Loading...
Report (2) -- OFFICE COPY RECEIVED ,� JUN 8 2022 U°9 CITY OF TIGARD -(� TARGET T-0345 BUILDING DIVISION Z�2 9009 SW Hall Blvd Tigard, OR 97223 Fire Protection Data BASIC FIRE PROTECTION, INC. 8135 NE MLK JR BLVD. PORTLAND, OREGON 97211 Table of Contents Fire Protection System Target Tigard Tigard,OR 1. Fire Protection Pipe and Fittings: a) Bullmoose: Schedule 10&40 b) Anvil: Cast iron c) Victaulic: Mechanical Tee 920 d) Victaulic: Firelock Fittings e) Victaulic: Couplings 005 fl FlexHead: Flexible Sprinkler Connections 2. Valves: a) Nibco: OS&Y gate valve flanged b) Nibco:OS&Y gate valve thread c) Victaulic:Butterfly valve 705 d) Victaulic: Check valve 717 e) Nibco:Check valve 3. Fire Pump Equipment a) GVI:Fire pump meter b) Ashcroft:Pressure gauges 4. Hangers: a) Cooper B-Line: Ring Hanger Fig.200 b) Cooper B-Line: Top Beam Clamp Fig.65 c) Cooper B-Line: Retaining Strap Fig.69 d) Cooper B-Line: Sway Brace Fig.4L e) Cooper B-Line: Sway Brace Fig.980 fl Hilti:Kwik Bolt TZ g) h) 5. Fire Sprinklers: a) Reliable:G Upright sprinkler Brass b) Reliable:G recessed chrome/chrome pendent c) Reliable:F I standard response sprinklers d) Reliable:F 1 FR quick response sprinklers e) Reliable:GLI 12 K11.2 sprinkler fl Tyco:EC-25 Upright Extended coverage g) Reliable:F3QR56 dry sprinkler h) i) 6. Misc.: a) Potter Roemer:FDC 6 way connection b) FPPI:Identification signs c) ,... ' ; °C)95- As the leading supplier of steel sprinkler pipe,we understand that there are no second chances in fire suppression. You need products of enduring quality and exceptional strength-plus reliable service.You need Bull Moose. Bull Moose Fire Sprinkler Pipe Product Information Nominal Pipe Size(Inches) 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6" 8" NPS(In.) 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 0.0.(in) 1.315 1.660 1.900 2.375 , 2.875 3.500 4.500 6.625 8.625 1.315 1.660 1.900 2.375 2.875 3.500 4.500 O I .(in) 1.097 1.442 1.682 2.157 2.635 3260 4.260 6.357 8.249 O 1.049 1.380 1.610 2.067 2.469 3.068 4.026 W Empty Weight(Ibift) 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940 W 1.680 2.270 2.720 3.660 5.800 7.580 10.800 Water Filled Weight(lb/ft) 1.820 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086 —I 2.055 2.918 3.602 5.114 7.875 10.703 16.316 Op C.R.R. 15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805 G 1.00 1.00 1.00 1.00 1.00 1.00 1.00 W Pieces per Lift 91 61 61 31 30 19 19 10 7 W 70 51 44 30 30 19 19 u Lift Weight(Ibs)21'lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490 ,, 2,470 2,431 2,513 2,306 3,654 3,024 4,309 I/1 Lift Weight(Ibs)24'lengths 3,079 2,650 3,060 2,344 2,542 1,979 2,563 2,230 2,848 N 2,822 2,778 2,872 2,635 4,176 3,456 4,925 Lift Weight(Ibs)25'lengths 3,208 2,760 3,187 2,442 2,648 2,052 2,670 2,940 2,894 2,992 2,745 4,350 3,601 5,130 t ar r f r'r r' l 1I' , in Ia, .0 ')I 1111 pi 1:ii,f, 11,Iqr,, r r,= , OTHER BENEFITS/SERVICES: • UL listed(US&Canada)and FM approved • We have the most stocking locations in the industry, • ASTM A135 and A795 Type E,Grade A Certified for best delivery and availability • Plain end or roll groove • Complies with NFPA-13,13R and 14 • Eddy Guard II' bacterial-resistant internal coating • Industry-leading hydraulic characteristics • Custom length options • CRR of 1.0 and greater • Hot dipped galvanization • All pipe NDT weld tested • Reddi-Pipe'red or black pipe eliminates field painting • Compatible for use in wet,dry, preaction and deluge sprinkler systems Exclusive maker of Reddi-Pipe® RED OR BCI(PAINTED PIPE. • The only maker with EPDs(to help earn LEED points). G liit c®us LISTED CEP.TIIIED # ✓ APPROVEDNFPA' "'""F'". •,.. ,~�....�.....« 14446 a � 4 ,800.325.44fi '' �: BULL ]�/[OOSE �sale a ooseTube.com� � � � / l Nv LStar" Anvil® Cast Iron Product - Submittal Sheet ((Z))ANVIL. Anvil® Cast Iron Threaded and Flanged Fittings ®® APPROVED AnvilStarTM offers the most complete line of Cast Iron and Malleable Iron Threaded Fittings in the industry. Our versatile range of fittings is designed to provide dependable, fire-rated service. Cast Iron Threaded Fittings, are manu- factured in accordance with ASME " 4 B16.4. They are UL listed and FM Approved and are available in sizes 1/4" NPS through 12" NPS. 114 416. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined Phone: undefined Architect/Engineer:undefined Contractor: undefined Address: undefined Notes 1: undefined Notes 2: undefined 3/05-100 For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule,go to www.anvilstar.com or contact your local AnvilStar representative ..... Cast Iron Flanged Fittings Class 125 (Standard) FIGURE 82S Unit Weight Size F Flanged Concentric Reducer Stack Galli. . , . . UPS ON UPS ON in mm Os kg Os kg 2 50 1'12 40 5 127 12.00 5.44 - - " '14 1'h 2V2 65 2 50 5 127 14.00 6.35 - - -... 1'1a 40 14.00 6.35 - - 3- I 80 2 50 65 6 152 16.00 726 - - 2'h 19.00 8.62 19.00 8.62 i 2 50 24.00 10.88 24.00 10.88 1 4 100 2°12 65 7 178 26.00 11.79_4 26.00 11,79 3 80 28.00 12.70 28.00 12.70 21/7 65 31.00 14.06 - - 5 125 3 80 8 203 32.00 14.51 - - 4 100 39,00 1769 - - 2 50 34.00 15.42 - - ... - 2'h 65 37.00 16 78 - - 6 150 3 80 9 229 39.00 17 69 - - 1..--4--•1 4 /00 5 125 47.00 2/.32 47.00 21.32, 50.00 22.68 - - 4 100 66.00 29.93 - - 8 XV 5 125 11 279 71.00 32.20 - - 6 150 77.00 34.92 77.00 34.92 4 /00 85.00 38.55 - 5 . - - 10 25 125 0 2 305 90.00 4 a 82 1 6 150 100.00 45.35 - - 8 200 120.00 54.42 - - 6 150 140.00 63.49 - - 12 300 8 200 14 356 155.00 70.29 - - 1 10 250 180.00 81.63 - - FIGURE 826 Unit Weight Size F Flanged Eccentric Reducer Stack Gatv, UPS ON UPS ON in mm lbs kg Ityk kg 2 50 16.00 7.26 - - 3 80 6 /52 21, 65 22,00 9,98 - - 2 50 28 00 12.70 - - ' .:,... 4 100 2'h 65 7 178 28.00 12.70 - - 3 80 28.00 12.70 - - , 5 125 4 100 8 203 39.00 17.69 - - 3 80 47.00 21.32 - - J1 6 150 4 100 9 229 50.00 22.68 50.00 22.68 5 /25 51 00 23.13 - - •--- 4 100 71.00 32.20 - - 8 200 5 125 11 279 76.00 34.47 - - -- 6 150 77.00 34.92 - - 10 250 12 305 6 /50 107 00 48.53 - - 1.•---F--01 8 200 120.00 54.42 - _ 8 12 300 200 14 356 155.00 70.29 - _ 10 250 180.00 81.63 - - $ot.s.,,e 0.?63 i54 10 eL'OP It'll pew or I 3+,1,,tic CARBON STEEL PIPE- HOLE CUT PRODUCTS Mechanical-T® Bolted Branch Outlets VdS LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLES 920 AND 920N Victaulic Mechanical-To Outlet provides a direct branch connection at any location a hole can be cut in pipe.The hole is cut oversize to receive a "holefinder" locating collar which secures the outlet in position permanently.A pressure responsive gasket seals on the pipe O.D. Cross-type connections can be achieved by utilizing two upper housings of the same style and size,with the same or differing branch size connections. NOTE:Style 920 and Style 920N housings cannot be mated to each other to achieve a cross connection. Style 920 and Style 920N Mechanical-T outlets are available with grooved or female threaded STYLES 920 AND 920N STYLE 920 CROSS outlet.Specify choice on order. Units are supplied painted with plated bolts. Galvanized hous- PATENTED ings are available,supplied with plated bolts. All sizes of Style 920 and 920N are rated at 500 psi/3450 kPa working pressure on Schedule 10 and 40 carbon steel pipe.They may also be used on high density polyethylene or poly- butylene(HDPE)pipe. Pressure ratings on HDPE are dependent on the pipe rating.Contact Victaulic for ratings on other pipe.Style 920 and 920N are not recommended for use on PVC plastic pipe. Standard piping practices dictate that the Mechanical-T Styles 920 and 920N must be installed so that the main and branch connections are a true 90°angle when permanently attached to the pipeline surface. Additionally,the Vic-Tap Ile hole cutting tool,which allows for hole cutting capabilities on pressurized systems,utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic-Ball Valve to create the Style 931 Vic-Tap II Mechanical-T unit.See page 8 for further information. MATERIAL SPECIFICATIONS Housing/Coating: Ductile iron conforming to ASTM A-536,grade 65-45-12,with orange enamel coating. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. • Optional: Hot dipped galvanized Gasket: (Specify choice*) • Grade"E" EPDM EPDM(Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect_ Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.02018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictaulac* REV 0 11.02 1 CARBON STEEL PIPE- HOLE CUT PRODUCTS 1 1.UL Mechanical-I® Bolted Branch Outlets STYLES 920 AND 920N • DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Branch Hole V t It V t Female Nominal Size 920 Diameter T** Thd. Gm. W Y Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. Y > 1.4 Z > mm 920N kPa _•0_00 mm mm mm mm mm mm kg kg MINI 2 x 1/2(a)° 920N 500 1.50 2.00 2.53 _ 1.61 5.35 2.75 3.1 /� 50 15 3450 38.1 51 64 41 136 70 1.5 lil ^ nu '' 1 i 1(a)' 920N 500 1.50 1.97 2.53 _ 1.61 5.35 2.75 3.1 20 3450 38.1 50 64 41 136 70 1.5 40 u 1(a)A 920N 500 1.50 1.85 2.53 1.61 5.35 2.75 3.0 1VI 25 3450 38.1 47 64 41 36 70 1.4 1 Y(a)to 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2 GROOVED OUTLET 32 3450 44.5 52 70 76 41 136 76 1.7 1.5 1 Yz(a)1" 920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.2 40 3450 44.5 52 70 79 41 136 83 1.7 1.5 = Y > a Z N 2'h x 1/2(a)§U 500 1.50 2.21 2.74 _ 1.82 5.64 2.75 3.0 _ 65 15 4 Y > 4 Z 920N1 3450 38.1 56 70 46 143 70 1.4 i PI1a(1)§s 920N 500 1.50 2.18 2.74 1.82 5.64 2.75 3.0 _ _ -. T 20 3450 381 55 70 46 143 70 1.4 A61 �1 MI, T 1(a)§0 920N 500 1.50 2.06 2.74 1.82 5.64 2.75 2.9 i 1l =4- 25 3450 38.1 52 70 46 143 70 1.4 �� 1,/t(a)'3 500 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.2 y 32 3450 44.5 58 76 83 46 160 76 1.7 1.5 t(a) 920N 500 2.00 2.28 3.00 3.25 1.82 6.26 3.25 3.6 3.3 FEMALE THREADED OUTLET P/z 40 _ 3450 50.8 58 76 83 46 159 83 1.7 1.6 76.1 x 1/2(a) 920N 300 1.50 2.22 2.75 2.25 6.46 3.18 3.9 15 2065 38.1 : 56 70 57 164 81 1.8 • Provides a direct branch connection at '/,(a)` 920N 300 1.50 2.19 2.75 2.25 6.46 3.18 3.9 any location where a hole can be cut 20 2065 38.1 56 70 57 164 81 1.8 in the pipe 1(a) 920N 300 1.50 2.07 2.75 2.25 6.46 3.18 3.8 25 2065 38.1 53 70 57 164 81 1.7 • A pressure responsive gasket provides 1 Ya(a)o j 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2 the seal 32 3450 44.5 58 76 84 49 160 76 1.6 !. 1.5 111/2(a)a 920N 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3 • Request Publication 11.03 for 40 j 3450 50.8 58 76 84 49 160 83 1.6 1.5 Mechanical-T cross assemblies 3 x 1/2(a)o 920N 500 1.50 2.52 3.05 _ 2.28 6.15 2.75 3.4 80 15 3450 38.1 64 78 58 156 70 1.6 • Pressure rated up to 500 psi/3450 kPa /(a)a 920N 500 1.50 2.49 3.05 2.28 6.15 2.75 3.4 on steel pipe; also available for use 20 3450 38.1 63 78 58 156 70 1.6 with HDPE pipe 1 (a) 920N 500 1.50 2.38 3.06 _ 2.28 6.15 2.75 3.3 25 { 3450 38.1 61 78 58 156 70 1.6 • Sizes from 2 x 12750 x 15 mm 1 Yu(a)tal 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.7 through 8 x 4"/200 x 100mm 32(b) I 3450 44.5 65 83 90 58 156 76 1.8 1.8 11/2(a)to 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8 40(b) I 3450 50.8 71 89 90 58 156 83 1.9 1.8 2(a)a 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6 50 3450 63.5 70 89 90 58 172 99 2.3 2.1 3/z x 2 920N 500 2.50 3.00 1 3.75 2.44 6.72 3.88 1 3.8 90 50 3450 63.5 76 95 62 171 99 1.8 IMPORTANT NOTES: TABLE CONTINUED ON PG.3 Style 920 and Style 920N housings cannot be **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). mated to one another t Available with grooved or female threaded outlet.Specify choice on order. to achieve cross connections. t Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 2'/z"BSPT clearly on order. §Vds approved for fire protection services a LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.(0 2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jCtaUlled' 11-02 2 ri(V () CARBON STEEL PIPE- HOLE CUT PRODUCTS 11.VL Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Branch Hole V#N V# Female Nominal Size 920 Diameter T*' Thd. Grv. W Y Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs. < Y > Z--► mm 920N kPa -0.00 mm mm mm mm mm mm kg kg _ 1 ^ TABLE CONTINUED FROM PAGE 2 4 , 4 /z(a)o i 500 1.50 3.03 3.56 2.69 7.01 2.75 3.7 V g 100 x 15 920N 3450 38.1 77 90 68 178 70 1.8 1i1, ^ Iiu I 111 11 l --.,-.�. - - 3/4(a)n 920N 500 1.50 3.00 3.56 2.69 7.01 2.75 3.7 _20 3450 38 76 90 68 78 70 1.8 y v t(a)n 920N 5001.50 2.88 3.56 2.69 7.01 2.75 3.6 l--1 25 3450 38.1 73 90 68 178 70 1.8 GROOVED OUTLET 1 Ya(a)to 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6 32(b) 3450 44.5 78 96 102 68 178 76 1.9 1.8 1/z(a)to 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9 40(b) 3450 50.8 83 102 102 68 178 83 2.0 1.9 ri Y > 44Z-1 2(a)to 920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6 t 1 PR _ 50 3450 63.5 83 102 102 68 178 99 2.3 2.1 V /'�,4111,1181 I 2'h(a)t 920 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0 65 3450 69.9 73 102 102 68 186 118 2.6 2.3 76.1 mm 920 500 2.75 2.88 _ 4.00 2.69 7.34 4.63 _ 6.4 I I 3450 69.9 73 102 68 86 18 2.9 l� 3(a)t 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4 80 920 3450 88.9 84 114 105 68 196 130 3.8 2.9 1 + FEMALE THREADED OUTLET 11/4(a)II 500 1.75 3.08 3.78 2.63 7.64 3.05 5.0 108.0 x 32 920N 3450 44.5 78 96 67 194 78 2.3 1 k(a)o 1 920N 500 2.00 3.28 4.00 2.63 7.64 3.25 5.0 • Provides a direct branch connection at _ 40 3450 50.8 83 102 67 194 83 2.3 any location where a hole can be cut 2(a) 920N 500 2.50 3.25 4.00 _ 2.63 7.64 4.00 4.0 in the pipe 50 3450 63.5 83 102 67 194 102 1.9 76.1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 7.8 • A pressure responsive gasket provides _ 3450 69.9 73 102 102 67 194 109 3.6 3.5 the seal 3(a) 920 500 3.50 3.31 4.50 4.50 2.63 7.63 4.88 6.8 6.5 80 3450 88.9 84 114 114 67 194 124 3.1 3.0 • Request Publication 11.03 for 5 1 Yz(a)t 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.6 Mechanical-T cross assemblies 125 x 40 920 3450 50.8 102 121 121 80 246 94 3.4 3.4 2(a)t 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0 PPP • Pressure rated up to 500 psi/3450 kPa 50 920 3450 63.5 102 121 121 80 246 111 3.7 3.6 on steel pipe; also available for use 21/2(a)t 920 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9 with HDPE pipe -6s _ 3450 69.9 92 121 121 80 246 118 3.8 3.6 76.1 mm o 920 500 2.75 3.75 4.75 3.16 9.70 4.63 8.0 • Sizes from 2 x 1/2"/50 x 15mm 3450 69.9 95 - 121 80 246 118 - 3.6 through 8 x 4"/200 x 100mm 3(a)t 920 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8 80 3450 88.9 97 127 118 80 246 135 3.8 4.0 2 500 2.50 3.75 4.50 _ 3.17 8.00 3.88 8.01 - 33.0 x 50 920N 3450 63.5 95 114 81 203 99 3.6 3�_ 500 3.50 3.81 5.00 3.00 9.46 5.31 8.0 80 920 3450 88.9 97 127 76 . 240 135 3.6 TABLE CONTINUED ON PG.4 IMPORTANT NOTES: **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). Style 920 and Style 920N housings cannot be t Available with grooved or female threaded outlet.Specify choice on order. mated to one another t Center of run to end of fitting. to achieve cross connections. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 21/2'BSPT clearly on order. §Vds approved for fire protection services n LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. ri • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.(02018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. Cf.'dUI1C CARBON STEEL PIPE-HOLE CUT PRODUCTS 1 1•UL Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Style Max.Work Approx. Size No. Pressure@ Dimensions Weight Each Run x Branch Hole V f# V# Female Nominal Size 920 Diameter T** Thd. Grv. W Y Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches_Inches Inches Lbs. Lbs. r Y I. < Z > mm 920N kPa -0.00 mm mm mm, tom mm mm kg 'kg, - ' 1 / TABLE CONTINUED FROM PAGE 3 7•� 5 139.7 x 1/'t 920N 500 2.00 3.78 4.50 3.30 8.23 3.25 7.0 V 40 3450 50.8 96 114 84 209 83 3.2 sae40...k r Phi 2 t 920N 500 2.50 3.75 4.50 3.30 8.23 3.88 9.0 50 3450 63.5 95 114 84 209 99 4.1 y v 6 1 Yn(a) 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 5.1 4.8 1� 50 x 32(b) 920N 3450 44.5 112 130 130 96 232 83 2.3 2.2 GROOVED OUTLET 1'Y2(a)to 920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 5.1 40(b) 3450 50.8 112 130 130 96 232 83 2.4 2.3 2(a)to 920N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6 50 3450 63.5 111 130 130 96 232 99 2.7 2.5 Y x ri Z --_--- 2'h 920 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.6 t PR 65 3450 69.9 110 130 130 94 267 118 3.8 3.4 V _ 500 2.75 4.15 5.21 3.69 10.51 4.63 _ 8.4 it �� sic T rlal I 761 mm° 920 3450 69.9 105 32 94 267 118 3.8 F>- -1�- 3(a)t 920 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.4 W 80 3450 88.9 110 140 130 94 267 135 4.5 3.8 Li 4(a)to 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1 100 920 3450 114.3 97 146 137 94 267 159 4.6 4.6 _ FEMALE THREADED OUTLET 159.0 x 1/'(a) 920N 500 2.00 4.41 5.13 3.63 9.40 3.25 7.8 40 3450 50.8 112 130 92 239 83 3.5 2(a) 920N 500 2.50 4.38 5.13 _ 3.63 9.40 3.88 8.0 • Provides a direct branch connection at _ 50 3450 63.5 111 130 92 239 99 3.6 any location where a hole can be cut 76.1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 9.5 In the pipe 3450 69.9 111 140 130 92 239 118 4.3 4.3 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.0 • A pressure responsive gasket provides 80 920 3450 889 110 140 130 92 239 135 3.7 6.4 the seal 108.0mm 920 500 4.50 4.45 _ 5.38 3.63 9.40 6.12 10.0 3450 114.3 113 137 92 239 155 4.5 • Request Publication 11.03 for 4 500 : 4.50 3.81 5.75 3.63 9.40 6.25 8.0 Mechanical-T cross assemblies 100 920 3450 114.3 96.80 146 92 239 159 8.2 TABLE CONTINUED ON PG.5 • Pressure rated up to 500 psi/3450 kPa **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). on steel pipe; also available for use t Available with grooved or female threaded outlet.Specify choice on order. with HDPE pipe # Center of run to end of fitting. • Sizes from 2 x 1/2'Y50 x 15mm # Female threaded outlets are available to NPT and BSPT specifications. through 8 x 47200 x 100 mm @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 2/2"BSPT clearly on order. §Vds approved for fire protection services n LPCB approved for fire protection services IMPORTANT NOTES: 0 Approved for use in China by Tianjin Approvals Company. Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �C1.aUI1C® 11.022 FRi_'V0 CARBON STEEL PIPE- HOLE CUT PRODUCTS J. 1.V L Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N • DIMENSIONS 1 I Style !Max.Work, Approx. Size No. •Pressure('I Dimensions Weight Each Run x Branch Hole V$k V± Female Nominal Size 920 Diameter T** Thd. Grv. W Y Z Thd. Grv. Inches or psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs.ii < Y x' < Z > mm 920N kPa -0.00 mm mm mm mm mm mm kg kg 31 NMTABLE CONTINUED FROM PAGE 4 li�� 1 500 1.50 3.88 4.56 _ 3.79 9.34 2.75 8.0 _ v `i 165.1 x 25 920N 3450 38.1 99 116 96 237 70 3.6 n. 132 920N 500 1.75 4.43 5.13 _ 3.79 9.34 3.25 8.4 ._-olio , , 3 3450 44.5 113 30 96 237 83 3.8 111 Piz(a)to 500 2.00 4.41 5.13 5.13 3.79 9.34 3.25 8.4 5.4 iiilsf +. IVI 40 920N 3450 50.8 112 130 130 96 237 83 3.8 2.4 GROOVED OUTLET 2(a)t 1 920N 500 2.50 4.38 5.13 5.13 3.79 9.34 3.88 8.5 6.0 50 I 3450 63.5 111 130 130 96 237 99 3.9 2.7 76.1 mm 920)13450500 69.92.75 1104.01 5.13 130 1325.21 923.63 26710.51 1184.63 83..96 3.47.6 Y E-Z--- 3(a)t 0 920 500 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4 t 80 3450 88.9 110 140 130 92 267 135 4.6 3.8 v del liu 4(a)to 920 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4 T �1I 100 3450 114.3 97 146 137 92 267 159 4.8 3.8 4111 8 x 2(a)t 920 500 2.75 5.44 6.19 6.25 4.81 12.42 4.50 11.6 11.6 �_ w I v I 200 50 3450 69.9 138 157 159 122 316 114 5.3 5.3 l-l 2h(a)t i 500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6 65 920 3450 69.9 129 157 157 122 316 114 5.3 5.3 FEMALE THREADED OUTLET ""'" 76.1 mm of 920 500 2.75 5.25 6.25 4.81 12.42 4.56 _ 11.6 i 3450 69.9 133 159 122 316 116 5.3 3(a)to 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 11.6 • Provides a direct branch connection at 80 920 3450 88.9 135 165 165 122 316 135 5.7 5.3 any location where a hole can be cut 4(a)to i 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5 In the pipe 100 j 3450 114.3 122 171 162 122 316 159 6.9 5.7 **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). • A pressure responsive gasket provides t Available with grooved or female threaded outlet.Specify choice on order. the seal # Center of run to end of fitting. • Request Publication 11.03 for # Female threaded outlets are available to NPT and BSPT specifications. Mechanical-T cross assemblies @ See page 7 for Fire Protection approvals and pressure ratings: • Pressure rated up to 500 psi/3450 kPa (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. On steel pipe; also available for use (b)For 76.1 mm threaded outlet,specify 2/2"BSPT clearly on order. with HDPE pipe §Vds approved for fire protection services o LPCB approved for fire protection services • Sizes from 2 x 1/z"/50 x 15 mm 0 Approved for use in China by Tianjin Approvals Company. through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections. kwww.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. i-..--- I-, FireLock° Fittings jetaulid 10.03 Material Specifications: Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Fitting Coating: ❑ Orange enamel ❑ Red enamel in Europe, Middle East, Africa, and India ❑ Optional: Hot dipped galvanized Approvals/Listings: Otis ® vds 2r LISTED Product Description: FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees feature CAD- developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I FireLock® Fittings I Publication 10.03 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. 1 ictaulic victaulic.com I FireLock° Fittings I Publication 10.03 . Dimensions: . k-CtoE1 ,� c -"o i to..j p CtoE o b to f oj- to E NO. 001 NO. 003 NO. 002 No. 006 g No.001 No.003 No.002 No.006 90°Elbow 45° Elbow Straight Tee Cap Actual Approx. Approx. , Approx. Approx. Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each C to E Each inches inches inches Lbs. 1 inches Lbs. inches Lbs. inches Lbs. mm mm mm kg i mm kg mm kg mm kg 1'/a 1.660 _ _ j - - - 0.82 0.3 32 42.4 l 21 0.1 11/2 1.900 - - - - _ 0.82 0.4 40 48.3 - - I - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 1 51 0.8 70 1.1 22 0.3 21/2 2.875 3.00 3.1 I 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 i 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 3.00 3.8 - - 76.1 76 1.5 57 1.1 76.2 1.7 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 I 22 0.5 108mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - - 4 108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 139.7 mm 5.500 4.88 12.4 3.25 8.2 4.88 15.4 - - 139.7 124.0 5.6 82.6 3.7 124.0 6.9 159mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 - - 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 165.1 mm 6.500 5.43 17.6 3.50 11.4 5.50 22.0 - _ 165.1 139.7 7.9 88.9 5.2 139.7 9.9 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 I 5.8 ry 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com I FireLock® Fittings I Publication 10.03 Flow Data: Frictional Resistance Actual Equivalent Feet/meters of Straight Pipe' Nominal Outside No.002 Size Diameter Elbows j Straight Tee inches inches No.001 I No.003 I mm mm 90°Elbow 45°Elbow Branch Run 11/4 1.660 - - - - 32 42.4 - - - - 1Y 1.900 - - - - 40 48.3 - - - - 2 2.375 3.5 1.8 8.5 3.5 50 60.3 _ 1.1 0.5 2.6 1.1 -21/2 w2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 _ 108mm 4.250 6.4 3.2 - 15.3 6.4 108.0 2.0 -_- 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 139.7 mm 5.500 8.3 4.1 20.6 8.3 139.7 2.5 1.3 6.3 2.5 159mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 _7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 165.1 mm 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 ' The flow data listed is based upon the pressure drop of Schedule 40 pipe. General Notes: NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N/009H couplings, use FireLock No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ictaulic. • n vw..R I..5ra.r ...vulm r5 Style 005H ✓ctaulicm with Vic-Plus' Gasket System 10.02 Material Specifications: ,.... a .4 0 4 ���r>liTill Housing: Ductile iron conforming to ASTM A-536, grade ■► 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Patented Exaggerated for clarity Housing Coating: (specify choice) ticPitt6' Standard: Orange enamel (North America); red et System enamel (Europe) -- --- ❑ Optional: Hot dipped galvanized Approvals/Listings: O ® LPCB Coupling Gasket: (specify choice) C US (VdS) LISTED NOTE:Additional gasket styles are available.Contact Victaulic for details. 104-1a/02 See Victaulic Publication 10.01 for more details. ❑ Grade "E" EPDM Type A Vic-PIusTM Gasket System' LPC and VdS Approved,see notes on page 3 EPDM (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved — - by Factory Mutual Research for wet and dry(oil free air) Product Description: sprinkler services up to the rated working pressure using the Grade "E"Type A Vic-Plus'° Gasket System, requiring no field FireLock Style 005H rigid coupling has a unique, lubrication for most installation conditions. patented angle-pad design which allows the housings ❑ Grade "L" silicone to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads, rigidity is Recommended for dry heat, air without hydrocarbons to obtained. +350°F and certain chemical services. Support and hanging requirements correspond to For dry services, Victaulic continues to recommend the NFPA 13 Sprinkler Systems. Angle-pad design permits use of Grade "E" Type A FlushSeal®Gasket. assembly by removing one nut/bolt and swinging the Contact Victaulic for details. housing over the gasket. This reduces components to handle during assembly. Bolts/Nuts: Heat-treated plated carbon steel, trackhead Style 005H FireLock coupling are designed and meeting the physical and chemical requirements of recommended for use ONLY on fire protection systems. ASTM A-449 and physical requirements of ASTM A-183. ' Standard gasket and FlushSeal gasket approved for dry pipe systems to Vic-Plus" Gasket System: —40°F/-40°C.Based on"typical"pipe surface conditions,supplemental lubricant is recommended for services installed below 0°F/-18°C and Victaulic offers a gasket system which requires no field for all dry pipe systems or systems to be subjected to air tests prior to lubrication on wet pipe systems that are hydrostatically being filled with water.Supplemental lubrication may also be required on tested. The Vic-Plus System (patented) is dry, clean, pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams.Victaulic continues to recommend the use of and non-toxic. It reduces assembly time substantially FlushSeal gaskets for dry services. and eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (1-100) for supplemental lubrication requirements and dry pipe fire protection system notes. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Couplings I Rigid I Style 005H I Publication 10.02 10.02 1538 Rev M Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctaulic° . victaulic.com I Couplings I Rigid I Style 005H I Publication 10.02 Dimensions: v > <-z1 Rated for wet and dry sprinkler systems at 350 psi/2413 kPa ��i V4for 1 1/4-4/32- 100 mm sizes and 300 psi/2068 kPa for r)ille 4 -8'/108-200 mm sizes; Schedule 10 roll grooved or M `1f 0 , v/ Schedule 40 cut or roll grooved steel pipe. Style 005H is rigid `40 .... `�� and does not accommodate expansion,contraction or angular deflection. Actual I Maximum Maximum Allow. Approx. Nominal Outside ' Working End Pipe End _ Dimensions -- Weight Size Diameter Pressure14 Load' Separation2 Bolt/Nut3 X Y Z Each inches inches I psi lbs. inches No.-size inches inches inches lbs. mm mm kPa N mm inches mm mm mm kg 1'A 1.660 350 755 0.05 2.75 4.50 1.88 1.2 32 42.4 2413 3370 1.2 2 3/e x 2'/4 70 114 48 0.5 1'/z 1.900 350 990 0.05 3.00 4.75 1.88 1.2 40 48.3 2413 4415 1.2 2 3/8 x 2'/4 76 121 48 0.5 2 2.375 350 1550 0.07 3.50 5.25 1.88 1.6 50 60.3 2413 6900 1.7 2-3/e x 2'/2 89 133 48 0.7 2 1 2.875 350 2270 0.07 4.00 5.75 1.88 1.9 65 73.0 2413 10110 1.7 2 ;/e x 21/2 102 146 48 .09 3.000 350 2475 0.07 4.13 5.75 1.88 1.9 76.1 mm 76.1 2413 11010 1.7 2-3/a x 2'/z 105 146 48 0.9 3 3.500 350 3365 0.07 4.63 6.13 1.88 2.1 80 88.9 2413 14985 1.7 2 3/e x 21/2 118 156 48 1.0 4 --� 4.500 350 5565 0.16 �-�- --� 5.75 7.25 2.13 3.1 100 114.3 2413 24770 4.1 2-3/e x 2/' 146 184 54 1.4 4.250 300 4255 0.16 5.63 7.25 2.13 3.1 108.0 mm 108.0 2068 18940 4.1 2 3/e x 2'/Z 143 184 54 _ 1.4 5 5.563 300 7290 0.16 _ 6.88 9.00 2.13 4.5 125 141.3 2068 32445 4.1 2 Y:x 3 175 229 54 2.0 5.250 300 6495 0.16 6.63 9.00 2.13 4.5 133.0 mm 133.0 2068 28900 4.1 2 Y2 x 23/4 168 229 54 2.0 5.500 300 7125 0.16 6.88 9.00 2.13 4.8 139.7 mm _139.7 2068 31715 4.1 2 Y'x 23/4 175 229 54 2.2 6 6.625 300 10340 0.16 8.00 10.00 2.13 5.0 150 168.3 2068 46020 4.1 2 1/2 x 3 203 254 53 2.3 6.250 300 9200 0.16 7.63 10.00 2.13 5.5 159.0 mm 159.0 2068 40955 4.1 2 '/z x 23/a 194 254 54 2.5 6.500 300 9955 0.16 8.15 10.00 2.13 5.5 165.1 mm _165.1 2068 44295 4.1 2 '/Z x 3 207 254 54 2.5 8 8.625 300 17525 0.19 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 2-5/8 x 4'/4 267 334 67 5.1 1 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1/times the figures shown. 2 The allowable pipe separation dimension shown is for system layout purposes only.Style 005H couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 3 Number of bolts required equals number of housing segments.Metric thread size bolts are available(color coded gold)for all coupling sizes upon request. Contact Victaulic for details. 4 Style 005H couplings are VdS and LPC Approved to 16 Bar/235 psi. 10.02 1538 Rev M Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ictaulic' victaulic.com I Couplings I Rigid I Style 005H I Publication 10.02 Listings/Approvals: The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Related Working Pressure Related Working Pressure Related Working Pressure psi psi psi Pipe 1- Size Pipe Size Pipe Size Sch. inches UL ULC FM Sch. inches UL ULC FM Sch. inches UL ULC FM 175 175 175 EL 1'/a—2 300 N/A N/A MT 11/4—2 300 N/A N/A 1/a 3 350 350 350 ET 114—2 300 N/A N/A STF 11/4—4 N/A N/A 300 10,40 5—8 300 300 300 EZ 4—6 3006 N/A 300 Steady 1 Y—2 N/A N/A 300 Thd. BLT 11/4—2 300 300 N/A FF 1'/a—4 N/A N/A 300 TF 3—8 N/A N/A 300 DF P/n—4 300 300 300 GAL 7 1'/a—2 300 N/A N/A WLS 1'/a—2 300 300 N/A DT 1'/a 2 300 300 N/A MLT 1'/a—2 300 N/A N/A XL 11/4—3 300 300 300 EF 11'/a—4 1757 N/A 175 MF 1'/a—4 300 N/A I 3005 j 5 FM approved for service in 1 1/2—4"pipe. 6 UL Listed for service up to 4"pipe only. 7 UL Listed for service up to 3"only. 1 1 ii 1 s i i r! 7 'i Installation Note r Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products + the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard Ion our website at www.victaulic.com. equipment without notice and without incurring obligations. 1 Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic°is a registered trademark of Victaulic Company. 1 10.02 1538 Rev M Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 Jctaulic FLEXHEAD Flexible Sprinkler Connections (' ) STANDARD TALL SERIES HOSE Unlike traditional hard-piped fire protection systems ±fs�" k�T� 13 / FlexHead° sprinkler connections allow engineers, �x architects, contractors and building owners a degree of versatility reviousl unavailable, featuring: • Industrial grade material • Acceptable for use in a return-air plenum STANDARD TALL HOSE:available in 24", 36 48", 60 72 hose lengths. • Perfect center-of-tile and aesthetic uniformity Rated working pressure 175psi, Straight model, Standard 1"I.D. • Approved for use with medium and heavy load grids (ASTM C635, 636) • 1 00% leak-tested connections • All welded, no o-rings • Adjustable height and sprinkler alignment • Proven technology • Ceiling system compatibility STANDARD ELBOW TALL HOSE: 24' 36", 48", 60 72' hose lengths • Compatible with FM / UL sprinklers Rated working pressure 175psi, Elbow model. • Meets 2013 NFPA 13 guidelines • UL Approved for installation in dry wall ceiling grids APPROVED 113 FLEXHEAD SUSPENDED CEILING DETAIL The benefits of installing FlexHead Commercial Connections include: • Uniform bids / construction schedules • Reduced man power and labor costs • Retrofit existing buildings within confined spaces quickly and easily • Increased efficiency • Quick and easy installation • Simple friction loss / water pressure calculations FLEXHEAD SHEETROCK CEILING DETAIL • Relocate and reconfigure without draining and disassembling • Flexible design provides versatility for changes in floor plan or occupancy • Reduced service calls • No call-backs due to quality manufacturing • Rapid construction schedules allowing fast-track __ building occupancy PROJECT INFORMATION APPROVAL STAMP Project: El Approved Address: ❑Approved as noted Contractor: ['Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: FP-8.18 FLEXHEAD® Flexible Sprinkler Connections fr)AM/IL STANDARD TALL SERIES HOSE 20XXT(STRAIGHT) L±20mm ,7` 6.3 18) / 3 [159] TYP 304SS SCH 40 PIPES [26.2] I ' Il/ltlltllNNllllllNlltllltltltlllllltltl stIm llll IItIt1111NllltltlltUM, 1111111111111111111111111111111111111111111Illlllllllltllllllllflft111ft111HH 1 p 1.31 1111111111111111111111111111111111►1111111 IIIHlllllllll�lllllllllfl►111111►1111 HlHlllllllllllllllf lllllllllllllllllllllll►11111111►1 IIIIIIIII II IIIIIIIIIHII [33.40] ; 5 5 s �1�1�1l1�►11�►11111►►If►�Ifllf►If►111►Iflllf►ll►llf►AIlf►11►11►11►111►11►►Iff►1►111►llflll►ll►►If►►11►If1�►►111►111►11►11f►I1f►11t11►11►►11►I1f►1�1111►�1 i t //// uum uuuuuuuuuuuuuu meemw ee uuuwu uuum u rr `-OUTLET SIZE I"NPT THREADS SEE CHART TO ANSI 81.20.1 MODEL NUMBER: 20XXT-XX I =50(1/2"NPT OUTLET SIZE) OR 75(3/4"NPT OUTLET SIZE) -=TALL SERIES HOSE All dimensions are in inches -=HOSE LENGTH(24",k¢",5'",Q",OR L") FLEXHEAD STANDARD TALL HOSE SERIES - 111 INTERNAL DIAMETER (I.D.) HOSE SERIES Hose Minimum Max.Number Equivalent Length of 1 in.Schedule 40 Pipe(Ft.) Max.Rated Model Outlet Assembly Braid Bend Radius of 90°Bends q g p Working Pressure Number Orifice Length Length FM Size (L) (B) FM UL FM UL UL FM UL 5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor In./rm. In./mm. In./mm. In./mm. In./mm. In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Film. Ft./m. PSI/Kpa PSI/Kpa 24 14.7 11 18.4 7.7 7.6 2024T 50 610 373.4 1 3 3.4 5.6 2.3 2.3 36 26.7 16 26.6 11.5 11.5 2036T50 9)4 678.2 2 3 4.9 8.1 3.5 3.5 20481-50 1/2 48 38.7 8 3 3 4 24 30.3 15.3 15.3 - 175 175 1.27 1219 983.0 200 76.2 7.3 9.2 4.6 4.7 1205 1205 2060T 50 60 50.7 4 4 29 35.8 19.1 19.3 - - 1524 1287.8 8.8 10.9 5.8 5.8 72 62.7 35 45.6 23 23.2 2072T-50 1828 1592.E 4 4 10.1 13.9 7 7 - 20241-75 24 14.7 1 3 12 N/A 14.7 7.1 670 373.4 3.7 4.5 2.1 36 26.7 18 21.5 21.6 21.8 10.9 2036T 75 914 678.2 2 3 5.5 N/A 6.5 6.6 6.6 3.3 2048115 3/4 48 38.7 8 3 3 4 23 N/A 30.5 30.6 29 14.8 175 175 1.90 1219 983.0 200 76.2 7.0 9.3 9.3 8.8 4.5 60 50.7 29 39.5 39.6 36.1 18.7 2060T 15 1524 1287.8 4 4 8.8 N/A 12 12 11 5.6 20721 75 72 62.7 4 4 32 N/A 48.5 48.8 43.2 22.6 1828 1592.6 9 8 14.7 14.9 13.1 6.8 Model Numbers:The"T"designates Tall Series Hose.The"50"designates 1/2"Outlet Hose Series.The"75"designates'/"Outlet Hose Series. Equivalent Lengths are shown with maximum number of 90°bends at the minimum bend radius per agency.2-45°or 3-30°bends equal 1-90°bend.Different values were obtained by FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss(equivalent length of pipe). See listing(s)approval agency for the latest approval details. FP-8.18 FLEXHEAD Flexible Sprinkler Connections ((�Z)/IM/iL STANDARD TALL SERIES HOSE 20XXET(ELBOW) L±20mm - V` (El ✓` - 3 9 i.• TYP 304SS SCH 40 PIPE [76.�1 I / i }�}�}�}�}�}�}�}�}�}}�}}}}}}}}}}(}}}}}}tt}}}}}}tt}}}}}t}}}}}}}}}}}t t}t�}�}�}�}�f�}�}�}�}�}�it�f�t�}�}�}��f�}f�}�}�}�}�f�}�}�}�}�t�}�t�}�}�}���}�}��}�}�}��}�}�}}�}�}}�}�}�}�t�}}�f}�}�}�}�}�}}�}�}�}�}}�}��}��}�} 'ff:10}}}}}}}}}}it}}t}t}t}t}t}t}t t}t}t}t}t}}}}}}}}}}}}}}}}}}} t}tit}}t}t}t}t}ttt}t}t}t}titititititt}hilt}t}t}t}t}itit}t}}}}}}}}t}t}}}}}}}}}}} }}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}}'[L1}}}}}}}}t}}titttt}}}}}}}}}}}� 11}ttt}tt}itt}itit}titititt}tit}t}tit}t}t}}}tt}tt}}}}ittt}}t}}}t}}}}}}}t}}t}t}}}t 1 }}}}}}}}}}}}}}}}}}}}}t}}}}}t}}}tot}}}}}}}}}}}}}}}ttt}ttt}}}}}tI titt}t}itt}itt}tit}t}�i�t}t}t}}flit}t}t}itt}fait}t}it}tittttt}}}}}}}}}}}}tttt �I,t01.4,},t,}/t'},0,4.t,}/t'},0.1..1,1.11.0.t,},tlrt,},t,}'t,}.1.1,,10't.1.0,t,1.1.1.t .1.1t't'tt'} ,tt'tt'},t,},t'},tit,},ttt},t,}'t,}1t/},t,}/t,}'t,},t't'},t'}'t'}1t/},t'},t,},t'},t,},t,},t},t,}'}'t'},t'},t,},t,},}'ttt'},t,},ilittt'},tli ) 7 1"NPT THREADS J TO ANSI B 1.20.I 72 MODEL NUMBER: [183] 20XX ET-XX TT�_50(1/2"NPT OUTLET SIZE) OR 75(3/4"NPT OUTLET SIZE) -=ELBOW TALL SERIES HOSE -=HOSE LENGTH(24",Q¢",la",¢Q",OR L") MI 'OUTLET SIZE SEE CHART 01.31 [33.40] FLEXHEAD ELBOW TALL HOSE SERIES - 1" INTERNAL DIAMETER (I.D.) HOSE SERIES Hose Minimum Max.Number Equivalent Length of 1 in.Schedule 40 Pipe(Ft.) Max,Rated Model Outlet Assembly Braid Bend Radius of 90°Bends 4 gWorking Pressure Number Orifice Length Length FM Size a) (B) FM UL FM UL UL FM UL 5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor In./rm. In./mm. In./mm. In./mm. InJmm. In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. PSI/Kpa PSI/Kpo 2024E150 24 19.5 1 3 19 26.4 6.8 7.4 610 495.3 5.8 8.0 2 2.2 2036ET-50 36 31.5 2 3 23 30.1 11.8 12.5 914 800.1 7.0 9.1 3.6 3.8 2048E150 1/2 48 43.5 8 3 3 4 27 33.8 16.9 17.6 175 175 1.27 1219 1104.9 200 76.2 8.2 10.3 5.1 5.3 1205 1205 2060ET50 60 55.5 4 4 32 37.5 21.9 22.7 - 1524 1409.7 9.8 11.4 6.6 6.9 2012ET50 72 67.5 4 4 35 41.2 27 27.8 1828 1714.5 10.7 12.5 8.2 8.4 2024ET-75 24 19.5 1 3 18 N/A 14.7 8.2 610 495.3 5.5 4.5 2.5 36 31.5 23 25.2 26 21.8 13 2036ET75 914 800.1 2 3 7.0 N/A 7.7 7.9 6.6 3.9 2048E175 3/4 48 43.5 8 3 3 4 23 N/A 32.9 33 29 17.8 175 175 1.90 1219 1104.9 200 76.2 7.0 10 10 8.8 5.4 1205 1205 2060ET15 60 55.5 4 4 29 N/A 40.6 40 36.1 22.6 1524 1409.7 8.8 12.3 12.) 11 6.8 2072E115 72 67.5 4 4 32 N/A 48.5 47 43.2 27.5 1828 1714.5 9.8 14.7 14.3 13.1 8.3 Model Numbers:The"ET"designates Elbow Tall Series Hose.The"50"designates 1"Outlet Hose Series.The"75"designates' "Outlet Hose Series. Equivalent Lengths are shown with maximum number of 90°bends at the minimum bend radius per agency.2-45°or 3-30°bends equal 1-90°bend.Different values were obtained by FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss(equivalent length of pipe). See listing(s)approval agency for the latest approval details. FP-8.18 mie FLEXHEAL1 Flexible Sprinkler Connections (*)ANVIL INSTALLATION INSTRUCTIONS MPO24BKT2 Multi-Position Open Hub Bracket (MPO) Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System Recommend the use of proper PPE for installation. MPO24BKT2 is approved for use with the standard FlexHead®Flexible Sprinkler Hose in accordance to NFPA 13, 13D, & 13R for use in wet and dry sprinkler system.The Standard Flexible sprinkler hoses are UL approved for Limited flexibility and 43 are intended for direct sprinkler connection. 0-= The MPO24BKT2 is pre-assembled at �� St nlda deTall , ' FlexHead® center tile position. (See below for 2024T,2036T,2048T,2060T Standard Tall Elbow additional installation configurations) 2072T,20XXH,20XXHE,20XXI 2024ET,2036ET,2048ET,2060ET,2072ET 1 T Bar Ceiling _ ---.. 3MPO Bracket Installation Grid Installation i{ Maneuver the flexible sprinkler drop from the branch to the ilia MPO bracket. Review that the hose length, number of bends, The MPO bracket is designed , ..,4 and bend radius are applicable for the installation per NFPA for use on ceiling grids conforming guidelines. (See corresponding hose submittal for installation to ASTM C 635*. information.) Locate the center of the The MPO bracket has an open hub for ease of installation. ceiling tile marking,align the Open the hinge apparatus by turning the locking shaft 1/a turn. offset screw with that marking for true center of tile installation. Slide the flexible hose drop into the hub. Ensure the drop is Insert one bracket leg at a time, applying a downward pressure vertical,and the SS Flexible°hose is not applying a substan- on the bracket leg and T-Bar. Place the second leg on the tial moment on the bracket causing sprinkler misalignment. T-Bar and repeat process. (Fig. 1) Latch the hinge door closed , a � and adjust the sprinkler drop 2 FlexHead Flexible ' for desired ceiling height. 1 ,�- Tighten the set screw till hand Hose Installation , ` ,. , tight plus 1"turn,(100 in-Ibs). I Apply Teflon®tape or pipe � �` sealant to the 1" NPT thread. 1,;a= Install desired sprinkler head, Install into branch outlet.Any or per the manufacturer's direction is acceptable,ensure � .• _ installation instructions. ;/ . ; . the hose is allowed at least one ,.1 , '- .._ bend per installation to allow for Do not wrench on seismic movement. (See Friction braided hose Loss Chart on page 8 for details.) Tighten hose using the pipe drop section, never apply a wrench to the braided hose for installation. (Fig.2) Installation Configurations Installation Complete ,t: 4 it i 24"Tile—24/4-Quarter Mark Position ', 3: Z. v ffa 141/2"Wood Stud -Center Position* U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097 20XXHE,20XXSF,20XXE&20XXI,20XXET with MP024BKT2 Bracket has not been evaluated by UL. 'Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636. •FM Approved,Installation has not been evaluated by UL. FP-8.18 FLEXHEAD Flexible Sprinkler Connections (Eir Annn L INSTALLATION INSTRUCTIONS ADOXXBKT3 Adjustable Open Hub Bracket (ADO) Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System Recommend the use of proper PPE for installation.ADOXX- The ADOXXBKT3 is pre-assembled at 4/: 0 BKT3 is approved for use with the standard FlexHead®and center tile position. (See below for atiat'nouB SuperFlex"" Flexible Sprinkler Hose in accordance to NFPA 13, additional installation configurations) 13D, & 13R for use in wet and dry sprinkler system.The ADO16BKT3&ADO24BKT3 UL Listed and FM Approved. Standard&SuperFlex- Flexible sprinkler hoses are UL ADO3OBKT3&ADO48BKT3 FM Approved. approved for limited flexibility and are intended for direct sprinkler connection. .,,,- , r . r ,� FlexHead® �..� , Standard Tall FlexHead® 2024T,2036T,2048T,2060T, ,, Standard Tall Elbow � SuerFlex'"' P» ,v 2072T,20XXH,20XXHE,20XXI �"" 2024ET,2036ET,2048ET,2060ET,2072ET 2036SF,2048SF,2072SF 1 T Bar Ceiling _ cook ADO Bracket , Grid Installation ,. Installation Maneuver the flexible sprinkler t ' The ADO bracket is designed for P iiiiiii, `'e . iuse on ceiling grids conforming to ' = drop from the branch to the ADO `ti,, t 4'1�4 kASTM C 635`. ,` bracket. Review that the hose z�Locate the center of the length, number of bends,and i `.. t,r ceiling tile marking,align the bend radius are applicable for offset screw with that marking for true center of tile installation. the installation per NFPA guidelines. (See corresponding Insert one bracket leg at a time,applying a downward pressure }:. hose submittal for installation -- /- on the bracket leg and T-Bar. Place the second leg on the 11` T-Bar and repeat process. (Fig. 1) information.) The ADO bracket has an open I ai AIIIIFF FlexHead Flexible ., i • _'� hub for ease of installation. p: Open the hinge apparatus byy el Hose Installation P g PP , ,. , turning the locking shaft�/a turn. ,i p , A. For threaded fitting branch 1 I �'" � connection:Apply Teflon®ta a or +� t= Slide the flexible hose drop into PP Y p the hub. Ensure the drop is vertical, and the SS Flexible®hose pipe sealant to the 1" NPT r , , is not applying a substantial moment on the bracket causing thread. Install into branch outlet. Tigthen the hose using the pipe It a`' , sprinkler misalignment. Latch the hinge door closed and adjust section, never apply a wrench to the sprinkler drop for desired ceiling height.Tighten the set PP Y Do not wrench on screw till hand tight plus 3/4"turn,(130 in-lbs).(Fig.3a and 3b) the braided hose when installing. braided hose B.For groove connection follow the grooved coupling manufac- Install desired sprinkler head,per the manufacturers turer's installation instructions. installation instructions. C. For SLT connection follow Gruvlok®installation instructions, "Fig 7074SLT SlideLOK®Ready for Installation Cap&Fitting Instructions". The FlexHead connection can be installed in any direction from the branch. Ensure the hose is allowed at least one bend per installation to allow for seismic movement. (See fiction Loss Chart on Page 3 for details) Installation Configurations Installation Complete r. 7 e 4 L 1i; Pi li gt.. I t ,r • t �� :. ' t NMI :', Y ter:= 24"Tile-24/4-Quarter Mark Position 1412"Wood Stud-Center Position• U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097 20XXT,220XXET,20XXH,20XXHE,20XXI,with ADOXXBKT3 Bracket has not been evaluated by UL. 'Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636. 'FM Approved,Installation has not been evaluated by UL. FP-8.18 FLEXHEAD Flexible Sprinkler Connections ((Z 4N'. IL • INSTALLATION INSTRUCTIONS MPT24BKT1 Multi-Position Tall Bracket (MPT) Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System Recommend the use of proper PPE for installation. MPT-24- approved for limited flexibility and are 11> 4) BKT1 is approved for use with the standard FlexHead®and intended for direct sprinkler connection. �ppppy� SuperFlexTM Flexible Sprinkler Hose in accordance to NFPA The MPT bracket is set for 24"center of tile installation. (See 13, 13D,& 13R for use in wet and dry sprinkler system.The back side for additional installation configurations) Standard&SuperFlexTM Flexible sprinkler hoses are UL FlexHead® FlexHead® FlexHead® ' Standard Tall go. Standard Tall Elbow SuperFlex'" " 2024T,2036T,2048T,2060T,2072T 2024ET,2036ET,2048ET,2060ET,2072ET 2036SF,2048SF,2072SF 4 T Bar Ceiling Grid Installation FlexHead Flexible Hose Installation The MPT bracket is designed for use on ceiling grids 4A. For threaded fitting branch connection:Apply Teflon® conforming to ASTM C 635*. tape or pipe sealant to the 1" NPT thread. Install into branch Locate the center of the ceiling tile marking,align the offset outlet.Tigthen the hose using the pipe section, never apply a screw with that marking for true center of tile installation.Insert wrench to the braided hose when installing. one bracket leg at a time,applying a downward pressure on the B.For groove connection follow the grooved coupling manufac- bracket leg and T-Bar. Screw the self tapping screw using a turer's installation instructions. #2 square head driver. Place the second leg on the T-Bar and C.For SLT connection follow Gruvlok®installation instructions, repeat process. (Fig. 1) "Fig 7074SLT SlideLOK®Ready for Installation Cap& Fitting Instructions". ill ...„ , Fig.1 The FlexHead connection can be installed in any direction from • the branch. Ensure the hose is allowed at least one bend per installation to allow for seismic movement. (See fiction Loss „Ic 4 Chart on Page 3 for details) e . — • / _ . , _ _ ....,"' .'iiir .........- ,. i:., iP,,,, �r r Do not wrench on braided hose 3 TF Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636. FP-8.18 •,. FLEXHEAD Flexible Sprinkler Connections (T') N ,JJ 3Secure the Flexhead Sprinkler Drop to A Ceiling Tile Installation —The flexible sprinkler MPT Bracket — Maneuver the flexible sprinkler drop got drop system with MPT Bracket is able to be installed prior from the branch to the MPT bracket. Review that the hose to the ceiling tile installation, preventing the need for sprinkler length,number of bends,and bend radius are applicable for the contractor tile adjustment. installation per NFPA guidelines. (See corresponding hose For ease of tile installation,cut the largest sprinkler hole submittal for installation information.) recommended by the manufacturer.The largest hole that The MPT bracket has an open hub for ease of installation. is still covered by the sprinkler escutcheon allows for an easier Open the hinge apparatus by turning the locking shaft%turn. install. Slide the flexible hose drop into the hub. Ensure the drop is Angle the tile at 45 degrees and push the tile through the hole vertical, and the SS Flexible®hose is not applying a substantial and up above the ceiling T-bar, maneuver the tile and allow it moment on the bracket causing sprinkler misalignment. Latch to drop in the proper location. (Fig.4) the hinge door close and adjust the sprinkler drop for desired ceiling height.Tightening the set screw till hand tight plus two t' full revolutions, (130 in Ibs). (Fig. 3a and 3b) o °t,¢t } , t, ;,, Install desired sprinkler head, per the manufacturer's installation j { x1�;` kA(� 4�L d� instructions. j Il=t' ' _'' t1s: as ,:,:. 3;S ..t A east �f444;v Pf .. c fi .• *...4 to. e T ti_ ytd I 'a �` , 8 {3 i , Ej `a:l1i 4 , -,,rt Ea „ 1 i#n t3#� °Eyj q ., 3 „ rt ,^" r , s t t€ q7 kT Y � $� a.,,t F ..£ '✓.ces�r#cs51f ?". 4 ;.4, y1' 55 _ ,f (' Installation Complete i .',,I;:::',, ,' 1 t3 IL 8 Itit i R C¢,kx�t.''.I-, a., „++yam- Attie /I� C';4? a„�e x. kS j r;3 a s,z t �$ a -#x6.E t,# a S 1",1s ll�" :1 ll 01 t 1 tl1 lit t MAY$ILY ys it 1 k�' 'tw yt S k , x,1,? - a i Installation Configurations 1PM r d''.