Report (2) COMcheck Software Version 4.1.5.3 OFFICE COP1tr
Ali Interior Lighting Compliance Certificate
BuP22.z —
Project InformationR Energy Code: 2015IECCECEIVED ZNb SIrJ eSV-.
Project Title: Lululemon
Project Type: Alteration 2 3 201Z
CITY OF TIGARD
Construction Site: Owner/Agent: BUILDING DIVISION Designer/Contractor:
Washington Square Peter Leptuch
9585 SW Washington Sq Road Peter A. Leptuch, P.E.
Portland, OR 97223 300 N. Carroll blvd.
Suite#200
Denton, TX 76201
(940) 735-5127
pleptuch@yahoo.com
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Retail:Sales Area 7584 1.59 12059
Allowance:Furniture,clothing,cosmetics highlighting/Fix.ID:Track lighting 1 6506(a) 1.40 960(b)
Total Allowed Watts= 13019
(a)Area claimed may exceed total floor area when Retail Merchandise Highlighting allowance(s)are specified.
(b)Allowance is(B x C)or the actual wattage of the fixtures given in Proposed Power section,whichever is less.
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp I Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Retail:Sales Area(7584 sa.ft.)
LED 1 copy 1: D5:STRIP LIGHT:Other: 1 9 24 216
LED 6:D6:linear LED:Other: 1 2 20 40
LED 2: FL:STRIP LIGHT:Other: 1 2 11 22
LED 1 copy 1: L4:STRIP LIGHT:Other: 1 1 39 39
LED 1:L8:STRIP LIGHT:Other: 1 10 69 690
LED 3:L2:Surface LED:Other: 1 2 14 28
LED 9:LS2:linear LED:Other: 1 245 4 1102
LED 6 copy 1:P1:linear LED:Other: 1 45 4 198
LED 3 copy 1: R3: LED:Other: 1 4 66 264
LED 5:RF1-S: DN light:Other: 1 8 12 96
LED:RW1:DN light:Other: 1 18 12 216
LED 10:RF4:DN light:Other: 1 8 15 120
Track lighting 1:track: Wattage based on current limiting device capacity 0 0 960 960
Track lighting 2:track: Wattage based on current limiting device capacity 0 0 1080 1080
Track lighting 3:track: Wattage based on current limiting device capacity 0 0 1080 1080
Track lighting 4:track: Wattage based on current limiting device capacity 0 0 1080 1080
Track lighting 5:track: Wattage based on current limiting device capacity 0 0 1080 1080
Track lighting 6:track: Wattage based on current limiting device capacity 0 0 1200 1200
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017 - KPA- EV-Lululemon -Washington S Page 1 of 14
Portland, OR\LLL_Portland,OR_2018Comcheck(Passes).cck
Total Proposed Watts= 9512
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans,specifications, and other calculations submitted with this permi application,The proposed interior lighting
systems have been designed to meet the 2015 IECC requirement ' C' c k Ver ' 4.1 .3 and to comply with any
applicable mandatory requirements listed in the Inspection Ch: 'is ��
Peter A. Leptuch, P.E. Air /�/ d
Name-Title Sig at re Dat
PROF
Fss
��' �NGI NCF9 �(2
/d :5s
,Or A/, A/Za.
OREGON o•• U�
"lRy 10�Q,�J
1pAML
cXPIRES /2/3i/u
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\ (P-2022)\ 22.017-KPA-EV-Lululemon-Washington S Page 2 of 14
Portland, OR\LLL_Portland, OR_2018Co_mcheck(Passes).cck
COMcheck Software Version 4.1.5.3
11ic Mechanical Compliance Certificate
111
Project Information
Energy Code: 2015 IECC
Project Title: Lululemon
Location: Portland, Oregon
Climate Zone: 4c
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
Washington Square Peter Leptuch
9585 SW Washington Sq Road Peter A. Leptuch, P.E,
Portland, OR 97223 300 N. Carroll blvd.
