Plans (77)
M EC2020-00139 , GENERAL DEMO NOTES: 2 A. ALL EXISTING PIPING AND DUCTWORK INDICATED ON PLAN WAS TAKEN FROM EXISTING MECHANICAL PLANS AND/OR FIELD OBSERVATION AND SHALL NOT BE CONSIDERED 100%ACCURATE. THE CONTRACTOR SHALL -J VERIFY LOCATION OF ALL EXISTING SYSTEMS PRIOR TO CONSTRUCTION AND SHALL NOTIFY THE OSR OF ANY POTENTIAL CONFLICTS. IT 14 I B. CONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL -- f 1 - DRAWINGS,SPECIFICATIONS&EXISTING CONDITIONS FOR BIDDING PURPOSES. 1 I NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS TARGET® -— -� — -' KNOWLEDGE. GENERAL NOTES: 2 (E) 2 I C. PATCH ALL PENETRATIONS WHERE PIPING OR DUCTWORK IS REMOVED. EXISTING TO REMAIN. PATCHING SHALL BE BY GENERAL CONTRACTOR. 1❑ 1000 NICOLLET MALL - -Z I ❑2 REMOVE EXISTING DUCTWORK,EQUIPMENT AND G.R.D.S SHOWN CROSS HATCHED. MINNEAPOLIS, MN 55403 4 - - - - D. FIELD VERIFY LOCATIONS AND QUANTITY OF ALL EXISTING EQUIPMENT, CAP DUCTWORK AIR TIGHT IF NOT REUSED. ® FIXTURES AND DUCTWORK NECESSARY TO COMPLETE SCOPE OF WORK. EXISTING SENSOR TO BE REMOVED,VERIFY LOCATION MICHAEL D. WOEHRL P.E. E. INDICATED TO BE REMOVED. REMOVED EQUIPMENT TO CONNECT TO EXISTING. :, • I I 2 -- - r �, �— - - - - - - - - - - - - - -- - -` a .: _. - - - - - BE DISPOSED OF BY CONTRACTOR. PROVIDE OSR& - , d TARGET FACILITIES MANAGEMENT FIRST RIGHT OF PROVIDE 1/4"HARDWIRE CLOTH OVER DUCT OPENING. 9100 49th Avenue N. 2 (E) 24x24 , `_ L. _ -. i REFUSAL ON REMOVED EQUIPMENT.PROVIDE OSR 8 TARGET MINNEAPOLIS, MN 55428 - - - - - /' DEMOLISHED EQUIPMENT. RST RIGHT OF REFUSAL ON TEMPERATURE SENSOR, MOUNT AT 60 AFF F f / O(E) 8' 2 I I ❑ XISTING TO BE RELOCATED. D FACILITIES MANAGEMENT FI I 2 E 220 I RECEIVED 2 - 1 - F. ARRANGE ALL REQUIRED WORK TO KEEP DISRUPTIONS TO STORE OPERATIONS 7❑ E Tel: (763) 367-7600 RECEIVE - -- 220 (E) 2 - - - - C TOA MINIMUM. COORDINATE ANY DISRUPTIONS WITH TARGET OSR AND Fax: (763) 367_7601 1 12 (E) 8, - Z 8.0 _ ® EXISTING CEILING TO BE REMOVED.RAISE EXISTING DUCTWORK AS HIGH AS MAR 112020 --- _ 1 STORE MANAGER. 220 - . --- POSSIBLE,COORDINATE ELEVATION WITH OTHER TRADES. Qkly OF TIGARD P G. SUBMIT(2)COPIES OF REDLINED AS-BUILT UPDATES. ONE COPY TO BE 9❑ BALANCING DAMPER,MOUNT IN AN ACCESSIBLE LOCATION. � kINNG D"SION 2 g \, � I RETAINED AT THE STORE. RETURN SECOND COPY TO THE OSR TO BE 9'0 14"0 8x24 (E) 2 I FORWARDED TO THE MECHANICAL ENGINEER. 10 BALANCE EXISTING G.R.D.TO CFM INDICATED. 4 M i 2- ( `y ) — I{L H. CONTRACTOR SHALL COORDINATE ALL PHASES OF DEMOLITION WITH 11 MODIFY SPRINKLER PIPING AND HEAD LOCATION FOR REVISED CEILING AND WALL J - 1 C _ ,= -- r- T , ARCHITECTURAL DEMOLITION PLANS. LAYOUT, IN ACCORDANCE WITH NEPA 13 AND TARGET'S HYDRAULIC DESIGN CRITERIA. L - - -- - - 1 E)e2O VVT - .. E . 'CVT 2 :: { 1❑(E) - - - -- - - - - I ' 10 I I � I 12 PPISTING CEILING NG AS NEEDED.MODIFY SPRINKLER SYSTEM AS NEEDED TO MO BE REMOVED.WALLS TO EXTEND TO DECK.EIT NFPA 13SE ALER ND 24x24 _ 19 t - - - - - I: GENERAL NOTES: 6' I g` I = v�` I:, Q � STOCK HYDRAULIC DESIGN CRITERIA.COORDINATE ELEVATION WITH OTHER TRADES. (E) I ! so (E) 2 vvr — C✓�d, . I T ; ; OFFICE COPY ------ ^ --- --- --- --- - - --- ^ �_ �, = ___ _ _ �.�' III `. � � I 1 8 e 10 a 8x24 T "' ', L i A. COORDINATE LOCATIONS OF GRILLES,REGISTERS,AND DIFFUSERS IN CEILING WITH 13 Wx10"EXHAUST DUCT UP TO PRV-1 ON ROOF.ROUTE DUCT THROUGH DUCT CHASE.SEE (E) 2 10 3 ~' `1 L' �LL'� ARCHITECTURAL REFLECTED CEILING PLAN. CITY OF TTGARD \ II I I I 12 (E) .2 I ARCHITECTURE FOR CHASE LOCATION. REVIEWED TOR CUDE COMPLIANCE - - - - - - B. SEE SHEET PM01 FOR TYPICAL PIPE AND DUCT HANGER DETAILS. - - - i 14 REMOVE PRV-1 ON ROOF.CAP AND INSULATE CURB WEATHER TIGHT. Approved:f '12x 560 �J (E)40x12' -- ---- -- I -._i I (I �} ) L / I C. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH O'I•C: y , , d ! � i SMACNA STANDARDS. 15 MOUNT BOTTOM OF EQUIMPENT AT V-0"ABOVE FINISHED CEILING. Pcrniit #: 3 (E 7 VVT T I ( I D. COORDINATE LOCATIONS OF GRILLES,REGISTERS,AND DIFFUSERS IN CEILING WITH Address: ' 1 1 ;I I 18 19 I _ r T - II. � -- 16 ROUTE NEW DUCTWORK AND MOUNT NEW EQUIPMENT HIGH AS POSSIBLE.COORDINATE CJE�c^f� S V 1-1 I f3 J �' i ARCHITECTURAL REFLECTED CEILING PLAN. 24"x8'-- - 6x12 E. 1 ( 2 E ELEVATION WITH OTHER TRADES. Suite #: -- 2U E O I I I ( \\ VVI 2 O 2 y ate. D L _ pzx \ — — — — — — — I , ( L VALIDITY OF PERMIT vuT - � _ _:T _ 1-._ l l �I._1 140_ _ __ _ T 18 - �� � �/ ! BASED ON CONSTRUCTION - , DOCUMENTS AND OTHER Date No. Description -- — - - __ —_ _. ...