Loading...
Report r)Pr PY Standard Coverage, Quick Response i I Upright, Pendent and Recessed Pendent Sprinklers �ctaul,c- K2.8 (4.0), K4.2 (6.1), K5.6 (8.1), K8.0 (11.5) FR52022-6 l? 41.01 9EC E IVE � A JUN 1 5 202Z 4 CITY OF TIGARD 1.0 PRODUCT DESCRIPTION 3UILDING DIVISION QUICK RESPONSE UPRIGHT SPRINKLERS SIN V2815 V4215 V2704 V3402 ORIENTATION UPRIGHT UPRIGHT UPRIGHT UPRIGHT K-FACTOR' 2.8 Imp./4.0 S.I. 4.2 Imp./6.1 S.I. 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1/2"NPT/15mm BSPT 1/2"NPT/15mm BSPT 1/2"NPT/15mm BSPT/IGS 3/4"NPT/20mm BSPT/IGS MAX.WORKING PRESSURE 175 psi/1200 kPa 175 psi/1200 kPa 175 psi/1200 175 psi/1200 kPa cULus 250 psi/172525 kPa GLOBE RE-DESIGNATION GL2815 GL4215 - — GLOBE EQUIVALENT - - GL5615 GL8118 QUICK RESPONSE PENDENT SPRINKLERS SIN V2801 V4201 V2708 V3406 ORIENTATION PENDENT PENDENT PENDENT PENDENT K-FACTOR' 2.8 Imp./4.0 S.I. 4.2 Imp./6.1 S.I. 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1/2"NPT/15mm BSPT 1/2"NPT/15mm BSPT Y"NPT/15mm BSPT/IGS 3/4"NPT/20mm BSPT/IGS MAX.WORKING PRESSURE 175 psi/1200 kPa 175 psi/1200 kPa 175 psi/1200 kPa 175 psi/1200 kPa cULus 250 psi/1725 kPa GLOBE RE-DESIGNATION GL2801 GL4201 — GLOBE EQUIVALENT - - GL5601 GL8101 QUICK RESPONSE RECESSED PENDENT SPRINKLERS SIN V2801 V4201 V2708 V3406 ORIENTATION PENDENT PENDENT PENDENT PENDENT K-FACTOR' 2.8 Imp./4.0 S.I. 4.2 Imp./6.1 S.I. 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1/2"NPT/15mm BSPT Y2"NPT/15mm BSPT 1/2"NPT/15mm BSPT/IGS 3/4"NPT/20mm BSPT/IGS MAX.WORKING PRESSURE 175 psi/1200 kPa 175 psi/1200 kPa 175 psi/1200 175 psi/1200 kPa cULus 250 psi/172525 kPa ESCUTCHEON Recessed Recessed Recessed Recessed GLOBE RE-DESIGNATION GL2801 GL4201 - — GLOBE EQUIVALENT - GL5601 GL8101 AVAILABLE GUARDS/SHIELDS SPRINKLER V28 V42 V27 V34 Upright ■ • Pendent • • AVAILABLE WRENCHES SPRINKLER V56-2 Recessed V56 Open End V27-2 Recessed V27 Open End V34-2 Recessed V34 Open End 3/,6 Hex-Bit V2815 and V4215 ■ V2707 and V2704 ■ • V3402 MI • V2801,and V4201 ■ ■ V2706 and V2708 ■ ■ • V3406 IN II NI Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar VdS: 5 psi/35 kPa/.35 bar (Upright only) Temperature Rating: See tables in section 2.0 ' For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • •victaulic.com 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. 1 Jctaulic victaulic.com • •2.0 CERTIFICATION/LISTINGS , UPRIGHT APPROVALS/LISTINGS = SIN V2815 V4215 V2704 V3402 Nominal K Factor Imperial 2.8 4.2 5.6 8.0 Nominal K Factor S.I.2 4.0 6.1 8.1 11.5 Orientation UPRIGHT UPRIGHT UPRIGHT UPRIGHT Approved Temperature Ratings F°/C° 135°F/57°C 135F/57°C 135F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C cULus 175F/79°C 175°F/79°C 175°F/79°C 175F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 200F/93°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C FM - - 175°F/79°C 175F/79°C 200°F/93°C 200°F/93°C 286F/141°C 286°F/141°C 135F/57°C 135°F/57°C { 1 155°F/68°C 155F/68°C LPG$ - - 175F/79°C 175F/79°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C CE - - 175°F/79°C 175F/79°C 200F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C I 155°F/68°C 155°F/68°C VdS - - 175°F/79°C 175F/79°C I 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C • 155°F/68°C 155°F/68°C K-ZSTZ - - 175°F/79°C 286F/141°C 286°F/141°C 2 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10. PENDENT APPROVALS/LISTINGS SIN V2801 V4201 V2708 V3406 Nominal K