Plans (79) M EC2020-00019 GENERAL NOTES ABBREVIATIONS A/C AIR CONDITION(ED) CD CONDENSATE DRAIN EQUIP EQUIPMENT IN INCHES OSA OUTSIDE AIR TYP TYPICAL 1. REMODEL CONSTRUCTION CUTTING & PATCHING BY GENERAL CONTRACTOR. 8. REPLACE EXISTING DUCTWORK IF THE TERMINAL CONNECTION USES MORE AD ACCESS DOOR CFM CUBIC FEET PER MINUTE ERV ENERGY RECOVERY VENTILATOR EAT LEAVING AIR TEMPERATURE PSI POUNDS PER SQUARE INCH V VOLT THAN 20' OF FLEXIBLE DUCTWORK. AFF ABOVE FINISHED FLOOR CLG CEILING ESP EXTERNAL STATIC PRESSURE LF LINEAR FEET QTY QUANTITY VD VOLUME DAMPER(HAND OPERATOR) 2. INSTALLATION WILL COMPLY WITH 2014 OREGON MECHANICAL SPECIALTY CODE ALT ALTERNATIVE CND CONDENSATE DRAIN EXH EXHAUST MA MIXEDAIR RA RETURN AIR VFD VARIABLE FREQUENCY DRIVE (GMSC), 2014 OREGON STRUCTURAL SPECIALTY CODE (OSSC), 2014 OREGON 9. ALL MATERIALS & PRODUCTS USED WILL BE NEW UNLESS OTHERWISE DIRECTED AL ALUMINUM CONC CONCRETE EXIST EXISTING MAX MAXIMUM RET RETURN VRV VARIABLE REFRIGERANT VOLUME ENERGY EFFICIENCY SPECIALTY CODE (OEESC)AND ASHRAE STANDARDS. BY THE OWNER.ALL EXISTING DUCTWORK, GRILLES & DIFFUSERS TO REMAIN, APD AIR PRESSURE DROP CONT CONTINUE(D)(ATION) EXP EXPANSION MBH THOUSAND BTU PER HOUR REV REVISION wi WITH UNLESS OTHERWISE DIRECTED BY THE OWNER. APPROX APPROXIMATELY CL CENTERLINE F DEGREES FAHRENHEIT MD MOTORIZED DAMPER RH RELATIVE HUMIDITY WB WET BULB 3. LOAD CALCULATIONS WERE PERFORMED WITH AN APPROVED EQUIVALENT ARCH ARCHITECT(URAL) DDC DIRECT DIGITAL CONTROL FC FLEXIBLE CONNECTOR MECH MECHANICAL RPM REVOLUTIONS PER MINUTE WC WATER COLUMN COMPUTATION PROCEDURE AND EQUIPMENT SIZING AND CAPACITY DOES NOT 10. PROGRAMMABLE ROOM THERMOSTATS TO BE MOUNTED 48"ABOVE FINISHED AUTO AUTOMATIC DEFL DEFLECTION FD FIRE DAMPER MFG MANUFACTURER SA SUPPLY AIR W/o WITHOUT EXCEED THE LOADS CALCULATED AS PER SECTION 503.2 OF THE OEESC. FLOOR. PER SECTION 503.2.4 OF THE OEESC THERMOSTATS SHALL BE CAPABLE BDD BACKDRAFT DAMPER ON DOWN FPM FEET PER MINUTE MH MOUNTING HEIGHT SF SQUARE FEET WPD WATER PRESSURE DROP OF CONTROLLING THE TEMPERATURE BETWEEN 55°F AND 85°F WITH A BHP BRAKE HORSE POWER DWG DRAWING FSD FIRE SMOKE DAMPER MIN MINIMUM SH SENSIBLE HEAT W WATT 4. NEW DUCTWORK TO BE INSTALLED USING SHEET METAL RUN OUTS IN DEADBAND OF 5°F. OFF-HOUR CONTROLS SHALL BE ACCOMPLISHED USING A BLDG BUILDING EAT ENTERING AIR TEMPERATURE