Suite #200
Denton,TX 76201
(940) 735-5127
pleptuch@yahoo.com
Mechanical Systems List
Quantity System Type&Description .� \1 '�t`nil'',
1 HVAC System 1 (Single Zone): ^ '`� NGIN/r 95SU
Heating: 1 each-Duct Furnace,Electric,Capacity=4 kBtu/h 2
No minimum efficiency requirement applies '�/ ''r% 1
Cooling: 1 each-Hydronic Coil,Capacity=48 kBtu/h,Unknown Economizer `j'�u
No minimum efficiency requirement applies
Fan System: None
-, 1 OREGON o�ti 1
1 HVAC System 8(Single Zone): 2(j 2 JC
Heating: 1 each-Duct Furnace,Electric,Capacity=25 kBtu/h T9 qRY A�Q.�
No minimum efficiency requirement applies gDAM k-
Cooling: 1 each-Hydronic Coil,Capacity=88 kBtu/h,Unknown Economizer
No minimum efficiency requirement applies "XPIRFS:/1/3I/i1i
Fan System: None
1 Water Heater 1:
Electric Instantaneous Water Heater,Capacity:15 gallons w/Heat Trace Tape Installed
Proposed Efficiency:4.80 SL,%/h(if>12 kW),Required Efficiency:2.10 SL,%/h(if>12 kW)
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this d.cument is consistent with the building
plans, specifications, and other calculations submitted with this permit appl' atio Th- . oposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck V- o ,.1. -- an.,
,#a.• any applicable mandatory
requirements listed in the Inspection Checklist. �'�
III
Peter A. Leptuch, P.E. //tr'/Altit 034/
Name-Title ignature/ Date
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017- KPA- EV-Lululemon -Washington 5 Page 3 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
i
COMcheck Software Version 4.1.5.3
il Inspection Checklist
Energy Code: 2015 IECC
IPA
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# i Plan Review Complies? Comments/Assumptions
& Req.ID
1 C103.2 Plans,specifications, and/or ❑Complies
[PR2]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the mechanical DNot Observable
systems and equipment and DNot Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
C103.2 Plans,specifications,and/or DComplies ______
[PR3P calculations provide all information ❑Does Not
with which compliance can be
determined for the service water DNot Observable
heating systems and equipment and DNot Applicable
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C103.2 Plans, specifications,and/or ❑Complies
[PR4]i calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\ 22.017-KPA-EV-Lululemon-Washington S Page 4 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
Section I
# j Footing/Foundation Inspection Complies? Comments/Assumptions
& Rey.ID L_—
C403.2.4. Snow/ice melting system sensors for ❑Complies
5, future connection to controls. Freeze ❑Does Not
C403.2.4. protection systems have automatic
6 controls installed. [Not Observable
[FO913 ❑Not Applicable
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) i 3 !Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\ (P-2022)\_22.017-KPA- EV- Lululemon-Washington 5 Page 5 of 14
Portland, OR\LLL Portland, OR_2018Comcheck(Passes).cck
Section
Plumbing Rough-In Inspection Complies? Comments/Assumptions
'Se Re9.1D
C404.5, Heated water supply piping conforms OComplies
C404.5.1, to pipe length and volume ODoes Not
C404.5.2 requirements. Refer to section details. Not Observable
[PL6J3 ONot Applicable
C404.5, Heated water supply piping conforms OComplies
��4—
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details. Not Observable
[PL613 ONot Applicable
C404.5, Heated water supply piping conforms ❑Complies
C404.5.1, to pipe length and volume ❑Does Not
C404.5.2 requirements. Refer to section details.[PL6]3 ONot Observable
ONot Applicable
C404.6.1, Automatic time switches installed to OComplies
C404.6.2 automatically switch off the ❑Does Not
[PL3]1 recirculating hot-water system or heat ❑Not Observable
trace.
ONot Applicable
C404.6.3 Pumps that circulate water between a OComplies �—
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating ONot Observable
cycle. ONot Applicable
C404.6.3 Pumps that circulate water between a OComplies
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating ONot Observable
cycle. ONot Applicable
C404.6.3 Pumps that circulate water between a OComplies
[PL7]3 heater and storage tank have controls ❑Does Not
that limit operation from startup to ❑Not Observable
<= 5 minutes after end of heating
cycle. ONot Applicable
C404.7 Water distribution system that pumps OComplies
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source ONot Observable
owt
demandthrough ar recirculationc ld- aer watersupply system.pipeis a ONot Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
C404.7 Water distribution system that pumps OComplies
[PL8]3 water from a heated-water supply ❑Does Not
pipe back to the heated-water source Not Observable
through a cold-water supply pipe is a
demand recirculation water system. ONot Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
['Ti High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017-KPA-EV-Lululemon-Washington 5 Page 6 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
Section
Plumbing Rough-In Inspection ; Complies? Comments/Assumptions
C404.7 Water distribution system that pumps OComplies
[PL8j3 water from a heated-water supply ❑Does Not
pipe back to the heated-water sourceO Not Observable
through a cold-water supply pipe is a
demand recirculation water system. LJNot Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F,
Additional Comments/Assumptions:
j 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 13 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017-KPA-EV-Lululemon-Washington S Page 7 of 14
Portland, OR\LLL_Portland,OR_2018Comcheck(Passes).cck
Section
# I Mechanical Rough-In Inspection Complies? Comments/Assumptions
C402.2.6 Thermally ineffective panel surfaces of❑Complies
[ME41)3 sensible heating panels have ❑Does Not
insulation >= R-3.5.
