High Wall Heat Pump Ductless System
Indoor Model: 40MHHQ24---3
Submittal Data
Job Data: Location:
Buyer: Buyer P.O.#: Carrier#:
Unit Number: Model Number:
Performance Data Certified By: Date:
STANDARD FEATURES
•Up-Down Louver control(fixed or swing)
•Remove filter from the top
•Improved serviceability with easy access to fan and electrical
connections
„� ,,.� •. � .. •Four fan speeds
•Sleep Mode
y� / •Follow Me(senses temperature at handheld remote)
RECEIRECEIVED •Quiet operation
VED• LL��LL.�� •Aluminum Blue Hydrophilic pre-coated fins
al
„JUL 0 6 ZOZ Controls:
•Wireless Remote Controller included with indoor unit
CITY OF TIGARD •Optional Wired Remote Controller KSACNO401AAA
BUILDING DIVISION LIMITED WARRANTY*
•10 year limited to original purchaser on compressor and parts upon
timely registration,otherwise 5 years
*For residential applications.See warranty for full details.
System Size 24 Face Area(sq.ft.) I Sq.Ft. 2.58
Indoor Model 40MHHQ24---3 No.Rows 2
Indoor Coil
Voltage,Phase,Cycle V/Ph/Hz 208/230-1-60 Fins per inch 20
Electrical Power Supply Powered from outdoor unit Circuits 2
MCA A. 0.45 Unit Width in(mm) 43.83(1113)
Controls Wireless Remote Controller(°F/°C Convertible) Standard Unit Height in(mm) 13.41 (341)
Wired Remote Controller(°F/°C Convertible) Optional Unit Depth in(mm) 9.22(234)
Operating Cooling Indoor DB Min-Max °F(°C) 63-90(17-32) Net Weight lbs(kg) 40.12(18.2)
Range Heating Indoor DB Min-Max °F(°C) 32-86(0-30) Number of Fan Speeds 4
Pipe Connection Size-Liquid in(mm) 3/8(9.52) Indoor Airflow(lowest to highest) CFM 353/483/589/647
Piping
Pipe Connection Size-Suction in(mm) 5/8(16) Sound Pressure(lowest dB(A) 38/42/48/49
to highest)
Air throw Data ft(m) 37.7(11.5)
Moisture removal Pint/h(L/h) 5.73(2.71)
Field Drain Pipe Size O.D. in(mm) 0.625(16)
Performance may vary based on the outdoor unit matched to.See compatible outdoor units pages for Performance Data.
Accessories
53DS-900---118 Condensate Pump(208/230V)
KSACNO401AAA Wired Remote Control 7 Day Programmable
Copyright 2017 CAC/BDP•7310 W.Morris St. Indianapolis,IN 46231 Edition Date:02/2017 Catalog No:40MHHQ-24-3-01SB
SUBJECT TO CHANGE WITHOUT NOTICE Page 1 Replaces:NEW
Compatibility Table
Indoor Unit 40MHHQ24---3
Outdoor Unit 38MHRQ24A--3
Construction View
Indoor Model: 40MHHQ24---3
r—JIi2ii[317] 12.47 C3173�'
I 1--1600 C279]-- 11,00 C2793—� !
9.75 C2481— 9.75 C2483
IU
.. (; J! DHJjT
u hd
ll!
2.17 C553 — 2,12 C543 16.10 (4093 2.17 (551
I I 1/,85 C453] 7.46 01e9]
43.52 111063 _
. .
