Loading...
Plans (94) M EC2021 -00436 I op MECHANICAL SYMBOL LIST GENERAL MECHANICAL NOTES RECEIVED INTERFACE NOTE: This is a standard symbol list and not all items listed may be used. E N G I N E E R I N G A. THE INTENT OF THESE DRAWINGS IS TO PROVIDE A COMPLETE AND WORKABLE FACILITY WITH JUN 17 2011 COMPLETE SYSTEMS AS SHOWN,SPECIFIED AND REQUIRED BY APPLICABLE CODES. INCLUDE ALL Abbreviations OA OUTSIDE AIR MITERED ELBOW WITH TURNING WORK SPECIFIED AND SHOWN ON THE ACCOMPANYING DRAWINGS, INCLUDING APPURTENANCES, CITY OF TIGARU VANES CONNECTIONS, ETC.,IN THE FINISHED JOB. BUILDING DIVISION A/C AIR CONDITION(ED) RADIUSED ELBOW OBD OPPOSED BLADE DAMPER B. ALL WORK AND MATERIALS SHALL CONFORM TO THE LOCAL AND STATE CODES,AND ALL FEDERAL, 100 SW Main Street STATE AND OTHER APPLICABLE LAWS AND REGULATIONS. Suite 1600 OC ON CENTER Portland, OR 97204 OD OUTSIDE DIAMETER AD ACCESS DOOR C. CONTRACTOR RESPONSIBLE FOR OBTAINING AND PAYMENT FOR ALL PERMITSINSPECTION CERTIFICATES REQUIRED IN ACCORDANCE WITH PROVISIONS OF CONTRACT DOCUMENTS,LICENSES,AND 503.382.2266 t�—�-1 ECCENTRIC TRANSITION, . AFF ABOVE FINISHED FLOOR RECTANGULAR OR ROUND www.interfaceengineering.com PD PRESSURE DROPY D. THESE PLANS ARE DIAGRAMMATIC IN NATURE,CONTRACTORS SHALL INCLUDE APPROPRIATE i FLAT OVAL DUCT DROP ALLOWANCES FOR OFFSETS AS REQUIRED TO ACCOMMODATE VERTICAL AND HORIZONTAL BOO BACKDRAFT DAMPER PH PHASE VARIATIONS IN THE LOCATIONS AND ELEVATIONS OF DUCTWORK,PIPING AND OTHER EQUIPMENT. BFF BELOW FINISHED FLOOR FLAT OVAL DUCT RISER E. MATERIALS AND EQUIPMENT SHALL BE NEW. WORK SHALL BE OF GOOD QUALITY, FREE OF FAULTS 4%QED PROFESS PRV PRESSURE REDUCING VALVE AND DEFECTS AND IN CONFORMANCE WITH THE CONTRACT DOCUMENTS. G I N EE �O BFP BACKFLOW PREVENTER ,y A PSI POUNDS PER SQUARE INCH y y FLEX DUCT F. COORDINATE DEMOLITION,CUTTING, PATCHING, ETC.WITH EXISTING FIELD CONDITIONS, ALL NEW 1744330PE�"/�/J BHP BRAKE HORSEPOWER �vvwvv�ij OR EXISTING WORK CUT OR DAMAGED SHALL BE RESTORED TO ITS ORIGINAL CONDITION. OGOtQ ' QTY QUANTITY RE CD CEILING DIFFUSER FLEXIBLE CONNECTION G. CONDITIONS SHOW ON THE PLANS RELATIVE TO THE WORK TO BE PERFORMED ARE BASED ON THE R RISE BEST INFORMATION AVAILABLE BUT ARE SUBIECTTO VERIFICATION. VERIFY LOCATIONS AND �Oq ELEVATIONS OF DUCTWORK AND UTILITIES TO BE CROSSED OR CONNECTED. w" F� CD CONDENSATE DRAIN � '' NON-SYMMETRICAL WYE �` H. PROVIDE CEILING ACCESS PANELS FOR COMPONENTS LOCATED ABOVE INACCESSIBLE CEILING EXPIRES: 12'3112 i CONT. CONTINUATION RA RETURN AIR SYSTEMS. MAINTAIN FIRE RATINGS WHERE REQUIRED. RET RETURN RECTANGULAR DUCT DROP COP COEFFICIENT OF PERFORMANCE '� 1. SEAL ALL EXISTING AND NEW FIRE RATED PIPE AND DUCTWORK PENETRATIONS WITH UL LISTED AND RPM REVOLUTIONS PER MINUTE FIRE MARSHAL APPROVED FIRE RETARDANT MATERIALS AND METHODS. CU CONDENSING UNIT RECTANGULAR DUCT RISER SA SUPPLY AIR J. CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS STEEL AND COMPONENTS REQUIRED TO SUPPORT CV CHECK VALVE DUCT, PIPE,MECHANICAL EQUIPMENT,AND PONE TS, HANGERS PANELS RELATED AI MECHANICAL SEER SEASONAL ENERGY EFFICIENCY RATING RECTANGULAR MAIN WITH EQUIPMENT. PROVIDE FLOOR SUPPORT COMPONENTS, HANGERS AND SEISMIC RESTRAINTS AS CW COLD WATER RECTANGULAR BRANCH REQUIRED. SF SQUARE FEET D DROP RECTANGULAR MAIN WITH ROUND r SH SENSIBLE HEAT BRANCH J DB DECIBEL SOV SHUT OFF VALVE �� RECTANGULAR OFFSET LESS THAN O D. DB DRY BULB 15" O SP STATIC PRESSURE }'�\ RECTANGULAR OFFSET MORE THAN O DIA DIAMETER W \� 15° 0 DX DIRECT EXPANSION T,TEMP TEMPERATURE Ez C ♦/� TD TEMPERATURE DIFFERENCE ROUND DUCT DROP LL� �/♦ EAT ENTERING AIR TEMPERATURE TH TOTAL HEAT ®—� � ROUND DUCT RISER EER ENERGY EFFICIENCY RATING EF EXHAUST FAN V VOLT TOTAL PRESSURE ROUND DUCT WITH ROUND BRANCH Cn 4< EFF EFFICIENT V W/ WITH � ===4 ROUND WYE Z ELECT ELECTRICAL EWW WATT SYMMETRICAL WYE T ENTERING WATER TEMPERATURE O W ♦^ WB WET BULB O 2 V♦ EXH EXHAUST Uj WC WATER COLUMN General = J F FAHRENHEIT a FD FIRE DAMPER Dampers —X—X— DEMOLISH ♦^ W FLA FULL LOAD AMPS EXISTING WORK Z a t n FIRE DAMPER V FT FEET FD FD CL S GAL GALLONS I FIRE/SMOKE DAMPER NEW WORK Q M J � J Z � GPH GALLONS PER HOUR 1 MOTORIZED DAMPER 30X16 RECTANGULAR DUCT SIZING bMD GPM GALLONS PER MINUTE . 11711 MD 30"PJ ROUND DUCT SIZING = O W Z SMOKE DAMPER U HD HEAD SD SD = �� VOLUME DAMPER —� CONTINUATION O L. 0 HP HORSEPOWER �-c I�FFICE COPT( W HTG HEATING X CITY OF TIGARD,` � � w DETAIL NUMBER AND SHEET LOCATION 1&EVII:WLD FOR CODE COMPLIANCE HTR HEATER Diffusers and Grilles X HWC HOT WATER COIL o _X EQUIPMENT IDENTIFICATION OTC: 1 1 EXHAUST AIR O \� Ii ® ® LOCATION Pensdt#: ! y) pC aF]d 1 -C '1 y_? Q W M a ID INSIDE DIAMETER O KEYED NOTE Addms m RETURN AIR Suite 0. _ IE INVERT ELEVATION Date: -7:� QQ���� � POINT OF CONNECTION � Z�ISHEET TITLE IN INCHES ® ® SUPPLY AIR A SECTION NUMBER AND SHEET LOCATION COVER SHEET - KW KILOWATT 12x12 CD-1 DIFFUSER OR GRILLE IDENTIFICATION xxx THE ACTIVATION OF A DUCT MECHANICAL LAT LEAVING AIR TEMPERATURE SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND Piping Systems LBS. POUNDS Ductwork Fittings SGNIBLESUAL AT A PERVISORONSTANTLY Y LH LATENT HEAT RL— REFRIGERANT LIQUID ATTENDED LOCATION REVISIONS MA MIXED AIR SHOWN ARE NET INSIDE) —RS— REFRIGERANT SUCTION OMSC 