Plans (19) M EC2020-00152 ROOFTOP UNIT SCHEDULE: etcel HVAC, INC TAG MFG. MODEL CONDITION TONS CFM COOLING HEATING ELECTRICAL WEIGHT NOTES NETMBH SEER EER INPUTMBH OUTPUTMBH AFUE VOLTAGE MCA MCOP CONTACT INFO: RTU- 2 CARRIER 48FCDA04 NEW 3 1200 34.5 14 11.5 67 54 81 460- 3 12 15 612 1, 2 MAIC P o.BOX 1188 CANBY.OR 97013 PHONE'.(971)930.7194 RTU- 3 CARRIER 48FCDA04 NEW 3 1200 34.5 14 11.5 67 54 81 460-3 12 15 612 1, 2 EMAIL JEREMY®ExCELWAC NET CCB 0 214346 RTU-4 CARRIER 48FCDA04 NEW 3 1200 34.5 14 11.5 67 54 81 460-3 12 15 612 1, 2 NOTES: 1) PROVIDE AND INSTALL NEW HONEYWELLVISION PRO THERMOSTAT PROJECT #: 2) UNIT WEIGHT INCLUDES ADDITIONAL ACCESSORY WEIGHT AS SHOWN 20-332 U U Z Lu UNIT HEATER SCHEDULE: o' ZJ HEATING ELECTRICAL ¢ U TAG MFG. MODEL CONDITION CFM WEIGHT NOTES 0 x INPUTMBH OUTPUTMBH I AFUE VOLTAGE HP MCOP N 1-- LU UH- 1 MODINE PDP200 NEW 2870 200 1 160 1 80 120- 1 1 1/6 1 30 1 239Q n � 0 NOTES: 0 LL O z O ~ 0 ¢ � U) of ON ` ) ofQ U_ o W C7 _ Z � ¢ AREA OF WORK RECEIVE U DID Z MAR 17 2020 U o it CITY OF TIGARD ui Z = a BUILDING DIVISIQr U) xo 0 D � ¢ ° m _j I-- cncn w � 19 O ¢ Z z � z U¢ Oit A 0- r` n 0 ¢ 0 z _ U) O W 0 Z F - w � Q = � U Q U) O U7 [Y T O F w � w W 0 < 0 J 0 U � w _ w o � PLEASE CIRCLE ONE: NOT FOR CONSTRUCTION FA PERMIT SET oSol } ONSITE SET AS-BUILT SET 1h1 • s� Approved plans �? shall be on job site. roteetiD OFFICE COPY' Sol D CITY OF TIGARD PACTRUST ADDRESS 15350 " REVIEW[;D 1710 It (-vlll: CODIPLTANCB SEQUOIA PARKWAY SUITE #300 PORTLAND,OR 97224 Approved: ] OTC: I ) REVISION: Permit #: Address: 7 %5�� a1H B Suite #: By' Date: 3 Z3_� A A DRAWN BY: DATE: Z.T.B. 02/20/2020 SHEET NO. 1 VICINITY MAP N M0.1 NTS LI I UF TiuAF�D pproved by Planning M o . 1 Date: — 311-1414 Initials: 10 11 12 13 14 15 16 17 e INC CONTACT INFO: MAIL.P O.BOX 1180 CANBY.OR 97013 SHEET NOTES: PHONEYCEXC LWA EMAIL:JEREMV�IXCELFNAC.NET 7374 CCB It 214345 DEMO ALL (E) SUPPLY AND PROJECT #: RETURN DUCTWORK BACK TO (E) 20-332 ROOFTOP UNIT SUPPLY AND RETURN DROPS r ^ v ! U Z ® (E) ROOFTOP UNIT TO REMAIN W o = FOR WAREHOUSE FREEZE U PROTECTION ` X r 2 W ® N = N �3 DEMO AND REPLACE (E) 0 o � Z Qo ® ROOFTOP UNIT WITH LIKE-IN-KINDQ O W Z = 2 TON Z V L � ~ Z 111 W h 1 7376 w wQ 0a [380 LBS z = o Z 0 M ¢ ~ J) V' W � k;f III U O - Q � U � r13 0 co z U 49 LBS - o � W U Z_ W LULU RTU - 2 7 U Q �D � U � xO ...,,..