Factor Imperial 2.8 4.2 5.6 8.0 Nominal K Factor S.I.2 4.0 6.1 8.1 11.5 Orientation PENDENT PENDENT PENDENT PENDENT Escutcheon Flush/Extended Flush/Extended Flush/Extended Flush/Extended Approved Temperature Ratings F°/C° 135FI57°C 135°F/57°C 135°F/57°C 135°F/57°C 155F/68°C 155°F/68°C 155°F/68°C 155°F/68°C cULus I 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C } 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 286F/141°C 286°F/141°C 135°F/57°C 135FI57°C 155°F/68°C 155°F/68°C FM - - 175°F/79°C 175°F/79°C 200F/93°C 200°F/93°C 286°F/141°C 286°F/141°C t 155°F/68°C CCC _ 200°F/93°C 155F/68°C K-ZSTX I 286°f/141°C 286°F/141°C 2 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10. NOTES • Listings and approval as of printing. • Where cULus Listed,Polyester and VC-250 Coatings Listed as Corrosion Resistant(V3402 with VC-250 Only) • Where FM Approved,VC-250 Coating Approved as Corrosion Resistant • New York City Acceptance-All UL Listed and/or FM Approved sprinklers acceptable to NYC per section 28-113 of the Administrative Code and the OTCR Rule. • • 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic° victaulic.com • • 2.0 CERTIFICATION/LISTINGS (CONTINUED) RECESSED PENDENT APPROVALS/LISTINGS SIN V2801 i V4201 V2708 V3406 Nominal K Factor Imperial 2.8 4.2 5.6 8.0 Nominal K Factor S.I 2 4.0 6.1 8.1 11.5 Orientation PENDENT PENDENT PENDENT PENDENT Escutcheon Recessed Recessed Recessed Recessed Approved Temperature Ratings F°/C° 135'F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 155°F/68°C cULus 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 200F/93°C 200F/93°C 175°F/79°C 200F/93°C 286°F/141°C 286F/141°C 200F/93°C 286°F/141°C FM 135F/57°C 135°F/57°C WITH Y"ADJUSTMENT 155°F/68°C 155F/68°C ESCUTCHEON ONLY 175F/79°C 175°F/79°C 200°F/93°C 200°F/93°C CCC 155°F/68°C 155°F/68°C K-ZSTX 200F/93°C 286°F/141°C 286°F/141°C For K-Factor when pressure is measured in Bar,multiply S.I.units by 10. NOTES • Listings and approval as of printing. • Where cULus Listed,Polyester and VC-250 Coatings Listed as Corrosion Resistant(V3402 with VC-250 Only) • Where FM Approved,VC-250 Coating Approved as Corrosion Resistant • New York City Acceptance-All UL Listed and/or FM Approved sprinklers acceptable to NYC per section 28-113 of the Administrative Code and the OTCR Rule. • • 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic` victaulic.com • • 3.0 SPECIFICATIONS — MATERIAL Deflector: Bronze Bulb Nominal Diameter: 3.0mm - v/13 mm Nominal make-in Load Screw: Bronze Pip Cap: Bronze Frame Lodgement spring Spring Seal: PTFE coated Beryllium nickel alloy Pip cap and ®- 2/"/ Frame: Brass spring sealBulLim, 63 mm Lodgement Spring: Stainless steel Load screw le Deflector Installation Wrench: Ductile irone"..•.. Sprinkler Frame Finishes: 1516"/ 33 mm • Plain brass • Chrome plated 17/�6"/ • White polyester painted3,4 Deflector 37 mm Pi.,,,-_,-- .Pi.,,,-_,-- .• Flat black polyester painted3, Be4 Load screw lit • Custom polyester painted3,4 Pip cap and spring seal thi 2Yz"/ • 1_ VC-2505Lodgement spring 63 mm 3 Not available on the Intermediate Level Style Pendent. Frame 4 UL Listed for corrosion resistance. I 1 5 UL Listed and FM Approved for corrosion resistance. ;� r r - 'h"/13mm NOTE Nominal make-in • For cabinets and other accessories refer to separate sheet. 