Loading...
Plans (13) M EC2020-00556 OFFICE COPY RECF" IED AUG 18 2020 CITY OF-1 RD BUILDING DI,, 'ION 1 I 2 3 I 4 Scope of Work Latimer HVAC will perform the following scope of work: Latimer HVAC 1. Provide and install new split systems (gas furnace and AC) replacing existing. CCB#220839 2. Common return plenum- provide smoke detector for equipment shutdown. A B C D 3. Provide (3) ceiling mount exhaust fans for restrooms. 4. Ducting and air distribution modifications as drawn. OFFICE COPY 5. Gas piping extension to water heater. Flue water heater. 6. Ductless HP for 2"d floor break room. MY OF TIGARD_ REVIEWED FOR CODE COMFLUNCB Equipment Schedule Approved: 'T.1 I D ±1 V-3 3/4" t36'-V t16'-3 3/4• FI-. Carrier 595C5B120E24--22- 120,000 Btu @ 96% AFUE. 1990 cfm @ 0.5sp. 1HP. 120/1/60- 14.9 MCA, OTC: s I 20 MOCP. In mechanical mezz. Provide mixing box economizer, connect to existing louver. PermAC1- Carrier 24ACC660B003 ton. 230/1/60, 31.1MCA, 50 MOCP. 57,000 Btu cooling, 14 seer, Address: L]OP ;In " — clef cS 16 economizer. 275# On ground. Address: (�R� V ce y M e �— _ F2-. Carrier 595C5BO8OE21--20- 80,000 Btu @ 96% AFUE. 1595 cfm @ 0.5sp. 1 HP. 120/1/6P i4.5 MCA, Suite #: 20 MOCP. In mechanical mezz. Provide motorized damper for outside air, connect to existing louver. BYE— '' Date: AC2- Carrier 24ACC648AC03- 4 ton. 230/1/60, 24.31VICA, 40 MOCP. 45,000 Btu cooling, 14 seer. 213# On ground. i ® ® Ft ,� *� HPi FCU3- Carrier 38MAQB12R-3/40MAQB12B-3- 1-ton. 230/1/60, 15 MCA, 15 MOCP. 12,000 Btu cooling, 21.5 seer, 12,000 Btu heating, 10 hspf. Wall mounted. Outdoor- 83#, indoor- 20#. EF3- Panasonic FV05-11-80 cfm @ 0.25sp. On switch. S 3 �+ -�� 3)(qui^ l ��'(F6) S� I �3 ��IZ f4cN) ►�� S r 1 ► S`l s ' e' ' °Yj i I, �° ev n, i1 9- 1 "ZJ `� �"SR ( fi�C / ��✓2 ( GALS) 1`y l eAeAl Mechanical General Notes: OFFICE I OFFICE OFFICE OFFICE O tl1 C FA.a� 1. Cooling equipment does not exceed the load of the calculated requirement. 106 107 108 109 .n 2. All steel ducting will be 26 ga minimum galvanized. Flex per Mfg. Uj * 3. Heating and cooling ducting to be designed to not exceed 0.5 we positive (supply) and 0.5 we negative . ` (return). V W M I��`� 4. Provide programmable thermostat. S degree deadband minimum. 7 day. Microprocessor. Set program for W N 1 1 Zk I� ` night energy savings. LL P � a J p (4 2) L )�F�J —ry ZYXib 5. Seal ducting with UL listed mastic or mastic tape. � ( �FWR I I �' FIt.J�,l co 6. Fan motor does not exceed allowable, first available above BHP. / 7. Max leakage rate of OSA or exhaust dampers to be 4 cfm/sft @ 1.0 SID O (n O i `\If 8. Provide O and M to building owner. z C S' Q rSrX�m IzxLi j2hro O 64re Ivn IFs ) s R Q t� sviv&- Faso O CD O , I RE TROOM CENTRAL ROOM `f r S� " /Y 5 DQ NO EXCEPTION TAKEN • .i RESTROOti `` O - I -- -- ° l�// - ❑ MAKE CORRECTIONS NOTED �L 73 ❑ REVISE AND RESUBMIT i7 +r ❑ REJECTED ❑ SUBMIT SPECIFIED ITEM ❑ FOR REFERENCE ONLY, NOT REVIEWED V / ST G io�1:N Mr� 'This review is for general conformance with 1�1 design concept only.Any deviation from plans or 6699C 1 ' specifications not clearly noted by the Contractor I v�(1 ) aX � has not been reviewed.Review shall not 1 . FUP �'� , ` (t L 'L� - UP- `/ constitutes complete check of all detailed IS I �( 1. dimensions or count to serve to relieve the Contractor of contractual responsibility for any error or deviation from the contract requirements." Z I Z u i (v20 I�LJ iJu Z By Brendan Sanchez Date 7/28/2020 B { ff Access Architecture,LLC 400 Columbia Street,Ste. 120 Iu Vancouver,WA 98660 l X lv _y I ^9,i Z t L ham--—r H W� NOTE: Reviewed for aesthetics only. Ndri bil t v�— I1� I LOBBY � Legend 1 Zk 101 / _ 1% rs�I/ l V 2 / OFFICE OFFICE 103 I 113 I 112 :?