(41Mechanical Compliance Certificate JUN 9 2021
t;ITY OF TIGARD
3UILDING DIVISION'
Project Information
Energy Code: 90.1 (2019) Standard
Project Title: Trader Joes -Tigard �y
Location: Tigard, Oregon t1 f'20 2Z-Cd<173
Climate Zone: 4c / QA) P t fC K M.
Project Type: Alteration � ZO0
Construction Site: Owner/Agent: Designer/Contractor:
Mechanical Systems List
Quantity System Type & Description
3 HVAC System
Heating: 1 each - Duct Furnace, Gas, Capacity = 336 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Cooling: 1 each - DX DOAS (Dehumidification), Capacity = 144 kBtu/h, Air-Cooled Condenser, No Economizer,
Economizer exception: Humidity Requirements
Proposed Efficiency = 4.10 ISMRE, Required Efficiency: DX-DOAS unit 4.00 ISMRE
Fan System: FAN SYSTEM 1 --Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply, Single-Zone VAV, 4700 CFM, 5.0 motor nameplate hp, 0.95 fan energy index
SYSTEM VERIFICATION REQUIRED.
1 HVAC System
Heating: 1 each - Duct Furnace, Gas, Capacity = 286 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Cooling: 1 each - DX DOAS (Dehumidification), Capacity = 144 kBtu/h, Air-Cooled Condenser, No Economizer,
Economizer exception: Humidity Requirements
Proposed Efficiency = 4.10 ISMRE, Required Efficiency: DX-DOAS unit 4.00 ISMRE
Fan System: FAN SYSTEM 2 --Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 2 Supply, Single-Zone VAV, 4000 CFM, 5.0 motor nameplate hp, 0.95 fan energy index
SYSTEM VERIFICATION REQUIRED.
1 HVAC System
Split System Heat Pump
Heating Mode: Capacity = 32 kBtu/h,
Proposed Efficiency = 9.60 HSPF, Required Efficiency = 8.20 HSPF
Cooling Mode: Capacity = 30 kBtu/h,
Proposed Efficiency = 18.00 SEER, Required Efficiency: 14.00 SEER
SYSTEM VERIFICATION REQUIRED.
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 90.1 (2019) Standard requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Brendan Arnold-Mech Engineer 13Nc 5/03/2022
Name-Title Signature Date
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 1 of 10
in° COMcheck Software Version COMcheckWeb
Inspection Checklist
Energy Code: 90.1 (2019) Standard
Requirements: 81.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
6.4.4.2.1, calculations provide all information ❑Does Not
6.7.2 with which compliance can be Location on plans/spec: M1.0
[PR2]1 determined for the mechanical ['Not Observable
systems and equipment and ❑Not Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
4.2.5.2 Commissioning shall be performed as ❑Complies Requirement will be met.
[PR5]1 stated in Sections 5.9.2, 6.9.2, 7.9.2, ❑Does Not
8.9.2, 9.9.2, 10.9.2, 11.2(d), and ['Not Observable Location on plans/spec: M1.0
G1.2.1(c). Commissioning must utilize
ASHRAE/IES Standard 202 or other ❑Not Applicable
generally accepted engineering
standards acceptable to the building
official. FPT and verification
requirements for commissioning are
as stated in Section 4.2.5.1.
Commissioning shall document
compliance of the building systems,
controls, and building envelope with
required provisions of this standard.
Commissioning requirements shall be
incorporated into the construction
documents.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) I 3 Low Impact(Tier 3)
Project Title: Trader Joes -Tigard Report date: 05/03/22
Data filename: Page 2 of 10
Section
# Footing/ Foundation Inspection Complies? Comments/Assumptions
&Req.ID
6.4.3.7 Freeze protection and snow/ice ❑Complies Exception: Requirement does not apply.
[FO913 melting system sensors for future ❑Does Not
connection to controls.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) i 3 Low Impact(Tier 3)
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 3 of 10
Section Mechanical Rough-In Plans Verified Field Verified ,
# Inspection Value Value Complies. Comments/Assumptions
& Req.ID._
6.4.1.4, HVAC equipment efficiency Efficiency: Efficiency: ❑Complies See the Mechanical Systems list
6.4.1.5 verified. Non-NAECA HVAC ElDoes Not for values.
