Report (3) COMcheck Software Version COMcheckWe I r . .
Mechanical Compliance Certificate
►` (t 2O2z -00G7,
Project Information I I C�5 e Sw 7Z4' AVE RECEIVED
Energy Code: 90.1 (2019) Standard an 2 12U22
Project Title: Everbowl TI
Location: Tigard, Oregon CITY OF TIGARCJ
Climate Zone: 4c
Project Type: Alteration BUILDING DIVISIO "
Construction Site: Owner/Agent: Designer/Contractor:
Iti51 11974 SW 72nd Ave. Suite fr Oregon Mickey Ingalls
Tigard, Oregon 97223 Integ Engineering
5120 Franklin Blvd., Suite 1
Eugene, Oregon 97403
9163429556
mickey@integengineering.com
Mechanical Systems List
QuantitySystem Type & Description
1 [E] HP-13
Split System Heat Pump
Heating Mode: Capacity = 40 kBtu/h,
Proposed Efficiency = 9.00 HSPF, Required Efficiency = 8.20 HSPF
Cooling Mode: Capacity = 36 kBtu/h,
Proposed Efficiency = 16.00 SEER, Required Efficiency = 14.00 SEER
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
SYSTEM VERIFICATION REQUIRED.
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 90.1 (2019) Standard requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Mickey Ingalls - E.I.T. Mickey Ingalls Mi keyyIngalsdb' 07/08/2022
Name-Title Signature Date
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 1 of 8
COMcheck Software Version COMcheckWeb
1/1/(1(1 Inspection Checklist
Energy Code: 90.1 (2019) Standard
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
Plan Review Complies? Comments/Assumptions
& Req.ID
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
6.4.4.2.1, calculations provide all information ❑Does Not
6.7.2 with which compliance can be
[PR2]i determined for the mechanical ❑Not Observable
systems and equipment and ❑Not Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
4.2.2, Plans, specifications, and/or ❑Complies
8.4.1.1, calculations provide all information ❑Does Not
8.4.1.2, with which compliance can be
8.7 determined for the electrical systems ❑Not Observable
[PR6]2 and equipment and document where ❑Not Applicable
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
4.2.5.2 Commissioning shall be performed as ❑Complies Exception: Buildings, additions, or alterations with less than
[PR5]1 stated in Sections 5.9.2, 6.9.2, 7.9.2, ❑Does Not 10,000 ft2 of conditioned space and combined heating,
8.9.2, 9.9.2, 10.9.2, 11.2(d), and ❑Not Observable cooling, and service water heating equipment totaling less
G1.2.1(c). Commissioning must utilize than 960,000 Btu/h in capacity.
ASHRAE/IES Standard 202 or other ❑Not Applicable
generally accepted engineering
standards acceptable to the building
official. FPT and verification
requirements for commissioning are
as stated in Section 4.2.5.1.
Commissioning shall document
compliance of the building systems,
controls, and building envelope with
required provisions of this standard.
Commissioning requirements shall be
incorporated into the construction
documents.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 2 of 8
Section
Footing/ Foundation Inspection Complies? Comments/Assumptions
& Req.ID
6.4.3.7 Freeze protection and snow/ice ❑Complies Exception: Requirement does not apply.
[FO913 melting system sensors for future ❑Does Not
connection to controls.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) tjMedium Impact(Tier 2) :3`Low Impact(Tier 3) 1
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 3 of 8
Section Mechanical Rough-In i Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
& Req.ID 1
6.4.1.4, HVAC equipment efficiency Efficiency: Efficiency: EComplies See the Mechanical Systems list
6.4.1.5 verified. Non-NAECA HVAC ❑Does Not for values.
[ME1]2 equipment labeled as meeting
90.1. ❑Not Observable
....................._....
❑Not Applicable
6.4.3.4.1 Stair and elevator shaft vents ❑Complies Exception: Requirement
0E3]3 have motorized dampers that ❑Does Not does not apply.
automatically close.
❑Not Observable
❑Not Applicable
6.4.3.4.2, Outdoor air and exhaust systems ❑Complies Exception: Gravity dampers
6.4.3.4.3 have motorized dampers that ❑Does Not acceptable in systems with
[ME4]3 automatically shut when not in ❑Not Observable outside or exhaust air flow
use and meet maximum leakage rates less than 300 cfm
rates. Check gravity dampers ❑Not Applicable where dampers are
where allowed. interlocked with fan.
6.4.3.4.5 Enclosed parking garage ❑Complies Exception: Requirement
[ME39]3 ventilation has automatic ❑Does Not does not apply.
contaminant detection and
capacity to stage or modulate ['Not Observable
fans to 50%or less of design ❑Not Applicable
capacity.
6.4.3.4.4 Ventilation fans >0.75 hp have ❑Complies Requirement will be met.
[ME5]3 automatic controls to shut off fan ❑Does Not
when not required.
