Loading...
Plans (102) M EC2022 -00077 SHOP DRAWING / SUBMITTAL REVIEW OFFICE COPS X❑APPROVED ❑APPROVED WITH CHANGES NOTED !N OF TIG ❑ REVISED AND RESUBMIT ❑ REJECTED Approved...lly' ............................................( ) Contitionally approved..............................[ j SUBMITTAL WAS REVIEWED FOR DESIGN CONFORMITY For only the work as described in: AND GENERAL CONFORMANCE TO CONTRACT DOCUMENTS ONLY. THE CONTRACTOR IS RESPONSIBLE PERMIT NO �fr�oz�- UU677 FOR CONFIRMING AND CORRELATING DIMENSIONS AT See Letter to: Follow.................................. J Attach................................ .I J JOBSITE FOR TOLERANCE, CLEARANCE, QUANTITIES, JOB Ad less: FABRICATION PROCESSES AND TECHNIQUES OF By: irifs� Die CONSTRUCTION, COORDINATION OF HIS WORK WITH OTHER TRADES AND FULL COMPLIANCE WITH - -- CONSTRUCTION DOCUMENTS. IOLDS Ou Y • BY: JASON KARAM DATE: 01/21/2022 PANDTm TTP. I!LQ HANGER PROCESS DESIGN, LLC FULLLLSTRAP P clRnATTACH PL® 12 GA. WIRE 12 GA. LAGS DUCE TO RIGm ASCTORUUCCULAGS W/ACOUsnCALAROUND W/TIN STRAP STRUCTURE FL►-�-11 --- I ------JI----------1L------J--------- IIL-----JI--- ---L-----�II---------IL------�J 'I$, 3f AY • CL- HEASMC RCIN O DUCTTO GRILLE 45" EVERY R CHA INDIRECTION `i Z C\2 CN2 HANGER Ful C.CUM. - - - I - i - - I - f - - F - � ELAN„ AL DOLUME ER -----J--------L-----J--------�----- --------L'-----j TYP. DIFFUSER O iTYP. DUCT p� ^ ---- --------�- ---__--- _-- -- -- 1_M A DUCT HANGER DETAIL Z Z N.T. .S - ; - E~ i Q a a SHOP DRAWING / SUBMITTAL REVIEW E-4 Z AREA OF WORK ❑X APPROVED ❑APPROVED WITH CHANGES NOTED � W KEYPLAN ❑ REVISED AND RESUBMIT ❑ REJECTED E'I Ex-I scAle: NTS SUBMITTAL WAS REVIEWED FOR DESIGN CONFORMITY E'�I Z E- AND GENERAL CONFORMANCE TO CONTRACT 1-4 DOCUMENTS ONLY, THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND CORRELATING DIMENSIONS AT Q W JOBSITE FOR TOLERANCE, CLEARANCE, QUANTITIES, /U W FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION, COORDINATION OF HIS WORK WITH CU OTHER TRADES AND FULL COMPLIANCE WITH co CONSTRUCTION DOCUMENTS. � BY: JASON KARAM DATE: 01/24/2022 PROCESS DESIGN, LLC w SHEET tNDEX F N 0 M0 . 0 - COVER SHEET, LEGEND , DETAILS Cn M1 . 