ELC2021 - 00630 ELECTRICAL SPECIFICATIONS SYMBOL LEGEND RECEIVED GENERAL: LIGHTING: SEE FIXTURE SCHEDULE 6.3. LISTING AS EQUAL DOES NOT RELIEVE THE MANUFACTURER FROM MEETING THE REQUIREMENTS OF THE OCT ? 5 7,021 1.1. ALL ELECTRICAL WORK SHALL COMPLY WITH ALL APPLICABLE CITY, COUNTY, STATE, AND SERVING ELECTRICAL CONTRACT DOCUMENTS. O DOWNLIGHT FIXTURE - SURFACE OR PENDANT UTILITY CODES, ORDINANCES, RULES, AND REGULATIONS AND THE LATEST ADDITION OF THE NATIONAL LIGHTING: 11 DOWNLIGHT FIXTURE - CEILING RECESS VI I I Ur I IUAHD ELECTRICAL CODE. h BUILDING DIVISION li! WALL MOUNTED FIXTURE 1.2. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE A.D.AA.G. (AMERICANS WITH DISABILITIES ACT 7.1. VERIFY ALL CEILING TYPES WITH CEILING CONTRACTOR AND ORDER CORRECT LIGHTING FIMRE FOR COLING S E A ACCESSIBILITY GUIDELINES) BEING INSTALLED. VERIFY RECESSING DEPTHS OF ALL FIXTURES PRIOR TO ORDERING. ® 1-0 EXIT LIGHT FIXTURE - SEE SCHEDULE FOR MOUNTING ® 1.3. 1.3 FIELD COORDINATE LOCATION OF LIGHTING AND POWER OUTLETS IN ALL MECHANICAL, ELECTRICAL, AND 7.2. FLUORESCENT EMERGENCY LIGHTING FIXTURES, SHOWN SHADED OR NOTED ON THE LUMINAIRE SCHEDULE, SHALL LIGHT FIXTURE - PENDENT OR SURFACE SCOTT I EDWARDS ARCHITECTURE LLP • EQUIPMENT ROOMS WITH DUCTWORK, PIPING, AND EQUIPMENT LOCATIONS. ELECTRICAL CONTRACTOR SHALL BE PROVIDED WITH A BATTERY PACK TO OPERATE TWO LAMPS FOR A TOTAL OUTPUT OF 1400 LUMENS, MOUNT LIGHT FIXTURE - CEILING RECESS IN FIXTURE WIREWAY. FIXTURE AND LAMPS SHALL BE SWITCH ABLE, UNLESS NOTED OTHERWISE, WITH A HOT 2525 E. Burnside St., Portland, OR 97214 COORDINATE THE LOCATION OF ALL ELECTRICAL DEVICES AND EQUIPMENT CONNECTIONS WITH IONS.ARCHITECTURAL, REFERENCE CIRCUIT TO THE BATTERY PACK. PROVIDE ALL REQUIRED PARTS AND ACCESSORIES, INCLUDING O� phOne:(503) 226-3617 www.seallp.COm STRUCTURAL, MECHANICAL AND OTHER TRADES TO AVOID CONFLICTS WITH HEIGHTS AND LOCATIONS. ® EMERGENCY AND/OR N.L. (NIGHT LIGHT) FIXTURE C INDICATOR LIGHT AND TEST SWITCH, DO NOT ENERGIZE BATTERY PACK UNTIL 24 HOURS PRIOR TO FINAL 1.4. ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF NEW RACEWAYS AND EQUIPMENT SHALL BE THE INSPECTION TO AVOID DESTROYING THE BATTERY DURING CONSTRUCTION. E:3 BATTERY OPERATED EMERGENCY LIGHT I{'�! C RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. ALL WORK SHALL BE PERFORMED BY A TRADESMAN WIRING DEVICES, PANELS AND RACEWAYS O+ " EXPERIENCED IN THE WORK REQUIRED. ALL FINISHES SHALL MATCH EXISTING ADJACENT FINISHES. PATCH ALL 7.3. EMERGENCY LIGHTS SHALL BE POWERED FROM A LOCAL LIGHTING CIRCUIT. PROVIDE UNSWITCHED HOT OPENINGS IN FIRE RATED WALLS IN A MANNER MAINTAINING THE ORIGINAL FIRE AND SMOKE RATINGS. REFERENCE CIRCUIT TO FIXTURES OR FIXTURE POWER PACK. LUMINAIRES MARKED WITH "NL" SHALL BE SINGLE POLE SWITCH UNSWITCHED FOR NIGHT LIGHT OPERATION UNLESS "NL" FIXTURES ARE SHOWN TO BE DIMMABLE WITH MINIMAL OCCUPANCY SENSOR SWITCH '-yI Ep PRO 1.5. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF DIMMABLE LEVEL DOWN TO FOOTCANDLE LEVEL AS REQUIRED TO COMPLY WITH IBC REQUIRED MINIMUM PATH ® ,` ELECTRICAL WORK THAT IS OUTSIDE OF THE CONTRACT LIMITS OF CONSTRUCTION. OF EGRESS LIGHTING LEVEL. $3 THREE WAY SWITCH WITH IDENTIFICATION LETTER SWITCH MOUNTING HEIGHT - 48" AFF. TO CENTER 1.6. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY LOSS OR DAMAGE CAUSED BY HIM OR HIS WORKMEN TO THE 7.4. EXIT SIGNS SHALL BE POWERED FROM A LOCAL LIGHTING CIRCUIT. PROVIDE UNSWITCHED HOT REFERENCE SINGLE CONVENIENCE OUTLET- MOUNT 18" AFF. TO CENTER 73416PE 9� FACILITY DURING THE COURSE OF CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING OR CIRCUIT TO FIXTURES. EXIT FIXTURE CHEVRON DIRECTION(S). WHERE SHOWN ON PLAN OR REQUIRED TO REPLACING SUCH LOSS OR DAMAGE AT NO ADDITIONAL COST TO THE OWNER. COMPLY WITH PATH OF EGRESS, SHALL BE PROVIDED ON EXIT FIXTURES. FIELD COORDINATE DIRECTIONAL DUPLEX CONVENIENCE OUTLET- MOUNT 18" AFF. TO CENTER ARROWS IN FIELD AS REQUIRED, NY 1.7. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND CANNOT SHOW EVERY CONNECTION, JUNCTION BOX, WIRE, DOUBLE DUPLEX CONVENIENCE OUTLET- MOUNT 18" AFF. TO CENTER CONDUIT, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE AND FUNCTIONAL 7.5. COORDINATE WITH CEILING CONTRACTOR FOR FIRE RATED ENCLOSURES AT LIGHT FIXTURES WHERE REQUIRED. ,,yy,ELECTRICAL SYSTEM. FIRE RATING PROVISIONS SHALL BE BY CEILING CONTRACTOR UNLESS NOTED OTHERWISE. ELECTRICAL W DUPLEX CONVENIENCE OUTLET- MOUNT 6" ABV COUNTER TO CENTER1.8. NO DESIGN CHANGES SHALL BE MADE TO THE ELECTRICAL SYSTEM WITHOUT THE PRIOR APPROVAL OF THE CONTRACTOR SHALL COORDINATE WITH CEILING CONTRACTOR TO PROVIDE SUPPORT WIRES FOR LUMINAIRES (TWO 0 SWITCHED DUPLEX CONVENIENCE OUTLET- MOUNT 18" AFF. TO CENTER PER LUMINAIRE). ELECTRICAL ENGINEER AND THE ELECTRICAL INSPECTOR. DUPLEX CONVENIENCE OUTLET- MOUNT AT CEILING OR ABOVE WINDOW SCOPE OF WORK EQUIPMENT: p FLOOR TYPE SERVICE FITTING WITH INDICATED DEVICES RENEWAL DATE: 12/31/2022 2.1. FURNISH ALL MATERIALS. TOOLS, AND LABOR AND PAY ALL PERMITS AND FEES REQUIRED FOR THE ELECTRICAL 8.1. ALL ELECTRICAL COMPONENTS INSTALLED OUTDOORS, EXPOSED TO WEATHER, OR IN DAMP LOCATIONS SHALL BE GROUND FAULT INTERRUPTER RECEPTACLE- MOUNT 18" AFF. TO INSTALLATION UNLESS OTHERWISE NOTED ON PLANS. ALL PERMITS AND INSPECTIONS SHALL BE PROVIDED AS WEATHERPROOF, NEMA 3R. CENTER OR 6" ABV LAV TO CENTER WHERE APPROPRIATE. REQUIRED BY THE LOCAL CODE AUTHORITY. 