS-60&JPS-72 Series aPv-o1171s-olsass LR6-72(8K)(HV)(PE)(PB)(PH)-xxxM(40mm) Axitec AXlpower 72(40mm), JAP6 60-xxx.JAM6-60-xxx/SI,JAM6(K)-60/ i Mission Solar EnergyMSE Series CONTRACTOR: AXlpremiurn 60(35mm), BRS FIELD OPS l xxx,JAP6(k)-72-xxx,/4BB,JAP72SYY-xxx/ZZ. Mitsubishi KE & MLE Series AXtpremlum 72(40mm) 385-498-6700 JAP6(k)-60-xxx/4BB.JAP60SYY-xxx/ZZ, ; Neo Solar Power Co. D6M & D6P Series DNA-120 MF26 ; Aptos JA Solar JAM6(k)-7 2-xxx/ZZ,JAM 7 2 SYY-xxx/Z7- , DNA-144MF26 VBHNxxxSAIS&SA16, I I JAM6(k)-60-xxx/ZZ,JAM60SXY-xxx/ZZ BVM6610, VBHNxxxSA17& SA18, BCwiet I L YY.O1,02,03,09,10 SVM6612 Ii.ZZ.SC,PR,BP,HIT,IB,MWPanasonic VBHNxxxSA17(E/G)&SA18E. P6K&MHK-36 Series f ...n VSHNxxxKA01 & KA03 & KA04, Jinko JKM &JKMS Series VBHNxxxZAOI,VBHNxxxZA02, CS6V-M.CSbP-P,CSbK M.OSSA-M, Kyocera KU Series VSHNxxxZA03,V8HNxxx7_A04 CS6K-MS,C56U-P,CS61LI-M.CS6X-P.CS6K-MS, -_._.__. ( LtxxxN2T A4 Peimar SGxxxM(FB/BF`; CS6K-M,CS6K-P,C56P-P,CS6P-M,C53U-P, Canadian Solar i LGxxx(A1C/E1C/EIK/N1cMlK N2T/N2W/ r CS3U-MS,CS3K-P„C53K-MS,CSIK-MS,CS3K. I Q1c/Q1K/51C/52N -A5 Phono Solar PS-60,PS-72 a Plus,Pro,Peak,G3,G4,G5,G6(*),67,G8(*) CS3U,C53U-MB-AG.CS3K-MB-AG.CS6K, LGxxx(AIC/MIC/MIK/N1C/N1K/QiC/Q1K/ Q,Cetis CS6U,CS3L,MW,CSIH-MS,CSIU-M5 Pro,Peak L-G2,L-G4,L-65,L-G6,L-G7 I QAC/QAK)-A6 _ Centrosolar America C-Series&E-Seties Lis Electronks LGxxx(N2T/N2M-E6 Alpha(72)(Black) CT2xxMxx-01,CT2xxPxx-01, LGxxx(N1c/MK/N2W/Slc/52"-G4 N Peak(Black) PEAK Energy Series certainTeed CTxxxMxx-02,CTxxxM-03, MaaccN2fi-15 tTxxxMxx-04,CTxxxHCI1-04 LGxxx(NiMt/ZT/N2V4)-L5 PEAL(Energy BLK2 Series j Dehul DH-60M LGxxx(N1C/Q1c/Q1K)-N5 REC PEAK Energy 72 Series TwiriPeak Series -- LGxxx(N1C/N1K/N2W/Q1C&K)-V5 I Eco Sotargy Orion 1000&Apollo 1000 TwinPeak 2 Series i ric:4tota Mono PERC _ TwinPeak 2 8LK2 Series GLL GCL-P6& GCL-M6 Series ^ LL~ TwlnPeak 2S(M)72(XV) TwlnPeak 3 Series(38mim) SHEET NAME: Please see the SFM UL2703Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM. SPEC SHEETS SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See page J for further information. REVISION: PAGE NUMBER: 0 SS Nov Report No. 102393982LAX-002 Page 3 of 122 Issued: 11-Apr-2016 Report No 102393982LAX-002 Page 39 of 122 Issued: 11-Apr-2016 BLUE RAVE Ur►irac,Inc Revised: 18-Jan-2021 Unirac, Inc Revised 18-Jan-2021 1403 N.Research Way 200 Product 2t!�d� 11A illustrations Orem,UT 84097 ktodels Unirac SFM IfJustration 1-Other ratings 800.377.4480 Model Similarity NA WWW.BLUERAVENSOLAR.COM Furca Rating: 30A CONFIDENTIAL-THE INFORMATION �ti" t HEREIN CONTAINED SHALL NOT BE 7 USED FOR THE BENEFIT OF ANYONE Module Orientation: Portrait Or Landscape EXCEPT BLUE RAVEN SOLAR NOR Maximum Module Size: 17.98 fill SHALL IT BE DISCLOSED IN WHOLE OR Ateo P-Sedes IN PART TO OTHERS OUTSIDE UL2703 Design Load Rating:33 PSF Downward,33 PSF Upward, 10 PSF Down-Sbpe RECIPIENTS ORGANIZATION,EXCEPT Tested Loads-50 sft2400Pa Downward,50 s(l2400Pa Uplift, 15 sf1720Pa Down Slope CHSM661_2P,CF-t;M66I2P �CH 12K IN CONNECTION WITH THE SALE AND f7 p p IO USE OF THE RESPECTIVE EQUIPMENT, Tama TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical Loading orgy 1CHS 12M ,CHSP++Ifr610M PL)PPV �1 WITHOUT THE WRITTEN PERMISSION !V""" `h OF BLUE RAVEN SOLAR LLC. Increased sire ML