606.4.1 MAX MAXIMUM BELLMOUTH —RHG— REFRIGERANT HOT GAS SHEET INDEX MBH THOUSAND BTU'S PER HOUR CONCENTRIC SQUARE TO ROUND MD MOTORIZED DAMPER M1.0 COVER SHEET- MECHANICAL MIN MINIMUM r--� —j CONCENTRIC TRANSITION, M1.1 SCHEDULES- MECHANICAL RECTANGULAR OR ROUND MD2.1 ROOF PLAN-DEMOLITION - MECHANICAL N/A NOT APPLICABLE DRAWN BY r—X X—j DUCTWORK TO BE DEMOLISHED M2.0 FLOOR PLAN-MECHANICAL JDC NIC NOT IN CONTRACT M2.1 ROOF PLAN -MECHANICAL FLAT OVAL DUCT ELBOW CHECKED BY NO. NUMBER M4.1 ENLARGED PLANS- MECHANICAL VALIDITY OF PERMIT Rick Slienzi M4.2 ENLARGED PLANS- MECHANICAL THE ISSUANCE OF A PERMIT OB NO. NTS NOT TO SCALE BASED ON CONSTRUCTION � M8.1 DETAILS -MECHANICAL DOCUMENTS AND OTHER 2020-0465 M8.2 PHOTO DETAILS-MECHANICAL DATA SHALL NOT PREVENT DATE THE CODE OFFICIAL FROM REQUIRING THE CORRECTION 01/11/2021 OF ERRORS. OSSC 105.4 SHEET NUMBER BID SET M1 .0 FILE: M10 WOODWARD.DWG - M1.0 I EDIT: 1/11/2021 10:26 AM BY JONATHANC PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE (E) AIR HANDLING UNIT SCHEDULE SUPPLY FAN COOLING COIL HEATING COIL MIX BOX DAMPER CFM RETURN FAN NEW ELECTRONIC CONTROL DEVICES WATER CONTROL CONTROL MIN ARRANGEMENT TOTAL CLG COND HTG FLOW VALVE VALVE DETAIL MIN MAX TOTAL OSA OSA RA MA EA HW REF REF , INTERFACE SYMBOL AREA SERVED LOCATION TYPE CFM (MBH) STAGES UNIT (MBH) (GPM) SIZE TYPE REFERENCE OAD OAD RAD EAD CFM DMPR DMPR DMPR DMPR DMPR VLV LLV-1 LLV-2 OTHER NOTES E N G I N E E R I N G (E)ASU-1 MULTIPURPOSE MECHANICAL RM 1 7500 - - 94 13 3/4" 3-WAY 3/M8.1 1500 6000 6000 - - 1 1 1 0 0 1 0 0 1, 7 (E)ASU-2 KINDERGARTEN&ADM MECHANICAL RM 1 8000 283 1 2 CU-2 92.2 1 12 3/4" 2-WAY 3/M8.1 1100 6900 6900 6900 16900 1 1 1 0 1 1 1 1 1, 7 (E)ASU-3 NORTH POD MECHANICAL RM 1 7000 257 2 CU-3 90.4 11 3/4" 3-WAY 4/M8.1 850 6150 6150 6150 6150 1 1 1 0 1 1 1 1 1, 7 (E)ASU-4 NOT USED MECHANICAL RM 100 SW Main Street (E)ASU-5 CLASSROOM POD MECHANICAL RM 4 7100 270 2 CU-4 105.1 7 3/4" 3-WAY 3/M8.1 1600 5500 5500 - - 1 1 1 0 1 1 0 0 1, 2, 7 Suite 1600 Portland, OR 97204 (E)ASU-6 DISHWASHING MECHANICAL RM 6 1300 - 42 2.8 1/2" 2-WAY 4/M8.1 - 1300 1300 1300 1300 0 0 0 1 0 1 0 0 , 503.382.2266 (E)ASU-7 KITCHEN MECHANICAL RM 3 2140 - - - 46.5 3 1l2" 2-WAY 4/M8.1 - - - - - 0 1 0 1 2 1 0 0 1, 3 www.interfaceengineering.com (E)ASU-8 GYM MECHANICAL RM 4 7700 - - 124 8.3 3/4" 3-WAY 3/M8.1 1200 6500 6500 6500 6500 1 1 1 0 2 1 1 0 0 1 1 1,4, 5 (E)ASU-9 MUSIC MECHANICAL RM 4 2000 60 1 CU-6 44 2.2 1/2" 2-WAY 4/M8.1 300 1700 1 1700 1700 1700 1 1 1 1 0 1 1 1 0 0 1 1, 5, 6 O PROFfS (E)ASU-10 ARCADE/TOILETS GIRLS 503 3 1500 - - - 37 3.3 1/2" 2-WAY 4/M8.1 - - - - - 0 0 0 0 0 1 0 0 1 \`�1�aGINffpS � �oy (E)ASU-11 CLASSROOM POD MECHANICAL RM 1 10400 440 4 CU-5A-5B 20512.7 1" 3-WAY 3/M8.1 1350 9050 9050 9050 9050 1 1 1 0 2 1 2 2 1 1, 5, 6 ?r 17430PE NOTES: ORf0 1 REMOVE ALL REPLACED AND ABANDONED PNEUMATIC TUBING AND CONTROL DEVICES. gyp 4-pr 29.1 2 EA DAMPER LOCATED IN ROOF HOOD IN CEILING OF THE MULTI-PURPOSE ROOM. REYV W.F�FL 3 UNIT DAMPERS CONSIST OF A COIL FACE DAMPER; BYPASS DAMPER; TWO DUCT SUPPLY ZONE CONTROL DAMPERS MAX. CAD- FUTURE COIL MAX. CAD " 4 EA DAMPERS LOCATED IN ROOF HOOD IN CEILING OF THE GYM. MIN. CAD EAD FOR ASU-8 MIN. CAD 5 PROVIDE NEW FREEZE STAT(LOW TEMPERATURE ALARM)SENSOR AFTER HEATING COIL. 6 A P R LOC TE I O F O D IN C ICL 00 F F CAD F F OAD F 7 REPLACE EXISTING HEATING WATER VALVE WITH NEW VALVE AND ACTUATOR. 1 SF C C A MBB SF MB SF C & SF C C SF C L T T T BP T T RAD RAD TYPE 1 TYPE 2 TYPE 3 TYPE 4 TYPE 5 J ASU ARRANGEMENT TYPES O O UNIT HEATER / HW COIL SCHEDULE (N) CONDENSING UNIT SCHEDULE ��Imm V SUPPLY FAN BASIS OF DESIGN AIR SOURCE CONDENSER ELECTRICAL �/♦ CONTROL CITY EER APPROX. MAX TOTAL FAN CAP VALVE DETAIL NOM OF COMPRESSOR CAP AMBIENT OR DIMS WT 1 SYMBOL CFM RPM MHP (MBH) SIZE REFERENCE NOTES SYMBOL UNIT SERVED MFR MODEL TONS CIRCUITS TYPE (MBH) DB (°F) SEER VOLTS PH MCA MOCP (LxWxH) (LBS) NOTES ♦^ CUH-4 200 900 1/30 20 1/2 2/M8.1 1, 2 CU-2 ASU-2 CARRIER 38APDO25 25 2 SCROLL 283 95 208 3 121 150 1200 1, 3 CIO UH-8 755 1550 1/20 38 1/2 1/M8.1 1,2 ACCU-3 ASU-3 CARRIER 38AUDC25 20 2 SCROLL 257 95 208 3 74 100 1000 1, 2 Q BHC-1 500 N/A N/A 21.6 1/2 1 1/M8.1 1, 2, 3 ACCU-4A ASU-11 CARRIER 38AUDC25 20 2 SCROLL 220 95 208 3 74 100 1000 1, 2 BHC-2 1940 N/A N/A 1 35.6 1/2 1 1/M8.1 1, 2, 3 ACCU-48 ASU-11 CARRIER 38AUDC25 20 2 SCROLL 220 95 208 3 74 100 1000 1, 2 J Z NOTES: 1. UNIT SIZED FOR 20OF EWT; 170F LWT 1 ACCU-5 ASU-5 CARRIER 38AUDC25 20 2 SCROLL 270 95 208 3 74 100 1000 1, 2 2. PNEUMATIC VALVE ACTUATOR TO BE REPLACED WITH NEW ELECTRIC ACTUATOR. CU-6 ASU-9 CARRIER 38AUZ07 6 1 SCROLL 60 95 208 3 10 15 400 1, 4 O Uj 3. REPLACE EXISTING HEATING WATER VALVE WITH NEW VALVE AND ACTUATOR. O 1 NOTES: 1. PROVIDE WITH SINGLE POINT CONNECTION. 2Uj W 2. PROVIDE HOT GAS BYPASS FOR CAPACITY CONTROL , J Q 3. PROVIDE HOT GAS BYPASS OR ONE DIGITAL SCROLL COMPRESSOR FOR CAPACITY CONTROL. 