Si_
41
r-1 fR J
L 43.83 C1113] .1 0.61 C163
, i
_ _i......,
.1 . I r . a
r 0
rci,
0.97 122]-..1
_ - - - I I I �s -/
0.79 C201
0.61 C157 0.71 C18] 2.39 1611
1.99 050]- 0.63 C163 1.99 1501
2.39 (61] 1.10 C28] 0,62 E163
! 20.31 C5161 1 ! ui,_ — — i• i — — li, �I
11 Mill-- MM MI Ill III II��1�lMO—N�ltll mil
1 21,18 [5387 l �11- �1-r 1I1— .� IMO:11 _1�
I,` I 1 .� JI �I
c(,terar• us c
.ftu:Ml CERTIFIED
RnreO Onetv,WWI Iv
ANAIStaxt.de 719141
Copyright 2017 CAC/BDP.7310 W.Moms St. Indianapolis,IN 46231 Edition Date:02/2017 Catalog No:40MHH0-24-3-01SB
SUBJECT TO CHANGE WITHOUT NOTICE Page 2 Replaces:NEW
38MHR
Outdoor Unit Single Zone Ductless System b
Sizes 09 to 24
Product Data
INDUSTRY LEADING
FEATURES /BENEFITS
A PERFECT BALANCE BETWEEN
��\ BUDGET LIMITS,ENERGY SAVINGS AND
�', `�� COMFORT.
PO� a The 38MHR series ductless systems are a matched combination of
y'j�illi }1 )? an outdoor condensing unit and an indoor fan coil unit connected
1t\ \1�*41' i/Of ' only by refrigerant tubing and wires.
,�,�'x' ' The ductless system permits creative solutions to design problems
� '
� '' such as:
• Add—ons to current space (an office or family room
addition)
4 1 I
NOTE: Images are for illustration purposes only. Actual models • Special space requirements
may differ slightly. • When changes in the load cannot be handled by the
existing system
• When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork
• Historical renovations or any application where
preserving the look of the original structure is essential.
The ideal compliment to your ducted system when it is impractical
or prohibitively expensive to use ductwork.
The compact indoor fan coil units take up very little space in the
room and do not obstruct windows.The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
Inverter Technology Fast Installation
The inverter driven compressor is designed to run at various input This compact ductless system is simple to install.Only wires and
power frequencies (Hz) which controls the compressor's motor piping need to run between the indoor and outdoor units. These
speed. units are fast and easy to install ensuring minimal disruption to
Even Temperature—The control package,including the inverter, customers in homes or the workplace. This makes these systems
monitors the outdoor and indoor temperatures as they relate to the the equipment of choice for retrofit applications.
selected indoor set point and adjusts the compressor speed to match Simple Servicing and Maintenance
the load and keep the system operating continuously rather than Removing the top panel of the outdoor unit provides immediate
cycling and creating temperature swings.This translates to higher access to the control compartment,providing the service technician
comfort levels for the occupants. access to the diagnostic LEDs to facilitate the troubleshooting
Rapid Pull Down/Warm—Up — Comfort is increased by the process. In addition, the draw—thru design of the outdoor unit
inverter system's ability to ramp up the compressor speed enabling means that dirt accumulates on the outside surface of the coil.Coils
the system to reach the user selected room temperature set point can be cleaned quickly from the inside using a pressure hose and
quicker. detergent.
Humidity Control—Running the system for longer periods and On the indoor units, service and maintenance expense is reduced
continuously varying the compressor speed enhances the humidity due to the permanent easy to clean filters.Also, error codes are
control.
displayed on the front panel to alert the user to certain system
Individual Room Comfort malfunctions
F Maximum comfort is provided because each space can be Built—in Reliability
controlled individually based on the usage pattern. Ductless system indoor and outdoor units are designed to provide
Low Sound Levels years of trouble—free operation.
When noise is a concern, ductless systems are the answer. The Both the indoor and outdoor units are well protected.Whenever
the microprocessor detects abnormal conditions,the unit stops and
indoor units are whisper quiet.There are no compressors indoors, P P
either in the conditioned space or directly over it,and there is none an error code appears.
of the noise usually generated by air being forced through the Inverter systems provide additional reliability due to the soft start.
ductwork. This refers to the ability of the inverter to start the compressor
When sound ordinances and proximity to neighbors demand quiet motor using reduced voltage and reduced current. This feature is
operation,this outdoor unit is the right choice.With the inverter beneficial from an electrical standpoint(eliminates current spikes)
technology, these units run at lower speeds most of the time as well as an overall reliability standpoint due to reduced stress on
resulting in reduced sound levels. all associated system components.
