Loading...
Plans (45) FPS2021 -00067 OFFICE COPY nFFICE COW F1SYSTEM DESIGN - Kiddie Academy Tigard GENERAL NOTES n RECEIVED 4 Z System Design to be per NFPA#13 2016 Edition Y o 1. SYSTEM DESIGNED AND INSTALLED PER NFPA-13,2016 Ed. �Al` ¢ YO�e I a Ordinary Group II (Shell) 10' x 13' 2. HANGERS SHALL BE PER NFPA-13,UL LISTED AND/OR FM APPROVED 1 , 1 Z Light Hazard (Classrooms/Offices) 15' x 15' 3. SCHEDULE 40 PIPE TO BE USED FOR THREADED FITTINGS CITY OF TIGARD 9 c 4. SCHEDULE 10 OR FLOW PIPE TO BE USED WITH GROOVED FITTINGS I I I Tn Utilize K5.6 Pendant/UprightSprinklers 5. ALLWIRING,PAINTINGAND PATCHING BYOTHERS s 1 3 1 BUILDING DIVISION = j Overhead Sprinkler Head Spacing not to Exceed 130 SgFt 6. INSTALL FLEX-VIC HEADS AT LAY-IN-TILE CEILINGS r F I 1 I w Classrooms/Offices Head Spacing not to Exceed 225 SgFt FREEZING IS THE OWNER'S RESPONSIBILITY TO PROVIDE ADEQUATE HEAT TO PREVENT WET SPRINKLER PIPE FROM 10 gP 8. MAIN DRAINS,AUXILLARY DRAINS AND INSPECTOR'S TESTS ARE TO BE PROVIDED AND INSTALLED IN , ACCORDANCE WITH NFPA-13 9. ALL SYSTEM CONTROL VALVES SHALL BE OF THE INDICATING TYPE WITH TAMPER SWITCHES 3 3 (WIRING BY OTHERS) 10. ALL SPRIGS,DROPS AND ARMOVERS ARE I"SCH.40 PIPE U.N.O. r 11. ALL OUTLETS FROM MAINS ARE WELDED U.N.O. ` 12. RIGID COUPLINGS SHALL BE INSTALLED ON ALL GROOVED LINES U.N.O. i T 13. SPRINKLER SYSTEMS WILL BE MONITORED BYAN OFFSITE CENTRAL STATION INCLUDING FLOW SWITCHED rnn nnW AND TAMPER SWITCHES ON CONTROL VALVES(BY OTHERS) Iul eALA ILA p 14. THE EDGE OF ANY JOIST, BRACING,PIPES,E.Q. BRACING,HANGERS,LIGHTS LESS THAN 1 FT.WIDE, ETC.,TO B n r LOCATED MINIMUM OF V-2"HORIZONTALLY AWAY FROM ESFR SPRINKLER HEADS z 16. BRANCH LINE HANGERS TO BE LESS THAN 6"FROM TOP OF PIPE TO ATTACHMENT POINT U.N.O. SECTIONALFire m --- SCALE: N.T.S. KEYNOTES 0 ` 4 e ROOF ASSEMBLY: Fire Riser r••••••••.............. MEMBRJP0ANE Ir COVEO8 RIGID INSULATION TO R-38........ G u _. I �� .-.}" ,•YL'd -4 I -DECIONG PER STRUCTURAL YLU EDC •I' ( i O CORNICE BEYOND in ° ° N - - - - -- COLOR SEE EXTERIOR ELEVATIONS O3 CANOPY-SEE UA8.1 FOR MORE INFO F _- 8 HANGER DE SAMMY NO. J c c L OENTRY CANOPY-SEE 1.4-6/A9.2 FOR MORE INFO 0 C C J Z r- .- : ° I ` - ._.__ i Side Sammy Screew 2 \ \ . SI 0 ROOF JOISTS PER STRUCTURAL �. ur cam. I 1 _ ?"I' I « ...._ ; s r4 ✓• t.'^. 