[ME1]2 equipment labeled as meeting
90.1. [Not Observable
❑Not Applicable
6.4.3.4.1 Stair and elevator shaft vents Complies Exception: Requirement
[ME3]3 have motorized dampers that ❑Does Not does not apply.
automatically close.
[Not Observable
❑Not Applicable
6.4.3.4.2, Outdoor air and exhaust systems ❑Complies Requirement will be met.
6.4.3.4.3 have motorized dampers that ElDoes Not
[ME4]3 automatically shut when not in ❑Not Observable Location on plans/spec:
use and meet maximum leakage M1.0
rates. Check gravity dampers ❑Not Applicable
where allowed.
6.4.3.4.5 Enclosed parking garage ❑Complies Exception: Requirement
[ME39]3 ventilation has automatic ❑Does Not does not apply.
contaminant detection and
capacity to stage or modulate El Not Observable
fans to 50%or less of design ❑Not Applicable
capacity.
6.4.3.4.4 Ventilation fans >0.75 hp have ❑Complies Requirement will be met.
[ME5]3 automatic controls to shut off fan ❑Does Not
when not required.
❑Not Observable
❑Not Applicable
6.4.3.8 Demand control ventilation ❑Complies Requirement will be met.
[ME6]1 provided for spaces >500 ft2 and EDoes Not
>25 people/1000 ft2 occupant
density and served by systems ❑Not Observable
with air side economizer, auto ❑Not Applicable
modulating outside air damper
control, or design airflow >3,000
cfm.
6.5.3.2.1 DX cooling systems >= 75 kBtu/h ❑Complies Requirement will be met.
[ME40]2 (>= 65 kBtu/h effective 1/2016) ❑Does Not
and chilled-water and See the Mechanical Systems list
evaporative cooling fan motor hp ❑Not Observable for values.
>= 1/4 designed to vary supply ❑Not Applicable
fan airflow as a function of load
and comply with operational
requirements.
6.4.4.1.1 Insulation exposed to weather ❑Complies Requirement will be met.
[ME7]3 protected from damage. ❑Does Not
Insulation outside of the
conditioned space and associated ❑Not Observable
with cooling systems is vapor ❑Not Applicable
retardant.
6.4.4.1.2 HVAC ducts and plenums R- R- ❑Complies Requirement will be met.
[ME8]2 insulated per Table 6.8.2. Where El Does Not
ducts or plenums are installed in
or under a slab, verification may ❑Not Observable
need to occur during Foundation ❑Not Applicable
Inspection.
6.4.4.1.3 HVAC piping insulation thickness. in. in. ❑Complies Location on plans/spec:
[ME9]2 Where piping is installed in or ❑Does Not NA
under a slab, verification may
need to occur during Foundation ['Not Observable
Inspection. ❑Not Applicable
6.4.4.1.4 Thermally ineffective panel ❑Complies Location on plans/spec:
[ME41]3 surfaces of sensible heating ❑Does Not NA
panels have insulation >= R-3.5.
['Not Observable❑Not Applicable
I 1 High Impact(Tier 1) 2 fMedium Impact (Tier 2) j 3 Low Impact(Tier 3)
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 4 of 10
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
& Req.lD_
6.4.4.2.1 Ducts and plenums having ❑Complies Requirement will be met.
[ME10]2 pressure class ratings are Seal ElDoes Not
Class A construction.
❑Not Observable
❑Not Applicable
6.8.1-15, Electrically operated DX-DOAS ❑Complies Requirement will be met.
6.8.1-16 units meet requirements per ElDoes Not
[ME110]2 Tables 6.8.1-15 or 6.8.1-16. ❑Not Observable Location on plans/spec:
M1.0
❑Not Applicable
6.4.4.2.2 Ductwork operating >3 in. water ❑Complies Exception: Requirement
[ME11]3 column requires air leakage ElDoes Not does not apply.
testing. ❑Not Observable
❑Not Applicable
6.4.4.2.2 Ductwork operating >3 in. water ❑Complies Exception: Requirement
[ME11]3 column requires air leakage ElDoes Not does not apply.
testing. ['Not Observable
❑Not Applicable
6.4.4.2.2 Ductwork operating >3 in. water ❑Complies Exception: Requirement
[ME11]3 column requires air leakage ❑Does Not does not apply.
testing. ❑Not Observable
❑Not Applicable
6.5.2.3 Dehumidification controls ❑Complies Requirement will be met.
[ME19]3 provided to prevent reheating, ElDoes Not
recooling, mixing of hot and cold
airstreams or concurrent heating ❑Not Observable
and cooling of the same ❑Not Applicable
airstream.