4. PROVIDE TWO STAGE COMPRESSOR FOR CAPACTY CONTROL. W (E) CONTROL DAMPER SCHEDULE (N) DX COOLING COIL SCHEDULE ? W (� AIR DAMPER SIZE COIL DATA COOLING DATA HANDLER MIN OSA OSA RETURN RELIEF EXHAUST OTHER AIR AIR MAX TOTAL SENS TAG DAMPER DAMPER DAMPER DAMPER DAMPER DAMPER NOTES HANDLER FLOW WIDTH HEIGHT # APD CAP CAP EDB EWB LDB LWB CONDENSING N N (E)ASU-1 30x8 30x22 30x30 TAG REFRIGERANT (CFM) (IN) (IN) ROWS (IN H2O) (MBH) (MBH) (°F) (°F) ("F) ("F) CIRCUITING UNIT NOTES Q J Z N (E)ASU-2 72x4 72x12 72x16 72x16 ASU-2 R-41 OA 8000 88 41 4 0.27 283 230 86.5 66.7 56.7 54.6 DUAL CU-2 (E)ASU-3 60x4 60x18 60x18 60x18 ASU-3 R-41 OA 7000 78 31 6 0.63 257 212 82.8 68.6 54 52.8 SINGLE CU-3 = O V Z (E)ASU-5 55x4 55x12 55x12 55x12 R-41 OA 6000 65 39 6 0.56 259 203 84 66.6 51.9 51.4 SINGLE CU-4 W` V_ (E)ASU-6 20x14 20x14 4 ASU-9 , R-41 OA 2000 27 34.50 6 0.55 78.8 62.2 81.3 65.2 51.9 50.9 SINGLE CU-6 ■ = (' (E)ASU-7 - 20x14 - 5 (E)ASU-8 60x16 60x6 56x20 (2)36x36 1 R-41 OA 10400 58.5 1 38 6 0.84 206 168 82.8 65.7 53.3 52.3 SINGLE CU-5A, 5B 1 Q W (E)ASU-9 10x24 4x24 30x12 24x24 1 (E)ASU-10 NOTES: 1. TWO COILS IN ASU-11 >= 0 (E)ASU-11 70x6 70x22 70x22 70X22 3 N C3 EF-5 10x6 SA 2 / Q EF-6 10x6 SA 2 �/ WC4cn NOTES: 1. REMOTE RELIEF DAMPER (N) WALL MOUNTED HEAT PUMP SCHEDULE P 2 2 T 2. DAMPER IN DUCT LINKED TO ASU OPERATION BASIS OF DESIGN ELECTRICAL SHEET TITLE 3. AHU VAV 4. 10X16 ZONE DAMPER MAX 5. (2)DAMPERS TO EF-5 AND EF-6 HOODS SCHEDULES - 5. WT SYMBOL AREA SERVED MFR MODEL VOLTS PH MCA MOCP (LBS) NOTES MECHANICAL HP-2 PORTABLE BARD W30HB-A10 208 1 76 80 375 1, 2 HP-3 PORTABLE BARD W30HB-A10 208 1 76 80 375 1, 2 HP-4 PORTABLE BARD W30HB-A10 208 1 76 80 375 11 1, 2 NOTES: 1. PROVIDE WITH FULL ECONOMIZER, 2-INCH FILTERS, PROGRAMMABLE T-STAT AND CO2 VENTILATION CONTROL. REVISIONS 2. PROVIDE WITH SPLIT ELECTRICAL FEED. 1 ADDENDUM 1 2/2/2021 DRAWN BY JDC CHECKED BY Rick Silenzi JOB NO. 2020-0465 DATE 01/11/2021 SHEET NUMBER BID SET M1 . 1 FILE: M11 WOODWARD.DWG - M1.1 EDIT: 2/2/2021 12:02 AM BY RICKSI PLOT: 2/2/2021 8:49 AM BY RICK SILENZI -9 \ -2 �/ O SHEET KEYNOTES E NTA IE R F RCE I i I i I 1. CONDENSING UNIT TO BE DEMOLISHED. REMOVE ALL --- — — – _ _ --- --- -- I EQUIPMENT SUPPORTS AND ANCHORS. REMOVE ALL 1 INTERIOR AND EXTERIOR REFRIGERANT PIPING, I ' COMPONENTS AND SUPPORTS BACK TO THE AIR HANDLER I ! ! II COIL. ROOF CURBS TO BE LEFT IN PLACE FOR RE-USE. 100 SW Main Street I I � Suite 1600 2. CONDENSING UNIT AND PIPING TO REMAIN. Portland, OR 97204 �I 503.382.2266 I 3. ROOFTOP UNIT TO REMAIN. www.interfaceengineering.com ! I 4. NOT USED. 5. REFRIGERANT PIPING ROOF PENETRATION TO BE REPLACED I _ _ _f_ I -_ -- I - --- I WITH NEW. Ep PROffS --__-__ __ __-.___- -. _ —. ,__ _�-_____. _. __. ________ -1-- - --------- --- -- - - --- - ----.-- - ---- -- ----- 6. REFRIGERANT PIPING TO BE REMOVED. �aG 1 N(f� r�p9 �-- - - - - � 7. WALL MOUNTED PORTABLE CLASSROOM HEAT PUMP TO BE 17430PE4 I I AREA 9 REMOVED AND REPLACED. 0REG0 - - -- ------- -- - - -- -- -- - B. WALL MOUNTED UNIT TO REMAIN. 9y0�.28,1e W.F I i I EXPIRES: 12131/21 I I I I I I I -- _ F----- - - -+-- -- - �— -- I--- -- --I-- - - - -- +- - - - — ' — -- -T ---- - — t- - - - - - -- i B�o � CU-5 MECHANICAL RQOM I x MECHANICAL O ASU-5 I X ROOM I O Ix ASU-11 -- -- _--_ 6 ( AREA 1 LU i II x x REA 11 I I OPEXTOI I j- -- AREA 18Bsow u -D ♦♦Fm AREA8 (E)SKYLIGHT (—�v � J I I k I I I ; III II W -- � °oCLU IO)7 W I � W � cu-z , 6 I W -1 -Z -1 -1 -1 -1 -9 -8 •7 -2 -2 -3 INTERFACE E N G I N E E R I N G O SHEET KEYNOTES I 1 - . _ - 1. ASU-10 FAN COIL ABOVE THE CEILING TO HAVE THE HW ' � CONTROL VALVE REPLACED. SEE MECHANICAL SCHEDULES FOR ADDITIONAL DETAIL. 100 SW Main Street Suite 1600 2. BUILDING CONTROL PANELS LOCATED IN THE JANITOR6' -_ Portland, OR 97204 CIASSROgM CLASSROOM CLASSROOM CLASSROOM I 1 T ____-- _ ROOM. 503.382.2266 1 I I 18 19 20 21 ; www.interfaceengineering.com 3. PROVIDE NEW WALL MOUNTED HEAT PUMP FOR THE I II PORTABLE CLASSROOM. RECONNECT TO DUCTWORK, GRILLES AND CONTROLS. I I 4. PROVIDE NEW HEATING WATER CONTROL VALVE. SEE �Ep PROpf SCHEDULE FOR DETAILS. s{�O g 5 EXISTING PNEUMATIC DAMPER ACTUATOR TO BE REPLACEDp 1 A 4 � — pis r WITH ELECTRONIC ACTUATOR. 174330P,E-/�/1 S - --- - -- -- - -- - -- 1 - _ - I OREGOtC i SS . _ _ - CLASSR M C ROO CLASSROOM CLASSROOM u n 1 25 1 za zz I CLASSROOM CLASSROOM EXPIRES: 12/31121 11 12 ' i CUH-3 4 I �I If --------- AT UM - - - - - -U i CM 27 CLASSROOM I I - – — _---- �I CLASSB04 M 23 _ B _ CLASSROOM I — I Ma.1 B G M4.2 r ABOVE ABOVE T C _ _ MM - I I U CLASSROOM ATRIUM I OPK cuH a a �I ♦A li 9 �_ V I � —_ - 29 CLASSROOM I ACTIVITY ROOM - _ __ - --- - - - -= _ --- z OFFI 30 31 I ( 1 RELIEF DAMPERS - RASU-8 -- - -- - - .F W V) FOR AS U-8 O CLASSROOM CLASSROOM _ Uj LU -8 7. IBRARY GYM j Q J � W CLASSROOM _ CLASSROOM 4 _ D10! ASU-10 1 2 SOUnRCE R 32--- - - -- --- -- -_ --- ABOVE CEILING r -. -- -- - - ----- - - --- - - - - - V) OY 2 S G W-T413 Q = I M4.1 UN E G 'OFFICE NITO R [ -- �L ____- --—_-- — --- ---- -- t�RELIEF DAMPER (/� N 1 D1 1 D1122 r�� FOR ASU-9 4 UH-8 ti ABOVE — I CONE.RM W ED109 O Q ? C! CLASSROOM — R_KR BOYS 6 ( GIRLS D107 OBBY LU LU 5 Z w-ns I -T7 W - I 10 1 .L � -�` -m= _-- I - ------ TIBU M4.1 -_— -- --1 -- -------- --- - -- L,t>.4L1 �..lY-_ ___ __. L._ _ n-(, _. M►,I 1 1 U �J 0 �� J' T I EPTION/ADMI D7 0 ABOVE - MUSIC G B c I 1 I D102 CAF€TERIA I H :)RAGE- c I li I Q � C.