- 1 f /Ili %to4 r 24"Tile—24/4 16"Tile—16/2 16"Metal Stud 141/2'Wood Stud Quarter Mark Position Center Position Center Position• Center Position* U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097 20XXET with MPT-248KT1 Bracket has not been evaluated by UL. •FM Approved,Installation has not been evaluated by UL. FP-8.18 FLEXHEAD Flexible Sprinkler Connections 41 l..1.4 FRICTION LOSS DATA & SPECIFICATIONS Minimum Max.Number Equivalent LengthMax-Rated uiva of 1 in.Schedule 40 Model Outlet Hose Bend Radius of 90°Bends Q g Pipe(Ft.) Working Pressure Number Orifice Assembly FM Size Length FM UL UL FM UL FM UL 5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor 22.4 k-Factor In./cm. In./mm. In./mm.In./mm.ln./mm.In./mm. Ft./m. Ft./m. Ft./m. Ft-/m. Ft./m. Ft./m. Ft./m. PSI/Ksa PSI/K,a Su+�erFlex 1 Internal Diameter(ID)Hose Series ,- ; . A ,: 2036SF 50 36 5 2 30 16.2 16.9 11.5 _ 914 9.1 4.9 5.1 3.5 20485F-50 1727 1489 178 50.82 02.8 8 3 14J5.4 3 28.7 8.7 28.9 9.3 4.7 - - 20725F 50 72 12 4 71 53.9 54.3 23.2 - 1828 21.6 16.4 16.5 7 20365F 75 36 5 2 29 - 21.5 21.6 21.8 22 914 8.86.5 6.5 6.6 6.7 20485F-75 3/4 48 7 2 8 3 44 - 30.5 30.6 31.1 30.8 - 1.90 1219 178 50.8 13.49.2 9.3 9.4 9.3 20725E 15 72 12 4 70 - 48.5 48.8 49.9 48.6 1828 21.314.7 14.8 15.2 14.8 Su'erFlex Elbow I"Internal Diameter(ID)Hose Series 2036ESF-50 36 _ 2 _ 25.8 26.1 12.5 914 7.8 7.9 3.8 2048ESF 50 / 48 7 N/A _ 3 _ 36.1 36.3 17.6 - 175 175 1.27 1219 178 11 11 5.3 1205 1205 2072ESF-50 72 _ 4 _ 57.3 56.9 27.8 _ - 1828 174 17.3 8.4 2036ESF-75 36 _ 2 _ 25.2 26 25.9 25.7 914 7.6 7.9 7.9 7.8 2048ESF 75 13/90 1489 I�8 N/A - 3 - - 32.9 30 30 30 - 1205 120 2072ESF-75 72 _ 4 _ _ 48.5 47 47.3 47.6 1828 14.8 14.3 14.4 14.5 Flexhead Standard Tall 1"Internal Diameter(I.D)Hose Series 20241 50 24 3 1 11 18.4 7.7 7.6 - 610 3.4 5.6 2.3 2.3 36 16 26.6 11.5 11.5 20361 50 914 3 2 4.9 8.1 3.5 3.5 2048T-50 12�7 1489 200 76 2 4 3 7.3 30.3 1q 3 15.4 -4.7 175 15 0 20601 50 60 4 4 29 35.8 19.1 19.3 1524 8.8 10.9 5.8 5.8 2072T 50 72 4 4 35 45.6 23.0 23.2 1828 10.7 13.9 7 - 24 12 7.3 5.9 14.7 7.1 20241 75 610 3 I 3.7 - 2.2 1.8 4.5 2.1 36 18 21.5 10.4 21.8 10.9 20361 75 914 3 2 5.5 - 6.5 3.1 6.6 3.3 - 20481-75 3�4 48 8 3 4 3 23 - 30.5 14.9 29 14.8 _ 175 175 1.90 1219 200 76.2 7.09.3 4.5 8.8 4.5 1205 1205 20601 75 60 4 4 29 - 39.5 19.4 36.1 18.7 1524 8.812 5.9 11 5.6 2012T 75 72 4 4 -32 48.5 24.0 43.2 22.6 - 1828 9.814.7 7.3 13.1 6.8 Hexheod Standard Tall Elbow 1"Internal Diameter(1.0)Ho9e Series 2024ET-50 24 3 1 19 26.4 6.8 7.4 - - - 610 5.8 8.0 2 2.2 2036E1-50 36 3 2 23 30.1 11.8 12.5 - - 914 7.0 9.1 3.6 3.8 2048E150 1/2 48 8 3 4 3 27 33.8 16.9 17.6 - - - 175 175 1.27 1219 200 76.2 8.2 10.3 5.1 5.31205 1205 2060E1-50 60 4 4 32 37.5 21.9 22.7 _ _ 1524 9.8 11.4 6.6 6.9 2072E1-50 72 4 4 35 41.2 27.0 27.8 - - - 1828 10.7 12.5 8.2 8.4 See Table Notes on Page 8. FP-6.18 FLEXHEAD Flexible Sprinkler Connections (E'43)/INVIIL FRICTION LOSS DATA & SPECIFICATIONS Minimum Max.Number Equivalent Length of 1 in.Schedule 40 Pipe(Ft.) Max.Rated Model Outlet Hose Bend Radius of 90'Bends q gWorking Pressure Orifice Assembly Number Size Length FM UL UL FM UL FM FM UL 5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor 22.4 k-Factor In./rm. In./mm. In./mm.In./mm.In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. PSI/Kpa PSI/Kpa 24 18 8.8 8.7 14.7 8.2 2024ET 15 610 3 1 5.5 - 2.6 2.6 4.5 2.5 - 2036ET75 36 3 2 _ 25.5 14.2 21.8 13 914 r 7.7 4.2 6.6 3.9 2048ET-75 3/4 48 8 3 4 3 23 - 32.9 18.4 29 17.8 _ 175 175 1.90 1219 200 76.2 1 10 5.6 8.8 5.4r. 2060E175 60 4 4 40.6 22.7 36.1 22.6 - 1524 _ 12.3 6.9 11.0 6.8 2072ET 15 72 4 4 48.5 27.0 43.2 27.5 1828 - 14.7 8.2 13.1 8.3 Flexhead Hi.h Pressure 1"Internal Diameter(I.D)Hose Series 2024H-50 24 3 2 11 18.4 7.7 7.6 - 610 3.4 5.6 2.3 2.3 2036H 50 36 3 3 16 26.6 11.5 11.5 - 914 4.9 8.1 3.5 3.5 2048H 50 1/2 48 8 3 4 4 24 30.3 15.3 15.4 300 300 1.27 1219 200 76.2 7.3 9.2 4.6 4.7 2068 206E 2060H 50 60 4 4 29 35.8 19.1 19.3 1524 8.8 10.9 5.8 5.8 2072H 50 72 4 4 35 45.6 23.0 23.2 0.7 13.9 7 2024H 15 24 610 3 2 12 3.1 - 14.7 4.5 6.8 2.0 14.7 4.5 7.1 _ 2.1 2036H 15 36 3 3 18 21.5 11.4 21.8 10.9 - 914 5.56.5 3.4 6.6 3.3 2048H75 1/4 1�.90 1489 200 76.2 4 4 23 - 30.5 16.0 29 14.8 - 2068 20 8 2060H 75 60 4 4 29 39.5 20.6 36.1 18.7 - - 1524 8.812 6.2 11.0 5.7 2072H 75 -72 4 4 32 48.5 25.3 43.2 22.6 - 1828 9.814.7 7.7 13.1 6.8 Flexhead Hiih Pressure Elbow 1"Internal Diameter(I.D)Hose Series 2024HE 50 24 3 2 19 14.7 6.8 7.4 610 5.8 4.5 2 2.2 - - - 2036HE-50 36 3 3 23 21.8 11.8 12.5 _ _ - 914 7.0 , 6.6 3.6 3.8 2048HE 50 1231 1489 200 76.2 4 4 e 2 728 8 16.)9 .3 - - - 30 8 Po68 2060HE-50 60 4 4 32 36.1 21.9 22.7 - - - 1524 9.8 11 6.6 6.9 2072HE-50 72 4 4 35 43.2 27.0 27.8 _ _ _ 1828 10.7 13.1 8.2 8.4 2024HE 75 24 3 2 18 - 145 - 14.7 8.2 610 5.54.54.5 25 2036HE-75 36 3 3 23 25.2 26 21.8 13 _ - 914 7.07.7 7.9 6.6 3.9 2048HE-75 3/4 48 8 3 4 4 23 - 32.9 33 29 17.8 _ 300 300 1.90 1219 200 76.2 7.010 10 8.8 5.4 2068 2068 2060HE 15 60 4 4 29 40.5 40 36.1 22.6 _ - 1524 8.8 12.3 12.2 11.0 6.8 2012HE 75 72 4 4 32 - 48.5 47 43.2 27.5 1828 9.814.8 14.3 13.1 8.3 Flexhead Dr Pendent S stem 1"(eternal Diameter(1-D)Hose Series 2024 DPS 24 _ 1 - 18.4 7.7 7.6 - 7.1 10.7 6105.6 2.3 2.32.1 3.3 2036-DPS 36 - 2 _ 26.6 11.5 11.5 _ 10.9 15.1 914 8.1 3.5 3.5 3.3 4.6 2048 DPS 1 48 7 _ 3 _ 30.3 15.3 15.4 _ 14.8 21.5 175 254 )219 180 9.2 4.1 4.1 4.5 6.5 1205 2fl60 OP5 60 - 4 - 35.8 19.1 19.3 - 18.7 25.3 1524 10.9 5.8 5.9 5.7 7.7 20720PS 72 _ 4 _ 45.6 23 23.2 - 22.6 26.9 1828 13.9 7 76.9 8.1 See Table Notes on Page 8. FP-6.18 FLEXHEAD Flexible Sprinkler Connections *)ANVIL FRICTION LOSS DATA & SPECIFICATIONS Minimum Max.Number E utvalent Len th of 1 in.Schedule 40 Pie(Ft.) Max.Rated Model Outlet Hose Bend Radius of 90°Bends Number q g P Working Pressure Orifice Assembly Size Length FM UL UL FM UL FM FM UL 5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor 22.4 k-Factor In./cm. In./mm. In./mm,In./mm.In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. PSI/Kpa PSI/Kpa 20241 24 610 - - - - 20361 36 r 914 20481 '/s 48 8 314;.:)9 r _ _ _ _ 175 175 1.27 1219 200 76.2 1205 1205 20601 60 c - 1524 '1 12 ' 20721 1828 10.7 20241 24 _ 11.6 610 3.5 20361 36 _ 16 _ 914 4.9 20481 Y4 48 8 3 4 3 23 _ 17.9 _ _ 175 175 1.90 1219 200 76.2 0 54 1205 1205 20601 604 4 29 _ 24.7 _ 1524 : 7.5 20721 724 4 _ 28.9 - 1828 8.8 Flexhead Institutional for use with Amerlux Ceilin. S stem-1"Internal Diameter(I°0)Hose Series 20241A 24 - 1 11 _ 18.4 - - - - 610 3.4 5.6 20361A 36 _ 2 16 - 26.6 - - - 914 4.9 8.1 '/z 48 8 24 30.3 175 175 20481A 1.27 1219 200 - - 3 7.3 - 9.2 - - 1205 20601A 60 _ 4 29 _ 35°8 1524 8.8 10.9 _ 20721A 72 _ 4 35 ' _ 45.6 - - - 828 10.7 13.9 NOTES: Model Numbers: • "SF"designates SuperFlex'"Hose series. • "ESF"designates SuperFlex'"Elbow Hose series. • "E"designates elbow drop hose series • "T"designates straight tall style hose • "ET"designates elbow tall style hose series. • "H"designates high pressure 300psi working pressure hose series. • "HE"designates high pressure 300psi elbow hose series. • "DPS"designates dry pendant system. • "DT"designates drain tee hose series used in dry pendent/freezer application. • "DPS"and"DT"models are approved for use in cold storage application(Freezer,Cold Chamber)and combine an approved flexible sprinkler hose and an approved dry pendent sprinkler.UHO-1 or UHO-3 is required to connect the flexible sprinkler hose to the dry sprinkler. • "I"indicates instiutional flexible hose. • "A"indicates models for use with Amerlux Ceiling System. • "50"designates '/z"Outlet Hose series.The"75"designates Ye"Outlet Hose series.Inlet size 1". • Max Ambient Temperature Rating on all model numbers are 300°F(148'C). • Equivalent lengths are shown with maximum number of 90°bends at the minimum bend radius per agency.2-45°or 3-30°bend equal 1-90°bend.Different values were obtained by FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss (equivalent length of pipe). • All hoses require a minimum of one bend for installation.Bend radius tool available for 3"bend"T"hose,"SF"hose does not require bend radius tool. • FM equivalent length calculation includes Sprinkler Head Friction Loss. • See listing(s)approval agency for the latest approval details. FP-6.18 NIBCO www.nibco.com AHEAD OF THE FLOW® Revised 7/25/2018 300 PSI CWP Iron Body Gate Valves el Fire Protection Valve • Outside Screw and Yoke • Resilient Wedge • Epoxy Coated Interior/Exterior • Pre Grooved Stem for Supervisory Switch • NSF/ANSI NSF/ANSI 372 Drilled, Tapped and Plugged at Boss Location A** 300 PSI/20.6 Bar Non-Shock Cold Working Pressure ' C D1LISTED il UL/ULC LISTED' • FM APPROVED • CERTIFIED LEAD-FREE* "� NSF/ANSI 372 , 11> t ', APPROVED MATERIAL LIST PART SPECIFICATION 1 Valve Body Ductile Iron ASTM A536 2 Resilient Wedge Ductile Iron ASTM A536/EPDM ASTM D2000 3 Wedge Nut ASTM B584 UNS C83600 4 Dowel Pin ASTM A276 SS304 5 Stem Back Seat 0-Ring EPDM ASTM D2000 F-607-RWS 6 Bonnet Gasket EPDM ASTM D2000 7 Bonnet Ductile Iron ASTM A536 Flanged 0 E 8 Stem Packing EPDM ASTM D2000 t 2 9 Threaded Rod ASTM A276 SS304 e 10 Gland Bushing ASTM B584 UNS C83600 11 Gland Ductile Iron ASTM A536 �, O 12 Gland Nut ASTM B148 C95200 Aluminum Bronze 0 m 13 Yoke Ductile Iron ASTM A536 'i 6,,. e 14 Yoke Bushing ASTM B150 C61400 0 'i.UR!lL-. 0 15 Flat Point Set Screw ASTM F912M e INIA o 16 Yoke Bushing Retainer Cast Iron ASTM A126 Class B AitO 4;- 0 17 Handwheel Ductile Iron ASTM A536 �iii, 0 18 Handwheel Nut Carbon Steel Zinc Plated '' III, 19 Stem Stainless Steel 304 ®, ,,;1�/.iIA o 20 Bonnet Screw Corrosion-resistant Steel Ls 21 NPT Pipe Plug Steel ASME B16.14 h v 22 UL/FM Label(not shown)Aluminum Igin) ` -- 23 Yoke Nut ASTM B148 C95200 Aluminum Bronze , \� ' �" 24 Drive Screw Label(not shown)Stainless Steel 304 Position A o Coating-Electrostatically applied fusion-bonded epoxy 8-20 mil.inside and outside meets or exceeds AWWA C550. '-F -c- "'Drilled,tapped and plugged at Position A with yi'valve sizes 21'2"-4°,3/4"on 6"--8",1"on 10"-12". A t Compliance with the Standard for Gate Valves for Fire Protection Service,UL 262,and the Canadian Requirements,ULC/ORD-C262. NOTE:Flanged valve is consistent with ANSI B16.1 Class 125. F-607-RWS DIMENSIONS-WEIGHTS-QUANTITIES Fig xFlg Dimensions Bolt Size A B Open B Closed C D E F G Circle Flange Turns Weight In.mm. l Tnn.mm. 'in.mm. 1In.mm. In.mm. 1nm. . 1= Inin. rm--7mm. Holes To Open Los. rtg. 2' 65 7.5 190 17.8 453 14.9 378 0.69 17.5 7.0 178 7.9 200 1.50 38 1.42 36 5.50 140 4 6.3 39 18 3 80 8.0 203 19.7 500 15.9 405 0.75 19.0 7.5 191 7.9 200 1.73 44 1.42 36 6.00 152 4 10.0 44 20 4 100 9.0 229 21.0 534 16.6 422 0.94 24.0 9.0 229 10.2 260 2.13 54 1.42 36 7.50 191 8 10.0 72 33 6 150 10.5 267 29.3 744 22.9 581 1.00 25.4 11.0 279 12.4 315 2.24 57 1.54 39 9.50 241 8 15.0 117 53 8 200 11.5 292 37.0 939 28.5 724 1.13 28.6 13.5 343 14.8 375 2.48 63 1.54 39 11.75 298 8 16.7 198 90 10 250 13.0 330 44.8 1139 34.5 877 1.19 30.2 16.0 406 16.4 416 3.15 80 1.82 46 14.25 362 12 20.8 374 170 12 300 14.0 356 52.2 1326 39.9 1014 1.25 31.8 19.0 483 17.5 445 2.91 74 1.82 46 17.00 432 12 25.0 493 224 14* 350 15.0 375 62.2 1580 50.0 1270 1.38 35.0 21.0 533 19.7 500 2.95 75 3.20 81 18.75 476 12 43.8 620 284 16* 400 16.0 400 65.9 1674 50.4 1280 1.44 37.0 23.5 597 19.7 500 3.03 77 3.20 81 21.25 540 16 50.0 816 370 *14 and 16"valves 250 PSI CWP QWARNING:This product can expose you to chemicals including lead,which is known to the State of California to cause cancer and birth defects or other reproductive harm.For more information go to www.P65Warnings.ca.gov. FREEZING WEATHER PRECAUTION:Subsequent to testing a piping system,gate valve should be in an open position to allow complete drainage. Visit our website for the most current information. *Weighted average lead content<0.25% NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 20 TECH SERVICES PH:1.988.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455 www.nibco.com N IBCO www.nibco.com AHEAD OF THE FLOW® Revised 7/25/2018 • 175 PSI WWP Bronze Gate Valves Dezincification Fire Protection Valve • Screw-Over Bonnet • Resistant Outside Screw and Yoke • Solid Wedge 175 PSI/12.1 Bar Non-Shock Cold Water Id> (400 PSI Non-Shock CWP General Service) APPROVED C (20 US LISTED UL/ULC LISTED* • FM APPROVED • { APPROVED BY THE NEW YORK CITY B.S.A. 143-69-SA , 14 r . MATERIAL LIST to PART SPECIFICATION 1. Set Screw Steel ASTM A307 4E' 2. Handwheel Malleable Iron ii _' 1 3. Yoke Bushing Brass ASTM B16 4. Gland Bolts Steel ASTM A307 Zinc Platedii` i 5. Packing Gland Bronze ASTM B62 .w # s . 6. Packing Non Asbestos Aramid Fibers w/Graphite 7. Bonnet Bronze ASTM B62 T-104-0 8. Stem Silicon Bronze ASTM B371 Alloy C69430 Threaded 9. Stem Collar Silicon Bronze ASTM B371 Alloy C69430 10. Wedge Pin Bronze ASTM B140 Alloy C31400 11. Wedge Bronze ASTM B62 12. Body Bronze ASTM B62 0 © �'---'01 =1���� © C -y DIMENSIONS-WEIGHTS-QUANTITIES © :ii!`fir Dimensions Handwheel Size A B Diameter Weight Box Master O IT ' OPEN In. mm. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. 90 1/2 15 2.19 59 5.88 149 3.25 88 2.28 1.04 1 20 0 � %kb) 3/4 20 2.44 62 6.44 164 3.25 88 2.83 1.29 1 20 O ,f� 1 25 2.88 73 7.44 189 3.25 88 3.67 1.67 1 10 �y 11/4 32 3.13 79 8.69 221 4.00 100 5.83 2.65 1 10 0 �' my. 11/2 40 3.38 84 9.38 238 4.00 100 6.84 3.11 1 10 2 50 3.44 87 10.59 269 3.50 89 9.74 4.44 1 6 rA p t*'411 �,� "Compliance with Standard for Gate Valves for Fire Protection Service,UL 262,and the Canadian 0 IIIIIII.��t�1iil f IIIII PI Requirements. III F,y1 QWARNING:This product can expose you to chemicals including lead, IIIIIIII1 I IIIII Jul which is known to the State of California to cause cancer and birth defects � .41 1111110jy�� or other reproductive harm.For more information go to www.P65Warnings.ca.gov. A T-104-0 NPT x NPT Visit our website for the most current information. NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455III www.nibco.com 1 FireLock® Butterfly Valve ✓ctaul:c. Series 705 with Weatherproof Actuator 10.81 l 1.0 PRODUCT DESCRIPTION • Available Sizes: 2 — 12"/50—300 mm • cULus Listed, LPCB Listed, FM and VdS Approved for service up to 300 psi/2068 kPa /20 bar. • Designed for fire protection services only. • Features a weatherproof actuator housing Approved for indoor and outdoor use. • Actuation options: Hand wheel (2 — 12"/50—300 mm) • Exclusively for use with pipe and Victaulic products which feature ends formed with the Victaulic Original Groove System (OGS) groove profile (see section 7.0 for Reference Materials). 2.0 CERTIFICATION/LISTINGS sOuS ® VdS FLPCBJ USTED G410001 104j/04 ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved LDate victaulic.com 10.81 5662 Rev I Updated 07/2020 ©2020 Victaulic Company.All rights reserved. 1 ✓ctaulic FireLock® Check Valves ✓Ctaulic Series 717 & 717H 10.08 Grooved ends allow fast, easy installation with just .. two Victaulic couplings or the valve may be mounted I Op to flanged (ANSI CL.150) equipment using either to Victaulic Style 741 Vic-Flange®or Style 744 FireLock flange adapters on either end. Series 717 Series 717 (21/ -3/65-80mm) (4- 12"/100-300 mm) 4 ffif Series 717H High Pressure Check Valve (2-3'/50-80 mm) Approvals/Listings: cOus 11> VdS LPCB c' USTED See Victaulic Publication 10.01 for more details. The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD designed for hydrodynamic efficiency and available in 2"/50 mm —3"/80 mm (Series 717H) and 2 1/765 mm — 12"/300 mm (Series 717) sizes. Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa. See chart below for approved services for the Series 717 valves. In both valve designs, the single-disc mechanism incorporates a spring-assisted feature for nonslamming operation. This spring-assisted, single-disc design achieves a leak-free seal with as little as 5ft/1.5m of head. Series 717 and 717H FireLock Check Valves can be installed either vertically (flow upwards only) or horizontally. A cast flow arrow indicator is provided to assist with proper valve orientation. Both valves include upstream and downstream pressure taps. Each valve is factory-tested to the rated working pressure. For systems requiring a Riser Check option, refer to publication 10.09. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date Check Valve I FireLock® I Series 717 & 717H I Publication 10.08 victaulic.com 1 JCtaulic Check Valve I Firelock! I Series 717 & 717H I Publication 10.08 Material Specifications: Spring: All sizes Type 302/403 Stainless Steel Housing: Shaft Plug: Ductile iron conforming to ASTM A-536, grade • Series 717H (2 —3"/50—80 mm): Type 416 Stainless 65-45-12. Ductile iron conforming to ASTM A-395, Steel grade 65 45 15, is available upon special request. • Series 717 (2 1/2— 12"/65—300 mm): Carbon steel Body Coating: zinc plated Series 717H Body: Black Paint Pipe Plug: Series 717H Endface: Electroless Nickel • Series 717H (2—3"/50—80 mm): carbon steel zinc Series 717 (2 1 —3"): PPS Coating plated Series 717 (4— 12"): Black Paint • Series 717 (4— 12"/100—300 mm): Carbon steel zinc Body Seat: plated Series 717H — Nitrile 0-ring installed into an electroless nickel plated endface Series 717 (2 1/2—3"): PPS Coated ductile iron Series 717 (4— 12"): Electroless Nickel plated Disc Seal or Coating: (specify choicer) ❑ Grade "T" nitrile (Series 717H Only) Nitrile (Orange color code).Temperature range—20°F to +180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range; except hot, dry air over+140°F/+60°C and water over+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. ❑ Grade "E" EPDM (Series 717 Only) EPDM (green color code).Temperature range-30°F to +230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2 —3"/50—80 mm): CF8M Cast Stainless Steel • Series 717 (2 1/—3"): Aluminum bronze with elastomer seal • Series 717 (4— 12"/100—300 mm): Elastomer encapsulated disc with electroless nickel plated seat Shaft: • Series 717H (2 —3"/50-80 mm): Brass • Series 717 (2 1/—3"): Type 416 Stainless Steel • Series 717 (4— 12"/100—300 mm) Type 316 Stainless Steel • victaulic.com 2 jctaulie NIBCO www.nibco.com AHEAD OF THE FLOW° Revised 9/1/2021 200 PSI WWP Bronze Check Valves Dezincification Fire Protection Valve • Horizontal Swing • Rubber Disc Resistant 200 PSI/13.8 Bar Non-Shock Cold Water CONFORMS TO MSS SP-80 MATERIAL LIST PART SPECIFICATION 1. Bonnet Bronze ASTM B62 or B584 Alloy C84400 2. Body Bronze ASTM B62 or B584 Alloy C84400 3. Hinge Pin 316 SS or 304 SS KT-403-W 4. Disc Hanger Bronze ASTM B62 Threaded 5. Hanger Nut Bronze ASTM B97 Alloy C65500 or Brass ASTM B16 6. Disc Holder Bronze ASTM B62 7. Seat Disc Nitrite(WI PTFE(YI# 8. Seat Disc Nut Brass ASTM B16 or B97 Alloy C65500 9. Hinge Pin Plug Bronze ASTM B140 Alloy C32000 0 (Not Shown) 0 *10. Seat Disc Washer Stainless Steel etNL *Sizes 3/4",1",1Y4"and 1Y ��x"only.No Seat Disc Washers an 1/2"and 3/4"with PTFE(Y)discs. �j�i�� 9% i #2Yz"and 3"size only. 0 �N�pl► ` � %IYa t B tun 0 11111.111111111111 DIMENSIONS-WEIGHTS--QUANTITIESF"' A Dimensions Size A B Weight Box Master. KT-403-W In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. NPI x NPI 1/2 15 2.44 62 1.69 43 58 .26 10 50 3/4 20 2.94 75 1.88 48 .92 .42 10 50 1 25 3.56 90 2.31 59 1.55 .70 5 30 1 Y 32 4.19 106 2.69 68 2.32 1.05 5 20 11/2 40 4.50 114 2.94 75 3.00 1.36 2 10 2 50 5.25 133 3.81 97 4.87 2.21 2 10 21/2 65 8.00 203 5.06 129 11.48 5.22 1 5 3 80 9.25 235 6.25 159 17.53 7.97 1 4 Sizes 23/2"and 3"supplied as T-433-Y with PTFE seat disc. NIBCO check valves may be installed in both horizontal and vertical lines with upward flow or in any intermediate position. WARNING-Valve must be installed downstream of receiver tank if used in line with reciprocating air compressor. QWARNING:This product can expose you to chemicals including lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm.For more information go to www.P65Warnings.ca.gov. Visit our website for the most current information. NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 14 TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455 www.nibco.com GVI FIRE PUMP METERS - DIMENSIONAL DATA MACHINED or CAST CARBON STEEL"WCB" CONSTRUCTION&SPECIFICATIONS I METER DATA MATERIALS: MACHINED 1018/1026 CARBON STEEL 111 1 CONSTRUCTION: ALUMINUM BODY or CAST CARBON STEEL"WCB" OPERATION: DIAPHRAGM(BUNA CONVOLUTED) VALVES: 1/4"BRASS BALL ACCURACY: +2%FULL SCALE TEMPERATURE: 180°F/80°C FLANGE OPT: 150#ANSI B 16.5 ■ PRESSURE: 500 PSIG-3450 KPA 300#ANSI B 16.5 APPROX.WEIGHT: 3.75 LBS(1.7 KGS) ID TAG: POLYCARBONATE 4"DIAL STANDARD - 6"DIAL AVAILABLE MATERIALS AVAILIBLE:STAINLESS STEEL,BRASS,ALUMINUM,MONEL,VARIOUS PLASTICS, EPDXY COATED,AND MANY OTHERS. PLEASE CONSULT FACTORY. 60' / ‘ ... — - "...•\ > ♦Of %(79 slf 0 ,R v MI MESS= (1 Vri �.�' . / �� END VIEW A I A A BUTT WELD/GROOVED BUTT WELD GROOVED FLANGED BUTT WELD&GROOVED 150#FLANGED 300#FLANGED SIZE "A"DIM APPROX.WEIGHT "A"DIM APPROX.WEIGHT "A"DIM APPROX.WEIGHT 1-1/4" 4.875 2 lbs. 2" 5.000 3.5 lbs. 2-1/2" 4.000 5 lbs. 9.250 21 lbs. 10.000 28 lbs. 3" 4.000 6 lbs. 9.375 30 lbs. 10.250 36 lbs. 3-1/2" 4" 5.375 10 lbs. 11.375 40 lbs. 12.125 60 lbs. 5" 6.000 20 lbs. 13.000 58 lbs. 13.750 84 lbs. 6" 7.000 22 lbs. 14.000 70 lbs. 14.750 106 lbs. 8" 7.250 31 lbs. 15.250 93 lbs. 16.000 181 lbs. 10" 8.000 45 lbs. 16.000 149 lbs. 17.250 227 lbs. 12" 12.000 78 lbs. 21.000 238 lbs. 22.250 358 lbs. 14" 14.000 85 lbs. 16" 28.000 166 lbs. OPERATING INSTRUCTIONS G V I 1. CLOSE SYSTEM VALVE. VENTURI FIRE PUMP TEST METER 2. OPEN SYSTEM BY-PASS VALVE AND THROTTLE VALVE. 3. PURGE METER LOCATED ON VENTURI AS FOLLOWS: WASTE - HA OPEN SHUT-OFFDISCRGE VALVES&VENT VALVES. / D7.<3 0 AIR DT1 �3 - WHEN A STEADY STREAM OF WATER IS PASSING THROUGH THROTTLE VENT BY-PASS -- EACH PLASTIC HOSE,THE METER IS PURGED OF AIR. VALVE <2> ' , (5) 44 VALVE 1� - CLOSE VENT VALVE AFTER PURGING. PIPE I TERS FROM VALVE 4. START FIRE PUMP,READ METER IN GPM/LPM // \\ I 5. REFER TO PUMP GPM/LPM REQUIREMENT AND ADJUST ��,����1 THROTTLE VALVE FOR THIS REQUIREMENT. SUPPLY . 9 . 6. AFTER TEST OPEN SYSTEM VALVE AND CLOSE SYSTEM i i VALVE SYSTEM VALVE BY-PASS AND THROTTLE VALVES. FIRE PUMP TYPICAL PIPING 8800 JEFFERSON HIGHWAY - OSSEO, MN 55369 USA PHONE (763) 391-0990 FAX (763) 391-7668 EMAIL: info@gviflow.com r4, ASHCROFT® Data Sheet 1005P XUL Fire Protection Sprinkler Service Gauge FEATURES -- .: PowerFlex�° movement provides superior u t %`' I "�'ii resistance to shock, vibration and pulsation , ' ti<'120 lso llso l zo TrueZeror"" reduces reading errors by using boo 240 ! a "zero box" instead of convential dial pins �• ' yo Water or Air gauges available for wet/dry / 30 to Heat-resistant polycarbonate push-in window L '' wt Custom dials available 30 40 50 l TYPICAL USES 20 60 300 10 70 ' 400 to Fire Sprinklers for water or air systems „' 4n80 } 100 yam' • boo 1005P XUL ""°- 31/idialsize '1; SPECIFICATIONS KEY BENEFITS Accuracy: ±3-2-3%of span(ASME B40.100 Grade B) •Single scale,dual scale and triple scale Sizes: 3W dials available(bar,kPa,psi) Ranges: Single,dual or triple scale •Corrosion resistant ABS case 0-300 psi(water) 0-80 psi retard to 250 psi(air) •Custom Dials available 0-600 psi Process Connection Location: Lower Process Connection MIN/MAX TEMPERATURE LIMITS /4 NPT Size: Version Ambient Process Storage Dial: Black figures on white background 1005P XUL -40°F to 150°F -40°F to 150°F -40°F to 150°F Pointer: Black,aluminum (-40°C to 65°C) (-40°C to 65°C) (-40°C to 65°C) Weather Protection: Weather resistant Movement: PowerF/ex—with Brass/polyester segment Approvals: UL 393 listed for fire protection sprinkler service UL Canada listed FM approved WETTED COMPONENTS Bourdon Tube Process Connection Bronze Brass NON-WETTED COMPONENTS Case Window ABS(Polycarbonate blend) Polycarbonate 1 of 3 All specifications are subject to change without notice. ashcroft.com All sales subject to standard terms and conditions, into@ashcroft.com ©2018 Ashcroft Inc.1005p-xul_gauge_ds1.0_Rev B.,11/18 1.800.328.8258 ASHCROFT' Data Sheet Trust the shield:" 1005P XUL Fire Protection Sprinkler Service Gauge ORDERING CODE Example: 35 W 1005 P H 02 L XULZO 100# Dial Size 35-31/2" 35 Movement type W-PowerF/ex'" W Model 1005 1005 Case/Window Material P-ABS/Polycarbonate P Process Connection Material H-Brass H Process Connection Size 02-V4 N PT 02 Process Connection Location L-Lower L Options(If choosing an option(s)must include an"X") — X__ UL-(required-UL393 listed and FM approved) UL ZO-Bulk pack ZO ZP-Customer part number on carton/plain white label ZQ-Customer part number printed directly on carton Ranges Single Scale 100#-0/80 psi retard to 250 psi outer scale 100# 300#-0/300 psi outer scale 600#-0/600 psi outer scale Dual Scale(psi/kPa) 100#-AGN-0/80 psi retard to 250 psi outer scale;0/550 kPa retard to 1750 kPa inner scale 300#-AGS-0/300 psi outer scale;0/2000 kPa inner scale 600#-AGV-0/600 psi outer scale;0/4000 kPa inner scale Triple Scale(psi/kPa/bar) —-- — _ 100#-CAA-0/80 psi retard to 250 psi outer scale;0/550 kPa retard to 1750 kPa middle scale;0/5.5 bar retard to 17.5 bar inner scale 300#-CAB-0/300 psi outer scale;0/2000 kPa middle scale;0/20 bar inner scale 600#-CAC-0/600 psi outer scale;0/4000 kPa middle scale;0/40 bar inner scale 2 of 3 All specifications are subject to change without notice. ashcroft.com All sales subject to standard terms and conditions. info4fashcroft.com 02018 Ashcroft Inc.1005p-xul_gauge_ds1.0_Rev B.,11/18 1.800.328.8258 ASHCROFT' .rsbni 1ro Data Sheet 1005P XUL Fire Protection Sprinkler Service Gauge DIMENSIONS in [] are millimeters For reference only,consult Ashcroft for specific dimensional drawings Lower Connection Dial Size A BCD E G Weight inches 31/2. 3.70 1.14 2.72 3.61 0.47 0.56 5.36 oz [94] [29] [69] [92] [11.0) [14.2] 0.152 kg A FB �� M E G 1/4 NPT 3 of 3 All specifications are subject to change without notice. ashcruft.cum All sales subject to standard terms and conditions. info@ashcrott.com ©2018 Ashcroft Inc.1005p-xul_gauge_ds1.0_Rev B.,11/18 1.800.328.8258 . A Pipe Hangers Fig. 200 - "Trimline" Adjustable Band Hanger (Cooper B-Line Fig. B317ONF) Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (Cooper B-Line Fig. B317ONFF) Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (Cooper B-Line Fig. B317ONFC) Size Range: Fig. 200 - 1/2"(15mm)thru 8"(200mm) pipe C U` US Material: Steel, Pre-Galvanized to G90 specifications M LISTED .... • Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. . Features: • (1/2"(15mm)thru 2"(5omm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design ® =_ keeps adjusting nut from separating with hanger. Hanger is easily , v installed around pipe. _ ;i • (21/2"(65mm)thru 8"(2oomm)) Spring tension on nut holds it securely in B hanger before installation.Adjusting nut is easily removed. A Approvals: Underwriters Laboratories listed (1/2"(15mm)thru 8" (2oomm)) in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4"(20mm)thru 8"(2oomm)). / Conforms to Federal Specifications WW-H-171E&A-A-1192A,Type 10 - Fig.zoo /z.200-3/4 and Manufacturers Standardization Society ANSI/MSS SP-69& SP-58, Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Type 10. Maximum Temperature: 650°F(343°C) Finish: Pre-Galvanized. Stainless Steel T materials will be supplied with (2) hex nuts in place of a knurl nub. `' Order By: Figure number and pipe size .4' , ittito 44 **Note: For metric hanger rod sizes add the metric rod size to the figure number. ,•,,,..... Example: 200M8-11/2 or 200M10-11/2 Fig. 200 Fig. 200C Fig. 200F Pipe Size Rod Size A B Max. Rec. Load Approx.Wt./100 Part No. in. (mm) in. mm" in. (mm) in. (mm) lbs. (kN) lbs. (kg) 200-1/2 1/2" (15) 3/8"-16 M8 or M10 31/8" (79.4) 25/8" (66.7) 400 (1.78) 11 (5.0) 200-3/4 3/4" (20) 3/8"-16 M8 or M10 31/8" (79.4) 21/2" (63.5) 400 (1.78) 11 (5.0) 200-1 1" (25) 3/8"-16 M8 or M10 33/8" (85.7) 25/8" (66.7) 400 (1.78) 12 (5.5) 200-11/4 11/4" (32) _ 3/8"-16 M8 or M10 33/4" (94.0) 27/8" (73.0) 400 (1.78) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 M8 or M10 37/8" (98.4) 27/8" (73.0) 400 (1.78) 14 (6.4) _200-2 2" (50) 3/8"-16 M8 or M10 41/2" (114.3) 3" (76.3) 400 (1.78) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 M10 55/8" (142.9) 41/8" (104.7) 600 (2.67) 27 (12.3) 200-3 3" (75) 3/8"-16 M10 57/8" (149.1) 4" (101.6) 600 (2.67) 29 (13.3) 200-31/2 31/2" (90) 3/8"-16 M10 73/8' (187.3) 51/4" (133.3) 600 (2.67) _ 34 (15.6) 200-4 4" (100) 3/8"-16 M10 73/8" (187.3) 5" (127.0) 1000 (4.45) 35 (16.0) 200-5 5" (125) 1/2"-13 M12 91/8" (231.8) 61/4" (158.7) 1250 (5.56) 66 (30.2) 200-6 6" (150) 1/2"-13 M12 101/8" (257.2) 63/4" (171.4) 1250 (5.56) 73 (33.4) 200-8 8" (200) 1/2"-13 M12 131/8" (333.4) 83/4" (222.2) 1250 (5.56) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 61 1101.1 COOPER B-Line Beam Clamps Fig. 65 - Reversible Steel C-Type Beam Clamp 3/4" (19.0mm) Throat Opening ®TDLCO Fig. 65XT - Reversible Steel C-Type Beam Clamp 3/4" (19.0mm) Throat Opening (bottom of page) O US Size Range: LISTED Fig.65 - 1/2"-13 rod sizes, and 5/8"-11 rod sizes Fig.65XT - 3/8"-16 rod size(see below) Material: Steel with hardened cup point set screw and jam nut Function: Recommended for hanging from steel beam where flange thickness does not exceed 3/4"(19.0mm). B D Features: All steel construction eliminates structural deficiencies associated with - casting type beam clamps. May be used on top or bottom flange of beam. (Beveled lip E allows hanging from top flange where clearance is limited.) May be installed with set c screw in up or down position. Offset design permits unlimited rod adjustment by A.1 ..p./iV allowing the rod to be threaded completely through the clamp. Open design permits a%� inspection of thread engagement. F 4'u Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). %.