6.5.2.4.1 Humidifiers with airstream EComplies Location on plans/spec:
[ME68]3 mounted preheating jackets have ElDoes Not NA
preheat auto-shutoff value set to
activate when humidification is ❑Not Observable
not required. ❑Not Applicable
6.5.2.4.2 Humidification system dispersion ❑Complies Location on plans/spec:
[ME69]3 tube hot surfaces in the ❑Does Not NA
airstreams of ducts or air-
handling units insulated >= R ❑Not Observable
0.5. ❑Not Applicable
6.5.2.5 Preheat coils controlled to stop ElComplies Location on plans/spec:
[ME70]3 heat output whenever ElDoes Not NA
mechanical cooling, including
economizer operation, is active. ['Not Observable
❑Not Applicable
6.5.2.6 Units that provide ventilation air ❑Complies Location on plans/spec:
[ME10613 to multiple zones and operate in ❑Does Not NA
conjunction with zone heating
and cooling systems are ['Not Observable
prevented from using heating or ❑Not Applicable
heat recovery to warm supply air
above 60°F when representative
building loads or outdoor air
temperature indicate that most
zones demand cooling.
6.5.3.6 Motors for fans >= 1/12 hp and ❑Complies Requirement will be met.
[ME72]z < 1 hp are electronically- ElDoes Not
commutated motors or have a Location on plans/spec:
minimum motor efficiency of ❑Not Observable M1.0
70%.These motors are also ❑Not Applicable
speed adjustable for either
balancing or remote control.
1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact(Tier 3) 1
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 5 of 10
Section
Mechanical Rough-In Plans Verified Field Verified
Complies? Comments/Assumptions
& Re .ID Inspection Value Value
6.5.3.6 Motors for fans >= 1/12 hp and ❑Complies Requirement will be met.
[ME72]2 < 1 hp are electronically- ❑Does Not
commutated motors or have a Location on plans/spec:
minimum motor efficiency of ❑Not Observable M1.0
70%.These motors are also ❑Not Applicable
speed adjustable for either
balancing or remote control.
6.5.3.4 Parallel-flow fan-powered VAV air ❑Complies Exception: Requirement
[ME108]2 terminals have automatic ❑Does Not does not apply.
controls to a) turn off the
terminal fan except when space ❑Not Observable
heating is required or if required ❑Not Applicable
for ventilation; b)turn on the
terminal fan as the first stage of
heating before the heating coil is
activated; and c) during heating
for warmup or setback
temperature control, either
operate the terminal fan and
heating coil without primary air
or reverse the terminal damper
logic and provide heating from
the central air handler through
primary air.
6.5.3.4 Parallel-flow fan-powered VAV air ❑Complies Exception: Requirement
[ME108]2 terminals have automatic ❑Does Not does not apply.
controls to a) turn off the
terminal fan except when space ❑Not Observable
heating is required or if required ❑Not Applicable
for ventilation; b)turn on the
terminal fan as the first stage of
heating before the heating coil is
activated; and c) during heating
for warmup or setback
temperature control, either
operate the terminal fan and
heating coil without primary air
or reverse the terminal damper
logic and provide heating from
the central air handler through
primary air.
6.5.3.7 Required minimum outdoor air ❑Complies Requirement will be met.
[ME109]2 rate is the larger of minimum EDoes Not
outdoor air rate or minimum Location on plans/spec:
exhaust air rate required by ❑Not Observable M1.0
Standard 62.1, Standard 170, or ❑Not Applicable
applicable codes or accreditation
standards. Outdoor air ventilation
systems shall comply with one of
the following: a) design minimum
system outdoor air provided <
135%of the required minimum
outdoor air rate, b) dampers,
ductwork, and controls allow the
system to supply <= the
required minimum outdoor air
rate with a single set-point
adjustment., or c) system
includes exhaust air energy
recovery complying with Section
6.5.6.1.
