Plans (56) M EC2019 -00388 10 • 9 • 8 • 7 ■ 6 • 5 • 4 • 3 ■ 2 • 1 7 TABLES AND CALCULATIONS PROJECT NOTES ►-i PARKING GARAGE VENTILATION ACOUSTICAL NOTES 1. PARKING GARAGE VENITLATION REQUIREMENTS: THE FOLLOWING MEASURES SHALL BE TAKEN TO MINIMIZE NOISE TRANSMISSION J-J i i GARAGE & LEVEL 1 VENTILATION CALCULATIONS VENTILATION REQUIRED: FROM THE HVAC EQUIPMENT TO THE INTERIOR SPACES: 11 L L RECEIVED ARCHITECTS 0.75 CFM/SF x 8,270 SF = 6202.5 CFM (MAX) FAN COIL UNITS: _ 0.05 CFM/SF X 8,270 SF = 413.5 CFM (MIN) A) MOUNT FAN ON SPRING ISOLATORS WITH A MINIMUM 1" DEFLECTION. 2014 OM SC-TABLE 403.3 B) PROVIDE FLEX CONNECTOR BETWEEN UNIT AND AND DUCTWORK. JUN 112019 1 7 5 0 BLANKENSHIP ROAD ) ROOM ROOM N0. 6250 CFM C MECHANICAL AREA, SF ROOM CFM MAX. VENTILATION PROVIDED = SUSPEND FAN COIL UNITS WITH THREADED ROD AND NEOPRENE GROMMET S UITE 400 UNITS) CATEGORY DEFAULT PROVIDED MIN. VENTILATION PROVIDED = 450 CFM ISOLATORS. CITY OF TIGARD DEFAULT PEOPLE/1000 CFM/PERSON CFM/SQ.FT CFM CFM CFM BUILDING DIVISION WEST L I N N , OREGON 9 7 0 6 8 OCCUPANTS RATE RATE (PERSON) (AREA) (TOTAL) 2. THE TERMINATION POINT FOR PARKING GARAGE EXHAUST OUTLETS EXHAUST FANS: TEt 503 . 305 . 8033 FAX 503 . 305 . 8034 SQ.FT HEALTH SHALL BE 10 FEET FROM OPERABLE OPENINGS INTO A BUILDING, A) PROVIDE FLEX CONNECTOR BETWEEN FAN AND DUCTWORK. PROPERTY LINES & MECHANICAL AIR INTAKES; 10 FEET ABOVE FITNESS CENTER 020 FCU-1 710 CLUB/WEIGHT 6 10 20 0.06 120 43 163 175 ADJOINING FINISHED WALKING GRADE. EXHAUST OUTLETS EXTENDING B) SUSPEND INLINE FANS WITH THREADED ROD AND NEOPRENE GROMMET ISOLATORS. ROOMS TO THE ROOF SHALL EXTEND 3 FEET ABOVE ROOF SURFACE. ■ C) ISOLATE DUCTWORK FROM THE ROOF WITH %" THICK NEOPRENE PADS ■ FOOD PREP, FOOD 009, FCU-8 750 KITCHEN/ 6 0 0 0.06 0 45 45 50 3. PARKING GARAGE VENTILATION SYSTEM SHALL BE EQUIPPED WITH EQUIVALENT TO MASON W. PREP STOR & PANTRY 011 & 012 WAREHOUSES CARBON MONOXIDE SENSORS THROUGHOUT THE GARAGE (1 SENSOR D) PROVIDE 1" DUCT LINER FOR THE DUCTWORK BETWEEN THE FAN AND THE VERTICAL SHAFT. FOR EVERY 5,000 SF). CO SENSORS SHALL BE EQUIPPED WITH A MEETING ROOM 013 FCU-2 638 CONFERENCE/ 24 50 5 0.06 120 38 158 165 LOW ALARM (SET TO 50 PPM) AND HIGH ALARM (SET TO 200 PPM). ROOFTOP FANS: FCU-3 MEETING PARKING GARAGE EXHAUST FANS (GEF-1) SHALL BE EQUIPPED WITH A) MOUNT FAN ON SPRING ISOLATORS WITH A MINIMUM 2" DEFLECTION. A VARIABLE FREQUENCY DRIVE PROVIDED BY MECHANICAL B) PROVIDE FLEX CONNECTOR BETWEEN FAN AND DUCTWORK. FCU-4 CONFERENCE/ CONTRACTOR UNLESS OTHERWISE NOTED, WHEN ANY OF THE MEETING ROOM 014 FCU-5 1'280 MEETING 36 50 5 0.06 180 77 257 260 ASSOCIATED CO SENSORS (PER FLOOR) GO INTO LOW ALARM, THE C) (EQUIVALENT TO MASONRK FROM TTE HE ROOF WITH h" THICK NEOPRENE PADS ■� EXHAUST FAN FOR THAT LEVEL SHALL OPERATE AT 1/2 SPEED. IF i >OBISON EMPLOYEE, THE CO SENSORS GO INTO HIGH ALARM, THE EXHAUST FAN SHALL CONDENSERS: BREAKROOM & 025, 026, FCU-6 812 OFFICE SPACE 8 5 5 0.06 40 49 89 100 RAMP UP TO FULL SPEED. 028 & 029 A) SUSPENDED CONDENSERS SHALL BE INSTALLED WITH 2" STATIC DEFLECTION BUSINESS CENTER SPRINGS. ENGINEERING, INC 4. GEF-2 SHALL RUN CONTINUOUSLY TO PROVIDE MINIMUM B) PROVIDE ROOF MOUNT CONDENSERS WITH PLASTIC PADS MINIMUM 4" THICK 1940140TH AVE W.,SUITE 302 FRONT DESK & 021 FCU-7 2,000 RECEPTION AREA 10 30 5 0.06 50 120 170 175 VENTILATION AT ALL TIMES. AND EXTENDING 6" BEYOND FOOTPRINT OF CONDENSER ON ALL SIDES. 206LYNNW9 OD,WA 98036 NORTH CORRIDOR 6433437 L ROOFTOP AIR HANDLERS: CONTACT:JON ROBISON LAUNDRY 034-036 FCU-9 1,160 COMMERCIAL 5 10 25 0 125 0 125 125A) MOUNT UNITS ON SPRING ISOLATORS WITH A MINIMUM 2" STATIC DEFLECTION. LAUNDRY B B) PROVIDE FLEX CONNECTOR BETWEEN UNIT AND DUCTWORK. • C) PROVIDE DUCT LINER IN LIEU OF WRAPPING SUPPLY DUCT ACROSS ROOF TO • 032 038, WATER HEATER VENTILATION SATISFY ENERCY CODE FOR MINIMUM INSULATION. BOH OFFICE 043 FCU-10 1,160 OFFICE SPACE 5 5 5 0.06 25 70 95 100 For the table below: Header Vent Length F MULTI PURPOSE 021 FCU-12 278 MULTIPURPOSE 12 120 5 0.06 60 17 77 100 • Header is the main vent pipe into which several vents connect SEQUENCE OF OPERATION �y5 D PRO FS ASSEMBLY G I NfF�S�o . Vent Length is the distance from the end of the header to the \�� N SPLIT SYSTEM AIR CONDITIONER 5,423 � MAIN LOBBY, vent termination. 