ONot Observable
ONot Applicable
C403.2.12 HVAC fan systems at design ❑Complies See the Mechanical Systems list for values.
.1 conditions do not exceed allowable ODoes Not
[ME65)3 fan system motor nameplate hp or fan :Not Observable
system bhp. ONot Applicable
C403.2.12 HVAC fan systems at design ❑Complies See the Mechanical Systems list for values.
.1 conditions do not exceed allowable ❑Does Not
[ME65]3 fan system motor nameplate hp or fan ONot Observable
system bhp. ONot Applicable
C403.2.12 Fans have efficiency grade(FEG) >= ❑Complies
.3 67.The total efficiency of the fan at ❑Does Not
(ME117)2 the design point of operation <= 15% ONot Observable
of maximum total efficiency of the
fan. ONot Applicable
C403.2.12 Fans have efficiency grade(FEG) >= ❑Complies
.3 67.The total efficiency of the fan at ❑Does Not
[ME117]2 the design point of operation <= 15% ONot Observable
of maximum total efficiency of the
fan. ONot Applicable
C403.2.13 Unenclosed spaces that are heated ❑Complies •
[ME71)2 use only radiant heat. ❑Does Not
ONot Observable
ONot Applicable
C403.2.3 HVAC equipment efficiency verified. ❑Complies See the Mechanical Systems list for values.
[ME55]2 ❑Does Not
ONot Observable
ONot Applicable
C403.2.6. Demand control ventilation provided ❑Complies
1 for spaces>500 ft2 and >25 ❑Does Not
[ME59]1 people/1000 ft2 occupant density and :Not Observable
served by systems with air side
economizer,auto modulating outside ONot Applicable
air damper control, or design airflow
>3,000 cfm.
C403.2.6. Enclosed parking garage ventilation OComplies
2 has automatic contaminant detection ❑Does Not
[ME115]3 and capacity to stage or modulate Not Observable
fans to 50%or less of design capacity.
Not Applicable
C403.2.7 Exhaust air energy recovery on ❑Complies
[ME57)1 systems meeting Table C403.2.7(1) ❑Does Not
and C403.2.7(2).
:Not Observable
ONot Applicable
C403.2.8 Kitchen exhaust systems comply with ❑Complies
[ME116]3 replacement air and conditioned ❑Does Not
supply air limitations,and satisfy hood :Not Observable
rating requirements and maximum
exhaust rate criteria. ONot Applicable
C403.2.9 HVAC ducts and plenums insulated. ❑Complies
[ME6o)2 Where ducts or plenums are installed ❑Does Not
in or under a slab,verification may ONot Observable
need to occur during Foundation
Inspection. ONot Applicable
1 High Impact(Tier 1) 2 (Medium Impact(Tier 2) 13 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017-KPA-EV-Lululemon-Washington 5 Page 8 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
Section
# Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Req.ID
C403.2.9 Ducts and plenums sealed based on ❑Complies
[ME10]2 static pressure and location. :Does Not
ONot Observable
ONot Applicable
C403.2.9. Ductwork operating >3 in. water ❑Complies
1.3 column requires air leakage testing. ❑Does Not
[ME11)3 :Not Observable
❑Not Applicable
C403.2.9. Ductwork operating >3 in.water OComplies
1.3 column requires air leakage testing. ❑Does Not
[ME11]3 :Not Observable
ONot Applicable
C403.4.2. Three-pipe hydronic systems using a ❑Complies
1 common return for hot and chilled ❑Does Not
[ME5O]2 water are not used.
:Not Observable
:Not Applicable
C403.4.2. Three-pipe hydronic systems using a DComplies
1 common return for hot and chilled ❑Does Not
[ME50]2 water are not used. ONot Observable
ONot Applicable
C403.4.2. Chilled water plants with multiple ❑Complies
6 chillers have capability to reduce flow ❑Does Not
[ME26]3 automatically through the chiller plant :Not Observable
when a chiller is shut down. Boiler
plants with multiple boilers have the ONot Applicable
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
C4- 03.4.2. Chilled water plants with multiple ❑Complies
6 chillers have capability to reduce flow ❑Does Not
[ME26]3 automatically through the chiller plant ONot Observable
when a chiller is shut down. Boiler
plants with multiple boilers have the ❑Not Applicable
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
C4- 03.4.4. Multiple zone VAV systems with DDC ❑Complies See the Mechanical Systems list for values.