8.2. THE SERVICE ENTRANCE ASSEMBLY AND ALL OF ITS COMPONENTS SHALL BE BRACED TO WITHSTAND A MINIMUM ®A SPECIAL OUTLET WITH IDENTIFICATION, SEE SCHEDULE OR NOTE OF 100% OF AVAILABLE FAULT CURRENT SUPPLIED BY THE POWER COMPANY AND SHALL BE SUPPLIED WITH 2.2. ALL MATERIALS SHALL BE NEW. OF FIRST CLASS QUALITY, SHALL BE U.L. LISTED AND LABELED, AND FREE OF COPPER BUSS. DEFECTS. G BRANCH CIRCUIT PANELBOARD 8.3. PROVIDE AT THE COMPLETION OF THE PROJECT NEATLY TYPED ACCURATE PANEL BOARD DIRECTORIES INDICATING ------ CONDUIT - UNDER FLOOR OR UNDER GROUND 2.3. VERIFY AND COORDINATE THE FOLLOWING WITH THE MECHANICAL CONTRACTOR: ALL BRANCH CIRCUITS AND SPARES. ALL SPARES SHALL BE LEFT IN THE OFF POSITION. ZOOMOCd rv• 2.3.A. LOCATION Of EQUIPMENT; E.G. MOTORS, HEATERS, T-STATS, ETC. 8.4. PROVIDE A 120 VOLT, 20 AMP, WEATHERPROOF GFCI RECEPTACLE WITHIN 25 FEET AND ACCESSIBLE TO ALL f- HOME RUN TO PANEL INDICATED MECHANICAL EQUIPMENT. - - 2.3.6. EQUIPMENT ELECTRICAL CHARACTERISTICS; E.G. VOLTAGE, PHASE, HP, AMPS, CONTROL WIRING, ETC. #10 WIRING DESIGNATIONS, LONG SLASH IS NEUTRAL THIS AREA OF WORK 8.5. LABEL ALL PANEL BOARDS, AND MAJOR SINGLE LINE COMPONENTS WITH PERMANENTLY AFFIXES PHENOLICHiiWIRE, SHORT SLASH PHASE WIRE, SLASH WITH DOT IS F__�_____________________ BILLING & HELP . 2.4. ACQUIRE THE NUMBER OF COMPLETE SETS OF CONTRACT DRAWINGS AND FURNISH SETS TO THE TELEPHONE LETTERING (1' MINIMUM) GROUND WIRE. N10 INDICATES AWG WIRE SIZE. AND ELECTRICAL POWER UTILITIES FOR UTILITY DESIGN AND COORDINATION AS REQUIRED BY EACH UTILITY. _ ' FIVI CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMISSION OF ALL PLANS AND PERMITS REQUIRED TO THE UTILITY ❑' DISCONNECT SWITCH WITH SIZE AND TYPE INDICATED - OFFICE SPACE COMPANY(IES). 8.6. DO NOT MOUNT OUTLET BOXES BACK TO BACK. PROVIDE A MINIMUM 16" OF SEPARATION UNLESS SEPARATED BY A STUD. AUXILIARY SYSTEMS _ ; 2.5. INCLUDE ALL CHARGES THAT MAY APPLY FROM THE POWER, TELEPHONE AND OTHER UTILITY COMPANIES. ® COMBINATION TELEPHONE/DATA OUTLET- MOUNT 18" AFF. PROVIDE ALL WORK REQUIRED FOR THE INSTALLATION OF UTILITY SERVICES. 8.7. PANEL BOARDS SHALL HAVE COPPER BUS, WITH FULL NEUTRAL AND GROUND BUSSES. MINIMUM AIC RATING _ - -- SHALL BE 10,000 AMPS. PANELS SHALL HAVE LOCKING DOORS WITH MATCHING KEYS. PANELS SHALL BE D TELEPHONE OUTLET- MOUNT 18" AFF. •' == EXIST. ELECTRICAL RM. 2.6. FULLY GUARANTEE THE INSTALLATION FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY MANUFACTURED BY SQUARE "D", CUTLER HAMMER, OR SIEMENS. LOAD CENTERS ARE NOT ACCEPTABLE. 11958 SW Garden Place THE OWNER, AGAINST ANY IMPERFECT WORKMANSHIP AND MALFUNCTION OF EQUIPMENT. ANY WORK IDENTIFIED R D POWER/DATA POLE (UNLESS NOTED OTHERWISE) __ TO BE DEFECTIVE WITHIN THE GUARANTEE PERIOD SHALL BE PROMPTLY REPAIRED OR REPLACED AT NO 8.8. ALL BRANCH CIRCUIT PANEL BOXES SHALL BE MINIMUM 5-3/4" DEEP AND 20" WIDE. PROVIDE MOUNTING P 0 POWER/DATA WALL FEED F�jIS ADDITIONAL COST TO THE OWNER. HARDWARE IN ALL SPACES FOR FUTURE DEVICES, ALL RECESSED PANELS SHALL HAVE THREE 3/4" SPARE 0 ! Tigard, OR 97223 CONDUITS STUBBED TO ABOVE AND ACCESSIBLE CEILING. GROUNDING: ONE-LINE DIAGRAM 8.9. ALL SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE, WITH COVER INTERLOCK AND HANDLE LOCK OFF 3.1. GROUNDING OF ELECTRICAL SERVICE AND EQUIPMENT SHALL BE PER THE APPLICABLE SECTIONS OF NEC PROVISIONS. SWITCHES SHALL BE MANUFACTURED BY SQUARE "D", CUTLER HAMMER, OR SIEMENS. RATINGS AND n XX/YY CIRCUIT BREAKER FRAME SIZE/ TRIP, 3 POLE FUSING SHALL BE AS SHOWN ON THE DRAWINGS. COORDINATE FUSING FOR SWITCHES SERVING MECHANICAL AKRI B I S ARTICLE 250, AND AS SHOWN ON THE DRAWINGS. EQUIPMENT WITH MANUFACTURERS RECOMMENDED FUSE SIZE. -�- LOAD INTERUPTER SWITCH V 3.2. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR, IN ACCORDANCE WITH NEC 250, IN ALL CONDUITS 8.10. DRY TYPE TRANSFORMERS SHALL BE 60 HZ, WITH KVA RATINGS AS NOTED ON THE DRAWINGS. TRANSFORMERS ' TRANSFORMER •I WITH CONDUCTORS. ENGINEERING L.L.C. SHALL HAVE A SHEET STEEL ENCLOSURE, ALUMINUM WINDINGS AND CORE AND COIL ASSEMBLY SHALL BE __ ISOLATED FROM THE MOUNTING FRAME WITH VIBRATION ISOLATORS. PROVIDE SIX 2 1/2 % TAPS. FOUR BELOW �- CURRENT TRANSFORMER [� ] 3231 soun+CammY CLUB WAY.STE.lot MMPE.ARIZONA 85282 CONDUCTORS: AND TWO ABOVE NORMAL. INSTALL TRANSFORMERS A MINIMUM OF 9" FROM ADJACENT WALLS OR STRUCTURE. I C - ' (6 r.f6o21393-0202 TRANSFORMERS SHALL BE MANUFACTURED BY SQUARE "D", CUTLER HAMMER, OR SIEMENS. TRANSFORMERS h- POTENTIAL TRANSFORMER WITH SWITCH AND FUSE DRAM eY WE CHECED BY: SM JOB NUMBER.21238 4.1. WHERE WIRING AND CONDUIT SIZES ARE INDICATED FOR HOME RUNS, THESE SIZES APPLY TO THE ENTIRE SHALL BE COMPLIANT WITH IECC. IGCC AND/OR ENERGY EFFICIENCY REQUIREMENTS OF THE ADOPTED CODE BY -11• GROUND ELECTRODEFOR QUESTIONS REASE CALL WLUAMs ORN , LENGTH FROM THE PROTECTIVE DEVICE IN THE PANEL TO THE EQUIPMENT OR LAST WIRING DEVICE. THE LOCAL AND/OR STATE AUTHORITY HAVING JURISDICTION. II Ip 4.2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, OR IN FLOOR SLAB UNLESS NOTED OTHERWISE WIRING DEVICES: L--II -----------------------------------g- ON THE PLANS. 