1 O SUSPFNOEO ACOUSTIC CEILING TILE-SEE REFLECTED CEILING PIAN V _z 2 Q VI - 1 (0 LL = = W Q to -- ` All 4t / STOREFRONT CA AZINr Q 13 J !n -. Area , 'O fWork,,- : I� Rod ad Z�7 O FRAME COLOR GRAY TINT COLOR,DARK BRONZE J x o 0 0 to LL ' -.r u ._,. .. .r`+ ." - Pipe �'in CONCRETE SLAB PER STRUCTURAL-- O ~ ~ Q ' I ; u , I Swivel Ring , O PROVIDE BASE PER GEOTECHNICAL REPORT O �'e r ^. --�—+ v�� T I Oq RECESS FOR FLAT SCREEN N-- PFtOVIC1E FOVJER/DAT4 CO O ' 10 LAMINATE HEADER OVER ALL CLASS ROOM DOORS W (n FRP WAINSCOT - Y co OFFICE COPY . NZ_ co LL LL LL LL G REVIEWED FOR CODE COMPLIANCE Lu } I CITY OP TIGARD a. a _ - 'Approved. s OTC:- permit TC:Permit aQa L nQ P1 9 -7 0 Address: U pV p!?a><3oow 1 U1. j Suite#: t Z I, I ! By: Date: Z n Lu II ! N I LU d p j Tn Z w w x � U) s is � WYAT T c v FIRE PROTECTION, INC. LI 0 9095 S.W.Burnham O Ol Z E 7 Tigard.OR 97223 �+ 0) 05 !l7ffi7 Fire Hydrant Fire Flow L 4) to m to PROJECT I SW 741 AVE. 7 SW DURHAM RD. (A � � a C o s gP"°Nsid� ADDRESS !, TIGARD OR O a Q •� n UO LLI a. L01 00 LUQ I6 --- - -- -- a 4.0�M r 3, Ln 't3 CROSS STREET '' ----- — -- - i- E 7uj� '� � o uJ FLOW SW 741 JUST NORTH OF SW DURHAM RD. � � va Y ZtO-, if LL I , c� LL I LOCATION a � j STATIC 112 AUTOMATIC Q ;% 3 PITOT RESIDUAL ', 90 / 1 2.5" PITOT FLOWED FIRE PROTECTIO o I GPM ; 1767 m SYSTEMS, INC. X 4 1 18,296 calculated per NFPA 291 s GPM AT 20 PSI CL % DATED '; 03.16.18 9:30 AM (n I MONITOR " HYDRANT SW DURHAM RD. @ SW 741' SW 7411, SOUTH SIDE OF LOCATION DURHAM RD. 1 -1 W STATIC 1112 • R DETAIL 111 y SYSTEMS DATED j 03.16.18 9:30 AM SCALE: rv.rs WITNESS �79F PROSEG�`O ...... Qu(haL ......... ....... WITNESSED BY '. 5 19435 SW 129th AVENUE Parts Legend TITLE i TUALATIN. OR 97062 (503)692-9284 Y.iar Key Note Size Description Quantity ORGANIZATION CITY OF TIGARD PUBLIC WORKS FAX: (503)692-1186 Supply Flow Test Data 1 4 From The City 1 OR CCB#0067534 Static Pressure 112.000 2 4 Flexible Coupling 1 SIGNATURE Residual Pressure: fo.000 WA CCB#AFPSYI.091 BZ Flow 1767.00PLEASE PROVIDE 3 4 Globe UM 1 PERFORMED BY JACK GARDNER __ _ Outcide Hose Flow 1250.00 ' :,` ''@ 4 2 Main Drain 1 COMPLETED NFPA 13 = � 5 4 To System 1 c• DRAWN BY: M. $trOf1 6 Spare Sprinkler Box 1 MATERIAL AND TEST 9 7 Bell (Wiring by Others) 1 CERTIFICATE AT DATE: 2021 May 4 FINAL INSP>ECTIO"I - - — AHJ: City of Tigard SITE MAP FLOW TEST EHEIAAD THER INKLER SHEET: SCALE : 1/32" = I' INCH INGSP- 1 of 2 10-01 AFP. PROJECT#: 21072 (3) 2x8 GLB 51/2 x9 GLB 5 