1. DESCRIPTION: SINGLE ZONE SPLIT AIR CONDITIONER VESTIBULE, NORTH 002 & 006 FCU-11 1,500 LOBBIES/ 20 30 7.5 0.06 150 90 240 250 PREFUNCTION • Maximum vent length starts at the end of the header system. a_e FL CORRIDOR . Use 10 ft(3 m)as equivalent vent length for 900 elbows. .. 2 2'1' SU IED MODE: " OREGON 2.1. SUPPLY FAN: CYCLES AS NEEDED O �0 INDOOR POOL 050 PDU-1 1,730 SWIMMING POOL 0 0 0 0.48 0 830 830 830 For use with CU 1991 interna* (indoor)tanklesswater heaters only. 2.2. HEAT PUMP HEATING: CYCLED IN SEQUENCE TO MAINTAIN HEATING SETPOINT. RK 2.3. HEAT PUMP COOLING: CYCLED IN SEQUENCE TO MAINTAIN COOLING SETPOINT. 9/28/18 2.4. HEATING/COOLING LOCKOUT: INTERLOCK HEATING AND COOLING TO BREAKFAST AREA 008 RTU-1 1,590 DINING ROOM 40 70 7.5 .18 300 286 586 750 Common Vent Maximum Equivalent Vent Length PREVENT SIMULTANEOUS HEATING AND COOLING. • RinCtai Common Vent System or Schedule 40 PVC/CPVC CORRIDOR ITO . DESCRIPTIONISIINGLE ZONE ROOFTOP PACKAGE UNITS, GAS-FIRED HEAT, ■ TOTAL 2,250 HEADER DIAMETER ELECTRIC COOLING, 100% OUTSIDE AIR. Water Heater #Water Max System 3 in. 4 in. 6 in. 2.UN000UPIED MODE: UNITS OPERATE 24/7/365. LAUNDRY ROOM Madel I Heaters BTU/HR 3 in. 4 in. 6 in. 6 in. 3.000UPIED MODE: COMBUSTION AIR CALCULATIONS Vent Diameter Vent Diameter Vent Diameter Vent Diameter 3.1. SUPPLY FAN ON CONTINUOUSLY DUCT INSULATION SCHEDULE 2 398,000 65 FT 3.2. DAMPERS: FIXED BY AIR BALANCER AT VENTILATION POSITION. R-VALUE EQUIPMENT INPUT RATING (BTUH) 150 FT 3.3. HEATING: CYCLED IN SEQUENCE. SERVICE MATERIAL (MIN. (3) DEXTER T-80 DRYERS 215,000 3 s97,00a 3.4. COOLING: CYCLED IN SEQUENCE. w w CU199i 4 796,000 65 FT 1501sT 3.5. HEATING/COOLING DEADBAND: INTERLOCK HEATING AND COOLING TO INSTALLED) TOTAL INPUT RATING 645,000 PROVIDE 5F DEGREE DEADBAND BETWEEN HEATING AND COOLING. SUPPLY & RETURN AIR DUCTS IN MINERAL-FIBER (REU-N3237FFC-US) 5 995,000 150 FT 3.6. LOW LIMIT: SUPPLY AIR LOW LIMIT, 55 F. N R-5 IFGC 304.6.2: ONE PERMANENT OPENING METHOD. 6 1,194,000 UNCONDITIONED SPACE BLANKET N PROVIDE 1 OPENING WITHIN 12" OF THE TOP OF THE ENCLOSURE. � M OPENING SHALL BE SIZED FOR 1 SQ.IN. FREE AREA PER 3,000 7 1,393,000 70 FT EXHAUST FANS: SUPPLY & RETURN AIR DUCTS OUTSIDE MINERAL-FIBER R-8 BTUH INPUT RATING: 8 1,592,000E GUESTROOM BATHROOM EXHAUST: CONTINUOUS LOW SPEED; HIGH SPEED ACTIVATED W O THE BUILDING BLANKET BY DEDICATED WALL SWITCH. 645,000 BTUH X 1 SQ. IN. PER 3,000 BTUH = 215 SQ. IN. FREE x DROUND &UCTS IN RECTANGULAR EXHAUST AIR CE BLANKET FIBER N/A AREA PER OPENING. CORRIDOR EXHAUST FAN: RUNS CONTINUOUSLY. Z O o (5) 90' BENDS Z ■ FITNESS CENTER: RUNS WHEN SPACE IS OCCUPIED. INTERLOCK TO OPERATE WHEN ■ ROUND & RECTANGULAR SUPPLY AIR FOR A LOUVER WITH 50% FREE AREA: 6" . MINERAL-FIBER TDL LIGHTS ARE ON DUCTS, EXPOSED WITHIN CONDITIONED N/A 215 SQ. IN. X 2 430 SQ. IN LOUVER 6„ SPACE BLANKET SELECTION: 34"x20" LOUVER PROVIDED (680 SQ. IN. LOUVER) MAX PIPE ROUTING FOR 6" VENT IS 150'. THEREFORE THE VENT ROUTING PUBLIC RESTROOMS: RUNS CONTINUOUSLY. � � ~ ROUND & RECTANGULAR RETURN AIR IS ACCEPTABLE r MINERAL FIBER N/A O DUCTS, EXPOSED WITHIN CONDITIONED C/) °z SPACE BLANKET B THROUGH PENETRATIONS FOR 4" DUCT (_ NOTES General Guidelines (1) DUCT INSULATION SHALL COMPLY WITH IMC AND IECC POOL ROOM �+ PER EXCEPTION TO IBC SECTION 717.6.1, A DUCT IS PERMITTED TO PENETRATE ,....