4.3. SCHEDULE 40 PVC CONDUIT SHALL BE USED FOR ALL UNDERGROUND EXTERIOR CONDUIT, IN SLABS, BELOW 9.1. SWITCHES SHALL BE OF THE QUIET TYPE, SPECIFICATION GRADE, 20 AMP, 120/277 VOLT AC. HUBBELL 1221 SLABS ON GRADE, AND IN CONCRETE OR MASONRY WALLS. ALL BENDS OVER 30 DEGREES SHALL BE MADE (SINGLE POLE), 1223 (THREE-WAY). EQUAL BY LEVITON OR PASS & SEYMOUR. WITH WRAPPED INTERMEDIATE METAL CONDUIT. USE LONG SWEEP FITTINGS FOR ALL 90 DEGREE BENDS. ALL KEY PAN _ CONDUIT, EXCEPT THAT USED FOR COMMUNICATIONS, SHALL BE PROVIDED WITH A CODE SIZED EQUIPMENT 9.2. RECEPTACLES, UNLESS NOTED OTHERWISE, SHALL BE DUPLEX, 120 VOLT, 20 AMP, GROUNDING TYPE, NEMA GROUNDING CONDUCTOR. 5-20R. HUBBELL 5362, OR EQUAL BY LEVITON OR PASS & SEYMOUR. SCALE: 1/32" = V-0" 4.4. ALL BELOW GRADE CONDUIT SHALL BE INSTALLED A MINIMUM OF 24 INCHES BELOW FINISHED GRADE. BELOW 9.3. PROVIDE ALL WIRING DEVICES WITH APPROPRIATE COVER PLATES. PROVIDE BLANK COVER PLATES FOR ALL GRADE CONDUIT SHALL BE 3/4 INCH DIAMETER, MINIMUM, EMPTY BOXES. COVER PLATES SHALL BE LEXAN, PLASTIC OR STAINLESS STEEL IN FINISHED AREAS. GALVANIZED COVER PLATES MAY BE USED IN EQUIPMENT ROOMS. 4.5. ALL WIRING SHALL BE IN CONDUIT. RIGID OR INTERMEDIATE METALLIC CONDUIT (IMC) SHALL BE USED FOR ALL CONDUIT LARGER THAN 2 INCH, WHERE SUBJECT TO MOISTURE, OR WHERE SUBJECT TO PHYSICAL DAMAGE. 9.4. COORDINATE DEVICE AND COVER PLATE COLORS WITH ARCHITECT. 120V WIRE SIZE SCHEDULE FEEDER SCHEDULE ELECTRICAL METALLIC TUBING (EMT) MAY BE USED FOR INTERIOR, PROTECTED CONDUIT, 2 INCHES IN SIZE AND9.5. DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS SHALL BE GFCI AND INSTALLED CONCEALED BEHIND THE DISTANCE (FT) HOT,NEUTRAL,GROUND DISTANCE (FT) HOT,NEUTRAL,GROUND NOTE: NOT ALL MAY APPLY TO THIS SHEET. SMALLER. WATER COOLER ACCESS PLATE, OR DIRECTLY BELOW AND CENTERED ON THE COOLER. 2OA 3OA 4.6. FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR ALL CONNECTIONS TO MOTORS. LIQUID-TITE CONDUIT SHALL ID MAX. AMP FEEDER SIZE BE USED WHERE SUBJECT TO MOISTURE. BOND FLEXIBLE CONDUIT PER NEC REQUIREMENTS. 9.6. DUPLEX RECEPTACLES INSTALLED OUTDOORS SHALL BE GFCI, WEATHER-RESISTANT TYPE WITH WEATHER-PROOF <120 FT. #12, 1/2 C. <110 FT. #10, 1/2" C. WHILE-IN-USE COVER, 4.7. INSTALL A PULL WIRE IN ALL EMPTY CONDUITS. 120- 175 FT. #10, 3/4" C. 1 10- 170 FT. #8, 3/4" C. Al 20A 2#12 & 1#12GRD, 1/2"C 9.7. DEVICES SHALL BE TAMPER-RESISTANT WHERE INSTALLED IN AREAS WHERE REQUIRED BY THE NEC ARTICLES 4.8. ALL CONDUCTORS SHALL BE COPPER. BRANCH CIRCUIT WIRING SHALL BE 112 AWG MINIMUM, OTHER SIZES AS 406 AND 517, 175-275 FT. #8, 3/4" C. 170-250 FT. #6, 3/4" C. A2 20A 3#12 & 1#12GRD, 1/2"C INDICATED ON THE DRAWINGS OR AS REQUIRED BY CODE. INSULATION SHALL BE THHN/THWN FOR CONDUCTORS IECC LIGHTING CONTROL: 275-400 FT. #6, 3/4" C. 250-315 FT. #4, 1 " C. A3 20A 4#12 & 1#12GRD, 1/2"C 16 AND SMALLER AND XHHW FOR 14 AND LARGER. 315-375 FT. #3, 1 .25 C. B1 30A 2#10 & 1#10GRD, 1/2"C 4.9. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH NUMBERING ON THE PROGRAMMABLE TIME CLOCK / RELAY PANELS, COMPLIANT WITH IECC AND ASHRAE / IES 90.1 ENERGY CODES, SHALL NOTE: �IOC B2 30A 3#10 & 1#10GRD, 1/2"C PANEL SCHEDULE PROVIDED. BE CAPABLE OF; NS E WIRE SIZE SCHEDULE ABOVE FOR FEEDER SIZES FOR LONGER FEEDER B3 30A 4#10 & 1#1OGRD, 1/2"C 4.10. ALL SECONDARY SERVICES, FEEDERS, AND BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODED AS 10.1. ACCEPTING REMOTE SWITCH INPUTS FOR BOTH "ON" AND "OFF" OVERRIDES OF BOTH INDIVIDUAL AND GROUPED RUNS. 84 30A 6#10 & 1#10GRD,3/4"C FOLLOWS: RELAYS C1 40A 2#8 & 1#10GRD, 3/4"C PHASE 208/120 VOLT 120/240/1-PH 480/277 VOLT 10.2. PROGRAMMING A MINIMUM OF 64 TIME OF DAY AND 32 HOLIDAY SCHEDULES. C2 40A 3#8 & 1#10GRD, 3/4"C A BLACK BUCK BRAWN C3 40A 4#8 & 1#10GRD, 3/4"C B RED RED ORANGE 10.3. 24 HOUR "OFF" OVERRIDE PROGRAM, WITH RETURN TO NORMAL SCHEDULE AFTER 24 HOURS. C BLUE --- YELLOW D1 60A 3#6 & 1#10GRD, 3/4"C NEUTRAL WHITE WHITE GRAY 10.4. PROVIDING A MINIMUM 4 HOUR MEMORY BATTERY BACK UP OF PROGRAMMED SCHEDULES, RELAY, & SWITCH GROUND GREEN GREEN GREEN INPUT ASSIGNMENTS. a 20AMP CIRCUITS. D2 60A 4#6 & 1#10GRD, 1"C 4.11, WRAP UNDERGROUND STEEL CONDUIT WITH HALF LAPPED 3M (OR EQUAL) PIPE PRIMER AND SCOTCHWRAP #50 ,µ �� E1 BOA 3#4 & 1#8GRD, 1 1/4"C TAPE, OR PROVIDE PVC COATED PIPE, INSTALL PER MANUFACTURER REQUIREMENTS. 10.5. PROVIDING A MINIMUM 5 MINUTE WARNING FLASH PRIOR TO SCHEDULED "OFF" COMMANDS. #12 AWG, 1/2C. MINIMUM E2 BOA 4#4 & 1#8GRD, 1 1/4"C 4.12. ALL CONDUITS PENETRATING ROOFS, FLOORS, OR WALLS SHALL BE MADE WATERTIGHT BY PROPER FLASHING. 10.6. PROVIDING A MAXIMUM 2 HOUR "ON" OVERRIDE OF ANY INDIVIDUAL OR GROUP OF DESIGNATED RELAYS. 30AMP CIRCUITS. F1 IOOA 3#3 & 1#8GRD, 1 1/4"C CAULKING, OR SEALING. 10.7. INDICATING INDIVIDUAL AND GROUP RELAY STATUS WITHIN THE CONTROL PANEL. ��yy F2 100A 4#3 & 1#8GRD, 1 1/4"C 4.13. PROVIDE ALL FIXTURES AND DEVICES WITH SUITABLE METAL OUTLET BOXES, CONFORMING TO NEC ARTICLE 370. #10 AWG 1/2" C. MINIMUM FT 100A 4#3 & 1#6GRD, 1 1/4"C 30KVA - - SUPPORT BOXES RIGIDLY FROM STRUCTURE. 10.8. MANUAL "ON AND "OFF" OVERRIDE, WITHIN THE PANEL, OF ANY INDIVIDUAL OR GROUP RELAYS. ( ) _ 4.14. NO MC CABLE ALLOWED FOR MAIN BRANCH CIRCUITS FROM SES OR PANELBOARDS. MC CABLE MAY BE USED 10.9. ASTRONOMICAL TIME CLOCK PROGRAMMING. 