* A Exceeds requirements of the National Fire Protection Association(NFPA), pamphlet 13, 3/8"-16 rod will support 1/2"(15mm)thru 4"(1o0mm)pipe `/ 1/2"-13 rod will support thru 8"(200mm) pipe Finish: Plain.Contact Cooper B-Line for alternative finishes and materials. Set Screw and p Locknut Included Order By: Figure number and finish Fig.65 Patent#4,570,885 (9 m 3 0 N Part Rod Size B C D E _ No. A in. (mm) in. (mm) in. (mm) in. (mm) 65..112 1/2"-13 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/16" (14.3) 65-5/8 5/8"-11 11/2" (38.1) 3/4" (19.0) 1" (25.4) 9/16" (14.3) A Part F Approx.Wt./100 ' No. in. (mm) Lbs. (kg) ., , 65-1/2 11/4" (31.7) 55 (24.9) 4 1 65-5/8 11/4" (31.7) 55 (24.9) * Maximum loads for clamp with set screw in up or down position. .';"; 1 ae.-. Fig. 65XT-3/8 - Beam Clamp in - - (25.4) C( uS Feature: Extruded holes allows for more thread >t LISTED engagement of threaded rod and set screw. /44.-6, (39 t9N.7)s" Weight: Approx.Wt./100 28.0 Lbs.(12.7kg) byt Finish: Plain or Electro-Galvanized 3i.ej� , 1. , -„09.13) I Order By: Figure number and finish Approvals: Underwriters Laboratories Listed f 4. (cULus)and FM Approved (FM)for up to 4" `ii fsok,,i' • t . (100mm) pipe. Set Screw and '/e° Locknut Included 13/e" (22.2) Designed to meet or exceed requirements of (34,9) FM DS 2-0. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. MIIIIIIIIMIMIIIIIMIIIMIIIIIIIIMIIIIIMIIPIOPIIIIIIM COOPER B-Line Beam Clamps Fig. 69 - Beam Clamp Retaining Strap (Cooper B-Line B3367) ®TOLcO Size Range: 3/8"-16 thru 3/4"-10 rod D Vi. US 4"(101.6mm)thru 16"(406.4mm) lengths uSTED Note: longer lengths are available consult factory Material: Pre-Galvanized Steel Function: To offer more secure fastening of various types of beam clamps to beam where danger of movement might be expected. NFPA 13 requires the use of retaining straps with all beam clamps installed in earthquake areas. Satisfies requirements of NFPA 13. Important Note: Good installation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly.Therefore a locking mechanism of some kind,such as a hex for the Fig. 69 will provide a more secure reliable installation. Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved for use with any listed beam clamp. Finish: Pre-Galvanized Order By: Figure number, length (L), and finish. Note: Minimum return on strap is 1"(25.4mm) For Use With: Any Cooper B-Line or TOLCO beam clamp. )«� )l, y jII C *I co co }i1g m Hole Dia. D Length 1�1 Part No. in. (mm) 69-3/8-L 7/16" (30.1) Specify = too 69-1/2-L 9/16" (30.1) Specify = 69-5/8-L 11/16" (50.8) Specify 69-3/4-L 13/16" (63.5) Specify 1i1 7._1\ 1� All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPER B-Line Seismic Bracing TOLCO Fig. 4L- sway brace attachment (FM approved) OPM 111> Size Range: 1"(25mm)through 12" (300mm) IPS. APPROVED Material: Steel. set soh& Function: For bracing pipe against sway and seismic disturbance. Hardware Included a=iith Approvals: Approved by Factory Mutual Engineering (FM), 1"(25mm)through 12" 1 'I',1 c (300mm)pipe. For UL Listed information refer to UL Listed page 74. Included in (II�?I��' v3 our Seismic Engineering Guidelines approved by the State of California Office of I !ll!! m Statewide Health Planning and Development(OSHPD). For additional load, spacing !Mill■ and placement information relating to OSHPD projects, please refer to our Seismic !I■ n o ;n Engineering Guidelines, OPM-0052-13. /7.‘ in Installation Instructions: Fig.4L is the "braced pipe" attachment component of a D longitudinal and lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO'"structural attachment component to form a complete A bracing assembly. NFPA 13 and/or FM guidelines should be followed. - -+ T To Install: Place the Fig.4L over the pipe to be braced and tighten bolts.Then engage "bracing pipe" into jaw opening and tighten set bolt until head snaps off. Jaw attachment can pivot for adjustment to proper brace angle. (For complete c detailed instructions see instruction sheet IL309015EN). 1 1 ? Finish: Plain, Electrogalvanized. • j Order By: Figure number, pipe size and finish. �1t!' 'ice Designed to meet or exceed requirements of FM DS 2-8. 4 j> . otiV ` to et" , Ar 4 , 0 r„ Iii. s' S 1%) Lateral 1,, Longitudinal With Plain& Brace Brace Electrogalvanized Finish FM Max.Rec.Load FM Max.Rec.Load Nom Pipe A Bolt Logitudinal Lateral Approx. Size (Max) C D Size 30°-44° 45°-59° 60°-74° 75°-90° 30°-44° 45°-59° 60°-74° 75°-90° Wt./100 Part No. in. ,mm) in. in. in. in. lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. 41-1 1 (25) 5 2 13/8 1/2-13 1060(4.72) 1160(5.16) 1400(6.23) 1500(6.68) 1370(6.10) 1940(8.63) 2380(10.59) 2650(11.79) 176 4L-11/e 11/4 (32) 52/7 21/16 15/e 1/2-13 1060(4.72) 1160(5.16) 1400(6.23) 1500(6.68) 1370(6.10) 1940(8.63) 2380(10.59) 2650(11.79) 182 41-1'/2 11/2 (40) 51/2 ! 21/3 12/3 1/2-13 740(3.30) 1020(4.54) 1250(5.57) 920(4.10) 1370(6.10) 1940(8.63) 2380(10.59) 2650(11.79) 187 41-2 2 (50) 62/7 22/3 2 1/2-13` 740(3.30) 1020(4.54) 1250(5.57)' 920(4.10) 1420(6.32) 1990(8.86) 2440(10.86) 2720(12.10) 204 4L-2'/2 21/2 - 67/e I 3 21/3 1/2-13 520(2.32) 650(2.90) 790(3.52),1040(4.63) 1410(6.28) 1990(8.86) 2440(10.86) 2720(12.10) 220 41-65mm - (65) 67/3 l 3 21/3 1/2-13( 520(2.32) 650(2.90) 790(3.52) 1040(4.63) 1410(6.28) 1990(8.86) 2440(10.86) 2720(12.10) 218 41-3 3 (80) 73/7 31/4 25/e 1/2-13 520(2.32) 650(2.90) 790(3.52)!1040(4.63) 1410(6.28) 1990(8.86) 2440(10.86) 2720(12.10) 323 41-31/2 31/2 (90) 8 131/2 27/e 1/2-13 520(2.32) 650(2.90) 790(3.52) 1040(4.63) 1410(6.28) 1990(8.86) 2440(10.86) 2720(12.10) 343 41-4 4 (100) 83/7 i 33/4 31/e 1/2-13 520(2.32) 650(2.90) 790(3.52) 1040(4.63) 1410(6.28) 1990(8.86) l 2440(10.86) 2720(12.10) 253 4L-5 5 - 95/e i 43/3 35/8 1/2-13 1520(2.32) 650(2.90) 790(3.52)'1040(4.63) 1410(6.28) 1990(8.86) !2440(10.86) 2720(12.10) 313 41-125mm - (125) 95/3 1 43/3 35/e 1/2-13! 520(2.32) 650(2.90) 790(3.52) 1040(4.63) 1410(6.28) 1990(8.86) 12440(10.86) 2720(12.10) 312 41-6 6 - 113/7 573 44/7 1/2-13! 870(3.87) 1200(5.34) 1460(6.50)',.1630(7.26) 1560(6.94) 2210(9.84) :2710(12.06) 3020(13.44) 540 41-150mm - (150) 113/7 1 51/3 44/7 1/2-13 870(3.87) 1200(5.34) 1460(6.50)',1630(7.26) 1560(6.94) 2210(9.84) l 2710(12.06) 3020(13.44) 538 41-8 8 - 133/5 62/5 52/3 1/2-13 1190(5.30) 1440(6.41) 1580(7.03)j 1750(7.79) 1560(6.94) 2210(9.84) 12710(12.06) 3020(13.44) 645 4L-200mm - (200) 133/3 t 62/5 52/3 1/2-13 1190(5.30) 1440(6.41) 1580(7.03) 1750(7.79) 1560(6.94) 2210(9.84) 2710(12.06) 3020(13.44) 643 41-10 10 (254) 173/5 81/4 71/4 1/2-13 1620(7.21) 1660(7.38) 1570(6.98)'1740(7.74) 1620(7.21) 2300(10.23)''2820(12.54) 3140(13.97) 1349 41-12 ,12 (300) 193/3 9'/4 81/4 1/2-13 1620(7.21) 1660(7.38) 1570(6.98)t 1740(7.74) 1620(7.21) 2300(10.23)12820(12.54) 3140(13.97) 1526µ Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,resulting in a listed seismic bracing assembly.Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that,in addition to the other exclusions from Eaton B-Line Division warranty,Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Updated$2-21 B-Line series Fire Protection Solutions 75 Eaton Seismic Bracing Fig. 980-TOLCO Universal swivel sway brace attachment-3/a"-16 to 3/4rr-10 rods Fig.980H -TOLCO Universal swivel sway brace attachment-'/8'-9 to 11/4°-7 Size Range: One size fits bracing pipe 1"(25mm)thru 2" (50mm), B-Line series 12 gauge (2.6mm)channel. Material: Carbon steel OPM APPROVED Function: Multi-functional attachment to structure or braced pipe fitting. Features: This product's design incorporates a concentric attachment opening which is critical to the performance of structural seismic connections and in y accordance with NFPA 13, 2019 Section 18.5.11.5.The Fig. 980 mounts to :=_ 980e---14o ' N any surface angle and the break off bolt head assures verification of proper.installation / 0 Installation: Fig.980 is the structural or transitional attachment component of a J longitudinal or lateral sway brace assembly. It is intended to be combined with /� Q B the "bracing pipe" and TOLCO'" "braced pipe" attachment, Fig. 1000, 1001, \A 3000, 4L, or other TOLCO approved attachment to pipe to form a complete bracing assembly. NFPA 13 guidelines should be followed. set Bolt Mounting Hardware To Install: Place the Fig. 980 onto the "bracing pipe".Tighten the set bolt until Included Is Not Included the head breaks off.Attachment can pivot for adjustment to proper brace angle. Approvals:—Approved by Factory Mutual Engineering (FM). Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to ° our Seismic Engineering Guidelines, OPM-0052-13. For UL Listed information refer to UL Listed page 60. ..=j' `=t trda Note: Fig. 980 Swivel Attachment and Fig. 1000, 1001, 4L or other TOLCO $ 4 approved attachment to pipe that make up a sway brace system of bracing materials which satisfies the requirements of Factory Mutual Engineering and the National Fire Protection Association (NFPA) Finish: Plain, Electro-Galvanized or Stainless Steel — Fig Sea Contact customer service for alternative finishes. Order By: Figure number and finish. �40 Fig.1001 Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, Fig yeo Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Designed to meet or exceed requirements of FM DS 2-8. Fig.4L Brace Longitudinal Lateral Brace Brace A B D** `Max.Design Load***(FM) Approx.Wt/100 Catalog# in. (mm) in. (mm),, in. (mm)'30°-44° 45°-59° 60°- ° ° lbs. (kg) IbsJ(kN) IbsJ(kN) Ibsj(kN74) Ibs 15f(kN°-90►, 9803/e '/1e (11.1)( 149 (67.6) 980-1/2 9/16 (14.3) 2370 2790 3360 3750 148 (67.1) 980 5/e 49/16 (114.9)i 21/16 (52.4) 11/16 (17.5) (10.54) (12.41) (14.94) (16.68) 147 (66.7) 9803/4 13/16 (20.6)i 146 (66.2) 980H 7/s } 15/16 (23.811 402 (182.3) 980H-1 s 11/16 (27.0)1 Fig.980H is not UL Listed 400 (181.41 980H-1'/e 6/° (171.4) 3/2 (88.9) 13/16 (30.2) or FM Approved 397 (180.1) 980H-1'/4 j 15/16 (33.3) 390 (176.9) **Mounting attachment hole size. ***Installed with 1"or 11/4"schedule 40 brace pipe. Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Fire Protection Solutions 61 Eaton MI�..TI The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 19. Please refer to the publication in its entirety for complete details on this product including data development, product specifications, general suitability, installation, corrosion and spacing and edge distance guidelines. US&CA: https://submittals.us.hilti.com/PTGVol2/ To consult directly with a team member regarding our anchor fastening products, contact Hilti's team of technical support specialists between the hours of 7:00am — 6:00pm CST. US: 877-749-6337 or HNATechnicalServices(cc�hilti.com CA: 1-800-363-4458, ext. 6 or CATechnicalServices(c�hilti.com Hilti, Inc. 7250 Dallas Parkway, Suite 1000 Plano, TX 75024 1-800-879-8000 www.hi lti.corn FIIL.TI 3.3.5 KWIK BOLT TZ EXPANSION ANCHOR PRODUCT DESCRIPTION KWIK Bolt TZ carbon steel and stainless steel anchors Anchor System Features and Benefits • Used with Hilti Dust Removal System(DRS)for dustless a1� drilling and installation(compliant with Table 1 of OSHA ally 1926.1153 regulations for silica dust exposure). • Accurate SafeSetTM installation when using the Hilti SIW- 6AT-A22 impact wrench and the SI-AT-A22 Adaptive Torque Module • Product and length identification marks facilitate quality control after installation. • • Through fixture installation and variable thread lengths improve productivity and accommodate various base plate thicknesses. • Type 316 stainless steel wedges provide superior Carbon Steel KB TZ performance in cracked concrete. Stainless Steel KB-TZ • Ridges on expansion wedges provide increased reliability. • Mechanical expansion allows immediate load application. • Raised impact section(dog point)prevents thread damage during installation. • Bolt meets ductility requirements of ACI 318-14 Section 2.3. • ACI 349-01 Nuclear Design Guide is available. Call Hilti Technical Support. Hilti SIW-6AT-A22 impact wrench and the SI-AT-A22 Adaptive Torque Module tt f,7� Iftigr'' a s '11, a a a 1� �d3 , " *` SAPS-�'T a o.b o o o c Ira{ 0 S- Uncracked Cracked Grout-filled Seismic Design Hollow Drill Bit Profis Anchor Fire sprinkler concrete concrete concrete Categories A-F with Adaptive design software listings masonry Torque Tool (AT) Approvals/Listings ICC-ES(International Code Council) ESR-1917 in concrete per ACI 318-14 Ch.17/ACI 355.2/ICC-ES AC193 -2018 International Building Code/International ESR-3785 in grout-filled CMU per ICC-ES AC01 Residential Code(IBC/IRC) ELC-1917 in concrete per CSA A23.3-14/ACI 355.2 -2015 National Building Code of Canada(NBC-C) City of Los Angeles 2017 LABC Supplement(within ESR-1917) RR 26057 grout-filled CMU Florida Building Code 2010 FBC with HVHZ FM(Factory Mutual) Pipe hanger components for automatic sprinkler systems 3/8 through 3/4 UL and cUL(Underwriters Laboratory) Pipe hanger equipment for fire protection services for 3/8 through 3/4 's KLA( °DBS C CD us /vARIMAI m WILDING ua SA MY Y APPROVED LISTED 286 Anchor Fastening Technical Guide Edition 19 13.0 ANCHORING SYSTEMS 13.3.5 KWIK BOLT TZ EXPANSION ANCHOR Hilti,Inc.(U.S.)1-800-879-8000 I en espanol 1-800-879-5000 I www.hilti.com I Hilti(Canada)Corporation I www.hilti.com I 1-800-363-4458 Anchor Fastening Technical Guide, Edition 19 MATERIAL SPECIFICATIONS Carbon steel with electroplated zinc Carbon steel KB-TZ anchors have the following minimum bolt fracture loads.' Anchor diameter Shear Tension (in.) (Ib) (Ib) 3/8 NA 6,744 1/2 7,419 11,240 5/8 11,465 17,535 3/4 17,535 25,853 Carbon steel anchor components plated in accordance with ASTM B633 to a minimum thickness of 5 pm. Nuts conform to the requirements of ASTM A563, Grade A, Hex. Washers meet the requirements of ASTM F844. Expansion sleeves(wedges)are manufactured from type 316 stainless steel Stainless steel Stainless steel KB-TZ anchors are made of type 304 or 316 material and have the following minimum bolt fracture loads.' Anchor diameter Shear Tension (in.) (Ib) (Ib) 3/8 5,058 6,519 1/2 8,543 12,364 5/8 13,938 19,109 3/4 22,481 24,729 All nuts and washers for type 304 anchors are made from type 304 stainless. All nuts and washers for type 316 anchors are made from type 316 stainless. Nuts meet the dimensional requirements of ASTM F594. Washers meet the dimensional requirements of ANSI B18.22.1,Type A, plain. Expansion sleeve(wedges)are made from type 316 stainless steel. 1 Bolt fracture loads are determined by testing in a universal tensile machine for quality control at the manufacturing facility. These loads are not intended for design purposes. See tables 4 and 16 for the steel design strengths of carbon steel and stainless steel,respectively. INSTALLATION PARAMETERS Figure 1 - Hilti KWIK Bolt TZ specifications thread h I I rff/A t eanch h of 'eunthr h nom ICI ho • dbit Anchor Fastening Technical Guide Edition 19 13.0 ANCHORING SYSTEMS 13.3.5 KWIK BOLT TZ EXPANSION ANCHOR 287 Hilti,Inc.(U.S.)1-800-879-8000 I en espanol 1-800-879-5000 I www.hilti.com I Hilti(Canada)Corporation I www.hilti.com I 1-800-363-4458 FIIIILTI Table 1 - Hilti KWIK Bolt TZ carbon steel specifications Setting Nominal anchor diameter d° information Symbol Units 3/8 1/2 5/8 3/4 Nominal bit d. in. 3/8 1/2 5/8 diameter b't 3/4 Minimum nominal h in. 1-13/16 2-5/16 3-1/16 2-3/8 3-5/8 3-9/16 4-7/16 3-13/16 4-5/16 5-5/16 embedment °°"' (mm) (46) (59) (78) (60) (91) (91) (113) (97) _ (110) (135) Effective minimum h in. 1-1/2 2 2-3/4 2 3-1/4 3-1/8 4 3-1/4 3-3/4 4-3/4 embedment of (mm) (38) (51) (70) (51) _ (83) (79) (102) (83) (95) (121) in. 2 2-5/8 3-3/8 2-5/8 4 3-3/4 4-3/4 4 4-5/8 5-3/4 Min.hole depth h ° (mm) (51) (67) (83) (67) (102) (95) (121) (102) (117) (146) Min.thickness t in. 0 0 0 3/4 1/4 3/8 3/4 0 0 7/8 of fixture' `"'" (mm) (0) (0) (0) (19) (6) (9) (19) (0) (0) (23) Max.thickness t in. 2-13/16 2-5/16 1-9/16 4 2-3/4 5-5/8 4-3/4 5-9/16 4-15/16 3-15/16 of fixture max (mm) (71) (59) (40) (101) (70) (143) (121) (141) (125) (100) Installation torque T ft-lb 25 40 60 110 (concrete) "s` (Nm) (34) (54) (81) (149) Installation torque T ft-lb n/a 15 n/a 25 35 n a 70 (masonry) "s` (Nm) (20) (34) (47) / (95) Fixture hole d in. 7/16 9/16 11/16 13/16 diameter h (mm) (11.1) _ (14.3) (17.5) (20.6) Available anchor e in. 3 3-3/4 5 3-3/4 4-1/2 5-1/2 7 4-3/4 6 8-1/2 10 5-1/2 7 8 10 lengths each (mm) (76) (95) (127) (95) (114) (140) (178) (121) (152) (216) (254) (140) (178) (203) (254) Threaded length in. 1-1/2 2-1/4 3-1/2 1-5/8 2-3/8 3-3/8 4-7/8 1-1/2 2-3/4 5-1/4 6-3/4 2-1/2 4 5 7 i including dog point thread (mm) (38) (57) (89) (41) (60) (86) (124) (38) (70) (133) (171) (63) (103) (128) (179) in. 1-1/2 2-1/8 3-1/4 3 Unthreaded length 1°"thr (mm) (39) (54) (83) (77) 1 Minimum thickness of fixture is a concern only when the anchor is installed at the minimum nominal embedment. When KWIK Bolt TZ anchors are installed at this embedment,the anchor threading ends near the surface of the concrete. If the fixture is sufficiently thin,it could be possible to run the nut to the bottom of the threading during application of the installation torque. If fixtures are thin,it is recommended that embedment be increased accordingly. Table 2- Hilti KWIK Bolt TZ stainless steel specifications' Setting Nominal anchor diameter(in.) information Symbol Units 3/8 1/2 5/8 3/4 Nominal bit diameter db;t in. 3/8 1/2 5/8 3/4 Nominal min. h in. 2-5/16 2-3/8 3-5/8 3-9/16 4-7/16 4-5/16 5-5/16 embedment "°"' (mm) (59) (60) (91) (91) (113) (110) (142) Effective min. h in. 2 2 3-1/4 3-1/8 4 3-3/4 4-3/4 embedment et (mm) (51) (51) (83) (79) (102) (95) _ (121) in. 2-5/8 2-5/8 4 3-3/4 4-3/4 4-5/8 5-3/4 Min.hole depth h ° (mm) (67) (67) (102) (95) (121) (117) (146) Min.thickness t in. 1/4 3/4 1/4 3/8 3/4 1/8 1-5/8 of fixture' """ (mm) (6) (19) (6) (9) (19) (3) _ (41) Max.thickness t in. 2-1/4 4 2-3/4 5-5/8 4-3/4 4-5/8 3-5/8 of fixture ma. (mm) (57) (101) (70) (143) (121) (117) .' (92) Installation torque T ft-lb 25 40 60 110 (concrete) '"st (Nm) (34) (54) (81) (149) Installation torque T ft-lb 15 25 35 70 (masonry) '"st (Nm) (20) (34) (47) (95) Fixture hole d in. 7/16 9/16 11/16 13/16 diameter " (mm) (11.1) (14.3) (17.5) (20.6) Available I in. 3 3-3/4 5 3-3/4 4-1/2 5-1/2 7 4-3/4 6 8.5 10 5-1/2 8 10 anchor lengths each (mm) (76) (95) (127) (95) (114) (140) (178) (121) (152) (216) (254) (140) (203) (254) Threaded length I in. 7/8 1-5/8 2-7/8 1-5/8 2-3/8 3-3/8 4-7/8 1-1/2 2-3/4 5-1/4 6-3/4 1-1/2 4 6 including dog point thread (mm) (22) (41) (73) (41) (60) (86) (124) (38) (70) (133) (171) (38) (102) (152) in. 2-1/8 2-1/8 3-1/4 4 Unthreaded length I."thr (mm) (54) (54) (83) (102) 1 Refer to figure 1 of this section for diagram of installation parameters 2 Minimum thickness of fixture is a concern only when the anchor is installed at the minimum nominal embedment.When KWIK Bolt TZ anchors are installed at this embedment,the anchor threading ends near the surface of the concrete.If the fixture is sufficiently thin,it could be possible to run the nut to the bottom of the threading during application of the installation torque.If fixtures are thin,it is recommended that embedment be increased accordingly. 288 Anchor Fastening Technical Guide Edition 19(3.0 ANCHORING SYSTEMS 13.3.5 KWIK BOLT TZ EXPANSION ANCHOR Hilti,Inc.(U.S.)1-800-879-8000 I en espanol 1-800-879-5000 I www.hilti.com I Hilti(Canada)Corporation I www.hilti.com I 1-800-363-4458 Anchor Fastening Technical Guide, Edition 19 . DESIGN DATA IN CONCRETE PER ACI 318 ACI 318-14 Chapter 17 design The load values contained in this section are Hilti Simplified Design Tables.The load tables in this section were developed using the Strength Design parameters and variables of ESR-1917 and the equations within ACI 318-14 Chapter 17. For a detailed explanation of the Hilti Simplified Design Tables, refer to section 3.1.8. Data tables from ESR-1917 are not contained in this section, but can be found at www.icc-es.org or at www.hilti.com. Table 3- Hilti KWIK Bolt TZ carbon steel design strength with concrete/pullout failure in uncracked concrete1,2,3,45 Nominal Tension-4N„ Shear-4V anchor Effective Nominal diameter embed. embed. f o=2,500 psi f,=3,000 psi f'c=4,000 psi f'e=6,000 psi f'c=2,500 psi f' =3,000 psi f' =4,000 psi f'c=6,000 psi in. in.(mm) in.(mm) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) 1-1/2 1-13/16 1,185 1,300 1,500 1,835 1,545 1,690 1,950 2,390 (38) (46) (5.3) (5.8) (6.7) (8.2) (6.9) (7.5) (8.7) (10.6) 3/8 2 2-5/16 1,635 1,790 2,070 2,535 2,375 2,605 3,005 3,680 (51) (59) (7.3) (8.0) (9.2) (11.3) (10.6) (11.6) (13.4) . (16.4) 2-3/4 3-1/16 2,670 2,925 3,380 4,140 7,660 8,395 9,690 11,870 (70) (78) (11.9) (13.0) (15.0) (18.4) (34.1) (37.3) (43.1) (52.8) ES 2 2-3/8 2,205 2,415 2,790 3,420 2,375 2,605 3,005 3,680 1/2 (51) (60) (9.8) (10.7) (12.4) (15.2) (10.6) _ (11.6) (13.4) (16.4) 3-1/4 3-5/8 3,585 3,925 4,535 5,555 9,845 10,785 12,450 15,250 (83) (91) (15.9) (17.5) (20.2) (24.7) (43.8) (48.0) (55.4) (67.8) 3-1/8 3-9/16 4,310 4,720 5,450 6,675 9,280 10,165 11,740 14,380 5/8 (79) (91) (19.2) (21.0) (24.2) (29.7) (41.3) (45.2) (52.2) (64.0) 4 4-7/16 5,945 6,510 7,520 9,210 13,440 14,725 17,000 20,820 (102) (113) (26.4) (29.0) (33.5) (41.0) (59.8) (65.5) (75.6) (92.6) 3-1/4 3-13/16 4,570 5,005 5,780 7,080 9,845 10,785 12,450 15,250 (83) (97) (20.3) (22.3) (25.7) (31.5) (43.8) (48.0) (55.4) (67.8) 3/4 3-3/4 4-5/16 5,380 5,895 6,810 8,340 12,200 13,365 15,430 18,900 (95) (110) (23.9) (26.2) (30.3) (37.1) (54.3) (59.5) (68.6) (84.1) 4-3/4 5-9/16 6,940 7,605 8,780 10,755 17,390 19,050 22,000 26,945 (121) (142) (30.9) (33.8) (39.1) (47.8) (77.4) I (84.7) (97.9) (119.9) Table 4- Hilti KWIK Bolt TZ carbon steel design strength with concrete/pullout failure in cracked concrete1'2,3,4,5 Nominal Tension-<1;,N„ Shear-cl)V„ anchor Effective Nominal diameter embed. embed. f',=2,500 psi f,=3,000 psi f„=4,000 psi f'o=6,000 psi f'c=2,500 psi f c=3,000 psi f'0=4,000 psi f<=6,000 psi in. in.(mm) in.(mm) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) lb(kN) 1-1/2 1-13/16 860 940 1,085 1,330 1,095 1,195 1,385 1,695 (38) (46) (3.8) (4.2) (4.8) (5.9) (4.9) (5.3) (6.2) (7.5) 3/8 2 2-3/8 1,565 1,710 1,975 2,420 1,685 1,845 2,130 2,605 (51) (60) (7.0) (7.6) (8.8) (10.8) (7.5) (8.2) (9.5) (11.6) 2-3/4 3-1/8 2,050 2,245 2,595 3,175 5,425 5,945 6,865 8,405 (70) (79) (9.1) (10.0) (11.5) (14.1) (24.1) (26.4) (30.5) (37.4) 2 2-3/8 1,565 1,710 1,975 2,420 1,685 1,845 2,130 2,605 1/2 (51) (60) (7.0) (7.6) (8.8) (10.8) (7.5) (8.2) (9.5) (11.6) 3-1/4 3-5/8 3,195 3,500 4,040 4,950 6,970 7,640 8,820 10,800 (83) (91) (14.2) (15.6) (18.0) (22.0) (31.0) (34.0) (39.2) (48.0) 3-1/8 3-9/16 3,050 3,345 3,860 4,730 6,575 7,200 8,315 10,185 5/8 (79) (91) (13.6) (14.9) (17.2) (21.0) (29.2) (32.0) (37.0) (45.3) 4 4-7/16 4,420 4,840 5,590 6,845 9,520 10,430 12,040 14,750 (102) (113) (19.7) (21.5) (24.9) (30.4) (42.3) (46.4) (53.6) (65.6) 3-1/4 3-13/16 3,235 3,545 4,095 5,015 6,970 7,640 8,820 10,800 (83) (97) (14.4) (15.8) (18.2) (22.3) (31.0) (34.0) (39.2) (48.0) 3/4 3-3/4 4-5/16 4,010 4,395 5,075 6,215 8,640 9,465 10,930 13,390 (95) (110) (17.8) (19.5) (22.6) (27.6) (38.4) (42.1) (48.6) (59.6) 4-3/4 5-9/16 5,720 6,265 7,235 8,860 12,320 13,495 15,585 19,085 (121) (142) (25.4) (27.9) (32.2) (39.4) (54.8) (60.0) (69.3) (84.9) 1 See section 3.1.8 to convert design strength value to ASD value. 2 Linear interpolation between embedment depths and concrete compressive strengths is not permitted. 3 Apply spacing,edge distance,and concrete thickness factors in tables 7 to 14 as necessary. Compare to the steel values in table 4. The lesser of the values is to be used for the design. 4 Tabular values are for normal weight concrete only.For lightweight concrete multiply design strength by A.as follows: for sand-lightweight,Ae=0.68;for all-lightweight,A. =0.60 5 Tabular values are for static loads only.Seismic design is not permitted for uncracked concrete.For seismic tension loads,multiply cracked concrete tabular values in tension only by aN...s=0.75. No reduction needed for seismic shear.See section 3.1.8 for additional information on seismic applications. Anchor Fastening Technical Guide Edition 19 13.0 ANCHORING SYSTEMS 13.3.5 KWIK BOLT TZ EXPANSION ANCHOR 289 Hilti,Inc.(U.S.)1-800-879-8000 I en espanol 1-800-879-5000 I www.hilti.com I Hilti(Canada)Corporation I www.hilti.com I 1-800-363-4458 ,, Bulletin 110 December 2020 co . c MN Reilabid Model G Automatic Sprinklers Ft T Spray Upright,Spray Pendent,And 8-- Conventional o B a- N Product Description S. o The Reliable Model G Automatic Sprinkler utilizes the cen = ='c ... ter strut solder in compression principle of construction. The , fusible alloy is captured in the cylinder of the solder capsule ..= --m- by a stainless steel ball. When the fusible alloy melts, the ball 4 ' ( �+ � ,i / moves into the cylinder allowing the cylinder to fall away from �( - -� `"""`")�� the sprinkler. When this happens, the lever is released to • spring free from the sprinkler so that all of the operating parts ' , :�:,::� clear from the waterway allowing the deflector to distribute ' 7 le the discharging water. Except for the parts in the cylinder as mentioned above, Upright Pendent the sprinkler components are made from copper based alloys for maximum corrosion protection. Lead plated, wax coated or wax over lead plated sprinklers are available for specially -- severe environments. Chrome plated sprinklers are available '. . for decorative purposes. 