Inverter Technology—Enhanced Economical Agency Listings
Operation All systems are listed with AHRI(Air conditioning,Heating,and
Ductless systems are inherentlyeconomical to operate.Individual Refrigeration Institute) and are ETL certified per UL 1995
y P standard.
rooms are heated or cooled only when required,and since the air is
delivered directly to the space,there is no need to use additional
energy to move the air in the ductwork.This economical operation
is enhanced further when the inverter system output matches the
load resulting in a more efficient system.
Easy—To—Use Controls
The systems have microprocessor—based controls to provide the
ultimate in comfort and efficiency. The user friendly wired and
wireless remote controls provide the interface between the user and
} the unit.
Secure Operation
1, If security is an issue,outdoor and indoor units are connected only
by refrigerant piping and wiring to prevent intruders from crawling
through ductwork or wall openings.In addition,since the outdoor
-il
unit can be installed close to an outside wall,coils are protected
°i from vandals and severe weather.
y
Alt
K,f
2
MODEL NUMBER NOMENCLATURE
OUTDOOR UNIT
38 MH R O 09 A —— 3
38=OUTDOOR UNIT
VOLTAGE
1 =115-1-60
MH=MODEL 3=208/230-1-60
UNIT TYPE
R=OUTDOOR UNIT
SYSTEM TYPE
C=COOLING ONLY
O=HEAT PUMP NOT USED
NOMINAL CAPACITY
09—3/4 TON
12—1 TON MAXIMUM NUMBER OF FAN COIL UNITS THAT
18—1-1/2 TONS CAN BE CONNECTED TO THE OUTDOOR UNIT
24—2 TONS A=1:1
A `Nt ER TFM
■..1 CERTIFIED:.
Use of the AHRI Certified
TM Mark indicates a C US
manufacturer's L33TFD
participation in the
program For verification
of certification for individual
products,go to
www.ahridirectory.org.
3
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation OUTDOOR UNITS
i Low Voltage Controls S Crankcase Heater
Comfort Features
11
:i Microprocessor Controls S
The crankcase heater is standard on all unit sizes.Heater clamps
Auto Restart Function S must be placed around the compressor oil stump.
Auto Changeover S
Energy Saving Features
Inverter Driven Compressor S
46°F Heating Mode(Heating Setback) S
Safety And Reliability
3 Minute Time Delay For Compressor S
? High Compressor Discharge Temperature S
E; Low Voltage Protection S
Compressor Overload Protection S
Compressor Over Current Protection S
EA' IPM Module Protection S
Condenser High Temp Protection in Cooling Mode S
Aluminum Blue Hydrophilic pre—coated fins S
l Ease Of Service And Maintenance
Diagnostics S
Liquid Line Pressure Taps S
T Application Flexibility
Crankcase Heater S
Legend
1 S Standard
A Accessory
I
t.i
i
a
r
th
k
rh
li
,I
A
I
ii
ii
ft
DIMENSIONS - OUTDOOR
System Size Height(H)In.(mm) Width(W)in.(mm) Depth(D)in.(mm) Weight-Net lbs.(kg)
9K (115) 21.85(555) 30.31(770) 11.81(300) 57.3(26)
12K (115V) 21.85(555) 30.31(770) 11.81(300) 57.8(26.2)
Cooling 9K (208/230V) 21.85(555) 30.31(770) 11.81(300) 54.7(24.8)
Only
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 53.8(24.4)
18K (208/230V) 21.81(554) 31.50(800) 13.11(333) 70.1(31.8)
24K (208/230V) 27.64(702) 33.27(845) 14.29(363) 88.6(40.2)
System Size Height(H)In.(mm) Width(W)In.(mm) Depth(D)in.(mm) Weight-Net lbs.(kg)
9K (115) 21.85(555) 30.31(770) 11.81(300) 61.5(27.9)
12K (115V) 21.85(555) 30.31(770) 11.81(300) 65.0(29.5)
Hest 9K (208/230V) 21.85(555) 30.31(770) 11.81(300) 57.1(25.9)
Pump
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 60.6(27.5)
18K (208/230V) 21.81(554) 31.50(800) 13.11(333) 94.6(42.9)
1 all (208/230V) 27.64(702) 33.27(845) 14.29(363)
30.66(779) W3
to
in
H (101«1111011140 c °
o
I'll - -
_=-_I --7_.,._f
19.17(487) W1
11.81(300) D 30.31(770) W
m I \2.76(70) W
0.98(251) B1
0
D2 D3 1�
is fl, , a-.-
J� M
, p N �
- I i
fi ii \ (0 1
0, 1
c\i 2.42(61.5)'A2
H1
.011
a i H2 Fr
ril Unit:inch(mm)
rn �� 0.47(1 Al
m
ri
Fig.1-Sizes 9K and 12K
5
E
DIMENSIONS—OUTDOOR(CONT)
ft-----''a fr. Loh,,,iiii .