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 7 3 Low Impact(Tier 3)
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 6 of 10
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
& Re ID
6.5.3.7 Required minimum outdoor air ❑Complies Requirement will be met.
[ME109]2 rate is the larger of minimum ElDoes Not
outdoor air rate or minimum Location on plans/spec:
exhaust air rate required by M1.0
Standard 62.1, Standard 170, or ❑Not Applicable
applicable codes or accreditation
standards. Outdoor air ventilation
systems shall comply with one of
the following: a) design minimum
system outdoor air provided <
135%of the required minimum
outdoor air rate, b) dampers,
ductwork, and controls allow the
system to supply <= the
required minimum outdoor air
rate with a single set-point
adjustment., or c) system
includes exhaust air energy
recovery complying with Section
6.5.6.1.
6.5.3.3 Multiple zone VAV systems with ❑Complies Exception: Requirement
[ME42]3 DDC of individual zone boxes ElDoes Not does not apply.
have static pressure setpoint
reset controls. ❑Not Observable See the Mechanical Systems list
❑Not Applicable for values.
6.5.3.3 Multiple zone VAV systems with ❑Complies Exception: Requirement
[ME42]3 DDC of individual zone boxes ❑Does Not does not apply.
have static pressure setpoint
reset controls. ❑Not Observable See the Mechanical Systems list
❑Not Applicable for values.
6.5.3.3 Multiple zone VAV systems with ❑Complies Exception: Requirement
[ME42]3 DDC of individual zone boxes ❑Does Not does not apply.
have static pressure setpoint
reset controls. ['Not Observable See the Mechanical Systems list
❑Not Applicable for values.
6.5.4.2 HVAC pumping systems with >= ❑Complies Location on plans/spec:
[ME25]3 3 control values designed for ElDoes Not NA
variable fluid flow (see section
details). ['Not Observable
❑Not Applicable
6.5.6.1.1 Exhaust Air Energy Recovery for ❑Complies Location on plans/spec:
[ME56]1 Nontransient Dwelling Units ❑Does Not NA
❑Not Observable
❑Not Applicable
6.5.6.1.2 Exhaust air energy recovery for ElComplies Exception: Requirements do
[ME111]1 spaces other than Nontransient ❑Does Not not apply.
dwelling units meeting Tables
6.5.6.1.2-1, and 6.5.6.1.2-2. Not Observable
❑Not Applicable
6.5.7.2.1 Kitchen hoods >5,000 cfm have ❑Complies Exception: Requirement
[ME32]2 make up air>=50%of exhaust ❑Does Not does not apply.
air volume.
❑Not Observable
❑Not Applicable
6.5.7.1 Conditioned supply air to space EComplies Requirement will be met.
[ME100]2 with mechanical exhaust <=the ❑Does Not
greater of criteria of supply flow, Location on plans/spec:
required ventilation rate, exhaust Not Observable M1.0
flow minu the available transffer ❑Not Applicable
air(see section details).
1 High Impact(Tier 1) , 2 'Medium Impact (Tier 2) 3'Low Impact(Tier 3)
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 7 of 10
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value
& Req.ID Complies? Comments/Assumptions
6.5.7.1 Conditioned supply air to space EComplies Exception: Spaces with
[ME100]2 with mechanical exhaust <= the ❑Does Not regulated positive pressure
greater of criteria of supply flow, air flows.
required ventilation rate, exhaust ❑Not Observable
flow minu the available transffer ❑Not Applicable Location on plans/spec:
air(see section details). M1.0
6.5.3.8 Occupied standy controls for ❑Complies Exception: Requirement
[ME112]1 zones serving rooms that are ❑Does Not does not apply.
required to have automatic
partial OFF or automatic full OFF ❑Not Observable
lighting controls per Section ElNot Applicable
9.4.1.1 shall meet the following
within five minutes of all rooms in
that zone entering occupied-
standby mode: a)Active heating
set point shall be setback at least
1°F, b)Active cooling set point
shall be setup at least 1°F and
c)All airflow supplied to the zone
shall be shut off whenever the
space temperature is between
the active heating and cooling
set points.