7/�6"/11 mm ty/�6"/ Nominal make-in Deflector 40 mm Lodgement spring Load screw a Ara Pip cap and AI L Bulb spring seal 2356"/ Pip cap and tiIi2Y,"/ Bulb58mm spring seal �� 57 mm • Load screw `�\ Lodgement spring "WV Frame Frame Deflector r 11/4"/ -7/16"/11 mm 31 mm Nominal make-in 17A6"/ Deflector 37mm 37 mm Deflector Load screw 4v` `�4r Bulb Load screw (I' Bulb Alt rink cap and Pip cap and spring seal 2h"/ 63 mm spring seal ���_ 2/z'/ Lodgement spring son Lodgement spring EI 63 mm Frame = Frame � I I—A I I--A I - 1/2"/13 mm - 1/2713 mm Nominal make-in Nominal make-in • • 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic° us victaulic.com • • 4.0 DIMENSIONS 23/e760 mm 2"/51 mm Hole in ceiling 7/e722 mm Max.Ns"Adj.) W'/16 mm Max.(h"Adj.) _ 1/873 mm Min. 'iA& 1 Typical ceiling r =-1 1 k"/29 mm Min.(3"Adj.) 13/s"/34 mm Min.eh"Adj.) ,_, Finished surface 1'/e747 mm Max. 2'3Sc'"/75 mm 2Ve"/60 mm 2"/51 mm Hole in ceiling 7/e"/22 mm Max.(3/4"Adj.) q , %716 mm Max.('h"Adj.) 14373 mm Min. reami� �.�'. %— W�• Typical ceiling rozaiiir Finished surface 1 W/47 mm Max 2'SA6"/75 mm 1 Ye'"/29 mm Min.OW Adj.) 13/s734 mm Min.('h"Adj.). 23/e760 mm 2"/51 mm D. Hole in ceiling 1"/25 mm Max.(3/a"Adj.) — 14719 mm Max.('h"Adj.) 1/4"/6 mm Min. W111111_ l I Typical ceiling 1316/30 mm Min.('h"Adj.) 1$/16/24 mm Min.(3/4'Adj.) :, Finished surface P3/46743 mm Max. 2t5A6775 mm • • 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic. victaulic.com • 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS • • Read and understand all instructions before attempting to install „sc% C5Q.A. any Victaulic products. • Always verify that the piping system has been completely depressur- ized and drained immediately prior to installation, removal, adjust- 0ment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from -67°F/-55°C to those shown in the table below. 1-40:Victaulic FireLockTM Automatic Sprinklers Installation and Maintenance Instructions I-V9:Style V9 Victaulic FireLockTM IGSTM Installation-ReadyTM Sprinkler Coupling Installation Instructions • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,as well as Victaulic performance,maintenance, Victaulic reserves the right to change product specifications,designs and standard safety,and warning instructions.Nothing in this or any other document,nor any verbal equipment without notice and without incurring obligations. recommendation,advice,or opinion from any Victaulic employee,shall be deemed to Installation alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Reference should always be made to the Victaulic installation handbook or installation of sale,installation guide,or this disclaimer. instructions of the product you are installing.Handbooks are included with each shipment Intellectual Property Rights of Victaulic products,providing complete installation and assembly data,and are available No statement contained herein concerning a possible or suggested use of any material, in PDF format on our website at www.victaulic.com. product,service,or design is intended,or should be constructed,to grant any license Warranty under any patent or other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such material,product,service,or design in the infringement of any patent or other intellectual Trademarks property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic and all other Victaulic marks are the trademarks or registered trademarks of or patent applications for articles and/or methods of use in the United States and/or other Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. countries. • • 41.01 16343 Rev C Updated 04/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctauliia FireLockTM Model FL-QR/DRY Standard Coverage, Quick Response Dry, Upright, Pendent and ✓ctauI,c` Recessed Pendent Sprinklers K5.6 (8.1), K8.0 (11.5) 45.01 • 001 F'R Qi � 3 %r y 110 1.0 PRODUCT DESCRIPTION UPRIGHT QUICK RESPONSE DRY SPRINKLERS SIN V3602 V3604 ORIENTATION UPRIGHT UPRIGHT K-FACTOR1 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1"NPT/25mm BSPT/1"IGS 1"NPT/25mm BSPT/1"IGS MAX WORKING PRESSURE 175 psi(1200 kPa) 175 psi(1200 kPa) ESCUTCHEON Plain Plain GLOBE EQUIVALENT GL5639 GL8139 PENDENT QUICK RESPONSE DRY SPRINKLERS SIN V3606 V3608 ORIENTATION PENDENT PENDENT K-FACTOR' 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1"NPT/25mm BSPT/1"IGS 1"NPT/25mm BSPT/1"IGS MAX WORKING PRESSURE 175 psi(1200 kPa) 175 psi(1200 kPa) ESCUTCHEON Plain/Flush/Sleeve and Skirt/Extended Plain/Flush/Sleeve and Skirt/Extended GLOBE EQUIVALENT GL5635 GL8135 RECESSED PENDENT QUICK RESPONSE DRY SPRINKLERS SIN V3606 V3608 ORIENTATION PENDENT PENDENT K-FACTOR' 5.6 Imp./8.1 S.I. 8.0 Imp./11.5 S.I. CONNECTION 1"NPT/25mm BSPT/1"IGS 1"NPT/25mm BSPT/1"IGS MAX WORKING PRESSURE 175 psi(1200 kPa) 175 psi(1200 kPa) ESCUTCHEON Recessed Recessed GLOBE EQUIVALENT GL5635 GL8135 AVAILABLE GUARDS/SHIELDS SPRINKLER V34N36 V34/V36 Intermediate Shield V34N36 Int.Shield/Guard Upright • • Pendent • • AVAILABLE WRENCHES Sprinkler V36 Recessed V36 Open End 3/16 Hex Bit(V9) Upright • • Pendent ■ • ■ Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: Pendent: 7 psi/48 kPa/.5 bar Upright: 12 psi/83 kPa/0.8 bar Temperature Rating: See tables in section 2.0 For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • •victaulic.com 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. 1 ictaulicf victaulic.com • 2.0 CERTIFICATION/LISTINGS , C®US LISTED APPROVALS/LISTINGS SIN V3602 V3604 Nominal K Factor Imperial 5.6 8.0 Nominal K Factor S.I 2 8.1 11.5 Orientation Upright Upright Escutcheon Plain Plain Approved Temperature Ratings F°/C° 135F/57°C 135°F/57°C cULus 155°F/68°C 155°F/68°C 200°F/93°C 200FI93°C (......_..-------.__._...._-.._.....__.________.___.j.__ 286°F/141°C 286°F/141°C , 135°F/57°C 135°F/57°C FM 155°F/68°C 155F/68°C 200°F/93°C 200°F/93°C 286°F/141°C CCC 1 155°F/68°C — APPROVALS/LISTINGS SIN V3606 V3608 V3606 V3608 Nominal K Factor Imperial 5.6 8.0 5.6 8.0 Nominal K Factor 5.12 8.1 11.5 8.1 11.5 Orientation Pendent Pendent Pendent Pendent Escutcheon Plain,Flush,Sly&Skt,Ext Plain,Flush,Sly&Skt,Ext Recessed Recessed Approved Temperature Ratings F°/C° 135Ff57°C 135°F/57°C 135°F/57°C 135°F/57°C cULus 155Ff68°C 155°F/68°C 155°F/68°C 155F/68°C 200Ff93°C 200F/93°C 200°F/93°C 200'F/93°C 286°F/141°C 286F/141°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 135F/57°C 135°F/57°C 155°F/68°C 155°F/68°C FM 200°F/93°C 200°F/93°C 155°F/68°C 155°F/68°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C CCC I _ 155F/68°C — 155°F/68°C — 2 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10. NOTES • Listings and approval as of printing. • Temperatures are listed for all hazards and approved for V3605 and V3606 dry sprinklers up to 48"length. • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic' victaulic.com 3.0 SPECIFICATIONS — MATERIAL Deflector: Brass or Stainless Steel ^y Spring seal assembly P� Bulb Nominal Diameter: 