GENERAL NOTES ICIII'TYY��O(F;TIIGAh!, 00OO ssoe@)
—� A. REFERENCE DRAWING E0.1 FOR SYMBO��LEGEI TVIS'Or
® -___ _ GENERAL NOTES.
a B. COORDINATE ALL TV MOUNTING HEIGHTS WITH
IOEI�Q
AM
L
ARCHITECT PRIOR TO INSTALLATION. CONSULTANTS:
EXAM 5 EXAM 4 EXAM 3 C. COORDINATE WITH ARCH ITECTECTURAL ELEVATIONS
112 113 114 AND FURNITURE LOCATIONS/FURNITURE
MANUFACTURER'S REQUIREMENTS FOR
- _ - - RECEPTACLE MOUNTING HEIGHTS AND LOCATIONS
® ® AS REQUIRED. f 1 IGD
ItlUI ..
e.,1) ) i3ODECOMPLIANCE
D. ALL RECEPTACLES, INCLUDING PATIENT CARE AREAS REVIENXT10064`'
SUCH AS, BUT NOT LIMITED TO, TREATMENT, Approved; �LCa03I=
NDIVIDUAL CARE, AND EXAM ROOMS, SHALL HAVE
REDUNDANT GROUND PER NEC 517.13. OTC: ( _ I
SLC b{�Pi
Permit #: Im 19
C E. PROVIDE A METAL RACEWAY SYSTEM, METALLIC Address: !T1 b f✓
CORRIDOR CABLE ARMOR, OR SHEATH ASSEMBLY THAT C
QUALIFIES AS AN EQUIPMENT GROUND CONDUCTOR Slli[C #:
IN ACCORDANCE WITH SECTION 250.118 OF THE NEC By:
IN PATIENT CARE AREAS AS REQUIRED BY SECTION
517.13 OF THE NEC. AN INSULATED EQUIPMENT
GROUND CONDUCTOR SHALL BE PROVIDED IN
ADDITION AS INDICATED IN SECTION 517.13 OF THE
4F NEC. THIS INCLUDES ALL LIGHTING IN PATIENT CARE
AREAS. NON HCF RATED MC CABLE IS ALLOWED FOR
PATIENT ) THOSE AREAS NOT IDENTIFIED BY THE ARCHITECT AS
TOILET PATIENT CARE AREAS.
110 SEAL ON THIS DOCUMENT AUTHORIZED BY:
NURSE
F. ALL BENDS IN GROUNDING CONDUCTORS SHALL
j \ 12' RADIUS.
A MINIMUM 12RADIUS.
STATION d ,,
G. GROUNDING CONNECTIONS SHALL BE MADE AS DC�
_ ml PNCE RE ) FOLLOWS TO FORM A CONTINUOUS GROUNDING 5 l
115 SYSTEM: CS~ LOUISE M.
° A. CADWELD OR THERMOWELD ALL CABLE TO CABLE. SCHLA=R (7
B. CADWELD OR THERMOWELD CABLE TO GROUNDROD. 0
p+ H
---JJJ C. CADWELD OR THERMOWELD TO EXISTING • TOLEDO,OH
------rr-------r�
\
e C103 GROUND. � '!>1141 lep
, ARI-11622
RI-11622 p
H IDENTIFY ALL
EXPOSED NG CORRIDOR / Fu
LOCATE 4erL C
X-RAY 09/02/2021
-
_____ _ VIEWING
AREA I BE MADE TO THE W. CONNECTIONS TO EBPORTIONOF THE COLUMN AT
UTILITYDING STEEL COLUMNS SHALL
108 T T T 1168 � i 18"ABOVE FINISHED FLOOR. PROJECT INFORMATION:
CI tt $JL J. GROUNDING SYSTEM RESISTANCE SHALL MEASURE
WI AT 3 OHMS OR LESS AT ANY POINT OF THE LOOP.
INDIVIDUAL GROUND RODS OR GROUND ROD
L—� 76 CORRIDOR CLUSTERS SHALL NOT MEASURE IN EXCESS OF 25 T I GA R D, OR
4r4.,
pp PHYSICIANS LL �Ji C102 OHMS OF GROUND RESISTANCE. ( '16'75 SW PACIFIC HWY.
1
BREAK ROOM i J K. PROVIDE TAMPER PROOF RECEPTACLES AS
104C REQUIRED BY THE AHJ. ALL RECEPTACLES SHALL BE TIGARD, OREGON 97223
L SAM 1 EXAM 2 X-RAY HEALTHCARE RATED.
49
105 106 116A L —�
L. ALL MATERIAL LOCATED IN MECHANICAL PLENUMS
SHALL BE RATED FOR SUCH INSTALLATIONS.
PLAN NOTES
- - - B
1. SAWCUT FLOOR AND INSTALL(1) 1"CONDUIT FOR
POWER AND(2) T'CONDUITS FOR DATA. COORDINATE
PATCHWORK WITH GENERAL CONTRACTOR AND ANY
i/ BELOW GRADE UTILITIES PRIOR TO CUTTING FLOOR.
®�I
2. COORDINATE EXACT LOCATION OF CEILING CLIENT INFORMATION:
\ ADMIN MOUNTED PROCEDURE EQUIPMENT DEVICE WITH
\ 104A TRIAGE 1 / EQUIPMENT INSTALLER PRIOR TO INSTALLATION.
PRINTER 103A
MANAGER CHECK-OUT % 3. LOCATION FOR NEW DATA TERMINATION. BOND NEW O
GROUND BAR WITH 1#6G. TO THE GROUND BUS IN
--I1048 C101 PANEL MPA. MAINTAIN CLEARANCE AROUND
EQUIPMENT.
G T'S0316 G 4. REFERENCE ELECTRICAL SYMBOL LEGEND, SHEET AMERICAN FAMILY
�� -� E0.1, FOR DESCRIPTION OF SURFACE MOUNTED
/� / MULTI-OUTLET RACEWAY.
J
LOBBY
Bl , CARE
5. PROVIDE 120V POWER FOR REMOTE FLUSH VALVE.
CONITRA FY EXACT TOR. ELECTRICAL REQUIREMENTS CONTIRACTOR TOTH G 3700 CAHABA BEACH RD
® PROVIDE ALL FINAL CONNECTIONS. BIRMINGHAM, AL
TOILET 1 /
- . .. _ _
O 102 6. PROVIDE 120V POWER FOR DOOR SECURITY FROM 35242
a / . THE NEAREST 120V GENERAL USE RECEPTACLE
VESTIBULE CIRCUIT. ELECTRICAL CONTRACTOR TO PROVIDE ALL
FINAL CONNECTIONS. CLIENT PROJECT NO:
1018
7. APPROXIMATE LOCATION FOR (2) INCOMING 2"
COMMUNICATION CONDUITS, EXTEND CONDUITS
O WITH PULL STRING TO NEW DATA LOCATION.
REFERENCE PLAN NOTE#3 THIS SHEET FOR
j ADDITIONAL INFORMATION.
i
I
I
.7 09-03-21 PLAN REVIEW CITY SUBMITTAL
A NO. DATE SUBJECT
A REVISION OR ISSUE
SSO1001 Madison
Architects, L.L.C.
1001 Madison Avenue
Toledo OH 43604
T. (419)255-3830
a_
TV PROJECT NO: 021 -01005-00 a
III�� PROJECT MANAGER: M.ALFIERI
DESIGNED: D. STEVENS of
ULIULI
- ---- --- ----- / CHECKED: Checker vo
Ir I/ DRAWING TITLE: o
FLOOR PLAN - POWER &
TECHNOLOGY ° (D