0 - MECHANICAL HVAC PLANS z 2 . w N a w ROOF TOP UNIT SCHEDULE: ` z MECHANICAL LEGEND MANUF. AIR COOLING HEATING OPER. ELECTRICAL ARI RATINGS DUCTWORK FITTINGS (DOUBLE/SINGLE LINE) AND CONTROLS ABBREVIATIONS TAG NOMINAL AND AREA FLOW TOTAL INPUT OUTPUT WT. VOLT MCA MOCP EER SEER TONS MODEL SERVED (CFM) (MBTU) (MBTU) (MBTU) LBS.) PHASE REMARKS DOUBLE LME DUCTWORK SINGLE LIE DUCTWORK P.O.C. POM OF COMECTXNJ � Bo ®Roor� (E)AC-5 2 SEE PRINT 800 1 , 4 SUPPLY AS ELBOW U, 3 PH. FETIRNAIR ELEOWUP BDD BACKDRAFTDAMPER (E)AC-12 6 SEE PRINT 2400 1, 2, 3, 4 w -� -� OUTSIDE AWEXHAUS'ELBOW UP BTU RASH TH�L UNIT 3 PH. ^ OFM CUBICFEET PER MINUTE (E)AC-24 2 SEE PRINT 800 1 , 4 Y-1 SUPPLY AIR ELBOW DOWN (E) EXISTING 3PH. RETURN AIR ELBOW DOWN ESP EXTERNAL STATIC PFS NOTES: 1--1 AA/EXFWUSi ELBOW DOWN EM EXHAUST AR 1 PERMANENTLY LABELED FOR AREA SERVED. 4 (E)TO REMAINouTmE QPM GALLONS PER MINUTE 2 FACTORY ECONOMIZER w -------- FLEXIBLE DUCT HP HORSEPOWER MA MAKE-UP AIR 3 SMOKE DETECTOR r�, y� SQUARE ELBOW MBH MAN BTU PER HOUR w MFR MANUFACTURERRADIUP. (N) NEW nlll\rt**,III a RSD A0OUsELeoW OSA POUNDS PER OUTSIDE AIR VENTILATION COMPLIANCE SCHEDULE � w PSI POUNDS PER 8OUARE ITCH AIZESSH'v.NAMN INSI PEOPLE OUTDOOR AREA OUTDOOR REQUIRED SYSTEM ZONE AIR (SIZES BROWN ARE NET IlgDE) RA RERIFII AIR SA SUPPLY AS ROOM OCCUPANT AIRFLOW RATE IN AIRFLOW RATE IN BREATHINGZONE OUTDOOR AIR DISTRIBUTION ® SUPPLY AIR DFFUBER a RELOCATE HVAC OR AREA DENSITY BREATHINGZONE BREATHINGZONE OUTDOORFLOW INTAKE FLOW EFFECTNENESS (REM) R3.avE UNIT ZONE (SQ. FT.) OCC. / 1000 SQ. FT. (CFM/PERSON) CFM / SQ. FT. (CFM) (CFM) (Configuration) NOTES C/1 I--I SUPPLY AIR SDEWALLREGISTER (E)AC-5 SGYM 108 1029 10 20.0 0.06 267.54 267.54 1.00 COMPLIES rn REFERENCE TOTAL 1029 - - - - 267.54 - COMPLIES LORETURN (� LO ��M � a coNrEcsrTQExISirNGATTIiBPDNr. (E)AC-12 S GYM 108 1156 10 20.0 0.06 300.56 300.56 1.00 COMPLIES LO W ® O EXHAUST AIR cI3NKG REGISTERs CATK ^MF-AND QONDnm TOTAL 1156 300.56 COMPLIES 'i E" O A EaUPrMAW NUMBER (E)AC-24 S GYM 108 667 10 20.0 0.06 173.42 173.42 1.00 COMPLIES ® ROOF TOP EXHAUST FAN e SEE SCHEDULES TAN 109 51 5 5.0 0.06 4.335 4.34 1.00 COMPLIES F TAN B 110 52 5 5.0 0.06 4.42 4.42 1.00 COMPLIES a w ® QaN°MaMrTi�owAusTFnN REVLSION GGX 113 687 10 20.0 0.06 178.62 178.62 1.00 COMPLIES a 9 N tJ 2ozp DFIFUSEF/ SMARK µMBER TOTAL 1457 - - - - 360.80 - COMPLIES RETURN/EXHAUST AR 9DEWALL REGISTER 500 .--____-- ---_- -- -- `--- MVD MANUAL VOLUME DAMPER SCK SIZE 20KI0 Per chapter 4, section 403 8 table 403. 