� THREE FLOORS OR LESS WITHOUT A FIRE DAMPER AT EACH FLOOR, PROVIDED (2) EXTERAL DUCT INSULATION IS IDENTIFIABLE PER IMC 604.7 When installing Common Vent, fallow these guide)*nes: o (3) INSULATION/LINING NOTES: ALL DUCTS TO BE EXTERNALLY COMBUSTION AIR CALCULATIONS IT MEETS ALL OF THE FOLLOWING REQUIREMENTS: INSULATED, EXCEPT MAXIMUM 20 FEET MAY BE LINED IMMEDIATELY EQUIPMENT INPUT RATING (BTUH) . Use only the materials listed in this manual for vent, pipe,intake i and fittings.g Failure to comply UPSTREAM/DOWNSTREAM OF AIR HANDLING UNITS FOR NOISE air I with this 1. THE DUCT SHALL BE CONTAINED AND LOCATED WITHIN THE CAVITY OFA ATTENUATION. INTERNAL INSULATION FOR SUPPLY DUCTS AND OUTSIDE (1) POOL WATER HEATER 400,000 warning could result in property damage, personal WALL AND SHALL BE CONSTRUCTED OF STEEL NOT LESS THAN 0.019 INCH AIR DUCTS MUST BE CLOSED-CELL ELASTOMERIC. FIBERGLASS DUCT TOTAL INPUT RATING 400000 injury,ordeath. (26 GAGE) IN THICKNESS. , LINER IS NOT ALLOWED. . When cutting vent components,ensure that the cuts IFGC 304.6.2: ONE PERMANENT OPENING METHOD. are straight. 2.THE DUCT SHALL OPEN INTO ONLY ONE DWELLING OR SLEEPING UNIT AND PROVIDE 1 OPENING WITHIN 12" OF THE TOP OF THE ENCLOSURE. . Chamfer and deburr all edges before installing the THE DUCT SYSTEM SHALL BE CONTINUOUS FROM THE UNIT TO THE EXTERIOR OPENING SHALL BE SIZED FOR 1 SQ.IN. FREE AREA PER 3,000 components. OF THE BUILDING. BTUH INPUT RATING: • Vent oints must not leak. Confirm as tight 3.THE DUCT SHALL NOT EXCEED 4-INCH NOMINAL DIAMETER AND THE TOTAL ■ ■ DRYER EXHAUST LENGTH connections of every vent joint. S g AREA OF SUCH DUCTS SHALL NOT EXCEED 100 SQUARE INCHES IN ANY 100 400,000 BTUH X 1 SQ. IN. PER 3,000 BTUH 133 SQ. IN. FREE SQUARE FEET OF FLOOR AREA. THIS WIDTH SHOULD BE 3" # OF 90' MAXIMUM DUCT LENGTH (FT) AREA PER OPENING. . Before operating the water heater(s),ensure vent ELBOWS WITHOUT BOOSTER FAN system is clean and free of debris. FOR A LOUVER WITH 50% FREE AREA: 4.THE ANNULAR SPACE AROUND THE DUCT IS PROTECTED WITH MATERIALS 0 56 133 SQ. IN. X 2 266 SQ. IN LOUVER • Vent system must be supported according to the vent THAT PREVENT THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO manufacture's installation instructions. IGNITE COTTON WASTE WHERE SUBJECTED TO ASTM E 119 1 48 SELECTION: 12"x24" LOUVER PROVIDED (288 SQ. IN. PER LOUVER) • Venting should be as direct as possible with a TIME-TEMPERATURE CONDITIONS UNDER A MINIMUM POSITIVE PRESSURE 2 40 minimum number of fittings, DIFFERENTIAL OF 0.01 INCH (2.49 Pa) OF WATER AT THE LOCATION OF THE 3 32 B • The common vent system must only be installed by a PENETRATION FOR THE TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE NOTE: LENGTHS GIVEN FOR RECOMMENDED 4"0 WATER HEATER trained and qualified professional. RATING OF THE CONSTRUCTION PENETRATED. c) VENT WITH 4" WALL CAP. FOR EXTRA 90' ELBOW, COMBUSTION AIR CALCULATIONS COMMON VENT TERMINATION CLEARANCES 5.GRILLE OPENINGS LOCATED IN A CEILING OF A FIRE-RESISTANCE-RATED REDUCE THE ALLOWABLE VENT SYSTEM LENGTH BY FLOOR/CEILING OR ROOF/CEILING ASSEMBLY SHALL BE PROTECTED WITH A 10 FT. EQUIPMENT INPUT RATING (BTUH) . Vent termination per ANSI Z223.1/NFPA 54, For LISTED CEILING RADIATION DAMPER INSTALLED IN ACCORDANCE WITH SECTION clearances not specified in ANSI Z223.1/NFPA 54, 716.6.2.1. (7) RINNAI DEMAND DUO WH 199,000 clearances are in accordance with local installation TOTAL INPUT RATING 1,393,000 codes and the requirements of the gas supplier. MAXIMUM VENT AREA CALCULATIONS AT MAX: (8) 40 PIPES IFGC 304.6.2: ONE PERMANENT OPENING METHOD. Refer to section "3.5Vent the WaterHeater"for SINGLE PIPE = 12.5 SQ. IN. ■ PROVIDE 1 OPENING WITHIN 12" OF THE TOP OF THE ENCLOSURE. additional clearance requirements specific to the 8 * 12.5 = 100 SQ. IN. MAX • OPENING SHALL BE SIZED FOR 1 SQ.IN. FREE AREA PER 3,000 BTUH INPUT RATING: CODE VENTS SHALL NOT EXCEED 100 SQ. IN. PER 100 SF OF FLOOR AREA. 1,393,000 BTUH X ( SQ. IN. PER 3,000 BTUH = 465 SQ. IN. FREE AREA PER OPENINGAPPLICABLE CODES FOR A LOUVER WITH 50% FREE AREA: 2012 INTERNATIONAL BUILDING CODE (IBC) 465 SQ. IN. X 2 = 930 SO. IN LOUVER ® 10-APR-2019 ASI 03 2014 OREGON MECHANICAL SPECIALTY CODE (OMSC) SELECTION: 20"x84" LOUVER PROVIDED (1680 SQ. IN. PER LOUVER) 2014 OREGON PLUMBING SPECIALTY CODE (OPSC) ® 2018-10-09 PLUMBING FIXTURE REVISIONS Fn 2014 OREGON ELECTRICAL SPECIALTY CODE (OESC) m 1 2014 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC) 2016-09-28 PERMIT RESUBMITTAL Q 2018-09-04 CONSTRUCTION SET Q1=FfCE COPY 2017-09-06 PERMIT CITY OF TIGARD MARK DATE REVISION/ISSUE REVIEWED FOR CODE COMPLIANCE ■ Approved: 1 ■ 704-0PROJECT NUMBER DRAWN BY CHECKED BY OTC: I I 704-004 IN ]MR Permit#: rme-�c-yQni9-c'Oo-? Address: )�L 79 Sir Eg tet, \,, THE ORIALL GINALAND UNGS AND NPUBLISHED WO OF THTTEN MATEIUKL E ARCHING TECFAND MAIN Y Suite #: NOT BE DUPLICATED,USED OR DISCLOSED WITHOUT THE PRIOR WRITTEN CONSENT OF THE ARCHITECT. By: Dater 0 HILL ARCHITECTS Q PROJECT NOTES VALIDITY OF PERIMIT THE ISSUANCE OF A PERMIT TABLES BASED ON CONSTRUCTION DOCUMENTS DATA LNOT PREVENT & CALCULATIONS THE CODE OFFICIAL FROM REQUIRING THE CORRECTION OF ERRORS, OSSC 105.4 ' ` O O 1 10 • 9 • 8 • 7 • 6 • 5 4 • 3 • 2 • 1 ti.. 10 ■ 9 ■ 8 ■ 7 ■ 6 ■ 5 ■ 4 ■ 3 ■ 2 ■ 1 SCHEDULES 1-1 FAN SCHEDULE VRF FAN COIL UNIT SCHEDULE HIL L ELECTRICAL NOMINAL NOMINAL EQUIP NO. SERVICE aROOFMOUNTED E AIRFLOW, CFM ESP. IN WG OPERATION WEIGHT, LBS BASIS OF DESIGN (1)(11) FAN ELECTRICAL VOLTAGE HP COOLING HEATING A RC H 1 TE c r s = EQUIP NO. SERVICE MOUNTING/ BASIS OF DESIGN (1)(2)(3)(4) EF-1 CORRIDOR - WEST 1,700 1.0 277V/1P 3/4 CONTINUOUS 136 GREENHECK SWD-I5-VG DISCHARGE AIRFLOW, MIN. OSA CAPACITY, CAPACITY, EF-2 PUBLIC RESTROOMS 625 0.75 120V/lP 1/4 CONTINUOUS 37 GREENHECK G-099VG CFM ESP. IN WG CFM BTUH BTUH VOLTAGE AMPS 1 7 5 0 B LAN KE N SH I P ROA D EF-3 CORRIDOR - SOUTH 800 1.0 277V 1P 1 /4 CONTINUOUS 72 GREENHECK SWD-IO-VG FCU-1 FITNESS CENTER HORIZ/DUCTED 600 0.5 (5) 24,200 27,300 208V/1PH 1.0 LG ARNU243BGA4 5 U 1 r E 4 0 0 8 WEST LINN . OREGON 97068 EF-4 GARAGE ELEC 8017 INLINE 1465 0.29 115V/1P 749 W CONTINUOUS 65 GREENHECK CSP-A1410 FCU-2 MEETING ROOM 013 HORIZ/DUCTED 600 0.5 (5) 24,200 27,300 208V/1PH 1.0 LG ARNU243BGA4 TEL 503 ' 05 . 8033 FAX 503 . 305 . 8034 - - - - - - - FCU-3 MEETING ROOM 013 HORIZ/DUCTED 600 0.5 (5) 24,200 27,300 208V/1PH 1.0 LG ARNU243BGA4 EF-6 LEVEL 2 VENDING CEILING MOUNTED 250 0.25 120V/1P FHP CONTINUOUS 24 GREENHECK SP-A250 FCU-4 MEETING ROOM 014 HORIZ/DUCTED 1,100 0.5 (5) 36,200 40,600 208V/1PH 3.5 LG ARNU363BRA4 EF-7 LEVEL 3 VENDING CEILING MOUNTED 250 0.25 120V/1P FHP CONTINUOUS 24 GREENHECK SP-A250 FCU-5 MEETING ROOM 014 HORIZ/DUCTED 1,100 0.5 (5) 36,200 40,600 208V/1PH 3.5 LG ARNU363BRA4 ■ EF-8 LEVEL 4 VENDING CEILING MOUNTED 250 0.25 120V/1P FHP CONTINUOUS 24 GREENHECK SP-A250 FCU-6 BOH OFFICE HORIZ/DUCTED 1,000 0.5 (5) 28,000 31,500 208V/1PH 3.5 LG ARNU283BRA4 ■ B F- GARA - IC E TOR IN 115V 1P FHP NTINUOUS -3 GR EC SP-A FCU-7 FRONT DESK HORIZ/DUCTED 1,100 0.5 (5) 36,200 40,600 208V/1PH 3.5 LG ARNU363BRA4 EF-10 GARAGE ELEC B016 INLINE 1509 0.25 120V/1P 745 W (7) 65 GREENHECK CSP-A1550 FCU-8 FOOD PREP/PANTRY HORIZ/DUCTED 1,400 0.5 (5) 48,000 54,000 208V/1PH 1.8 LG ARNU483NKA4 - - FCU-9 LAUNDRY ROOM HORIZ/DUCTED 1,200 0.5 (5) 42,000 43,800 208V/1PH 3.5 LG ARNU423BRA4 EF-12 POOL AREA UTILITY UPBLAST 1,000 1.0 277V/1P 1/2 CONTINUOUS 108 GREENHECK SWD-I3-VG FCU-10 BREAKROOM HORIZ/DUCTED 1,200 0.5 (5) 42,000 46,000 208V/1PH 3.5 LG ARNU423BRA4 L FCU-11 LOBBY HORIZ/DUCTED 1,200 0.5 (5) 42,000 46,000 208V/1PH 3.5 LG ARNU423BRA4 TF-1 MECHANICAL PENTHOUSE INLINE 10,000 0.5 460V/3P 5 CONTINUOUS 295 GREENHECK BSQ-240-50 FCU-12 MULTI PURPOSE ROOM HORIZ/DUCTED 600 1 0.5 1 (5) 24,200 27,300 208V/1PH 1.0 LG ARNU243BGA4 NOTES: (1) INSTALL UNITS