Report (2) • 48VLUE,:48VLUF Ultra Low NOx:Product Data • 7 Carrier- Turn to the experts Product Data Innovative Unit Base Desien On the inside a high-tech composite material will not rust and incorporates a sloped drain pan which improves drainage and helps inhibit mold,algae and bacterial growth. On the outside metal base rails provide added stability as well as easier handling and rigging. Convertible Duct Configuration IN Unit is designed for use in either downflow or horizontal applications. Each unit is converted from horizontal to downflow and includes two horizontal duct covers. Downflow operation is provided in the field to allow vertical ductwork connections. The basepan seals on the bottom openings to ensure a positive seal cin the vertical airflow mode. o Efficient operation high-efficiency design offers SEER (Seasonal Energy Efficiency Ratios) of 14.0, 11.5 EER, and AFUE (Annual Fuel Utilization Efficiency)ratings up to 81.0%. 0 O O Energy-saving,direct spark ignition saves gas by operating only when A 170030 the room thermostat calls for heating. Standard units are furnished with Fig.1—Unit 48VL natural gas controls. Single-Packaged Products with Energy-Saving Features and Puron® Ultra Low NOx units meet South Coast Air Quality Management R-41 OA refrigerant. District (SCAQMD) and San Joaquin Air Pollution Control District • 14.0 SEER (SJAPCD) are regulating a reduction of 65%, down to no more than • 11.5 EER 14ng/J of NOx emissions. • 81.0%AFUE(Single phase and three phase models) Durable, Dependable Components • ECM Blower Motor-Standard Turbo-tubular"m heat exchaneers are constructed of stainless steel • Direct Spark Ignition and aluminized steel for corrosion resistance and optimum heat transfer • Low Sound Levels for improved efficiency. The tubular design permits hot gases to make • Dehumidification Feature multiple passes across the path of the supply air. • Dense Wire Condenser Coil Guard-Standard In addition, dimples located on the heat exchanger walls force the hot gases to stay in close contact with the walls,improving heat transfer. Features/Benefits ECM Blower Motor is standard on all models. One-piece heating and cooling units with low sound levels, easy Direct-drive PSC (Permanent Split Capacitor) condenser-fan installation,low maintenance,and dependable performance. motors are designed to help reduce energy consumption and provide for Puron is Carrier's unique refrigerant designed to be environmentally cooing operation down to 40°F (4.4°C) outdoor temperature. balanced. Puron is an HFC refrigerant which does not contain chlorine Motormaster® II low ambient kit is available as a field-installed that can harm the ozone layer. The most important advantage of Puron accessory. refrigerant is that it has not been banned in future air conditioning Thermostat Controls systems as the traditional refrigerant R-22 has been.Puron refrigerant is Time Guard®II anti-short cycle protection circuitry. If a non-corporate in service in millions of systems proving highly reliable and is thermostat without anti-short cycle protection is used the Time Guard Il non-ozone depleting. field-installed anti-short cycle kit is recommended. Easy Installation Refrigerant system is designed to provide dependability. Liquid filter Factory-assembled package is a compact, fully self-contained, driers are used to promote clean,unrestricted operation.Each unit leaves combination gas heating/electric cooling unit that is prewired,pre-piped, the factory with a full refrigerant charge.Refrigerant service connections and pre-charged for minimum installation expense. These units are make checking operating pressures easier. available in a variety of standard and optional heating/ cooling size High pressure switch provides added reliability for the compressor. combinations with voltage options to meet residential and light Low pressure switch (24 and 30 size only) provides added reliability commercial requirements. Units are lightweight and install easily on a for the compressor. rooftop or at ground level.The high tech composite base eliminates rust problems associated with ground level applications. Indoor and outdoor coils are computer-designed for optimum heat transfer and efficiency. The indoor coil is fabricated from copper tube and aluminum fins and is located inside the unit for protection against Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 1 48VLUE,48VLUF Ultra Low NOx:Product Data damage. The outdoor coil is internally mounted on the top tier of the Standard horizontal metal duct covers with insulation come with the unit. unit and cover the horizontal duct openings.These can be left in place if Low sound ratings ensure a quiet indoor and outdoor environment with the units are converted to downflow. sound ratings as low as 69dBA. Integrated Gas Control UGQ board provides safe and efficient Easy to service cabinets provide easy 3-panel accessibility to control of heating and simplifies trouble-shooting through its built-in serviceable components during maintenance and installation. The diagnostic function. basepan with integrated drain pan provides easy ground level` Cabinets are constructed of heavy duty, phosphated, zinc-coated installation with mounting pad. A nesting feature ensures a positive prepainted steel capable of withstanding 500 hours in salt spray.Interior basepan to roof curb seal when the unit is roof mounted.A convenient surfaces of the evaporator/heat exchanger compartment are insulated 3/4-in. (19.05 mm)wide perimeter flange makes frame mounting on a with cleanable semi-rigid insulation board,which keeps the conditioned rooftop easy. air from being affected by the outdoor ambient temperature and provides improved indoor air quality.(Conforms to American Society of Heating, Refrigeration and Air Conditioning Engineers 62.2.) The sloped drain pan minimizes standing water in the drain.An external drain is pr;vdt J. Table of Contents Features/Benefits .. ........... ...... ........ ........... .... 1 Model Number Nomenclature .. .. ..... . ........ ......... .. ...3 AHRI Capacities.. .. .......... ...... ................ ....... 