6 of individual zone boxes have static ❑Does Not
[ME110)3 pressure setpoint reset controls. ONot Observable
ONot Applicable
C403.4.4. Multiple zone VAV systems with DDC ❑Complies See the Mechanical Systems list for values.
6 of individual zone boxes have static ❑Does Not
[ME110]3 pressure setpoint reset controls. ONot Observable
ONot Applicable
C403.4.5 Condenser heat recovery system that ❑Complies
[ME31]3 can heat water to 85 4F or provide ❑Does Not
60%of peak heat rejection is installed ONot Observable
for preheating of service hot water.
ONot Applicable
C403.4.5 Condenser heat recovery system that ❑Complies _
[ME31]3 can heat water to 85 2F or provide ❑Does Not
60%of peak heat rejection is installed ['Not observable
for preheating of service hot water.
DNot Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\ 22.017-KPA-EV-Lululemon-Washington S Page 9 of 14
Portland, OR\LLL_Portland,OR_2018Comcheck(Passes).cck
Section
Mechanical Rough-In Inspection Complies? Comments/Assumptions
& Rec.ID L_.---..._._.._._. __.....____.___.........._._........_......_.._._._...__._.._..-....._'r.._..
C408.2.2. Air outlets and zone terminal devices ❑Complies
1 have means for air balancing. ❑Does Not
[ME53)3 ❑Not Observable
❑Not Applicable
C408.2.2. HVAC hydronic heating and cooling ❑Complies
2 coils have means to balance and have ❑Does Not
[ME54]3 pressure test connections. ❑Not Observable
❑Not Applicable
C408.2.2. HVAC hydronic heating and cooling ❑Complies
2 coils have means to balance and have ❑Does Not
[ME54]3 pressure test connections. ❑Not Observable
❑Not Applicable
C403.5, Refrigerated display cases,walk-in ❑Complies
C403.5.1, coolers or walk-in freezers served by ❑Does Not
C403.5.2 remote compressors and remote Not Observable
[ME123]3 condensers not located in a ❑
condensing unit, have fan-powered :Not Applicable
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
I 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017 -KPA-EV-Lululemon-Washington S Page 10 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
Section
# j Rough-In Electrical Inspection Complies? ( Comments/Assumptions
& Req.ID_'__._..._ 1
C405.2.1 Lighting controls installed to uniformly OComplies
[EL15]1 reduce the lighting load by at least ❑Does Not
50%. ONot Observable
❑Not Applicable
C405.2.1 Occupancy sensors installed in OComplies
[EL18J1 required spaces. ODoes Not
['Not Observable
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies
C405.2.2. per approved lighting plans and all ODoes Not
3 manual controls readily accessible and
[EL23]2 visible to occupants. [Not Observable
❑Not Applicable
C405.2.2. Automatic controls to shut off all OComplies
1 building lighting installed in all ODoes Not
[EL22J2 buildings.
❑Not Observable
❑Not Applicable
C405.2.3 Daylight zones provided with OComplies
[EL16J2 individual controls that control the ODoes Not
lights independent of general area
lighting. ❑Not Observable
❑Not Applicable
C405.2.3, Primary sidelighted areas are OComplies
C405,2.3. equipped with required lighting ODoes Not
1, controls. :Not Observable
C405.2.3.
2 ❑Not Applicable
[EL2011
C405.2.3, Enclosed spaces with daylight area OComplies
C405.2.3. under skylights and rooftop monitors ODoes Not
1, are equipped with required lighting
C405.2.3. controls. ❑Not Observable
3 ❑Not Applicable
[EL21]1
C405,2.4 Separate lighting control devices for OComplies _~—
[EL4]1 specific uses installed per approved ODoes Not
lighting plans.
['Not Observable
❑Not Applicable
C405.2.4 Additional interior lighting power OComplies
[EL8J1 allowed for special functions per the ODoes Not
approved lighting plans and is :Not Observable
automatically controlled and
separated from general lighting. ❑Not Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies
[EL6J1 face. ODoes Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) _ 2 Medium Impact(Tier 2) 1 3 Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\ 22.017- KPA- EV-Lululemon-Washington S Page 11 of 14
Portland, OR\LLL Portland,OR_2018Comcheck(Passes).cck
Section I
# I 1 Final Inspection Complies? Comments/Assumptions
C303.3, Furnished O&M instructions for ❑Complies
C408.2.5. systems and equipment to the ODoes Not
2 building owner or designated
[FI17]3 representative. ONot Observable
ONot Applicable
C303.3, Furnished O&M manuals for HVAC DComplies
- ��
C408.2.5. systems within 90 days of system ❑Does Not
3 acceptance.