❑Not Observable
❑Not Applicable
6.4.3.8 Demand control ventilation ❑Complies Exception: Systems with a
[ME6]1 provided for spaces >500 ft2 and ❑Does Not design outdoor airflow less
>25 people/1000 ft2 occupant than 1200 cfm.
density and served by systems Not Observable
with air side economizer, auto ❑Not Applicable
modulating outside air damper
control, or design airflow >3,000
cfm.
6.5.3.2.1 DX cooling systems >= 75 kBtu/h ❑Complies Exception: Requirement
[ME40]2 (>= 65 kBtu/h effective 1/2016) ❑Does Not does not apply.
and chilled-water and
evaporative cooling fan motor hp ❑Not Observable See the Mechanical Systems list
>= 1/4 designed to vary supply ❑Not Applicable for values.
fan airflow as a function of load
and comply with operational
requirements.
6.4.4.1.1 Insulation exposed to weather ❑Complies Requirement will be met.
[ME7]3 protected from damage. ❑Does Not
Insulation outside of the
conditioned space and associated El Not Observable
with cooling systems is vapor ❑Not Applicable
retardant.
6.4.4.1.2 HVAC ducts and plenums R- R- ❑Complies Requirement will be met.
[ME8]2 insulated per Table 6.8.2. Where ❑Does Not
ducts or plenums are installed in
or under a slab, verification may ❑Not Observable
need to occur during Foundation ❑Not Applicable
Inspection.
16.4.4.1.3 HVAC piping insulation thickness. in. in. ❑Complies Requirement will be met.
![ME9]2 Where piping is installed in or ❑Does Not
under a slab, verification may
need to occur during Foundation ❑Not Observable
Inspection. ❑Not Applicable
6.4.4.1.4 Thermally ineffective panel ❑Complies Exception: Requirement
[ME41]3 surfaces of sensible heating ❑Does Not does not apply.
panels have insulation >= R-3.5.
['Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 13jLow Impact(Tier 3) 1
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 4 of 8
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
& Req.1D 1
6.4.4.2.1 Ducts and plenums having ❑Complies Requirement will be met.
[ME10]z pressure class ratings are Seal ❑Does Not
Class A construction.
❑Not Observable
❑Not Applicable
6.8.1-15, Electrically operated DX-DOAS ❑Complies Exception: Requirement
6.8.1-16 units meet requirements per ❑Does Not does not apply.
[ME110]2 Tables 6.8.1-15 or 6.8.1-16.
❑Not Observable
❑Not Applicable
6.4.4.2.2 Ductwork operating >3 in. water EComplies Exception: Requirement
[ME11]3 column requires air leakage ❑Does Not does not apply.
testing.
[Not Observable
❑Not Applicable
6.5.2.3 Dehumidification controls ❑Complies Exception: Cooling capacity
[ME19]3 provided to prevent reheating, ❑Does Not 40 kBtu/h.
recooling, mixing of hot and cold
airstreams or concurrent heating ENot Observable
and cooling of the same ❑Not Applicable
airstream.
6.5.2.4.1 Humidifiers with airstream ❑Complies Exception: Requirement
[ME68]3 mounted preheating jackets have ❑Does Not does not apply.
preheat auto-shutoff value set to
activate when humidification is ❑Not Observable
not required. ❑Not Applicable
6.5.2.4.2 Humidification system dispersion ❑Complies Exception: Requirement
[ME69]3 tube hot surfaces in the ❑Does Not does not apply.
airstreams of ducts or air-
handling units insulated >= R ❑Not Observable
0.5. ❑Not Applicable
6.5.2.5 Preheat coils controlled to stop ❑Complies Requirement will be met.
[ME70]3 heat output whenever ❑Does Not
mechanical cooling, including
economizer operation, is active. ['Not Observable
❑Not Applicable
6.5.2.6 Units that provide ventilation air ❑Complies Exception: Requirement
[ME106]3 to multiple zones and operate in ❑Does Not does not apply.
conjunction with zone heating
and cooling systems are ['Not Observable
prevented from using heating or ❑Not Applicable
heat recovery to warm supply air
above 60°F when representative
building loads or outdoor air
temperature indicate that most
zones demand cooling.
6.5.3.3 Multiple zone VAV systems with ❑Complies Exception: Requirement
[ME42]3 DDC of individual zone boxes ❑Does Not does not apply.
have static pressure setpoint
reset controls. ❑Not Observable See the Mechanical Systems list
❑Not Applicable for values.
6.5.4.2 HVAC pumping systems with >= ❑Complies Requirement will be met.
[ME25]3 3 control values designed for ❑Does Not
variable fluid flow (see section
details). ❑Not Observable
❑Not Applicable
6.5.6.1.1 Exhaust Air Energy Recovery for ❑Complies Requirement will be met.
[ME56]1 Nontransient Dwelling Units ❑Does Not
❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 5 of 8
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
Req.ID
6.5.6.1.2 Exhaust air energy recovery for ❑Complies Exception: Requirements do
[ME111]1 spaces other than Nontransient ElDoes Not not apply.
dwelling units meeting Tables
6.5.6.1.2-1, and 6.5.6.1.2-2. ❑Not Observable
❑Not Applicable
6.5.7.2.1 Kitchen hoods >5,000 cfm have ❑Complies Exception: Requirement
[ME32]2 make up air>=50%of exhaust ❑Does Not does not apply.
air volume.