4 Physical Data ........ ....... .. ...... ....... ........... .... 6 Options and Accessories. .. ..... . ....... ....... .. ............ 7 Unit Dimensions.. .. ...... ... . .............. . .... ... .. .. ... 8 Unit Dimensions.... .......... ....... .......... .. ....... .. . 9 Performance Data. .. ..... .. ............... .............. .. 12 Application Data.. ........ .. .. ... .. ...... .... .... ... .. .. .. 25 Electrical Data............ .. ..... ........ ........ ... .... .. 26 Connection Wiring Schematic 208/230-1-60.... ....... .. ..... .. 27 Controls......... .. . .. ..... ....... . ..... .... .... ... .. . . .. 31 Guide Specifications. .. ..... . . ...... ....... .. ..... ..... .. .. 32 Manufacturer reserves the right to change,at anytime,specifications and designs without notice and without obligations. 2 48VLUE,48VLUF Ultra Low NOx:Product Data Model Number Nomenclature 48VL U E 24 040 3 0 _ Type of Unit Options 48VL- Single Packaged GP-Base unit with tin plated indoor Air Conditioner and Gas coil hairpins and stainless steel HX Furnace System TP-Base unit with tin plated indoor Low NOx Indicator coil hairpins(Single Phase Only) -Standard See Price Page for full list of factory N-Low NOx options. U-Ultra Low NOx (Only used if ordering an option.) Major Series Minor Series Electrical Supply 3-208/230-1-60 Nominal Cooling Capacity 5-208/230-3-60 024-2.0 Tons 030-2.5 Tons 036-3.0 Tons Nominal Heat Input Size(Btuh) 042-3.5 Tons 040-45,000 048-4.0 Tons 060-60,000 060-5.0 Tons 090-89,000 GAS-FIRED (� �L us A.SNRAE Use of the AHRI Certified C v us C TM Mark indicates a manufacturer's participation in the LISTED LISTED COMPLIANT program For verification of certification for individual products,go to www.ahridirectory.org. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 3 48VLUE,�48VLUF Ultra Low NOx:Product Data AHRI* Capacities Cooling Capacities and Efficiencies Unit Size Nominal Tons 7StarMcityt =EER$ SEER24 2 14.0 30 2.5 14.0 36 3 14.0 42 3.5 14.0 48 4 1550 4600014.0 60 5 1750 56000 11.5 14.0 *. Air Conditioning,Heating&Refrigeration Institute. t. Rated in accordance with U.S.Government DOE Department of Energy)test procedures and/or AHRI Standards 210/240. $. At"A"conditions-80°F(26.7°C)indoor db/67°F(19.4°C)indoor wb&957(35°C) outdoor db. **. Rated in accordance with AHRI Standard 270. Notes: L Ratings are net values,reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard:80°F(26.7°C)db,67°F wb(19.4°C)indoor entering-air temperature and 95°F db(35°C)outdoor entering-air temperature. 2. Before purchasing this appliance,read important energy cost and efficiency information available from your retailer. LEGEND dB-Sound Levels(decibels) db-Dry Bulb SEER-Seasonal Energy Efficiency Ratio wb-Wet Bulb COP-Coefficient of Performance Gas Heating Capacities and Efficiencies, Single and Three Phase Models Unit Size Heating Input(Btuh) Output Capacity(Btuh) Temperature Rise Range°F(°C) AFUE(%) 24040 45,000 37,000 25-55 30040 (14-31) 81.0 24060 30060 60,000 49,000 25-55 81.0 36060 (14-31) 42060 42090 48090 89,000 73,000 35-65 81.0 60090 (19-36) LEGEND AFUE-Annual Fuel Utilization Efficiency NOTE:Before purchasing this appliance,read important energy cost and efficiency information available from your retailer. A-Weighted Sound Power Level Unit Size Sound Rating(dBA) Typical Octave Band Spectrum(dB without tone adjustment) 125 250 500 1000 2000 4000 8000 24 69 71.5 71.0 64.0 61.3 60.0 57.6 49.0 30 72 76.3 70.5 67.8 64.4 63.8 61.4 54.3 36 72 74.5 71.7 68.9 68.0 62.6 57.9 52.5 42 72 73.0 71.1 68.9 68.4 62.6 57.6 53.2 48 72 75.4 70.7 68.9 67.4 62.6 59.9 56.7 60 72 81.3 72.6 68.2 65.4 62.9 59.0 54.4 NOTE:Tested in compliance with AHRI 270 but not listed with AHRI. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 4 48VLUE,48VLUF Ultra Low NOx:Product Data ECONOMIZER HVAC Unit Compressor Cover • Replacement Panel Shipped with Economizer COIL NOTE:On units with base rails this compressor cover is shipped with the HVAC unit. FILTER Replacement Return Chamber Panel Shippec with Economizer ECONOMIZER 4 OO� �O CAULK BOTTOM CORNER Hood OF ECONOMIZER SIDE VIEW ON EACH SIDE m FI LTER CO Vertical Economizer ECONOMIZER 0 0 O O Filter Door BASE Replacement Panel FLANGE Economizer ON BASEDETAIL Panel Grommet for Economizer /! Wiring FILTER RACK a BEND FLANGE AT 90-SCREW TO DIVIDER WITH 1-IN.(25 mm)BCREW • Horizontal Economizer TOP FILTER RACK • • EVAPORATOR COI L • • MANUAL OUTSIDE AIR DAMPER • REPLACEMENT • PANEL • • � • MANUAL OUTSIDE AIR HOOD ,fir • • '� DAMPER P • BLADE i i i • o � • o • BOTTOM FILTER • RACK o o O • A09375 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 5 48VLUE„48VLUF Ultra Low NOx:Product Data E E v E c E o _ o (o o x d 0) to r- N Co V N N M O (fl W CO � M O O X O O (0 l!) `-'LOLO 0 to V N m 7 tV N N CO (O r X V `� Z V COXM Ix L MO (fl M p r N O to >' N X x N O N CO CO � CO C� w 0) _ \ LO O W O r- ONr- W Ycy O V N (P T w N t0 NC) if7 X k G O CO (0 (+) O p O p � N � M, � a O _ _ ' O N x to N O N CO (n CO O V O t` p O N In O x X x X N O N O (0 O 0 N V N to N M (0 N (0 CO x 'XV v �# N p V M th CO O LO CO •�-- a1 L X X X W N @ p N p o N (0 (O 3 M r- 0 _ O_ 10 O O N p V p p N t0 O O r tfn O N W N p O CO p M .- f� X N t2 � on C`i A V N (0 N CO (fl N M V M x 7 .� N V r M (0 CO n N + + N - O p Cn N CO LO CD O C) [P r N t` � ¢ N M O V O O c' r O O X N i0 —O o (o M M M z O N N 00 °� t•7 x x V ik M CO (0 C\O CO .�- 6 .a r + + DU N M N Q LO O toOCD (00 N N O O O n p O U (o W (0 p (V C:) V m W r O N pr, N at0• M N CO •-- p N CO N N t00 p M O Ox Cyi LO x O LO N N N N X O LO c N CD N MO CO O O O_ V O N N o-' �{ U (0 O (O f� p m O O to to _ on O O O O != N O V fA c- r p N O in N (n � •n M N C) O N O M M N N O O M O O V r ty C4p p r (� (o O N N O N a 2>1 `- c m � w CO 0 _ _o v o00 to z O N N 1 M V N O V' O `- r O O N O c o It M (O N W (O N O X X N (O N C O C6 (`) p O LO o 0 p 04 N \ N Y p C.1 O U i N x tt) ?z LO O � (f) N C CO S CO O LO tpo y N t� f� X ?. O N N M N O? p 0 M O N O i0 ' O x o 0 M �- (n N '- (T U) N p 0 M 0 O ” + t + t CV C=I N 0 CS N (0 r M <n N O O O Ln t x O ` N O LQ C-4 O V U-) W m0 00 0 w W (n G N � 28-6 a�N W N W U � ` CO � o " U m7 -ooa� o to o W 3 COLIJ 0 U o o c N Y Q p w 3 zz 3 0 n o mww F- W E �_ z (J O U) W W o N m U E J _ W ¢ 0 v J W CO U J F-• C a aLD S2 wwoz _z C 0 EJ � � °c_) Uz � jofQ o (D civ ¢ (n ¢ ¢ C) .9 wwg E n— � a0 = a w a> > aU) o n¢ U (n m 0 w LL E c 0 n J o � U w m (n a U R (n n V ¢ Z Z W W W W O w M O U Q 0 5 m m U W m C W w v af C7 w C7 `m a� ii E U tY 5 w Z U O O m 2 m = O r 0 = z 3 mxw_ u ¢ D .0 N N 0 y ¢ O C c E Z N D_ o M m W H 3 H m .m O O 3 0 0 o nOi rmi o f xs m C7 •y'�O 3 W -C 0220w > > w � � o Do •_ o 0 d z V) U) U 0f00 tY O Oo_ w 0 z 0 a 2 of LL ? 