1.: ,A, All sprinklers are individually hydrostatically tested.All sprin- um• klers are identified as to their fusing point by markings that appear on several of the operating parts and by an identifying '--r color that appears on the frame. Sprinkler Types '. it Standard Upright—This deflector configuration is normally used with exposed piping installations. Water is distributed Small Orifice Upright Conventional laterally and downward in a wide pattern approximating a hemisphere which is completely and uniformly filled with wa- ter in the form of small drops or spray. Standard Pendent — This deflector configuration is nor- Application and Installation mally used where the space above the piping is limited or Standard sprinklers are used in fixed fire protection sys- where a concealed piping installation is employed. The dis- tems:Wet, Dry, Deluge or Preaction.Care must be exercised charge characteristics of the standard pendent are virtually that the orifice sizes, temperature ratings, deflector styles identical to the standard upright as described above. and sprinkler spacings are in accordance with the latest pub- lished standards of the National Fire Protection Association or Large and Small Orifice —By varying the orifice size, a the approving authority having jurisdiction. large or small orifice sprinkler is created that will distribute The sprinklers must be installed with the Reliable Model W2 as much as 40% more water or 65% less water than the Sprinkler Wrench.Any other type of wrench may damage the normal '/2' (15mm) orifice sprinkler. sprinkler. The approvals or listings of Reliable Automatic Sprinklers by Conventional —This deflector configuration is used pri- major approving organizations are shown in the tabulated list marily in those countries where the LPC installation rules provided on the back of this bulletin. have precedence. The sprinkler is designed to distribute a portion of its water discharge upward against the ceiling with the balance downward. It may be installed in either the upright or the pendent position. Sprinklers with conventional deflectors are available with orifice sizes corresponding to light, ordinary and extra—high hazard installations. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Technical Data "K"Factor Sprinkler Sprinkler Identification Number Sprinkler Type Height Approvals (SIN) US Metric SSU SSP Standard—Upright(SSU)and Pendent(SSP) Deflectors Marked to Indicate Position 1/2'(15 mm)Standard Orifice with 1/2 NPT(R1/2)Thread 5.62 81.0 2 7/8"(73 mm) 1,2,3,4,5,6 R1025 R1015 7/16"(11 mm)Small Orifice with 1/2"NPT(R1/2)Thread 4.24 61.0 2 7/8"(73 mm) 1 R1023 R1013 3/8"(10 mm)Small Orifice with 1/2"NPT(R1/2)Thread 2.82 40.6 2 7/8"(73 mm) 1,2, R1021 R1011 5/16"(8 mm)Small Orifice with"/2"NPT(R1/2)Thread 1.98 28.5 2 7/8"(73 mm) 1,5 R1022 R1012 17/32"(20 mm)Large Orifice with 1/2"NPT(R1/2)Thread 7.96 114.7 2 7/8"(73 mm) 1,2, R1026 R1016 17/32"(20 mm)Large Orifice with 3/4"NPT(R3/4)Thread 8.20 118.2 2 15/16"(75 mm) 1,2, R1027 R1017 20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 3,4,6 R1027 R1017 10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 3,4, R1024 R1014 Conventional—Installed in Upright or Pendent Position 10mm XLH with 10mm Thread 4.10 59.1 73 mm 4 R1074 15mm Standard Orifice with(R1/2) Thread 5.62 81.0 73 mm 3,4,6 R1075 20mm XHH with(R3/4)Thread 8.20 118.2 75.4 mm 3,4,6 R1077 Temperature Ratings Sprinkler Maximum Maintenance Classification Rating Ambient Frame 11) Model G Sprinklers should be inspected and the sprinkler system Temperature Color maintained in accordance with NFPA 25. Do not clean sprinklers °F °C °F °c with soap and water, ammonia or any other cleaning fluids. Re- Ordinary 135 57 100 38 Black move any sprinkler that has been painted (other than factory ap- Ordinary 165 74 100 38 Uncolored plied) or damaged in any way.A stock of spare sprinklers should Intermediate 212 100 150 66 White High 286 141 225 107 Blue be maintained to allow quick replacement of damaged or operated iiiFrame color does not apply to painted or plated sprinklers sprinklers. Prior to installation, sprinklers should be maintained in —Use sprinkler rating as identified on operating parts. the original cartons and packaging until used to minimize the po- Finishes(1) tential for damage to sprinklers that would cause improper opera- Standard Finishes tion or non-operation.Use only the Model W2 Sprinkler Wrench for Bronze All Temperature Ratings sprinkler removal and installation. Any other type of wrench may Chrome —All Temperature Ratings damage the sprinkler. White(2) —All Temperature Ratings Approval Organizations Only Frame and Deflector are Painted 1. Underwriters Laboratories, Inc. and UL Certified for Cana- Special Application Finishes da(cULus). Bright Brass Plated —Only frame,deflector and cap are plated.135°F 2. Factory Mutual Research Corporation (57°C),165°F(74°C),212°F(100°C)Temp.Rating. 3. Loss Prevention Council Black Plated —Only frame,deflector and cap are plated.All Temp. 4. Pleniere Assemblee Polyester Coated(2)(4) Ratings. Lead Plated —Only frame and deflector are coated. 5. N.Y.C.BS&A No.587-75—SA or Wax-Coated(3) —165°F(74°C),212°F(100°C)and 286°F(141°C) N.Y.C. MEA 258-93-E Wax-Coated Over Temp.Ratings. 6. CE Certificate: Lead Plated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. 1438-CPR-0054(R1015) 1438-CPR-0056(R1077) 1438-CPR-0053(R1025) 1438-CPR-0057(R1027) —165°F(74°C)Clear Wax,212°F(100°C) Brown 1438-CPR-0052(R1075) 1438-CPR-0058(R1017) Wax. (1) Other colors and finishes are available.Consult factory for details. OrderingInformation (2) UL listed and NYC MEA Approved only. (3) 212°F(100°C)brown wax may be used on 286°F(141°C) Specify: sprinklers when maximum ambient temperatures do not exceed 150°F 1. Model G (66°C).UL Listed,FM Approved,NYC MEA 258-93-E. 2. Deflector (4> FM Approved for R1027 only • Upright • Pendent • Conventional 3. Nominal Orifice 4. Inlet Thread 5. Temperature Rating 6. Finish The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. �' Recycled i1F Paper ® (800)431 1588 Sales Offices + Ii (800)848 6051 Sales Fax Revision lines indicate updated or new data. (914)829 2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.12/20 P/N 9999970005 Bulletin 111 Rev. P co MI Reliable° Model G 1 Recessed Automatic Sprinkler The Most Compact Attractive ,, . - _. • k and Easily Installed Sprinkler Iiito,,, " Ever Designed! #. Features 1. 1 1" (38mm) Total adjustment provided by adjustable inlet versions. 2. 1/2" (13mm) Total adjustment provided by economical standard inlet version. ,� 9 . ., ... • w 3. Adjustable inlet version available with either •a., �„'R ..., ' * '" V -'"' 1" NPT male or female threads eliminating costly reducing coupling. 4. Small diameter escutcheon. 5. Available in brass, chrome or white finish. The Model G Recessed Sprinkler's threaded two-piece 6. Multiple orifice sizes for design flexibility. construction makes initial field installation a very easy 7. Listed by Underwriters Laboratories Inc. & task. It allows ceilings panels to be removed without shutting down the fire protection thus facilitating main- Underwriters' Laboratories of Canada. Ap- tenance of above ceiling services. The adjustable one proved by Factory Mutual Research Corp. inch NPT inlet versions have one and one half inches of & Loss Prevention Council, NYC BS&A No., adjustment which eliminates both the normally required 587-75-SA. reducing coupling and the need to accurately cut drop nipples. This sprinkler can be adjusted after the ceil- ing is in place and even while the system is pressurized eliminating the final corrections to pipe hangers or ceil- Product Description ings that might otherwise be required. Today's modern buildings demand that a sprinkler not The Reliable Model G Automatic Sprinkler is the heart only provide the best fire protection but also achieve an of the Recessed Sprinkler. This sprinkler utilizes the cen attractive appearance. Reliable's Model G Recessed ter strut solder in compression principle of construction. Sprinkler meets both criteria. It combines the fire fighting The fusible alloy, captured in the cylinder of a small sol capability of a proven sprinkler with the smallest practi- der capsule by a stainless steel ball,acts as the trigger of cable recessing unit. Its small profile does not disrupt the the sprinkler. When the fusible alloy melts, the sprinkler overhead aesthetics, and yet one vertical glance upward operating parts spring free from the sprinkler clearing the gives a visual assurance of the finest in fire protection,an waterway and allowing the deflector to distribute the dis automatic sprinkler system. charging water. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Product Description and Installation The Reliable Model G Recessed Sprinkler has been de- This wrench must be used. The wrenching pads of the signed with ease of installation in mind. A choice of three sprinkler easily slip into the rectangular cut-outs of the inlets with up to one inch adjustment coupled with the 1/2" wrench as the outside diameter locates the threaded (13mm) escutcheon adjustment enables most systems cup. A '/2" (13mm) drive ratchet can then be used for to be installed using pre-cut drop nipples. The adjust- installation and tightening. ment can be accomplished after the ceiling installation Figure 5 shows the removal of the wrench. Care should and while the system is pressurized thereby providing be taken during this procedure to avoid hitting the de- sprinkler protection before construction is completed. flector with the wrench. The wrench should be lowered The Non-Adjustable inlet version (Figure 1) Consists until it clears the sprinkler. The installation completed of the Reliable Model G Sprinkler with an attached cup by threading the escutcheon on until it contacts the ceil- recessed in the ceiling. A ceiling hole of 2 1" (57mm) ing. To avoid leaving smudge marks on the ceiling, the diameter is recommended. Reliable Model FEA Flush Sprinkler Escutcheon Wrench The Adjustable inlet version uses the same sprinkler as should be used. the Non-Adjustable inlet version except the 1" of addi- Note' tional adjustment is provided by a telescoping sprinkler inlet section that threads in or out of a stationary Coupling 1. Use hex wrench on Coupling Reducer to tighten Reducer(either 1" male or 1"female)as shown in figures Adjustable Sprinkler into fittings. Do not use RC-1 2 or 3. The Sprinkler-Cup assembly comes attached to Wrench for this purpose. the inlet Coupling Reducer and is retained from separa- 2. Do not install the Model G Recessed Sprinkler in tion past its maximum adjustment length by a snap ring. ceilings which have positive pressure in the space This combination is simply installed after the system drop above. nipple, elbow or tee has been "roughed in" to the dimen Maintenance sions shown in figures 2 or 3. Wrenching means are pro- vided by hex flats on the coupling reducer as depicted in The Model G Recessed Pendent Sprinklers should the figures-do not wrench on any other part of the sprin- be inspected and the sprinkler system maintained in kler. After the ceiling tiles have been cut and installed in accordance with NFPA 25 vs 20. Do not clean sprin- place (a 21/4" [57mm)hole is recommended), the sprin- klers with soap and water, ammonia or any other clean- kler can be adjusted using the RC-1 Concealed Wrench. ing fluid. Remove any sprinkler that has been painted When using the wrench in this application, however, do (other that factory applied) or damaged in any way. A not over-torque beyond the adjustment stops. stock of spare sprinklers should be maintained to allow Figure 4 shows a 1/2" NPT non-adjustable inlet sprin- quick replacement of damaged or operated sprinklers. kler,with the attached sprinkler cup combination inserted Prior to installation, sprinklers should be maintained in into the special Reliable Model RC-1 Installation Wrench. the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. 'ADD 5/IS"FOR PINILE ON 1'SYSTEM l TEE OR ELBOW lr-"I'l� 1 l;.;•--1 1 '- III I r j r -1�OROP�/NPPLE ->--4411-H- - t lli1F- -- -- i-rii + HI u�Iiilill' -4-- __L I I :I i i i"1" 1 I,L_'Ii� —__ _fill_ 'll-J - NOTE I 0 ,__Ild IlU__� o 2 3/16'0/A _ � [33.SJ �=imIMWE CEIL\C I.•ne-,� NOTE I r 1 1 J//" 1"NPT MALE .� '�.��;;^TT" /�. COUPLING 1'NPT FEMALE l.,ll CEILING (�4I COUPLING REDUCER t.. �.._.....__ t�1 / 2 J/�.. J f/I'35/1' Y', ;',;'j� (]O) FACE OF FRYING TO _ I I -' FACE OF DIMENSION �— DROPS NIPPLE w 1"INLET IIIl4X. I"INLET TO CEILING 1/2"ESCUTCHEON —••l ADJUSTM ENT MAX.A`USTMENT DIMENSION [13J ADJUSTMENT T'- SPRINKLERCUP 'fw-n SPRINKLER 3f 014 11EO' CEIL\C �r� 1' -ASSEMBLY+/ CET .�.u.Jl� ASSEMBLY // �� � �..L6 Eii iln-II i '=1 ' I CEILING TTT A 0 CEILING A I DIMENSIONS IN PARENTHESIS/N MILLIMETERS y, Ld I 1�im i ' P / 1/2"ESCUTCHEON Q 5/8 1/2'ESCUTCHEON =v 5/" MAX.ADJUSTMENT �� MAX.ADJUSTMENT -4 2 I. Ion •fusta•e net 11' vae •fusta•e net 1 ll' emae •justa•e net Figure 1 Figure 2 Figure 3 2. Technical Data Total Nominal "K"Factor Approval Sprinkler Sprinkler Inlet Adjustment Orifice U.S. I Metric Thread Organizations Identification Number(SIN) Non-Adjustable 1/2"(13mm) 1/2"(15mm) 5.62 81.0 1/2"NPT(R1/2) 1,2,3,4,5,7 R1015 Non-Adjustable 1/2"(13mm) 7/6"(11mm) 4.24 61.0 1/2"NPT(R1) 1,3,4 R1013 Non-Adjustable 1/2"(13mm) 3/8"(10mm) 2.82 40.6 1/2"NPT(R1/2) 1,3,4 R1011 Non-Adjustable 1/2"(13mm) 17/32"(20mm) 7.96 114.7 1/2"NPT(R1/) 1,3 R1016 Adjustable 11/2"(38mm) 1/2"(15mm) 5.53 79.7 1"NPT Male or Female 1,2,3,4 R1118 Adjustable 11/2"(38mm) 7/16"(11mm) 4.24 61.0 1"NPT Male or Female 1,3,4 R1113 Adjustable 11/2"(38mm) 3/8 (10mm) 2.75 39.2 1"NPT Male or Female 1,3,4 R1117 Adjustable 11/2"(38mm) 15mm 5.53 79.7 R1 Male or Female 5 R1118 "Sprinkler escutcheon provides 1/2"(13mm)of the total adjustment. Adjustable inlets,when used,provide 1"(25mm)of the total adjustment. Temperature Ratings Ordering Information Specify: Sprinkler Rating Maximum Ambient 1. Temperature Rating Classification Temperature 2. Nominal Orifice °F °C °F °C 3. Sprinkler Finish Ordinary 135 57 100 38 4. Escutcheon Finish Ordinary 165 74 100 38 5. Sprinkler Type: Either Non-Adjustable Inlet(Fig. 1) 1" Intermediate 212 100 150 66 male Adjustable Inlet (Fig. 2) 1" Female Adjustable Inlet(Fig. 3) Approval Organizations Finishes (1) 1. Underwriters Laboratories Inc. 2. Factory Mutual Research Corp. Standard Finishes • Light Hazard Occupancies - No limitations Sprinkler Escutcheon • Ordinary Hazard Occupancies - Groups 1 & Bronze Brass 2, Wet Systems Only Chrome 3 Chrome 3. Underwriters Laboratories of CanadaWhite Panted White Painted 4. NYC BS &A No. 587-75-SA Special Application Sprinklerk Escutcheon 5. Loss Prevention Council Bright Brass(2) Bright Brass • XLH, OHI and OHII Occupancies Only Black Plated(2) Black Plated 6. NYC MEA 258-93-E Satin Satin 7. EC Certificate: 1438-CPD-0054 (R1015) Polyester Coated 3> Polyester Coated (1)Other color Finishes available upon request.Consult Factory for details. (2)Only frame,deflector and cap are plated Note: Unless otherwise indicated, Ordinary hazard ap- (3)Only frame and deflector are painted or coated.Operating parts provals are without limitations. 7/16"(11mm)and 3/"(10mm) are chrome plated.UL Listed and MEA Approved only. orifice sprinklers are limited to light hazard occupancies. 1 . . , 40'y 4 li E ri j t, {, lei ,` tl f,; f 1 4 '41{e Figure 4 Figure 5 3. Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • DetectorCorporateOffices check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co., Inc. a Recycled ® (800)431-1588 Sales Offices Paper , Rel I a (80014))829 848 2042051 Sales Fax Revision lines indicate updated or new data. (9 www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.09/17 P/N 9999970006 Bulletin 013 November 2019 ® Models F1 . Standard Response n 0 W Sprinklers o 3 0- Model F156 Sprinkler Types o Standard Upright 0.7 w .. co Standard Pendent - -• - Conventional � �< �` Vertical Sidewall 1 I 0 .. Horizontal Sidewall "'' t' : .0 i. sue Model F156 Recessed Sprinkler Types Upright Pendent Conventional Pendent/F1/F2/FP Horizontal Sidewall Model F142, F1XLH & F128 Sprinkler Types N -, ,,;, Standard Upright . .... ,a1• Standard Pendent - '` Model F142, F1XLH &F128 Recessed Sprinkler Vertical Sidewall Horizontal Sidewall Recessed Types Pendent/F1/F2 Pendent/F1/F2/FP Approval Organizations °` 't` 1. Underwriters Laboratories Inc. and certified for ii,P ' ��� : Canada(cULus) ( 110 f jib' ,,_ `l 2. Factory Mutual Approvals (FM) 3. Loss Prevention Council (LPCB, UK) 4. VdS Schadenverhutung GmbH Recessed Recessed XLH Upright 5. EC Certificate: 0786-CPD-40237 (RA1314) Horizontal Sidewall Pendent/FP 0786-CPD-40253 (RA1325) 0786-CPD-40254 (RA1375) i UL Listing Category #� i;"' . �;` Sprinklers,Automatic&Open (VNIV) 41 ,„ . Product Description XLH Pendent XLH Recessed XLH Recessed The F156, F142, F1XLH & F128 Series Glass Bulb Pendent F1/F2 Pendent FP Sprinkler combines the durability of a standard sprinkler The F156, F142, F1XLH & F128 Series Automatic Sprin- with the attractive low profile of a decorative sprinkler. kler utilizes a 5.0 mm frangible glass bulb.The glass bulb Whether installed on exposed piping or in an office ceil- consists of an accurately controlled amount of special ing, it is functional and attractive. fluid hermetically sealed inside a precisely manufactured Beautifully versatile is the description for the Reliable glass capsule. This glass bulb is specially constructed to Models F156, F142, F1XLH & F128 Series Recessed provide fast thermal response. glass bulb sprinkler. Recessing the F156, F142, F1XLH & At normal temperatures, the glass bulb contains the F128 Series enhances its already low profile decorative fluid in both the liquid phase and in the vapor phase. The appearance, and facilitates a rapid and perfect installa- vapor phase can be seen as a small bubble. As heat is tion. applied, the liquid expands forcing the bubble smaller The recessed escutcheon of the Models F156, F142, and smaller as the liquid pressure increases. Continued F1XLH & F128 are highly adjustable. The two piece con- heating forces the liquid to push out against the bulb, struction makes field installation a very easy and rapid causing the glass to shatter, opening the waterway and task. This also allows ceiling panels to later be removed allowing the deflector to distribute the discharging water. without shutting down the fire protection system, thus fa- The F156, F142, F1XLH & F128 Series Sprinkler tern- cilitating maintenance of above ceiling services. perature rating is identified by the color of the glass bulb capsule as well as frame color where applicable. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Pintle (XLH Only) Deflector l/t ,t\, Load Screw //asher Bulb Cup Frame RIP14. a � 013FG04 Model F142,F1XLH Upright Technical data: Max. Min. Models Nominal K-Factor Response Thread Working Working Temperature Finish Size Pressure Pressure Rating F156 5.6(80 Metric) 250 PSI* V2" NPT See F1XLHF142 4.2(60 Metric) Standard (RY2) 7 PSI "Temperature "Finishee Table" 175 PSI Ratings"Table F128 2.8(40 Metric) Material Data: Frame Deflector Load Screw Pintle Cup Washer Bulb CDA Alloy 260, CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360 DZR Brass CDA Alloy 220 or or or coated with PTFE Adhesive Glass QM Brass or CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape CDA Alloy 510 *Note: Model F156 upright, pendent, and recessed pendent sprinklers (SIN RA1325 and RA1314) are cULus Listed for 250 psi (17 bar). 2. Model F156, Upright, Pendent & Conventional Sprinklers Model F142, F1XLH & F128 Upright & Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench or Model W2 Sprinkler Wrench Installation Data: Nominal Thread Nominal K-Factor Sprinkler Approval Sprinkler Identification Number Orifice Size Height Organization (SIN) US Metric Upright Pendent Standard-Upright(SSU)and endent Deflectors Marked to Indicate Position 1/2"(15mm)(1) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) 1, 2, 3,4,5 RA1325(2)(3)(5)(6) RA1314(2)(3)(5)(6) '/16"(10mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) 1 RA1323(2)(6) RA1313(6) 3/8"(10mm) 1/2" NPT(R1/2) 2.8 40 2.25"(57mm) 1 RA1321(2)(6) RA1311(6) Conventional-Install in Upright or Pendent Position 15mm(1) 1/2" NPT(R1/2) 5.6 80 57mm 3, 4,5 RA1375(5) (1)Refer to Bulletin 024 for Special Response Sprinklers(F1S5-56) (2)cULus Listed corrosion resistant(Polyester coated)sprinkler. (3)Polyester coated FM Approved sprinkler. (4) (5)Polyester coated LPCB&VdS approved sprinkler RA1325,RA1314&RA1375. (6)Electroless Nickel PTFE Plated -UL listed Corrosion Resistant 4,,,,, , , ,,,, illl 4 r 1140 4- ..'. ) ,. Upright Pendent Conventional Model F156, F142, F1XLH & F128 Recessed Pendent Sprinklers(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Thread Nominal K-Factor Sprinkler Sprinkler Identification Number Orifice Size US Metric Height (SIN) 1/2" (15mm) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) RA1314(2) (/16"(10mm) 1/2" NPT(R1/2) 4.2 60 2.25"(57mm) RA1313(2) 3/8"(10mm) Y2" NPT(R1/2) 2.8 40 2.25"(57mm) RA1311(2) (1)Refer to escutcheon data table for approvals&dimensions (2)Electroless Nickel PTFE Plated -cULus listed Corrosion Resistant 2 v4'HOLE Dv. i.,Y 1mm•Du L _ =3 WI _1 rr_ ,"x I/2"REDUCER f' -- --=i1 2 HOLE DIN. EILING mJ I T 1 x 1/2'aEDLeea HOLE IN CEILING I I TURUNTN)G FACE OF FITTING INST SPRINKLER k 'SOIL"OLA.[58.1mm]IGHT �� —_�— WRCNCH 8055� \ / TO ACE OF CEILING DIMENSION CUP --- FI ESCUTXIIAACHFON - 1 AT MAXIMUM RECESS 715 dmm) J AT MINIMUM RECESS=J B 95 CEILING L — /7.mm] FACE OF FITTING ft FSCUTCHEOHd�110� ,, .L■ AF2 ESCUTPHCDII ii�y�!'i TO FACE OF CEILING J/4719mm] y, a) T MAXIMUM RECESS=J/d"(19mm] _ 'MIIli _ ill DIMENSION F2 JUSTMENTON �� .��� MINIMUM RECESS J/BT95mm] I I AT MAXIMUM RECESS= 1-1/2(JBmmJ 1/ADJUSTMENT "(IlT]mm) 1 li;`:11 ,i///i' AT �- I�I II I AT MINIMUM RECESS= 1725.d J ApIuSTMENT 1 Ih (L E1 ESCUTCHEON ,��L--'/ mm l� , 1�. AT MAXIMUM RECESS=7/6722.2mm] k t, ,II i/ 1�N�� (J2mm] AT MINIMUM RECESS=I-5/8741.Jmmi $-�/I ,�, I/ F2 ESCUTFHFOR ``''■ 1.}' AT MAXIMUM RECESS=9/16(Id.3mmJ vi,� AT MAXIMUM RECESS= Y 750.Bmm I-I/B72B.BmmJ ) �.l'I AT MINIMUM RECESS= 1725.4mm) \:�i% AT MINIMUM RECESS=I-5/8741.SmmJ ADJUSTMENT 2 I%,1 DN, 3 VA.DA4. _ t (72.2mmJ [82.BmmJ DIJFLOIC RECESSED PENDENT W/F1 OR F2 ESCUTCHEON RECESSED PENDENT W/FP ESCUTCHEON m,FI:R24 'SPRINKLER NOT FM APPROVED WITH Ft ESCUTCHEON "SPRINKLER NOT FM APPROVED WITH FP ESCUTCHEON Model F156, F142,F1XLH&F128 Ftor F2 Model F156, F142, F1XLH&F128 FP 3. • Model F156 Vertical Sidewall Sprinkler Installation Wrench: Model W2 Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy 4104101100 U.S. Patent No. 6,374,920 Sprinkler Type Deflector to Ceiling Distance (Min.-Max.) Upright 4"(102mm)- 12"(305mm) Pendent 4"(102mm)- 12"(305mm) Installation Data: Vertical Sidewall ---------------- Nominal K Factor Sprinkler Nominal Thread Size Sprinkler Approval 1'1 Identification Orifice US Metric Height Organizations Numbers(SIN) 1/2"(15mm) 1/2" NPT(R1/2) 5.6 80 2.25"(57mm) 1,2,3 RA138501(2)(30) LPC Approval is pendent only,57°C through 141°C ratings. (2)cULus Listed corrosion resistant(Polyester coated)sprinkler. (3)cULus Listed&FM Approved corrosion resistant for lead,wax and wax over lead. (4)Electroless Nickel PTFE Plated -cULus listed Corrosion Resistant Model F156 Horizontal Sidewall Sprinkler Deflector:HSW Installation Wrench: Model W2 Sprinkler Wrench FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON �������4 AT MAXIMUM RECESS = 1 725.4mm) AT MINIMUM RECESS = 3/8[9.5mmJ F1 ESCUTCHEON F2 ESCUTCHEON AT MAXIMUM RECESS = 1-3/8 734.9mm] AT MAXIMUM RECESS = 3/4 719mm] AT MINIMUM RECESS = 2-1/16 752.4mm] AT MINIMUM RECESS = 3/8 79.5mmJ F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8741.3mm] 2 1/4"HOLE DIA. -•-7/8. AT MINIMUM RECESS= 2-1/16 752.4mm] [57.2mm] (3.2mm7 I"X 1/2"REDUCER 4"-12" 1 15/16" DIA. 1����� 49.2mm [101.6m LING T.8mmJ [ ] � � -�-- 2 27/32"DlA. CEILING TO [72.2mmJ DEFLECTOR 1111t' ,111 TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS. F7 ESCUTCHEON 3/4 719mm]ADJUSTMENT F2 ESCUTCHEON 1/2 772.7mm]ADJUSTMENT RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4"- 6"[101.6MM - 152.4MM]CEILING TO DEFLECTOR. Horizontal Sidewall Note: For Recessed HSW Sprinklers use installation wrench GI-R2. FM and cULus permits use with Fl or F2 escutcheons for "Light Hazard"only. Installation Data:Horizontal Sidewall Nominal K Factor Sprinkler A roval Organizations Height pp g Sprinkler Nominal Orifice Thread Size Identification US Metric Light Hazard Ordinary Numbers(SIN) Hazard 1/2"(15mm) 1/2"NPT(R1/2) 5.6 80 2.63"(67mm) 1, 2 1 RA1335(1x2)(3)(4) ")cULus Listed corrosion resistant(Polyester coated)sprinkler. (2)cULus Listed&FM Approved corrosion resistant for lead,wax and wax over lead. (3)Polyester coated FM approved sprinkler. (4)Electroless Nickel PTFE Plated -cULus listed Corrosion Resistant 4. Application Maintenance Model F156,F142,F1XLH,F128&Model F156,F142,F1XLH& The Model F156, F142, F1XLH & Model F156, F142, F1X- F128 Recessed sprinklers are used in fixed fire protection systems: LH & F128 Recessed Sprinklers should be inspected and Wet,Dry,Deluge or Preaction. Care must exercised that the orifice the sprinkler system maintained in accordance with NFPA size,temperature rating,deflector style and sprinkler type are in ac- 25. Do not clean sprinklers with soap and water, ammonia cordance with the latest published standards of the National Fire or any other cleaning fluid. Replace any sprinkler which has Protection Association or the approving Authority Having Jurisdic- been painted (other than factory applied) or damaged in lion Installation. any way. A stock of spare sprinklers should be maintained Installation to allow quick replacement of damaged or operated sprin- Model F156, F142, F1XLH & F128 Series sprinklers are stan- klers. Prior to installation, sprinklers should be maintained dard response sprinklers intended for installation as specified in in the original cartons and packaging until used to minimize I NFPA 13.They must also be installed with the Model W2 Sprinkler the potential for damage to sprinklers that would cause im- Wrench specifically designed by Reliable for use with these sprin- proper operation or non-operation. klers. Temperature Ratings The Model F156, F142, F1XLH & F128 Recessed Sprinklers Sprinkler Max.Ambient Bulb are to be installed with a maximum recess of 3/4 inch 19mm .The Classification Temperature ( ) °C °F Temp. Color Model F1,F2,and FP Escutcheon illustrated are the only recessed Ordinary 57 135 100°F(38°C) Orange escutcheon to be used with the Model F156,F142,F1XLH&F128 Ordinary 68 155 100°F(38°C) Red Recessed Sprinklers.The use of any other recessed escutcheon Intermediate 79 175 150°F(66°C) Yellow will void all approvals and negate all warranties. When installing Intermediate 93 200 150°F(66°C) Green Model F156, F142, F1XLH&F128 Recessed Sprinklers use the High('1 141 286 225°F(107°C) Blue Model GFR2 Sprinkler Wrench. Any other type of wrench may Extraa High(11(2 2160 500 47 300°F(149°C) Mauve Ultra 260 500 475 F(246 C) Black damage these sprinklers. (I)Not available for recessed Sprinklers. Note:A leak tight'/2'NPT(R1/2)sprinkler joint can be obtained with (2)cULus listed for SIN RA1325 and RA1314 only. a torque of 8-18 ft-lbs(11-24 N-m). Do not tighten sprinklers over Maximum Working Pressure maximum recommended torque. It may cause leakage or impair- 175 psi (12 bar) ment of the sprinklers. SIN RA1325& RA1314 cULus listed for 250 psi (17 bar) Glass bulb sprinklers have orange covers to protect the bulb dur- 100% Factory tested hydrostatically to 500 psi (34.5 bar) ing the installation process. REMOVE THIS PROTECTION ONLY Finishtlt AFTER THE SYSTEM HAS BEEN HYDROSTATICALLY TESTED Standard Finishes AND, WHEN APPLICABLE,THE ESCUTCHEONS HAVE BEEN Sprinkler Escutcheon INSTALLED. RASCO wrenches are designed to install sprinklers Bronze Brass when covers are in place. Chrome Chrome 6 s Polyester Coated White Painted Ordering Information Special Application Finishes Specify: Sprinkler Escutcheon 1. Sprinkler Model Electrdess Nickel PTFE3x101 Electroless Nickel PTFE 2. Sprinkler Type Bright Brass Bright Brass Black Plated Black Plated 3. Nominal K-Factor Black Paint(3((9) Black Paint 4. Temperature Rating Off White(3((9( Off White 5. Sprinkler Finish Chrome Dull Chrome Dull 6. Thread Type: [1/2" NPT] [ISO 7-1 R'/2] Lead Plated(3x4)(8) 7. Escutcheon Finish (where applicable) wax Coated(3)(4)c6xe1 Note:When Models F156, F142, F1XLH & F128 Recessed Sprinklers Wax Over Lead(3)(4icsuel are ordered,the sprinklers and escutcheons are packaged separately. (1)Other colors and finishes are available on special order.Consult factory for Escutcheon Data t't details.Custom color painted sprinklers may not retain their UL Corrosion resistance listing. (11 SIN:RA1335-cULus and FM permits use with F1 or F2 escutcheons for light (2)200°F(93°C)maximum. hazard only. (3)UL and ULC listed only. (4)155°F to 200°F(68°C to 93°C)ratings only. (5)286°F(141°C)sprinklers may be coated for ambient conditions not exceeding 150°F(66°C). (6)cULus listed"corrosion resistant"applies to SIN Number RA1325(Upright) RA1323 (upright), RA1321(Upright), RA1335 (HSW), RA1385(VSW) and RA1314(Pendent)in standard black or white.Corrosion resistance in other polyester colors is available upon request. (')FM Approved finish as"Polyester Coated"applies to SIN number RA1314, RA1335&RA1325 in standard black or white. (8)FM Approved finish applies only to SIN number RA1335&RA1385. (9)LPCB and VdS Approved finish applies only to RA1325,RA1314 and RA1375. (101cULus listed Corrosion Resistant applies to SIN RA1325,RA1314,RA1323, RA1313,RA1321,RA1311,RA1385 and RA1335 5. Reliable. . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. ' Recycled ReF ®a (800)431 1588 Sales Offices YiW Paper (800)848-2051 Sales Fax (914)829 2042 Corporate Offices Revision lines indicate updated or new data, www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.11/19 P/N 9999970299 Bulletin 014 October 2020 CO ® Model Fl FR Series ReliableQuick Response o Glass Bulb Sprinklers o o cs Model F1FR56 Sprinkler Types .� -. m Standard Spray Upright o NI Standard Spray Pendentill Ili o Conventional Upright/Pendent Vertical Sidewall fp Horizontal Sidewall . � Model F1FR56 Recessed Sprinkler Types Upright Pendent Conventional Standard Spray Pendent tf., -, ,:.- Horizontal Sidewall "" Model F1FR56 Concealed Sprinkler Types In N �`` '" ,;''' Standard Spray Pendent Model F1FR42, F1FRXLH & F1FR28 Sprinkler .' Types Vertical Sidewall Horizontal Sidewall Recessed Standard Spray Upright Pendent/F1/F2 Standard Spray Pendent ..,,, .. Model F1 FR40 Sprinkler Types , „, °r Standard Spray Pendent ° ,�' Model F1 FR42 F1 FR40 F1 FRXLH & F1 FR28 v A .. �' Recessed Sprinkler Types w, , k`, .a,�n Standard Spray Pendent Model F1 FR56LL&F1 FR42LL Low Lead Sprinkler Recessed Concealed Recessed Types Horizontal Sidewall Pendent Pendent/FP Standard Spray Pendent with less than 0.25% Lead Content Listing &Approvals a c, :i The following organizations provide Listings or Approvals � it for various Model F1FR series sprinklers. See the Design and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed specific listings and approvals applicable to each sprin- Pendent F1/F2 kler. Product Description 1. Underwriters Laboratories Inc. and Certified for ;4_ Reliable Model F1FR series sprinklers Canada(cULus) in accordance with ANSI/UL199. are quick response automatic sprin- 414 I, 2. FM Approvals (FM) 3. Loss Prevention Certification Board (LPCB) klers with a glass bulb thermal element. -I, , 4. VdS Schadenverhutung GmbH (VdS) Model F1FR series sprinklers are Stan 5. Underwriters Laboratories Inc. and Underwriters dard Spray sprinklers, with the excep Laboratories of Canada Certified for Health Effects tion of the Model F1FR56 Conventional XLH Recessed to NSF/ANSI Standard 61 Annex G (ULH) sprinkler which is an Old-style/Conven- Pendent FP tional sprinkler. 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- The Model F1FR Series automatic sprinklers utilize a 3.0 CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) mm frangible glass bulb.These sprinklers have demonstrat- (EC) ed response times in laboratory tests which are five to ten 7. WaterMark certified. Certificate Number 23347. times faster than standard response sprinklers. This quick (WM) response enables the Model F1FR Series sprinklers to apply UL Listing Category water to a fire faster than standard-response sprinklers of the Sprinklers,Automatic&Open (VNIV) same temperature rating. Quick Response Sprinkler The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely man- ufactured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid Model F1FR Series sprinklers must be installed with the in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended ute the discharging water. installation torque may cause leakage or impairment of the Model F1 FR Series sprinklers provide a wide range of op- sprinkler. tions where quick-response, glass bulb sprinklers are used: Recessed Sprinklers • Pendent, recessed pendent, upright, horizontal Model F1FR Series Recessed sprinklers are to be installed sidewall, and vertical sidewall deflectors as shown in Fig. 1, Fig. 2,or Fig.3,as applicable to the spe- • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons • Flush, recessed, and concealed installations that are permitted to be used with each Model F1FR Series See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch- Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties. specific Model F1FR series sprinkler configurations. Concealed Sprinklers Model F1FR Recessed Pendent and Recessed Horizon- Model F1FR Series Concealed Pendent sprinklers are to tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig. 4 or Fig. 5,as applicable to the Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent cessed Escutcheon Data table in this Bulletin for listing and and Model F1 FR56LL Concealed Pendent sprinklers have approval information with each specific Model F1FR series a factory-installed Model CCP cup. A protective cap is in- sprinkler. Model F1 and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on (19mm)and 1/2-inch (12.7mm) of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed Model FP recessed escutcheons,shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a 1/2-inch(12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The Model F1 FR56 Concealed Pendent and Model F1 FR56LL cover plate and sprinkler cup assemblies are joined using Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage- Model CCP cover plates.A standard profile Model CCP cov- ment. A choice of two Model CCP cover plate assemblies er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm)or 5/8-inch (8mm) of cover cover plate adjustment. In addition,a low profile Model CCP adjustment. Do not install Model F1FR Series Concealed cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure (8.0mm) of cover plate adjustment. See the Design and In- in the space above. stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The proved cover plate options. Model GFR2 wrench is used to engage the sprinkler wrench- Application ing surfaces and to install the sprinkler in the fitting.Remove the Model F1FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov- Data Sheets, and the requirements of the Authority Hay- ing the wrench from the sprinkler/cup assembly,care should be ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any temperature rating,deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is com- in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and design and installation standards. In addition, Model pushing the cover plate onto the cup. Final adjustment is made F1FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the provided in this Bulletin. cover plate in the counter clockwise direction.After installation, Installation inspect all sprinklers to ensure that there is a gap between the Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above. dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover place.Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with kler system is placed in service for fire protection. Removal Model F1 FR56 Concealed Pendent and Model F1 FR56LL of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with clasp by hand. Do not use tools to remove bulb protectors. which it is not specifically listed my prevent good fire pro- tection and will void all guarantees, warranties, listings and approvals. 2. Technical Data: Sensitivity: Quick-response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar) SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar) Design and Installation Information Nominal Nominal Nominal Orifice Sprinkler Listings K-factor Deflector/ Installation Approval Model Diameter Orientation Height Wrench SIN and Notes US Metric inches mm inches mm Approvals Pendent 2.25 57 W2 RA1411 cULus 2 F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2 Upright 2.25 57 W2 RA1421 cULus 1,2 F1 FR40 4.0 57 3/8 10 Pendent 2.25 57 W2 RA1418 VdS Recessed Pendent 2.25 57 GFR2 RA1418 VdS Pendent 2.25 57 W2 RA1413 cULus 2 F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 Upright 2.25 57 W2 RA1423 cULus 1,2 F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 W2 RA1410 cULus, ULH Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH F1FRXLH Pendent 2.25 57 W2 RA1413 cULus 2 (F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2 with Pintle) Upright 2.25 57 W2 RA1423 cULus 1,2 cULus, FM, Pendent 2.25 57 W2 RA1414 LPCB,VdS, EC, 1,2,3,4 WM cULus, FM, Recessed Pendent 2.25 57 GFR2 RA1414 LPCB,VdS, EC, 1,2,3,4 WM F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 GFR2 RA1414 cULus,VMS,EC, 5,6 cULus, FM, Upright 2.25 57 W2 RA1425 LPCB,VdS, EC, 1,2,3,4 WM "Conventional 2.25 57 W2 RA1475 LPCB,VdS, EC, 4 (Pendent or Upright)" WM Pendent 2.25 57 W2 RA1415 cULus, ULH 1 F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH Concealed Pendent 2.25 57 GFR2 RA1415 cULus, ULH 6 Horizontal Sidewall 2.63 67 W2 RA1435 cULus, FM 1,2,3,7 F1FR56 5.6 80 1/2 15 Recessed Horizontal 2.63 67 GFR2 RA1435 cULus, FM 8 Sidewall F1FR56 5.6 80 1/2 15 Vertical Sidewall 2.25 57 W2 RA1485 cULus, FM, 1,2,3,9 (Pendent or Upright) LPCB (1)cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. (2)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. (3)Available with FM approved Polyester coating in black or white. (4)Available with LPCB and VdS approved Polyester coating. (5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin- klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only. (6)Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment. (7)cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to ceiling distance shall be 4 inches to 12 inches(102mm to 305mm).FM Approval of the F1FR56 Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (8)cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (9)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. Listed and Approved Temperature Ratings Ordinary Temp. Intermediate Temp. High Temp. Classification Classification Classification Deflector/ 100°F(38°C)Max.Ambient 150°F(65°C) Max.Ambient 225°F(107°C)Max. Model Orientation Temp. Temp. Ambient Temp. 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C)Temp. Temp. Rating Temp.Rating Temp. Rating Temp. Rating Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1FR28 Recessed Pendent cULus Upright cULus F1FR40 Pendent VdS Recessed Pendent VdS Pendent cULus F1FR42 Recessed Pendent cULus Upright cULus F1FR42LL Pendent cULus, ULH Recessed Pendent cULus, ULH Pendent cULus F1FRXLH Recessed Pendent cULus Upright cULus Pendent cULus, FM, LPCB,VdS, EC,WM Recessed Pendent cULus, FM, LPCB,VdS, EC,WM F1FR56 Concealed Pendent* cULus,WM cULu MS,EC, cULus,WM WUpright cULus, FM, LPCB,VdS, EC,WM "Conventional LPCB,VdS, EC,WM (Pendent or Upright)" Pendent cULus, ULH F1FR56LL Recessed Pendent cULus, ULH Concealed Pendent* cULus, ULH Horizontal Sidewall cULus, FM F1FR56 Recessed Horizontal cULus, FM Sidewall F1FR56 Vertical Sidewall(Pen cULus, FM, LPCB dent or Upright) * Model F1FR56 Concealed Pendent and F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C)temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Deflector/ Model F1 Model F2 Model FP Model Orientation (Fig. 1 &3) (Fig. 1 &3) (Fig.2) SIN 3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA1413 F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410 F1FR42XLH Recessed Pendent cULus cULus cULus RA1413 F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus,VdS,EC,WM RA1414 EC,WM VdS, EC,WM F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 4. 2 1/4"HOLE DIA. J [57.2mm] 1 15/16"DIA J [49.2mm] L_---_—_—_-1 s_=-Is--�r i TURN COLLAR IT T 1" X 1/2" REDUCER UNTIL TIGHT AGAINST SPRINKLER I WRENCH BOSS \ \ I / FACE OF FITTING 0- \ TO FACE OF CEILING DIMENSION I 1Fl ESCUTCHEON II r II AT MAXIMUM RECESS = 1[25.4mm] L ®tea+ J AT MINIMUM RECESS = 3/8[9.5mm] F1 ESCUTCHEON + ��� II /F2 ESCUTCHEON 3/4"(19mm] M 1 -- OIL AT MAXIMUM RECESS = 3/4'[19mm] ADJUSTMENT I ®3sd� IAT MINIMUM RECESS = 3/8[9.5mm] F2 ESCUTCHEON I�,-moo III27.7/// /,1/2[12.7mm] t \ ., 9 I"��ADJUSTMENT `� li, Fl ESCUTCHEON ;II II, 1/8" 1 AT MAXIMUM RECESS = 7/8[22.2mm] 0 Ill [3.2mm] /AT MINIMUM RECESS = 1-5/8[41.3mm] F2 ESCUTCHEON `,\: I V AT MAXIMUM RECESS = 1-1/8 728.6mm] �1 � AT MINIMUM RECESS = 1-5/8"[41.3mm] i ,••2 27/32" D .,IA - [72.2mm] Fig. 1 Model F1FR56,F1FR56LL,F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon L _-! 1 I 1 1" X 1/2" REDUCER 2 5/8" DIA. [66.7mm] HOLE IN CEILING 1 I 2 5/16" DIA. [58.7mm] CUP L — — J CEILING FACE OF FITTING TO FACE OF CEILING ®���.. DIMENSION -- Itii Illlli- !!!IIII Ii jT MAXIMUM RE = 1 /2mm] ii �I T MINIMUM RECESS = 1[25.4mm] ��! ., AT MAXIMUM RECESS = 9/16[14.3mm] 1 `/1 �� /2(12.7mm] y,,,��` AT MINIMUM RECESS = 1[25.4mm] ADJUSTMENT ,,���M_,_�m.,,, 3 �1/4" DIA. -. [82.6mm] I-472 Model F1FR56,F1 FR56LL,F1FR42,F1 FR40,F1FR42LL,F1FRXLH&F1FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. FACE OF FITTING TO FACE OF CEILING DIMENSION Fl ESCUTCHEON j/ A AT MAX/MUM RECESS = 1"[25.4mm) AT MINIMUM RECESS = 3/879.5mm] Fl ESCUTCHEON F2 ESCUTCHEON AT MAXIMUM RECESS = 1-3/8[34.9mm] AT MAXIMUM RECESS = 3/4"[19mm] AT MINIMUM RECESS = 2-1/16'[52.4mm] AT MINIMUM RECESS = 3/8"[9.5mm) F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8[41.3mm] 2 1/4" HOLE DIA. 1/8„ AT MINIMUM RECESS = 2-1/16[52.4mm] (57.2mm) ` [3.2mm] 1" X 1/2" REDUCER n"I 1 u"udl --r,� (1) 11111 1 15/16" DIA. )nm Il}�������I11�=— "^ei� 4 —12 xix � =_, [101.6mm-304.8mm] [49.2mm] iiiii--r I�,IIIIIIIIII. �; 2 27/32" DIA. CEILING TO ""' (72.2mm] DEFLECTOR TURN COLLAR UNTIL TIGHT AGAINST WRENCH BOSS.SPRINKLER Fl ESCUTCHEON 3/4[19mm] ADJUSTMENT F2 ESCUTCHEON 1/2[12.7mm] ADJUSTMENT OUFGOJE RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" — 6" [101.6MM — 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig.3 Model F1 FR56 Recessed Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon 1" x 1/2" REDUCING TEE OR ELBOW ''''''''; — _, _ r —' 2 5/8" DIA. __ 2 5/16" DIA — HOLE IN CEILING CUP _.11111 [>•r- - ��il®�`d ��III 1 1/2" MAX. f-- , , FACE OF FITTING : _TO FACE OF CEILING ,,/-1 .1L ti I aIII ,,,,,,,, DIMENSION CEILING1 /iiiiii/ i 1/2" MAX. Itigy,....:2=:...— COVER ADJUSTMENT 15/16" COVER PLATE ASSEMBLY t 3 5/16" DIA. SPRINKLER / CONCEALED, 1/2" ADJUSTMENT o17FGO1A Fig.4 Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth 1/2-inch(12.7mm)adjustment-Model CCP cover plate 6. 7" x 1/2" REDUCING TEE OR ELBOW — - - - }} - - - -+- --- +4 - - - — 1---- r-- P -2 5/8" DIA. 2 5/16" DIA �, HOLE IN CEILING L_W J CUP —JkilliiiIi 1 1/2 MAX. _�il� FACE OF FITTING """"I/: '' TO FACE OF CEILING // LpI,i ,//////// DIMENSION � ,x,,,,,,, CEILING _—_ - - 5/16" MAX. 3/4" COVER ADJUSTMENT COVER PLATE / f ASSEMBLY 3 5/16" DIA. SPRINKLER CONCEALED, 5/1 6" ADJUSTMENT 017FG02A Fig. 5 - Model F1 FR-56/1-1 FR56LL Concealed Pendent sprinkler with low profile 5/16-inch (8.0mm) adjustment- Model CCP cover plate Maintenance Material Data The Model F1 FR Series sprinklers should be inspected and Frame: DZR Brass, QM Brass,or Low Lead Brass the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220, 260,or 510 any other cleaning fluids.Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544 or gentle vacuuming. Replace any sprinkler which has been Cup: CDA Alloy 651 or 693 painted(other than factory applied)or damaged in any way. Washer: Nickel Alloy 440 or 360,coated with PTFE A stock of spare sprinklers should be maintained to allow Adhesive Tape quick replacement of damaged or operated sprinklers. Bulb: Glass Finishes (1) Standard Finishes Sprinkler Escutcheon Cover plate ) Ordering Information Bronze Brass Chrome Specify: Chrome Plated Chrome Plated White 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42] Polyester Coated(4X5)(6) White Painted [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] Special Application Finishes Sprinkler Escutcheon Cover plate') 2. Sprinkler Deflector/Orientation: [Pendent][Recessed Electroless Nickel Electroless Nickel Bri ht Brass Pendent][Upright][Conventional][Horizontal Sidewall] PTFE(') PTFE g [Recessed Horizontal Sidewall][Vertical Sidewall] Bright Brass13' Bright Brass Black Plating 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2] Black Plated Black Plated _ Black Paint Black Paint12u6' Black Paint Off White 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F Off White121c61 Off White Satin Chrome (68°C)][175°F(79°C)][200°F (93°C)][286°F (141°C)] Chrome Dull Chrome Dull 5. Sprinkler Finish ")Other finishes and colors are available on special order. Consult the 6. Escutcheon Model: [F1][F2][FP] factory for details.Custom color painted sprinklers may not retain their UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, 7. Escutcheon Finish (where applicable) unless specified otherwise. 8. Cover plate Model: [standard profile CCP 1/2-inch (2) cULus Listed only. (12.7mm) adjustment][low profile CCP 5/16-inch (3) 200°F(93°C)maximum. (8.0mm) adjustment] (4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and 9. Cover plate Temperature Rating: [135°F(57°C)for use RA1415 (Pendent) in standard black or white. Corrosion resistance in with Ordinary Temperature sprinklers][165°F (74°C) other polyester colors is available upon request. for use with Intermediate Temperature sprinklers] (5) FM Approvals finish as"Polyester coated"applies to SIN Number 10. Cover plate Finish RA1414,RA1435 and RA1425 in standard black or white. (6)LPCB and VdS Approved finish applies only to RA1425,RA1414,RA1418 (VdS)and RA1475. Note: When Model F1 FR Series Recessed sprinklers are ordered, the (7)cULus listed Corrosion Resistant sprinklers and escutcheons are packaged separately. 7. liti i4iiiiinfaiiikaft4tiMiiliiO4.4v4WW44#44#404i d}i4liAdd.... 'ItihtkiteMiii F6titOrtMiiiitOki?hardouwrtiiutt o.1430tri.feNkeiks,ftti t ..... YM#. irkiiNYtdislitii#4dQfi.. 3x, Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled Relbit (800)431 1588 Sales Offices Paper ia (800)848 6051 Sales Fax Revision lines indicate updated or new data. (914)829 2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.10/20 P/N 9999970300 Bulletin 132 February 2021 O Model GL112 Series Sprinklers Storage& Non-Storage Sprinklers K11.2 (160 metric) Product Description Reliable Model GL112 upright and pendent sprinklers are standard coverage quick response sprinklers utilizing a levered fusible allow solder link thermal element in 165°F / .r (74°C)or 212°F(100°C)temperature rating.These sprinklers 'JP 01 are intended for use in hydraulically calculated control mode density area(CMDA) storage and non-storage occupancies in accordance with the area/density curves of NFPA 13 or other f applicable standards. Upright Pendent The Model GL112 sprinkler is FM Approved as a quick response storage and non-storage sprinkler when used in accordance with FM Global Property Loss Prevention Data Model GL112 Series Sprinklers Sheets. The Model GL112 is provided with 3/4-inch NPT or ISO 7-R3/4 threads. Sprinklers without guards are installed using the Model H wrench. For use as an intermediate level sprinkler,the Model GL112 I upright sprinkler is available with a factory installed water shield. Various other water shields, guards, or guard/shield s, options are also available for both upright and pendent models (please refer to Technical Specifications on following pages). Sprinkler guards or guard/shields may be installed in the field or factory installed. Use of the Model JV sprinkler Upright with Factory Installed Shield wrench is required for installation where a guard is added to the sprinkler prior to threading the assembly into a fitting. Model GL112 Specifications Table A Sprinkler Identification Listings and Style Number(SIN) Approvals Sensitivity K-Factor Upright R3226 FM Quick Response 11.2 (160 metric) Pendent R3216 FM www.reliablesprinkler.com Model GL112 Upright Sprinkler SIN R3226 Technical Specifications Sensitivity Style:Upright Quick Response Threads:3/4"NPT or ISO 7-1 R3/4 Nominal K-Factor: 11.2(160 metric) Temperature Ratings Max.Working Pressure: 175 psi(12 bar) 165°F(74°C) 212°F(100°C) �-- — Material Specifications 11 Thermal Sensor:Nickel Alloy Solder Link Sprinkler Frame:Brass Alloy Guards&Water Shields Guard&Water Shield i \ Button/Cup:Brass Alloy D-8 Guard ' Sealing Assembly:Brass with PTFE Water Shield(factory installed) Load Screw:Bronze 111 Deflector:Bronze Alloy Sprinkler Wrench }1r Levers:Bronze Alloy Model H Ejection Spring:Stainless Steel Model JV(when guard is installed prior to .Nµ.... make-in) Sprinkler Finishes Standard(Bronze)Only Listings and Approvals FM Approved ------�~ Model GL112 Upright Components and Dimensions Figure 1 f 4-1/2"(114 mm) . 1-7/8" _ (48 mm) --- Deflector it r je_a_e _1_1 t lI r 01111 N.11Load . Frame Screw Optional:1i.