9 PROVIDE DEDICATED G1 125A 3#1 & 1#6GRD, 1 1/2"C CT.I.Y__OrTIGAM FOR WHIPS TO LIGHT FIXTURES AND CIRCUITING IN WALLS TO RECEPTACLES OR OTHER SIMILAR LOADS. G2 125A 4#1 & 1#6GRD, 1 1/2"C RBVi$\�rl;D r,v�C�QD$CA1�pLIANCE 10.10.REPROGRAMMING OF SWITCH INPUTS, SCHEDULES. AND RELAY ASSIGNMENTS BY THE TENANT, AT THE NEUTRALS OR TIE-HANDLE/ PANEL, WITHOUT SUPPLEMENTAL SOFTWARE OR FACTORY SUPPORT BEING REQUIRED. Hl 150A 3#1/0 & 1#6GRD, 1 1/2"C SUBMITTALS: 10.11.STANDARD SWITCH RELAYS, RATED FOR 20 AMPS 0 120 /277 VOLT. COMMON TRIP AT PANEL FOR H2 15DA 4#1/0 & 1#6GRD, 1 1/2"C Approved: G 5.1. PROVIDE AN ELECTRONIC PDF SUBMITTAL OR MINIMUM OF SIX (6) SETS OF SHOP DRAWINGS FOR THE �+ HT 150A 4#1/0 & 1#6GRD, 1 1/2"C (45KVA OTCs S FOLLOWING; LIGHTING FIXTURES, DISCONNECT SWITCHES, PANEL BOARDS, ALL SHOP DRAWING SUBMITTALS SHALL 10.12.THE CONTRACTOR SHALL INSTALL ALL NECESSARY SWITCH OVERRIDES, WITHIN THE PERMITTED PROJECT, HARED NEUTRAL RUNS. ) BE BOUND, LABELED, AND MARKED TO IDENTIFY EXACTLY WHICH ITEM WILL BE PROVIDED, IN ORDER TO COMPLY WITH IECC AND ASHRAE / IES 90.1 ENERGY CODES. ill 175A 3#2/0 & 1#6GRD, 2"C Permit #: <LG ' 5.2. SUBMIT FIRE ALARM SHOP DRAWINGS TO THE LOCAL AUTHORITY FOR REVIEW. 10.13.THE CONTRACTOR SHALL PROVIDE THE INITIAL PROGRAMMING AND OWNER OPERATIONS TRAINING, 9 EMERGENCY CIRCUITS SHALL J2 175A 4#2/0 & 1#6GRD, 2"C Address: _ _ / HAVE DEDICATED NEUTRALS. K1 200A 3#3/0 & 1#6GRD, 2"C 13y: #: SUBSTITUTIONS: 10.14.ALTERNATE LATCHING RELAYS, ALLOWING FOR A UL LISTED PANEL SYSTEM RATING OF 10K AIC K2 2OOA 4#3/0 & 1#6GRD, 2"C $ (APPLIES TO 8 RELAY PANELS AND LARGER) ITEMS 1,3,4,6,& 8 ARE REQUIRED, PER IECC & ASHRAE / IES ?' C71 6.1. EQUIPMENT LISTED BY BRAND NAME OR CATALOG NUMBER SHALL BE INTERPRETED /S ESTABLISHING A 90.1. KT 200A 4#3/0 & 1#2GRD, 2"C (75KVA) _ STANDARD OF QUALITY. L1 225A 3#4/0 & 1#4GRD, 2"C IfL/�L�IZ' O 6.2. ANY CONFLICT ARISING FROM THE USE OF SUBSTITUTED MATERIALS SHALL BE THE RESPONSIBILITY OF THE L2 225A 4#4/0 & 54GRD, 2 1/2"C w E SUPPLIER, WHO SHALL BEAR ALL COSTS REQUIRED TO MAKE THE EQUIPMENT COMPLY WITH THE INTENT OF THE 00 .o PLANS AND SPECIFICATIONS. M1 250A 3-250MCM & 1#4GRD, 2 1/2"C Drawing: N M2 250A 4-250MCM & 1#4GRD, 2 1/2"C N T N1 300A 3-350MCM & 1#4GRD, 3"C ELECTRICAL jOn N2 300A 4-350MCM & 1#4GRD, 3"C SPECIFICATIONS O P1 400A3-SOOMCM & 1#3GRD, 3"C as P2 400A 4-500MCM & 1#3GRD, 4"C o PT 400A TWO SETS 4-3/0 & 1#1/OGRD, 2.5"C (112.5KVA) 0) � a � 00 o U N Job No. 21065 t N M. I Date: 10/19/2021 0 O N N o Drawn By: - I N CON Checked By: ELECTRICAL SHEET INDEX N 0 Sheet No: II EO.1 - ELECTRICAL SPECIFICATIONS N � CD C E1.1 - ELECTRICAL DEMOLITION PLAN E2.1 - LIGHTING PLANE3.1 - POWER PLAN EOml o0 E5.1 - ONE-LINE DIAGRAM AND PANEL SCHEDULES GENERAL NOTES 1 . DEVICE MOUNTING HEIGHTS ARE SHOWN FOR REFERENCE ONLY. COORDINATE ALL FINAL MOUNTING HEIGHTS AND/OR LOCATIONS, AS REQUIRED, WITH ARCHITECTURAL DETAILS, ELEVATIONS AND MILLWORK CONTRACTOR. S E A 2. WHERE SHOWN, EXISTING CIRCUITS ARE FOR REFERENCE ONLY AND HAVE NOT BEEN FIELD VERIFIED. CONTRACTOR SHALL FIELD VERIFY SCOTT IEDWARDS ARCHITECTURE LLP — — — — — — EXISTING CIRCUITING AND UPDATE PANEL SCHEDULES AS REQUIRED. O Ot VERIFY LOADS ON EXISTING CIRCUITING PRIOR TO ADDING NEW. 2525 E. Burnside St., Portland, OR 97214 EX EX I phone:(503) 226-3617 www.seallp.com 3. REFER TO THE INSTALLATION PLANS FOR NEW ELECTRICAL DEVICE ® E LAYOUT AND REUSE CIRCUITING. EXISTING CONDUITS AND CONDUCTORS MAY BE REUSED IF FEEDERS ARE TESTED AND DETERMINED TO BE IN —_ —_ _ — —_ GOOD CONDITION, OTHERWISE, REMOVE FEEDERS AND PROVIDE NEW AS SHOWN ON INSTALLATION DRAWINGS. &73416PE# 4. REMOVAL OF COMMUNICATIONS DEVICE SHALL INCLUDE REMOVAL OF EX COMMUNICATIONS CABLING BACK TO SOURCE UNLESS OTHERWISE DIRECTED BY OWNER. I I EX z EX EX z i I 5. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE NY DEMOLITION OF DEVICES AND CIRCUITING SHOWN. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL CIRCUITING. UPDATE PANELSCHEDULES ACCORDINGLY. AT END OF PROJECT THE ELECTRICALEX ® EX I CONTRACTOR SHALL PROVIDE AN ACCURATE SET OF AS—BUILT DRAWINGS IX OO Ex Ex THAT DOCUMENTS CIRCUITING LOCATIONS FOR EXISTING AND NEW FIXTURES AND DEVICES AS WELL AS UPDATED PANEL SCHEDULES WITH RENEWAL DATE: 12/31/2022 I t1a — SPARE CIRCUIT BREAKERS IDENTIFIED. WHERE CIRCUITING IS NOT REUSED Ex REMOVE CIRCUITING BACK TO SOURCE PANEL AND LABEL CIRCUIT I BREAKER AS SPARE. SPARE CIRCUIT BREAKERS ARE TO BE LEFT IN THE Ex Ex I I 'OFF' POSITION. I v @_ 6. ELECTRICAL CONTRACTOR TO TEST EXISTING EMERGENCY BATTERY I EX III IR /I IR /I PACKS AND PROVIDE NEW WHERE EXISTING UNIT IS FOUND TO BE EX DEFECTIVE OR INOPERABLE. NEW UNIT SHALL MATCH BUILDING �OOM*CQre� STANDARDS. Ex Ex Ex Ex Ex Ex Ex 7. EXAMINE THE CONTRACT DRAWINGS AND ALL AVAILABLE INFORMATION BILLING & HELP CONCERNING EXISTING INSTALLATION AND LOCAL CONDITIONS. VISIT THE r — 71 r — 7 r — 7 - — SITE TO UNDERSTAND THE NATURE AND SCOPE OF ALL WORK TO BE OFFICE SPACE R R R Ex — — — — — — — — — — PERFORMED AND VERIFY EXISTING CONDITIONS. THE SUBMISSION OF A BID WILL BE TAKEN AS EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN Ex I MADE AND THAT ALL EXISTING CONDITIONS HAVE BEEN CONSIDERED. NOTIFY ENGINEER IF ANY DISCREPANCIES OR CONFLICTS ARE OBSERVED. t _ .j t _ .j t — .j r R�� r R�I 11958 SW Garden Place EX Tigard, OR 97223 r — � AEi EXDEMOLITION KEY NOTESEx R I R / I - - - - - - 1 . EXISTING EXTERIOR LIGHTING FIXTURE TO REMAIN. NO CHANGE. AKRI