0 C/5 LL 2 0 J (n m Q� H Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 6 48VLUE,48VLUF Ultra Low NOx:Product Data Options and Accessories FACTORY FIELD ITEM DESCRIPTION INSTALLED INSTALLED OPTION ACCESSORY Coil Options Base-unit tin plated indoor coil hairpins X Compressor Start Kit Compressor Start Kit assists compressor start-up by providing X additional starting torque on sing phase units only. Corporate Thermostats Thermostats provide control for the system heating and cooling X functions. Crankcase Heater Crankcase Heater provides anti-floodback protection for X low-load cooling applications. Horizontal Economizer with solid state controls and barometric relief dampers includes filter racks and provide outdoor air X Economizer during cooling and reduce compressor operation. Vertical Economizer with solid state controls and barometric relief dampers includes filter racks and provide outdoor air X during cooling and reduce compressor operation. Filter Rack features easy installation,serviceability,and Filter Rack high-filtering performance for vertical or horizontal applications. X Includes 1-in.filter. Flat Roof Curb 14-in.(356 mm)Flat Roof Curb is available for roof mounted X applications. Flue Discharge Deflector Directs flue gas exhaust 90 degrees upward from current X discharge. Heat Exchanger Stainless Steel Heat Exchanger X Low Ambient Kit(Motormaster II Control)allows the use of Low Ambient Kit mechanical cooling down to outdoor temperatures as low as X 0°F(-18°C)when properly installed. Manual Outside Air Damper Manual Outside Air Damper includes hood and filter rack with adjustable damper blade for up to 25%outdoor air. X Square-to-Round Duct Transition Kit Square-to-Round Duct Transition Kit enable 24-48 size units to X be fitted to 14 in.(356 mm)round ductwork. Automatically prevents the compressor from restarting for at Time Guard II least 4 minutes and 45 seconds after shutdown of the X compressor.Not required when a corporate programmable thermostat is applied or with a RTU-MP control. Louver Metal Outdoor Coil Grilles Louver Metal Outdoor Coil Grilles provide hail and vandalism X protection. Low Cabinet Air Leakage Cabinet air leakage of 2.0%or less at.5 in.W.C.when tested in X accordance with ASHRAE standard 193. Low Pressure Switch Kit This kit is designed for use when a low pressure control is X desired. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 7 48VLUE,-48VLUF Ultra Low NOx:Product Data Unit Dimensions 24-36 �gz y n... o _ O S 0 o e - 2 z M �y 7 � - r- - a- w --- -- -- �1_j 72 1:f MW — s 3 o - w 2 C3 O A200161 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 8 48VLUE,48VLUF Ultra Low NOx:Product Data Unit Dimensions 42-60 F2 mw nii LLJ 3 Ws - R o a M oa ¢dso< 3 w 0 LLI > TI - ®® g W 0 3 F > _ W O U- 3 w _ S; 0 0 A200157 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 9 48VLUE,'48VLUF Ultra Low NOx:Product Data B Dashed hms show c—support 4 �j �y/ lowttipn for(rga kra6epan un,Is. HVAC unit HVAC unit base rails basepan G C Anchor screw \Sealing Gasket Screw Bracket to �\ Unit Base Rail Roofcurb Hold Down Bracket � Provided with Curb 1 Wood nailer* \� Flashing field supplied Roofcurb* Insulation Roofing material (field supplied) field supplied Cant strip p E \ field supplied v *Provided with roofcurb SMALL/COMMON CURB I I I SMALL- Skl 'PLY BASE /�tiB IlR I UNIT G I I I \� I I LARGE j F�1 H I R UF2N I BASE I UNIT E \ I I I I I I --------------- -----j UNIT PLACEMENT ON COMMON CURB LARGE CURB SMALL OR LARGE BASE UNIT Accessory Dimensions A180216 A B(small/common B(large base) C D E F G H Unit Size Catalog Number IN. base) * IN' IN. IN. IN. (mm) IN.(mm)* IN.(mm) (mm) IN. (mm) (mm) IN.(mm) IN.(mm) Small 9 e r CPRFCURB011 BOO 14(356) 10(254) 822 30.6(778) 47.8 14(356) 16(406) (1214) ( ) 2.7(69) 46.1 (1170) Large CPRFCURB013B00 14(356) 14(356) 43'9 42.2(1072) (1116) *Part Number CPRCURB011 B00 can be used on both small and large basepan units.The cross supports must be located based on whether the unit is a small basepan or a large basepan. NOTES: L Roof curb must be set up for unit being installed. 2. Seal strip must be applied,as required,to unit being installed. 3. Roofcurb is made of 16-gauge steel. 4. Attach ductwork to curb(flanges of duct rest on curb). 5. Insulated panels:1-in.(25.4 mm)thick fiberglass I Ib.density. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 10 48VLUE,*48VLUF Ultra Low NOx:Product Data Selection Procedure (With Example) DETERMINE COOLING AND HEATING REQUIREMENTS AT SELECT HEATING CAPACITY OF UNIT TO PROVIDE DESIGN CONDITIONS: DESIGN CONDITION REQUIREMENT. Given: In the Pleating Capacities and Efficiencies table, note that the single Required Cooling Capacity(TC).......................................34,000 Btuh phase unit 036090 will provide 73,000 Btuh with an input of 90,000 Sensible Heat Capacity(SHC)...........................................25,000 Btuh Btuh. Required Heating Capacity................................................60,000 Btuh DETERMINE FAN SPEED AND POWER REQUIREMENTS AT Condenser Entering Air Temperature ...............................95°F(35°C) DESIGN CONDITIONS. Before entering the air delivery tables,calculate the total static pressure Indoor-Air Temperature..................80°F(26°C)edb 67°F(19°C)ewb required. From the given example, the Wet Coil Pressure Drop Table, Evaporator Air Quantity.......................................................1200 CFM and the Filter Pressure Drop Table: External Static Pressure................................................0.100 IN.W.C. External Static Pressure 0.100 IN.W.0 Electrical Characteristics........................................................208-1-60 Filter 0.07 IN.W.0 SELECT UNIT BASED ON REQUIRED COOLING CAPACITY Wet Coil Pressure Drop 0.180 IN.W.0 Enter Net Cooling Capacities table at condenser entering temperature of Total Static Pressure 0.287 IN.W.0 95°F(35°C).Unit 036 at 1200 CFM and 677(19°C)ewb(entering wet Enter the table for Dr Coil Air Delive bulb)will provide a total capacity of 34,200 Btuh and a SHC of 27,400 y Delivery—It speont t and 0 CFM is Btuh.Calculate SHC correction,if required,using Note 4 under Cooling Discharge. ink w e). W.C. ESP, the closest speed n SP. CFM is Capacities tables. Med-Low(pink wire),which delivers 1213 CFM at.3 in ESP. SELECT UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE. The Electrical Data Table shows that the unit is designed to operate at 208-1-60. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 11 48VLUE,48VLUF Ultra Low NOx:Product Data Typical Piping and Wiring ROOF-MOUNTING CURB ROOF RETURN-AIR FLEXIBLE DUCT SUPPLY-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX (FIELD-SUPPLIED) A09230 INDOOR a THERMOSTAT RETURN AIR TOP COVER FROM �—POWER SOURCE r' DISCONNECT 191-1 PER NEC* FROM GAS LINE *NEC-NATIONAL ELECTRICAL CODE A09231 Application Data Condensate trap—A 2-in. (50.8 mm) condensate trap must be field Maximum cooling airflow — To minimize the possibility of supplied. condensate blow-off from the evaporator, airflow through the units Ductwork— Secure downflow discharge ductwork to roof curb. For should not exceed 450 CFM per ton. horizontal discharge applications,attach ductwork to unit with flanges. Minimum cooling airflow—Minimum cooling airflow is 350 cfni per To convert a unit to downflow discharge—Units are equipped with ton. factory-installed inserts in the down-flow openings. Removal of the Minimum ambient cooling operation temperature — All standard inserts is similar to removing an electrical knock-out.Use the duct cover units have a minimum ambient operating temperature of 40°F (4°C). to seal the horizontal discharge openings in the unit. Units installed in With accessory low ambient temperature kit, units can operate at horizontal discharge orientation do not require duct covers. temperatures down to 0°F(-17°C). Airflow—Units are draw-thru in the cooling mode and blow-thru in the Minimum temperature—Air entering the heat exchanger in heating heating mode. mode must be a minimum of 50°F(10°C)continuous and/or 45°F(7'C) intermittent. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 25 48VLUE,148VLUF Ultra Low NOx:Product Data Electrical Data Model NominalV-PH-HZ Voltage Range Compressor OFM IFM IDM Power Supply MIN MAX RLA LRA FLA FLA FLA MCA MOCP 2404030 208/230-1-60 197 253 8.7 46 0.6 3.9 0.70 15.4 20 2406030 208/230-1-60 197 253 8.7 46 0.6 3.9 0.70 15.4 20 3004030 208/230-1-60 197 253 13.0 57 0.7 3.9 0.70 21.1 30 3006030 208/230-1-60 197 253 13.0 57 0.7 3.9 0.70 21.1 30 3606030 208/230-1-60 197 253 16.7 79 1.05 5.8 0.70 27.8 40 3606050 208/230-3-60 197 253 10.4 73 1.05 5.8 0.70 19.9 3n 4206030 208/230-1-60 197 253 16.7 109 1.07 3.8 0.70 25.8 40 4206050 208/230-3-60 197 253 11.2 88 105 3.8 0.70 18.9 30 4209030 208/230-1-60 197 253 16.7 109 1.07 3.8 0.70 25.8 40 4209050 208/230-3-60 197 253 11.2 88 1.05 3.8 0.70 18.9 30 4809030 208/230-1-60 197 253 19.6 130 1.05 6.9 0.70 32.5 50 4809050 208/230-3-60 197 253 13.7 83.1 1 1.05 6.9 1 0.70 1 25.1 35 6009030 �208/2300�-3-6O 197 253 23.7 152.5 Ll .05 6.9 0.70 37.6 60 6009050 197 253 15.9 110 .05 6.9 0.70 27.9 ±:�:40 LEGEND EXAMPLE:Supply voltage is 230-3-60. A e c AB=228 v BC=231v FLA-Full Load Amps AC=227 v IDM-Inducer Motor Average'Voltage_ IFM-Indoor Fan Motor 9 9 - 228+ 231 + 227 LRA-Locked Rotor Amps Moron 3 686 MCA-Minimum Circuit Amps = 3 MOCP-Maximum Over Current Protection OFM-Outdoor Fan Motor = 229 RLA-Rated Load Amps Determine maximum deviation from average voltage. (AB)229-228 =1 v NOTES: (BC)231-229 =2 v (AC)229-227 =2 v 1. In compliance with NEC(National Electrical Code) requirements Maximum deviation is 2 v. for multimotor and combination load equipment (refer to NEC Determine percent of voltage imbalance Articles 430 and 440),the overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker. / Voltage Imbalance=100 x 2 2. Minimum wire size is based on 60 C copper wire. Ifother than 229 60 C wire is used, or if length exceeds wire length in table, determine size from NEC. =0.8% 3. Unbalanced 3-Phase Supply Voltage This amount of phase imbalance is satisfactory as it is below the Never operate a motor where a phase imbalance in supply volt- maximum allowable 2%. age is greater than 2%.Use the following formula to determine the percentage of voltage imbalance IMPORTANT: If the supply voltage phase imbalance is Voltage imbalance more than 2%, contact your local electric utility company =100 x m_ax voltage deviation from average voltage immediately. average voltage A06564 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 26 48VLUE,•48VLUF Ultra Low NOx:Product Data Connection Wiring Schematic 208/230-1-60 CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING SCHEMATIC 208/230-1-60 F USED--,,,,CONT BLK-- 0 -BLK FIELDL1�/� SUPPLY_- BLK 11 21 BLK— POWER­ LK CAP 1 BLU H OFM POWER __L2�YEL 23 23 YEL YEL SEE NOTE 8 e EQUIP GN� BLU F BRN UNIT ONLY - BLK F BLU ® GND MAXIMUM WIRE BLU YEL N SIZE 2AWG LBLJ �—GRN/YEL GND IFM PEv BLK L1 BRN COM 12345 COMP YEL C R INDUCER SPEED Zoe RED LOW SPEED m amp m S IDM VIO INT.SPEED I BLURED&VIO HIGH SPEED TO IGC YEL SEE NOTE 4/5 BLK YEL YEL COM (208 230 TRAN BLK RE C 24V v10 /IF USED CCH /' RED 1 1 2 1 3PL1BLK-401—BLK�gLK 1 2 3 GRN BLK 1-74YEL GRNIYEL Lh BLK BLKIF ORN GROUNDED BRN rSTANDOFF p CCH rh 9 T1 0 � L2 L1 P3 —YEL—0FS0-777 BRN r z YEL o 1 IGC � ORG-O O-BRN� 08 v O GRNIYEL 77 BTS P1 BLU 9 6 3 G 8 5 2 BLU LS nED 7 4 1 VIO 4 RED SEE NOTE 7 TO IFM , f /SEE NOTE 4/5 YEL BRN SWHEN EE NOT �� \ VIO ro I RN ko MOTOR P2 N U COM DEHUM�FANN ,, COOL HEAT > CG cGwwc 19 W Y R G CDH D T-S/-T�AT ORN BLU nTC__DH BRN-/T'��--C 6RN GRN=TT-' YEL G M GRY RED �T--R GRNIYELYEL -!T'��--Y PRESSURE WHT 'rr-'SWITCH LF IF