�r lFactory � 7`2� , Installed • �_ 2-3/a•no mm) ll". �� Lever Arms Water � � � RASCO �� Shield RASCO Cup/Seal O Assembly �._� Solder Link Thermal Element ---- 132FG01 COMPONENTS DIMENSIONS Bulletin 132 'tellablewww Page 2 of 5 February 2021 .reliablesprinkler.com Model GL112 Pendent Sprinkler SIN R3216 Technical Specifications Sensitivity Style:Pendent Quick Response Threads:3/4"NPT or ISO 7-1R3/4 Nominal K-Factor:11.2(160 metric) Temperature Ratings Max.Working Pressure:175 psi(12 bar) 165°F(74°C) —= 212°F(100°C) Material Specifications Thermal Sensor:Nickel Alloy Solder Link Guards&Water Shields D-8 Guard 0/1 Sprinkler Frame:Brass Alloy D 9 Guard&Water Shield Button/Cup:Brass Alloy S-2 Water Shield Sealing Assembly:Brass Alloy with PTFE }� Load Screw:Bronze Deflector:Bronze Alloy Sprinkler Wrench Levers:Bronze Alloy Model H Ejection Spring:Stainless Steel Model JV(when guard is installed prior to make-in) Sprinkler Finishes Standard(Bronze)Only Listings and Approvals FM Approved Model GL112 Pendent Components and Dimensions Figure 2 3-1/4"(83 mm) OQSVEI ODSVIi Frame Cup/Seal (tiIp 1 2-3/4"(70 mm) Assembly Optional S-2 Water Shield Lever Arms Solder Link ���� Thermal Element Load Screw Deflector 1-1/2" (38 mm) 132FG02 COMPONENTS DIMENSIONS Bulletin 132 BEM Page 3 of 5 February 2021 www.reliablesprinkler.com Model GL112 Commodity Selection and Design Criteria Overview Table B Storage Type NFPA FM Global Sprinkler Type CMDA Storage Response Type QR QR System Type Pendent-Wet Pendent-Wet Upright-Wet, Dry, Preaction Upright-Wet, Dry, Preaction Temperature Rating °F(°C) 165, 212(74, 100) 165, 212 (74, 100) Roof Construction See NFPA 13 See FM Global 2-0 Ceiling Slope See NFPA 13 See FM Global 2-0 Maximum Coverage Area See NFPA 13 See FM Global 2-0 Minimum Coverage Area See NFPA 13 See FM Global 2-0 Maximum Spacing See NFPA 13 See FM Global 2-0 Minimum Spacing See NFPA 13 See FM Global 2-0 Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0 Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0 Open Frame, Single, Double, Multiple Row,or Portable Rack Storage of Class See NFPA 13 See FM 2-0&8-9 I - IV Commodity and Group A Plastic Solid Pile or Palletized Storage of Class See NFPA 13 See FM 2-0&8-9 I - IV Commodity and Group A Plastic Idle Pallet Storage See NFPA 13 See FM 2-0, 8-9&8-24 Rubber Tire Storage See NFPA 13 Pendent N/A Upright-See FM 8-21 Rolled Paper Storage See NFPA 13 See FM 8-21 Flammable Liquid Storage See NFPA 13 See FM 7-29&8-9 Aerosol Storage See NFPA 13 See FM 7-31 Auto Components in Portable Racks See NFPA 13 N/A Bulletin 132 ® EI Page 4 of 5 February 2021 www.reliablesprinkler.com Installation Maintenance The Reliable Model GL112 QR sprinkler must be installed Reliable Model GL112 sprinklers should be inspected and the according to NFPA Standards or the appropriate FM Global sprinkler system maintained in accordance with NFPA Data Sheets for all area/density methods of design as well as 25,as well as the requirements of any Authorities Having the Authority Having Jurisdiction. Jurisdiction. Use only the Model H sprinkler wrench for sprinkler installation Prior to installation,sprinklers should remain in the original or use the Model JV wrench to install the sprinkler/guard cartons and packaging until used.This will minimize the assembly(Figure 3). Any other type of wrench may damage potential for damage to sprinklers that could cause improper the sprinkler. Damaged sprinklers must be replaced operation or non-operation. immediately. Do not clean sprinklers with soap and water, ammonia liquid or Note: Sprinklers should be tightened between 14-20 lb-ft any other cleaning fluids. Remove dust by gentle vacuuming (19-27.1 N•m)torque. Exceeding the maximum recommended without touching the sprinkler. torgue may cause leakage or impairment of the sprinklers. Replace any sprinkler which has been painted (other than Wrenches Figure 3 factory applied). A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Failure to properly maintain sprinklers may result in inadvertent operation or non-operation during a fire event. Model H Wrench (sprinkler) Guarantee For the Reliable Automatic Sprinkler Co., Inc.guarantee,terms, and conditions,visit www.reliablesprinkler.com. Ordering Information Specify the following when ordering. Model GL112 Sprinkler Model JV Wrench (with guard installed) • [Upright][Pendent] [Upright with factory installed shield] Temperature Rating • [165°F(74°C)] [212°F(100°C)] Guard/Shield • See Technical Specifications Sprinkler Wrench • [Model H][Model JV(required with pre-installed guards)] N O ti 0) 0) 0) 0) z Bulletin 132 Page 5 of 5 February 2021 MEM www.reliablesprinkler.com Worldwide www.tyco-fire.com tIICii Contacts Model EC-25 (CMDA and CMSA Applications) 25.2 (360) K-factor (360) Upright Sprinkler Extended Coverage General storage and non-storage applica- tions. When used in conformance with : Description applicable FM Global Property Loss p Prevention Data Sheets, the Model *') ", The TYCO Model EC-25, Extended EC-25 Upright Sprinkler provides low Coverage 25.2K Upright Sprinkler hydraulic demand,the spacing advan is a UL Listed, standard response, tages of extended coverage, and the extended coverage Control Mode obstruction benefits of an upright r Density Area (CMDA) sprinkler for sprinkler. , storage applications. It is also FM For more information on applica- `'_"' Approved as a quick response, tions and benefits of the Model EC-25 extended coverage CMDA sprinkler Upright Sprinkler, refer to the available and as a Control Mode Specific Appli- White Papers at www.tyco-fire.com. cation (CMSA) sprinkler, as well as FM Approved for storage and non-stor- NOTICE age applications. The Model EC-25 Upright Sprinklers Technical When used in accordance with described herein must be installed Data National Fire Protection Association and maintained in compliance with this (NFPA) 13, smoke vents and draft cur- document, as well as with the applica- Approvals tains are not required as specified in the ble standards of the NFPA, in addition UL and C-UL Listed:CMDA 2015 edition of the International Building to the standards of any other authori- (Standard Response) Code(IBC) and International Fire Code ties having jurisdiction. Failure to do so (IFC)for CMSA sprinklers with an RTI of may impair the performance of these ( Approved:CMDA and CMSA Q 50 or less and a design of 12 or fewer devices. (Quick Response) sprinklers. NYC Approved under MEA 355-01-E The owner is responsible for main- These sprinklers offer a maximum coy- taining their fire protection system Approvals only apply to the service condi- erage area of 196 ft2 (18,2 m2), which and devices in proper operating con tins indicated in the Design Criteria section. is almost double the area offered by dition. Contact the installing contrac- Finish standard coverage sprinklers used for tor or sprinkler manufacturer with any Natural Brass similar applications. questions. Physical Characteristics The Model EC-25 Upright Sprinklers Frame Brass comply with the criteria for the pro- Sprinkler Deflector Copper tection of retail stores as described in Compression Screw Stainless Steel NFPA 13. Identification HStrut MMONEL ONEL Where the FM Approval is utilized, the Number (SIN) Link Assembly Solder,Nickel Model EC-25 Upright Sprinkler has Button Brass undergone full-scale fire Sealing Assembly. Beryllium Nickel w/TEFLON successfullyat Global for ceiling-only Refer to Table A for sprinkler identifica- Ejection Spring INCONEL testing g- y tion number. Deflector Nut Brass Response Time Index(RTI) IMPORTANT Less than or equal to 50(m-s)0.5 Refer to Technical Data Sheet Additional Technical Data TFP2300 for warnings pertaining to Refer to Table A for additional techni- regulatory and health information. cal data. Always refer to Technical Data Sheet TFP700 for the "INSTALLER Operation WARNING" that provides cautions The fusible link assembly is co with respect to handling and instal- prised of two link halves that m are joined lation of sprinkler systems and corn- ponents. Improper handling and together by a thin layer of solder.When installation can permanently damage the rated temperature is reached, the a sprinkler system or its compo solder melts and the two link halves nents and cause the sprinkler to fail separate,allowing the sprinkler to acti- to operate in a fire situation or cause vate and flow water. it to operate prematurely. Page 1 of 4 AUGUST 2018 TFP213 TFP213 Page 2 of 4 3 10 TEMPERATURE 2-9/16" DIA. RATING (65,0 mm) C Al-It 2 — 1- Frame O4 ��� 2- Deflector r0 alto t -I���rjis Ili i st y_ 1 1 I I I I ( -i j j 1 i I 3- Compression Screw ifll 4- Hook 1 3-3/4" 5- Strut (95,3 mm) 6- Link Assembly II^ 5 7- Button .1 6 1_! L /I 1� 9/16" 8 Gasketed Spring Plate �� '�'" 14,3 mma� ■ ■ ( ) 9- Ejection Spring ?gyyq;. 9 WRENCH = NOMINAL 10- Deflector Nut a 1 FLATS MAKE IN 411111 •ISO 7-R1 pipe thread can be 1 ! 8 �— provided on special request. 7 �_ ! S� 1" NPT* 1 1 FIGURE 1 MODEL EC-25 UPRIGHT SPRINKLER,25.2K EXTENDED COVERAGE Design Item Description Criteria Sprinkler Identification Number(SIN) TY9128 K-factor(gpm/psi)(Ipm/bar) 25.2 gpm/psis(362,9 Ipm/bar'=) UL and C-UL Listing Criteria Temperature Rating°F(°C) 165°F(74°C) 212°F(1o0°C) NFPA 13,Chapters 12 thru 20— Density/Area Design Thread Size 1 in.NPT or ISO 7-R 1 The TYCO Model EC-25 Extended Sprinkler Orientation Upright Coverage Upright Sprinklers (TY9128) are UL and C-UL Listed for installs- Maximum Working Pressure,psi(bar) 175 psi(12,1 bar) tion in accordance with the extended TABLE A coverage upright spray sprinkler MODEL EC-25 UPRIGHT SPRINKLER requirements of NFPA 13 or other appli- TECHNICAL DATA cable NFPA standards when used in conjunction with the following • Minimum distance between sprin- normally associated with high guidelines: klers is 8 ft(2,44 m). temperature sprinklers. As such, • Protection of extra hazard and high- • Minimum flow requirement is based the Model EC-25 Upright Sprinklers piled storage occupancies where on the design density applied are listed storage sprinklers having area/density design criteria are over the actual coverage area per a K-factor greater than 11.2 (161,4) provided. sprinkler. For example,when: and having ordinary and interme- diate temperature ratings of 165°F • Unobstructed or non-combustible A sprinkler spacing is 14ft x 12 ft-6 in. or 74°C and 214°F or 101°C. Conse- obstructed construction. (4,3 m x 3,8 m) or 175 ft2 (16,3 m2), quently, the Model EC-25 Sprin- • Model EC-25 Sprinklers, having and the design density is 0.6 gpm/ft2 klers, in accordance with NFPA 13, been specifically tested and Listed (24,4 mm/min), the sprinkler design may be used in conjunction with the for non-combustible obstructed flow rate is 105 gpm (397 Lpm) and density curves for high temperature construction, are suitable for use the required design pressure is sprinklers. within trusses or bar joists having 17.4 psi(1,2 bar). • NFPA obstruction rules for Extended non-combustible web members • The minimum clearance between Coverage Sprinklers must be utilized. greater than 1 in. (25,4 mm) when the deflector and the top of storage applying the 4 times obstruction is 36 in. (0,9 m). For clearances of System Type criteria rule defined under"Obstruc- 36 in. (0,9 m) up to 48 in. (1,21 m), Wet pipe, dry pipe, and pre-action tions to Sprinkler Discharge Pattern the minimum design pressure is systems are acceptable. Development." 22 psi (1,52 bar). For clearances FM Ap proval Criteria • Maximum coverage area per of 48 in. (1,21 m) and greater, the sprinkler is 196 ft2(18,2 m2). minimum design pressure is estab- FM Loss Prevention Data Sheets lished by the minimum flow require- 2-0,3-26,and 8-9 • Maximum distance between sprin- ment. However, the pressure can TYCO Model EC-25 Extended Cover- klers is 15 ft (4,6 m) when the never be less than 7 psi (0,5 bar). age 25.2K Upright Sprinklers(TY9128) coverage area does not exceed are FM Approved to be utilized in accor- 144 ft2(13,4 m2), and the maximum • Ordinary and intermediate temper- dance with the following guidelines. distance between sprinklers is ature rated Model EC-25 Upright 14 ft (4,3 m) when the coverage Sprinklers have been investigated Application area does not exceed 196 ft2 for use in high-piled storage occu- The Model EC-25 Extended Coy- (18,2 m2). pancies at the hydraulic demand erage Upright Sprinklers are TFP213 Page 3 of 4 Storage Type NFPA FM Global Sprinkler Type CMDA CMDA/CMSA Response Type SR OR System Type Wet/Dry/Preaction Wet Temperature Rating°F(°C) 165°F(74°C) 165°F(74°C) 212°F(100°C) 212°F(100°C) Open Frame(i.e.,no solid shelves),Single,Double,Multiple- Row,or Portable Rack Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9 B Plastics Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9 B Plastics Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0,8-9,and 8-24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3 Roll Paper Storage Refer to NFPA 13 Refer to FM 8-21 (Refer to the Standard) Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM 7-29 (Refer to the Standard) t Aerosol Storage (Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31 Automotive Components in Portable Racks Refer to NFPA 13 N/A (Control mode only;refer to the Standard) N/A-Not Applicable I TABLE B MODEL EC-25 UPRIGHT SPRINKLER COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FM Approved ceiling-level Storage 100 ft2(9,3 m2).The maximum distance NFPA 13—Alternative System Sprinklers for storage occupancy between sprinklers is 14 ft(4,3 m).The Design (CMSA)Criteria hazards and other similar high heat minimum distance between sprinklers The TYCO Model EC-25 Extended Cov- release type fires. When compared is 10 ft(3,05 m). with other FM Approved Storage Sprin- erage Upright Sprinklers(TY9128)have with other Model C-25 Upright Sprin- Note: When a wall or obstruction successfully undergone large-scale klkler provides low hydraulic demand, makes a minimum spacing of 10 ft fire tests at FM Global to comply with the hya of (3,05 m)impossible, consult FM Global the current edition of NFPA 13.As such, the spacinga , and the advantagesFM of Global extendedobstruc- Property Loss Prevention Data Sheet NFPA 13 may be utilized for design covtion benefits of an upright sprinkler. 2.0 for applicable guidelines. options with the Model EC-25 Upright Sprinkler Location Sprinklers for providing ceiling-only Model EC-25 Upright Sprinklers should Locate sprinklers with respect to protection. be used in conformance with applica- the ceiling/roof in accordance with This allows for the protection of Pallet- ble FM Global Property Loss Preven- FM Global Property Loss Prevention ized,Single, Double,and Multiple Row tion Data Sheets. Data Sheet 2.0. Open Racks. Protection is up to 30 ft Hydraulic Design (9,1 m) of Cartoned, Unexpanded bstructions To determine the hydraulic design for O Group A Plastic Commodities in a the Model EC-25 Upright Sprinkler refer Follow the obstruction requirements maximum 35 ft (11 m) ceiling con- to the applicable FM Global Property as detailed in FM Global Property Loss dition with extended spacing up to Loss Prevention Data Sheet. Prevention Data Sheet 2.0. 196 ft2 (18,2 m2). This protection is System Type Other Details delivered while maintaining very rea- Wet pipe systems only All other design details should be in sonable flow and pressure require- accordance with FM Global Property ments. Pipe sizes as well as water Sprinkler Spacing Loss Prevention Data Sheet 2.0 as well supply requirements can now be kept The maximum coverage area per as any other applicable FM Global Data to a minimum when compared to other sprinkler is 196 ft2 (18,2 m2). The Sheet. design methods for high piled storage minimum coverage area per sprinkler is challenges. TFP213 Page 4 of 4 NRENCInstallation Inspection, testing, and maintenance must be performed as indicated below H The TYCO Model EC-25 Extended and in accordance with the local ECESS Coverage 25.2K Upright Sprinklers are requirements and/or national codes. to be installed in accordance with this Any impairment must be immediately section. corrected. The"' Damage to the fusible Link Assembly The owner is responsible for the inspec- + during installation can be avoided by tion, testing, and maintenance of their � !f ijll`I� fire protection system and devices in V, handling the sprinkler using only the frame arms and the appropriate sprin compliance with this document,as well "FITTING SIDE" kler wrench. Do not grip or apply any as with the applicable standards of any TOWARDS SPRINKLER , force to the fusible Link Assembly. authorities having jurisdiction.Contact FITTING Damaged sprinklers must be replaced the installing contractor or product immediately. manufacturer with any questions. A leak tight 1 in. NPT sprinkler joint Automatic sprinkler systems are rec- FIGURE 2 should be obtained by applying a ommended to be inspected, tested, W-TYPE 1 minimum-to-maximum torque of and maintained by a qualified Inspec- SPRINKLER WRENCH 20 to 30 lb-ft(26,8 to 40,2 N•m).Higher tion Service in accordance with local levels of torque may distort the sprin requirements and/or national codes. When used in accordance with kler inlet with consequent leakage or Limited NFPA 13, smoke vents and draft cur- impairment of the sprinkler. tains are not required as specified in the Note:Install the Model EC-25 Upright 2015 edition of the International Building Sprinkler in the upright position. Warranty Code(IBC)and International Fire Code (IFC)for CMSA sprinklers with an RTI of Step 1. With pipe thread sealant For warranty terms and conditions,visit 50 or less and a design of 12 or fewer applied,hand-tighten the sprinkler into www.tyco-fire.com. sprinklers. the sprinkler fitting. Do not apply any Construction Type force to the Link Assembly,and handle Ordering the Model EC-25 Upright Sprinkler only In accordance with NFPA 13 for by the Frame arms. Procedure Extended Coverage Sprinklers for High Piled Storage. Step 3. Wrench-tighten the Model Contact your local distributor for avail Obstruction Criteria avail- EC-25 Upright Sprinkler using only the ability.When placing an order,indicate Follow Sections 8.8.5.1, "Extended 2) 1 Suly en Wrench(Ref.Figure ande the full product description and part Coverage Obstruction Guidelines for 2) and by full ly engaging (seating) the number(P/N). Sprinkler Discharge Pattern Develop wrench on the sprinkler wrench flats. ment"; 8.12.5.2 and 8.12.5.3, "ESFR Step 4. After installation, inspect the Sprinkler Assemblies Obstruction Criteria," for obstructions Link Assembly of each Model EC-25 Specify:Model EC-25 Extended Cover that prevent the pattern from reaching Upright Sprinkler for damage. In par- age 25.2K Upright Sprinklers(TY9128), the hazard below. ticular, verify that the Link Assembly (Natur I Brass peraturenish, rating), with Exception: When using Model EC 25 and Hook are positioned as illustrated EC-25 Upright S Sprinkler, anycon- inFigureo and thatt, the Link Assembly 165°F° (10o C) P/N 58-450-1-265 14 p has not been bent, creased, or forced ( tinuous obstruction 4 in. (100 mm) or out of its normal position in any way. Special Order in less accordancellbepermitted wit ed to be13,ignosecred n Damaged sprinklers must be replaced Sprinkler Assemblies with immediately. 21.5.3.2.3. ISO 7-R 1 Thread Connection Specify:Model EC-25 Extended Cover- Deflector Distance below Ceiling Care and age 25.2K Upright Sprinklers(TY9128) Follow NFPA 13, Section 8.8.4 for with ISO 7-R 1 thread connection, allowed deflector distances below Maintenance (specify temperature rating), with ceiling. Natural Brass finish, P/N(specify): Clearance to Storage The TYCO Model EC-25 Extended Cov 165°F(74°C) P/N 58-451-1-165 Minimum 36 in.(0,9 m)from the deflec- erage 25.2K Upright Sprinklers must be 212°F(100°C) P/N 58-451-1-214 tor to the top of storage required. maintained and serviced in accordance with this section. Sprinkler Wrench Maximum Distance Before closing a fire protection system Specify W-Type 1 Sprinkler Wrench, between Sprinklers main control valve for maintenance P/N 56 872 1 025 14 ft(4,3 m) work on the fire protection system Minimum Distance that it controls, obtain permission to between Sprinklers shut down the affected fire protection 10 ft(3,0 m) system from the proper authorities and notify all personnel who may be affected by this decision. 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 ,' �� e 2018 Johnson Controls.All rights reserved.MI specifications and other Information shown were current as of document revision date and are subject to change without notice. Johnson ,' NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association, MONEL and INCONEL are registered trademarks of Special Metals Corporation; Controls TEFLON is a registered trademark of DuPont Bulletin 157 February 2021 MII Reliabl ® Model F3QR56 Dry K5.6 (80 metric) D Quick-Response, -11 CY Standard Spray Sprinklers 1 N Features 1. Available in the following configurations: :, • Pendent with standard escutcheon • Pendent with Model HB extended escutcheon • Pendent with Model FP recessed escutcheon • Pendent with Model F1 recessed escutcheon is I • Concealed Pendent with Model CCP cover plate • Horizontal Sidewall with Standard escutcheon 1' • Horizontal Sidewall with Model HB extended escutch Pendent Pendent/HB eon Horizontal Sidewall with Model FP recessed escutch (See Fig. 1) (See Fig. 2) • eon (FM Standard Response) • Horizontal Sidewall with Model F1 recessed escutch- eon (FM Standard Response) • Upright 2. Available with 1" NPT, IS07-1R1, 3/4" NPT, or IS07- 1 R3/4 inlet fitting. 3. 3/4" NPT inlet fittings permit replacement of older 3/4" ,,:= inlet dry sprinklers without changing to a larger sprinkler fitting. Recessed FP Pendent Concealed 4. Sprinklers, escutcheons, and cover plates are available (See Fig. 3) (See Fig.4) in a wide variety of standard and special application fin- ishes. 5. White polyester, black polyester, and Electroless Nickel `, PTFE (ENT) finish sprinklers are cULus Listed as Corro- sion Resistant. 6. Available with cULus Listed 250 psi (17.2 bar) pressure s' rating for Dry Pendent and select HSW configurations. t' ° . FM Approved for 175 psi (12 bar). Product Description Recessed F1 Pendent Horizontal Sidewall Model F3QR56 Dry sprinklers are quick-response, standard (See Fig. 5) (See Fig. 6) coverage sprinklers with a nominal K-Factor of 5.6(80 metric). Available in Dry Pendent, Dry Horizontal Sidewall, and Dry Up- right configurations, Model F3QR56 Dry sprinklers all use a 3 4µ mm glass bulb operating element. See the Temperature Rat- i ings table in this Bulletin for available temperature ratings. Mod- :� t el F3QR56 Dry sprinklers are intended for installation on wet- pipe, dry-pipe, or preaction sprinkler systems in accordance i , with NFPA 13, FM Property Loss Prevention Data Sheets, and Horizontal Sidewall/HB Recessed FP other applicable installation standards. (See Fig. 7) Horizontal Sidewall Model F3QR56 Dry Pendent and Sidewall sprinklers are avail- (See Fig.8) able with a variety of escutcheon options as illustrated in Figs. I. 1 through 3 and Figs. 5 through 9. In addition, Model F3QR56 i. " K Dry Pendent sprinklers are also available with the Model CCP conical concealed cover plate as illustrated in Fig. 4. Available r . sprinkler, escutcheon, and cover plate finishes are identified in ` the Finishes table in this Bulletin. The Model F1 escutcheon, Model FP escutcheon,and Model CCP cover plate are the only recessed escutcheons and cover plate listed for use with Model Recessed F1 F3QR56 Dry sprinklers;the use of any other recessed escutch- Horizontal Sidewall eon or cover plate with Model F3QR56 Dry sprinklers will void (See Fig. 9) Upright all guarantees,warranties, listings and approvals. (See Fig. 10) Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Inlet fittings are available with 1"NPT,ISO 7-1 R1,3/4"NPT,or See the Available Configurations, Listings, and Approvals ISO7-1 R3/4 threads.Sprinklers with 3/4"NPT and ISO7-1 R3/4 table in this Bulletin for further information on Model F3QR56 inlet fittings are intended primarily for replacement of existing Dry sprinklers. 3/4"or IS07-1 R3/4 inlet dry sprinklers, but may also be used in new installations. Available Configurations, Listings, and Approvals Available Sprinkler Sprinkler Escutcheon or Listings and Inlet Identification Model Cover Plate Length Approvalsm Threads Number (See Figs. 1-9) (SIN) Standard 2" to 36" Escutcheon (50 to 900 mm) HB Extended Escutcheon F1 Recessed cULus, NYC 3/4" NPT or Escutcheon 3-1/2"to 36" IS07-1 R3/4 (90 to 900 mm) FP Recessed Escutcheon F3QR56 Dry CCP Cover Plate Pendent Standard 2"to 48" R5714 Escutcheon (50 to 1200 mm) HB Extended Escutcheon 1" NPT F1 Recessed cULus, FM, NYC or Escutcheon 3-1/2"to 48" IS07-1 R1 (90 to 1200 mm) FP Recessed Escutcheon CCP Cover Plate Standard 2"to 48" Escutcheon (50 to 1200 mm) HB Extended Escutcheon cULus(2), NYC(2) 3/4" NPT or F1 Recessed 3-1/2"to 48" IS07-1 R3/4 Escutcheon (90 to 1200 mm) FP Recessed F3QR56 Dry Escutcheon Horizontal Sidewall Standard 2" to 48" R5734 Escutcheon (50 to 1200 mm) cULus(2), FM13>, NYC(2) HB Extended 3-1/2" to 48" Escutcheon (90 to 1200 mm) 1" NPT or F1 Recessed IS07-1 R1 Escutcheon 3-1/2"to 48" cULus12>, FP Recessed (90 to 1200 mm) FM13>I4>, NYC(2) Escutcheon F3QR56 Dry N/A 5"to 48" cULus(2) 1" NPT or R5724 Upright (127 to 1200 mm) ISO7-1 R1 (1)For available temperature ratings and finishes see the Temperature Ratings and Finishes tables,respectively,in this Bulletin. (2)cULus Listing and NYC for Light Hazard and Ordinary Hazard only. (3)FM Approved for Light Hazard only. (4)Model F3QR56 Dry Horizontal Sidewall with Model F1 or Model FP recessed escutcheon are FM Approved as Standard Response. 2. Listing and Approval Agencies See the Available Configurations, Listings, and Approvals table in this Bulletin for listings and approvals applicable to each available configuration. 1. Listed by Underwriters Laboratories, Inc. and UL Certified for Canada (cULus) 2. Certified by FM Approvals (FM) 3. Permitted in New York City based on UL Listing per Local Law 33/2007 (NYC) Technical Data Nominal K-Factor: 5.6 gpm/psi12 (80 L/min/bar12) Sprinkler Listing or Approval Deflector to Ceiling Distance Maximum Working Pressure F3QR56 Dry cULus, NYC See note below 250 psi(17.2 bar) Pendent FM See note below 175 psi(12 bar) 4"to 6" 250 psi(17.2 bar) F3QR56 Dry cULus,NYC Horizontal Sidewall 4"to 12" 175 psi(12 bar) FM See note below 175 psi(12 bar) F3QR56 Dry Upright cULus See note below 175 psi(12 bar) Note: Deflector distance to be in accordance with applicable NFPA, FM,or other agency requirements. Information is provided only when additional clarification is necessary. Temperature Glass Bulb Color Sprinkler Cover Plate Maximum Ceiling Listings and Classification Temperature Rating Temperature Rating Temperature Approvalso> Orange 135°F(57°C) Ordinary 135°F(57°C) 100°F(38°C) cULus, FM,NYC Red 155°F(68°C) I Intermediate Yellow 175°F(79°C) 165°F(74°C) 150°F(66°C) cULus, NYC IIntermediate Green 200°F(93°C) 165°F(74°C) 150°F(66°C) cULus, FM,NYC None 225°F(107°C) cULus, FM(2),NYC High Blue 286°F(141°C) 165°F(74°C) 150°F(66°C) cULus, NYC ("For listed and approved sprinkler,escutcheon,and inlet configurations see the Available Configurations,Listings,and Approvals table in this Bulletin. (2)High temperature classification is FM Approved with Standard and Model HB escutcheons only. Finishes4 Component Sprinkler Escutcheono> Cover Plate Bronze Brass(3) White Paint Standard Finishes White Polyesteri21 White Polyester Chrome Chrome Chrome Electroless Nickel PTFE(2) Type 316 Stainless Steel Satin Chrome Special Application Finishes Black Polyester(2) Black Polyester Black Paint Custom Color Paint Custom Color Polyester Customer Color Polyester Black Plating (1)Standard and Model HB escutcheons are supplied with both the can and escutcheon finished.Model F1 escutcheons are supplied with both the collar and es- cutcheon finished.Model FP escutcheons are supplied with the escutcheon finished;the cup is galvanized or stainless steel with no further finish. (2)cULus Listed as a Corrosion Resistant Sprinkler. (3)Brass finish available for standard,Model F1,and Model FP escutcheons only. (4)Dry upright sprinkler available in standard bronze only. 3. r . Model F3QR56 Dry Pendent Sprinkler with Standard Escutcheon (SIN R5714) "A"Dim. 2"to 48"(51mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 2"to 36"(51mm to 914mm)in 1/4"(6mm)increments for 3/4"connections rz s7 j Hill I I 1iIIi' 11,h I1_-1 __klllll -_-0 111111 I B11111 I; II 'I'll I I 1111111 1 ___ 1 � "'r- --j� `I_ ��z 1-- ---J E I=-1 r I==1 ' L -_-- J System Fitting ` UI" Inlet Fitting I 2-1/8" "A" Dimension [54mm] Dia. Hole in Ceiling 1-1/4" II Sprinkler Can [32 mm] Escutcheon Adjustment Escutcheon I 15/32" t� I •txj4: 3 A Ceiling [12mm] Iiiiinumpolialimim Nominal Escutcheon Position 4 -- j 1/4" [6 mm] 1-5/8" Escutcheon Adjustment 4 [41 mm] �u.1/4" [6 mm] i Nominal Protrusion 3" -- [76 mm] COMDRYDETI DIA. Fig. 1 Note:The sprinkler can protrudes 1/4"when escutcheon is in nominal position. Escutcheon adjustment provides-'/a"(-6mm)to+11/4" (+32mm)"A"dimen- sion adjustment range. Sprinkler Guard: Model C2 4. Model F3QR56 Dry Pendent Sprinkler with Model HB Extended Escutcheon (SIN R5714) "A"Dim. 3'/2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2" to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections rz s� h71- fY 7 r Iwo II will I RIIIII 4 _ -An Imo I I MIIIII 1�1 $III1I1I I I n1II 'I----�L'� _-1 Iml '-- 7-'1T�---J ?- L J System tee } Inlet fitting "A" Dimension 2-1/2" [64 mm] Dia. Hole in Ceiling 1/2" [13mm] Escutcheon Adjustment ArtfriffArl I 1 t " Cell ings: • 1-1/4" I [32mm] Escutcheon Nominal Position of Escutcheon I Sprinkler Can 1/2" [13mm] Escutcheon Adjustment Deflector distance below ceiling is 3-1/2" COMDRYDET2 (89mm) minimum, 4-1/2" (114mm) maximum. 