Bt 2. EXISTING LIGHTING FIXTURE TO BE REMOVED AND RELOCATED TO NEW LOCATION AS SHOWN ON INSTALLATION PLAN, SHEET E2.1 . t _ .j ENGINEERING — — 3. EXISTING DEVICE TO BE REMOVED AND RELOCATED TO NEW LOCATION 3z31 souHcaxnavauBw v.sre loz rez Ex Ex AS SHOWN ON INSTALLATION PLAN, SHEET E3.1 . EXTEND EXISTING P.i602;313ozo1 CIRCUITING TO NEW LOCATION AS REQUIRED. gwwNB : ws CHECKED BY: SM OFOR OUESTOW PLEASE CALL `MLLLMA SHOW I I IX ®Ex 4. EXISTING CEILING MOUNTED MOTION SENSOR TO REMAIN. NO CHANGE. Ex I I I IL 5. EXISTING INSTA—HOT TO REMAIN. NO CHANGE. Ex Ex Ex Ex Ex IX I I 6. EXISTING ROOFTOP UNIT TO REMAIN. NO CHANGE. II II II II II IQ EX ®EX L I I _ ? I EX EX EX EX EX EX I R / I I / I � R I I � I EX EX r EX I I EX EX EX Ex I EX EX Ex I I EX EX EX EX Ex EX EX ©- .I Ex W E a - - - - - - - - - - - - - - - - - - - - - — Drawing: Co .2 W) = ELECTRICAL N3 Ni DEMOLIT ON PLAN Wv I EX EX Ex PANEL A ABBREVIATION LEGEND - POWER p Ex Ex EX EXISTING DEVICE TO REMAIN. CONNECT TO NEW AREA/ROOM v o` IX EX CIRCUITING AS SHOWN ON POWER INSTALLATION PLANS. °o EX EES REMOVE EXISTING DEVICE AND REUSE WHERE POSSIBLE. OTHERWISE a RETURN TO OWNER STOCKPILE, OR AS DIRECTED BY OWNER. m 0 ^ R DEMO PLAN—RELOCATE EXISTING DEVICE. Job No: 21065 + N Ex Ex INSTALLATION PLAN—NEW LOCATION FOR RELOCATED DEVICE. + I NEW EXISTING CIRCUITING TO NEW LOCATION OR PROVIDE WITH Date: 10/19/2021 EX CIRCUIT � " ABBREVIATION LEGEND - LIGHTING Drawn By: - 0 I N — EX EXISTING FIXTURE TO REMAIN. CONNECT TO NEW AREA/ROOM Checked By: °„3o EX,, I CIRCUITING AND LIGHTING CONTROL AS REQUIRED. 1 ® 1 ® 1 ® I Sheet No: O O I EXD REMOVE EXISTING FIXTURE AND RETURN TO OWNER STOCKPILE OR AS DIRECTED BY OWNER. N N� EX EX IX N - - - - - - - - - - - - - - - - - - - - - - - R DEMO PLAN—RELOCATE EXISTING FIXTURE. 6o` INSTALLATION PLAN—NEW LOCATION FOR RELOCATED FIXTURE. El 11 v EXTEND EXISTING CIRCUITING TO NEW LOCATION OR PROVIDE WITH ■ o NEW CIRCUIT SHOWN ON PLANS. GENERAL NOTES xxx 1 . WHERE EQUIPMENT DESIGNATION SYMBOL IS SHOWN, REFER TO HVAC/PLUMBING EQUIPMENT SCHEDULE (SHEET E3.1) FOR F E3 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - CONTROL/FEEDER, OCP INFORMATION AND SOURCE PANEL. REFER TO I ❑1 TVP. PANEL SCHEDULES (E5.# SERIES SHEETS) FOR CIRCUITING (TYPICAL). E% EX I 2. DEVICE MOUNTING HEIGHTS ARE SHOWN FOR REFERENCE ONLY. S EA ® E I COORDINATE ALL FINAL MOUNTING HEIGHTS AND/OR LOCATIONS AS SCOTT IEDWARDS ARCHITECTURE LLP REQUIRED WITH ARCHITECTURAL DETAILS, ELEVATIONS AND MILLWORK ff — — — — CONTRACTOR. 2525 E. Burnside St., Portland, OR 97214 II � 3. ELECTRICAL CONTRACTOR SHALL LABEL ALL DEVICES: J-BOXES, phone:(503) 226-3617 www.sealip.com 5NI EX I Ex RECEPTACLES, POWER POLES, POWER WHIPS WITH CIRCUIT DESIGNATION. TING EX EXISTING EX 4. BRANCH CIRCUITING SHALL BE MINIMUM #12 AWG WITH MININUM 1/2" ERENC TRY TECH STO CONDUIT. EX EX EX EX EX 11'xle' 5. HOMERUN CIRCUITS MAY BE COMBINED INTO COMMON CONDUITS a73416POEV I 176 SF I WHERE ALLOWED BY NEC. PROVIDE DEDICATED NEUTRALS WHEN FEEDING (2)5'DESKS AFCI OR GFCI CIRCUIT BREAKERS. PROVIDE COMMON TRIP HANDLES IF I COMBINING CIRCUITS AND SHARING NEUTRAL CONDUCTORS. EX® I E% Ex 6. REFER TO SHEET E0.2 FOR LIGHTING FIXTURE SCHEDULE AND IECC. li]TYP. EX E% OREGON tP Oct 21, 2021 -� � I I � I II RENEWAL DATE: 12/31/2022 I a R Ex J ❑ KEY NOTES EX EXISTING 1 . EXISTING EXTERIOR LIGHTING FIXTURE TO REMAIN. NO CHANGE. Ex NFERENC EX HALLA HAL 2. NEW LOCATION OF RELOCATED LIGHTING FIXTURE. EXTEND EXISTING 1 A e 1 R CIRCUITING TO NEW LOCATION AS REQUIRED. ®®� n c��• .,o' C1+' F R R Ex 3. PROVIDE NEW LIGHTING CONTROL / LAYOUT AS SHOWN. LIGHTING FIXTURE SCHEDULE 4. REFER TO HVAC/PLUMBING EQUIPMENT SCHEDULE AND GENERAL TYPE DESCRIPTION MANUFACTURER AND MOUNTING DIMMABLE LAMP DATA VOLT NOTES I I a EXI 3 / E NOTE #1 FOR ADDITIONAL INFORMATION. BILLING HELP CATALOG NUMBER QUAN. WATT TYPE ORDERING TBREAK T RAG OFFICE SPACE O YES / O CODE 5. CONNECT TO EXISTING LOCAL LIGHTING CIRCUIT. PROVIDE 1 NO VOLTAGE 2 EX 2 3 ,sss NON-SWITCHED LEG OF LIGHTING CIRCUIT FOR EMERGENCY LIGHTING L6 WALL SCONCE MODERN FORMS: WS-W81619 W N 1 15 LED FWF 120 1, 2 EXISTIN L12 EXIT SIGN- SINGLE FACE LITHONIA: EDG - 1 - GMR - EL- SD Pis N 3 LED FWF 120 1, 2, 3 RF LY RM R 6. PROVIDE NEW GYP LID WITH GYP FRAME COMPATIBLE WITH EXISTING MOUNTING LAMP TYPE EX R R EX I 11958 SW Garden Place R: RECESSED • W: WALL F: FLUORESCENT • CF: COMPACT FLUORESCENT 0.75' 2 . RELOCATED FIXTURE MOUNTED IN HARD LID CEILING.S:SURFACE • P: PENDANT • MH: METAL HALIDE • LED: LIGHT EMITTING DIODE Tigard, OR 97223 • E: EXTERIOR • I: INCANDESCENT • FWF: FURNISHED WITH FIXTURE OL12 L120 GENERAL NOTES: a � � ❑5 1. PROVIDE BALLAST/DRIVER DISCONNECT PER NEC 410.130(G)FOR LIGHTING FIXTURES. EX EX IF EXISTING AMB I S NOTES: �RR�y� 1. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR FIXTURE MOUNTING HEIGHT. Ex EX ENGINEERING L.L.C. 2.VERIFY FIXTURE FINISH PRIOR TO ORDERING. R I I 3X3,sIXlrH COUrrRY CLUB WAY.STE.102 TEMPE,ARIZONA 65262 3. PROVIDE WITH MINIMUM 90-MINUTE BATTERYBACKUP I I P.leozl3v3-0zm E(eo2)393-ozo2 AKRIBIS ENGINEERING, LLC -JOB IN 21 Fe Ex EX EX Ex Ex iEx DRAWN BY: WS CHECKED BY: SM JOB NUMBER:21236 FOR 9UESTONS PLEASE CALL'.WILLIAM SHORN II LIGHTING FIXTURE LOAD CALCULATIONS 5L CI DEMOLITION PLAN EXRRI Ez TYPE DESCRIPTION LAMP W/FIX FIXQTY WATTS 1 EXD RECESSED 2X4 FLUOR 40 1 40 ❑5 O EXD RECESSED DOWNLIGHT FLUOR 18 1 18 EXISTING LAYOUT TOTAL 58 WATTS BI'LING R — — — — — — 51 INSTALLATION PLAN (25)6'DESKS TYPE DESCRIPTION LAMP W/FIX FIXQTY. WATTS I' III: L6 RR WALL SCONCE LED 15 1 15 EX EX EX E% EX EX R NEW LAYOUT TOTAL 15 WATTS 2❑ NET ADD/(REDUCTION) (43) WATTS R (0,36) AMPS I L EF 4 (g) 1 I E EX EX COMcheck Software Version 4.1.5.1 THIS AREA FOR IECC Interior Lighting Compliance Certificate EX EX EX EX EX Ex EX HELP 1 . 