� � it ; M4.2 �_ �_ _ 2 O W N a HEALT CLASSROOM CLASSROOM C SSROOM I D10 ABOVE M4.2 M 5 4 D189 RELIEF DAMPEROS I �I I i FOR ASU-1 ABOVE , �- - --- -y. .. _ .DD� SHEET TITLE i' PRINCI AL - - - - — w M — — — — — — — — — - D1 — — — -- - I— — — FLOOR PLAN - ! I I I ( O HP-2 MECHANICAL -N I I T I I HP-4 HP-3 I ALTERNATE#1 REVISIONS I i IV i I O O 0 -- - { - + -- - --- -- --------- -i 10 PORTABLE CLASSROOM i W DRAWN BY �I JDC I I - -1-- ----o-- - -- I I CHECKED BY Rick Silenzi JOB NO- -1 IY-1 fll-1� IV -1 VCV� -8 -7 -2 -B -2 -3 -2 -2 -1 N-1 2020-0465 DATE 01/11/2021 1 FLOOR PLAN - MECHANICAL SHEET NUMBER S-IAOZ 0 8' 16' 32' SCALE: 1/16"=I'-O" BID SET M2 .0 FILE: M20 WOODWARD.DWG — M2.0 EDIT: 1/10/2021 11:43 PM BY RICKSI PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE INTERFACE O SHEET KEYNOTES E N G I N E E R I N G I I 1. NEW CONDENSING UNIT-SEE MECHANICAL SCHEDULE FOR --t-- — �— DETAILS. INSTALL NEW REFRIGERANT PIPING AND SUPPORTS TO AIR HANDLER COIL PER DETAIL 6/M8.1. !! 100 SW Main Street i PROVIDE ANCHORING AND SUPPLEMENTAL STEEL !! SUPPORTS PER DETAIL 7/M8.1. Suite 1600 I I I ! I I ! I Portland, OR 97204 2. CONDENSING UNIT AND PIPING TO REMAIN. 503.382.2266 www.interfaceengineefing.com 3. ROOFTOP UNIT TO REMAIN. I � 4. NOT USED. 5. REFRIGERANT PIPING DOWN THROUGH THE ROOF. SEE I DETAIL 8/M8.1. 6D PROFESS _ _ __ �5 aGINf � ip 'k, y - — �- �a f 6. NEW REFRIGERANT PIPING. SEE SCHEDULE FOR SIZE AND Q 'r ! ! I AREAI I SPECIFICATIONS FOR DETAILS. 43 -S _ _OREGOE czar. -F,-" IT -T tion W F�,��� ! I I I I I ! ! EXPIRES: 12/31/21 i I ! i W-T'• ------ --- --a----- CU-5 1 Bz ! � JI- i MECHANicAL ROOM MECHANICAL ! O ASU-5 ! ROOM O 6 ASU-11 AREA 1 I 4- zl _ i V I � � e N 11 WDs� ° 5 i CU 1, IT –AREA i 18sCow1 Cu-4 AREAE)SKG ! -- -- -- I --B-C� `Ol��ZJQJi. 14 WAREA 12 WQJN1L.LL W 7 o Uj CU-2 1 –i — – — – — – — – — – .113 6 1 1 1 Cu-3 AREA 19. --- �JQ WN N M s _ O Z,. ; ARAREA 17 CU-6 1 WZ; f ❑ i � ( MECHANICAL ROOM ARE ASU-1:ASU-2 = -- - W I MECW ! Q I ! ! Q AREA 13! L R I IQ�/ o ASID-3 MECHANICAL ROOM MECHANICAL ROOM ASU-6;ASU-7 ASU-8;ASU-9 AREA 20 N Q rp: - - SHEET TITLE ROOF PLAN - i MECHANICAL I I I I I I I I I S I I I i I I AREA 15 i $ REVISIONS— -P �. �. � — — ._._._ — — I --� PORTABLE CLASSROOM g I w I I I I I I I I I I i ! AREA 16 DRAWN BY JDC —v---- CHECKED BY Rick Silenzi ! JOB NO. SIV 27� -119 -8 -2 -6 -2 W-3 -2 V�V-2 �W-�1 -1 DATE 2020-0465 01/11/2021 1 ROOF PLAN - MECHANICAL SHEET NUMBER Stii00Z 0 8' 16' 32' SCALE: 1/16"=1'-0" BID SET M2 . 1 FILE: M21 WOODWARD.DWG — M2.1 EDIT: 1/10/2021 11:30 PM BY RICKSI PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE O SHEET KEYNOTES INTERFACE 1. GENERAL SCOPE OF WORK IN THE MECHANICAL ROOM INCLUDES BUT IS E N G I N E E R I N G NOT LIMITED TO THE FOLLOWING: THE REMOVAL OF ALL PNEUMATIC W6 •2 W-3 CONTROLS,TUBING, CONTROL PANELS, ABANDONED CONDUITS AND V PATHWAYS. PATCH ANY HOLES OR OPENINGS IN THE MECHANICAL UNITS, DUCTWORK AND WALLS LEFT BY DEVICE REMOVAL. 2. GENERAL SCOPE OF WORK FOR AIR HANDLING UNITS INCLUDES BUT IS 100 SW Main Street NOT LIMITED TO THE FOLLOWING: Suite 1600 A. REPLACE ALL PNEUMATIC DAMPER ACTUATORS FOR OSA, RELIEF, Portland, OR 97204 NEW REFRIGERANT PIPING TO EXHAUST AND MIXING WITH NEW ELECTRONIC ACTUATORS. I OCU-2 ON ROOF. SEE M2.1 FOR 503.3$2.2266 B. REPLACE ALL REFRIGERANT PIPING, COMPONENTS, VALVES AND RELATED CONTINUATION REFRIGERANT DEVICES WITH NEW. www.intert 382.2 ineenng.com Er O C. REPLACE PNEUMATIC HEATING WATER VALVE ACTUATOR WITH NEW T - LE TR NI ACTUATOR. __.____ - - - •H D. REMOVE EXISTING R-22 DX COIL AND REPLACE WITH NEW R-41 OA DX COIL. SEE SCHEDULE FOR SIZE AND FIELD VERIFY COIL DIMENSIONS PRIOR TO ED PROF SUBMITTAL. 1�8 fsS E. SEE MECHANICAL SCHEDULES FOR DETAILS. 4��5 �aG1 Nff9 /Or 3. PNEUMATIC ACTUATOR TO BE REPLACED ON THE 3-WAY,4" HEATING 1743OPE WATER VALVE WITH A NEW ELECTRONIC ACTUATOR AND TIED INTO ��,,vv THE EXISTING CONTROL SYSTEM, OREGO O 4. REPLACE EXISTING PNEUMATIC VALVE ACTUATOR ON HEATING VALVE 9'1p�FPt 28,1�Q of OOASU-2 2 g 9 ZONES ASU-1 5 WITH NEW ELECTRONIC ACTUATOR. REPLACE EXISTING PNEUMATIC RFWW,fW� O SENSOR WITH NEW DIGITAL SENSOR. SEE SCHEDULES FOR DETAILS. EXPIRES. 12/81/21 5. GENERAL SCOPE OF WORK FOR AIR HANDLING UNITS INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING: I I)i A. REPLACE ALL PNEUMATIC DAMPER ACTUATORS WITH NEW ELECTRONIC — — _. --- - - - -- -- --- - - - - - W J ACTUATORS. B. REPLACE PNEUMATIC HEATING WATER VALVE ACTUATOR WITH NEW ELECTRONIC ACTUATOR AND CONNECT TO THE CONTROL SYSTEM. C. SEE MECHANICAL SCHEDULES FOR DETAILS. 3 6. NEW REFRIGERANT PIPING SIZED PER MANUFACTURERS CRITERIA FOR OUNIT SIZE AND TO MAINTAIN OIL RETURN. FOLLOW EXISTING ROUTING 1 AND MAINTAIN PENETRATIONS THROUGH THE WALL. SEE DETAIL 9.M8.1 9 EDH-1 FOR SUPPORT DETAIL. 7. REMOVE EXISTING PNEUMATIC CONTROL DAMPER ACTUATORS IN O DUCT AND AND REPLACE WITH NEW ELECTRONIC ACTUATOR. 8. FIRE/SMOKE PNEUMATIC DAMPER ACTUATORS TO BE REPLACED O _ _ - - - - - - - - - • WITH NEW ELECTRONIC ACTUATORS. SEE PLAN AND SCHEDULES ----__- --- FOR NUMBER OF ZONES. 