,ems, -�
/eZ.\ V H
I1 ro I/�/�_.\il1013) 6 0
\``
N
13.11 (333)
20.24(514) W1
D 31.50(800) 2.76(7 0)
W W2
g
;tit• I - t B2 2.43(6 1.8)
c 61
o
n
..•. i 1
I
17311 ifi
,eN D2 � D3 - - - - I D1
rn
pip N ...
M
Oru I m
Cy o
,-'�
i'+1 .4.00
'0'9�R 0.87(2 2)
?al Al �0zA1R61
G
g H2 I 1
M
M
2.43(6 1.6)
A2 Unit: inch(mm)
Fig.2-Size 18K
,f
6
DIMENSIONS— OUTDOOR(CONT)
27.64(855)W3
g$%fl \
H ,); ( )
II��IIIIIgliet���'�� ����i�� i� �► Illl��l�
V\ , -.10..'
.7ZSI.....".:.:.r"' 1//,1 (
j IL il _., --,
c)
13.66(347) D N 21.26(540)A
0
33.27(845) W
35.98(914) WI
t� 1.10(28)
I i � - C w
D2 D3 'i; \ %, i ///
2 rii I •
Mk-y-4 R
_____________7 ill 1
`r / n
1 %\ ' ' 2
Rl
0 0 0 7.83(199)A2
MI1�11� H1 . .
Feirt-eil
. IU H2
miii 1.42(36) A3
(U
VD
PS
Unit: inch (mm)
Fig.3—Size 24K
7
CLEARANCES- OUTDOOR
A
Air-inlet
B C
,,;,,,-
_. Ion ---,--2-.,,,,:-,.,.,,-7-.,-----
,_A----.---,T--„,--.-,....-.,--„,,-,,,,•
s O
Air-outlet 0
ifr
A07894
Fig.4—Outdoor Unit Clearance
UNIT MINIMUM VALUE In.(mm)
A 24(610)
B 24(610)
C 24(610)
D 4(101)
E 4(101)
NOTE:The outdoor unit must be mounted at least 2in.(50mm)above the maximum anticipated snow depth.