AS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER IN COMPLIANCE WITH LOCAL CODES. ROBISON SF-1 LEVEL 1 OSA SUPPLY UTILITY 575 1.0 1 OV/1P 1 CONTINUOUS 34 GREENHECK SFD-7.5-VG (2) CONTRACTOR TO FIELD COORDINATE ROUTING OF REFRIGERANT LINES ON PLANS. SF-2 LEVEL 1 OSA SUPPLY UTILITY 605 1.0 120V/1P 1/2 CONTINUOUS 34 GREENHECK SFD-7.5-VG (3) PROVIDE CONDENSATE PUMP. ENGINEERING, INC SF-3 LEVEL 1 OSA SUPPLY UTILITY 575 1.0 120V/1P 1/2 CONTINUOUS 34 GREENHECK SFD-7.5-VG (4) HIGH STATIC PRESSURE UNIT. 1940140TH AVE W.,SUITE 302 (5) SEE VENTILATION CALCULATIONS ON SHEET MO.01 FOR OUTSIDE AIR REQUIREMENTS. LYNNWOOD,WA 98036 206364,3343TEL BEF-1 BATHROOM EXH FAN CEILING MOUNTED 20/80 0.25 120V/1P FHP (12) 15 PANASONIC FV-05VK3 (2) CONTACT:.JON ROBISON GEF-1 GARAGE PARKING INLINE 6,250 1.5 460V/3P 5 (5) 592 GREENHECK TBI-FS-5H30-50 (4) ■ GEF-2 GARAGE PARKING UTILITY UPBLAST 575 1.0 120V/1P 1/2 1 CONTINUOUS (5) 1 34 1 GREENHECK SFD-7.5-VG HEAT RECOVERY BOX - REFRIGERANT CONTROLLER SCHEDULE ■ NOTES: (1) PROVIDE BACKDRAFT DAMPERS ON EXHAUST FANS. (2) PROVIDE SPEED CONTROLLER. NUMBER OF ELECTRICAL (3) INTERLOCK WITH LIGHT SWITCH. EQUIP NO. SERVICE TYPE BRANCHES VOLTAGE POWER INPUT(W) BASIS OF DESIGN (1)(2) CONNECTED INDOOR UNITS (4) PROVIDE VARIABLE FREQUENCY DRIVE. (5) REFER TO GARAGE EXHAUST FAN REQUIREMENTS ON M001. (6) NOT USED HR-1 FLOOR 1 SINGLE 4 208V/1P 40 LG PRH042A (3) ���� GINFPRO Fss, (7) INTERLOCK FAN WITH THERMOSTAT. SET THERMOSTAT TO 78'F. HR-2 FLOOR 1 SINGLE 3 208V/1P 40 LG PRH031A (3) ��� �N5,423�� �y (8) NOT USED. HR-3 FLOOR 1 SINGLE 3 208V/1P 40 LG PRH031A (3) (9) NOT USED. (10) NOT USED. HR-4 GARAGE SINGLE 2 208V/1P 26 LG PRH021A (3) OREGON (11) VIBRATION ISOLATION: FANS < 150 LBS RUBBER ISOLATORS, FANS > 150 LBS SPRING ISOLATORS NOTES: (1) PROVIDE CONDENSATE PIPE AND ROUTE TO APPROVED RECEPTOR. (12) FAN SHALL BE 2-SPEED, WITH 20 CFM CONTINUOUS LOW SETTING, HIGH SPEED ACTIVATED BY DEDICATED WALL SWITCH. DO NOT CONNECT TO LIGHT SWITCH. (2) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO FIELD COORDINATE ROUTING. (3) SEE SHEET M410 VRF RISER DIAGRAM qRK 9/28/18 ROOFTOP HVAC UNIT SCHEDULE ( ELEC COOL/GAS HEAT) EQUIP SUPPLY FAN PROVIDE 100% COOLING WEIGHT, BASIS OF DESIGN HEATING ELECTRICAL VRF OUTDOOR UNIT SCHEDULE SERVICE DISCHARGE AIRFLOW, ESP, IN MOTOR MIN. OSA, OSA CAPACITY, SEER/ INTPUT, OUTPUT, AFUE N0. STAGES VOLTAGE MCA MOCP LBS (2)(3)(5) ■ CFM WG HP CFM ECONOMIZER? MBH EER MBH MBH % NOMINAL NOMINAL ELECTRICAL ■ RTU-1 LEVEL 1ABREAKFAST VERTICAL 1,200 0.75 1 (4) YES (1) 36,000 S15.0 EER 120 96 1 80.0 480V/3P 11 15 550 TRANE YHC036 EQUIP NO. SERVICE TONS COOLING EER HEATING COP NOISE (DB) WEIGHT (LBS) BASIS OF DESIGN CAPACITY, CAPACITY, (1)(2)(3)(4)(5) BTUH BTUH VOLTAGE MCA MOCP RTU-2 LEVEL 1 BREAKFAST VERTICAL 1,200 0.75 1 (4) YES (1) 36,000 15.0 120 96 1 80.0 48OV/3P 11 15 550 TRANE YHC036 AREA SEER 16 192,000 9.5 216,000 3.2 48OV/3PH 35.7 50 62.0 659 LG ARUM192DTE5 NOTES: (1) PROVIDE 100% MODULATING ENTHALPY CONTROLLED ECONOMIZER AND ASSOCIATE CONTROLS. HP-1 LEVEL 1 AND BASEMENT 14 168,000 9.5 189,000 3.2 480V/3PH 28.5 35 61.0 639 LG ARUM168DTE5 (2) PROVIDE DEMAND CONTROL VENTILATION CONTROLS PER ENERGY CODE. REFER TO SHEET M001 FOR SEQUENCE OF OPERATION. (3) PROVIDE 7 DAY PROGRAMMABLE THERMOSTATIC MEETING ENERGY CODE REQUIREMENT NOTES: (1) INSTALL UNITS AS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER IN COMPLIANCE WITH LOCAL CODES. w (4) REFER TO VENTILATION SCHEDULE. (2) CONTRACTOR TO FIELD COORDINATE ROUTING OF REFRIGERANT LINES ON PLANS. u' (5) PROVIDE FACTORY AVAILABLE RETURN AIR SMOKE DETECTOR(S), CAPABLE OF SHUTTING DOWN THE ROOFTOP UNIT UPON ACTIVATION. w 1--4 w M I PIR:IP11111 J!,! 