9. PE SWITCH TO BE REMOVED AND EQUIPMENT TO OPERATE V DIRECTLY FROM DIGITAL CONTROLS. ASU-1 , ASU-2 1 MECHANICAL ROOM PLAN CONTROL GENERAL NOTES 0 2' 4' 8' Q •1 A. WHERE EXISTING PNEUMATIC DEVICES ARE REMOVED, REMOVE ALL Q SCALE: 1/4"=1'-0" ASSOCIATED PNEUMATIC PIPING AND CONTROLS. CONNECT NEW ACTUATOR/DDC DEVICES TO EXISTING JCI SYSTEM CONTROL PANEL. J ALTER PROGRAMMING AS REQUIRED FOR THE NEW DIGITAL DEVICE. • - - B. CONFIRM DAMPER AND VALVE SIZES PRIOR TO SUBMITTAL. APPROX O LU DAMPER SIZES ARE SHOWN ON SCHEDULE. O C. PATCH WALL WHERE PNEUMATIC DEVICES ARE REMOVED FROM FINSIHED = W UjQ ROOM/WALL. J D. CONTRACTOR TO FIELD VERIFY LOCATION OF ALL EQUIPMENT, CONTROL W PANELS AND DEVICES TO ENSURE ALL SYSTEMS ON PNEUMATIC V, CONTROLS ARE UPGRADED TO DIGITAL CONTROLS. Q moi• Q D ~ M ��r W � MM-1 �►r-� Q Q Z W z ASU-5 O _ 0 o � QNEW REFRIGERANT PIPING TO Qom = OCON IN ROOF. SEE M2.1 ;FOR NEW G TO -4 REFRIGERANT/7\ � 0 CONTINUATION PIPING TO CU-4 ON --- - - - - - - ROOF. SEE M2.1 C4 RS RL RHG OR CONTINUATION Q W M Cq H O ASU-3 O � SHEET TITLE ENLARGED PLANS 09ZONES - MECHANICAL l 1 7 FSD EF 7 O O REVISIONS O , I I i DRAWN BY ASU-3 ASU-5JDC CHECKED BY 2 MECHANICAL ROOM PLAN 3 MECHANICAL ROOM PLAN Rick Silenzi 0 2' 4' 8' JOB NO. 0 2' 4' 8' 2020-0465 SCALE: 1/4"=1'-0" SCALE: 1/4"=1'-0" DATE 01/11/2021 SHEET NUMBER BID SET Wal FILE: M41 WOODWARD.DWG — M4.1 EDIT: 1/7/2021 9:44 AM BY JONATHANC I PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE O SHEET KEYNOTES 1. GENERAL SCOPE OF WORK IN THE MECHANICAL ROOM INCLUDES BUT IS INTERFACE NOT LIMITED TO THE FOLLOWING: THE REMOVAL OF ALL PNEUMATIC CONTROLS, TUBING, CONTROL PANELS,ABANDONED CONDUITS AND E N G I N E E R I N G PATHWAYS. PATCH ANY HOLES OR OPENINGS IN THE MECHANICAL UNITS, DUCTWORK AND WALLS LEFT BY DEVICE REMOVAL. 2. GENERAL SCOPE OF WORK FOR AIR HANDLING UNITS INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING: A. REPLACE ALL PNEUMATIC DAMPER ACTUATORS FOR OSA, RELIEF, 100 SW Main Street EXHAUST AND MIXING WITH NEW ELECTRONIC ACTUATORS. Suite 1600 .1 B. REPLACE ALL REFRIGERANT PIPING, COMPONENTS, VALVES AND RELATED Portland, OR 97204 REFRIGERANT DEVICES WITH NEW. 503.382.2266 C. REPLACE PNEUMATIC HEATING WATER VALVE ACTUATOR WITH NEW www.interfaceengineering.com ELECTRONIC ACTUATOR. D. REMOVE EXISTING R-22 DX COIL AND REPLACE WITH NEW R-410A OX COIL. SEE SCHEDULE FOR SIZE AND FIELD VERIFY COIL DIMENSIONS PRIOR TO SUBMITTAL. W=2 Wm 1 --- — -- -„ __ — — �K E. SEE MECHANICAL SCHEDULES FOR DETAILS. �ERfU PROpfss 3. NOT USED. �v\� �N01 N£'p 10 QL EF-9 O NEW REFRIGERANT LINES4. REPLACE EXISTING PNEUMATIC VALVE ACTUATOR ON HEATING VALVE 17430PE/f UP TO CU-6 ON ROOF. O6 WITH NEW ELECTRONIC ACTUATOR. REPLACE EXISTING PNEUMATIC 43 t SENSOR WITH NEW DIGITAL SENSOR. SEE SCHEDULES FOR DETAILS. 0REG0 5. GENERAL SCOPE OF WORK FOR AIR HANDLING UNITS INCLUDES BUT IS 92QRFPr zs. G2�� I I' FSO NOT LIMITED TO THE FOLLOWING: fW W.F A. REPLACE ALL PNEUMATIC DAMPER ACTUATORS WITH NEW ELECTRONIC ACTUATORS. EXPIRES 1294/21 O ASU 6 7 I I B. REPLACE PNEUMATIC HEATING WATER VALVE ACTUATOR WITH NEW ELECTRONIC ACTUATOR AND CONNECT TO THE CONTROL SYSTEM. 5 C. SEE MECHANICAL SCHEDULES FOR DETAILS. tr 6. NEW REFRIGERANT PIPING SIZED PER MANUFACTURERS CRITERIA FOR UNIT SIZE AND TO MAINTAIN OIL RETURN, FOLLOW EXISTING ROUTING AND MAINTAIN PENETRATIONS THROUGH THE WALL. SEE DETAIL 9.M8.1 FOR SUPPORT DETAIL. 7. REMOVE EXISTING PNEUMATIC CONTROL DAMPER ACTUATORS IN 2 EF-5 O DUCT AND AND REPLACE WITH NEW ELECTRONIC ACTUATOR. 8. MULTIZONE PNEUMATIC DAMPER ACTUATORS TO BE REPLACED J WITH NEW ELECTRONIC ACTUATORS. SEE PLAN AND SCHEDULES O 2 EF-6 I FOR NUMBER OF ZONES. ( —I 9. PE SWITCH TO 8E REMOVED AND EQUIPMENT TO OPERATE DIRECTLY FROM DIGITAL CONTROLS. O O 7 EFS 4 UH-6 v 4 BHC-1 U ♦^ � II � � V♦ 0 O CONTROL GENERAL NOTES ���'H O>C A. WHERE EXISTING PNEUMATIC DEVICES ARE REMOVED, REMOVE ALL U)07 (2)FSD'S I * ASSOCIATED PNEUMATIC PIPING AND CONTROLS. CONNECT NEW Q ACTUATOR/DDC DEVICES TO EXISTING JCI SYSTEM CONTROL PANEL. ALTER PROGRAMMING AS REQUIRED FOR THE NEW DIGITAL DEVICE. Z B. CONFIRM DAMPER AND VALVE SIZES PRIOR TO SUBMITTAL. APPROX O ASU-6, ASU-7 ASU-8, ASU-9 DAMPER SIZES ARE SHOWN ON SCHEDULE. C. PATCH WALL W HERE PNEUMATIC DEVICES ARE REMOVED FROM FINSIHED1 MECHANICAL ROOM PLAN 2 MECHANICAL ROOM PLAN = LU Uj 0 2' 4' 8' 0 2' 4' 8' ROOM/WALL. D. CONTRACTOR TO FIELD VERIFY LOCATION OF ALL EQUIPMENT, CONTROL PANELS AND DEVICES TO ENSURE ALL SYSTEMS ON PNEUMATIC SCALE: 1/4"=1'-0" SCALE: 1/4"=1'-0" CONTROLS ARE UPGRADED TO DIGITAL CONTROLS. U) Uj W-7 -2 W-6� -� -� W W8 � aO� a � z W W - --- -- -- - -- ----- - - — -- -- - ---- - - - -- - - - - - - Q >= D C') QW Na SHEET TITLE 7 FSD UH-7 a OO ENLARGED PLANS i - MECHANICAL I REVISIONS 9 EF-8 ASU-11 2 C _c - lu it NEW REFRIGERANT PIPING TOO DRAWN BY CU-5A AND CU-5B ON ROOF. JDC6 SEE M2.1 FOR CONTINUATION. CHECKED BY Rick Sllenzi JOB NO. ASU-1 1 2020-0465 3 MECHANICAL ROOM PLAN DATE 01/11/2021 0 2' 4' 8' SHEET NUMBER SCALE: 1/4"=1'-0" BID SET M4.2 FILE: M42 WOODWARD.DWG — M4.2 EDIT: 1/7/2021 9:43 AM BY JONATHANC PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE 0 Rw INTERFACE E N G I N E E R I N G ACCU BOLT ACCU UNIT TO ISOLATOR AS SPECIFIED BY MANUFACTURER. HWS--j HWS— SPRING ISOLATORS ----- --- ---I--I —HWR---- ---- DEFLECTION 5" MIN 2 — —HWR----1--- ---� . . I 1/2"THICK GALVANIZED AV (PROVIDE SEISMIC STEEL PLATE 100 SW Main Street EXISTING PIPING EXISTING PIPING SNUBBERS AS REQUIRED) Suite 1600 Portland, OR 97204 IF Lai 503.382.2266 _ I www.interfaceengineering.com __------ ---J EXISTING ROOF CURB n'r AV Y! + ip ROOF M `"`�yyy SJri EXISTING PNEUMATIC `� ►-L M �`lF� PRO�fis/ CONTROL VALVE I �'�yt ANG 1 N f£� �y ACTUATOR TO BE I EXISTING PNEUMATIC a REPLACEDCONTROL VALVE 17430PE AIR ACTUATOR TO BEf�avv FLOW REPLACED OREGO 9 sFR 28.j9ya ,�� EXISTING UNIT C I DV SECURE SPRING ISOLATOR ZOR�VW. DV HEATER EXISTING COIL TO CURB W/ANCHOR BOLT NOTE: EXPIRES: 12(31(2 i PROVIDE SUPPLEMENTAL STEEL SUPPORTS SINGLE COIL TWO WAY MOTORIZED VALVE ACROSS EXISTING CURBS AS NEEDED FOR UNIT SUPPORT. 