8
SPECIFICATIONS - OUTDOOR COOLING ONLY
COOLING ONLY
Size 9 12 9 12 18 24
System Outdoor Model 38MHRCO9A--1 38MHRC12A--1 38MHRCO9A--3 38MHRC12A--3 38MHRC18A--3 38MHRC24A--3
Voltage,Phase,Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Electrical MCA A 13 13 7 7 11 16
MOCP-Fuse Rating A. 20 20 15 15 15 25
Operating Cooling Outdoor DB Min „F("C) 0-122
Range -Max (-17-50) 0-122(-17-50) 0-122 -17-50) 0-122(-17-50) 0-122(-17-50) 0-122(-17-50)
Total Piping Length ft(m) 82(25) 82(25) 82(25) 82(25) 98(30) 164(50)
Piping Lift* ft(m) 32(10) 32(10) 32(10) 32(10) 65(20) 65(20)
Piping Pipe Connection In.(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8
Size-Liquid (9.52)
Pipe Connection In.(mm) 3/8(9.52) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(16)
Size-Suction
Type R410A R410A R410A R410A R410A R410A
Refrigerant Charge lbs(k9) 1.06(0.48) 1.30(0.59) 1.06(0.48) 1.30(0.59) 2.09(0.95) 2.64(1.20)
Metering Device EEV EEV EEV EEV EEV EEV
Face Area Sq.Ft 4.15 4.15 4.15 4.15 4.78 4.78
No.Rows 1 1 1 1 2 2
Outdoor Coil
Fins per inch 22 22 22 22 22 22
Circuits 2 2 2 2 4 6
Type Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter
Model ASN98D22UFZ ASN98D22UFZ ASN98D22UFZ ASN98D22UFZ ASM135D23UFZ ATF235D22UMT
Compressor Oil Type VG74 VG74 VG74 VG74 VG74 VG74
Oil Charge FI.Oz. 13.0 13.0 13.0 13.0 13.0 23.6
Rated Current RLA 9.0 9.5 4.5 4.5 7.0 11.0
Unit Width In.(mm) 30.31(770) 30.31(770) 30.31(770) 30.31(770) 31.50(800) 33.27(845)
Unit Height In.(mm) 21.85(555) 21.85(555) 21.85(555) 21.85(555) 21.81(554) 27.64(702)
Unit Depth In.(mm) 11.81(300) 11.81(300) 11.81(300) 11.81(300) 13.11(333) 14.29(363)
Outdoor
Net Weight lbs(kg) 57.3(26) 57.8(26.2) 54.7(24.8) 53.8(24.4) 70.1(31.8) 88.6(40.2)
Airflow CFM 506 506 506 506 518 553
Sound Pressure dB(A) 50.5 52.0 53.0 54.0 57.0 59.5
*Condensing unit above or below the indoor unit
COMPATIBILITY TABLE
INDOOR UNIT OUTDOOR UNIT
38MHRCO9A--1 38MHRC12A--1 38MHRCO9A--3 38MHRC12A--3 38MHRC18A--3 38MHRC24A--3
40MHHC09---1 •
40MHHC12---1 •
High Wall 40MHHC09---3 •
40MHHC12---3 •
40MHHC18---3 •
40MHHC24---3 •
-------
PERFORMANCE
Indoor Model 40MHHC09---1 40MHHC12---1 40MHHC09---3 40MHHC12---3 40MHHC18---3 40MHHC24---3
Energy Star NO NO NO NO NO NO
Cooling System Tons 0.8 1.0 0.8 1.0 1.5 2.0
High Wall Cooling Rated Capacity Btu/h 9,000 12,000 9,000 12,000 18,000 24,000
Cooling Cap.Range Btu/h 4400-10200 4800-13200 4400-10000 4800-13000 5800-18600 9400-25200
Min-Max
SEER 16.6 17.3 16.0 16.5 17.0 17.5
EER 11.6 10.7 10.6 10.8 10.5 10.9
9
SPECIFICATIONS - OUTDOOR HEAT PUMP
HEAT PUMP
Size 9 12 9 12 18 24 ,
System
-