1(4) PROVIDE HORIZONTAL EXHAUST DISCHARGE ADAPTER MANUFACTURER PART NUMBER LG PRAGX3SO > N CORRIDOR MAKE- UP AIR UNIT THROUGH - WALL HEAT PUMP SCHEDULE H � x SUPPLY FAN COOLING HEATING ELECTRICAL SUPPLY FAN COOLING HEATING AUX. HEAT, ELECTRICAL OEQUIP NO. SERVICE AIRFLOW, =MOTORIN. OSA, KW BASIS OF DESIGN EQUIP COOLING ENT AIR LVG AIR GAS AIR TEMP WEIGHT, BASIS OF DESIGN CFMCFM BTUH EER BTUH COP (208V) VOLTAGE MCA MOCP ■ < NO. DISCHARGE AIRFLOW, ESP, IN MOTOR EER LBS (2)(3)(4)(5)(6)(7)(8)(9)(10) ""' u CFM WG (1) HP/BHP TOTAL INPUT OUTPUT VOLTAGE MCA MOCP TWHP-1 PER DWGS 270 1 1/8 1 35(6) 9,100 12.2 10,900 1 3.7 3.4 208V/1P 16 20 GE AZ61H09DA (1)(2)(3)(4)(5)(6) DB WB DB WB ENT LVG n (MBH) (MBH) (MBH) NOTES: (1) EXTERIOR GRILLE SHALL BE THE ARCHITECTURAL GRILLE. COORDINATE STYLE AND COLOR WITH ARCHITECT. SIZE OF LOUVER SHALL BE COORDINATED WITH WINDOW MANUFACTURER. (2) PROVIDE UNIT SUPPORT SUB-BASE RECEPTACLE ACCESSORY KIT WITH ATTACHMENT CORD. AHU-1 HORIZONTAL 2,250 1.0 4.0/0.98 120.5 93 68 49.6 49.6 200 160 24 89.8 11.3 480V/3P 27.5 35 2870 TRANE HORIZON G120 (3) PLUG AND RECEPTACLE SHALL BE BEHIND AN ACCESS COVER, NOT READILY ACCESSIBLE TO HOTEL GUESTS. z PROVIDE FACTORY STICKER SPECIFYING NO CONTROLS AT UNIT. UNIT SHALL BE CONTROLLED EXCLUSIVELY BY REMOTE THERMOSTAT. PROVIDE VERDANT VX-TR-KT REMOTE THERMOSTAT WITH y NOTES: (1) ESP IS EXTERNAL TO UNIT CASING; DOES NOT INCLUDE CASING, CLEAN FILTER, WET COIL, OR AUX HEAT LOSSES. (4) OCCUPANCY (2) PROVIDE FACTORY ASSEMBLED AND INSULATED HORIZONTAL DISCHARGE CURB WITH VIBRATION ISOLATION RAILS. SENSOR. o (3) UNIT SHALL INCLUDE MODULATING GAS HEATING WITH STAINLESS STEEL HEAT EXCHANGER. (5) REFRIGERANT SHALL BE R-410A. r--H (4) UNIT SHALL INCLUDE THE FOLLOWING: SIGHT GLASS, STAINLESS STEEL DRAIN PAN, MANUAL RESET HIGH PRESSURE SWITCHES & AUTO RESET LOW PRESSURE SWITCHES, CONDENSER FAN CYCLING (6) PROVIDE FRESH AIR KIT FOR VENTILATION AIR TO GUESTROOM. r--I CONTROL, INTEGRAL NON-FUSED DISCONNECT SWITCH, CONVENIENCE OUTLET, R-410A REFRIGERANT. (5) DIRECT DRIVE FAN WITH VFD. (6) DISCHARGE TEMPERATURE CONTROL WITH TERMINAL INTERFACE. SPLIT AIR CONDITIONER SCHEDULE - OUTDOOR UNIT (7) DUCT SMOKE DETECTOR. NOMINCAL (8) PROVIDE MERV 8 PREFILTER AND MERV-12 SECONDARY FILTER. PROVIDE FULLY SYNTHETIC MEDIA WITH SPECIAL SUPPORTING STRUCTURE TO PREVENT MOISTER LADEN FILTER COLLAPSE. EQUIP NO. SERVICE CAPACITY, TOTAL COOLING SEER ELECTRICAL BASIS OF DESIGN (1)(2)(3)(5) CONNECTED INDOOR (9) WARRANTIES: 5 YEAR COMPRESSOR, 25 YEAR HEAT EXCHANGER, 1 YEAR PARTS. TONS CAPACITY, BTUH (EER) VOLTAGE MCA MOCP UNIT (10)ACCEPTABLE MANUFACTURERS ARE AAON, MCQUAY, TRANE (DOAS), OR GREENHECK. 0 C- 17 000 7 08V 1P 1 G L U 8 H V A - ■ B OAC-2 ELEVATOR EQUIP ROOM 3.0 33,000 17.50 208V/1P 19 30 LG LSU363HLV (4) IAC-2 ■ OAC-3 ROOM 51, 392, 492 4.0 48,000 17.00 208V/1 P 30 50 LG ARUN048GSS4 IAC-4,7,8 THIS WIDTH SHOULD BE Y OAC74 ROOM 194, 294, 394 5.0 60,000 17.00208V/1P 25.440 LG ARLN06OGSS4 IAC-5,6 NOTES: 1) ­ARl OSTED WITHL A A R S, I S AL A I N A CSO ES AND- COMPRESSOR SHORT L 0 IL RI R, R G L R, L Q ID ELECTRIC HEATERS SOLENOID VALVE, AND SAFETY PRESSURE SWITCHES. INSTALL REFRIGERANT TUBING IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. HEATING ELECTRICAL (2) WITH FACTORY ELECTRICAL DISCONNECT. EQUIP NO. SERVICE MOUNTING/ DISCHARGE WEIGHT, LBS BASIS OF DESIGN (1)(2)(3) (3) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO FIELD COORDINATE ROUTING. BTU/HR. VOLTAGE INPUT KW (4) PRIOR TO ORDERING, CONTRACTOR TO COORDINATE WITH ELEVATOR MFR OR DATA ROOM EQUIPMENT SUBMITTAL TO ENSURE UNIT CAN ADEQUATELY COOL THE ROOM. (5) PROVIDE LOW AMBIENT KIT. L' EH-1 STAIR 1 WALL MOUNTED 5,120 277V/1P 1.5 10 DAYTON 5E186 EH-2 STAIR 2 WALL MOUNTED 5,120 277V/1P 1.5 10 DAYTON 5E186 EH-3 STAIR 3 WALL MOUNTED 5,120 277V/1P 1.5 10 DAYTON 5E186 EH-4 FIRE SPRINKLER ROOM WALL MOUNTED 5,120 277V/1P 1.5 10 DAYTON 5E186 NOTES: (1) INSTALL UNITS AS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER IN COMPLIANCE WITH LOCAL CODES. (2) HEATER SHALL HAVE INTEGRAL