4 COIL PIPING DIAGRAM 7 ACCU MOUNTING DETAIL 1 HOT WATER UNIT HEATER DETAIL NO SCALE NO SCALE NO SCALE J O O HWS ♦� GALV'D STEEL CAP AND RAIN HOOD, V ♦�^ HWS ---- ----HWR------- --- Jf SECURED TO FLASHING WITH SCREWS � r----- --HWR---- ---� HOOD TO SIUIT PIPING LL HOLES N SIDE UNDER EXISTING PIPING M '^ EXISTING PIPING Y/ GALV'D STEEL FLASHING, NAIL 3"O.C. Q I EXISTING PNEUMATIC CONTROL VALVE REFRIGERANT PIPING AND ELECTRICAL AV I ACTUATOR REPLACED TO BE I I I CONDUIT(PIPE INSULATION NOT SHOWN) J Z ROOF AV p w AIRM _ I FLOW ��I j �,. 0_ W W QM AIR J C Iriprw FLOW V EXISTING COIL W EXISTING PNEUMATIC C I�-�-� DV CONTROL VALVE 0 ,w DV ACTUATOR TO BE EXISTING COIL Z V REPLACED BHC, CUH HEATING COIL TWO WAY MOTORIZED VALVE SINGLE COIL THREE WAY MOTORIZED VALVE jum 2 COIL PIPING DIAGRAM 5 COIL PIPING DIAGRAM J J w � NO SCALE O a Z Z NO SCALE 8 PIPING AND CONDUIT ROOF PENETRATION H O C c°� NO SCALE M-PIPE 6-10 Q 3: Q Q L co a FIRST STAGE a fi tn w SIGHT GLASS a W N Q LIQUID LINE NCD HWS SOLENOID VALVE ffL r ----T ----HWR------- ----- RL PIPE CLAMP J/ HOT GAS BYPASS SHEET TITLE CONTROL VALVE HOT Gns— DETAILS - EXISTING PIPING M -LJ--RS— -- TEMPERED REF. PIPE MECHANICAL INSULATION W/EXTERIOR JACKET DX COOLING COIL I PURGE I I SADDLE EXISTING PNEUMATIC CONTROL VALVE I I ACCU STRUT INTEGRAL TO ROOF SUPPORT ACTUATOR TO BE REPLACED I 6" MAX I J DRIER L---- - REVISIONS IVLIQUID LINE LSOLENOID VALVESIGHT GLASS HOT GAS BYPASS SOLENOID VALVE SECOND STAGE MIN. 3-1/2" AIR FLOW MECHANICAL ROOM ROOF RECTOR SEAL, ROOF BLOX — MIRRO BLOCK OR EQUAL. ROOF MOUNTED PIPE C I DV GENERAL NOTES: SUPPORT SIZED FOR 5 PSI EXISTING COIL 1. TRAP& PITCH PIPING AS REQUIRED FOR ACTUAL RELATIVE LOAD MAX. LOCATION OF COMPRESSORS AND COILS. 2. PIPING SLEEVED AND SEALED THROUGH ROOF OR WALL. BHC, CUH HEATING COIL THREE WAY MOTORIZED VALVE 3. ALL VALVES OF REFRIGERANT TYPE. DRAWN BY4. ISOLATING VALVES AT ACCU ARE NOT SHOWN. NOTE: SUPPORT @ 48" JDC BY 3 COIL PIPING DIAGRAM 6 REFRIGERANT PIPING DIAGRAM 9 ROOF MOUNTED REFRIGERANT PIPE CHECKEDRickSilenZi NO SCALE NO SCALE NO SCALE JOB NO. 2020-0465 DATE 01/11/2021 SHEET NUMBER BID SET M8 . 1 FILE: M81 WOODWARD.DWG — M8.1 I EDIT: 12/18/2020 2:31 PM BY JONATHANC I PLOT: 1/11/2021 3:07 PM BY JONATHAN COPE i INTERFACE E N G I N E E R I N G I 100 SW Main Street I ; M w�R Suite 1600 1 Portland, OR 97204 503.382.2266 R www.interfar-eengineering.com r a"1Y.rz , PROI ._,. A , • ,. . Q���h ��G I N fE� gyp' 17430PE .. ,. W.FRG J O _ O CONDENSING UNIT CU-2 TO BE REPLACED. PROVIDE GALVANIZED CONDENSING UNIT CU-3 TO BE REPLACED. PROVIDE GALVANIZED CONDENSING UNITS CU-4A AND CU-4B TO BE REPLACED. PROVIDE � ♦ STEEL SUPPORT CROSS MEMBERS FOR SUPPORT AND ANCHOR TO STEEL SUPPORT CROSS MEMBERS FOR SUPPORT AND ANCHOR TO GALVANIZED STEEL SUPPORT CROSS MEMBERS FOR SUPPORT AND ♦ ♦ `/ EXISTING ROOF CURB AS REQUIRED. EXISTING ROOF CURB AS REQUIRED. ANCHOR TO EXISTING ROOF CURB AS REQUIRED. V //� V♦ 1 PHOTO DETAIL 2 PHOTO DETAIL 3 PHOTO DETAIL NO SCALE NO SCALE NO SCALE � Q J Z OW W W y aW a w n' Ir .� N z J J LU C4 � oaRZ V Wo i'. _ LU -- _ N j C4 maim - Uj- M C9 1 N H SHEET TITLE j PHOTO DETAILS - MECHANICAL REVISIONS CU-5 TO BE REPLACED. PROVIDE GALVANIZED STEEL SUPPORT CU-6 TO BE REPLACED. PROVIDE GALVANIZED STEEL SUPPORT TYPICAL WALL MOUNTED HEAT PUMP UNIT TO BE REPLACED. CROSS MEMBERS FOR SUPPORT AND ANCHOR TO EXISTING ROOF CROSS MEMBERS FOR SUPPORT AND ANCHOR TO EXISTING ROOF CURB AS REQUIRED. CURB AS REQUIRED. 4 PHOTO DETAIL 5 PHOTO DETAIL 6 PHOTO DETAIL DRAWN BY NO SCALE NO SCALE NO SCALE JDC CHECKED BY Rick Silenzi JOB NO. 2020-0465 DATE 01/11/2021 SHEET NUMBER BID SET M8.2 FILE: M82 WOODWARD.DWG — M8.2 EDIT: 1/11/2021 10:25 AM BY JONATHANC PLOT: 1/11/2021 11:00 AM BY JONATHAN COPE ELECTRICAL SYMBOL LIST INTERFACE E N G I N E E R I N G NOTE: This is a standard symbol list and not all items listed may be used. Abbreviations IN INCH, INCHES TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR Raceways KV KILOVOLT TYP TYPICAL 100 SW Main Street (E) EXISTING CONDUIT CONCEALED IN WALL OR CEILING SPACE Suite 1600 97204 KVA KILOVOLT AMPERES UL UNDERWRITERS LABORATORIES Portland, OR (N) NEW 5 2.226 KW KILOWATT LION UNLESS OTHERWISE NOTED –— — — ——– CONDUIT ROUTED BELOW FLOOR/GRADE www.interfaceengineering.com (R) RELOCATE (X) DEMOLISH LED LIGHT EMITTING DIODE V VOLTS, VOLTAGE �.....