USED --W C I /LP'S� -' HPS BRN C2 C1 BLUE--rr}-BLU BLK-e-BLK A220472 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 27 48VLUE,'48VLUF Ultra Low NOx:Product Data Ladder Wiring Schematic 208/230-1-60 LADDER WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING LEGEND 11-1 USE COPPER CONDUCTORS ONLY I L2 BLK FIELD SUPPLY 1 EQUIP GND 2081230 VAC.60 HZ.1 PH - FIELD SPLICE CONT COMPRESSOR CONTACTOR C c,21 OEM YEL CD TERMINAL(MARKED) EQUIP EQUIPMENT C;11 BLK—t—BLK FS FLAME SENSOR YEL o TERMINAL(UNMARKED) GND GROUND IF USED • SPLICE HPS HIGH PRESSURE SWITCH CAP 1 I IGNITOR H O SPLICE(MARKED) IDM INDUCED DRAFT MOTOR BLU BLu COMP C YEL C;23 — FACTORY LO VOLTAGE IFM INDOOR FAN MOTOR BRN IGC INTEGRATED GAS UNIT CONTROLLER /� F - - FIELD CONTROL WIRING LES LOW PRESSURE SWITCH SEE NOTE 10 TT S R YEL -- FIELD POWER WIRING LS1 PRIMARY LIMIT SWITCH Bw BLK ACCESSORY OR OPTIONAL LS2 SECONDARY LIMIT SWITCH WIRING MGV MAIN GAS VALVE BLU��BLU FACTORY HI VOLTAGE OEM OUTDOOR FAN MOTOR BTS BURNER THERMAL SWITCH OT QUADRUPLE TERMINAL PEv C CONTACTOR PEV PRESSURE EQUALIZER VALVE(IF USED) IGC CCH /-IFUSED- CHS IGC CAPi CAPACITOR,COMP TRAN TRANSFORMER CCH BLK—EEE�-BLK-0_BLK�BLK�y�YEL L2 CAP2 CAPACITOR,INDUCER(WHEN USED) T-STAT THERMOSTAT GRN CCH CRANKCASE HEATER 114 YEL L2 CHS CRANKCASE HEATER SWITCH a IFM SEE NOTE 8 c,z3 COMP COMPRESSOR MOTOR BLK 10 UNIT COMPONENT ARRANGEMENT CL1 SEE NOTE 8 caN/ z ;ii OUTDOOR FAN =SECTION C;it BLK 7L13 IDM COMPRESSOR INDOOR FAN CONTROL BOX AREA P3-2 —RE 1+7 SECTION SECTION P3-1(y wo PL z INDUCER SPEED MFRAN 23 23 IDM REo LOW SPEED LS2 21 D 71 YELVIO N. E LPS ELI 10 R V H H SPE 11 HPS V YEL L2 CAP IFM L1 BLK 270 20A DOM VEL L2 HCF PRS CAP2 USES RAN COMP IDM MGV T STAT RED ,aV �C —BRN GAS TI ra T1 Lsl secrloN IGC zavnc° ///Ps I — —/LP�s — c IGC Tt ❑r A F ELK SLK y—BLU-BLU Ct C2 BR °24VAC COM" FS 1 3A FUSE _ _ I �~ FS IT USED DH---- BLU P1-6 YEL M C �GRN/YEL GND HEATING FAN LOGIC P2-1 D9 D 72 T i,91 "T1" URN—DIC-BRN 'W BLOWER W SLOWER G'-�GRN P2-3"G BLU ENERGIZED ENERGIZED DE-ENERGIZED DE-ENERGIZED P1-2 P1-5 BW COOLING FAN LOGIC ry RED p2-4"R" PI-40__v" VEL P1-i 0 1 T T+60 Y___7� wo REo Y BLOWER Y BLOWER P2-5"Y" ENERGIZED ENERGQEO DEENERGIZEO DE-ENERGIZEDORN WHEN USEt w----'`WHT [/�� Pi-B SEE NOTE 6 P2-6 7 PRESSURE SWITCH SPIN P1.7 YEL NOTES: W II 1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED THEY P7-9 GRY MGV GRN/VEL MUST BE REPLACED WITH THE SAME WIRE OR ITS EQUIVALENT. 7r —BRN P1-3 2. SEE PRE-SALE LITERATURE FOR THERMOSTATS. LL U GRNIYEL IFM 3, USE 75 DEGREES C COPPER CONDUCTORS FOR FIELD INSTALLATION. a n 4. REFER TO INSTALLATION INSTRUCTIONS FOR CORRECT SPEED u SELECTION FOR IFM. -esu PEN "MOTOR COM' 5. SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND SEE NOTE 415- -REo COOLING CONNECTIONS FOR YOUR UNIT. _aRN N 6. ON SOME MODELS LS1 AND LS2 ARE WIRED IN SERIES.ON OTHER GEN P2-2"c^ MODELS ONLY LSI IS USED. 7.THIS FUSE IS MANUFACTURED BY LITTLE FUSE,PIN 287003. . DO NOT DISCONNECT PLUG UNDER LOAD. 9IIII""III'I�II'I'IIII„ 9. N.E.C.CLASS 2,24V. L110.PEV FOUND ON SELECT ROTARY COMPRESSORS. 345854-101 REV.0 1.INDUCER MOTOR USES A 230V CONTROL SIGNAL. 345854-101 REV.0 A220473 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 28 48VLUE,'48VLUF Ultra Low NOx:Product Data Connection Wiring Schematic 208/230-3-60 CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING SCHEMATIC 208/230-3-60 IF USED CONT BLK— S—BLK FIELD __L11��gLK 11 21 BLK CAP 1 OFM SUPPLY POWERSEE-R—YE SEE NOTE 8 YEL 23 23 YEL BRN -- L2 _BLU F YEL ® COMP GND EQUIP GNDe OF BLK C R YEL N UNIT ONLY S .75---GRN/YEL GND IFM MAXIMUM WIRE BLK Lt SIZE 2 AWG BRN COM 12345 INDUCER SPEED �Z o x RED I LOW SPEED I a 0 m YEL IDM VIO INT.SPEED I I I �REDVIQ HIGH SPEED BLK TO IGC SEE NOTE 4/5 YEL COM 208 230 IRE TRAN BLK /IF USED---_, C�RED CCH / CHS 2 3 �BLK�—BLK�BLK 1 2 3 PL1 BLK GRN YEL GRN/YEL BLK �:j I F BLK ORN GROUNDED THRU CCH (STANDOFF L) s 77 T1 0 F12 L1 P3 BRN YEL FS BRN 0_77Z YEL o YEL ECONOMIZER PLUG IGC o ORG-01 O-BRN-.-77 r ECOO O GRNIYEL--777 7 PBL SAT I BTS 1� 9 BLU n 1�1 L — J GRY 8 I 8 2 I Z YEL GRY ---BLU �LS1 S2 Y 3 I 3 BRN VIO�RED4 gLKSEE NOTE 7 TO IFM YELWHEN USED SEENOTE 4155 SEE NOTE 6 19 vW / \ VIO12� �p RN 0M JOR 0 COM DEHUM FAN COOL HEATCb CbCb ORN BRN T-STAT _ —0 RE YEL BRN— BLU ---DH MGV M BRN ^�___C !r RY GRN =TT1---G GRNNEL _ IF USED RED lT^�----R PRESSURE C r _LF //�� YEL '/T'�---Y SWITCH BRN C2 C1 BLU�BLU—T BLK�BLK WHT—T^r.'___W C D — — — — — — HPS GRYTT---Y2 A220474 Manufacturer reserves the right to change,at anytime,specifications and designs without notice and without obligations. 29 48VLUE,'48VLUF Ultra Low NOx:Product Data Ladder Wiring Schematic 208/230-3-60 LADDER WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING LEGEND iL1 USE COPPER CONDUCTORS ONLY AL2 IL3 BLK FIELD SUPPLY J-EQUIP GND BLU YEL Z2S FIELD SPLICE EQUIP EQUIPMENT 208/230 VAC.60 HZ.3PH = FS FLAME SENSOR C C2 O TERMINAL(MARKED) GND GROUND c;n aLK BLK OFM O TERMINAL(UNMARKED) HPS HIGH PRESSURE SWITCH f IF USED • SPLICE I IGNITOR vEL IDM INDUCED DRAFT MOTOR O SPLICE(MARKED) IFM INDOOR FAN MOTOR BRN CAP 1 FACTORY LO VOLTAGE IGC INTEGRATED GAS UNIT CONTROLLER BLUC;13 - - FIELD CONTROL WIRING LPS LOW PRESSURE SWITCH COMP C C LSi PRIMARY LIMIT SWITCH YEL -- FIELD POWER WIRING LS2 SECONDARY LIMIT SWITCH S R F ACCESSORY OR OPTIONAL MGV MAIN GAS VALVE YEL WIRING OEM OUTDOOR FAN MOTOR BLK Q FACTORY HI VOLTAGE OT QUADRUPLE TERMINAL BTS BURNER THERMAL SWITCH TRAN TRANSFORMER IGC CCH -IF USED-\ CHS IGC C CONTACTOR T-STAT THERMOSTAT \ L3 CAP1 CAPACITOR,COMP CCH BLK_E PBLK-�BLK�SUN�.YEL CAP2 CAPACITOR,INDUCER(WHEN USED) GRN CCH CRANKCASE HEATER 174 YEL1_3 CHFM S CRANKCASE HEATER SWITCH L1 ISEE NOTE 8 COMP COMPRESSOR MOTOR CONT COM PRESSOR CONTACTOR L1 BLK GRNNEL 73 C,1, C:11 SEE NOTE 8 Z}Z 30 UNIT COMPONENT ARRANGEMENT OUTDOOR FAN OEM C;11 BLK Pu 2 IDM SECTION P3-0 VIO COMPRESSOR INDOOR FAN CONTROL BOX AREA P3-2� RED INDUCER SPEED SECTION SECTION 1 a IDM Pu3 REO LOW SPEED IGC TRAM 23 23 hYEL LS2 21 C 11 PL11( RED V H P D LPS eLL L3 HPC CAP I IEM PRS Li BLK , tBB COM VEL L3 HCF GAP2 USED THAN coMP oM Mcv T-STAT RED z4r T c GA$ (__)--BRN i3 T1 LSi SECTION IGC `24VAC• /RESS r — —/LPS — C IGC T2 a ❑r BLK­Er BLK---*--Bw-ta- _BLU C1 C2 BR '24VAC COM' FS I 3A FUSE ��/ ` - \-J I �b FS IF USED DH---- BLU Pi-6 YEL M C �GRNYEL GND HEATING FAN LOGIC Pz-1 •oH° 0 72 T T,N "Ti" ORN�OI O—BRN� IFM W BLOWER N! BLOWER C"--- GRN P2 3"G, ENERGIZED ENERGIZED DE-ENERGIZED DE ENERGIZED P1-2 BLU —TS BRN MOTOR COM" /L''��1 Pi-5 BLU—�-.g y-- R'---'`RED COOLING FAN LOGIC P24 R P7-4 vlo !