FT FEET N/A NOT APPLICABLE SP STATIC PRESSURE KW KILOWATT ACCORDANCE WITH SMACNA STANDARDS. PROGRAMMABLE THERMOSTAT OR TIMECLOCK. OPTIMUM START CONTROLS BOD BOTTOM OF DUCT EF EXHAUST FAN FV FACE VELOCITY NC NOISE CRITERIA SPEC SPECIFICATION SHALL BE ABLE TO VARY THE START-UP TIME OF THE SYSTEM TO JUST MEET BOP BOTTOM OF PIPE EFF EFFICIENCY GA GAGE/GAUGE NC NORMALLY CLOSED SS STAINLESS STEEL HVAC�R CONTROLS 5. INSULATE & SEAL DUCTS AND PLENUMS PER OEESC 503.2.7 & OSMC 603.9. THE TEMPERATURE SET POINT AT THE TIME OF OCCUPANCY. PROVIDE A BSMT BASEMENT ELEC ELECTRIC(AL) GALV GALVANIZED NC NORMALLY OPEN TD TEMPERATURE DIFFERENCE TERMINAL CONNECTIONS WILL USE NOT MORE THAN 8' OF FLEXIBLE DUCTWORK. VANDLE PROOF GUARD FOR THERMOSTATS LOCATED IN PUBLIC AREAS AS BTUH BRITISH THERMAL UNIT PER HOUR ELEV ELEVATION HP HORSE POWER NTS NOT TO SCALE TEMP TEMPERATURE INSTALLATION OF FLEX DUCT WILL BE HUNG PROPERLY TO PROVIDE PROPER REQUIRED. CD CEILING DIFFUSER EQ EQUAL 10 INTERNAL DIAMETER OD OUTSIDE DIAMETER TP TOTAL PRESSURE CONTRACTORS • ENGINEERS AIRFLOW WITHOUT RESTRICTIONS. ALL SUPPLY AND RETURN AIR DUCTS AND HVAC DUCT SYMBOLS PLENUMS SHALL BE INSULATED WITH A MINIMUM OF R-5 INSULATION WHEN 11. COMPLEX MECHANICAL SUPPLY AIR SYSTEMS SERVING MULTIPLE ZONES SHALL SERVICE • MAINTENANCE LOCATED IN UNCONDITIONED SPACES (CEILINGS AND ATTICS)AND A MINIMUM BE VAV SYSTEMS AND SHALL REDUCE PRIMARY AIR SUPPLY TO EACH ZONE TO OF R-8 INSULATION WHEN LOCATED OUTSIDE THE BUILDING. EXCEPTION: WHEN ONE OF THE FOLLOWING WHEN THE ZONE TEMPERATURE IS IN A 5 DEG. F. ZONE FITTING SINGLE LINE DOUBLE LINE FITTING SINGLE LINE DOUBLE LINE FITTING SINGLE LINE DOUBLE LINE FITTING SINGLE LINE DOUBLE LINE SINGLE LINE THE DESIGN TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR AND TEMPERATURE DEAD BAND AFTER COOLING IS NO LONGER REQUIRED AND EXTERIOR OF THE DUCT OR PLENUM DOES NOT EXCEED 15 DEG. F. (RETURN BEFORE REHEATING, RECOOLING OR MIXING TAKES PLACE: VOLUME DAMPER tTi MAIN WITH RECTANGULAR EXTRACTOR EX RECTANGULAR �� SUPPLY AIR 9EX DUCT RISER OUTSIDE AIR DUCTS ABOVE CEILINGS). DUCT RUN OUTS IN A CONDITIONED SPACE & 1. TWENTY PERCENT OF THE MAXIMUM SUPPLY AIR TO EACH ZONE. FD RECTANGULAR 45° 6•• (503) 234-0477 • hunterdavisson.com EXHAUST DUCTS SHOULD BE UNINSULATED. 