� _. I- C) D_ U W � O W JO 605 LBS 1 T w Ta oof PLEASE CIri RCLE ONE: 1NOT FOR CONSTRUCTION PERMIT SET ONSITE SET RTU 1 2 AS-BUILT SET RTU - 1 1 — 1 3 ON PACTRU ST ADDRESS.15350 SW SEQUOIA PARKWAY SUITE 9300 PORTLAND,OR 97224 REVISION: B B B B DRAWN BY: DATE: Z.T.B. 02/20/2020 - SHEET NO. 1 DEMO PLAN N mi . 0 Ml o 1/8"=11•0' 10 11 12 13 14 15 16 17 e�'cel CONTACT INFO: MAIL:P.O.BOX 1188 CANBY,OR 97013 PHONE.(971)930-7194 EMAIL'.JEREMYCEXCELHVAONET 7374 CCB#.214345 Ll PROJECT #: 20-332 U Z W O = U ZJ U w CV = 0 Er Z W Q O Z 0 F:< O 0 N Q O LU _ U Z ~ � � 4 7376 CD w ~_ Z v WW RTU W Q � � Z z0 Q ¢ O m J H RTU A (p W < 3 � M d 0- r.- U) 0 ZJ ¢ 0 . . ~ _ (n O _. LU U z F W Q (DU o > O o co a x0 � W W U � O RTUMIA Q 0 2 U Of L/) D_ W D tY PLEASE CIRCLE ONE: NOT FOR CONSTRUCTION PERMIT SET ONSITE SET RTU AS-BUILT SET PAcTRuST ADDRESS:15350 SW SEQUOIA PARKWAY SUITE #300 PORTLAND,OR 97224 REVISION: I B B B B DRAWN BY: DATE: ZT-B. 02/20/2020 SHEET NO. 1 ROOF PLAN .O 1,8"=11 M2 . 0 10 11 12 13 14 15 16 17 e 'ciel CONTACT INFO: MAIL:P.O.BOX 1189 CANBY•OR 97013 PHONE:(971)930-7194 EMAIL:JEREMY®E)(CELHVAC.NET 185 CFM 7374 CCB#214345 8"0(TYP.4) PROJECT #: E 20-332 2 e FFI E FI E 70 e 104 OF IC m Z ib I 0 C M m Om Ot U ® 1011, CSV Q 1010 r FOm w O z LL FF CE 8°0 0 a 0 H4 2 80 FM a' p W a Z = 0-„0 ® ♦ , Z F- X U W O � z CF 7376 WF 12' 4:.., �..�..� W a �,g -1 O 7 = Q S 140 f~/J z I I +,. , . r o LL d n Z :y:, a co o r Z J FM z O L* _t=_ J . I VA � _ E W OZ e � n � ww k-XV U � FM Q Do ® FO 0 127— I w cwi M w � I 1W � O U � e It E OPEN OFFICE F1_ io 0_01 PLEASE CIRCLE ONE: NOT FOR 72/9 CONSTRUCTION e PERMIT SET RTU WAREHOUSE ONSITE SET 09 \ / AS-BUILT SET ------- ------�+----�- - --------'/ PACTRUST JAN ADDRESS:15350 SW SEQUOIA PARKWAY SUITE 1 p #300 PORTLAND,OR 97714 000 4L__1fe REVISION: 8 B B 4D B DRAWN BY: DATE: Z.T.B. 02/21/2020 SHEET NO. M2 . 