/�'��1 LSi LS2 t T]a 5 0 1 T T+60 Y----+—VEL P7.1 VIO RED xozy Y BLOWER Y BLOWER P2-5"Y" �% marc`gym ENERGIZED ENERGIZED DE-ENERGVED DE ENERGIZED P1-8 -ORN WHEN US \ tY SEE NO" W---- WHT COM" P2-6 W PRESSURE 2/,�.,B SWITCH SEE NOTE 4/5 -CONT C----"BRN Y2----t LGRV Pi-7 YEL �GEN/YEL NOTES: Q P1-9 OR MGV F'-BRN P73 1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED THEY n M J MUST BE REPLACED WITH THE SAME WIRE OR ITS EQUIVALENT. LL U RNIVEL BRN P2-2"C^ 2. SEE PRE-SALE LITERATURE FOR THERMOSTATS. o 3. USE 75 DEGREES C COPPER CONDUCTORS FOR FIELD INSTALLATION. o 4. REFER TO INSTALLATION INSTRUCTIONS FOR CORRECT SPEED YEL SELECTION FOR IFM. =p BLK EcoN HARNESS 5. SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND U RED 2 COOLING CONNECTIONS FOR YOUR UNIT. GR 3 BLK 6. ON SOME MODELS LS1 AND LS2 ARE WIRED IN SERIES,ON OTHER 4 BEN MODELS ONLY LSi IS USED. 5 7. THIS FUSE IS MANUFACTURED DE LITTLE FUSE,PIN 287003, IIII'1'III�I�II'IIII�II III 6 P-SBL 8. DO NOT DISCONNECT PLUG UNDER LOAD, T P_ - BL SAT WIM 9. N.E.C.CLASS 2,24V. e 10.INDUCER MOTOR USES A 230V CONTROL SIGNAL. 346093-101 REV.0 346093-101 REV.0 INEIIIX A220475 Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 30 48VLUE,'48VLUF Ultra Low NOx:Product Data Controls Operating Sequence Cooling Sequence of Operation Heating Sequence of Operation (Ultra Low NOx Single With the room thermostat SYSTEM switch in the COOL position and and Three Phase Models) the FAN switch in the AUTO position,the cooling sequence of operation On a call for heating,terminal W of the thermostat is energized,starting is as follows: the induced-draft motor for a 30 second pre-purge at intermediate speed. 1. When the room temperature rises to a point that is slightly above When the pressure switch senses that the induced-draft motor is moving the cooling control setting of the thermostat, the thermostat sufficient combustion air, the burner sequence begins. This function is completes the circuit between thermostat terminal R to terminals Y controlled by the integrated gas unit controller(IGC). and G. After 30 sec of pre-purge is complete, the pressure switch checks for 2. The normally open contacts of energized contactor (C) close and sufficient combustion. Then, the gas valve energizes and the system complete the circuit through compressor motor (COMP) to attempts to ignite with igniter being energized.The igniter energizes for condenser(outdoor)fan motor(OFM).Both motors start instantly. 5 sec and integrated gas controller(IGC)allows system to sense flame 3. The set of normally open contacts on the interface fan board (IFB) for 2 sec at the end of 5 sec of ignition trial.On first successful ignition, are closed which energizes a circuit to the indoor fan motor(IFM). system stays at the intermediate inducer speed for 10 sec and gradually NOTE: Once the compressor has started and then stopped, it should not ramps up to the high speed for steady-state operation. The system uses be started again until 5 minutes have elapsed.The cooling cycle remains the same logic for 2nd ignition trial. If a 3rd or 4th ignition attempt is on until the room temperature drops to a point that is slightly below the needed,the inducer speed is decreased to the low speed.On a successful cooling control setting of the room thermostat. At this point, the light on the 3rd or 4th attempt, the inducer speed is increased to the thermostat breaks the circuit between thermostat terminal R to terminals intermediate speed for about 10 seconds and then gradually ramps up to Y and G.These open circuits deenergize contactor coil C.The condenser the high speed for steady-state operation. In case the 4th attempt fails, and compressor motors stop. After a 60-sec. delay, the blower motor the system will lock out for 1 hr.After 1 hr. lock out period,the system stops. The unit is in a standby condition, waiting for the next call for starts with normal operating sequence. Once flame is established and cooling from the room thermostat. proven successfully,indoor(evaporator)fan motor is energized after 30 seconds. When the thermostat is satisfied and W is de-energized, the pre-mix bumer will stop firing and the indoor (evaporator) fan motor shuts off after a 90 second time-oft'delay. Please note that the IGC has the capability to automatically decrease the indoor (evaporator) fan motor"ON"delay and increase the indoor(evaporator)fan motor"OFF" delay in the event of high duct static and/or partially-clogged filter. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 31 • 48VLUE;48VLUF Ultra Low NOx:Product Data Guide Specifications Packaged Gas Heating/Electric Cooling Units Compressor: Constant Volume Application - Fully hermetic compressors with factory-installed vibration HVAC Guide Specifications ('oils:isolation. Size Range:2 to 5 Tons,Nominal Cooling Evaporator and condenser coils shall have aluminum plaL:; iius 60,000 to 90,000 Btuh, mechanically bonded to seamless copper tubes with all joints brazed. Nominal Heating Input Tube sheet openings shall be belled to prevent tube wear. General Heating Section: — Induced-draft combustion type with energy saving direct spark SYSTEM DESCRIPTION ignition system and redundant main gas valve. Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a — Induced-draft motors shall provide adequate airflow for hermetic scroll compressor for cooling duty.Unit shall discharge supply combustion. air vertically or horizontally as shown on contract drawings.Condenser — The heat exchangers shall be constructed of aluminized steel for fan/coil section shall have a draw-thru design with vertical discharge for corrosion resistance. minimum sound levels. — Pre-mixed burners shall be stainless steel and other alloys. QUALITYASSURANCE — All gas piping and electric power shall enter the unit cabinet at a — Unit shall be rated in accordance with AHRI Standards 210/240 and single location. 