6.5.7.2.4 Approved field test used to ❑Complies Exception: Requirement
[ME49]3 evaluate design air flow rates ❑Does Not does not apply.
and demonstrate proper capture
and containment of kitchen ❑Not Observable
exhaust systems. ❑Not Applicable
6.5.8.1 Unenclosed spaces that are ElComplies Exception: Requirement
[ME34]2 heated use only radiant heat. ❑Does Not does not apply.
['Not Observable
❑Not Applicable
6.4.3.9 Heating for vestibules and air ❑Complies Exception: Requirement
[ME63]2 curtains with integral heating ❑Does Not does not apply.
include automatic controls that
shut off the heating system when ['Not Observable
outdoor air temperatures > 45F. ❑Not Applicable
Vestibule heating and cooling
systems controlled by a
thermostat in the vestibule with
heating setpoint <= 60F and
cooling setpoint>= 80F.
6.5.10 Doors separating conditioned ❑Complies Exception: Building
[ME73]3 space from the outdoors have ❑Does Not entrances have automatic
controls that disable/reset closing devices.
heating and cooling system when ElNot Observable
open. ❑Not Applicable
Additional Comments/Assumptions:
1 [High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 'Low Impact(Tier 3)
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 8 of 10
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
10.4.1 Electric motors meet requirements ❑Complies Requirement will be met,
[EL912 where applicable. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) j
Project Title: Trader Joes-Tigard Report date: 05/03/22
Data filename: Page 9 of 10
. . .
Section
# Final Inspection Complies? Comments/Assumptions
&LReq.11)
0.4.3.1.2 Thermostatic controls have 5 °F []complies Requirement will be met.
[F13]3 deadband. []Does Not
[]NotObsemab|e
Location mnp|ans/spec: Ml.O
[]NotApp|icab|e
6.4.3.2 Temperature controls have setpoint []complies Requirement will be met. ---�—�----� ��---��� �—
[F120]3 overlap restrictions. []Does Not
[]NotObsen/ab|e
[]NotApp|icab|e
h.4.].]�l HVA[systems equipped with at least LJComp|ies Requirement will be met.
[F121]3 one automatic shutdown control. []Does Not
[]Not Observable
[]NotApp|icab|e
�-- ��������
6.4]].2 Setback controls allow automatic LJComp|ies Requirement will bomet.
[F122]3 restart and temporary operation as []Does Not
required for maintenance.
[]wotObsen/ab|e
[]Not Applicable
�� ��
6.4.3.5 Heat pump controls prevent LJComp|ios Requirement will be met.
[F15]3 supplemental electric resistance heat []Does Not
from coming on when not needed.
[]Not Observable
[]Not�pp|icab|e
6.4.3.6 When humidification and LJ[omp|ies Requirement will be met.
[H6]3 dehumidification are provided'oa []Does Not
zone' simultaneous operation is
prohibited. Humidity control prohibits []Not0bsemab|e
the use nf fossil fuel or electricity to []NotApp|icab|e
produce RH > 30% in the warmest
zone humidified and K* < 00Y6inthe
co|destzonedehumidified�
_
6.7.2.1 Furnished HVA[as'bui|tdrawings LJ[omp|ies
[F17]3 submitted within 90 days of system []Does Not
acceptance.
[]NotObsen/ab|e
[]NotApp|icab|e
0.7.2.2 Furnished O&M manuals for HVAC LJComp|ies
[F|O], systems within 90 days of system []Does Not
acceptance.
[:]Not Observable
[]Notxpp|icab|e
0.7.2.3 An airand/orhydro�-system []Complies �------�-
[F19]1 balancing report is provided for HvAC []Does Not
systems serving zones >50OO�2of
' []motOb�emab|e
conditioned area.
[]NotApp|icab|e
zo.4.3�—�Elevators
- reuesioneuwitxme --[]comp||es Exception: Requirement does not apply. '--- �-
[p124]2 proper lighting, ventilation power, and []Does mot
standby mode.
[]mntobservab|e
[]mot Applicable
Additional Comments/Assumptions:
Ll_[Hi"h Impact(Tier l) -��Medium Impact(Tier Z) ] Low Impact(Tier]) |
Project Title: Trader/ues Tigard Report date: 05/03/22