1/2 x9 TYP(2) GL8 5 1/2 x6 GLB 5 1/2 x6 GLB 5 1/2 x6 ^ (3) 2x8 GLB 5 1/2 x9 (3) 2x8 _ (3) 2x8 Hydraulic Information z I ( I i Remote Area 1 Shell CO OCCUPANCY CLASSIFICATION Ordinary Group 1111A O o C 0 2T-0 21 ,'-0 ^�+2 ' 685 2o'-T/� 21'-0 DENSITY(gpm/ft2) 0.20 for 1500ft2 (Actual 1514ft7) > 0' 1 -111%1 -11 1 '4 6'-11 -0 1 3'-0 91,-0 �2'-0 11'-7'/z 7'-91/2 2'-7 z 12'-0 6'-0 5'• Yz 12"0 3'-4'G 1 '-1 W N I TOTAL HOSE STREAMS 250.00 x I ii TOTAL HEADS FLOWING 14 i y 11/s 1K 1'� �! I 1'/s I 11/: ^ 1 1X 1y. ! K-FACTOR 5.6 10.10 21'-0 21' r-0 2 ' 20'-71/: 21.0 21'-0 TOTAL WATER REQUIRED 637.02 a•1 1/: s'.1,v2 v-112 4-11/2 61-11 5'-0 13 11-.7% 14-" 7'-91/2 2'-71/2- I 12'-0s'-0 s K ' ' TOTAL PRESSURE REQUIRED 62.333 W ! (gP ) BASE of RISER m 637.02 m o M yam° I BASE of RISER (psi) 62.333 z 1 I K IT K 11/2 1a , 1K SAFETY MARGIN (psi) +46.335 42.6% 5 2 0 10' 0 21' 2 ' '-0 2 ' 1 I 20' K 21 -0 1' (P ) ( ) N I 1 1 K 1K I 11/: 1'/z 1'/s 10' 0 i X21' 2 '-0 1'•0 2 ' 21' 0 2V-0 , -1 ' V- 1 I , -1 6'-1+ B5 ,9', T-0 8'-0 GL r-0 11'-71/2 Z 12'-0 8' K 5'- Hydraulic Information G _ .. Z'f 1/ B51/8 12'-0 S'-0h LB5 10,h 6 g Y Y Y W ' ! 1144581/2 11 -- 1Q �¢61I� — - Remote Area 2 Classrooms N ! 779 1177 d . I OCCUPANCY CLASSIFICATION Light Hazard W 4 8 8 i 11/2 11/2 1'/o 1;k K I 1'/z 1 1'/s 1'/z s'-10 2V-0 21 .0 ' 21' 21' 2r-0 21'-0 DENSITY (gpm/ft2) 0.10 for 1500ft2 (Actual 926ft2) 0'-1 8-11'/2 2'-11 s 12'-1'/s 11 6'-0 1 ' 3'-0 8'-0 12'-0 11'-T/z 1/z 2'-7 z 12'-0 6'-0'/: 5'- 'h 12'-0 3'�1'/: 8-7K 11'-10'/s $ o z Z m w QUICK RESPONSE REDUCTION 10 -0 Ceiling (40.0/o) 900ft _O i= a TOTAL HEADS FLOWING 13 a ? + 1156 1157 II 1158 i 11 I 04 E a a ' z w I� I 6 I ( K-FACTOR 5.6 U Z E E E- Ordinary II.O. ' I I (n LL z r m y{3roup 20gpmlft2 for 1514ft O v v a I 1 TOTAL WATER REQUIRED 492.18 w } 1K 11/2 11/i 4I 11/2 1'/a ! ( 11/240 0'-1 s 11/2 2'-1t 2 1r /2�K s'aX s'-0 21' 0 s-0 , s-0 21' 2' 1r-rr2 21 -01/2 ra 2 12'-0 s' a1/2 s- 1/2 211:-0 s��i� s 7i 2r-0 TOTAL PRESSURE REQUIRED 89.973 x , , o ~ LL x 2 1r-101/2 -0 BASE of RISER (gpm) 492.18 m ILL 1170 1171 to 1173 529 ` { BASE of RISER (psi) 89.973 N I Z a w g �° SAFETY MARGIN (psi) +19.960 (18.2 k) o: .M.. 11/: ! 