270-1995. Refrigerant Components: — Unit shall be designed in accordance with UL Standard 1995 and Refrigerant expansion device shall be of the TXV (thermostatic ANSI Z 21.47. expansion valve)or fixed orifice type. — Unit shall be manufactured in a facility registered to ISO 9001 Filters: manufacturing quality standard. — Unit shall be UL listed and c-UL certified as a total package for Filter section shall consist of field-installed,throwaway, 1-in. (25 mm) safety requirements. thick fiberglass filters of commercially available sizes. — Roof curb shall be designed to conform to NRCA Standards. Controls and Safeties: — Insulation and adhesives shall meet NFPA 90.1 requirements for — Unit controls shall be complete with a self-contained low voltage flame spread and smoke generation. control circuit. — Cabinet insulation shall meet ASHRAE Standard 62.2. — Compressors shall incorporate a solid-state compressor protector DELIVERY,STORAGE AND HANDLING that provides reset capability. — Unit shall be stored and handled per manufacturer's Operating Characteristics: recommendations. — Unit shall be capable of starting and running at 125°F (51°C) ambient outdoor temperature per maximum load criteria of AHRI Products Standard 210. EQUIPMENT — Compressor with standard controls shall be capable of operation General: down to 40°F(4°C)ambient outdoor temperature. Factory-assembled, single-piece, heating and cooling unit. Contained — Units shall be provided with fan time delay to prevent cold air delivery before the heat exchanger warms up. within the enclosure shall be all factory wiring, piping, controls, _ Unit shall be provided with 60-second fan time delay(single phase refrigerant charge with R-41 OA refrigerant,and special features required models)after the thermostat is satisfied. prior to field start-up. Unit Cabinet: Electrical Requirements: — Unit cabinet shall be constructed of phosphated, zinc-coated. All unit power wiring shall enter the unit cabinet at a single location. pre-painted steel capable of with-standing 500 hours in salt spray. Motors: — Normal service shall be through 3 removable cabinet panels. — Compressor motors shall be of the refrigerant-cooled type with — The unit shall be constructed on a rust proof unit base that has an line-break thermal and current overload protection. externally trapped,integrated sloped drain. — All fan motors shall have permanently lubricated bearings, and — Evaporator fan compartment top surface shall be insulated with a inherent,automatic reset,thermal overload protection. minimum 1/2-in. (12.7 mm) thick, flexible fiberglass insulation, — Condenser fan motor shall be totally enclosed. coated on the air side and retained by adhesive and mechanical — Evaporator Fan Motor to be ECM Motor. means. The evaporator wall sections will be insulated with a Compressor Protection: minimum semi-rigid foil-faced board capable ofbeing wiped clean. Solid-state control shall protect compressor by preventing "short Aluminum foil-faced fiberglass insulation shall be used in the entire cycling." indoor air cavity section. — Unit shall have afield-supplied condensate trap. Fans: — The evaporator fan shall be a multi-speed,direct-drive,as shown on equipment drawings. — Fan wheel shall be made from steel, be double-inlet type with forward curved blades with corrosion resistant finish. Fan wheel shall be dynamically balanced. — Condenser fan shall be direct drive propeller type with aluminum blades riveted to corrosion resistant steel spiders, be dynamically balanced,and discharge air vertically. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 32 ' 48VLUE,'48VLUF Ultra Low NOx:Product Data Guide Specifications (Continued) Ultra Low NOx: 10.Low Ambient Package: Shall provide NOx reduction to meet 14ng/J NOx emissions Shall consist of a solid-state control and condenser coil temperature requirements as shipped from the factorysensor for controlling condenser-fan motor operation, which shall Special Features Available: allow unit to operate down to WE (-18°C) outdoor ambient I. Coil Options temperature when properly installed. Base unit with tin plated indoor coil hairpins available as a factory 11.Manual Outdoor Air Damper: installed option. Package shall consist of damper, birdscreen, and rainhood which 2. Compressor Start Kit(single phase units only): can be preset to admit outdoor air for year-round ventilation. Shall provide additional starting torque for single-phase 12.Square-To-Round Duct Transitions(24-48 models): compressors. Shall have the ability to convert the supply and return openings 3. Thermostat: from rectangular to round. To provide for one-stage heating and cooling in addition manual or 13.Time Guard 11 automatic changeover and indoor fan control. Automatically prevents the compressor from restarting for at least 4 4. Crankcase Heater: minutes and 45 seconds atter shutdown of the compressor. Not Shall provide anti-tloodback required when a corporate programmable thermostat is applied or P protection for low-load cooling applications. with a RTU-MP control.Offered as a field installed accessory. 5. Economizer: 14.Louver Metal Outdoor Coil Grille (Horizontal-Field installed accessory) Shall provide hail and vandalism protection. Available as a field (Vertical-Field installed accessory) installed accessory. a. Economizer controls capable of providing free cooling using 15.Low Pressure Switch Kit outside air. Kit is designed for use when a low pressure control in desired.This b.Equipped with low leakage dampers not to exceed 3%leakage,at kit provides added reliability for the compressor. 1.0 IN.W.C.pressure differential. c. Spring return motor shuts off outdoor damper on power failure. 6. Filter Rack Kit: Shall provide filter mounting for downflow applications.Offered as a field installed accessory. 7. Flat Roof Curb: Curbs shall have seal strip and a wood nailer for flashing and shall be installed per manufacturer's instructions. 