�..... FLEXIBLE CONDUIT LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT W/ WITH '�v PROFfS A AMPERES,AMBER EXISTING CONDUIT CONCEALED IN WALL OR CEILING SPACE ave`; ��G I N r, SAO' L AFC ABOVE FINISHED CEILING V LOW VOLTAGE W/O WITHOUT MCA MINIMUM CIRCUIT AMPS WP WEATHERPROOF AFF ABOVE FINISHED FLOOR N MCC MOTOR CONTROL CENTER XFMR TRANSFORMER yy "VC it,1 ' AHJ AUTHORITY HAVING JURISDICTION MFS R. SAS MIN MINIMUM AIC AVAILABLE INTERRUPTING CAPACITY Connections / Equipment EXPIRES:06/30/22 MISC MISCELLANEOUS ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MOCP MAXIMUM OVERCURRENT PROTECTION HEAVY DUTY FUSED DISCONNECT SWITCH AWG AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM MT, MTD MOUNT, MOUNTED WALL-MOUNTED JUNCTION BOX C CONDUIT, CLOSE, CONTROL L-LN.I.C. NOT IN CONTRACT J JUNCTION BOX WITH FLEX CONNECTION TO EQUIPMENT CA CABLE N/A NOT APPLICABLE N NEUTRAL a MOTOR CONNECTION J COORD COORDINATE O NEC NATIONAL ELECTRIC CODE NON-FUSED DISCONNECT SWITCH CU COPPER ❑' O NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION DIM DIMENSION DIV DIVISION NESC NATIONAL ELECTRIC SAFETY CODE General. V NTS NOT TO SCALE ON DOWN -X-X- DEMOLISH Cn DTL DETAIL OC ON CENTER DWG DRAWING PH PHASE EXISTING WORK E EMERGENCY PNL PANEL NEW WORK Q PVC POLY-VINYL-CHLORIDE EA EACH PWR POWER ED EQUIPMENT IDENTIFICATION J EF EXHAUST FAN LOCATION O W QTY QUANTITY Ot EYED NOTE O z W EMT ELECTRICAL METALLIC TUBING LLj REQD REQUIRED FA FIRE ALARM Miscellaneous V J in RFI REQUEST FOR INFORMATION FMC FLEXIBLE METAL CONDUIT ♦/� Uj FT FOOT, FEET RM ROOM G BRANCH PANEL V♦ G, GND GROUND RMC RIGID METAL CONDUIT Z a FLUSH WALL MOUNTED BRANCH PANEL a GFCI GROUND FAULT CIRCUIT INTERRUPTER SHT SHEET STD STANDARD MAIN DISTRIBUTION PANEL/SUB DISTRIBUTION PANEL GFI GROUND FAULT INTERRUPTER Cl) N SWBD SWITCHBOARD W N GFP GROUND FAULT PROTECTION Z ti TBD TO BE DETERMINED HT HEIGHT Z H 0 ° D � Z � L � � = � o Q W M � HCV2 � SHEET TITLE COVER SHEET - ELECTRICAL REVISIONS DRAWN BY SHEET INDEX IE► CHECKED BY E1.0 COVER SHEET-ELECTRICAL Jeff Glanville E1.1 SCHEDULES -ELECTRICAL JOB NO. 2020-0465 ED2.1 ROOF PLAN - DEMOLITION - ELECTRICAL DATE E2.1 ROOF PLAN - ELECTRICAL 01/11/2021 Reference only SHEET NUMBER plot part of this permit BID SET E1 .0 FILE: E10 WOODWARD.DWG — E10 EDIT: 1/11/2021 3:53 PM BY JEFFREYG PLOT: 1/11/2021 3:53 PM BY JEFFREY GLANVILLE MECHANICAL EQUIPMENT CONNECTION SCHEDULE VOLTS/ WIRE / INTERFACE ITEM DESCRIPTION LOCATION PHASE LOAD MCA MOCP CONDUIT CIRCUIT NOTES E N G I N E E R I N G CU-2 CONDENSING UNIT ROOFTOP 208/3 121 150 1253 PANEL M 1 CU-3 CONDENSING UNIT ROOFTOP 208/3 74 100 803 PANEL N 1 CU-4A CONDENSING UNIT ROOFTOP 208/3 74 100 803 MDS 1 CU-413 CONDENSING UNIT ROOFTOP 208/3 74 100 803 MDS 1 CU-5 CONDENSING UNIT ROOFTOP 208/3 74 100 803 PANEL G 1 100 SW Main Street Suite 1600 1 Portland, OR 97204 HP-2 HEAT PUMP PORTABLE 208/3 76 80 803 2 1 503.382.2266 HP-2 HEAT PUMP PORTABLE 208/3 76 80 803 2 www.interfaceengineering.com HP-3 HEAT PUMP PORTABLE 208/3 76 80 803 2 HP-4 HEAT PUMP PORTABLE 208/3 76 80 803 2 O PROFFJS GENERAL MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES ���`' ��0I N fF /.o A. THE ABOVE INFORMATION IS FOR A SPECIFIC MANUFACTURER. ACTUAL MANUFACTURER FOR EQUIPMENT MAY BE DIFFERENT. COORDINATE WITH MECHANICAL EQUIPMENT SUBMITTALS FOR LOADS AND OVER CURRENT PROTECTION REQUIREMENTS PRIOR TO INSTALLATION OF WIRING. E B. MOCP = MAXIMUM OVER CURRENT PROTECTION Rem 11.1 MCA = MINIMUM CIRCUIT AMPACITY MFS R. 5A� C. PROVIDE DISCONNECTING MEANS FOR EACH ITEM OF EQUIPMENT LISTED IN THE SCHEDULE ABOVE, EXCEPT AS SPECIFICALLY EXPIRES 06/30/22 NOTED OTHERWISE IN SCHEDULE NOTES, BELOW. MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES 1 RECONNECT TO EXISTING FEEDER. CONTRACTOR TO FIELD VERIFY THAT EXISTING FEEDER MEETS OR EXCEEDS SIZE SHOWN IN WIRE/CONDUIT SCHEDULE. IF EXISTING FEEDER DOES NOT MEET OR EXCEED SIZE SHOWN, REPLACE EXISTING FEEDER WITH NEW PER SCHEDULE. 1 2 HEAT PUMP UNIT REQUIRES (2) CONNECTIONS VIA DEDICATED LOAD CENTER PER SHEET E2.1 PROVIDE FEEDERS FROM LOAD CENTER TO UNIT SIZED PER EQUIPMENT NAMEPLATE (ASSUMED 302 AND 502 LISTED BELOW). J WIRE/ CONDUIT SCHEDULE O 203 3#12 CU, 1 #12 CU GND., IN 3/4" C. O 302 2 #10 CU, 1 #10 CU GND., IN 3/4" C. 502 2 #6 CU, 1 #10 CU GND., IN 3/4" C. 803 3 #2 CU, 1 #8 CU GND., IN 1-1/4" C. 1253 3 #1 CU, 1 #6 CU GND., IN 1-1/4" C. V♦ � Q J W O2 � O WW VJ � W Z 13 (� J � J wN � Oa � z H 0 . X0 Z � w U) Q W N � SHEET TITLE SCHEDULES - ELECTRICAL REVISIONS 1 ADDENDUM 1 2/2/2021 DRAWN BY IEI CHECKED BY Jeff Glanville JOB NO. 2020-0465 DATE ,deference only 01/11/2021 Jot part of this permit SHEET NUMBER BID SET E1 . 1 FILE: Ell WOODWARD.DWG — Ell EDIT: 2/2/2021 12:37 AM BY JEFFREYG PLOT: 2/2/2021 12:38 AM BY JEFFREY GLANVILLE O SHEET KEYNOTES -13 -1 -1 -1 -9 -6 V�V-) V�-2 W-6 W-3 �V-2� (1N-2) W-1 -1 \ , 1 PROVIDE CONNECTION TO NEW HVAC UNIT VIA NEW WEATHERPROOF FUSED DISCONNECT AS SHOWN. SEE I I j ELECTRICAL EQUIPMENT CONNECTION SCHEDULE ON E1.1 INTERFACE FOR ADDITIONAL INFORMATION. ENGINEERING _+_-_ --- -a ---------- -_ -----_-- t---------- -- _------ - �_ i ------- ----_ —T ---- - - =-s= -- - F - -- �� ( 2 PROVIDE (2)HACR RATED CIRCUIT BREAKERS (30A/2P AND 50A/2P) IN NEW 100A, 1 PH, 3W NEMA 3R LOAD CENTER TO FEED NEW WALL MOUNTED HEAT PUMP. MATCH AIC RATING OF PORTABLE BUILDING PANELBOARD. CONNECT EXISTING FEEDER MADE AVAILABLE BY DEMOLITION TO NEW LOAD I I I ( I I CENTER. SEE ELECTRICAL EQUIPMENT CONNECTION 100 SW Main Street SCHEDULE ON E1.1 FOR ADDITIONAL INFORMATION. Suite 1600 3 DISCONNECT FED FROM SHARED BUSSED GUTTER INSIDE Portland, OR 97204 503.382.2266 MECHANICAL ROOM. GUTTER FED FROM MAIN DISTRIBUTION www.interfaceengineering.com I I I I I I I ( SWITCHBOARD ADJACENT TO GYM ON MAIN LEVEL. 