1'/z I 11/2 , 1'/s 1+/sit j I 1 z 1K F Y m m m 9'-10 21'-0 21'-0 21' 21' 1' 21',0 1'-0 Z o LL FF LL LL w 0'-1 8-111/2 2'-11 z 12'-1'/2 -11 6'-0 1 ' 3'-0 8'-0 12'-0 11'-71/2 7'-81/z 2• 2 12' `' S'- 'h 12-0 3' 4'h T/z 11'-10Yz $ a a 1184 1185 1188 118 858 i- Seismic Bracing Calculations 3)2x8 GLB 51Q x9 GLB 51/2 x9 GLB 51/2 x9 (3)2x8 (3)2 GLB 51/2 x9 GLB 51Q x9 (3)� (3)� Myw• ,01«TV LYV Me.f.ryxp Mva W ^-• 0 ILL SHELLC ��q/ d.n.2b ...� -- , s •�. 2 • AO z -ALE : YO'� = I' ,•.ansa.. ma ae.m..-w,n..rry>r•+-.oM>.-us,.r. Q o.r.aae.: ,au mew ame:nlu...e.m.a<e,w•.a sm r. z O uvam.a x..1/ ryas- +s+e mr xwq xsw- C? w.aaa es s-+1/ae.uw-.�+•a,xe.a T ILJ r m A B ; C D u,ua. >m ue.a sa.exra_new M-+wro.a x+�s rsxm u.m..n.L. rim s.umm e..0♦..•mnry own F 1 V OF..Mw M.rn•,l.n z a.s•ee.dc-•..ay sw.- rra,rm.'• noxiaorawao,we. n.swu..mm xu ceew,.m rme aw W , rma ,w1w Ae1•M 1 J 'R•baY« r tt.t au. 'n.a B,em k••M1pNnn Num°ar Saf 1 e.nw,,,y. nam Ilo ne alwaimp4nl 0 6 FLalerai Brace z 17 co• O LL Oan.Yr °-aP•• a+, O:+:mr uw'W+ As •� ' O FILE * •.\ IRECT R' *�� .-.wa .-^+ 'm°wa 3 E rop 1 '-0' C G "� a .,.,.. L. y pq 1'h 9 to SER ^+ 1x tx IV. 1'h r""'�'° s"' 4-11 Ir Q z -0 zr-0 xr-0 Q-0" C G 21' - b xr-0 ir-0 2r-0 zr-0 VI •••—• `a 10'a S• YJx-4'-1K 5'aY: Jx '3'J 8'J T-2x 4' 'A 4'-11 8'-t'/s t'-11 S -0'h: 7-0' 1'•7 • T•10'h 8'fi'h S-0'/s 3'•11 54X 3'-11 B'-1 3'-7Y. SJx 9'-11 T-8 = v a X ''-7K X •; :4 J 7!' Y 2'"� q 0'-7K a7 q' 4 9 o? 0'3'/.D'9 V O. o xx 1'-0x 0'-11x Yi D ,8 T-1 q 6' , 9, q 6ID q I Fpm I ' „' ^+�=N 0 a Q •� ^+ '-10 ARE 2 s q ^+° EL Ii x, ^+" S ^+ a — — — ^+ +ps 9 ^+ *p�• ' ADCA 11 'a • +pA• * ��' Aft CO ` Ln w ODD FRS TOD LcRS ' If 0 5YR LDSSCH �a rx�a:K a max:-mm.a,xe e,rma,- nr a �� 1/t O 0'-0" LG - 10'-0" CLG 10'-0' CLG E �� a O 14.1 1K 1'/' 1 '-0" C G 1K 1K 1K tx 1x tx Z •� zi• 21'-0 »-0 zr-0 era O cJ (or Y Z LL 11'•11 21-0 8'-0 1'-1'h 71 11'-11 4•-11/ 8•J^,— _ 21•-0: 12'-0 -17Ys1 11' Ya 8'• tx 1- 1018 {'-11K 5'Jx9'-7x Jx '11'40x 1h i R CEt i t rs,c-0h ra s-0x r-0 o•-Iva 7-0 x A i L I 1 '-0"CL 's s }'m Q ^ x 1^ ^* ^ I + ^ 6-0x 11 - I I I 1 AUT MATIC 'q IY_ R W 1x— !4 q , : I - : ,h 1x , _- - ,Y . 1K 7 FIRE PROTECTION Y1--0 ��b h' 7r-0 •4Y I ' ii 2r-0 Yr Yr-0 2i'a .- - S- a 2'JY,-4'•tY, 64P6 8'JX 7.10 7J 4'-0 'Jx S2x -0x •11 Y: 5-7Yi 5'J 6'd 0'-11x t7d •1 O-10x 50% -1 3'-11 0- x 5.4/, 7-11 7-t 3'•7x 1'•11'J 9'-0 1'-0 t-117-Th' 'A 101-5 2-" 1x0•dx +6� r;, I I -JAN'S I�-'� e•Jv. 3•-tt 4••7 . ^ i — I +p2' q ", ^+57' ^� 0"CL Seismic Bracing Calculations SYSTEMS, INC. 2 11 i7' Y r .A,,&" r 2E - 1x • q .Q 1'/,', '2 'tx ^+ q 1x V 7x :�. 