T-STAT, UON. SPLIT AIR CONDITIONER SCHEDULE - INDOOR UNIT (3) SET T-STAT TO MAINTAIN 557. FAN ELECTRICAL ■ EQUIP NO. SERVICE MOUNTING/ BASIS OF DESIGN (1)(3) CONNECTED OUTDOOR ■ DISCHARGE AIRFLOW, CFM MOTOR DRIVE VOLTAGE MCA MOCP UNIT 8 IAC-1 PBX HIGH WALL500 DIRECT 208V/1P 0.5 15 LG LSN180HEV OAC-1 IAC-2 ELEVATOR EQUIP ROOM HIGH WALL 850 DIRECT 208V/1P 0.5 15 LG LSN363HLV (2) OAC-2 POOL DEHUMIDIFICATION UNIT IAC-3 ROOM 194 HIGH WALL 494 DIRECT 208V/1P 0.52 15 LG ARNU183SKA4 OAC-4 IAC-4 ROOM 51 HIGH WALL 276 DIRECT 208V 1P 0.25 15 LG ARNU093SJA4 OAC-3 SUPPLY FAN POOL ROOM COOLING ELECTRICAL ® 10-APR-2019 ASI-03 POOL ELECTRIC IAC-5 ROOM 294 HIGH WALL 276 DIRECT 208V/1P 0.25 15 LG ARNU093SJA4 OAC-4 EQUIP DISCHARGE ROOM REL. SENSIBLE TOTAL RE-HEAT WEIGHT, BASIS OF DESIGN IAC-6 ROOM 394 HIGH WALL 537 DIRECT 208V/1P 0.52 15 LG ARNU243SKA4 OAC-4 ® 2018-10-09 PLUMBING FIXTURE REVISIONS m NO. AIRFLOW, ESP, IN MOTOR OUTSIDE TEMP HUMIDITY POOL CAPACITY CAPACITY HEATING KW VOLTAGE MCA MOCP LBS m CFM WG HP AIR (CFM) (.F) (%) TEMP (MBH) (MBH) CAPACITY (KW) IAC-7 ROOM 392 HIGH WALL 494 DIRECT 208V/1P 0.52 15 LG ARNU183SKA4 OAC-3 2018-09-28 PERMIT RESUBMTITAL (MBH) IAC-8 ROOM 492 HIGH WALL 494 DIRECT 208V/1P 0.52 15 LG ARNU183SKA4 OAC-3 SERESCO 0 E E C C N E T H A D I D A 0 A 2018-09-04 CONSTRUCifON SET PDU-1 HORIZONTAL 2050 1.0 2.4 460 83 60 83 27.7 54 36 15 48OV/3P 38 40 770 NE-004-PS-1-A3NH1202E5E2ANO (2) PRIOR TO ORDERING, CONTRACTOR TO COORDINATE WITH ELEVATOR MFR OR DATA ROOM EQUIPMENT SUBMITTAL TO ENSURE UNIT CAN ADEQUATELY COOL THE ROOM. (1)(2)(3)(4) (3) PROVIDE CONDENSATE PUMP KIT. 2017-09-06 PERMIT NOTES: (1) PROVIDE REMOTE CONDENSING UNIT. MARK DATE REVISIONASSUE (2) POVIDE STANDALONE 7-DAY PROGRAMMABLE THERMOSTAT DIFFUSER SCHEDULE (3) PROVIDE MERV 7 PRE-FILTER AND MERV 12 FINAL FILTER ■ (4) FAN SHALL RUN CONTINUOUSLY AIRFLOW RANGE, ■ PROJECT INMWN BY CHECKED BY CALLOUT DESCRIPTION CFM FACE SIZE, IN BASIS OF DESIGN (1) CD-1 CEILING DIFFUSER 0-1000 12x12 TITUS TMS CD-2 CEILING DIFFUSER 0-2000 2424 TITUS TMS ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK Of THE ARCHITECT AND MAY NOT BE DUPLICATED.USED OR DISCLOSED WITHOUT THE PRIOR WRITTEN POOL REMOTE CONDENSING UNIT EG-1 EXHAUST GRILLE 0-1000 12x12 TITUS 350ZRL CONSENT OF THE ARCHITECT EG-2 EXHAUST GRILLE 0-2000 24x24 TITUS 350ZRL 0 HILL ARCHITECTS ELECTRICAL EG-3 EXHAUST GRILLE 0-500 12x8 TITUS 350ZRL EQUIP NO. DISCHARGE WEIGHT, BASIS OF DESIGN a VOLTAGE MCA MOCP LBS EG-4 EXHAUST GRILLE 0-1000 24x18 TITUS 350ZRL a B SERESCO LD-1 LINEAR DIFFUSER 0-400 48x6 TITUS ML-38 3 SLOT PCU-1 HORIZONTAL 480/3P 5.0 15 90 G-V-0I-EUC-V (1) LD-2 LINEAR DIFFUSER 0-400 48x6 TITUS MLR-38 3 SLOT NOTES: (1) INTERLOCK POOL WATER CONDENSER WITH DEHUMIDIFICATION UNIT. RG-1 RETURN GRILLE 0-1000 12x12 TITUS 350ZRL MECHANICAL SCHEDULES RG-2 RETURN GRILLE 0-2000 24x24 TITUS 350ZRL RG-3 RETURN GRILLE 0-2500 38x36 TITUS 350ZRL RG-4 RETURN GRILLE 0-1000 12x12 TITUS 350ZRL SG-1 SUPPLY GRILLE 0-1000 18x10 TITUS 30ORL �/� 0 0 2 NOTES: (1) ALL DIFFUSERS, REGISTERS, AND GRILLES SHALL BE FACTORY , l 10 • 9 0 8 0 7 0 6 0 5 ■ 4 ■ 3 ■ 2 ■ 1 10 ■ 9 ■ 8 • 7 ■ 6 ■ 5 • 4 • 3 ■ 2 ■ 1 POC TO MANIFOLD. PROVIDE APPROVED TUBK COPPER TO PEX LAV CONNETION (TYP.)� 3 3 3 -CAP END UNUSED BRANCHES = x x Z 3/4' MANIFOLD—VIEGA MANABLOC OR EQUAL. ARIHITECTS �, a_LABEL PER FIXTURE _ 3/4" $ Q $ 1750 BIANKFN5H1P ROAD 3 3 3 3 a a s L SUITE 400 U U U U PROVIDE ISOLATION —/ N�4 ' WEST LINN . OREGON 97063 VALVE BEFORE I TEL 503 . 305 . 8033 FAX 503 . 305 . 