2. THREE HUNDRED CFM OR LESS WHERE THE MAXIMUM FLOW RATE IS FIRE DAMPER FD BRANCHJJJ JJI�� ROUN ROUND ( -� ® RETURN AIR LESS THAN 10 PERCENT OF THE TOTAL FAN SYSTEM SUPPLY AIRFLOW DUCT DUCT RISER 6. VOLUME DAMPERS OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE RATE. CONCENTRIC �I�� ROUND MAIN -1 SQUARE TO ROUND r-�15°MAX DUCT WITH CONICAL ROUND RECTANGULAR �-}--j EXHAUST AIR PROVIDED IN THE BRANCH DUCTS OR AT EACH INDIVIDUAL DUCT REGISTER, 3. THE MINIMUM VENTILATION REQUIREMENTS OF CHAPTER 4 OF THE 90°RECTANGULAR ROUND BRANCH TEE BRANCH DUCT DROP GRILLE OR DIFFUSER. IN ADDITION EACH VOLUME DAMPER OR OTHER MEANS GMSC UNLESS INCREASING THE VOLUME TO CRITICAL ZONES BEYOND 7uRN NG VANES ,' CONCENTRIC CEO PRO OF SUPPLY AIR ADJUSTMENT USED IN BALANCING SHALL BE PROVIDED WITH THE MINIMUM VENTILATION REQUIREMENTS RESULTS IN A DECREASE IN ROUNDTRANSITION `-�- ROUND Off_ ROOM THERMOSTAT 15°MAX 30°TRANSITION `�' ® m 11Y DUCT DROP ACCESS IN ACCORDANCE WITH SECTION 603.17 OF THE GMSC. OVERALL OUTSIDE AIR REQUIRED BY THE HVAC SYSTEM.AN INCREASE 't' R-W Ac-1 BEYOND MINIMUM VENTILATION RATES SHALL NOT BE APPLIED TO MORE RADIUS ELBOW ECCENTRIC �-p-� NON-SYMMETRICAL O pZ W RECTANGULAR UNIT CONTROLLED W 3PE., D 7. SHEET METAL DUCT JOINTS SHALL BE SEALED WITH MASTIC. WHERE MASTIC IS THAN 20 PERCENT OF THE ZONES WITH REHEAT. (RECTANGULAR 5°MAX WYE OFFSET MORE \ W USED TO SEAL OPENINGS GREATER THAN 1/4", A COMBINATION OF MASTIC AND OR ROUND) DOUBLE FORMED THAN 15° ` t� �, r MESH SHALL BE USED. 12. OPERATION AND MAINTENANCE MANUAL(S) SHALL BE PROVIDED TO THE TURNING VANES �47i2EG 143.1 BUILDING OWNER BY THE MECHANICAL CONTRACTOR IN ACCORDANCE WITH 13 , SECTION 503.2.9.3 OF THE OEESC. SPLIT SYSTEM FAN COILS DESIGN CONDITIONS - PORTLAND, OREGON EXPIRES: 66/30/2020 COOLING HEATING SUPPLYFAN ELECTRICAL (Heater+Motor) SHIPPING SPACE WINTER SUMMER TAG EXIST. NEW QTY. MFG. MODEL LOCATION SERVING OUTDOOR ESP UNIT AUX Kw CFM VOLTAGE/ MCA MOCP TOTAL TOTAL WEIGHT NOTES TEMPERATURE HUMIDITY TEMPERATURE HUMIDITY (IN-WC) (MBH) (MBH) PHASE (LBS) INDOOR 70°F t 2°F DB NOT CONTROLLED 75°F t 2°F DB NOT CONTROLLED AC-1 X 1 CARRIER FV4CNF036 CEILING EXTERIOR OFFICES NE 36 36.0 1,100 208/1 1 OUTDOOR 25.2°F DB N/A 91.4°F DB/67.3°F MCWB 28.1%RH ' AC-2 X 1 CARRIER FV4CNF024 CEILING EXTERIOR OFFICES NW 24 24.0 800 208/1 1 NOTES: AC-3 X 1 CARRIER FV4CNF036 CEILING EXTERIOR OPEN OFFICE SW 36 36.0 1,200 