1x, 7-10x t'-0 21'-0 -21'-0 21'-0 21' ' - - 'i 21'-0 0'-0YJx 9'J'h 8'-0 3'-0 176 4'-11x 7,5 11'•7 y-80'•11'h 17' 'h i -3Y, 8'J .1Ki r _ 8'i 5'4x r-7 �'a �'-7KI 4'6 9'.8 1'-1 SJY. .7-lx 1.3 .. r-7x Y-0Kr-7 Y-1 7-11K -11K aif 7-0 e..r.Miro„ntllen s.w,ac e,.r..wMm«,r. 3 1 gp ft O 2 ft' T SH R SH R m� TT�; 8 j9'- "CLG 7 _„ C1K6 ^+ ' 1x ” . 1x 1/. g_ 1y. tx 1K -21'-0 ry 21' 21'-0 21'-0 11-0 21'-0 T-0 9 6'-7 4'A 9'-11' •7K_S3 -0 •1 T-01' 3'-1'h 3'A'/e 8'J 10'-0 S-0x— '-11'h SJx S-1tx .• O �' _ _ _ — _. _, 0'•7 '-7 -_� gh' 8'Jx � 7-0 iwxu.a on•.-' o.r ur. .�, m u.+o:s...a..cw [n 7Jx TR-w-7r- 1'•11 h'7A � Ya`h rd 7-tx � - Ca 7� yam■. 11 1 �. � ' ^, 5p o A I.- Vv aIMp'_,q 'A •q b R ,•n w-• sm ,:oe,e.e xm,a •.mm ao.-.wexey en.c 9 �i'D,G8f1� �. 286 q 350 288 p q +i q ^+ +i rr +c 4 • 9 b ^ b r' ^ b 301 ^ b' 6� ' h' ^ b b 1/o s.unw°ar.ma..U.61,came C1 k lyE O 912 973 2 Y ,� C' 913 ^e ^' AREA 302 R :-A8 ARE 9 ^+ ARE 10 a.wsrrtNaawlm SRF PROTEC'� a H r rr 4211-0 YR O DS 3Y OL ow« ar ysw .- m.,- +► +s sr „ _ -e 19435 SW 129th AVENUE b 1x b ^ q ^� v ^ / q tx c� - fit 1x .y° tx ipa' 1x .r tr �� 1x �� ,, .'..« TUALATIN, OR 97062 2r-0 b zr-0 ^+ zr-0 2r-0 ^* ii a—++' Zi-0_^* w+ ^* xr-0 ^* 503 692-9284 4•-11 3• /, •7Y, YJx 'e 173 1-0 3'•11'/,0'-10'/, T-2 e•-lox q Ir-11A -tt`/. r-11 T-1x 7- tx rax • 7. 1'-7 178 &.0 S-0% •-Nx - d'.' 8J74 S•11x q S-0x i, q 7'-lox Y-1x 'q 7-0 0•d 0'6 '" ,«,o,-..,.e o.•. FAX: (503)692-1186 A' b 8¢ b �- 1-17 � q � b .. b Y-7K 08' b � + 376 377 ^ 379 380 ^ ^ 380 zr OR CCB#0067534 ,> R A +' b e / r ar '° m— .m a� �maa saz ^ t;, H no x eiw"m wro WA CCB#AFPSYI'091 BZ 842 977 H 943 rr 975 z1/ 944 945 10' 0" L >r r >r H 391 H - e e&a a I I C I N q N >9 n.m.w•«--wec.km.a:-Irw-c.wal H b q q Iq tx b �4r� th'_ !4 b tx - '4 / 1X ^'} 1'/, - '9 co• os 21'-0 b b b 21't b b b 27.71 ''p 21'-0' 2V-8 b '-0 b 21'-0 b • b b. • 21'-0 t Td 3' 6 7J'/s x 0•x T•2 8'-10'h S-1'6— r•71 3'•1x C-11x 1'aX-0'• •t'-7 178 1'-11-5'-0'h—S-0x— '•11'/,— 5'JYs S-11x e'-0x_ T-10x J 7.8 r ^s•�+'^^-'w'r� ems w4 rm sn.e M. Strong 1'•11'-0 3••rh1 JK Ye SJ -Lf474 'r.8 4'.0% p, 7.111/, 8, 5'-0 7-0— 0'-lox 2'-00'-0 ."i; _ _,7 ., sn,� DRAWN BY: r b - DATE: 2021 MAY 4 503 +r +a 824 ^+ 626 +i *i. ' ^+ +► ^+° A- 4 ^+� +° + rw urn"' ^ ^ ^ ^ ,. . ^ 520 ^ ^ ^ ^ ^ 4 1001 986 618576 987 988 h+h, 521 AHJ: City of Tigard 620 CLI ISSR.00 rLL7 J �a E.�a - oW as .e,.e a�,.me,a SHEET: SCALE : V8«= I' FP-2 of 2 063 AFP. PROJECT#: 21