8034 THE MANIFOLD WC (TYP.) LAV TUB KS COPPER \ SECONDARY PEX (UPONOR AQUAPEX) \ PROVIDE ACCESS PANEL CONDENSATE ALARM LIGHT LEVEL SENSOR ELEVATION NOTE: REFER TO RISERS ON SCHEDULE CEILING NOTE: COORDINATE LOCATION OF HVAC P501—P503 AND CALCULATIONS ROBISON UNITS WITH MECHANICAL DRAWINGS. ON P001 FOR PIPE SIZES. —ELECTRICAL ALTERNATOR ITEM DIM ROUTE SECONDARY CONDENSATE TO CONTROL PANEL SUMP COVER 48" ENGINEERING, INC TERMINATE AT CEILING ABOVE BATHTUB. PEX MANIFOLD 19401 40TH AVE W.,SUITE 302 INDICATOR LAMPS INLET PIPE LYNNWOOD,WA98036 TOGGLE SWITCHES IE AT SUMP WALL 27" 206364-3343TEL ESCUTCHEON PLATE DETAIL HIGH WATER ALARM 24" CONTACT:JON ROBISON SCALE: NONEP7.01 LAG PUMP ON 22" • SECONDARY CONDENSATE TERMINATION LEAD PUMP ON 20" ■ GATE VALVE PUMPS OFF 12" 0 FLOAT SUPPORT FABRICATED FROM PVC OR S.S. PIPE SUMP FLOOR 0" DIMENSIONS SUMP FLOORARE HEIGHTS ABOVE ����NGI N6- LAVATORY OR SINK CONDENSATE THREE COMPARTMENT SINK 2" VENT5 DRAIN ,423 yr SIZE PER PLAN IN WALL 1W" DISCHARGE PIPE LL OREGON CLEANOUTS "CLEANOUT-- INLET HUB- o LAG PUMP ON & HIGH WATER ALARM ON LEVEL 2�1Q FIXT. TAIL PIECE WALL PIPEIN NDS OF 1 I _ _ RK LEAD PUMP ON LEVEL TEE WITH FLOOR 2"- CoI BASI dg- - VARIABLE LEVEL 9�28�18 SLIP JOINT 3/16 VENT HOLE CONTROL SWITCH 3" SET GREASE TRAP ON FLOOR / ■ • UNDER DRAINBOARD WHERE 3" WASTE TOP CAN BE EASILY REMOVED P-TRAP WASTE FOR CLEANING EJECTOR PUMP- -- PUMPS OFF LEVEL GRAVEL ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS OR MEET LOCAL CODE REQUIREMENTS. UTILIZE HUBLESS CAST IRON PIPE, FITTINGS AND CONNECTORS FOR SINK CONNECTIONS. W w cr CONDENSATE TERMINATION AT SINK 3- COMP SINK AND GREASE TRAP EJECTOR PUMP STATION N DETAIL r5 DETAIL 4 DETAIL 3 SCALE: NONE P7.01 1--i1 SCALE: NONE P7.01 z SCALE: NONE P7.01 ■ z O o ■ < v z � o � Z FLAG NOTES: TWHP-1 TWHP-1 TWHP-1 1. GPRV-1 PRESSURE REGULATOR SET TO 10"WC �-- 1 TON 1 TO 1 TON 1"G OUTLET PRESSURE, VENTED TO EXTERIOR. FOURTH FLOOR (365 MBH) 2. PROVIDE LINE—SIZE LOW PRESSURE (10"WC x 1 INPUT/ 7"WC OUTPUT) REGULATOR AT EACH CONDENSATE PIPE SIZING WATER HEATER OR APPLIANCE FOR 1"G Y4'G FINE—TUNING GAS SUPPLY PRESSURE. SET TO PER 2012 UPC TABLE 814.1 (240 MBH) 120 MBH 7"WC OUTPUT. PROVIDE VENT TO EXTERIOR. (< 30') CONTRACTOR SHALL SELECT GPRV TO MATCH PIPE SIZE CAPACITY (TONS EACH PIECE OF EQUIPMENT. ■ 0 0 0 3/a" 20 ■ U U U 1" 40 D D D THIS WIDTH SHOULD BE 3" 1 A4 90 1W, 125 TWHP-1 TWHP-1 TWHP-1 2" 250 1 TON 1 TON 1 TON NOTES: THIRD FLOOR AHU-1 RTU-1 RTU-2 1. LENGTH FROM METER TO FURTHEST REGULATOR 125 MBH 120 MBH 120 MBH 275 FEET. DISTANCES FROM REGULATORS TO MOST u REMOTE APPLIANCES ARE LABELED ON THE RISER DIAGRAM. GAS PIPING IS SIZED PER 2014 OPSC, TABLES 1216.2(4) AND 1216.2(1) . p p p v v 2. PROVIDE CONNECTION TO EACH PIECE OF m EQUIPMENT WITH UNION, GAS COCK(TYP), AND SEDIMENT TRAP INSTALLED AS CLOSE AS POSSIBLE In TO THE APPLIANCE INLET WITH THE PLUMBING TWHP-1 TWHP-1 DESIGN. EXCEPTIONS: APPLIANCES WITH AN ■ 1 TON 1 TON 1}�"MP INTERNAL SEDIMENT TRAP, (OR) RANGES AND GAS ■ FIREPLACES. 3. PROVIDE VENTS TO OUTDOORS FOR GULATORS SECOND FLOOR PER LOCAL JURISDICTION AND NFPA- 4. ROUTING OF VENTS IS NOT SHOWN ON THE PL NS. 2"G p STRAINER (1400 MBH) ® 10-APR-2019 ASI-03 U DISCHARGE TO DRY _ - DISCHARGE TO DRY (1200 MBH) m e 2018-10-09 PLUMBING FIXTURE REVISIONS WELL ON GRADE. WELL ON GRADE. FROM GAS 2"MPG 1 G }�" 4 2018-09-28 PERMIT RESUBMITTAL UTILI (2810 MBH) MPG (1000 MBH) PlT 1 - 1 W'G Q 2018-09-04 CONSTRUCTION SET N ^ (800 MBH) O O2 a m 11 „G 1 2017-09-06 PERMIT FIRST FLOOR 2 PSI GAS METER 0 1 "MPG 1"MPG (600 MBH) 1%"G MARK DATE REVISION/ISSUE 0 2045 MBH 645 MBH 645 MBH p (< 20') U i Y4" ■ PROJECT NUMBER DRAWN BY CHECKED BY ■ "� 400 MBH 704-004 IN ]MR DISCHARGE TO DRY 10 a(< 20') WELL ON GRADE. 400 MBH 1%"MPGA 1 c� c� c� c� 0 c� c� ij(< 20') (1400 MBH) ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF THE ARCHITECT AND MAY NOT BE DUPLICATED,USED OR DISCLOSED WITHOUT THE PRIOR WRITTEN CONSENT OF THE ARCHITECT. 2 0 HILL ARCHITECTS 0 2 2 2 2 2 2 2 LAUNDETAILS 645 POOL EQUIPMENT CONDENSATE RISER DIAGRAM 400 MBH GAS RISER DIAGRAM WH-6 WH-6 WH-5 WH-4 WH-3 WH-2 WH-1 200 MBH 200 MBH 200 MBH 200 MBH 200 MBH 200 MBH 200 MBH DETAIL r2 DETAIL SCALE: NONE P7.01 SCALE: NONE P7.01 ��' O