20811 1 1. OUTDOOR CONDITIONS BASED ON ASHRAE FUNDAMENTALS 2013, 99.6% &0.4% DATE NOTES: O 1. FIELD VERIFY MISSING INFORMATION MINIMUM INSULATION R-VALUE FOR HVAC DUCT SYSTEMS (OREGON) O DUCT LOCATION ('3) DUCT TYPE J OUTSIDE RETURN COOLING HEATING GRILLES, REGISTERS AND DIFFUSERS AIR AIR SUPPLY SUPPLY Lim EXTERIOR OF BUILDING 8.0 8.0 8.0 SYMBOL MANF. MODEL DESCRIPTION FACE TYPE FRAME FINISH NOTES VENTED SPACES CD-1 PRICE PDC CEILING SUPPLY DIFFUSER PERFORATED T-BAR TYPE 3 WHITE (-1)) _ 8.0 8.0 8.0 -- - - - UNCONDITIONED SPACES&PLENUMS ('2) 5.0 5.0 5.0 5.0 CRA PRICE PDDR CEILING RETURN/EXHAUST PERFORATED T-BAR TYPE 3 WHITE FULLY CONDITIONED SPACES 8,0 _ NOTES: NOTES: THIS TABLE IS IN ACCORDANCE WITH THE 2014 OREGON ENERGY EFFICIENCY SPECIALTY CODE, 503.2.7. 1. INCLUDES UNCONDITIONED SPACES (ATTICS, CRAWL SPACES, VENTED MECHANICAL ROOMS) OUTSIDE THE BUILDING ENVELOPE 2. INCLUDES UNCONDITIONED, UNVENTED SPACES SUCH AS UNVENTED MECH. ROOMS, SHAFTS, OR PLENUMS IN THE BUILDING EXHAUST FANS 3. ENVELOPE INSULATION IS NOT REQUIRED IF THE DESIGN TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR AND EXTERIOR OF THE DUCT DAMPER FAN ELECTRICAL OPER. OR PLENUM DOES NOT EXCEED 15°F FLOW ESP -- MOTOR OWENS CORNING SOFT-R DUCTWRAP FRK WITH A THICKNESS OF 2.2" HAS AN INSTALLED RATING OF R-6.0 LU SYMBOL QTY. MANF. MODEL AREA SERVED TYPE DISCHARGE BACK- MOTOR- VOLTS/ MCA MOCP BHP HP DRIVE WEIGHT NOTES OWENS CORNING SOFT-R DUCTWRAP FRK WITH A THICKNESS OF 3" HAS AN INSTALLED RATING OF R-8.3 (CFM) (IN.WG) DRAFT OPERATED (RPM) PHASE (AMPS) (AMPS) [WATTS] [AMPS] (RPM) (LBS.) EF-1 1 DELTA SIG80 RR/SHOWER RM CEILING CABINET ROOF 80 0.25 X N/A 120/ 1 NIA 1 15 [14] [0.3] N/A DIRECT 15 1 O O NOTES: - SCOPE OF WORK: SHEET INDEX � 1. FAN OPERATES OFF LIGHT SWITCH, INTERLOCK BY EC 1. SAFE-OFF AND DEMO DUCT AS NECESSARY-HAUL AWAY SHEET SHEET REV REV BY OTHERS # NAME # DATE UJ 2. PROVIDE NEW EXHAUST FAN FOR SHOWER ROOM AND TIE M000 MECHANICAL COVER PAGE M I N I S P L IT (COOLING ONLY) INTO EXISTING TERMINATION MD104 LEVEL FOUR FLOOR PLAN- DEMO INDOOR FANCOIL UNITOUTDOOR CONDENSER 3. PROVIDE NEW TERMINAL UNIT ZONE FOR LARGE M104 LEVEL FOUR FLOOR PLAN - - CONFERENCE ROOM 1 ELECTIRCAL WEIGHT NOMINAL SENSIBLE ELECTIRCAL REFER. OPER. NOTES MR104 LEVEL FOUR REFLECTED CEILING PLAN QTY. MANF. AREA SERVED AIRFLOW ESP CAPACITY CAPACITY