>s1 - Floor Supply Register (FSR) REV DATE FILE 0C rx-o �fy �� SSR lel - High Wall Return Grill (WHR) F Thermostat/ FCU controller _ - Exhaust Fan �--- - Volume dampers / O - Smoke detector J - Existing duct, remove unfaced insulation. Seal duct, insulate R-8. - Louver - Existing high wall return, replace grill with new. DATE: I [111111110000 - Duct 6 3 - Existing floor supply register, replace with new. —� - New floor supply register. ' 10 >, FIRST FLOOR PLAN — VAC, f#,l,n 1/4' V-0 VALIDITY OF PERT fiT THE ISSUANCE OF A PERMIT BASED ON CONSTRUCTION DOCUMENTS AND OTHER DATA SHALL NOT PREVENT THE CODE OFFICIAL FROM CF ERPr: _ i::3.4 I 2 I 3 I 4 �- 6 - Latimer HVAC Latimer HVAC CCB#220839 HEATING.VENTILATION AIR CONDITIONING A B C D GAS- D t16-3 3!4" t36'-0" ±16'-3 3!4" Per 2019 OMSC Table C402.4(2) 213si inlet pressure @ 1.0 Psi pressure drop Max 50' developed length 1.25" pipe adequate for 583,000 Btu 1" pipe adequate for 284,000 Btu W pipe adequate for 151.000 Btu 1 Load- Fl- 120,000 Btu F2- 80,000 Btu WH- 199,000 Btu Total 399,000 Btu enLo�'� W117U✓ S w( F � 5 / (k� YtJQJ�r I,23°� Lj I AI�w IN U w N L LL U) � Q z 0 C Of I - - ----- ,S , L �W N 5N€ � � M Z U) F- tfl`�( l C75A OvvT 0 0 sA O DN I I DN Y 0 Pte' : s1"�� Q co ,MSC �� LJCIj1ll�tr Ar �►J��7:&r4_ - Ow BREAK ROOM 201 OFFICE G ZX -- 203 ZC62 AV Y 7 K- (5v dv%) B O/l-NM �iJ G,•�r�� I c. I X NO EXCEPTION TAKEN ❑ MAKE CORRECTIONS NOTED 0 REVISE AND RESUBMIT 0 REJECTED 0 SUBMIT SPECIFIED ITEM 0 FOR REFERENCE ONLY,NOT REVIEWED 'This review is for general conformance with Ventilation Requirements- based on 2019 OMSC table 403.3 design concept only.Any deviation from plans or specifications not clearly noted by the Contractor - has not been reviewed. Review shall not constitute a complete check of all detailed REV DATE FILE Outside Air Ventilation dimensions or count or serve to relieve the AZ RP RA VBZ EZ V0Z Natural Ventilation Contractor of contractual responsibility for any error or deviation from the contract requirements." Room Code Max Ventilation Area Outdoor Exhaust Exhaust Description/n Room Area Occupant Density Occupancy Factor Air Rate Breathing Zone Air Distribution Zone Outdoor Airflow Rate Airflow Yes Area Area Occupancy Classification Air Distribution Configuration By Brendan Sanchez umbers (SF) (People/1000 SF) (People) (CFM/Person) (CFM/5F) Ventilation(CFM) Effectiveness Airflow(CFM) (CFM/SF) (CFM) or No Reqd(SF) Avail(SF) Lobby 101 230 10 5 0.06 25.3 1 0 0 yes 9.2 21 Main entry lobby Ceiling or floor supply Date 7/28/2020 off 103 345 5 5 0.06 29.325 1 29.325 0 No Office space Ceiling or floor supply Access Architecture, LLC off 113 160 55 0.06 13.6 1 13.61 0 No Office space Ceiling or floor supply I 400 Columbia Street,Ste. 120 off 112 160 5 5 0.06 13.6 1 13.6 0 No Office space Ceiling or floor supply Vancouver,WA 98660 restroom 110 50 0 0 0 0 1 0 70 80 No Toilet room-public Ceiling or floor supply - - NOTE: Reviewed for aesthetics only. 4 hall 260 0 0 0.06 15.6 1 0 0 Yes 1 10.41 42 Corridor Ceiling or floor supply restroom 104 50 0 0 0 0 1 0 70 80 No Toilet room-public Ceiling or floor supply restroom 105 50 0 0 0 0 1 0 70 80 No Toilet room-public Ceiling or floor supply room 102 590 5 5 0.06 50.15 1 50.15 0 No Office space Ceiling or floor supply break 270 5 1 5 0.06 22.95 1 22.95 0 150 No Office space Ceiling or floor supply F1 2165 OSA MIN- 130 Ceiling or floor supply off 106 250 5 5 0.06 21.25 1 21.25 0 No Office space Ceiling or floor supply A off 107 160 5 5 0.06 13.6 1 13.6 0 No Office space Ceiling or floor supply off 108 160 5 5 0.06 13.6 1 13.6 0 No Office space Ceiling or floor supply off 109 415 5 5 0.06 35.275 1 35.275 0 No Office space Ceiling or floor supply DATE: (f i off 203 100 5 5 0.06 8.5 1 8.5 0 No Office space Ceiling or floor supply F2 10851 1 1 1 1 JOSA MIN- I 93 TOTALEXH I 390 I M2 , 0 m SECOND FLOOR PLAN 1-41044l�, A2.12 1/4"= V-0"