3.0mm Torsion spring filly.? Split Spacer: Stainless Steel ;�I Inlet fitting li � Load Screw: Brass Pip Cap: Stainless Steel III • inner tube Spring Seal Assembly: PTFE coated Beryllium nickelalloy and stainless steel I lOuter tubeFrame: BrassInlet Fitting: Brass • Outer Tube: Galvanized steel pipeIInner Tube: Stainless Steel Orifice insert ' NO �f 0 Orifice Insert: Stainless Steel f0 ! Escutcheon/Plate: 1010 - 1018 mild steel and stainless Frame d,in$ steel Split spacer % � ,� Pip cap Torsion Spring: SST wire Bulb W�� P $• Load screw- vp6 Installation Wrench: Ductile iron Deflector '.- Material Specifications Sprinkler Frame Finishes: V3606,V3608 • Plain brass • Chrome plated • White painted3'4 • Bright White painted3,4 • Flat black painted3,4 Deflector Load screw • Custom painted3 4 Bulb "'iMIt, ap • VC-25055 SplitPip spacer Is t gm g 3 Not available on the Intermediate Level Style Pendent. Frame 6 �y 4 UL Listed for corrosion resistance. lisp \d1 5 UL Listed and FM Approved for corrosion resistance. ja Orifice insert NOTES Ij� jl • Weather resistant escutcheon available upon request. • For cabinets and other accessories refer to separate sheet. Outer tube Inner tube Ij 1 Ij I' Escutcheon optional j (Not provided) I I 1 11 II Till IZy 6- jrf Torsion spring I 1 Inlet fitting Spring seal assembly Material Specifications V3602,V3604 • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctauliifr victaulic.com • 4.0 DIMENSIONS Tee with same outlet size `R: /- 1"IGS fitting ill-- —7 i as sprinkler thread size. See important Installation _ 0 Information;later in this document. I ' T '-1'NPT/BSPT -y- A (33/8"/ A 79 mm Min.) (2"/ 51 mm Min.) r kg!) T13/8"/ 1'/8"/ kilij 47 mm47mm Plain Barrel,Grooved Plain Barrel,Threaded V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Tee with same outlet size "F' ill as sprinkler thread size. r.. -- r 1"IGS fitting See"Important Installation . �0 Information;later in this document. 1 A 1"NPT/BSPT (2%"/ .) _ _ 13A"/44 mm Min. 13/4"/44 mm Min. _ Hole in ceiling Hole in ceiling 38 mm Min.) _�- Typical ceiling Typical ceiling A � A 4"/101 mm Finished surface 4"/101 mm Finished surface 21/2763 mm 2rh"/63 mm 3''/82 mm 34"/82 mm Sleeve and Skirt,Grooved Sleeve and Skirt,Threaded V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made-on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Optional Interchangeable Escutcheons Escutcheon "A"Dimension Adjustment Plain Barrel A=A Flush A=-1/4"/6mm Recessed A=+3/4"/6mm Slv/Skrt A=-1 3/8"/35mm • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 4 ✓otaulic' victaulic.com • •4.0 DIMENSIONS (CONTINUED) Tee with same outlet size "R' 1"IGS fitting as sprinkler thread size. I- I See"Important Installation � Q� Information';later in this — document. A 1"NPT/BSPT (2t5/67 75 mm Min.) _ _ 1 Yz"/38 mm Min. A (1 1/4"/ _�- Hole in ceiling 44 mm Min.) 1'h"/38 mm Min. Hole in ceiling 1/4"/ /4"/ r 6mm Typical ceiling 6mm Typical ceiling ♦ 2„/ 2/ Finished surface 51 mm Finished surface 51 mm L3mm 3"/76 mm Flush,Grooved Flush,Threaded V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Tee with same outlet size R 1"IGS fitting ill- - —1 i as sprinkler thread size. See"Important Installation i I IC kV Information;later in this document. 