1 e�'cel HVAC, INC CONTACT INFO: MAIL P.O.BOX 1188 CANBV,OR 97013 CODE REQUIRED OA VENTILATION (RTU_ PHONE (971) LHV EMAIL: HOEMY®EXCG-7194 NET BASED ON 2014 OREGON MECHANICAL SPECIALTY CODE STANDARDS °°eIf21434e OMSC CODE REQUIREMENTS -TABLE 403.3 ZONE AIR ZONE CRITICAL REMARK ROOM(S) FLOOR AREA OCCUPANCY OCCUPANT LOAD OA REQUIREMENTS MIN. EXHAUST OCCUPANTS DISTRIBUTION DISTRIBUTION SPACE PROJE T #: SQ FT TYPE PEOPLEJ1000 SF Rp (CFM / PER) I Ra (CFM /SF) (CFM_l SF) TYPE EFFECT. (Ez) 20-332 OPEN OFFICE 101 WEST 1,789 OFFICE SPACE 5 5 0.06 - 9 CSCRH 0.8 1 TOTALS 1,789 5 1 0 9 RESULTS OF ASHRAE STANDARD 62.1 2009 ANALYSIS BASED ON DATA ABOVE CIOz VENTILATION SYSTEM EFFICIENCY (Ev) 96% I ' ' m Q OUTDOOR AIR INTAKE REQUIRED FOR SYSTEM (Vot) 187 CFM U F- 187 OUTDOOR AIR PER UNIT FLOOR AREA (VoUAs) 0.09 CFM/ SF < X OUTDOOR AIR PER PERSON SERVED (VoUPs) 17.7 CFM/ P IN ~= 0 111 N OUTDOOR AIR AS A% DESIGN PRIMARY SUPPLY AIR 12% OA Z m _ - 2 Oz REMARKS (OA SOURCE) ° I- O �_ Q ~2Q - 1. REQUIRED DESIGN MINIMUM OA (17%)PROVIDED FROM RTU-2 W/ACTUAL MINIMUM OA (20%) w p Fr 2. AVERAGE ZONE OCCUPANCY REPORTED USING REDUCTION OF UP TO MAXIMUM 50% AS ALLOWED PER OMSC SECTION 403.3 W < LL oz 3. AVERAGE ZONE OCCUPANCY REPORTED BASED ON ARCHITECT/OWNER INPUT AND FIXED SEATING ALLOWANCES PER OMSC SECTION 403.3 1- L > 4. OUTSIDE AIR REQUIREMENT MET BY TRANSFER AIR IN ACCORDANCE WITH SECTION 403.2.2. r , W 1-7 Q a v Ux _ww W02o U n. t Z = a � V) IY o 0 < = C/) m zF (n U) wa CODE REQUIRED OA VENTILATION (RTU-3) o Z BASED ON 2014 OREGON MECHANICAL SPECIALTY CODE STANDARDS Q v orl- 0 OMSC CODE REQUIREMENTS -TABLE 403.3 ZONE AIR ZONE CRITICAL REMARK 0 M z w ROOM(S) FLOOR AREA OCCUPANCY OCCUPANTLOAD OA REQUIREMENTS MIN. EXHAUST OCCUPANTS DISTRIBUTION DISTRIBUTION SPACE n ¢ -' O SQ FT TYPE PEOPLE/1000 SF Rp (CFM / PER) Ra (CFM / SF) (CFM / SF) TYPE EFFECT. (Ez) _ LOBBY 100 428 LOBBIES 150 5 0.06 10 CSCRH 08 4 W O Z OFFICE 102 93 OFFICE SPACE 5 5 0.06 1 CSCRH 0.8 OFFICE 103 98 OFFICE SPACE 5 5 0.06 1 CSCRH 0.8 w OFFICE 104 135 OFFICE SPACE 5 5 0.06 1 CSCRH 0.8 Q OFFICE 105 158 OFFICE SPACE 5 5 0.06 1 CSCRH 08o O >_ TOTALS 912 25 0 14 o Df FO 0 � w RESULTS OF ASHRAE STANDARD 62.1 2009 ANALYSIS BASED ON DATA ABOVE o Q VENTILATION