-._— - - T PREVENT - I 12x12 (E) 2 I TDHE SH 1/31/202 - ALL NO 525 CODE OFFICIAL FROM 01/31/2020 BP 3.0 COMPLETE .. \. ._ `.; v ,. REQUIRING THE CORRECTIONCONSTRUCTION =,< ) ,. I , ,<• . ,., C ,,. r , . .. OF ERRORS. OSSC 105.4 __-_ HYDRAULIC DESIGN CRITERIA GUEST SERVICE & OFFICE HVAC DEMOLITION PLAN OCCUPANCY OR BASIS OF HOSE SPRINKLER M301 SCALE: 1/4"=1'-0" 0 2, 4, 8. 2 SYSTEM/ DENSITY COMMODITY STORAGE SPRINKLER STREAM TYPE AND TEMP AREA CLASSIFICATION ARRANGEMENT DESIGN ALLOWANCE SPACING F) RESTROOM HVAC DEMOLITION PLAN STOCK 0.45 GPM/SQ FT OVER SHELF STORAGE 15'STORAGE ON MEETS REQUIREMENTS OF 500 GPM K-25 165°F M301 SCALE: 1/4'=1'-0' 0 2' 4' 8' MOST REMOTE OF CLASS IV 12'HIGH 24'DEEP NFPA 13 SPECIAL DESIGNS UPRIGHT SPKLRS 2000 SQ FT COMMODITIES BACK TO BACK OF STORAGE PROTECTION EXTENDED 0.55 GPM/SQ FT SHELVING UNITS COVERAGE FOR 4 MOST 37"AISLES MAXIMUM HYDRAULICALLY CEILING HEIGHT SHALL NOT SPACING DEMANDING EXCEED 25 FT OR BE LESS 14'x14' 2 SPRINKLERS THAN 19FT SALES 0.20 GPM/SQ FT OVER ORDINARY HAZARD MAXIMUM 10'HIGH EXCEEDS NFPA 13 AREA/ 250 GPM K-14 155°F MOST REMOTE GROUP II DISPLAY ON 84" DENSITY CURVE FOR RECESSED SPKLRS ® ® , 2000 SQ FT. HIGH CANTILEVER ORDINARY HAZARD EXTENDED I�E X SHELF STEEL GROUPII COVERAGE GONDOLAS MAXIMUM 0.30 GPM/SO FT FOR 4 SPACING (E)COF EE SEAT NG MOST HYDRAULICALLY 16'x16' ESLES • ( I L DEMANDING SPRINKLERS D-Ci -. -- -- (E)COFFEE STO GE I OFFICES 0.10 GPMISQ FT LIGHT HAZARD NIA NFPA 13 AREAMENSITY 100 GPM QUICK 155°F 1 11 , 113 OVER MOST CURVE FOR LIGHT RESPONSE SPKLRS L a REMOTE HAZARD STANDARD 4 - - - ._.. -- -__. - _ 1500 SQ FT COVERAGE I RECESSED 11 0 I l I + PHARMACY, 0.20 GPMISQ FT ORDINARY HAZARD N/A EXCEEDS NFPA 13 AREA/ 250 GPM STANDARD 155°F ._..---- .::.-: --- �.- _: _ T ROUP II SPKLRS _I 16'0 12'0 , � 4 , I PHOTO OVER MOST G DENSITY CURVE FOR RESPONSE g �_ :. .�.. �_.�` - - = _.— _ _ - — - - — - -... -. �..-..— - — - — - — - — - - - — - - — - PROCESSING REMOTE ORDINARY HAZARD STANDARD B - — - — - — --- - _= - — -'� - t - — - T _ B B - B 000 SQ FT ROUP II COVERAGE E 26"x12" 16 &GUEST 2 G OR EXTENDED VT 24x24 8" 6x24 8 � SERVICES 13 ` 19 T 6 F C 245 F 8.0 6x24 F 50 A ! COVERAGE, 1 It L5�'�� I , RECESSED I. G, © -. .-.. (E S) TOCK 1 - - Jq—� 8"0 4 12x121 I 145 7- 2:24 x24 4 J J UEST SERVICE g I - I ' 12.0 x N - 120 10 (E)8,0 -- _ -- - - _- I F 24x24 _ , (E)8"0 - -- t. E 9.0 . I 16"x12" 1 0, 24x24 F PMOL r (E)14"0 (E)14"0 104 - NP. 8"0 12'0 12x8 I VZ V 16 4?879N27PE4 F 24x24 I p 8"0 _ g^ _. 200 m V 15 ( 16 G 300 M301 0 225 i� � - �� VUT VA 10 TYRi OREGON = I C 8,8"° 12x24 F I . I - - 2001.0 I _: .- 220 ! - L_ N 1 I I ,1 vvr -- — — - - - - -. 1 f (EI (E 18 7 A 0 FI E I I -ttc V21V 16 m EXPIRES:0613012020 T( IR TION 1 112 - 11I8' 1.0' 301 300 WOMEN MEN 19 DATE: 01/31/2020 200 VAV T I TYP. — - -- - IRT U\ ( R U _ 1 I x8"._ --- -_ - - I E) � 12x12 J 12x12 ---"- j v 6 �, 1 CASH FFICE 1 FLEXIBLE M BLE FULFILL (E STAIR A _ - * - - - -�--—IRT � ' ' ' I - ._... PRV 6 I W (E 1101R 6 , O 1 PMOL I I 3 RESTROOM HVAC PLAN TIT, B B m M301 SCALE: 1/4"=1'-0" 0 2 4' 8' 2 1 4 � ) . J 4 GUEST SERVICE & OPU STORAGE HVAC PLAN 7 PARTIAL ROOF HVAC PLAN z = O M301) SCALE: 1/4"=1'-0' 0 2' 4' 8' M301 SCALE: 114"=1'-0" 0 2' 4' 8' ~ 0' POWER ROOF VENTILATOR SCHEDULE p ELECTRICAL 10 9 7 6 5 4 3 2 1 0 z FAN NO. AREA SERVED MANUFACTURER MODEL Airflow TSP("WG) DRIVE ROOF OPENING DAMPER SIZE HP VOLTAGE PHASE FREQUENCY REMARKS PRV 1 GUEST RESTROOMS GREENHECK G-95-VG 725 0.375 DIRECT 121/2"X 121/2" 10"X 10" 0.250 120 1 60 PROVIDE SOLID STATE SPEED CONTROL FACTORY MOUNTED. "� L -�— L AIR FLOW i VARIABLE AIR VOLUME BOX SCHEDULE-OWNER FURNISHED M7 � _I_ _ � _ _ _ L _ _I_ _ _ L _ - 1 - _ � - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PRIMARY AIR FAN DATA ELECTRIC HEATING COIL I I I I I I DUCT LINER WHERE INLET COOLING COOLING HEATING _ _ SPECIFIED OFME DIAMETER AIRFLOW MIN AIRFLOW MAX AIRFLOW AIRFLOW AIRFLOW REHEAT H -i - — — - —i_ - T - T — - �r - — -i H Tag NO NO. AREA SERVED MANUFACTURER MODEL NUMBER (INCHES) (CFM) (CFM) (CFM) (CFM) HP FLA (CFM) COIL POWER(W) STAGES TEMP RISE(F) LAT(F) VOLTAGE REMARKS I I I I I I I _ DUCT TO MATCH 6"MINIMUM CONICAL SPIN IN VAV 10 M7 OPU ENVIRO-TEC SDR-08 8 600 600 600 0 CFM 0 600 CFM 7000 W 2 39.5°F 94.5°F 120 V ELECTRIC REHEAT COIL i i _ _ i_ _ _ _ REGISTER FLANGE PROVIDE SUPPORTS WITH DAMPER VAV 21 M7 GUEST SERVICE ENVIRO TEC SDR-08 8 400 400 400 0 CFM 0 400 CFM 4500 W 2 37.9°F 92.9°F 120 V ELECTRIC REHEAT COIL G I I I I I I I G OUTSIDE DIMENSIONS REGISTER WITH DAMPER TO PREVENT SAG MANUALLY ADJUSTABLE BETWEEN HANGERS i i FROM FACE SUPPLY DUCT _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ -� � Project Number PLAN VIEW MAIN F — - r / T-0345 PROVIDE REGISTER TAKEOFF THAT TOWASAIRL5OEGREES HARD DUCT GRILLES, REGISTERS & DIFFUSERS SCHEDULE 1 - I Config:RR DOWN TOWARDS