test: tH5M72"C Maximum Module Size: 22.3 112 UL2703 Design Load Rating: 113 PSF Downward, 50 PSF U AXhi6Pw1610 AXItiP6PfrSIf3T, �N/{ , ,� 9 i:a Award,317 PSF flown-Slope Awdn LG355S2W-A5 used for Mechanical Loading test, AXN6M613T d.AXN6P612T CERTIFIED Mounting configuration:Four mountings on each long nide of panel with the longest span of I Axiter AXI Power,AXI P irerniurn,AXI Black Pr+errliunt 24" _ __._.._ __ _ PV INSTALLATION UL2703 Design Load Rating:46.9 PSF Downward,40 PSF Upward, 10 PSF Down-Slope WM6610,BVM6612 PROFESSIONAL Datings LG395N2W-A5, LG360S2W-A5 and LG355S2W-AS used for used for Mechanical Loading Scott Gurney i (7 ( �MIiK-3fi Series #PV-011719-015886 test I Mounting configuration:Six mountings for two modules used with the maximum span of € CS6V-M, Pt -#4,CSSA-M, CONTRACTOR: 74.5" CMK-MS, -p C56U-M,C.S6X-P CS+6iK-M5. BRS FIELD OPS IEC 61646 Test Loads-112.78 psf15400Pa Downward, 50psff2400Pa Uplift385-498-6700 CS6Pf-M,CS6X-P,CS6P-Pt -M,C55U-i� Fire Class Resistance Rating; Canadian , -Class A for Steep Slope ApplicaWns when using Type 1 Modules.Can be installed at any CS311-MS,tS3K-PC53144S,CS3K-MS,CS3K, interstitial gap.Installations must Include Trim Rsil. CS3U,C531.1 3-AG,CSSK448-AG,CS6K, -Class A for Steep Slope Applications when using Type 2 Modules. Can be installed at any C56U,CS3L,C53W,CSI CS1U-tAS interstitial gap. Installations must include Trim Rail. -Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules. Centmotair Arnerka C Selries &E-Sones This system was evaluated with a 5"gap between tete bottom of the module and the roof's 4'T2atat t-CII,CT2xxPxte-01, surface CertairtTeed Clio mxX-02,CTMM-03, See section 7 0 itlustractions# 1, fa, laa. and tab for a complete list of PV rr7odoles evaluated CP9al x101=-04,CTr xxW_11-04 with these racking s stems t3 Rafmgs NA Oen DH-I Eco Solar n 1000 b to I _ Fr>etittrbt Mono PEK C,+CL GCL-P6 S GCL446 Series H TD-AN3,TD AN4, UB•AN1,IUD-ANI I Hetierw 36K 600 60R7211i0l&72P Series HT SOW HT60-1 HT 72-15 t4yuKG,MG TG.RI,K T1.MI.1f1&K15ufft JElk iT,THE &iT-SE Series Japan Solar IPS-60 IPyS-72 Series SHEET NAME: ro+aatstas-w-;tat ED1641Si} .20 -,», SPEC SHEETS REVISION: PAGE NUUMBER. 0 SS **%W Report No. 102393982LAX-002 Page 40 of 122 Issued: i 1=Apr-2018 Report No, 102393982LAX-002 Page 41 of 122 Issued: 11-Apr-2016 BLUE RAVE N Unirac,Inc Revised: 18-Jan-2021 Unirac,Inc Revised: 18-Jan-2021 1403 N.Research Way .0 Illustrations . iitustrat# ns Orem,UT 84097 Illustration 1s-runner Ratings Continue Illustration 1 as-Other Ratings Continue 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIMae MIOI Seri" H REIN CONTINFORMATION CONTAINED SHALL rt1� NOT BE Manuiamse b4odtteI k Op 11/Serks USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR FM bmwStrim SHALL IT BE DISCLOSED IN WHOLE OR 1Aft 60-mot,JM6-60- ,JAM6QCrW KM ErawOW des, RE CIN P SNRT TO OTHERS OUT SIDE `72' .>jAl�7 5 XCEPT PEM�4'Y 72��, IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, 111min ksk 3 Series, WITHOUT THE WRITTEN PERMISSION * X n4wrlFpik 2 Kxz S"bes. OF BLUE RAVEN SOLAR LLC. JSOAK t ?-72' )AM-/2 t4wdrtPaek series JAM -60-xx1=JAMdM'►'I-xKK;/1.3rtt11911esoin _nPrtnrs2 serus&156 N A B C E P i.YY:01,02,03,09,10 Rrxen RSM Series .