['Not Observable
❑Not Applicable
6.5.3.8 Occupied standy controls for ❑Complies Exception: Requirement
[ME112]1 zones serving rooms that are ❑Does Not does not apply.
required to have automatic
partial OFF or automatic full OFF ENot Observable
lighting controls per Section ❑Not Applicable
9.4.1.1 shall meet the following
within five minutes of all rooms in
that zone entering occupied-
standby mode: a)Active heating
set point shall be setback at least
1°F, b)Active cooling set point
shall be setup at least 1°F and
c)All airflow supplied to the zone
shall be shut off whenever the
space temperature is between
the active heating and cooling
set points.
6.5.7.2.4 Approved field test used to ❑Complies Exception: Requirement
[ME49]3 evaluate design air flow rates ❑Does Not does not apply.
and demonstrate proper capture
and containment of kitchen ❑Not Observable
exhaust systems. ❑Not Applicable
6.5.8.1 Unenclosed spaces that are ❑Complies Exception: Requirement
[ME34]2 heated use only radiant heat. ❑Does Not does not apply.
❑Not Observable
❑Not Applicable
6.4.3.9 Heating for vestibules and air ❑Complies Exception: Requirement
[ME63]2 curtains with integral heating ❑Does Not does not apply.
include automatic controls that
shut off the heating system when ❑Not Observable
outdoor air temperatures > 45F. ❑Not Applicable
Vestibule heating and cooling
systems controlled by a
thermostat in the vestibule with
heating setpoint <= 60F and
cooling setpoint >= 80F.
6.5.10 Doors separating conditioned ❑Complies Exception: Building
[ME73]3 space from the outdoors have ❑Does Not entrances have automatic
controls that disable/reset closing devices.
heating and cooling system when ❑Not Observable
open. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 6 of 8
•
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
8.4.2 At least 50%of all 125 volt 15-and ❑Complies
[EL10]2 20-Amp receptacles are controlled by Does Not
an automatic control device.
❑Not Observable
❑Not Applicable
8.4.3 New buildings have electrical energy ❑Complies
[EL11]2 use measurement devices installed. ❑Does Not
Where tenant spaces exist, each
tenant is monitored separately. In ['Not Observable
buildings with a digital control system ❑Not Applicable
the energy use is transmitted to to
control system and displayed
graphically.
10.4.1 Electric motors meet requirements ❑Complies Requirement will be met.
[EL9]2 where applicable. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Everbowl TI Report date: 07/08/22
Data filename: Page 7 of 8
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
6.4.3.1.2 Thermostatic controls have a 5 °F ❑Complies Requirement will be met.
[F13}3 deadband. ❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.2 Temperature controls have setpoint ❑Complies Requirement will be met.
[F120]3 overlap restrictions. ❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.3.1 HVAC systems equipped with at least ❑Complies Requirement will be met.
[F121)3 one automatic shutdown control. ❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.3.2 Setback controls allow automatic ❑Complies Requirement will be met.
[FI22]3 restart and temporary operation as ElDoes Not
required for maintenance.
❑Not Observable
❑Not Applicable
6.4.3.5 Heat pump controls prevent ❑Complies Exception: Heat pumps regulated by and meeting NAECA
[FI5]3 supplemental electric resistance heat ❑Does Not requirements and using internal electric resistance heating.
from coming on when not needed.
❑Not Observable
❑Not Applicable
6.4.3.6 When humidification and ❑Complies Requirement will be met.
[FI6]3 dehumidification are provided to a ❑Does Not
zone, simultaneous operation is
prohibited. Humidity control prohibits ❑Not Observable
the use of fossil fuel or electricity to ❑Not Applicable
produce RH > 30% in the warmest
zone humidified and RH < 60% in the
coldest zone dehumidified.
6.7.2.1 Furnished HVAC as-built drawings ❑Complies Requirement will be met.
[F17]3 submitted within 90 days of system ❑Does Not
acceptance.
❑Not Observable
❑Not Applicable
6.7.2.2 Furnished O&M manuals for HVAC ❑Complies Requirement will be met.
[F18]3 systems within 90 days of system ❑Does Not
acceptance.
❑Not Observable
❑Not Applicable
6.7.2.3 An air and/or hydronic system ❑Complies Exception: Requirement does not apply.
[FI9]1 balancing report is provided for HVAC ❑Does Not
systems serving zones >5,000 ft2 of
conditioned area. ❑Not Observable
❑Not Applicable
10.4.3 Elevators are designed with the ❑Complies Exception: Requirement does not apply.
[FI24]2 proper lighting, ventilation power, and ❑Does Not
standby mode.
ENot Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) T 3JLow Impact(Tier 3)_ 1
Project Title: Everbowl TI Report date: 07/08/22