Outdoor Model 38MHRW9A--1 38MHRQ12A--1 38MHRQ09A--3 38MHRO72A--3 38MHR018A--3 38MHRO24A--3
Voltage,Phase,Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Electrical MCA A. 13 13 8 10 15 18
MOCP-Fuse Rating A. 20 20 15 15 20 25
Cooling Outdoor DB °F(°C) 0-122(-17-50) 0-122(-17-50) 0-122(-17-50) 0-122(-17-50) 0-122(-17-50) 0-122(-17-50)
Operating Min-Max
Range Heating Outdoor DB
Min-Max °F(C) 0-86(-17-30) 0-86(-17-30) 0-86(-17-30) 0-86(-17-30) 0-86(-17-30) 0-86(-17-30)
Total Piping Length ft(m) 82(25) 82(25) 82(25) 82(25) 98(30) 164(50)
Piping Lift' ft(m) 32(10) 32(10) 32(10) 32(10) 65(20) 65(20)
Piping Pipe Connection In.(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.52)
Size-Liquid
Pipe Connection In.(mm) 3/8(9.52) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(16)
Size-Suction i
Type R410A R410A R410A R410A R410A R410A
Refrigerant Charge lbs(kg) 1.76(0.80) 2.11(0.96) 1.76(0.80) 2.11(0.96) 2.82(1.28) 3.97(1.80)
Metering Device EEV EEV EEV EEV EEV EEV
Face Area Sq.Ft 4,1 4.1 4.1 4.1 4.7 5.3
No.Rows 1 1.5 1 1.5 2 2
Outdoor Coll . -
Fins per inch 18 18 18 18 18 18
Circuits 2 4 2 4 4 4
Type Rotary Invader Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter
Model ASN98D22UFZ ASN98D22UFZ ASN98D22UFZ ASN98D22UFZ ASM135D23UFZ ATF235022UMT
Compressor Oil Type VG74 VG74 VG74 VG74 VG74 VG74
Oil Charge Fl.Oz. 13.0 13.0 13.0 13.0 15.8 23.6
Rated Current RLA 9.0 9.5 5.5 6.8 10.5 12.0
Unit Wdth In.(mm) 30.31(770) 30.31(770) 30.31(770) 30.31(770) 31.50(800) 33.27(845)
Unit Height In.(mm) 21.85(555) 21.85(555) 21.85(555) 21.85(555) 21.81(554) 27,64(702)
Unit Depth In.(mm) 11.81(300) 11.81(300) 11.81(300) 11.81(300) 13.11(333) 14.29(363)
Outdoor Net Weight lbs(kg) 61.5(27.9) 65.0(29.5) 57.1(25.9) 60.6(27.5) 94.6[442.911 105.2)47.
71
Airflow CFM 506 506 506 506 518 553
Sound Pressure dB(A) 52.0 53.0 54.0 53.0 57.0 60.1
*Condensing unit above or below the indoor unit
COMPATIBILITY TABLE
OUTDOOR UNIT
INDOOR UNIT
38MHROO9A--1 38MHRO12A--1 38MHROO9A--3 38MHRQ12A--3 38MHRQ18A--3 38MHRO24A 3
40MHHQO9---1 •
40MHHQ12---1 • ',
4OMHHQO9---3 •
High Wall
40MHHQ12---3 •
40MHHQ18---3 • -1
40MHHQ24---3 •
PERFORMANCE
Indoor Model I 40MHH009---1 40MHHQ12---1 40MHH009---3 40MHHQ12---3 40MHH018---3 40MHH024---3
Energy Star NO NO NO NO NO NO
Cooling System Tons 0.8 1.0 0.7 1.0 1.5 1.8
Cooling Rated Capacity Btu/h 9,000 12,000 8,500 12,000 18,000 22,000
Cooling Cap.Range Min-Max Btu/h 2400-10500 3000-12500 2400-10000 3000-12500 3500-19800 4000-24200
SEER 16.0 16.8 16.0 17.0 16.0 16.8
EER 11 10.8 10.5 10.9 11 10.5
Heating Rated Capacity(4AF) Btu/h 9,800 12,000 9,800 12,000 18,000 25,000