'DESKS ■ Project Information Energy Code: 2018 IECC Project Title: Zoom+Care Office TI Project Type: Alteration HELP TEAM Construction Site: Owner/Agent: Designer/Contractor: 11958 SW Garden Place Scott I Edwards Architect LLP AKRIBIS Engineering, LLC. (39)5'DESKS Tigard, OR 97223 2525 E. Burnside St. 3132 S. Country Club Way —. Portland, OR Suite 102 Tempe, AZ 85282 Ex EX EX EX EX EX E% Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (tt2) Watts/ft2 (B X C) 1-RR 110(Common Space Types:Restrooms) 68 0.85 58 Q / Total Allowed Watts= 58 EX _ _ _ _ _ _ _ _ _ _ _ _ _ _ % _ _ ABBREVIATION LEGEND - LIGHTING Proposed Interior Lighting Power L12 — — — — — — — — — — — — — — — — — — — — — — EX EXISTING FIXTURE TO REMAIN. CONNECT TO NEW AREA/ROOM Fixture ID : Description /Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) CIRCUITING AND LIGHTING CONTROL AS REQUIRED. Fixture Fixtures Watt. SERVER EXD REMOVE EXISTING FIXTURE AND RETURN TO OWNER STOCKPILE OR ui o RR 110(Common Space Types Restrooms 68 sqft) EX EX EX EXISTING ELEEC AS DIRECTED BY OWNER. Drawing: LED t:R:Relo.Recessed 2x4:Other: 1 t ao 4o EX CONFERENCE EX 6•x,4' R DEMO PLAN-RELOCATE EXISTING FIXTURE. rV 3 LED 2:L6:Wall Sconce:Other: 1 1 15 1s - LIGHTING PLAN II 15'X23' EX INSTALLATION PLAN-NEW LOCATION FOR RELOCATED FIXTURE. im Total Proposed Watts= 55 EXTEND EXISTING CIRCUITING TO NEW LOCATION OR PROVIDE WITH 345 SF _ W -•� PASSES NEW CIRCUIT SHOWN ON PLANS. Interior Lighting Compliance Statement I '11—X VACANCY SENSOR LEG END a Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the o, building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting EX EX CONTROL SWITCHES: n- systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any EX C4 ■/COLOR a ut applicable mandatory requirements listed in the Inspection Checklist. o ® SENSOR SWITCH: WSX PDT SA Job No: 21065 N (VACANCY SENSOR - STANDARD ROOM - LINE VOLTAGE) + N SENSOR SWITCH: sPODMRD //COLOR Date: 10/19/2021 0EX D (0-10V DIMMING SWITCHPOD SERIES - LINE VOLTAGE) o0 IVP. ® ® 1 Trp. I Drawn By: ry EX EX EX ❑ I CEILING MOTION SENSORS: SENSOR SWITCH: CMR PDT 10 co N _ _ _ O Checked B - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - — — — — M1 (CEILING MOTION SENSOR — EXTENDED RANGE — LINE VOLTAGE) N o Sheet No: u o cl LIGHTING PLAN NOTE: - - r SCALE: 3/16" = 1'-0" 1 . ALL SENSORS TO BE PROGRAMMED FOR MANUAL ON, AUTO OFF IN cp a COMPLIANCE WITH 2018 IECC C405.2.2.2 OCCUPANCY SENSORS AND I w C405.2.2.3.1 MANUAL DAYLIGHT CONTROLS Ell v ii 0 GENERAL NOTES r - - - - - - - - 1 . "j" WHERE EQUIPMENT DESIGNATION SYMBOL IS SHOWN, REFER TO HVALUMBING EQUIPMENT SCHEDULE (THIS SHEET) FOR CONTROL/FEEDER, OCP INFORMATION AND SOURCE PANEL. REFER TO I i PANEL SCHEDULES (E5.# SERIES SHEETS) FOR CIRCUITING (TYPICAL). 2. DEVICE MOUNTING HEIGHTS ARE SHOWN FOR REFERENCE ONLY. S EA — — — — LLL_ COORDINATE ALL FINAL MOUNTING HEIGHTS AND/OR LOCATIONS AS SCOTT IEDWARDS ARCHITECTURE LLP REQUIRED WITH ARCHITECTURAL DETAILS, ELEVATIONS AND MILLWORK CONTRACTOR. 2525 E. Burnside St., Portland, OR 97214 EXISTING EXISTING 3. ELECTRICAL CONTRACTOR SHALL LABEL ALL DEVICES: J-BOXES, phone:(503) 226-3617 www.sealip.com CONFERENCE ENTRY TECH STORAGE RECEPTACLES, POWER POLES, POWER WHIPS WITH CIRCUIT DESIGNATION. t t IDD t 6 2x15.5' 11'x16' 4. BRANCH CIRCUITING SHALL BE MINIMUM #12 AWG WITH MININUM 1/2" 186 SF 176 SF CONDUIT. (2)5'DESKS Ep PRO 5. HOMERUN CIRCUITS MAY BE COMBINED INTO COMMON CONDUITS Ex WHERE ALLOWED BY NEC. PROVIDE DEDICATED NEUTRALS WHEN FEEDING AFCI OR GFCI CIRCUIT BREAKERS. PROVIDE COMMON TRIP HANDLES IF 73416PE�' At COMBINING CIRCUITS AND SHARING NEUTRAL CONDUCTORS. 'A2'-10 6. RECEPTACLES SHALL BE TAMPER RESISTANT. oREcoN O sy o�c 21, 2021 +54•+54' Ex I RENEWAL DATE: 12/31/2022 EXISrl COON ER EX EX EX EX EX ❑ KEY NOTES CON ERENCE HALL HALL - - toe ITS 1 5 1 . NEW LOCATION OF RELOCATED DEVICE. EXTEND EXISTING CIRCUITING 1175 x SF TO NEW LOCATION AS REQUIRED. ne SF ❑ +5a Ex 2. CONNECT TO EXISTING LOCAL CIRCUITING AS SHOWN. Z�OM�Ca�' +54' EXISTING i NEW 3. PROVIDE POWER/CABLE/DATA FOR WALL MOUNTED T.V. REFER TO TEAM/ TECH STORAGE ol ARCHITECTURAL SHEETS FOR MOUNTING HEIGHT AND RECESSED BREAK01 15z1l. ENCLOSURE TYPE. BILLING & HELP 20'z 14.75' 185 SF 295 SF 4. REFER TO HVAC/PLUMBING EQUIPMENT SCHEDULE AND GENERAL OFFICE SPACE PRINTER EX XISTIN NOTE #1 FOR ADDITIONAL INFORMATION. UPPLY RM NA 85282 10 5. PROVIDE MEANS OF DISCONNECT FEEDER FOR WATER HEATER. REFER ,75x1075 TO GENERAL NOTE #1 FOR ADDITIONAL INFORMATION. zs sF 11958 SW Garden Place P D o Tigard, OR 97223 EXISTING O 17 R® EX AMBIS XIS ENGINEERING L.L.C. Al 3P I60O3 23' UT'3020MRY CLUB WAY,STE.102 TEMPE,1 1 Ab0O3930202 A2'-12 FDRAWN BY: VJS CHECKED BY: SM JOB NUMBER:21238 HALL C FOR auEsrioNs PLFlSE cn11:w,uw.n sHoan 10 EXISTING 00 R® B4 O BIL ING 'A2'-9,11,13,15 11 (25)f DESKS NEW RIPIDI A 1 O 0 ® � 5 d P D ❑j R B4 IT HELP P 11 (5)5'DESKS 'A2'-2,4,6,8 ABBREVIATION LEGEND - POWER HELP TEAM EX EXISTING DEVICE TO REMAIN. CONNECT TO NEW AREA/ROOM 1_1 4-1 CIRCUITING AS SHOWN ON POWER INSTALLATION PLANS. (39)5'DESKS EXD REMOVE EXISTING DEVICE AND REUSE WHERE POSSIBLE. OTHERWISE RETURN TO OWNER STOCKPILE, OR AS DIRECTED BY OWNER. R DEMO PLAN-RELOCATE EXISTING DEVICE. o INSTALLATION PLAN-NEW LOCATION FOR RELOCATED DEVICE. - - a EXTEND EXISTING CIRCUITING TO NEW LOCATION OR PROVIDE WITH o Ba NEW CIRCUIT SHOWN ON PLANS. a B4 <6> 64 NEW PANEL 'A2' PARTIAL SYMBOL LIST A2'-25,27,29,31 A2'-33,35,37,3 'A2'-17,19,21,23 A2'-1,35,7 / FACE-LESS GFCI CIRCUIT GUARD DEVICE E)y PANEL 'A' GFCI GUARD DEVICE BY HUBBELL, MODEL NO. GFBFHP20xxx. _ © MOUNT +44" AFF IN ACCESSIBLE LOCATION AS SHOWN FOR CU1 r ACCESS TO DEVICE WITHOUT MOVING EQUIPMENT. VERIFY COLOR 3T � WITH ARCHITECT. 4❑ r. _ VE CARD READER EXISTING AH1 12 PROVIDE 2-SQUARE J-BOX AND 3/4" CONDUIT WITH 90' ELBOW M 3 CONFERENCE 3T SF, x,b' CR IN ACCESSIBLE CEILING SPACE. VERIFY FINAL LOCATION WITH CITY Fff 3-1 w > ❑ 15x23' A2'-1a PROJECT MANAGER AND ARCHITECT. COORDINATE INSTALLATION Drawing: 03 2 +54- 345 SF At' WITH CARD READER SUPPLIER. N +54' x COMBINATION USB/DUPLEX RECEPTACLE POWER w caA2'-16 +12 USB/DUPLEX DEVICE BY HUBBELL, MODEL NO. USB20A5xxx. PLAN i v 2❑ VERIFY COLOR WITH ARCHITECT. o � TV-POWER-DATA (WALL MOUNTED) n`. PROVIDE HUBBELL FLAT PANEL 2-GANG IN-WALL ENCLOSURE, rn MODEL NO. NSAV62M WITH COVER-NSAV6C AND STANDARD a -_ -_ ® POWER KIT-NSOKPTR. PROVIDE WITH (1) DUPLEX AND AV m o CONNECTORS AS REQUIRED PER IT CONSULTANT. PROVIDE (2) 1 " Job No: 21065 DATA CONDUITS TO ABOVE CEILING. WHERE LOCATED IN A ROOM + QWITH POWER AV FLOOR DEVICE, PROVIDE CONDUITS FROM FLOOR DEVICE TO WALL AV BOX AS INDICATED AT FLOOR DEVICE. VERIFY Date: 10/19/2021 o I MOUNTING HEIGHT WITH ARCHITECT AND ARCHITECTURAL ELEVATION o N - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PLANS. Drawn By: - o I N TV (WALL MOUNTED) Checked By: - °Mo 04 PROVIDE HUBBELL FLAT PANEL 4-GANG IN-WALL ENCLOSURE, ® MODEL NO. NSAV124M WITH COVER-NSAVI2C. PROVIDE WITH (2) Sheet No: i o DUPLEX AND AV CONNECTORS AS REQUIRED PER IT CONSULTANT. 11 0 POWER PLAN PROVIDE (2) 1" DATA CONDUITS TO ABOVE CEILING. WHERE o 4 `N , PROVIDE SCALE: 3/16" = 1'-0" Ell a CONDUITS FROM FLOOR DEVICE TO WALL AV BOX AS INDICATED i? 0 AT FLOOR DEVICE. VERIFY MOUNTING HEIGHT WITH ARCHITECT AND CD I ARCHITECTURAL ELEVATION PLANS. Li � GENERAL NOTES 1. REFER TO FAULT-CALCULATION FOR EACH PANEL RATING. EXISTING FEEDER TO REMAIN UNCHANGED 2. ELECTRICAL CONTRACTOR AND SES GEAR MANUFACTURER SHALL EXIST. PANEL SDP2 AMPACITY 400 MAINS MLO KAIC: 14 EXISTING PROVIDE A SERIES RATED SYSTEM. PROVIDE WARNING LABELS AS VOLTAGE: 120/208V NEMA: 1 MOUNTING: Select PANEL CIRCUITS: X42 POWER Co. REQUIRED BY NEC110.22 AND 240.86(a). ENGRAVED LAMINATED S EA LOAD NO. M C N R L C/B PHASE C/B L R N C M NO. LOAD TRANSFORMER NAMEPLATES SHALL BE PROVIDED AT THE SES AND PANELBOARD. REFER EX .RTU-13 1 6.70 70 6.70 100 2 SPARE EXISTING FEEDER TO TO NEC 110.22 FOR SPECIFIC WORDING OF SERIES RATED LABELS. SCOTT I EDWARDS ARCHITECTURE LLP - 3 6.70 6.70 4 - REMAIN UNCHANGED 5 6.70 3 6.70 3 6 - 3. NO DESIGN CHANGES MAY BE MADE TO THE SYSTEM WITHOUT PRIOR 2525 E. Burnside St., Portland, OR 97214 r - - - - - - - - - - 1 APPROVAL OF THE DESIGN ENGINEER & THE ELECTRICAL INSPECTOR. P ( ) 6-3617 www.seallp.com SPARE 7 50 0.10 20 0.10 8 E-MON SUB-METERS hone: 503 22 p. 9 0.10 0.10 10 - I I 11 3 0.10 3 0.10 12 - I I 4. DESIGN IS BASED ON 75'C TERMINATIONS. PROVIDE 75'C SPACE 13 0.00 14 SPACE I M I EXISTING SES TERMINATIONS FOR SES AND PANEL. 160OA/120/208V/30/4W/NEMA 1 SPACE 15 0.00 16 SPACE I I SPACE 17 0.00 18 SPACE BRACED FOR 65KAIC 5. PROVIDE ALL ARC-FLASH LABELING AS REQUIRED PER NEC 110.16. Fp PRO SPACE 19 0.00 20 SPACE SPACE 21 0.00 22 SPACE i I �p r SPACE 23 0.00 24 SPACE EXIST. E] KEY NOTES 73416PE SPACE 25 0.00 26 SPACE I 200/3 EXIST. EXIST. EXIST. OREGON SPACE 27 0.00 28 SPACE I aoo/3 aoo/3 aoo/3 I 1 . EXISTING METER TO REMAIN. LJ7 Oct 21. 2021 SPACE 29 0.00 30 SPACE 1400AF 400AF 400AF SPACE 31 0.00 32 SPACE SPACE 33 0.00 34 SPACE I SPACE 35 0.00 36 SPACE L - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - J RENEWAL DATE: 12 31 20 PANEL A 37 19.48 200 27.48 PKVAA 8.00 38 PANEL B 22 (SUB-FEED C/B) 39 18.35 26.35 8.00 40 (SUB-FEED GB) 41 19.24 3 27.24 8.00 42 EXISTING EXISTING EXISTING EXISTING FEEDER TO FEEDER TO FEEDER TO FEEDER TO MANU: CUTLER-HAMMER LIGHTING LOAD @125%= 0.00 0.00 0.00 NOTES: REMAIN REMAIN REMAIN REMAIN UNCHANGED UNCHANGED UNCHANGED UNCHANGED 1. ALL CIRCUIT BREAKER ARE EXISTING UNLESS NOTED 100% + REMAINDER@ 50%)= 0.00 0.00 0.00 KVA OTHERWISE. w NON-CONTINUOUS LOAD= 00% 27.58 26.45 27.34 KVA SHOWN FOR u CF2 ZDOMare CONTINUOUS 125%= 0.00 0.00 0.00 KVA REFERENCE ONLY 25%OFL BILLING & HELP MOTOR= 8.38 8.38 8.38 KVA 200/3 200/3 TOTAL EXIST. PANEL SDP2 T � 1 OFFICE SPACE DEMAND= 35.96 34.83 35.72 JKVA EXIST. EXISTING EXIST. EXISTING EXIST. EXIST. PANEL FEEDER TO PANEL FEEDER TO PANEL PANEL ®2010-2021 AKRIBIS Engineering,L.L.C. 2.81 TOTAL DEMAND AMPS= 299,66 290.22 297.66 AMPS 'SDP1' REMAIN 'SDP2' REMAIN 'SDP3' 'SDP AC' UNCHANGED UNCHANGED 11958 SW Garden Place F3 Tigard, OR 97223 PANEL AMPACITY: 200 MAINS MLO KAIC 10 RATING: Fully@10K F [E VOLTAGE: 120/208V NEMA: 1 MOUNTING: SURF PANEL CIRCUITS: X42 F4 100/3 LOAD NO. M C N R L C/B PHASE C/B L R N C M NO. LOAD -- AKRI B I S EX LTS -NORTH 1 0.80 20/1 1.16 20/1 0.36 2 EX REC- TMB NEW EXIST EXIST. EX.LTS -SOUTH 3 0.80 20/1 1.60 20/1 0.80 4 EX REC- RR PANEL PANEL PANEL ENGINEERING L.L.C. EX.EXTERIOR EGRESS 5 0.80 20/1 1s0 20/1 0.80 6 EX REC- OFFICE 1 B' 323''a' CouNmv cwB wAv,stE,Toz rEMPe An¢oNA eszez EX WH-7 7 1.50 20 2.30 20/1 0.80 8 EX REC-OFFICE 2 P:leozl393-0201 F (602)393 0202 9 1.50 2 2.30 20/1 0.80 10 EX REC- BREAK 4#3 DRAWN BY WS CHECKED BY: SM JOB NUMBER 21238 FOR QUESTIONS PLEASE CALL:W1LUAM SHORTY EX WH-8 11 1 1.50 20 2.30 20/1 0.80 12 EX REC- RECEPTN 1#8 GND., 13 1.50 2 2.30 20/1 0.80 14 EX REC- CONFER. 