8. Flue Discharge Deflector Directs flue gas exhaust:90 degrees upward from current discharge. 9. Heat Exchanger Stainless Steel Heat Exchanger available as a factory installed option. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 33 ' 48VLUE,'48VLUF Ultra Low NOx:Product Data C 2022 Carrier.All rights reserved. Edition Date:05/22 Catalog No:48VL-ULN-07PD Replaces:48V L-ULN-06PD Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 34 1%,} Ex;Sal I RT 0 m Base unit dimensions 48SB018040-0480%SMALL-CABINET UNITS VIEW A-A 24" (tI1 6"L2298 (6096) 14 5/8• cAL 2.2WNI 3/1 (372.0)!A 30. 6) r 0 7C� : W VENT CAP 14 5/8' 1 3/0'DIA. (372.0) 18 1/2' 135.0)(POWER ENM 7 15/16'r- 469.97"� ' ELECTRICAL th+ENTRY3/4 3 IALE (201.6) VIEW PONT AIR OPENING CG 14 3/56- 49 7/8" 14 3/16" {� (360. ) (1266.5) T (360.5) r 28 REF2 3/16' 16 3/16ACS (723 13 (55./2 . 6) (411.2)2 3/16' (342.9) (55.6) " J MAIN SHIELD A = a * I D L2 3/16" (55.6) IXED RCMP ACCESS 9 1/16" 28 3/16" PANEL PANEL (230.2) (716.3) RETURN 1I&PA (617615)-� AIR OPENING B1 Tom_IEW --� B 24• 1-------- OPTIONAL SUPPLY (609.6) VENT OUT BLAMER ACCESS AIR OPENING REF OPTIONAL RETURN * PANEL AIR OPENING 1" (25.4) 15' (381.0) 23 3/4" 603.3 14 3/16 I 16' 31 5/16' (360.4) (406.4) (795.3) ' 2" DtA. 1 15/16' a = * * /2 (50.8) (49.2) (38.1) 12 6 GAS ENTRY (355.6) (309.6 7 11/16' • 2 1/16" 1/2"-14 NPT (195.3) (52.4) GAS CONNECTION /0 1/4' (260.4) RIGHT SIDE VIEW REAR VIEW P STANDARD DUCT PANEL ALTERNATE POWER SUPPLY ENTRY FOR SLAB MOUNT MODEL(ALTERCATE CONSTRUCTION) EVAP. COIL 22• 1 5/16' ��I�5 ACCESS PANEL A -'558 (33.3) '- 494 52' (69 4 I aPr(aWl xnRlR ss' * * I * * AIR II91I1Ww Io 13' P / N (930 23 OPTIRIYL yl"r 15' AIR @OIIN0 Csel w 17 /8' _� m s C447.7) ° s 9/16, G38�t <I a 3/4" NPT �I t tale' I+'3/32' 3 13/15' 2 3/4" 19715 I0)» ° nDRA I N (5064) = arle'_ aR u (10.5) (96.8) (69 9) OUTLET t�>,tr 2 5/16' (�2z7) 2 5/16 2 5/16 VIEW V EN 8-B (58.4) 3 13/16' (58.4) (58.4) REAR VIEW LEFT SIDE VIEW __j (96.8) 38 3/8' (975.0) OPTIONAL DUCT PANEL A FRONT VIEW UNIT ELECTRICAL UNIT VITT CORNER WT LB/KG REQ'D CLEARANCES FOR SERVICING in (mm) CHARACTERISTICS g A 1 8 C D Blower Access Panel Side. 30 620) Control Box Access Side 30(762.0) 1 T REQ'D CLEARANCES TO COMBUSTIBLE 30- 4 1 179�/36 1 6/ 7 MATERIAL in.(mm) 1 --1-W 104/47 97/ 7 80 1 9 44 7 Maximum Extension of Overhang 48 (1219.2 1.60 p 1 112T5-1 51 101 Unit Top . 36 4 min. 0- 11 1 Duct Side of Unit 6 min(10 4 min. 105/48 81/37 Side Opposite Ducts 30 (762 0 _M913036080 2OW30-1 .208/230-3-60,46D-3-60 17 Bottom of Unit 4820&230-3-60.460-3-60 86 175 84AIS 116163 1 1 7 1 NOTES: 5 7 1 7 1 Clearances must be maintained to prevent recircu- 8 9 119 54 106/48 lation of air from outdoor fan discharge -Tjgffff425W 2oW30-1-60,208/230-3-60,4604-80 779-r8-559 119/54 106/48 8 8 2, Dimensions in( )are millimeters 8 1- 8 1 87 9 173 1 5 87/39 8 . Accessory dimensions DEDICATED SMALL-CABINET ROOF CURBS 0'-1 3/4" O' - 1 3/4' O'- 1 3/4" [44.51 [44.5] [44.5] NOTES: 1•'6' 5UppLy 1. Completed specification sheet must accom- [457.2b I 1 pany pitched curb order. Contact Order d Correspondent or Product Manager for specification forms. 3'-10" 2. This area of the roof curb slopes slightly to [1168.41 the right for drainage purpose. D•-6 1/2" [1R5.11 1'-6" RETURN [457.21 0E SEE NOTE#2 0'-1 i/2" [38.11 TOP VIEW 15 TYPICAL FOR FLAT ROOF CURBS AND PITCHED ROOF CURBS ROOF CURB DECK PAN RAIL +� p 0'-1 3/4"[44.5] ------T- ----- I MOOD NAILER I I 1 I I I I 01- 1'[25.41REF I I I I TYPICAL ROOF CURB NAIL 1 I COUNTER FLASHING -7 ----I--1------� INSULATION ROOFING PAPER 1177.81 0'- 1 3/47 L CANT STRIP _L M.53 EMBOSSMENTS FOR LOCATING VIEW 15 NOT TO SCALE UNIT ON ROOF CURB CABINET UNIT POSITIONED ON ROOF CURB WOOD NAILER FLAT ROOF CURB PITCHED ROOF CURB 0"- 1" B 0.-6' 125.43 -� 1152.41 ---� CONSTANT B VARIES ACCORDING TO PITCH -T -0'- 13/4" i 0'- 1 3/4' [44.5] [44.51 A 7A UNIT SIZE CURB CURB P/N A B C D E F ROOF PITCH 48SB-900---0180'-8" [203.2 3'-61/2 - 1'-6" 1'-71/2" - _ Flat 48SB-900 019 [1079.5] 0'-11" [279.4 _ [457.2] [495.3] - 48SB-900---020 1'-2" [355.6 - 48SB018040- 48SB-900---021 0'-91/4" [235] 1:12 48SBO48096 48SB-900---022 1'-1/2" 317.5] 2:12 Pitched 48SB-900---023 T-6 1/2" 1'-3 3/4" 400] - 1'-6" 1'-7 1/2" _ 3:12 (see Note 1) 48SB-900---024 [1079.5] 1'-7" 482.6] - [457.2] [495 3] 4:12 48SB-900---025 1.10 1/2" 571 5]] 5:12 48SB-900---026 2'-13/4" 654.1 6:12 10 New RTU UNIT DIMENSIONS - 24-36 cc sm .o aD m Vom SS •+ ` w Z 6 V u • • 1;.1 O y (r U ¢ O Q �O � m c� 2S� AAAA p Jy F \ F Nom LL vi OZOw Nwm w •�• : —�.�ac6 -02 � wowW ti77 77 m 2 e w�Ow�w�"'=oNoo� 1 - W3� mo >0 o U to b N kf- CO OD b Q . o0 0 0 0 o = o o ao o a� ii o'so .61 f W w - s _ 175 m_ s - A"V3 s L NeJW R-ru ACCESSORY DIMENSIONS //1B / Dashed lines show o'oss suppon �, bcatlon for large basepan un'hs. HVAC unit HVAC unit G /C base rails basepan Sealing Gasket Roofcurb T TIF H A Anchor screw/ Wood nailer` Flashing field supplied Rb• Insulationtion Roofing material (field supplied) field supplied E Cant strip D field supplied SMALL/COMMON CURB A09413 'Provided with roofcurb A09090 ROOF CURB DETAIL Br I ----- C I I SMALL I G I SUPPLY I BASE I AIP I UNIT I I I I I I I \ I I I I I I \ I I I ? H F A I I 1 i I LARGE RETURN I BASE I AIR � UNIT I I I I DI-------------- -----I UNIT PLACEMENT ON / \ COMMON CURB A09094 LARGE CURB A09415 SMALL OR LARGE BASE UNIT A09414 UNIT CATALOG A B(small/common B(large CD E F G H SIZE NUMBER IN. base) base) IN. IN. IN. IN. IN.(mm) IN.(mm) (mm) IN.(mm) IN.(mm) (mm) (mm) (mm) (mm) Small CPRFCURB010A00 11 or (279) 10(254) 32.4 30.6(778) Large CPRFCURB011A00 14 (822) (356) 14(356) 16 47.8 2 7(69) 46 ( CPRFCURB012A00 11 (406) (1214) .11170) Large 1 (;49) 14(3 6) (43 .9 42.2(1072) CPRFCURB013A00 (356) *Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small and large basepan units.The cross supports must be located based on whether the unit is a small basepan or a large basepan. NOTES: 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied,as required,to unit being installed. 3. Roof curb is made of 16-gauge steel. 4. Attach ductwork to curb(flanges of duct rest on curb). 5. Insulated panels:1-in.(25.4 mm)thick fiberglass 1 lb.density. 10