[FI8]3 :Not Observable
ONot Applicable
C403.2.2 HVAC systems and equipment ❑Complies
[FI27]3 capacity does not exceed calculated ❑Does Not
loads.
ONot Observable
_ ONot Applicable
C403.2.4. Heating and cooling to each zone is ❑Complies -
1 controlled by a thermostat control. ❑Does Not
[FI47]3 Minimum one humidity control device
per installed ONot Observable
humidification/dehumidification ONot Applicable
system.
C403.2.4. Heating and cooling to each zone is ❑Complies _____
1 controlled by a thermostat control. ❑Does Not
[F147)3 Minimum one humidity control device ['Not Observable
per installed
r humidification/dehumidification ONot Applicable
system.
C403.2.4. Thermostatic controls have a 5 °F ❑Complies
1.2 deadband. ❑Does Not
, [FI38]3 :Not Observable
I
[Not Applicable
C403.2.4. Temperature controls have setpoint ❑Complies
1.3 overlap restrictions. ❑Does Not
[FI20]3 ONot Observable
ONot Applicable
C403.2.4. Each zone equipped with setback ❑Complies
2 controls using automatic time clock or El—Does Not
[FI39]3 programmable control system. :Not Observable
DNot Applicable
C403.2.4. Automatic Controls: Setback to 55°F OComplies
2.1, (heat)and 85°F(cool); 7-day clock, 2- ❑Does Not
C403.2.4. hour occupant override, 10-hour
Not Observable
2.2[F 40]3 backup ONot Applicable
•
C404.3 Heat traps installed on supply and ❑Complies
[FI11]3 discharge piping of non-circulating ❑Does Not
systems. ❑Not Observable
:Not Applicable
C404.4 All piping insulated in accordance with ❑Complies
[F125J2 section details and Table C403.2.10. ❑Does Not
ONot Observable
ONot Applicable
1 1 High Impact(Tier 1) 2l Medium Impact(Tier 2) 13 I Low Impact(Tier 3) I
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\ 22.017-KPA-EV- Lululemon-Washington S Page 12 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
Section
Final Inspection Complies? Comments/Assumptions
C405.4.1 Interior installed lamp and fixture OComplies See the Interior Lighting fixture schedule for values.
(FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts ONot Observable
are less than or equal to allowed ❑Not Applicable
watts.
C408.2.1 Commissioning plan developed by OComplies
[FI28]1 registered design professional or ODoes Not
approved agency.
ONot Observable
ONot Applicable
C408.2.3. HVAC equipment has been tested to OComplies
1 ensure proper operation. ODoes Not
[Fl31]1 ONot Observable
ONot Applicable
C408.2.3 HVAC control systems have been OComplies
2 tested to ensure proper operation, ODoes Not
[FI10)1 calibration and adjustment of controls.
ONot Observable
ONot Applicable
C408.2.4 Preliminary commissioning report ❑Complies
[FI29)1 completed and certified by registered ODoes Not
design professional or approved
agency. ONot Observable
ONot Applicable
C408.2.5. Furnished HVAC as-built drawings -Li-Complies
1 submitted within 90 days of system ODoes Not
[FI7)3 acceptance. ONot Observable
ONot Applicable
C408.2.5. Furnished as-built drawings for ❑Complies
1 electric power systems within 90 days ODoes Not
[FI16]3 of system acceptance. ONot Observable
:Not Applicable
C408.2.5. An air and/or hydronic system OComplies
3 balancing report is provided for HVAC DDoes Not
[FI43]1 systems. ONot Observable
ONot Applicable _
C408.2.5. Final commissioning report due to OComplies
4 building owner within 90 days of ODoes Not
[FI30]1 receipt of certificate of occupancy. ONot Observable
ONot Applicable
C408.3 Lighting systems have been tested to OComplies
[FI33]1 ensure proper calibration, adjustment, ODoes Not
programming, and operation. ONot Observable
ONot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) j 3 i Low Impact(Tier 3)
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017-KPA- EV-Lululemon-Washington S Page 13 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck(Passes).cck
w
Project Title: Lululemon Report date: 03/11/22
Data filename: C:\Users\Peter A Leptuch P E\Dropbox\_(P-2022)\_22.017-KPA- EV• Lululemon -Washington S Page 14 of 14
Portland, OR\LLL_Portland, OR_2018Comcheck (Passes).cck