Correspondence M-G ' OUP Design•Consulting•Value Engineering Massaad Engineering croup Inc. rt , I, (...,, ///3 (Si-) g/ I- ivi To: David Young From: Ibrahim Jaalouk CC: Date: May 26,2022 Job#: 2143 Re: Inspection Hello, The following is a response to a failed inspection report by Inspector. ITEM SI: All windows with a single trimmer are 5'-0"or less are structurally acceptable. ITEM S2: Beam per plan was supposed to be installed as dropped.However,contractor installed the beam top of wall with existing trusses hanging from its side.It is structurally acceptable as installed. ITEM S3: Each gable end has one brace at midspan.Contractor to add(2)more braces at each gable end per detail 2/S4 on each side of the existing brace. Please call our office if you have further questions. CTu� Respectfully Submitted, y04G INsr. c, Massaad Engineering Group Inc., � 5 520 Ibrahim Jaalouk Project Engineer C PQ EXPIRATION DATE. 12-31.2022 6775 SW 111'Ave,Suite 20 Beaverton,OR 97008 Tel:503-486-5387;Fax 503-486-5097 www.mgroupengineenng.com