TUALATIN VALLEY WATER DISTRICT Test#: 1361
FIRE HYDRANT FLOW TEST REPORT Hydrant ID #: 2S1W01A25FH50
Location: SW 72ND AVE & SW ELMHURST ST Date: 4/9/2019
Test made by: PAUL &COLTON RECEIVED
Witness: Time: 11:14 DEC 3 0 2021
Project name: CITY OF TIGARD
BUILDING DIVISION
Discharge coefficient: .54816
Inside dia. of outlet = 4.5 inches
Pitot reading = 50 psi Pitot 2 = 0 psi
Observed flow rate= 2340.6 gpm
Flow method: HOSE MONSTER
Static pressure: 110 psi Residual pressure: 68 psi
Flow at 20psi residual pressure (calculated): 3532 gpm
Location map: To be attached to test report and to show which hydrants were
used to monitor residual pressure and flow. y��7
Gage information: //<<
Static and residual pressure gage: 120997-2C Pitot gage: 9864E1
Hydrant information:
Hydrant ID Year Make Notes
Flow hydrant: 2S1W01A25FH50 2006 MUELLER see map for location
Read hydrant: 2S1W01A26FH50 2012 MUELLER see map for location
Remarks:
The mapping, flow or pressure information contained herein reflects conditions on the date and
time of the test. Tualatin Valley Water District makes no representation as to the system's
ability to meet specific fire flow requirements. Future system capability may differ from the
flows reported herein because of subsequent modifications to the district's system and/or
because flow and pressure may vary by time of day and season. Test gage callibration
information available upon request.
I
e 66
22GV;
. [...-
'j' 6'GY70� 2.80
co
6 g m pm
tiZ,
2 6`DCDA
xe. y
¢ '� DARTiv OUT- it GV ST.
A
ry r 16,32V 16.81V m
N .`s1 •'6-GV 16 RED
4.
498
00
2.ORP
1
Li
/ in6•GV
Q 6-DCOA
pi/1 1
6., 2 <
____
..Ng 6:01 :.CV
l' V.I
G,'
ELMHURST ST• gob, �MHURST
OPTS
r a
� ..
iv 6•GV
DCDA
tic II
r 0 I
12._ P--/-1Ric :::
LUBY11 .•,e ,- ,�
( .-{tSW 6c,Qe lila - o
II: FR/
DC. III
6 UML-Li O NIw -� 12 6N
6.G, R�x6 2-gFy 0, U . D all!
cv
,
12.8N
I BEVEL/AND ST ' r
TUALATIN VALLEY WATER DISTRICT Test#: 1361
FIRE HYDRANT FLOW TEST REPORT Hydrant ID #: 2S1W01A25FH50
Location: SW 72ND AVE & SW ELMHURST ST Date: 4/9/2019
Test made by: PAUL &COLTON
Witness: Time: 11:14 RECEIVED
Project name: DEC 3 0 2021
CITY OF TIGARD
Discharge coefficient: .54816 BUILDING DIVISION
Inside dia. of outlet = 4.5 inches
Pitot reading = 50 psi Pitot 2 = 0 psi
Observed flow rate = 2340.6 gpm
Flow method: HOSE MONSTER
Static pressure: 110 psi Residual pressure: 68 psi
Flow at 20psi residual pressure (calculated): 13532 gpm I 74.-i
Location map: To be attached to test report and to show which hydrants were ,, � aczi
used to monitor residual pressure and flow. V/` `7
Gage information: /`
Static and residual pressure gage: 120997-2C Pitot page: 9864E1
Hydrant information:
Hydrant ID Year Make Notes
Flow hydrant: 2S1 W01A25FH50 2006 MUELLER see map for location
Read hydrant: 2S1W01A26FH50 2012 MUELLER see map for location
Remarks:
The mapping, flow or pressure information contained herein reflects conditions on the date and
time of the test. Tualatin Valley Water District makes no representation as to the system's
ability to meet specific fire flow requirements. Future system capability may differ from the
flows reported herein because of subsequent modifications to the district's system and/or
because flow and pressure may vary by time of day and season. Test gage callibration
information available upon request.
f
V/ II I U V 1
7C , - 22GV��
D 0Fr Ircy
6•DC-$6.6V
m� '' $ "�" 6 �c>i 2'80
m^ m
Nj� I
DARTIOUTH Zf2 6V ST.
U q >
16�FV m '�mv ry 16'ifi V "WV i6•x12' _
u�. �u 'O 16•DI RED ;1
426 2:O /'r 12'BN'.1
o 4 r 498
2•CV;.i CV
6•DCDh I;
m'2 ORP
LiJ
i 1 in6•C_V
Q e DCDA
< ... _____
K ..
_.
:,... g
-"f 7, Ile C.
I wm6CV
6•CV `' M H U R S T
I Cr'S ELMHURST ST. GV6 ice.
,y
Z I r�
m �_�
I
I I , Li
ocoA1
•I
mss
ON
•
/ 6-0,C- .77
_________.
1.15.4Rt O ■ _
L .e.z..
1.84
1z• /z sw
„a. � m
R�12BN ►►EVELANDal
I [3EVELAND ST
•
A,.... >.00DA .- NI'��1