Report ' COMcheck Software Version COMcheckWeb
(6
Interior Lighting Compliance Certificate
c2022
r603 . 44
EL RG � C E I V E DProject Information SvA / PAC(
0
Energy Code: 2018 IECC
' • JUN 9 2022
Project Title: Tigard -Trader Joe's j al Y OF TIGARD
Project Type: New Construction
�: BUILDING DIVISION
Construction Site: Owner/Agent: Designer/Contractor:
Additional Efficiency Package(s)
Credits: 1.0 Required 0.0 Proposed
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed
(ft2) Watts /ft2 Watts
1-Multifamily 16152 0.68 10983
Total Allowed Watts = 10983
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp /Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
1-Multifamily
LED: A: 2'X4' RECESSED TROFFER: Other: 1 147 49 7203
LED: B: 4' SUSPENDED: Other: 1 7 38 266
LED: C: 2'X2' RECESSED TROFFER: Other: 1 17 29 493
LED: D: 4' STRIP: Other: 1 13 34 442
LED: X: EXIT SIGN: Other: 1 6 1 6
LED: T: 8'TRACK: Other: 1 1 600 600
Total Proposed Watts = 9010
Interior Lighting PASSES: Design 18% better than code
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist. C,r�`J �' l ���"''�
Tobin Bateen - Electrical / ' '`--- 05/22/2022
Name-Title Signature Date
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 1 of 6
COMcheck Software Version COMcheckWeb
(41
II Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2018 IECC
Project Title: Tigard -Trader Joe's
Project Type: New Construction
Exterior Lighting Zone 2 (Residential mixed use area (LZ2))
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts / Wattage (B X C)
Entry canopy 984 ft2 0.25 Yes 246
Total Tradable Watts (a) = 246
Total Allowed Watts= 246
Total Allowed Supplemental Watts (b) = 400
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable
areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp /Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
Entry canopy (984 ft2): Tradable Wattage
LED: F: 6" CAN: Other: 1 14 44 616
Total Tradable Proposed Watts = 616
Exterior Lighting PASSES: Design 5% better than code
Exterior Lighting Compliance
Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed exterior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Tobin Bateen - Electrical 7 ,(J- 4 J3G 05/22/2022
Name -Title Signature Date
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 2 of 6
COMcheck Software Version COMcheckWeb
rift
Inspection Checklist
Energy Code: 2018 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID — — — — —
C103.2 Plans, specifications, and/or ❑Complies
[PR4]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment '❑Not Applicable ,
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
C103.2 Plans, specifications, and/or ❑Complies
[PR8]1 calculations provide all information '❑Does Not
with which compliance can be
determined for the exterior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Additional Comments/Assumptions:
[1 High Impact(Tier 1) T2 LMedium Impact (Tier 2) ; 3 Low Impact(Tier 3) i
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 3 of 6
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.2. Spaces required to have light- ❑Complies
2 reduction controls have a manual ❑Does Not
[EL22]1 control that allows the occupant to
reduce the connected lighting load in ❑Not Observable
a reasonably uniform illumination ❑Not Applicable
pattern >= 50 percent.
C405.2.1, Occupancy sensors installed in .❑Complies
C405.2.1. classrooms/lecture/training rooms, ,❑Does Not
1 conference/meeting/multipurpose
[EL18]1 rooms, copy/print rooms, ❑Not Observable
lounges/breakrooms, enclosed offices, ❑Not Applicable
open plan office areas, restrooms,
storage rooms, locker rooms,
warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor-to-ceiling height partitions.
Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
C405.2.1. Occupancy sensors control function in ❑Complies
2 warehouses: In warehouses, the liElDoes Not
[EL19]1 lighting in aisleways and open areas is Observable
controlled with occupant sensors that
automatically reduce lighting power ❑Not Applicable
by 50%or more when the areas are
unoccupied.The occupant sensors
control lighting in each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
C405.2.1 Occupant sensor control function in ❑Complies
3 open plan office areas: Occupant ❑Does Not
[EL20]1 sensor controls in open office spaces
>= 300 sq.ft. have controls 1) ❑Not Observable
configured so that general lighting can ❑Not Applicable
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) automatically turn
off general lighting in all control zones
within 20 minutes after all occupants
have left the space, 3) are configured
so that general lighting power in each
control zone is reduced by >= 80%of
the full zone general lighting power
within 20 minutes of all occupants
leaving that control zone, and 4) are
configured such that any daylight
responsive control will activate space
general lighting or control zone
general lighting only when occupancy
for the same area is detected.
C405.2.2, Each area not served by occupancy ❑Complies
C405.2.2. sensors(per C405.2.1) have time- ❑Does Not
1, switch controls and functions detailed
C405.2.2. in sections C405.2.2.1 and C405.2.2.2. ❑Not Observable
2 ❑Not Applicable
[EL21]2
I_1 I High Impact(Tier 1) [ 2 Medium Impact(Tier 2) 13 Low Impact(Tier 3)
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 4 of 6
, Section
Rough In Electrical Inspection I Complies? Comments/Assumptions
& Req.ID_
C405.2.3, Daylight zones provided with ❑Complies
C405.2.3. individual controls that control the ❑Does Not
1, lights independent of general area
C405.2.3. lighting. See code section C405.2.3 ENot Observable
2 Daylight-responsive controls for ENot Applicable
[EL2312 applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
C405.2.4 Separate lighting control devices for ❑Complies
[EL26]1 specific uses installed per approved ❑Does Not
lighting plans.
[Not Observable
ENot Applicable
C405.2.4 Additional interior lighting power ❑Complies
[EL27]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and Not Observable
separated from general lighting. ❑Not Applicable
C405.2.5 .Manual controls required by the ❑Complies
[EL28]ni0 energy code are in a location with ❑Does Not
ready access to occupants and
located where the controlled lights are ❑Not Observable
visible, or identify the area served and ENot Applicable
their status.
C405.2.6 Automatic lighting controls for exterior ❑Complies
[EL30]ni° lighting installed. Controls will be ❑Does Not
daylight controlled, set based on
business operation time-of-day, or ENot Observable
reduce connected lighting > 30% ENot Applicable
C405.3 Exit signs do not exceed 5 watts per ❑Complies
[EL6]1 face. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
rl High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) —
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 5 of 6
Section
# Final Inspection 1 Complies? Comments/Assumptions
& Req.Id
C303.3, Furnished O&M instructions for ❑Complies
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated
[FI17]3 representative. ❑Not Observable
ENot Applicable
C405.4.1 Interior installed lamp and fixture EComplies See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts plot Observable
are less than or equal to allowed ,❑Not Applicable
watts.
C405.5.1 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[FI19ji with what is shown on the approved EDoes Not
lighting plans, demonstrating
proposed watts are less than or equal ENot Observable
to allowed watts. ENot Applicable
C408.2.5. Furnished as-built drawings for ❑Complies
1 electric power systems within 90 days ElDoes Not
[F116)3 of system acceptance.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
❑Not Observable
ENot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) i 3 Low Impact(Tier 3)
Project Title: Tigard -Trader Joe's Report date: 05/02/22
Data filename: Page 6 of 6