3-1/2" [89 mm] Escutcheon I Dia. Fig.2 Note: The sprinkler can protrudes 11/4"when escutcheon is in nominal position. Escutcheon adjustment provides-'/2"(-12.7mm)to+'/2"(+12.7mm)"A" dimension adjustment range. Sprinkler Guard: Model C2 5. Model F3QR56 Dry Pendent Sprinkler with Model FP Recessed Escutcheon (SIN R5714) "A"Dim. 31/2""to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 3/2 to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections r2 s1 -—— —— j , : 'd 1 1 II ' - I _1 1_ _ V a�l t iu C1 Ls11 ` Th. (--Z -- 1 r I- I Li L_I I_J System Tee 1.11V\ Inlet Fitting 2-5/8" [67 mm] Dia, -1.-- "A" Dimension Hole in Ceiling II Sprinkler 1/4" [6 mm] Cup Escutcheon Adjustment WWI Escutcheon � ' Ceiling �' l t,tt, f' �',-�1' VII0 3/4" [19 mm] Nom. Nominal V. Escutcheon Position 3 7/32" 1/4" [6 mm] Escutcheon Adjustment [82 mm] Dia. COMDRYDET3 Fig. 3 Note:Do not install the Model F3QR56 Dry Pendent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space above. 6. Model F3QR56 Dry Pendent Sprinkler with Model CCP Cover Plate (SIN R5714) • "A"Dim. 31/2' to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections rZ J--I --- ---- ---- i( --- 4 --- r II I---rii pp _ i_ ii 11 ',Hi I 1 psi;i; r_ I I l ' __I I__ISystem Tee --._ \ -/ Inlet Fitting 1 2-1/2" [64 mm] Dia. "A" Dimension Hole in Ceiling i Sprinkler Cup i 3/16" [5 mm] Model CCP 1/2 Cover Plate Adjustment lirMJ Cover Plate Assembly Ceiling ' / [22 8" Nominal Cover fff Plate Position 3/16" [5 mm] Cover Plate Adjustment •0 3-5/16" [84 mm] Dia. COMDRYDET4 Fig.4 Note:Do not install the Model F3QR56 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have positive pressure in the space above. 7. Model F3QR56 Dry Pendent Sprinkler with Model F1 Recessed Escutcheon (SIN R5714) "A"Dim. 31/2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections. r-z s7 iII I I i i i i - _I _ I_ 1 _ \\ i� II 11 ,i,ir I li,i,i, �I i\1/-- -4ft, ---i �� L--- 1--L _J' ' L- System Tee i i 1 U Inlet Fitting 2-1/4" [57 mm] Dia. 1--.. ..— Hole in Ceiling "A" Dimension Collar 1/4" [6mm] Escutcheon Adjustment ' 1 mm] 1/8" 1 '� Ceiling , [3 1 4 Nominal Escutcheon ---- Position --Escutcheon 1/4" [6 mm] Escutcheon Adjustment 2-27/32" _ [72 mm] Dia. COMDRYDET5 Fig. 5 8. Model F3QR56 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon (SIN R5734) "A"Dim. 2"to 48"(51 mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 2" to 36"(51mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling o 4" [102 mm] Min. 12" [305 mm] Max. ►I 15/32" [12mm] Sprinkler Can 2-3/32" \,_ System Fitting \ [53 mm] i Inlet Fitting _ - A 1 // � __� , 1 '""✓ NJ 1 I iii "� 5/8"[16 mm] ni I_-J-_' _ — 3" lit \\\ 1 // /I [76 mm] `\,== / r� 2-1/8" J---\ [54 mm] Dia. 1/4"[6mm] Nominal Protrusion Hole in Wall —. 1/4"[6 mm] Escutcheon Adjustment COMDRYDET6 1-1/4" [32 mm] .► Nominal Escutcheon Position Escutcheon Adjustment "A"Dimension Fig. 6 Note:The sprinkler can protrudes 1/4"when escutcheon is in nominal position. Escutcheon adjustment provides-'/4"(-6mm)to+11/4" (+32mm)"A"dimen- sion adjustment range. 1 9. Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model HB Escutcheon (SIN R5734) "A"Dim. 3v2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2 to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling ro � I 4" [102mm] Min. Escutcheon 12"[305mm] Max. Sprinkler Can System Tee 2 3/32" Inlet Fitting f [53mm] ► 1_ ,___., [ �,\ ,a M , '/ 5/8"[!6mm] 3-1/2 >-�` [89mm] _ -- -' - Escutcheon Dia. 2 1/2" Dia. [64mm] 1-1/4" 1-1/4"[32mm] Nominal Protrusion Hole in Wall --W.- [32mm] ---- 1/2" [13mm] Escutcheon Adjustment • COMDRYDET7 1/2" 13mm [ ] — Nominal Position Escutcheon — --11-- of Escutcheon Adjustment "A"Dimension Fig. 7 Note: The sprinkler can protrudes 11/4"when escutcheon is in nominal position. Escutcheon adjustment provides-'/2"(-12.7mm)to+'/z"(+12.7mm) "A" dimension adjustment range. 10. Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model FP Recessed Escutcheon(SIN R5734) • "A"Dim. 31/2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2 to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling Nom. ' _ _ 1-1/4" Escutcheon [32 mm] 4"[102 mm]Min. Sprinkler Cup =a3cULus,NYC:6"[152 mm]Max. System Tee FM: 12"[305 mm] Max. Inlet Fitting IL t_`1 1 / 1, ����II IIIIIIIIIIIII�6IIIII [16mm] 5/8" r 1111111111111 �_;I 13-7/32' _] __�J [82 mm] Dia. 2-1/2" [64 mm] Dia. Hole in Wall 1/4"[6 mm] Escutcheon Adjustment COMDRYDET8 1/4"[6 mm] • Nominal Escutcheon Position Escutcheon Adjustment "A"Dimension OW- Fig.8 Note:Do not install the Model F3QR56 Dry Horizontal Sidewall sprinkler with the Model FP escutcheon in walls which are positively pressurized with respect to the protected space. 11. • Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model Fl Recessed Escutcheon (SIN R5734) "A"Dim. 31/2"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2" to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling Nom. i -••• — 1-3/4" 1/8" [44 mm] Escutcheon [3 mm] Collar 4"[102 mm] Min. cULus, NYC:6"[152 mm] Max. System Tee FM: 12"[305 mm] Max. Inlet Fitting 'iii'iiiilliillI________ 11111 11111� l 5/8"[16 mm] i01111al ir---- 1 i ---t_J [72 mm] Dia. I 2-1/4"[57 mm] Dia. Hole in Wall •. 1/4"[6 mm] Escutcheon Adjustment • N Nominal Position COMDRYDET9 1/4"[6 mm] — of Escutcheon Escutcheon Adjustment --• "A"Dimension Fig. 9 12. Model F3QR56 Dry Upright(SIN 5724) • Order Dimensions 5"to 48"(127 mm to 1219 mm) u 4 iii oliminimi Note: Customer is responsible for determining correct deflector distance below structure above. Order Dimension 1 Inlet Fitting KO System Tee 1 - _J 1 j__, COMDRYDETI O J ` 7 lq I wild I I mill II II _� _ I_ — < is II i �II�'' �i i i i L s Z J Fig. 10 13. MINIMUM EXPOSED BARREL LENGTH WHEN CONNECTED TO WET PIPE SPRINKLER SYSTEM NOTE: STANDARD DRY PENDENT IS SHOWN, HOWEVER, MINIMUM EXPOSED BARREL LENGTH APPLIES TO ALL STYLES OF DRY SPRINKLERS CONNECTED TO A WET PIPE SYSTEM. WET PIPE EXPOSED BARREL AMBIENT AMBIENT TEMPERATURE T- -rI TEMPERATURE ___ \ __ -1" , II 1 NOTE: TEE MAY BE IN ANY 40'F/4'C I SOF/70'C I 60'F/16'C J_ EXPOSED TO - --LII--+-- I�III --Ii-ORIENTATION FOR WET PIPE DISCHARGE END EXPOSED MINIMUM BARREL LENGTH"* „' nn� ' 1 .I'"' 1 SYSTEMS. OF SPRINKLER.(FACE OF FITTING TO TOP OF CEILING)•++ l�r----I 1- -J 1 mom L__.kIit____ IN. (MM) IN. (MM) IN. (MM) L.' -1 I-zJ —_ 40T(CC) 0 0 0 —— 30F(-1'C) 0 0 0 MillIF HUMIDITY AND TEMPERATURE DIFFERENTIAL CAUSES CONDENSATION ON THE EXPOSED DRY (-TC) 4(100) 0 0 - _- -- SPRINKLER, CONSIDER WRAPPING THE EXPOSED 20F BARREL WITH INSULATION, FOAM INSULATING TAPE OR EQUIVALENT. 10'F(-12'C) 8(200) 1 (25) 0 OF(-18'C) 12 (300) 3(75) 0 MINIMUM (HEATED AREA) I SEAL THE CLEARANCE SPACE -10'F(-23'C) 14(350) 4(100) 1 (25) EXPOSED AROUND THE SPRINKLER TO AVOID BARREL I LEAKAGE OF AIR INTO THE PROTECTED -20'F(-29'C) 14(350) 6(150) 3(75) LENGTH AREA AND CONSEQUENT FORMATION OF CLEARANCE CONDENSATE AROUND THE FRAME, WHICH -30'F(-34'C) 16(400) 8(200) 4(100) DIMENSION HOLE COULD INHIBIT OPERATION OR CAUSE PREMATURE OPERATION. SEE BELOW FOR -40'F (-40'C) 18(450) 8 (200) 4(100) RECOMMENDED METHODS. -50'F(-46'C) 20 (500) 10(250) 6(150) _ -60'F(-51'C) 20(500) 10(250) 6 (150) ® BEIBEIMEEEE II - EEBEEREEE + FOR AMBIENT TEMPERATURES EXPOSED TO THE DISCHARGE ® _'. -INSIDE SURFACE OF END OF THE SPRINKLER THAT OCCUR BETWEEN THE VALUES 41113111332933 IMISEEEriINSULATION, WALL, OR LISTED, USE THE NEXT COOLER TEMPERATURE. ® BEEBEIEBE CEILING ++ THE MINIMUM EXPOSED BARREL LENGTH IS NOT THE SAME t AS THE "A"DIMENSION. THE MINIMUM EXPOSED BARREL __ LENGTH IS BASED ON A PROPERLY SEALED PENETRATION WITH A MAXIMUM WINO VELOCITY ON THE EXPOSED SPRINKLER OF �� 30 MPH (48 KM/H). LONGER EXPOSED BARREL LENGTHS WILL THERMAL ,Lr, ESCUTCHEON Imi HELP AVOID FREEZING OF THE WET PIPING WHERE HIGHER BARRIER gi,li WIND VELOCITY IS EXPECTED. 'tl� ++ THE MINIMUM EXPOSED BARREL LENGTH IS MEASURED �n� DISCHARGE END OF SPRINKLER FROM THE FACE OF THE FITTING TO THE INSIDE FACE OF THE INSULATION, WALL, OR CEILING LEADING TO THE COLD SPACE, WHICHEVER IS CLOSEST TO THE FITTING. PROTECTED (NON-CONDITIONED) AREA RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS SYSTEM PIPING (DRY SPRINKLER WITH STANDARD ESCUTCHEON SHOWN) PIPING \II-2191-7- -n-w:::-.F\ r -01---1 1 -F1F= 1%; v- hIIIH-F--------iiiili - ° - 1iFIV---F--I---t-1k-k- - Lr-1-_r_-LJ Ls--11 r-zJ L J f Li ii„ (HEATED AREA) (HEATED AREA) III„ MINIMUM MINIMUM EXPOSED EXPOSED BARREL BARREL LENGTH DECKTITE FLASHING INSIDE FACE SEAL LENGTH (SEE ABOVE) RASCO#4003910 (SEE ABOVE 5 7 (RECOMMENDED) -I ) CLEARANCE HOLE I INSULATED FREEZER, OR COOLER STRUCTURE - iii OR EXTERIOR FRAMING pm um w //AI/ 1 IN////S. .///////IIt' iI///I//a. (PROTECTED AREA) 1I`Y�II DISCHARGE END OF (PROTECTED AREA) �It��I� DISCHARGE END OF DYA� INRY COLD AREAR DRY SPRINKLER 1Y/ IN COLD AREA COMDRYDET11 Fig. 11 14. *CAUTION* RELIABLE DRY SPRINKLERS MAY BE INSTALLED IN A LISTED CPVC SPRINKLER FITTING, ONLY UPON VERIFICATION THAT THE FITTING DOES NOT INTERFERE WITH THE SPRINKLER'S INLET. Do not install dry sprinklers with standard inlets into CPVC fittings that have an internal obstruction;this will damage the sprinkler,the fitting,or both. Short inlet("PL")versions of Reliable dry sprinklers are available that may or may not be compatible with fittings having internal obstructions in existing installations.Sprinklers with the short inlet("PL")should only be installed in CPVC fittings of wet-pipe systems. In all cases,verify sprinkler and fitting dimensions prior to installation to avoid interference. Internal Obstruction No Internal Obstruction rirFemale / Female 1�111 Pipe �0 Pipe k `/ Thread Ot Thread 04 0 .r - CPVC Fitting with Internal Obstruction CPVC fitting INo Internal Obstruction Shorter _ Longer MI— Inlet -- Inlet Male 1 _ Male Pipe -- Pipe Thread IIIIII Thread III„ --mrri i I-—-------------—1=.-- Dry Sprinkler Dry Sprinkler Short Inlet ("PL") Standard Inlet BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION COMDRYDET2 Fig. 12 15. 3 { 1 • t Fig. 13-Model F3R Wrench --------- ----- Ili P �1£yy ix3N} t tad t �..vuwpt w9 7:„ �: xn E3?— Fig. 14-Model XLO2 Wrench 16. MATERIAL SPECIFICATIONS 0 ITEM# DESCRIPTION MATERIAL SPECIFICATION �`�-1 r� 0 _ 1 FRAME _ BRASS PER UNS C83600 ® 2 DEFLECTOR BRONZE PER UNS C51000 AlpIhr 3 LOAD SCREW BRASS PER UNS C22000 4 SEAT ADAPTOR BRASS ALLOY PER UNS C36000 t10 ,�/ 5 BULB INSERT COPPER ALLOY PER UNS C31400 6 GLASS BULB GLASS W/GLYCERIN SOLUTION �, 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 _ 1 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 `i 10 YOKE BRASS ALLOY PER UNS C38000 11 INLET BRASS ALLOY PER UNS C35330 11111 12 CAP BRASS ALLOY PER UNS C54400 13 SPRING WASHER/SEAL PTFE COATED BERYLLIUM NICKEL N 14 FLIP DISK BRASS ALLOY PER UNS 054400 PAINTED OR PLATED MILD STEEL,EXCEPT s CAN/ESCUTCHEON FOR TYPE 316 STAINLESS STEEL FOR 15 SPRINKLERS WITH ENT FINISH 0 0 (PIPE WRENCH MAY ONLY BE USED ON OUTER STEEL PIPE OF SPRINKLER) / .,...,, Okl .I 1'� COMDRYDET13 gilw0 CD tt © \1E APPEARANCE OF DEFLECTOR MAY VARY DEPENDING ON MODEL O '1 O „ _3�tTeA,s. Fig. 15 1 17. Installation Instructions When used on wet pipe systems, Reliable Model F3QR56 3a.Alternatively, where access to the outer tube of the dry sprinklers may be installed in ductile or malleable cast iron sprinkler is available, the Model F3QR56 Dry sprin- threaded tees, or CPVC tees and adapters upon verification kler may be installed using a pipe wrench. The pipe that the sprinkler inlet fitting does not interfere with the interior wrench shall only be permitted to interface with the of the fitting(see Figure 12). galvanized steel outer tube portion of the sprinkler When used on dry pipe systems, Reliable Model F3QR56 (Item #8 in Fig. 15). Do NOT wrench any other por- dry pendent sprinklers MUST ONLY BE installed in the outlets tion of the sprinkler assembly. A pipe wrench can in- of ductile or malleable cast iron threaded tees on horizontal pipe stall the sprinkler into the fitting with a large amount such that the inlet of the sprinkler protrudes above the bottom of torque; consideration should be given to the need level of the pipe. for future removal of the sprinkler because the instal- When used on dry pipe systems, Reliable Model F3QR56 lation torque will have to be matched or exceeded to dry sidewall and dry upright sprinklers may be installed in duc- remove the sprinkler.The recommended minimum to tile or malleable cast iron threaded tees, or CPVC tees and maximum installation torque is 22 - 30 lb-ft (30—40 adapters upon verification that the sprinkler inlet fitting does not N-m) for 1" NPT and IS07-1 R1 sprinklers, and 14 - interfere with the interior of the fitting(see Figure 12). 20 lb-ft (19—27 N-m) for 3/4" NPT and IS07-1 R3/4 DO NOT install Reliable dry sprinklers into elbows or cou- sprinklers. plings,welded outlets,mechanical tees,or gasket sealed CPVC 4. Standard and Model HB escutcheons can be installed fittings. by slipping the escutcheon over the can until the es- Dry sprinklers connected to wet pipe systems must be in- cutcheon is seated against the ceiling or wall. Model F1 stalled as indicated in Figure 11 and as required by NFPA 13 escutcheons are installed by pressing the escutcheon with the Exposed Minimum Barrel Length located in a heated onto the collar until the escutcheon is seated against area. the ceiling or wall. The Model FP escutcheon is installed An orange protective clip is factory installed on the sprinkler by pressing or threading the escutcheon into the cup to protect the glass bulb thermal element from damage. The by hand; the escutcheon can be tightened against the clip should remain in place during installation of the sprinkler ceiling or wall by turning the escutcheon in a clockwise and be removed when the sprinkler system is placed in service. direction and removed by turning the escutcheon in a Sprinklers with 3/4" NPT and IS07-1 R3/4 inlets are supplied counter-clockwise direction. To install the Model CCP with a protective cap on the inlet that must be removed before cover plate, first remove the protective clip. Install the installation. Model CCP cover plate on the sprinkler by pressing or Use the following steps for installation: threading the cover plate into the cup by hand; the cov- 1. Cut a hole in the wall or ceiling directly in-line with the er plate can be tightened against the ceiling by turning outlet of the fitting. See the Installation Data table for the the cover plate in a clockwise direction and removed by recommended hole diameter based on the escutcheon turning the cover plate in a counter-clockwise direction. or cover plate option selected. 5. Remove the orange protective clip when placing the 2. Apply pipe joint compound or PTFE tape to the male sprinkler system in service. threads of the sprinkler's inlet fitting. 3. Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table.The Mod- el F3R wrench is designed to be inserted into the groves in the sprinkler's wrench boss as shown in Fig. 13. The Model XLO2 wrench is designed to fit into the cup and engage the wrench boss as shown in Fig. 14. Do NOT wrench any part of the sprinkler assembly other than the wrench boss. When inserting or removing the wrench from the sprinkler, care should be taken to prevent dam- age to the sprinkler. The sprinkler is then tightened into the pipe fitting to achieve a leak free connection. The recommended minimum to maximum installation torque is 22 - 30 lb-ft (30—40 N-m) for 1" NPT and IS07-1 R1 sprinklers, and 14 - 20 lb-ft (19—27 N-m) for 3/4" NPT and IS07-1 R3/4 sprinklers. 18. Installation Data Sprinkler Suggested Hole Diameter in Installation Required Centerline of Sprinkler Model Escutcheon or Cover Plate Wall or Ceiling Wrench Tube/Inlet to Finished Ceiling Vertical Dimension* Standard Escutcheon 2-1/8"(54 mm) F3R HB Extended Escutcheon 2-1/2"(64 mm) F3R F3QR56 Dry Not F1 Recessed Escutcheon 2-1/4"(57 mm) XLO2 Pendent Applicable FP Recessed Escutcheon XLO2 2-1/2"(64 mm) CCP Cover Plate XL02 Standard Escutcheon 2-1/8"(54 mm) F3R 4-5/8"to 12-5/8" HB Extended Escutcheon 2-1/2"(64 mm) F3R (118 mm to 321 mm) F3QR56 Dry F1 Recessed Escutcheon 2-1/4"(57 mm) XLO2 cULus, NYC Horizontal 4-5/8"to 6-5/8" Sidewall FP Recessed Escutcheon 2-1/2"(64 mm) XLO2 (118 mm to 168 mm) F1 Recessed Escutcheon 2-1/4"(57 mm) XL02 FM 4-5/8"to 12-5/8" FP Recessed Escutcheon 2-1/2"(64 mm) XLO2 (118 mm to 321 mm) F3QR56 Dry N/A 1-1/2"(38mm) F3R Not Applicable Upright *Note:Based on 5/8"(16 mm)centerline of sprinkler tube/inlet to defector vertical distance. Maintenance The Model F3QR56 Dry Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. 4. Inlet Fitting: [Long — Standard Inlet Fitting][Short "PL" — Do not remove the factory applied thermally sensitive wax fillet Wet Pipe Systems only] between the bulb supporting cup and the wrenching boss. Do 5. Sprinkler Temperature Rating: See Temperature Ratings not replace this wax with a substitute substance. table An Alternate substance may interfere with proper operation of 6. Sprinkler Finish: See Finishes Table the sprinkler. Do not clean sprinklers with soap and water, am- 7. Escutcheon/Cover Plate Finish: See Finishes Table monia or any other cleaning fluids. Remove dust by using a soft 8. Length: brush or gently vacuuming. Replace any sprinkler which has *For dry pendents and dry sidewalls: "A" Dimension been painted (other than factory applied) or damaged in any is from face of tee to face of finished ceiling or wall in way. A stock of spare sprinklers should be maintained to allow 1/4" (6mm) increments. See Fig. 1 through Fig. 9. quick replacement of damaged or operated sprinklers. Prior *For dry uprights: Order dimension is from face of tee to installation, sprinklers should be maintained in the original to top of deflector in 1/4" (6mm) increments. See Fig. cartons and packaging until used to minimize the potential for 10. damage to sprinklers that would cause improper operation or Notes: non-operation. 1. For Dry Upright,customer is responsible for determining the Ordering Information correct deflector distance from structure above. Specify: 2. Length is based on normally gauged pipe thread"make-up" 1. Sprinkler: [Model F3QR56 Dry Pendent SIN R5714] of.600" (15mm) per ANSI B2.1 (approximately 7-1/2 threads). [Model F3QR56 Dry Horizontal Sidewall SIN R5734] [Model F2QR Dry Upright SIN R5724] 2. Escutcheon/Cover Plate: [None][Standard escutcheon] [Model HB extended escutcheon][Model F1 recessed escutcheon][Model FP recessed escutcheon][Model CCP cover plate—pendent only] 3. Inlet Threads: [1" NPT][ISO7-1 R1][3/4" NPT][ISO7- 1 R3/4] The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. 4 Recycled ® (800)431-1588 Sales Offices Nitr Paper Re 1 a 1 e (800j 848 6051 Sales Fax Revision lines indicate updated or new data. Co 914 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.02/21 P/N 9999970175 A \\\NPOTTERModel/Series No. R,OEMER CONNECTIONS (FDC) 5100-5400 RE PRfJ INLET TYPE BODY INLETPPER SERIES Member of Morris Group international." SPECIFICATIONS Cast brass or ductile iron body with drop clappers, type and size of outlet and number of inlets as selected by model number. Polished brass plate with lettering as selected. Polished brass double female snoots with rigid end 3" N.P.T. x 2-1/2" pin lug hose thread swivels, pin lug plugs and chains. Outlet location as selected by suffix letters. MODEL SELECTION ,, TWO-WAY ❑5104 Back Outlet ❑*5114 Back Outlet ❑*5116 Back Outlet ❑5124 Angle Outlet ❑*5134 Angle Outlet ❑*5136 Angle Outlet ❑5144 End Outlet ❑*5154 End Outlet MODEL 5216 (Shown) ❑*5156 End Outlet PRODUCT OPTIONS FOUR-WAY U 5206 Back Outlet FINISHES: ❑*5216 Back Outlet ❑-D Polished Chrome Plated ❑*5226 Angle Outlet VARIATIONS: ❑*5236 Angle Outlet ❑-F Sillcock Flange Plate with Sillcock ❑5246 End Outlet *5256 End Outlet THREADS: SIX-WAY ❑N.S.T. Li 5306 Back Outlet ]Other ❑5308 Back Outlet LETTERING AVAILABLE: ❑5326 Angle Outlet ❑STANDPIPE ❑5328 Angle Outlet ❑DRY STANDPIPE ❑AUTO. SPKR. ❑5346 End Outlet ❑AUTO. SPKR. STANDPIPE ❑5348 End Outlet ❑Other FOUR-WAY SQUARE ❑5406 Back Outlet ❑*5416 Back Outlet ❑5426 Angle Outlet U*5436 Angle Outlet NOTE: * = UL Listed Call Potter Roemer-Fire Pro for current listings and - POTTER ROEMER/FIRE PRO approvals.Dimensions are subject to manufacturer's FIRE EQUIPMENT ONFSA /Ip) A tolerance and may change without notice.Potter Roemer- �,J AMSSNUQCIATIFACTQNURERS' Headquarters: Also in: Fire Pro assumes no responsibility for use of void or "'^°"^"'°^ a P O.Box 3527 New York(800)526-4592 superceded data.©Copyright Potter Roemer-Fire Pro, City of Industry,CA Chicago(800)547-3473 Member of Moms Group International" Please visit "" 91744 U.S.A. Atlanta(800)762-0542 potterroemer.com for most current specifications. n,,,A, �� $ AS P E _ Los Angeles AreaMiami(866)961-3473 800-366-3473 5100-5400 SERIES Date: 10/02/15 NFPA 626-855-4890 www• Dotterroemer.com POTTER Model/Series No. ROEMER CONNECTIONS (FDC) 5100-5400 /\\\\ FIRE PRO INLET TYPE BODY INLET SERIES Member of Morris Group International' MODEL DIMENSIONS OUTLET LOCATION Dimensions Back Angle End No. Outlet Body Material A B C D E Model No. Model No. Model No. Inlets Size Two-Way 5104 5124 5144 2 4 Brass 51/4 14 15 - 71/2 *5114 *5134 *5154 2 4 Ductile Iron 5 1/4 14 15 - 7 1/2 *5116 *5136 *5156 2 6 Ductile Iron 7 3/4 14 15 - 7 1/2 Four-Way 5206 *5226 5246 4 6 Brass 7 3/4 29 30 - 8 1/2 *5216 *5236 *5256 4 6 Ductile Iron 7 3/4 29 30 - 8 1/2 Six-Way 5306 5326 5346 6 6 Brass 7 3/4 43 44 1/4 - 8 1/2 5308 5328 5348 6 8 Brass 9 3/4 43 44 1/4 - 8 1/2 Four-Way Square 5406 5426 - 4 6 Brass 7 1/2 12 - 8 3/4 8 *5416 *5436 - 4 6 Ductitle Iron 7 1/2 12 - 8 3/4 8 NOTE:*=U/L Listed ALL DIMENSIONS IN INCHES 1 1 approvals.Dimensions are subject to manufacturer's • FIRE EQUIPMENT 0NFSA POTTER ROEMERIFIRE PRO FirerPro assumes no es responsibility for'use o/vo void N.\ MANUFACTURERS' Also in: Call Potter Roemer-Fire Pro for current listings a may changeRoemer- .egjry"Fa.`^0['. ASSOCIATION Headquarters: p yor /� � "°"°-�"..w_.°°-'""""'.w P.O.Box 3527 New York(800)526-4592 superceded data.©Copyright Potter Roemer-Fire Pro, ""'"` City of Industry,CA Chicago(800)547-3473 Member of Morris Group International T"'Please visit `,"`° 91744 U.S.A. Atlanta(800)762-0542 potterroemer.com for most current specifications. 1 AS P E AngelesMiami(866)961-3473 1�' x Los Area 4-3473 5100-5400 SERIES Date: 10/02/15 NFPA C,/ 800-366-3473 Dallas ® m C 626-855-4890 www.potterroemer.com OPOTTER Model/Series No. ROEMER CONNECTIONS (FDC) 5100-5400 FIRE PRU INLET TYPE ODY INLET SERIES SERIES Member of Morris Group International• C - B C B _ C— 'I I i I 1 7 7.63cm rH_i Ej1if 1 IIil I 1 1 if i� j1 i j Nipple } --- i By 1 1 1 1 p p���-Others if O i i E WI Pi IIP (Typ.) \ % % f / 1 7f r A %r%r%r%r%city , Wall — — — — — I ir7'1ZT wGr 17 17 WITH BACK OUTLET BODY 31/2" 8.9cm WITH END OUTLET BODY (Horizontal) (Vertical) (Horizontal) (Vertical) Top SUFFIX-H SUFFIX-V [j0 ®®) Left 0 SUFFIX-VT SUFFIX-HL0 0 400 00[1 Right 1�SUFFIX-VB 0 SUFFIX-HR Bottom o Wall Wall _•allB ��. �1 i 1�h hod Oo�lr`• i I .— B 11111 �1 1110 B 'iil 1 1E1 1 ! --I . -•I A N3" 7.6cm P.— Nipple 3" IO } Angle Outlet By Back Outlet zscm 1 i E Others Nipple (TM) By Others- j� jl jl Up FOUR-WAY SQUARE BODY (TYp•) WITH ANGLE OUTLET BODY (Horizontal) (Vertical) 16" (O O7 Top 0 SUFFIX-VR fl_ 44" F40.6 cm�I,`.� 111.8cm7" I` 30" 40.8cmySUFFlX-HT O( RightLeft 76.2cm 15"�8 mI I38.1cm O I���� 1?8cmOO® Bottom Qj SUFFIX-VL I 7,, 16" J" �� O O O O Sam O O 40.6cm SUFFlX-HB zz 9 cm } Horizontal or Vertical PLATES Call Potter Roemer-Fire Pro for current listings and , POTTER ROEMER/FIRE PRO approvals.Dimensions are subject to manufacturer's FIRE EACTURERS ONFSA {p� MANUFACTURERS' tolerance and may change without notice.Potter Roemer- ASSOCIATION Headquarters: Also in: Fire Pro assumes no responsibility for use of void or """'°` "'"^"^°°`^"' ^^` P O.Box 3527 New York(800)526-4592 superceded data.©Copyright Potter Roemer-Fire Pro, City of Industry,CA Chicago(800)547-3473 Member of Morris Group International T"Please visit "`,-„ 91744 U.S.A. Atlanta(800)762-0542 potterroemer.com for most current specifications. k rW AS P E ne Los Angeles Area Miami(866)961-3473 1l1 -,NaF,D,„ c • ����/�' 800-366-3473 Dallas(866)644-3473 5100-5400 SERIES Date: 10/02/15 NFPA® "*.,._..;fe EMOEQ 626-855-4890 wwttr potterroemer.com Identification .., V „ r* L Signs M10.., it i } E „..:,... . , _.....„:„..„ ir-4, 73 >S,i.I I HIS'i11 VF(Xi 111 4.La 4,R J11 1 TY1IY 7I L — „.•r\ ', 1 +JIGLIIY.YII/ t 6 ... .1.* COP', r' 4_ L_.. .: , . rt Description Installation Specs Manufactured from .020" Installation of the 6" x 2", Material: white coated aluminum. All 5" x 7", and 9" x 7" alumi- .020" aluminum w/ sign types are screen num signs is accomplished removable plastic j printed with a fade resistant by several methods. The coating red ink. Each sign is shipped most common installation Sizes: with a clear protective plastic procedure is to use #16 6" x 2" i coating which can be re- Single Jack chain to hang 5" x 7" moved at time of installation. the sign on the area being 9" x 7" Each sign type meets or identified. Since all of the exceeds NFPA13 require- above mentioned signs are Available designations: ments. All signs (except 7" predrilled at all four corners, round) are drilled in four the last link of the chain can See current catalog for a full corners to allow for easy be opened and hooked listing of all available signs. installation. All signs (except through through the top 7" round) may be installed holes on the signs and hung with sign chain or with any on the appropriate valve or fastener that is suitable for piping. The signs may also the material that the sign is be fastened to a flat surface being attached. The 7" with fasteners appropriate to round bell signs are center the base material. (The 9" x drilled to allow for installation 7" Fire Alarm Bell sign must directly to the bell gong be drilled to be attached assembly. Type "A" 9" x 7" directly to the bell gong.) Control valve signs are drilled with the same four hole pattern as Type "B" 6" x 1:1:112L- For questions: 2" signs to allow for 1 800 344-1822 attachement of Type "B" to 1 800 344-3775 Fax Type "A". http://www.fppi.corn © 1996-1999 Fire Protection Products, Inc.