Plans (68) FPS2020-00011
RECEIVED
JAN 2 7 2020
CITY OF TICARD
BRU DING Divisinns
�I
I
w1
Source Information
Dale of Flow Test I info: 12/17/2018
Location of flow test data
Home Depot Hydrant
Source of flow test data
Wyatt Fire Protection
Source Data Points Pum Data Points
Calculation results for Design Area 1 - Canopy Pressure Flow Pressure Flow
This system as shown on Wyatt Fire Protection company print no dated 1/17/202 100.0010
00.00 0.00
for COCA COLA CANOPY at 15333 SW SEQUOIA PKWY#100 96.00 2224.00
contract no C20-10 is designed to discharge at a rate of 0.1 gpm/ft'(L/min/m2)of floor area over
a maximum area of 230 ft' when supplied with water at a rate of 30.3 qpm at 42.8 psi at the base of the riser.
Hose stream allowance of is included in the above. * 7
Occupancy classification: Light Hazard Number of heads flowing: 2
Commodity classification: System Type: Wet
Maximum storage height: Maximum velocity: 10.56 ft/s
Storage arrangement:
Flow from In-Rack sprinklers: 0 gpm Pressure Required at Source: 42.8 psi I
Flow from Overhead sprinklers: 30.3 gpm Pressure Available at Source: 100 psi
Flow from Inside Hoses: 0 gpm Surplus Pressure at Source: 57.2 psi
Flow from Outside Hoses: 0 gpm
Other fixed flows: 0 qpm
Total flow in system piping: 30.3 gpm
Additional flow at/beyond source: 100 qpm
Total of all flows: 130.3 gpm
LOCATION OF NEW CANOPY
15
41
1fi
18
r J
1
12
3
❑
i
SCOPE:
EXTEND SPRINKLER SYSTEM TO SITE PLAN
EXTERIOR CANOPY. SYSTEM TO BE ,/32•=1'-0°
FILLED WITH PROPYLENE GLYCOL
LISTED FOR USE IN FIRE SPRINKLER
SYSTEMS. GLYCOL SYSTEM TO BE ❑
CONTAINED WITH RP BACKFLOW a
DEVICE AND UTILIZE EXPANSION TANK 9,2„
FOR PRESSURE FLUCTUATIONS.
r1 oU m BACKFl.OW
DENCE, DRNN TO
VBE PIPED OUTSIDE
7 SAMMY SIDEWINDER (SWC)
1-V: ,a-Pa "riF11 15' _
- OFFICE COPY
FPT-,C
EXPANs ON
am e: T""T CITY OF TIGARD
LOCA ` HEAD EL NTH TE1. ALL THREAD ROD REVIEW.�D FOR CODE COMPLIANCE
Area: 249.40 EXTEND SPRINKLER PROTECTION \'rNf
TD EXTERIOR CANOPY.
Approved:
OTC: I I
Permit #: F•Pj�,�r _ C'7 �
Address: �S �� Z Po L . n e- Uk.
0
Suite #:
By: �_ Date:
I O
RCP—CANOPY HANGER DETAIL
1/4•=1'-0• NOT TO SCALE
VALIDITY OF PERN-Ii ,
EFIN:AL
ASE PROVIDE THE ISSUANCE OF A PERMIT
LETED NFPA 13 I BASED ON CONSTRUCTION
RIAL AND TEST DOCUMENTS AND OTHER
TIFICATE AT DATA SHALL NOT PREVENT
THE CODE OFFICIAL FROM
INSPECTI®`,T REQUIRING THE CORRECTION
OF ERRORS. OSSC 105.4
NOTES SPRINKLER SYMBOLS REVISIONS
Meets design requirements of NFPA 13 2013 edition. SYMBOL STATUS BRAND SIN TYPE FINISH TEMP F ORIFICE THREAD K' FACTOR NOTES TOT. DATE DESCRIPTION BY
I new piping to be Eddy Thread 40 w/ screwed ductile iron fittings. NEW TYCO TY323 SSP-OR Ch/Ch 200 1/2- 1/2- 5.6 2 COCA C0LA CANOPY
II hangers to be per NFPA 13 rea light hazard
J W YAT T PERMIT NO.
I onnovers greater than 2'-0' shall be provided with hangers.
Area of work to be protected ere a light hazard occupancy.
Max. sprinkler spacing to be 225 sq. ft. per head.
W SEQUOIA PKWY #10 0 CONTRACT N0. C20-10
Total area of work area is 230 sq. n. FIRE PROTECTION, INC. DRAWN BY M.COLLEY
9095 S.W. Burnham PORTLAND , O R 97224 SCALE 1/4" _ 1'-0•
Tigard, OR 97223 DATE 17 JAN 2020
(503) 684-2928 REVISED
VANOSDEL CONSTRUCTION, PO BOX 1057, BATTLE GROUND WA 98604 1 OF 1