1 4 PROVIDE NEW ROOFTOP MAINTENANCE RECEPTACLE WITH DIE-CAST WHILE-IN-USE COVER. CONNECT TO EXISTING - �`/ GENERAL PURPOSE RECEPTACLE CIRCUIT WITHIN QEp PRO Ff MECHANICAL ROOM. 1� SS I IAREA9 1 1 1 1 1 ms`s �NGINff ioy -S 5 PROVIDE NEW ROOFTOP MAINTENANCE RECEPTACLE WITH DIE-CAST WHILE-IN-USE COVER. CONNECT TO EXISTING GENERAL PURPOSE RECEPTACLE CIRCUIT WITHIN RE ON I i MECHANICAL ROOM If AVAILABLE, OTHERWISE WITHIN 9q I I I I I I I q y JANITOR'S ROOM ON GROUND FLOOR. PCH II. I Mfs R. SA'� 6 PROVIDE NEW ROOFTOP MAINTENANCE RECEPTACLE WITH I DIE-CAST WHILE-IN-USE COVER. CONNECT TO EXISTING EXPIRES:06/30/22 ROOFTOP RECEPTACLE CIRCUIT. 1 MECHANICAil I R w I7 PROVIDE (2)HACR RATED CIRCUIT BREAKERS (30A/2P AND 50Al2P) IN NEW 100A, 1PH, 3W NEMA 3R LOAD CENTER TO OFEED NEW WALL MOUNTED HEAT PUMP. MATCH AIC RATING rOF PORTABLE BUILDING PANELBOARD. REPLACE EXISTING CU-5 1 60A/2P BREAKER IN PORTABLE BUILDING PANELBOARD WITH (E) PANEL'G-WNEW 80A/2P BREAKER. MATCH EXISTING BREAKER (ON GROUND FLOOR) - - - - -1 -1 MANUFACTURER AND AIC RATING. PROVIDE (3)#2 CU CONDUCTORS AND(1)#8 CU GND. IN 1-1/4"C. FROM AREA 10 I' MECHANICAL ROOM PANELBOARD TO LOAD CENTER. (E)PANEL'F-W' AREA 1 q 1 (ON GROUND FLOOR) 3 �_. I� wP wr I I ENTO 8550. 1 cu 4A cU-4B 1 — AREA 18 V AREA 8 I I I I (ii-)-SKY LIGH B Q I i N I I I i I I AREA 12 I I I I � i -F 0 LU J f �REA 7 I li I I I I O W W -?A 1 -- CU-2 1 V Uj 1 CU-3 - _ J - - - W F 4 - - - - - - - --- - -- — -- - -- ---- AREA 19 a. 1 1 i I I A L'M-W' ( I 6 �i -T- ��4 - N a - - - T J N N F__ w T I —1 - 1 AREA 17 - - - - 1 cD s 1 _ Q Z ti AR _ MECHANICAL ROOM I H-65. � _ 1 n O ♦ ♦ W O I I I 1 4 i _ LU F I I - - - H O F MECHANICAL ROOM--'/, "' OOM AREA 13 _ 0 1 AREA 20 w VN 0 MECHANICAL MEZZANINE � I I I I I s E BELOW ROOF-_, __.-.____ -D Q W N - - ( I I I I I ❑ u I I 1 HP-2 2 SHEET TITLE ROOF PLAN - - 1 1 ELECTRICAL 7 HPC HP-3 7 r AREA 15 I ADD ALTERNATE#1 I O REVISIONS P g 1 ADDENDUM 1 2/2/2021 I I I i ICn PORTABLE CLASSROOM m I Q I a AREA 16 I I I DRAWN BY I IEI CHECKED BY -2 W-14 • -1 •1 -1 44.9 -8 -7 -6 -2 -3 -2 -Z-Z .1 .1 1 HP-1 z Jeff Glanville — JOB NO. 2020-0465 DATE Reference only 01/11/2021 1 ROOF PLAN - ELECTRICAL Not part of this permit SHEET NUMBER 0 T 0 8' 16' 32' H E2. 1 BID SET SCALE: 1/16"=1'-0" FILE: E21 WOODWARD.DWG - E21 I EDIT: 2/2/2021 12:24 AM BY JEFFREYG I PLOT: 2/2/2021 12:38 AM BY JEFFREY GLANVILLE O SHEET KEYNOTES �7) _2 -6 -2 -3 _Z _2 �11 -1 _1 1 EXISTING ROOFTOP MECHANICAL UNIT AND ASSOCIATED Q Y DISCONNECT TO BE REMOVED AND REPLACED. MAINTAIN eR T CONTINUITY OF EXISTING FEEDER TO DISCONNECT LOCATION FOR RECONNECTION TO REPLACEMENT UNIT. INTERFACE I Tim G WALL MOUNTED HEAT PUMP TO BE REMOVED AND E N G I N E E R I N G 1 ------- --__� _. --_______ __ _____------ _- _ ___ - - ffi-- - - F- ED. EXISTING LOAD CENTER TO ALSO BESHED. MAINTAIN CONTINUITY OF EXISTING FEEDERANEL WITHIN PORTABLE TO LOAD CENTER LOCATIONCONNECTION TO REPLACEMENT LOAD CENTER.G WALL MOUNTED HEAT PUMP TO BE REMOVED AND 100 SW Main Street ED. EXISTING DISCONNECT, SERVING FEEDER, AND Suite 1600 REAKER IN PORTABLE BUILDING PANELBOARD TO BE Portland, OR 97204 ED. SEE SHEET E2.1 FOR ADDITIONAL INFORMATION. _, 503.382.2266 www.interfaceengineering.com _" - _ .-1 - -- - 1- - _ . - - - - - - -- - - - —— - — �- - - - s D 1 N - ED PROF I I i I I AREA 9 -T �- RE ON i, I ✓,9�gRCH 11,1 I I MfSR. SA��` EXPIRES:06/30Y12 I MECHANICAL ROOM I I i opo - I sr 1 MCA: 165A CA 6-5A r I I I (ON GROUND FLOOR) X 1 FRED FROM 225A1jGW) AREA 3 BREAKER IN PAN1� AREA 10 I �-MECHANICAL ROOM mmi (E)PANEL'F-W' I Q I I I(ON GROUND FLOOR) AREA 1 W YYYYY X X ,r �X - - I - - - - - - - V - I oPEN.�roCIO I i BSCOW I`' 1 (x)CU-4A: 1 (x)CU-4B: AREA 18 AREA 8 MOCP: 150A FUSE MOCP: 150A FUSE FED FROM 200A FUSED SWITCH IN MDS FED FROM 200A FUSED SWITCH IN MDS T I 1 1 I \/ (E)SKYLIGHT — ry I N I ! AREA 12 I Z W I I I f I 1 (X)CU-2: 1 I O W W MCA: 124.5A FED FROM 200A/3P I J Q i BREAKER IN PANEL'M-W f - - { -G W 1 I I XIX—%X =_-�=<_===°===-i� MCA: 122A _ — , — AREA 19 Z V ( 1 -- - - - - FED FROM 175A/3P - -- - - - - -- ---- - BREAKER IN PANEL'N-W (E) PANEL 'M-W — 1 MXCAU50.A I Q - AREA 17 FED FROM 60AI3P FI (W-J)--- 'BREAKER IN PANEL -W W 04 o MECHANICAL ROOM = Z I ❑ �, � V W S I JCC x (E)PANEL = O AREA - _ -- ;- --�- - _ Z w -- - t I11Q MECHANICAL ROOM (E)PANEL N-W AREA 13 I I j li ! AREA 20 l �J u _ U) � � V N � MECHANICAL MEZZANINE QW C-4 a I I BELOW ROOFmo El- - - - - - - - - - ---� -- _ �__ - _ - -- - _�__ -------- F- C SHEET TITLE i I I I I ❑ ❑ 2 ROOF PLAN - DEMOLITION - 3 % ELECTRICAL LOCATION OF'MDS'ON GROUND IIEVEL I I X I I I I I I I I W i AREA 15 I 3 1 ADD ALTERNATE#1 Q I 0 REVISIONS 1 ADDENDUM 1 2/2/2021 ,'•�� - I - - - --- - - - - - - - - - - - - - \ -, PORTABLE CLASSROOM g I m I a I o_ I I I AREA 16 I I I I DRAWN BY IEI I I I � I-9 -8 CHECKED BY -2 Vl�-� -2 -1 -1 -1 -1 2 X JOB NO. Jeff Glanville 2020-0465 N 1 ROOF PLAN - DEMOLITION - ELECTRICAL Reference onit: DATE 01/11/2021 M 0 8' 16' 32' Not part of this permi) SHEET NUMBER SCALE: 1/16"=1'-0" BID SET ED2 . 1 FILE: ED21 WOODWARD.DWG - ED21 I EDIT: 2/2/2021 12:38 AM BY JEFFREYG I PLOT: 2/2/2021 12:41 AM BY JEFFREY GLANVILLE