FLOOR ELBOW E -I— - - — - -I- — - - — - — -I- - — E VOLUME 7 1 1 I Drawn By PLG PARALLEL WITH TYPE SERVICE MAKE MODEL DAMPER FRAME FINISH MATERX REMARKS FINISHED FLOOR TOTAL FLEX DUCT C CEILING DIFFUSER TUTTLE AND S1200-LT-WH - NOTE 1 WHITE ENAMEL STEEL 24"x24"MODULAR FULL-FACE DIFFUSER WITH ROUND NECK (] _ — _ _ _ _ M301 - - - I— - — - D LENGTH SHALL NOT BAILEY 1 3 2 4 Checked By M DW - - EXCEED 6 FEET D CEILING DIFFUSER TUTTLE AND S1200-SF-WH-RON OPPOSED BLADE NOTES 1 &2 WHITE ENAMEL STEEL 12"x12"MODULAR FULL-FACE DIFFUSER WITH ROUND NECK M301 M301 I M301 M301 I I , BAILEY r"` - r - - - r- - -r - - - + - - - - C, \ 15° F RETURN/TRANSFER TUTTLE AND CRE500-SF-02-WH - WHITE ENAMEL ALUMINUM I I I I I GUEST SERVICE , _ GRILLE BAILEY MINIMUM OF ONE DUCT DIAMETER G SUPPLY REGISTER TUTTLE AND T54-SF-02-SOBD-WH-SP OPPOSED BLADE NOTE 3 WHITE ENAMEL STEEL 12"x8"FACE;35 DEG FIXED DEFLECTION REGISTER,3/4'SPACING,&1 1/4"MARGIN. _ _ _ DUCT COLLAR OF STRAIGHT DUCT TO INLET OF BAILEY B I 1 B O P U STORAGE , & r _ DIFFUSER, R PROVIDE EQUALIZING _ ^ ^ ' SUPPLY REGISTER S ,0 Q J EXHAUST REGISTER TUTTLE AND T70D-SF-01 SOBD-WH OPPOSED BLADE NOTES 1 WHITE ENAMEL ALUMINUM 12 x12 FACE,35 DEG FIXED DEFLECTION REGISTER,3l4 SPACING,&1 1l4 MARGIN. CONNECTING i _ _ _ _ _ i _ _i_ _ _ � BOTTOM OF DUCT AT STRAP GRID AT DIFFUSER BAILEY A - -� A R E ST ROO M S HVAC 16'-6"ABOVE FINISHED L LINEAR SLOT DIFFUSER TUTTLE AND AIR-TRAC-CTL-01-C01-WH NOTE 3 WHITE ENAMEL ALUMINUM ONE SLOT,48"LONG,INSULATED FACTORY PLENUM.SEE PLAN FOR INLET SIZE AND SLOT WIDTH.PATTERN CONTROLLER ADJUSTED FOR FLOOR(MINIMUM)FOR DIFFUSER BAILEY VERTICAL THROW. 10 9 8 7 G 5 4 3 2 1 0 PLAN SECTION REAR STORAGE ROOMS. ALL GRILLES,REGISTERS&DIFFUSERS ARE FURNISHED BY OWNER AND INSTALLED BY MECHANICAL CONTRACTOR.QUANTITIES,SIZES AND DELIVERY DATES SHALL BE COORDINATED THROUGH THE TARGET REPRESENTATIVE AT 1$66-667-0822. 1. PROVIDE LAY-IN FRAME TYPE. 5 TYPICAL DUCT MOUNTED REGISTER � DIFFUSER FLEXIBLE DUCT CONNECTION 2. PROVIDESURFAEEMOUNT DFRAME'FORALLGYPBOARDCEILINGS. M301 NOT TO SCALE M301 NOT TO SCALE 3. PROVIDE SURFACE MOUNTED FRAME TYPE. KEYP LAN M 3 0 2/5/2020 1:58:28 PM 2 1 GENERAL DEMO NOTES: 4 A. ALL EXISTING PIPING AND DUCTWORK INDICATED ON PLAN WAS TAKEN FROM EXISTING rn❑ MECHANICAL PLANS AND/OR FIELD OBSERVATION AND SHALL NOT BE CONSIDERED 100%ACCURATE. THE CONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING j I L(E)4'SW SYSTEMS PRIOR TO CONSTRUCTION AND SHALL NOTIFY THE OSR OF ANY POTENTIAL = - I 1 CONFLICTS. ° I B. CONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL ' 10 I DRAWINGS,SPECIFICATIONS&EXISTING CONDITIONS FOR BIDDING PURPOSES.NO R -- - - - - - - - - - - - - - - - - - — _ — — _ — _ — _ _ _ _ — _ — _ — _ _ _ —5 _ _ — _ _ — _ — _ — - —{ g ) / / \ ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT TARGET® �� OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. yI II II / 1,{ i _ l--`�- � � � / � �•- - - - - - - - - - - - - - - - - 1- - - - - -(E)4"SW- - - - - - - - - - - - - - - - - - - - - - - - - C. PATCH ALL PENETRATIONS WHERE PIPING OR DUCTWORK IS REMOVED.PATCHING 1000 NICOLLET MALL I} ( `�.. :% SHALL BE BY GENERAL CONTRACTOR. MINNEAPOLIS, MN 55403 - - _ I I I j D. FIELD VERIFY LOCATIONS AND QUANTITY OF ALL EXISTING EQUIPMENT,FIXTURES AND DUCTWORK NECESSARY TO COMPLETE SCOPE OF WORK. MICHAEL D. WOEHRLE, P.E. E. / INDICATED TO BE REMOVED. REMOVED EQUIPMENT TO BE I DISPOSED OF BY CONTRACTOR. PROVIDE OSR& TARGET FACILITIES MANAGEMENT FIRST RIGHT OF MIN E 49th Avenue N. 23 1 / MINNEAPOLIS, MN 55428 F1 ff1 3 3 1 I� / REFUFACILITIES MANAGEMENL ON REMOVED T FIRST RIGHT OF REIPMENT.PROVIDEFUSAL ON TARGET - - - - - - 3 -i- L - - - DEMO'D EQUIPMENT. – C - — r / I — — — � C — I I Tel: (763) 367-7600 -(E)3'SW- - - - I I F. ARRANGE ALL REQUIRED WORK TO KEEP DISRUPTIONS TO STORE OPERATIONS TOA Fax: (763) 367-7601 -(E)2"SW-- ' I I MINIMUM. COORDINATE ANY DISRUPTIONS WITH TARGET OSR AND STORE \ I I-- -� �� i 11 � � I ❑� II � � � � IF � I I MANAGER. 2 I 3 I I 1 I I G. SUBMIT(2)COPIES OF REDLINED AS-BUILT UPDATES. ONE COPY TO BE RETAINED AT THE STORE. RETURN SECOND COPY TO THE OSR TO BE FORWARDED TO THE MECHANICAL ENGINEER. 2 ll Ll I I �\ H. CONTRACTOR SHALL COORDINATE ALL PHASES OF DEMOLITION WITH 11-\ T1 ), , I Q(E)3p " l 1❑N �� II --- - / r+ - - � - - - - - — - — - - - - - — - — - — - - - - - - — - — - — - - — - - - - - - - ARCHITECTURAL DEMOLITION PLANS. ok— I \\\ 5 = I GENERAL NOTES: — , I � �- i I I 3 / III III 1 -- � -- A. PITCH UNDERFLOOR SANITARY WASTE AND STORM PIPING 4"AND GREATER AT 1/8"PER FOOT,UNLESS NOTED OTHERWISE. PITCH ALL OTHER WASTE PIPING AT 1l4"PER FOOT o I I i UNLESS OTHERWISE NOTED. \ 1 ) o " 1❑(E)CO B. PITCH VENT PIPING AT 1/8"PER FOOT TO DRAIN BACK TO WASTE PIPE. _ LJ , ' u 1' r I I I I I 1 C. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"MINIMUM. D. PLUMBING CONTRACTOR SHALL FLUSH OUT ALL PIPING&DRAINAGE SYSTEMS PRIOR TO CONNECTION TO FIXTURES OR EQUIPMENT.REFER TO SPECIFICATION FOR PROPER PROCEDURE. PROCEDURE. E. REFER TO ARCHITECTURAL PLANS FOR TOP OF FLOOR DRAIN ELEVATIONS. - - - - - _ - _ - - - - - - - - - - _ - -� �- - - _ - O L KEY NOTES: I ❑ EXISTING TO REMAIN. Date No. Description 2 1 I 1 REMOVE EXISTING FLOOR DRAIN,FLOOR SINK,HUB DRAIN,OR MOP SINK AND CAP 01/31/2020 BP -3.0 COMPLETE 1 ❑ SANITARY BELOW FLOOR. CONSTRUCTION I 3❑ REMOVE FIXTURE,EQUIPMENT,AND PIPING SHOWN CROSS HATCHED.CAP WATER AND GUEST RESTROOM UNDERFLOOR PLUMBING DEMOLITION PLAN I VENT PIPING AT MAIN.CAP SANITARY UNDERFLOOR. P301 SCALE: 114"=V-0" 0 2' 4' 8' I 1 ® 1/2"COLD WATER LINE TO CLEANING SOLUTION DISPENSER. PROVIDE SHUTOFF VALVE, BACKFLOW PREVENTER AND 3/8"THREADED HOSE CONNECTION AT 5'-0"AFF.SOLUTION DISPENSER AND INSTALATION NIC. ❑ REMOVE EXISTING TRAP PRIMER PIPING IN WALLS.CAP AT MAIN AND UNDERFLOOR. 2 1 I I ABANDON TRAP PRIMER PIPING UNDERFLOOR. © 11/2'VENT DOWN. ❑ 3"VENT UP TO 4"VENT THROUGH ROOF. ' I ' I I I I 1 ® EXISTING CEILING TO BE REMOVED.RAISE EXISTING PIPING AS HIGH AS POSSIBLE. COORDINATE ELEVATION WITH OTHER TRADES. [� V I I 9❑ ROUTE NEW PIPING AS HIGH AS POSSIBLE.COORDINATE ELEVATION WITH OTHER I (E)2"CW 1 —(E)21/2"C (E)2"V xi ' I 10 CONNECT TO EXISTING. FIELD VERIFY EXACT SIZE&LOCATION OF EXISTING. g --�L -= - - — - — - — - — - — - — - — - — - — - - — - L - - - - - - - - - - - - - - g I 11 2"SANITARY PIPE UP. 3 �' 3 \\ i 3"SANITARY PIPE UP. 1 " I � �� 1 13 4"SANITARY PIPE UP. II 1 - - - - - - 4"Sw- - - - - - (EISALES (E)34"HW E)212"CW 1❑ J ® CO 101 1 14 2°VENT PIPE UP. - CO T 15 EXTEND 1/2"COLD WATER AND 1/2"HOT WATER FROM EXISTING PIPING IN WALL TO E3/4CW� _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ �O " q �j�� .. —---------_-- ---.-- -... ___ .- - - . EMERGENCY MIXING VALVE AND EYEWASH PER MANUFACTURER'S INSTALLATION *!�I 1 I o ) INSTRUCTIONS.SET MIXING VALVE TO 90 DEGREES.EXTEND INDIRECT DRAIN THROUGH L°f 21/2 CW r ' I - - - - - - 4"SW- - - - - 4"SW C.O. WALL TO ADJACENT MOP SINK AND TERMINATE WITH CODE COMPLIANT AIR GAP. DROP SANITARY WASTE PIPE IN WALL AND CONNECT TO EXISTING UNDERFLOOR 1) ; I FAM LY RESTROOM 1 t SANITARY WASTE PIPE.FIELD VERIFY LOCATION. E 21/2"V _- _- - (E)1 12"SW } ,`�Z�"�T(E)1 12"V'� 1 (E)CONTROL ROOM I 113 17 314'HOT WATER PIPE DOWN. O - L°f ' 1� I -I t4 1/2 COLD WATER PIPE DOWN. I 11 I FD-1 18 " I 3 13 19 1"COLD WATER PIPE DOWN. 6 co 1-1/4"COLD WATER PIPE DOWN. r W III 1 ) ( I W 1 3 I ( I I MEN \ I .. :=:P. 21 2"COLD WATER PIPE DOWN. WOMEN O t 112 - . 1 111 _Xll . I I - ^SW \ 22 SHUT-OFF VALVE MOUNT INACCESSIBLE LOCATION. oe m I ,2 \ I �� L' I 3 I I I 1 23 WASTE PIPING TO BE INSTALLED ON OUTSIDE EDGE OF CHECK LANES. IT �.(E)1 H� (E)CIRCULATION /87927PE 119 I 24 3"WASTE DOWN.3 I I FD-1 l NPD 1- - '- F1 41 25 4"WASTE DOWN WH e. I _ I 2"S -2 SW AP OFFICE 1❑ (E) (E)1"H �E)?CWj 128 26 CONNECT TO WASTE PIPING FROM SINK ABOVE. 1 I b I \ / _4 13^ ❑ OREGON .V. T �(E)1 1/4"Cb,�/�'� - TJX 7/ i I � - _ 27 BALANCING VALVE,BALANCE TO 2 GPM. ]- _ ASH OFFICE -' ❑ _ --- - -- --- ---- - I 1 . � 28 BALANCING VALVE,BALANCE T01 GPM EXISTING MOP I SINK TO REMAIN /„' / ' -- EXPIRES:0613012020 A - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ` - - - - - A DATE: 01/31/2020 - � ......... — I - 2 1 4 NN L.L 2 GUEST RESTROOM ABOVE FLOOR PLUMBING DEMOLITION PLAN 0 GUEST RESTROOM UNDERFLOOR PLUMBING PLAN O P301 SCALE: 1/4"=V-0” 0 2 4' 8 P301 SCALE: 1/4"=1'-0" 0 2' 4' 8' UJ �W 4 3 2 T ! l 0 co ` (E)COFFEE SEATING �. J N o I 116 I Cy m ti J _I _ 1 8 — - - - - J - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - = =- - - - - - - - - — - - - — - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - --- - --._.� - - - - - - - - - - - — - — - F i r FAMILY,RESTROOM 3H 17 18 16 Z J 8 i WCO F / tt3 1/2"CW (E SALES r - 9 8 1 (E 145 1 O ''�^^ -� vJ 8H -21/2"CW-- ) - ® J - 21/2"CW-- - - - - ' fn �r 6 - = V F 6 3H E 21 f' ------2"V----- - 2"V 22 1 (E)212"CIN (E)CONTROL ROOM 6 18 1 xF Fl-04-1gH 19 - F1 1/2"V I v PO 1 GUEST SERVICE L 26 10 1 1S �� 19 22 IHS 103 17 - ------- ---r 1 1/2"V -3"V--0m---2"V---------- -._ \ 3/4"HW - 1-HW }_ -- -- - �- - -- -- -- - - 1"HW--- .01 1 ;, --3/4"HWR-- --- --T - T-- -- --- -- --- --- --- ---•3/4"HWR---- -- - -- o U 6 F ��� � F � ='� / �l F I � 24 F 6 � 1 ,� _- 1 --- 28 I 3H z . 