SYSTEM EFFICIENCY (Ev) 89o7a on-OUTDOOR AIR INTAKE REQUIRED FOR SYSTEM (Vot) T 131 CFM LU OUTDOOR AIR PER UNIT FLOOR AREA (VoVAs) 0.14 CFM / SF OUTDOOR AIR PER PERSON SERVED (VoVPs) 10.5 CFM / P OUTDOOR AIR AS A % DESIGN PRIMARY SUPPLY AIR 11% OA PLEASE CIRCLE ONE: REMARKS (OA SOURCE) NOT FOR 1. REQUIRED DESIGN MINIMUM OA (17%)PROVIDED FROM RTU-3 W/ ACTUAL MINIMUM OA (20%) CONSTRUCTION 2. AVERAGE ZONE OCCUPANCY REPORTED USING REDUCTION OF UP TO MAXIMUM 50%AS ALLOWED PER OMSC SECTION 403.3 3. AVERAGE ZONE OCCUPANCY REPORTED BASED ON ARCHITECT/OWNER INPUT AND FIXED SEATING ALLOWANCES PER OMSC SECTION 403.3 4. OUTSIDE AIR REQUIREMENT MET BY TRANSFER AIR IN ACCORDANCE WITH SECTION 403.2.2. PERMIT SET ONSITE SET CODE REQUIRED OA VENTILATION (RTU-4) BASED ON 2014 OREGON MECHANICAL SPECIALTY CODE STANDARDS OMSC CODE REQUIREMENTS -TABLE 403.3 ZONE AIR ZONE CRITICAL REMARK AS-BUILT SET ROOM(S) FLOOR AREA OCCUPANCY OCCUPANT LOAD OA REQUIREMENTS MIN. EXHAUST OCCUPANTS DISTRIBUTION_ DISTRIBUTION SPACE SQ FT TYPE PEOPLE/1000 SF Rp (CFM / PER) Ra (CFM I SF) (CFM / SF) TYPE EFFECT. (Ez) OPEN OFFICE 101 EAST 1,209 OFFICE SPACE 5 5 0.06 7 CSCRH 0.8 WOMEN'S 107 118 OFFICE SPACE 5 5 0.06 1 CSCRH 0.8 MEN'S 108 118 OFFICE SPACE 5 5 0.06 - 1 CSCRH 0.8 TOTALS 1 1,445 1 15 0 1 9 RESULTS OF ASHRAE STANDARD 62.1 2009 ANALYSIS BASED ON DATA ABOVE VENTILATION SYSTEM EFFICIENCY (Ev) 97% OUTDOOR AIR INTAKE REQUIRED FOR SYSTEM (Vot) 127 CFM OUTDOOR AIR PER UNIT FLOOR AREA (VoVAs) 0-09 CFM / SF OUTDOOR AIR PER PERSON SERVED (VoUPs) 17.5 CFM / P OUTDOOR AIR AS A% DESIGN PRIMARY SUPPLY AIR 10% OA REMARKS (OA SOURCE) 1. REQUIRED DESIGN MINIMUM OA (17%) PROVIDED FROM RTU-4 W/ACTUAL MINIMUM OA (20%) PA CTR U ST 2. AVERAGE ZONE OCCUPANCY REPORTED USING REDUCTION OF UP TO MAXIMUM 50% AS ALLOWED PER OMSC SECTION 403.3 3. AVERAGE ZONE OCCUPANCY REPORTED BASED ON ARCHITECT/OWNER INPUT AND FIXED SEATING ALLOWANCES PER OMSC SECTION 403.3 QUOTA PARKWAY SW SEQUOIA PARKWAY SUITE 4. OUTSIDE AIR REQUIREMENT MET BY TRANSFER AIR IN ACCORDANCE WITH SECTION 403.2.2. #300 PORTLAND,OR 97224 REVISION: A 8 B B DRAWN BY: DATE: Z.T.B. 02/212020 SHEET NO. M2 . 1