1.25" C. EX WH-9 15 1.50 20 2.30 20/1 0.80 1 16 EX REC-OFFICE 3 17 1.50 2 2.30 20/1 0.80 18 EX REC-OFFICE 4 EX UNIT 14 19 0.80 20/1 1.60 20/1 0.80 20 EX REC- REF 1 ONE-LINE DIAGRAM EX UNIT 14 21 0.80 20/1 1.60 20/1 0.80 22 EX REC- REF 2 EX UNIT 18 23 2.50 30 3.30 20/1 0.80 24 EX REC- BREAK 1 SCALE: N.T.S. 25 2.50 3.30 20/1 0.80 26 EX REC- BREAK 2 27 2.50 3 3.30 20/1 0.80 28 EX REC- BREAK 3 EX LOAD 29 0.80 20/1 1.60 20/1 0.80 30 EX REC- OPEN OFF S EX LOAD 31 0.80 20/1 1.60 20/1 0.80 32 EX REC- OPEN OFF E EX-LOAD 33 0.80 20/1 1.60 20/1 0.80 34 EX REC- OPENOFFN EXLOAD 35 0.80 20/1 1.60 20/1 0.80 36 EX LOAD FAULT CURRENT CALCULATION - SES [A] NEW PANEL A2 37 8.29 100 10.79 30 2.50 38 EX LOAD ©2010-2021 AKRIBIS Engineering,L.L.C. 2.81 396.87 9.37 2 2.50 40 Fault F1 F2 F3 F4 41 8.88 3 9.68 20/1 0.80 42 EX LOAD PANEL PANEL PANEL LIGHTING LOAD @ 125%= 1.00 1.00 1.00 KVA NOTES: Location SES SDP2 A A2 RECEPTACLES 1.ALL CIRCUIT BREAKERS ARE EXISTING UNLESS NOTED AFC(from source) 65000 65000 53687 6743 100%+REMAINDER@ 50%)= 7.19 7.48 6.36 KVA OTHERWISE. Conductor size #3/0 #3/0 #3 NON-CONTINUOUS LOAD @ Conductor type Cu. Cu. Cu. PER NEC 210.4(6) 100% = 11.29 9.87 11.88 KVA 2. NEW/ MODIFIED LOADS ARE SHOWN IN GRAY. Length 10 200 5 PROVIDE COMMON TRIP HANDLES [A] PROVIDE NEW CIRCUIT BREAKER AS SHOWN. #of Sets 2 1 1 FOR ALL MULTI-CIRCUIT CONDUIT CONTINUOUS LOAD @ 125% = 0.00 0.00 0.00 KVA Type of Conduit STEEL STEEL STEEL RUNS. MOTORS+25%OF LARGEST C value 12843 12843 4760 MOTOR= 0.00 0.00 0.00 KVA -- TOTAL PANEL A DEMAND= 19.48 18.35 19.24 KVA Voltage primary 208 208 208 Voltage secondary(xfmr) 02010-2021 AKRIBIS Engineering, L.L.C. 2.81 TOTAL DEMAND AMPS= 162.37 152.93 160.37 AMPS xfmr impedence xfmr kva 'f Factor 0.21 6.96 0.06 AMPACITY: 100 MAINS: MLO KAIC: 10 RATING: Fully@ 10K Multiplier 0.83 0.13 0.94_ NEW PANEL A2 VOLTAGE: 120/208V NEMA: 1 MOUNTING: SURF PANEL CIRCUITS: X42 Calculated Fault Current 65000 53687 6743 6368 LOAD NO. M C N R L C/B PHASE CIE L R N C M NO. LOAD Fully@ Fully@ 114/115.FURN SYS 1 0.80 20/1 1.60 20/1 0.80 2 114/115.FURN SYS Rated (Series/Fully) 10K 1OK 114/115.FURN SYS 3 0.80 20/1 1.60 20/1 0.80 4 114/115.FURN SYS NOTE CONDUCTOR LENGTHS SHOWN IN THIS CALCULATION ARE SHORTEST 114/115.FURN SYS 5 0.80 20/1 1.60 20/1 0.80 6 114/115,FURN SYS DISTANCE DIRECT ROUTE AND SHALL NOT BE USED FOR BIDDING PURPOSES. 114/115.FURN SYS 7 0.80 20/1 1.60 20/1 0.80 8 114/115.FURN SYS 114/115.FURN SYS 9 0.80 4P 20/1 1.52 20/1 0.72 10 106.R.G 114/115.FURN SYS 11 0.80 20/1 1.52 20/1 0.72 1 12 101/102/103.R.G 114/115.FURN SYS 13 0.80 20/1 1.16 20/1 0.36 14 112.R.TMB 114/115.FURN SYS 15 0.80 20/1 0.98 Pill 20/1 0.18 16 112.R.SUMP PUMP 114/115.FURN SYS 17 0.80 20/1 0.80 20/1 18 SPARE 114/115.FURN SYS 19 0.80 20/1 0.80 20/1 20 SPARE 114/115.FURN SYS 21 0.80 20/1 0.80 20/1 22 SPARE 3 114/115.FURN SYS 23 0.80 20/1 0.80 2011 24 SPARE a 114/115.FURN SYS 25 0.80 20/1 0.80 26 SPACE LO 114/115.FURN SYS 27 0.80 20/1 0.80 28 SPACE w E 114/115.FURN SYS 29 0.80 20/1 0.80 30 SPACE Drawing: 0 n 3 114/115.FURN SYS 31 0.80 20/1 0.80 32 SPACE II 114/115.FURN SYS 33 0.80 20/1 0.80 34 SPACE C14 m 114/115.FURN SYS 35 0.80 20/1 2.98 30 2.18 36 [A] AH-1 & CU-1 ONE-LINE DIAGRAM AND j 114/115.FURN SYS 37 0.80 20/1 2.98 2 2.18 38 - PANEL SCHEDULES o 114/115.FURN SYS 39 0.80 20/1 2.30 20 1.50 40 WH-1 - RR 110 c SPARE 41 20/1 1.50 2 1.50 42 - 0 0_ 2' LIGHTING LOAD @125% = 0.00 0.00 0.00 KVA NOTES PANEL LOAD LEGEND SHEET LEGEND � aRECEPTACLETTSTTURVW E Too°k+ REMAINDER@ 50%)= 5.56 5.37 4.65 KVA [A] PROVIDE HACR CIRCUIT BREAKER FOR HVAC LOAD. O AREA NUMBER LINE ID Job No: 21065 U N NON-CONTINUOUS LOAD @ B LOAD TYPE A PANEL + PER NEC 210.4(B) 100%= 0.00 1.50 1.50 KVA 0 SDP2 : I PROVIDE COMMON TRIP HANDLES R = RECEPTACLE B ONE-LINE Date: 10/19/2021 O CONTINUOUS LOAD @ 125%= 0.00 0.00 0.00 KVA C O � FOR ALL MULTI-CIRCUIT CONDUIT ^7 O RUNS. MOTORS+ N = N/AIPMENT ID TAG PANEL DIAGRAM Drawn By: - I N MOTOR= 2.73 0.00 2.73 KVA A � � TOTAL NEW PANEL A2 DEMAND Checked B - n N = 8.29 6.87 8.88 KVA C = COPY MACHINE GD = GARBAGE DISPOSAL SD = SMOKE DETECTOR y U CF = COFFEE H = HVAC/PLUMB TV = TELEVISION PANEL j0 ®2010-2021AKRIBIS Engineering, L.L.C. 2.81 TOTAL DEMAND AMPS= 69.12 57.28 74.02 AMPS CH = CHAIR M = MISC. LOAD V = VENDING Sheet No: DW = DISHWASHER MW = MICROWAVE WS = WORKSTATION A2 o y EDF= DRINKING FOUNTAIN PP = POWER POLE X = X-RAY LOAD N C F = FREEZER PF = PRINTER/FAX CALCS /a G = GENERAL RECEPT RF = REFRIGERATOR E5ml II m NOTE: CONTRACTOR SHALL PROVIDE PANEL LOAD LEGEND AS WELL AS UPDATED LINE CARD AT o PANELBOARD PER NEC 408.4.