� ...._ 1 CERTIFIED 6_ZZ:SC.PR,ISP HST IB,Mw �S4noW SN72& t-s I r*0 1t M&�Sesta SEG 6&SRP-6 PV INSTALLATION Sh" NU-SA St Se^ea PROFESSIONAL Kyocem KU S � _.... Scott Gurney _ b � �;�„K m aPv-ots-otsass till xxx SIC-AS,LG xxx NIC AS. Solaro Fn.MerXT _ CONTRACTOR LG"xQI U0`,k5. NIgNIK)-A . _ Sine Kart, BRS FIELD OPS L£XIotSiCAS, LGOXAK45,tJGxXcf42T—A4, Stmn>Ioot,le Pita 385-498-6700 L&aKbwiu 1.16mmNZT A5,I.1Gd4ZW-A5 Sam S5 21i0 365 Lfi=x:S2W-AS„Ls=&1C-AS,LG=62`1110'44 _fir -------------------------- LG14 MCRWQ-G4.LGMN.2W-G4, Suntm _ __ ! MV Seats&OPID r S Series --- LlGxxxSiC44,L GxxxEIK-AS,LG XXxN2T-1 S, 51st Edlsoryr4w7e607 F-Saks.R-Ser*s&FLEX FXS Strias LGxxxwj((N2C}-VS.LGx"(QIC(N2W)-V5, Stwl11P1440w _ >��Serres&P�Series TF572.TPS%TP6S4.7'1a6 A LONG: LR6-6t1&LR6-72 Se�rks. latesl� TP672,H�wr M,Smart LR4-60&LP-442 Series -----.--__ _ _ Tam SC„Sc 0,SC B1,SC e12 Mission So<arEnergf MSE Ser; Tttw PAM,i+01%.DD06.1*06,DD06,PE06, Mitsuoi��s KE & MLE series M14.PE14,W14.0E14,DF_15,PEISH _ _ upsctar tK UP-i pint # Neo Solar Power Co. D6M Series aha s j t3RE t?7M 13lIC=048A 07Mbe 07A Vikrwr �td#r�. i�50rtrEr'a � VSHN=xSA17&SM 8, wawew_ 1,Ado Series eriascstiC V9�tFtwt"SA27(F,q &SA28E. wirrarco Yti Sere VBK K.At31 &KA03&KA04 �{r�}ts �C�� ffi.Yt_t4 �rfes V8HNxxxZA01,VBHM00aA02, MF,t=ZQ3,VSH#;rwtxZA44 MOO*SOW PS-60,PS-72 t Cells Ptus,Pro,Peak.,G3,G4,OS, +),G7, +) f Pro, L-G2,L-64,L-GS.L-G6,L-67 SHEET NAME: EDI SII 1SEt5ZiH+^41 SPEC SHEETS REVISION: PAGE NUMBER: 0 SS 1 SUN 1 BLUE RAVEN FLASHING & SLIDERSE an 1 FRAME 1 1403 N RESEARCH WAY,BUILDING J ■ MICRORAIL INSTALLATION GUIDEI' PAGE °°3»7448°' WWW.BLUERAVENSOLAR.COM --------------------------------------------------------------------------------------------------------------------------------------------- SFM _. ....._, CONFIDENTIAL-THE INFORMATION ~ INSTALL SLIDERS AND HEREIN CONTAINED SHALL NOT BE USED ANYONE°R THE EXCEPT B UEE RFITAVEN ROOF ATTACHMENTS: SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART Follow manufacturer instructions UP-SLOPE TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN forflashing installation procedures CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE �. ....:.am:�. EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF BLUE a -ty � RAVEN SOLAR LLC. NABCEP CERTIFIED PV INSTALLATION PILOT HOLES: FLASHINGS: PROFESSIONAL Scott Gumey Drill pilot holes for lag screws or Place flashings Mod NS+ 1• #PV-01 1719-015866 structural screws (as necessary) at CONTRACTOR: marked attachement points BRS FIELD OPS 385.498.6700 f 3 NOSE. If N-s modal edge as within 1"of the • Shirla!,r foutle above,you have the elision to asst.'tr li rr t theSMthrnent Int to span the next courst and cut shingtes as s inglR"uIred ! Mod NS+ 1' `� i INSTALL SLIDERS AND TRIMRAIL ROOF ATTACHMENTS: N"00OIL foot f xH: Less Than 1" Insertflashings per manufacturer instructionsIF NUYEM ' i:'a Lag screw or �truct dral 3 r with a maximum € met-er of 5/1 • Attach sliders to rafters • Verify proper row to row spacing for module size (Mod NS+ 1') • Ensure that Tri mraiLTM roof attachments in each row have sufficient u II u I1 i DOWN�StflPE engagement with slider dovetails for proper attachment. I GTI SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0