1"NPT/BSPT A (2'5Aa"/ -y A - - 74 mm Min.) (2"/ 51 mm Min.) /4"/ Y4"/ 6mm 6mm 2"/ 2"/ 51 mm 51 mm 3"/76 mm 3"/76 mm Intermediate,Grooved Intermediate,Threaded V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made-on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A"Dimension Adjustment Plain Barrel A=A Flush A=-'/4"/6mm Recessed A=+1/4"/6mm Slv/Skrt A=-13/8"/35mm • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 5 ,4 tlalullicr victaulic.com • • 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size 1"IGS fitting as sprinkler thread size. fi See"Important Installation r 1.miles-�•�l Information';later in this document. A MI 1"NPT/BSPT A _ _ (31/e"/ A 87 mm Min.) (21/47 2751 mm Min. 2751 mm Min. 57 mm Min.) Hole in ceiling Hole in ceiling Typical ceiling Typical ceiling 17/8747 mm lW/47 mm 11/8728 mm Finished surface 1Ys728 mm Finished surface 2/8773 mm 2/8773 mm Recessed,Threaded Recessed,Grooved V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C 1'/s"/47mm �I� 471'/mm �li� Km 0 1Yz"/38 mm Min. Hole in ceiling _ _ P/z"/38 mm Min. Hole in ceiling A (2"/51 mm Min.) Typical ceiling Typical ceiling Al 1OHO —� A Finished surface (31A3780 mm Min.) Finished surface 1"NPT/BSPT Tee with same outlet size as sprinkler thread size. irlll®i�� See"Important Installation - - J Information"later in this 1"IGS Fitting Installed Dimensions,Threaded document. Installed Dimensions,Grooved V3602,V3604 V3602,V3604 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made-on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A"Dimension Adjustment Plain Barrel A=A Flush A=-1/4"/6mm Recessed A=+Y"/6mm Slv/Skrt A=-13/8"/35mm • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulia victaulic.com • • 4.0 DIMENSIONS (CONTINUED) Tee with same outlet size "A 1"IGS fitting i lI— — —F i as sprinkler thread size. See"Important Installation N Information"later in this document. T I _ 1"NPT/BSPT A (1'h"/ A 38 mm Min.) 2W/60 mm Min. (1 Yz"/ 2;/s"/60 mm Min. —_ Hole in ceiling 38 mm Min.) i L — 4 Hole in ceiling Typical ceiling Typical ceiling Virr Finished surface Finished surface 5"/128 mm 57128 mm 33//"/96 mm 33/4"/96 mm 3'h"/89mm- 3h"/89 mm—> Extended Extended Sleeve and Skirt,Grooved Sleeve and Skirt,Threaded V3606,V3608 V3606,V3608 For wet system installation or dry/preaction systems installed in areas above 40°F/5°C Standard offering includes made-on escutcheon with "A" dimension shown above. Use the "Adjustments for Optional Interchangeable Escutcheons" table when making optional field adjustments to the standard ordered escutcheon. Adjustments for Interchangeable Escutcheons Escutcheon "A"Dimension Adjustment Plain Barrel A---A Flush A=-1/4"/6mm Recessed A=+1/4"/6mm Slv/Skrt A=-13/8"/35mm • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 7 ictBluliGr victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS • Read and understand all instructions before attempting to install any Victaulic 0• /rp r1111 products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment,or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.)standards, or equivalent standards, and in accordance with applicable • building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from —67°F/-55°C. 1-40;Victaulic FireLockTM Automatic Sprinklers Installation and Maintenance Instructions I-V9:Style V9 Victaulic FireLockTM IGSTM Installation-ReadyTM Sprinkler Coupling Installation Instructions • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 45.01 15896 Rev B Updated 03/2021 ©2021 Victaulic Company.All rights reserved. victaulic.com 8 ✓ctaulic`