EFFICIENCY TYPE WEIGHT 4. REWORK EXISTING DUCTWORK TO PROVIDE DEDICATED Q SYMBOL MODEL VOLTS/ MCA MOCP SYMBOL MODEL VOLTS/ MCA MOCP (CFM) (IN.WG) PHASE (AMPS) (AMPS) (LBS.) (MBH) (MBH) (SEER) PHASE (AMPS) (AMPS) (LBS) ZONE FOR CONFERENCE ROOM 2 1 IDAIKINI ELEVATOR EQ. RM. DS-1 FTK36NVJU 742 - 208/ 1 38 ACCU-1 RK36NMVJU 34.4 22.2 15.9 208/ 1 17 20 R410A 133 1, 2, 3 5. RELOCATE EXISTING CONTROLS (BY RELIABLE CONTROLS) 9600 SW OAK STREET 6. DUCTWORK MODIFICATIONS TO EXISTING TO PROVIDE TIGARD, OR 97223 NOTES: PROPER ZONING Approved plens 1. PROVIDE WITH CONDENSATE PUMP 7. FURNISH & INSTALL (X1) 3-TON SPLIT SYSTEM AS SHOWN shall be on job site. 2. PROVIDE WITH WIRELESS THERMOSTAT ON PLANS 3. PROVIDE WITH BAFFELS FOR LOW AMBIENT CONDITIONS SITE COPA REVISIONS 8. PROVIDE RETURN AIR GRILLES W/SOUND BOOTS FOR PRIVATE OFFICES AND CONFERENCE ROOMS CITY OF TIGARD - - c 9. REFRIGERANT PIPING AND INSULATION AND CONDENSATE TERMINAL UNITS DRAIN fliEVIE D FOR CODE COMPLIANCE U) Approve ] VALIDITY OF PERMIT E INLET MIN. REHEAT DESIGN ELECTRIC RESISTANCE HEAT OPER. 10. FABRICATE AND INSTALL GALVANIZED SHEET METAL OTC: Q SYMBOL EXIST NEW QTY. MANF. MODEL AREA SERVED SIZE FLOW FLOW FLOW EAT LAT POWER WEIGHT NOTES DUCTWORK I I THE ISSUANCE OF A PERMIT BASED ON CONSTRUCTION VOLTS/ STAGES Permit #: �Lor�p 'Zp� pn� 1 9 (IN.) (CFM) (CFM) (CFM) (°F) ('F) PHASE (KIM (LBS.) 11. DUCT LINER& DUCT WRAP AS APPROPRIATE DOCUMENTS AND OTHER O Address: 9600 n GIC 9r DATA SHALL NOT PREVENT X 1 INTERIOR OPEN OFFICE NORTH 225 750 55 55 1 Suite #: THE CODE OFFICIAL FROM 3 12. GRILLES, REGISTERS AND DIFFUSERS PER PLANS �- X 1 INTERIOR OPEN OFFICE SOUTH 70 225 55 55 1 By: Date: REQUIRING THE CORRECTION o VVT- X 1 INTERIOR SOUTHEAST OPEN OFFICE 12 150 500 55 55 1 13. START, CHECK AND ADJUST SYSTEMS � OF ERRORS. OSSC 105.4 Y VVT- X 1 RECEPTION /PLOTTER 12 100 325 55 55 1 14. TESTING, ADJUSTING &AIR BALANCING O VVT- X 1 NORTH - LUNCH ROOM 10 270 270 55 1 o- VVT- X 1 NORTH -OFFICES 12 340 340 55 1 DATE 01/07/2020 - ---- - - VVT- X 1 EAST-OPEN OFFICE 12 120 280 400 55 1 BUILDING PLAN: O VVT- X 1 SOUTH - LIBRARY/OFFICES 16 180 420 600 55 1 / AREA OF WORK DRAWN BY RM N VVT- X 1 SOUTH - LARGE CONE. 14 225 525 750 55 1 CHECKED BY TW o VVT-A X 1 CARRIER OPNDR14ZC SOUTH-MED. CONF. /OFFICES 14 400 400 600 55 81 208/3 5.0 1 30 2 ® MECHANICAL NOTES: III JETURTFFF11 0 1. FIELD VERIFY MISSING INFORMATION COVER PAGE N 2. ELECTRIC DUCT HEATER IS TO BE MOUNTED INLINE DOWNSTREAM OF ZONE DAMPER, CONTROLS BY OTHERS. SOO FOR DUCT HEATER: HEATER TO RUN OFF STAND-ALONE THERMOSTAT. THERMOSTAT TO BE SET TO 68°F AND WILL ACT AS I v A SECOND STAGE OF HEATING FOR THE CONFERENCE ROOM (AS NEEDED). ff 1111c cTTTFF IchI In cc M000 Ji 0 CONSTRUCTION - - - - - - - - - -41 o DRAWING PAGE SPECIFIC NOTES_ 01 REMOVE DIFFUSERS AND STORE IN SAFE PLACE TO BE REINSTALLED WITH NEW CEILING. HVAC/R • CONTROLS CONTRACTORS • ENGINEERS SERVICE • MAINTENANCE (503) 234-0477 • hunterdavisson.com co PRo ' p IN7 EGONory 13 , c� C YW Y �� EXPIRES: 06/30/2020 • - • •fit♦ __ •�•B.,ID ■ - • O I 081.08110 OFFICE • 'l r - OFFICE OFFICE OFFICE OFFICE■-- O 10"4JTYP. 3' Lim 414 _ 4i, 416 418 41g 8 ID WT- Q II ID ' _ ' ,�• ' _� EXST. EXST. _ _ r 1. 16"ID �XST. ilt I' X 8'0 •\Y• ._..._ ID • 8„ID \ 8"ID X 16"ID 1, CH ROOA 12"ID 12"ID 8"ID Fm 1b'0 E- - ------�_ _ _ 10,10EXST. 10"ID x w 10'10 c FD O O cn 8" . - . . - . pi 10"fb _ . ♦_ . . _ . A 1 �f10ID 8ID 80 Lu 10"ID 14"ID 2..0 ID 10,10f ff_ .0 41216" 1 16"0 2" 0 O O - 2 � UNISEX OPEN OFFICE EXE. EM. SHOWER 420 12"0=12"l 'Ll 411 i 16„ID T-,RA'GE iL :, 16,6„ID� . - . VER12"IDr f8„ID 1m��� 12-0 m 10"0 i j;.�. - . ' TIER! I10"ID 14 fdOPIERS10"ID 0,18"ID 1 ••• I ,� 8"ID ,M, - • i pID8"ID4ao -18 _ ------ -----------j DN U - 9600 SW OAK STREET Ll— 16"ID DST 12°ID I� O TIGARD, OR 97223 ID R,aF ' EXST. 1M- -- — . --.— 16"0 CONFERENCE NVf— REVISIONS 403 EXST 14"0 16"ID AC-3 - - c CONFERENCE O 12"ID 4nz OFFICE :}1: oa. . 1ID 101 EX3T 10"`0 En TT 2" 8„0r�80 tf f 0 8 � 80 f • f 10"ID 40 o _ Fa ID 10* 10 i. . _ . 0 .3 C O U;_, 7 0 Q DATE 01/07/2020 m o DRAWN BY RM 0 CHECKED BY TW 0 0 LEVEL FOUR C) LEVEL FOUR FLOOR PLAN — DEMO FLOOR PLAN - N DEMO 1 MD1 o O cocu 4 0 CONSTRUCTION o DRAWING PAGE SPECIFIC NOTES: 01 DRAIN CONDENSATE TO RESTROOM SINK TAILPIECE. L 02 FIELD VERIFY FCU LOCATION IS NOT ABOVE R EQUIPMENT. ROUTE REFRIGERANT LINESET UP TO CONDENSING UNIT ON ,ep�4 RRO F THROUGH PITCH POCKET �� a 04 REFERENCE 2/M104 FOR CONDENSING UNIT MOUNTING .anoi wa a aw mea m.a DETAIL. 01w�1 ME MWL N Iq ��` O1°�0 ,.w Q CONTROLS BY RELIABLE FIELD .