3642 TO 1 - -- �-TOTAL - -- J TOTAL 928 90 CAD No. 4538_ - - PROJECT No. 6089 -'® MD MOTOR®DAMPER CFM sm of the 2019 Edition of the Oregon Mechanical-Specialty code. PROPRIETARY Rao FIRE SMOKE DAMPER THESE DRAWINGS AND SPECIFICATIONS ARE CONFIDENTIAL AND SHALL REMAIN SHEET NO. ®VAV-1 THERMOSTATNOTED A®- WITH THE SOLE PROPERTY OF PROTEMP ASSOCIATES, INC. THEY SHALL NOT BE NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS CONTAINED IN THIS LEGEND WILL APPEAR ON DRAWINGS. REPRODUCED (IN WHOLE OR IN PART), SHARED WITH THIRD PARTIES OR USED moeo IN ANY MANNER ON OTHER PROJECTS OR EXSTENTIONS TO THIS PROJECT WITHOUT THE PRIOR WRITTEN CONSENT OF PROTEMP ASSOCIATES, INC. 1 of 2 i I I I I I I I I I I I I Z I I I - - - z C) I I I m a � U� C;d I I o o H 10 10 n o I I I �° I � � w d i Iw SHOP DRAWING / SUBMITTAL REVIEW O: f0 10 ❑X APPROVED ❑APPROVED WITH CHANGES NOTED .-i I oEPA DEMO T ❑ REVISED AND RESUBMIT ❑ REJECTED O s e SIDEW we wF_ SUBMITTAL WAS REVIEWED FOR DESIGN CONFORMITY RE — — AND GENERAL CONFORMANCE TO CONTRACT DOCUMENTS ONLY. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND CORRELATING DIMENSIONS AT pc) R• • JOBSITE FOR TOLERANCE, CLEARANCE, QUANTITIES, El— AO-4 `A01 FABRICATION PROCESSES AND TECHNIQUES OF m _ ND CONSTRUCTION, COORDINATION OF HIS WORK WITH I I 14 14 I OTHER TRADES AND FULL COMPLIANCE WITH i I - I JA" CONSTRUCTION DOCUMENTS. WER— — — — — — — — — — — — — — — s — gY; JASON KARAM DATE: 01/24/2022 c • O • O PROCESS DESIGN, LLC vas I I z I I DEMO 0.7E I kcn x (E) LL RETURN ~ • AC-12 En O • O Alii R 8 TON 00B A r DEM � A 74 • a ��n A a z G AC-24 Tao-si 2-70N - - - I - - - - - - - � i - I -MEN'S LOCKER LOCKER 115 0 1404 r: ,a WA ILS • TOW WALL TRANSFER ^� 8 1B"AFF - I S EB TYP(2) I rFF-F-1 4°a - I MEN'SID O — sEaVTRS — nsvtt,17 0 --1 M CHI I I w (R) I I STORAGE C I I� „I A 07 7- . - - z ttt P. N t0 Cm Cr O° -14 z � a w x qqq W fL d m CAD NO. 4538 PROPRIETARY PROJECT NO. 6089 1 HVAC—FLOOR PLAN THESE DRAWINGS AND SPECIFICATIONS ARE CONFIDENTIAL AND SHALL REMAIN SHEET NO. 10 THE SOLE PROPERTY OF PROTEMP ASSOCIATES, INC. THEY SHALL NOT BE o 1/8 -� —� REPRODUCED (IN WHOLE OR IN PART), SHARED WITH THIRD PARTIES OR USED m 1 NORTH 0 IN ANY MANNER ON OTHER PROJECTS OR EXSTENTIONS TO THIS PROJECT WITHOUT THE PRIOR WRITTEN CONSENT OF PROTEMP ASSOCIATES, INC. 2 OF 2