27 ( ) 1 > 2HS 3H ❑ t7 ❑ - - - - 1U 8 3H E CIRCULATION MEN WOMEN F i p 111 3H I x I v I FLEXIBLE FULFILLMENT _- __- _ 112 AP OFFICE g 6 - l 1S 2S 1 (E)VESTIBULE - - - - 103A 1 JI J F 128 _100 1 \ 3H 6 ' I I (E)CO _. L°f 6 S F 1 CASH OFFICE / ? I F \ F 1 CP 129 F is > 22 1S - I P601 2 1 -. - .......-_.-.-- 1Hs _ - _. -_ t Project Number 6 3H WCO x F i F - I ( 17 I M IHS � :. .:. \ _ � _ .,, I -- ---- -- - -._—- .._-._T ' L..1 ___.. ---------- 1p � -- --� / I `IF - B / j _ 3l4 HW 4"SW WCO 17 i / (E) WH (E)1 H i Config:RR WCO �� ��- 1, _ I •V• F 2 Drawn 15 By M D PLG 13 P601 I U (� --- ........ i° - ----- Checked BY W 4f 4 3 2 1 4 GUEST RESTROOM ABOVE FLOOR PLUMBING PLAN P301 SCALE: 1/4"=V-0" RESTROOM 0 2' 4' 8' PLUMBING PLANS 7 Reterence omy Not part of il�ris pwmit 2/5/2020 1:58:34 PM C D H P3000 UNISTRUT CLIP ENDS TO JOIST B E UP TO EYEWASH JOIST TOP CHORD OR BEAM FLANGE A❑-- G H 3/8"U-BOLT TARGET® —� LONGITUDINAL BRACE KEYNOTES: SUPPLY STOPS PIPE RISER ����� SEE SCHEDULE 1000 N I COLLET MALL MINNEAPOLIS, MN 55403 A❑ MOUNT CIRCULATING PUMP,AQUASTAT,AND SHUTOFF / U 2112"x 2"x 3116'ANGLE, ROOF ROD HANGER& VALVES BELOW CEILING IN ACCESSIBLE LOCATION. X 1/2"MIXED WATER LONG LEG VERTICAL VERTICAL ANGLE © TIMER. (110"F) BRACE,COPE LEG OF ANGLE BEAM ATTACHMENT MICHAEL D. WOEHRLE, P.E. © WIRING FROM PUMP TO TIMER... THERMOSTATIC MIXING VALVE �- 1/8'FILLET WELD 1/2"HOT WATER x 9100 49th Avenue N. WITH INTEGRAL CHECK VALVES AND LOCKING ADJUSTMENT CAP 1/2"COLD WATER 3116"FILLET WELD FOR PIPE SIZE SEE SCHEDULE MINNEAPOLIS, MN 55428 D❑ HOT WATER CIRCULATING PUMP. I REFER TO SPECIFICATIONS. (TYPICAL)ALL-AROUND ❑E CHECK VALVE. TYPICAL. INSTALL IN ACCESSIBLE LOCATION. PIPE CLAMP CALIBRATE MIXED WATER FOUR-WAY BRACE-SEE 3 3/8"EXPANSION ANCHOR Tel: 763 367-7600 TEMPERATURE TO 90"F. (PIPE MUST ROTATE P601 ( ) F❑ EXISTING WATER HEATER 45 (TYPICAL) WITHIN BRACE) Fax: (763) 367-7601 ❑G EXPANSION TANK. a - r FLEXIBLE COUPLING OR NOTE: .. : ' ' ' LONGITUDINAL BRACING AT 80'-0"OC MAX.,UNLESS NOTED. ❑H CONNECT TO EXISTING PIPING WALK VICTAULIC"TYPE COUPLING MAX SPACING FOR 10"AND 12"IS 24'OC. n RISER(S) THIS BRACING DETAIL APPLIES ONLY FOR COLD WATER PIPE&GAS PIPE WHERE SLEEVE MOVEMENT OF THE PIPE DUE TO TEMPERATURE DIFFERENTIAL IS NEGLIGIBLE. NOTE: FLOOR PROVIDE AT ALL SPRINKLER RISERS, WHEN THERMAL EXPANSION OR CONTRACTION IS INVOLVED,PROVIDE LONGITUDINAL BRACES DOMESTIC WATER MAIN RISER,AND AT ANCHOR POINTS. THE LONGITUDINAL BRACES AND THE CONNECTIONS MUST BE CAPABLE OF STORM DRAINS. RESISTING THE FORCE INDUCED BY EXPANSION AND CONTRACTION. HOT WATER CIRCULATING PUMP PIPING THERMOSTATIC MIXING VALVE FOUR-WAY BRACE FOUR-WAY BRACE ELEVATION 0 LONGITUDINAL PIPE BRACING P601 NOT TO SCALE P601 SCALE: NOT TO SCALE P601 SCALE: NOT TO SCALE '601 SCALE: NOT TO SCALEP601 SCALE: NOT TO SCALE PIPE BRACING SCHEDULE PIPE HANGER DIAGONAL BRACE LONGITUDINAL TOP CONN OF ROD MAXIMUM SIZE TYPE &OR VERTICAL BRACE DIAG&LONG SIZE LENGTH ANGLE ANGLES FOR RODS P3000 UNISTRUT CLIP ENDS TO JOIST UP TO CLEVIS 2"X2"X16 GA 21/2"X21/2"X16 GA 1/2"LAG BOLT 1/2" 25" JOIST TOP CHORD FLOOR DRAIN SCHEDULE Date No. Description 2" OR BEAM FLANGE 01/31/2020 BP -3.000MPLETE DRAIN NO. SERVICE WASTE VENT MANUFACTURER MODEL REMARKS CONSTRUCTION 2112" CLEVIS 2"X2"X16 GA 2112"X2112"X16 GA 3/4"MACH BOLT 112" 25" FD 1 GENERAL DRAIN 2",3"OR 4" 1-1/2"OR 2" JOSAM 30000-6S SQUARE STRAINER ADD VERTICAL ANGLE FROM SCHEDULE WHEN 3" CLEVIS 2'X2"X16 GA 2112"X21/2"X16 GA 3/4"MACH BOLT 112" 25' ROD GREATER THAN MAXIMUM ALLOWED. PROVIDE AT 10"AND 12"FOR ALL APPLICATIONS. 3112" CLEVIS 2"X2"X16 GA 21/2"X2112"X16 GA 3/4"MACH BOLT 1/2" 25" HANGER ROD AND ANGLE 4" CLEVIS 2"X2"X16 GA 21/2"X21/2"X16 GA 3/4"MACH BOLT 5/8" 31" SEE SCHEDULE CIRCULATING PUMP SCHEDULE 1/8"GROOVE WELD- 1"LONG/24"OC TOTAL HEAD CONNECTION SIZE(IN) ELECTRIC 5' CLEVIS 2"X2716 GA 21/2"X21/2'X16 GA 3/4"MACH BOLT 5/8' 31" DIAGONAL BRACE PUMP NO. DESCRIPTION LOCATION MANUFACTURER MODEL FLOW(GPM) (FT) RPM IN OUT VOLTAGE PH FLA REMARKS SEE SCHEDULE CP 2 CIRCULATING FLEXIBLE BELL&GOSSETT NBF-22 3.0 10 2940 3/4" 3/4" 115 1 0.80 BRONZE CONSTRUCTION,PROVIDE TIMER FOR PUMP CONTROL 6" CLEVIS 21/2°X21/2"X16 GA 21/2"X21/2"X16 GA 3/4"MACH BOLT 3/4" 37" PIPE SIZE-SEE SCHEDULE PUMP FULFILMENT 8" CLEVIS 2112"X2112"X16 GA 2112"X21/2"X16 GA 3/4"MACH BOLT 718" 43" COPE LEG OF ANGLE 10" CLEVIS 3"X3'X3/16" 3'X373/16" 3/4"MACH BOLT 7/8" N/A HANGER ROD CLIP PLUMBING FIXTURE SCHEDULE 12" CLEVIS 3"X373/16" 3"X3"X3/16" 314"MACH BOLT 718" N/A NOTE: FURNISHED BY INSTALL TRANSVERSE PIPE BRACING ON FIXT NO. TYPE WASTE VENT CW HW CONTR OWNER REMARKS NOTES: 1.SCHEDULE APPLIES TO WATER(&SPRINKLER)PIPES 2"AND LARGER ALL INTERIOR PIPING EXCEEDING 30 FEET F-1HS WATER 4" 2" 11/4" — No Yes M1 WALL HUNG.REFER TO ARCHITECTURAL DRAWING FOR MOUNTING HEIGHT.FLOW RATE: 1.28 GPF.SENSOR-OPERATED 2.SCHEDULE APPLIES TO FUEL(GAS)PIPES V AND LARGER IN LENGTH. MAX SPACING IS 40 FEET OC. CLOSET O 3.SCHEDULE APPLIES TO RWC PIPES 10"AND LARGER MAX SPACING FOR 10"AND 12"IS 12 FEET OC. F-1S WATER 4' 2' 11/4' — No Yes M1 WALL HUNG.REFER TO ARCHITECTURAL DRAWING FOR MOUNTING HEIGHT.FLOW RATE: 1.28 GPF.SENSOR-OPERATED CLOSET � /+ SF-2HS URINAL 2" 11/2' 1" — No Yes M1 WALL HUNG. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT.FLOW RATE:0.125 GPF. SENSOR-OPERATED 6� PIPE BRAKING SCHEDULE �7] TRANSVERSE PIPE BRACING F-2S URINAL 2" 11/7' 1 1" — No Yes M1 WALL HUNG. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT.FLOW RATE:0.125 GPF, SENSOR-OPERATED P601 SCALE: NOT TO SCALEP601 SCALE: NOT TO SCALE F-311 LAVATORY 11/2" 11/2" 112" 1/2" No Yes M1 WALL HUNG. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT. PROVIDE 0.5 GPM AERATOR AND CHROME PLATED P-TRAP AND ANGLED SUPPLIES WITH LOOSE KEY STOPS.FLOW RATE:0.5 GPM. SENSOR-OPERATED F-8 ELEC WATER 11/2" 11/2" 112" — No Yes WALL HUNG.REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT. COOLER F-8H ELEC WATER 11/2" 1 112" 112" — No Yes WALL HUNG.REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT. COOLER F-13 EMERGENCY 11/2" 11/2" 1/2" 112" Yes No PROVIDE EMERGENCY THERMOSTATIC MIXING VALVE AND SET TO 90 DRGREES FAHRENHEIT. EYEWASH PLUMBING EQUIPMENT RESPONSIBILITY MATRIX TESTING& ELECTRICAL EQUIPMENT DELIVERY SCHEDULE BALANCING OF EQUIPMENT SPECIFIED MFR FURNISH BY INSTALL BY CONNECTION START UP COORDINATION EQUIPMENT REMARKS CIRCULATING PUMP CP-1 BELL&GOSSETT PLBG CONTR PLBG CONTR ELEC PLBG CONTR PLBG CONTR PLBG CONTR PLUMBING FIXTURES F1HS THRU F3HS,F-8&F-811 VARIES OWNER PLBG CONTR ELEC IF POWER PLBG CONTR PLBG CONTR PLBG CONTR M1 ®1 REQ'D PLUMBING FIXTURES F-13 VARIES PLBG CONTR PLBG CONTR ELEC PLBG CONTR PLBG CONTR PLBG CONTR ,aFD PR G I Nee1p % 87927PE OREGON (E)4'SW EXPIRES:0613012020 DATE: 01/31/2020 S O 1t� 4"VENT THROUGH ROOF UJ w I fl C.O. ; ; ; CO //���/// m N 4"SW i i SHUT OFF v RC II VALVE rn If v ' II . II 1112"V II 1"CWS SHUT OFF VALVE T O 1"CW ii jl li ii II C.O.1. � 3/4"HW \,•• ii ii it li + —1 1/2"V 3'V ii II II 3/4"HWR 21/2'CW O I I I 11/2"V 4'SW .0 I I 1 F U) I I 1 1 {�--i �1 112'V •.• 3/4 CW ii ii 1 I I�11/2'V ii II 11/2"V 1/2"CW 8 �II ,•� ;, ATYPICAL OF 5 11/2"V Ij n li II ii ii �� 2"CW +•• p \ O I 1 � �'2"V� _ 1112"VII ('� C.O. I I II I I •/ T • • 8H ii3"V II �yS a ? 11/4"CW 11'HW SHUT OFF VALVE SW i i 1 1/2'y �"V'` 1 112"V "• 4 HW TYPICAL OF 9 SHUT OFF VALVE,MOUNT IN 3'SW I I 1 ., 1 1/2"SW 4"SW ' I C` F '?� �' " ACCESSIBLE LOCATION.TYPICAL. TYPICAL OF 5 II I ., "o F � � � 3"SW 3HS PD-1 ��� i ii Qr jj ii 1/2"HW 3HS o J� �1 j 1/2"HW W.C.O. TYPICAL 2" `` II ii ii 1+1 112"V TYPICAL OF S TYPICAL 1S 2"CW H �. U) 41S II a 11 n II OF 5 ( 1"CW TYPICAL 9 ii 1 11 ii i TYPICAL �1 /I I l % • kF OF 5 1 111 112"V OF 5 J � Jj \ ii SHUT OFF +• 1/2'CW \2"CW F i111 F f v F F 2HS Ij II II �I�I 2"� t F 2HS VALVE _y IJ_J1, II ii ii FD-1 IIII lfl l� ii 1HS 4"SW - 2S i i 2. a A� yg II �, ii I-1 1/2 V 4"SW i� � � � I � ` 1 1/4"CW � C� ii 1112"V II J_ � 3HS W.C.O. �� 1 112"V II I 1 3HS <" p "�� 1/2"HW „ 1S �� TYPICAL OF 3 F I u i i i i C.O. F ., ••• 1HS II "> til �� 1HS f t 1"HW�` � Project Number FD-1 F S F 3HS F i! T-0345 2" 3HS 1HS .. SW � 1HS ��., 3/4 HWR TYPICAL OF 3 I I TYPICAL OF 3 1/2"CW Config:RR 1 112"SW 4"SW 2"SW TYPICAL OF 3 TYPICAL OF 3 W.C.O. 3"SW 2"SW Drawn By PLG Checked By MDW RESTROOM WASTE AND VENT RISER DIAGRAM rq_"� RESTROOM DOMESTIC WATER RISER DIAGRAM PLUMBING P601 NOT TO SCALE '601 NOT TO SCALE SCHEDULES, DETAILS AND RISERS Reference ol* Not paft Of this Permit P601 2/5/2020 1:58:51 PM HVAC SYMBOLS PLUMBING / PIPING SYMBOLS SHEETINDEX PIPE HANGER SCHEDULE TYPE "H-1 " HANGERS DOUBLE LINE DRAWINGPM01 MECHANICAL SHEET INDEX WATER,WASTE, GAS, RWC,AND FIRE PROTECTION PIPING ITEM INDICATED REPRESENTATION SYMBOL DESCRIPTION P301 RESTROOM PLUMBING PLANS PIPE HANGER Sch Sch THREADED GROOVED TYPE L PVC/ I I P601 PLUMBING SCHEDULES, DETAILS AND RISERS SIZE SPACING 40 10 LIGHT WALL LIGHT WALL COPPER ABS ROOF DECK M301 GUEST SERVICE,OPU STORAGE,&RESTROOMS HVAC PLAN DUCT (1st FIGURE-SIDE SHOWN 24x20 ®° LAVATORY(MULTI-STATION NOT SHOWN) TARGET® 1" 8'-0"OR LESS H-1 H-1 H-1 H-1 H-3 H-1 2nd FIGURE-SIDE NOT 12-0" H-1 H-1 H-1 H-1 N/A NIA SHOWN) 1 10'-0"OR LESS H-1 H-1 H-1 H-1 H-3 H-1 � WATER CLOSET 1000 NICOLLET MALL a P1346 UNISTRUT HANGER 24x12 P4"q URINAL MINNEAPOLIS, MN 55403 12'-0" H-1 H-1 H-1 H-1 N/A N/A DUCT SECTION (SUPPLY) ID MICHAEL D. WOEHRLE P.E. 15'-0" H-1 H-1 N/A H-1 NIA N/A BEYOND W/(2)-1/2"X 2'LAG SCREW 2" 10'-0"OR LESS H-1 H-1 H-1 