�nms VERIFY THERMOSTAT LOCATIONS HVAC/R • CONTROLS ••'V•°°•• ••w^^�• WITH OWNER. h OAR Q EACH PRIVATE OFFICE AND CONTRACTORS • ENGINEERS CONFERENCE ROOM RECEIVES A SOUND BOOT ON THE JIB` RETURN GRILLE. SERVICE • MAINTENANCE ,CONDENSING UNIT— MOUNTING DETAIL /PREF. PIPING ROOF PENETRATION DETAIL (503) 234-0477 • hunterdavisson.com NTS Km PR Li 3f5E •. - y o: r EG02 ry 13 . c� EXPIRES: O6/30/2020 AC-2 EXST. O ®emum. 12"0 — 12"0 --— 0 78 0 8110® ® m CLim- �8 0 --J _ EXST. 10 --- - C 8"o 8"0 8.,0 r 16"0 v --7 � y Fm 16"�` i --- VVT— AC-1 ----- EXST. -------------- i — NEW 1 ® ♦A 10"0 8110110 c Lu ,1 ® 1o..oc 6 O 14"0 12"0 10"0 � 16" 16"0 O + O 2"0 L — — — — — — — — — — — — — — — — — 12 0 r rr�iri Wf— 12"0 uj -- ----- U—A 4 EXST. J FCU4a 2 OF - 10" NNGtilL 1 s' 12"0 LmJ NEW, oll 10"0 OFm 14" ii -�12 0 10"0 8.0 8"0 s"0 o —A® EW DN U 8..0 1s"0 9600 SW OAK STREET 1s"0 12"0 TIGARD, OR 97223 wr- - --- EXST. j REVISIONS �--++�� _ EXST. _ 1 z"0 AC-3 10„0 10"0 1 0 14"o 16"0 -------- 0 __ 0 12„0 L 10..0 EXST. 0„0 �O : t0..0 10., 12"0 8"0 0 �j 16' r-- CL c 3 10,10 -- L 3 0 0 w. U LEGEND: 0 Q DATE 01/07/2020 a) QQ CAP o DRAWN BY RM co CONNECT TO ' EXISTING CHECKED BY TW 0 LEVEL FOUR 0 LEVEL FOU R FL00 R P LAN FLOOR PLAN N U c M104 0 co to 0 CONSTRUCTION = 0 DRAWING HVAC/R • CONTROLS CONTRACTORS - ENGINEERS SERVICE • MAINTENANCE (503) 234-0477 • hunterdavisson.com REp PR fi Lu ' 31sE D 1 LIEGON c7 EXPIRES: 06/30/2020 1 10"0 CD-1 8"0 CD-1 10"0 CD-1 10'0 CD-1 10"0 CD-1 10"0 CD-1 10"0 CD-1 12"0 CD-1 300 85 250 250 250 250 250 350 --- --- --- - —2 r J t E r 777 W13 "0 D D-1 D "0 D- '0 CD-1 5 _ul - - 5 5 5 EX T. DNcl R M _- ' � --- 10"0 CD 1 413 _ __ ___ _. -__ _ - - - _ _ _ _ _ _ _ 200 - - O - f - - - -- D �21'f CC A c , a j W 10"0 CD-1 200 T o 0 0 HE o D1 DI a o /SE ' 0 EN FF CE H .11 VEA i j rii3i i� 2d 25 C 1 W — -- - — o c —A O A f j 10"0 CD-1 Fm El—illF 2007 _ S OR/ i ® 0Ma O _ PL T i C RS EX 1 30 AI'® Rf CEPTC;1' i 1 17 40: oull O - - 50 CD DN U so cD- 9600 SW OAK STREET CD-1 TIGARD, OR 97223 � C! tet O 0 ' -- - - � - -- - - -- -- _ � 300 O 10"0 D-1 - - - `T. REVISIONS ��-1 0 FE-AFl m Al—C CONT" Rr 0 N0 o a 40 cn a s E I. Q 0 L '= 10"0 CD-1 10"0 CD-1 12"0 CD-1 8"0 CD-1 8"0 CD-1 10"0 CD-1 10 0 CD-1 10"0 CD-1 10"0 CD-1 10"0 CD-1 3 250 250 400 200 200 200 200 300 300 300 c 0 t5 U 3 o DATE 01/07/2020 Q DRAWN BY RM 0 a) CHECKED BY TW LEVEL FOUR 0 REFLECTED LEVEL FOUR REFLECTED CEILING PLAN N CEILING PLAN N MR1 04 CC 0 CONSTRUCTION c 0 DRAWING