H-1 H-3 H-1 OR ITW BUILDEX SAMMYS SINK 12'-0" H-1 H-1 H-1 H-1 N/A N/A PURLIN SWG-25-380'SIDEWINDERS" DUCT SECTION EE 24x12 24'0 FOR WOOD. (RETURN) 9100 49th Avenue N. 15'-0" H-1 H-1 N/AH-1 H-1 N/AH-3 N-1 FOTHREADEDROD,MIN. JANITORS SINK MINNEAPOLIS, MN 55428 2 9'-0"OR LESS H•1 H-1 H-1 H-1 H-3 H-1 IT-0" H-1 H-1 H-1 H-1 N/A N/A SUPPLY DUCT TURNING TURNING 24,0 DOWN a ELECTRIC WATER COOLER Tel: 763 367-7600 15'-0" H-1 H-1 N/A H-1 N/A N/A TURNING UP OR DOWN UP Fax: 367-7601 3^ 10'-0"OR LESS N/A H-1 H-1 H-1 H-3 H-1 12'-0" N/A H-1 H-1 H-1 N/A N/A O HUB DRAIN RETURN DUCT TURNING TURNING 240 DOWN 15'-0" N/A H-3 N/A H-1 N/A N/A SWIVEL RING TURNING UP OR DOWN UP FLOOR DRAIN 4" 4'-0" N/A H-1 N/A H-1 H-3 H-1 8'-0" N/A H-1 N/A H-1 H-3 N/A TURNING TURNING ® FLOOR SINK EXHAUST DUCT 24"0 DOWN 10'-0" NIA H-3 N/A H-1 H-3 N/ALi UP TURNING UP OR DOWN 12'-0" N/A H-3 NIA H-1 N/A NIA ROOF DRAIN 15'-0" NIA H-3 N/A H-1 N/A N/A 6" 4'-0" N/A H-1 N/A H-1 N/A H-1 EXHAUST DUCT TURNING TURN -ING 01 CLEAN OUT TURNING UP OR DOWN UP 24"0 I DOWN 8'-0" NIA H-3 N/A H-1 N/A N/A 10'-0" N/A H-3 N/A H-1 NIA NIA FUNNEL DRAIN 12'-0' N/A H-3 N/A H-1 N/A N/A INCLINED RISE(R)OR DROP(D) 15'-0" NIA H-3 N/A H-1 N/A N/A REFER TO PLANS FOR BOD HEIGHTS ISI VENT THROUGH ROOF 8" 4'-0" N/A H-3 N/A N/A N/A H-1 WALL HYDRANT/INSIDE HOSE BIBB 8'-0" NIA H-3 N/A qN/AN/A /A N/A 10'-0" N/A H-3 N/A /A N/A 20x12 24x12 n GAS SHUTOFF VALVE ECCENTRIC DUCT FITTING 12'-0" N/A H-3 N/A /A N/A —���� PRESSURE REGULATOR 15'-0" N/A H-3 N/A NIA 10" 4'-0" N/A H-3 N/A IA H-1 INV.EL.X INVERT ELEVATION TAGDate No. Descri tlOrl12"+ 4'-0" NIA H-3 N/A /A H-3 CONCENTRIC DUCT FITTING 20x12 24x12 BOD X BOTTOM OF DUCT ELEVATION TAG 01/31/2020 BP -3.0 COMPLETE REFER TO SPECIFICATION FOR MAXIMUM ALLOWABLE HANGER SPACING FOR ROOF DECK CONSTRUCTION TYPE L COPPER AND PVC/ABS PIPING. + TOP CONNECTION N/A=NOT ALLOWED OR NOT APPLICABLE BALANCING P1346 UNISTRUT HANGER � � (2)-#12x1 "SCREWS,TYP. BRANCH DUCT TAKE-OFF jrDAMPER BOTTOM CONNECTION W/2-1/2'X 2"LAG SCREW OR ITW BUILDEX SAMMYS PURLIN GENERAL NOTES: USING RECTANGULAR SWG-25-380"SIDEWINDERS" � DROP IN DIRECTION OF FLOW DUCTWORK MAIN FOR WOOD,TYP. STRAP HANGER A. THIS PIPE HANGER SCHEDULE SHOWS MAXIMUM ALLOWABLE HANGER SPACING BASED ON 12x10 PIPE WEIGHT AND STRUCTURAL CONSTRAINTS. REFER TO SPECIFICATION SECTION"BASIC MECHANICAL MATERIALS AND METHODS"FOR ADDITIONAL PIPE HANGER REQUIREMENTS RISE IN DIRECTION OF FLOW PURLIN INCLUDING REQUIRED HANGER ROD DIAMETER AND MAXIMUM HANGER SPACING BASED 3/8"THREADED ROD,MIN SCREW STRAP TO DUCT. ON PIPE MATERIAL AND PIPE DIAMETER. SHUTOFF VALVE W/NUTS AND WASHERS MINIMUM 1"STRAP LENGTH ON UNDERSIDE OF DUCT. B. LOCATE TOP OF PIPE AT 4"MINIMUM BELOW ROOF DECK. 1 J� DUCT WIDTHS C. FIRE PROTECTION SPRINKLER PIPING SUPPORT SHALL COMPLY WITH REQUIREMENTS OF POWER ROOF VENTILATOR 1 WAFER CHECK VALVE P3000 UNISTRUT J DUCT WIDTHS LESS THAN 36" NFPA AND LOCAL CODE AUTHORITIES. \ 36"OR GREATER ROOF DECK D. DO NOT DEVIATE FROM PIPE HANGER DETAILS AS SHOWN. T b STRAINER (2)-#12x1 "SCREWS,TYP. DIFFUSER C 12" r, � (2)-#12x1 "SCREWS,TYP. 500 � UNION PURLIN DESCRIPTION C: REFERS TO TYPE PURLIN 12": NECK SIZE(SO OR RD) ^�� SWING CHECK VALVE 500: CFM STRAP HANGER (REFER TO M301 FOR DIFFUSER TYPE) FILTERED COLD WATER ROD HANGER OR TYPE "H-3" HANGER ROOF DECK SUPPLY, RETURN OR EXHAUST 18 EYE STRAP HANGER REGISTER H COLD WATER BAND SAME SIZE 200 AS STRAP HANGER 36"MAXIMUM GREATER THAN DESCRIPTION 1 REFERS TO TYPE HW - HOT WATER DUCT DIAMETER 36'DUCT DIAMETER 12x8: REGISTER SIZE 200: CFM Q (REFER TO M301 �R RECIRCULATING HOT WATER FOR REGISTER TYPE) GENERAL NOTES: g (E)SUB PURLIN S N' LIQUEFIED PETROLEUM A. REFER TO"SMACNA HVAC DUCT CONSTRUCTION STANDARDS"FOR HANGER REQUIREMENTS, CEILING RETURN GRILLE INCLUDING SIZES OF STRAP HANGERS,ROD HANGERS, STEEL ANGLES,AND FASTENERS, DESCRIPTION F: REFERS TO TYPE - - - - - - V - - - - - - VENT B. SUPPORT HANGER FROM PURLIN. DO NOT HANG FROM SUB-PURLINS. P1346 UNISTRUT ANGLE W/ 2412: GRILLE SIZE C. MAXIMUM LOAD FROM ANY HANGER IS 100 LBS, UNLESS APPROVED BY THE STRUCTURAL (2)- "1x2"LAG SCREWS TO (REFER TO M301 24x12 SEI STORM DRAIN ENGINEER. HANGER LOADS TO BE LOCATED 6"-0"FROM ANY OTHER HANGING LOAD. (E)PURLIN PURLIN,OR ITW BUILDEX SAMMYS FOR GRILLE TYPE) F D. PURLIN=3"X 14'OR LARGER SWG-10"SIDEWINDERS"FOR WOOD,TYP. CD CONDENSATE DRAIN SUB-PURLIN=2"X4" OR 2"X6" TRANSFER GRILLE 8 10"0 DUCTWORK 4 DUCT HANGERS THREADED ROD, MIN. 24x6 W/NUTS AND WASHERS,TYP. DESCRIPTION F: REFERS TO TYPE T/A F NATURAL GAS 24x6: GRILLE SIZE F 24x6 TIA: TRANSFER AIR T/A �— - —GW PM01 NOT TO SCALE (REFER TO M301 SQUARE TO GREASE WASTE FOR GRILLE TYPE) ROUND ADAPTER - —CWV— - COMBINATION WASTE&VENT �`���Go N EF 'o TRANSFER GRILLE& P3001 UNISTRUT DUCTWORK - —SW— - SANITARY WASTE Q� � 87927PE � DESCRIPTION 22'0 F: REFERS TO TYPE 2424: GRILLE SIZE YAG CONDENSATE VACUUM NOTE:DO NOT HANG TIA: TRANSFER AIR FROM SUB-PURLIN THREADED ROD (REFER TO M301 F F ;] SEE PLANS FOR HANGER WITH FOR GRILLE TYPE) 2T/A4 2T A4 SEE PLANS FOR OREGON REVERSE OSMOSIS FILTERED COLD WATER SWIVEL RING NECK SIZE NECK SIZE 6'-0"MIN&10'-0"MAX LINEAR SLOT DIFFUSER FLEXIBLE DUCT IRR SITE IRRIGATION 9 IE WITH BOOT DESCRIPTION K: DIFFUSER TYPE X PIPE ANCHOR EXPIRES:06/3012020 8": BOOT NECK SIZE 1.0": SLOT WIDTH PIPE BREAK 1 PIPE HANGER DETAILS - WOOD STRUCTURE 330: CFM 8"-10" (REFER TO M301 K GRILLE OR DATE: 01/31/2020 PM01 NOT TO SCALE FOR DIFFUSER TYPE) 330 CONNECT TO EXISTING OR SYSTEMS PROVIDED BY NIC. REGISTER - GRILLE OR BELOW REGISTER 3-5 DUCT DIAMETERS SIZED TO 12x12,2424 OR 6x24 OR 12x24 BELOW JOIST � 18.0 BOX INLET,TYPICAL O OWNER FURNISHED EQUIPMENT SYMBOL 24"x48"(18"x30"NECK) A VARIABLE AIR VOLUME BOX REFER TO SHEET A601 FOR EQUIPMENT NOTE: A INFORMATION MAXIMUM OF 18"OF FLEX DUCT MAY BE USED FOR FINAL CONNECTION.SALES FLOOR (SIZE AND SHAPE OF BOX WILL VARY) BOOTS ARE OWNER PROVIDED,ALL OTHERS ARE CONTRACTOR PROVIDED. A A BEAM 18'0 XD XI P PLUMBING DRAIN TAG O 3-5 DUCT DIAMETERS SIZED TO BOX INLET,TYPICAL �5 GRILLE & REGISTER BOOT FAN POWERED VARIABLE AIR VOLUME BOX FLEXIBLE CONNECTOR PM01 NOT TO SCALE BEAM CLAMP (SIZE AND SHAPE OF BOX WILL VARY) 18'0 MECHANICAL SYMBOLS w THRU BOLT BETWEEN JOIST BOTTOM DIAGONAL ANGLE SYMBOL DESCRIPTION CHORD ANGLES.SECURE TIGHT WITH DOUBLE NUT. TYP OF 2 18"0 Q / M BOLT THROUGH ANGLE PIPE H ER �_ M DIAGONAL ANGLE AND PIPE CLAMP SEE 1 2 SMOKE DAMPER LJJ TYP OF 2 PIPE INSULATION PM01 PM01 UNIT HEATER As BOLT THROUGH ANGLE PIPE H GER �� SECTION VIEW /�� AND PIPE CLAMP SEE / r \ �J FIRE DAMPER J 1 2 V / J n/ PIPE INSULATION �� PM01 PM01 PIPE-EJ.EVATL4N- — v ' LL MAY VARY THERMOSTAT OR TEMPERATURE SENSOR D BALANCING DAMPER POWER ROOF Q O VENTILATOR PIPE FL�YAll4N- — TEMPERATURE&HUMIDITY SENSOR TH MOTORIZED DAMPER z Q MAY VARY DOMESTIC WATER PIPE. - - - SEE ARCH FOR SEE PLANS FOR SIZE. O CURB AND FLASHING O BEAM CLAMP ANGLE TO DUCT STATIC PRESSURE SENSOR G PIPE CLAMP WITH NEOPRENE EXISTING BEAM. GRAVITY DAMPER � ) DOMESTIC WATER PIPE. - - SCRAPE AND REPAIR ROOF C ) SEE PLANS FOR SIZE. JOIST BOTTOM GASKET SECURED TIGHT TO CHORD ANGLES � FIRE PROOFING AT PIPE. RUN PIPE INSULATION C COMBINATION FIRE/SMOKE DAMPER '^ PIPE CLAMP WITH NEOPRENE CONNECTION. "� `J � OVER PIPE CLAMP. DIAGONAL 111 1 O GASKET SECURED TIGHT TO T -F} > i DOOR UNDER CUT PIPE. RUN PIPE INSULATION ANGLE i � i GRAVITY BACK-DRAFT OVER PIPE CLAMP. SECTION VIEW DOMESTIC SECTION VIEW DAMPER z WATER PIPE DOMESTIC _ _ BEAM CLAMP TO FIRE PROTECTION SYMBOLS SEE SPECIFICATION. WATER PIPE SECTION CUT A-A � EXTERNAL INSULATION. SECTION CUT A-A BOTTOM OF EXISTING THROUGH BEAM THRU BOLT THROUGH JOIST BEAM. SCRAPE AND ANGLE BETWEEN JOIST REPAIR FIRE SYMBOL DESCRIPTION SEAL INSIDE DRIP AN BOTTOM CHORD PROOFING AT BEAM 2"DEER IWATERGHT ITIGHT TH MASTIC ' CLAMP. 2"DEEP DRIP PAN v J ANGLES.TYP. Q DIAGONAL IN DIAGONAL F FIRE PROTECTION PIPING ANGLE ANGLE TYPOF2 TYP0P2 I I s DUCTED POWER ROOF VENTILATOR 30 DEGREE MIN 60 30 DEGREE MIN INSPECTORS TEST CONNECTION PM01 NOT TO SCALE DEGREE MAX 60 DEGREE MAX PIPE 1 UJ PIPE CLAMP PIPE CLAMP NOTE: NOT ALL SYMBOLS MAY APPEAR ON DRAWINGS. SECURED SECURED INSULATION TIGHT TO PIPE. TIGHT TO PIPE. K O ^ JOIST BOTTOM - O TIGHT BOTTOM PIPE. - O GALVANIZED Project Number `{J CHORD ANGLES JOIST OF BEAM BEAM STEEL SHIELD TYP PARALLEL TO JOISTS PERPENDICULAR TO JOISTS PARALLEL TO BEAMS PERPENDICULAR TO BEAMS Config:RR PLAN VIEW PLAN VIEW NOTES: NOTES: PIPE RING HANGER HIGH DENSITY CLEVIS HANGER Drawn By PLG • THIS BRACING DETAIL APPLIES ONLY FOR DOMESTIC WATER PIPE TO REDUCE PIPE MOVEMENT • THIS BRACING DETAIL APPLIES ONLY FOR DOMESTIC WATER PIPE TO REDUCE PIPE MOVEMENT INSULATION DURING WATER USAGE. DURING WATER USAGE. INSTERT OR Checked By M DW • THIS BRACING DOES NOT REPLACE PIPE HANGERS. • THIS BRACING DOES NOT REPLACE PIPE HANGERS. WOOD BLOCK • INSTALL DOMESTIC WATER PIPE ANCHORS WHERE SHOWN ON DRAWINGS. • INSTALL DOMESTIC WATER PIPE ANCHORS WHERE SHOWN ON DRAWINGS. SEE SPECIFICATIONS CONSULTANT QUALITY ASSURANCE REVIEW CONFIRMATION STAMP 2 DOMESTIC WATER PIPE ANCHOR DETAIL - JOIST AND BEAM CONSTRUCTION INSULATED PIPE AT HANGER DETAIL DOCUMENTS REVIEWED BY:ERIC NEBELUNG PM01 NOT TO SCALE PM01 NOT TO SCALE REVIEWERS PHONE:763-367-7600 MECHANICAL SHEET REVIEWERS E-MAIL: ERIC.NEBELUNG@NELSONRUDIE.COM INDEX DATE REVIEWED:01/27/2020 Pmou- 2/5/2020 1:58:55 PM