High Wall
Heating Rated Capacity(17°F) Btu/h 6,000 7,200 6,000 7,200 10,200 15,000
Heating Maximum Capacity(1AF) Btu/h 6,470 8,520 6,580 8450 11830 18,100
Heating Maximum Capacity(5°F) Btu/h 6,150 9000 6070 8880 10150 16760
Heating Cap.Range Min-Max Btu/h 2500-11800 3000-12800 2500-11800 3000-12800 3500-19800 4000-24200
HSPF 9.0 9.0 9.0 9.0 9.0 9.0
COP(4AF) W/W 3.06 3.10 3.08 3.20 3.22 2.90
COP(17F) W/W 8.40 8.20 8.20 8.20 8.00 7.60
COP(5°F) W/W 1.80 1.60 1.60 1.60 1.50 1.40
10
COOLING PERFORMANCE DATA - (COOLING ONLY)
COOLING OUTDOOR CONDITIONS(DB)
MODEL indoor Conditions OF 5F 17F 47F 77F 86F 95F 104F 113F 122F
DB UVB (-17C) (-15C) (-8C) (8C) (25C) (30C) (35C) (40C) (45C) (50C)
69.8E 59F TC 6.13 6.25 6.87 7.90 7.86 8.83 8.28 8.08 6.49 3.64
(21 C) (15C) SC 5.08 5.24 5.52 5.63 5.60 6.05 5.79 5.67 4.95 3.58
Input 0.20 0.21 0.24 0.29 0.55 0.84 0.92 1.11 0.99 ' 0.78
752E 62.6E TC 6.53 6.67 7.33 8.42 8.47 10.46 9.43 8.75 7.11 4.22
09 (24C) (17C) Input 0.20 0.211 0.24 0.29 0.55 1.08 1.05 6.12 1.00 0.7788
(115V) 80.6F gg,2F TC 7.02 7.17 7.87 9.05 10.37 11.35 10.14 9.41 7.72 4.78
(27C) (19C) SC 5.77 5.95 6.26 6.39 6.83 7.35 6.83 6.50 5.82 4.62
Input 0.19 0.20 0.23 0.29 0.70 1.11 1.06 1.15 1.02 0.79
89.6E 73.4E TC 7.80 7.96 8.75 10.06 13.21 13.15 11.73 10.90 8.98 5.96
(32C) (23C) SC 5.93 6.12 6.44 6.57 7.74 8.06 7.16 6.83 6.15 5.17
Input 0.19 0.20 0.23 0.28 0.93 1.17 1.10 1.20 1.04 0.81
69.8E 59F TC 6.53 6.67 7.33 8.42 8.57 11.44 9.94 8.98 7.80 4.84
SC 5.60 5.77 6.08 6.20 6.32 7.72 6.98 6.53 6.00 4.67
(21C) (15) Input 0.20 0.21 0.25 0.30 0.56 1.16 1.03 1.04 1.03 0.80
752E 62,6p TC 6.99 7.13 7.84 9.01 9.24 12.18 10.66 9.67 8.41 5.43
12 (24C) (17C) Input 0.20 0.21 0.24 0.30 0.56 1.19 1.06 1.06 1.05 0.81
(115V) 80.6F 66.2E TC 7.46 7.61 8.36 9.61 9.94 12.99 11.32 10.26 9.06 5.97
SC 6.36 6.56 6.90 7.04 7.30 8.60 7.88 7.43 6.94 5.72
(27C) (19C) Input 0.20 0.21 0.24 0.30 0.56 1.22 1.08 1.08 1.07 0.81
89.6E 73.4E TC 12.04 12.28 13.50 15.52 14.21 14.69 12.90 11.76 10.47 7.13
(32C) (23C) SC 8.19 8.45 8.89 9.07 8.68 8.85 8.19 7.79 7.34 6.20
Input 0.56 0.57 0.67 0.81 0.94 1.28 1.14 1.13 1.10 0.83
69.8E 59F TC 3.99 6.66 7.32 8.41 7.93 8.65 8.13 6.85 5.61 4.21
SC 3.33 5.55 5.84 5.96 5.77 6.14 5.88 5.24 4.66 3.33
(21C) (15C) Input 0.25 0.45 0.53 0.64 0.71 1.01 1.08 1.05 1.04 0.10
75.2E 62,6p TC 3.91 6.52 7.17 8.24 10.42 9.37 8.78 7.52 6.22 4.71
09 (24C) (17C) Input 0.21 0.38 0.44 0.54 1.05 1.02 1.101.07 1.06 0.10
(208-230V) 80.6F 66.2F TC 4.65 7.74 8.51 9.78 11.23 10.12 9.53 8.22 6.03 1.88
(27C) (1 gC) SC 3.77 6.28 6.62 6.75 7.50 6.94 6.72 6.20 5.17 1.47
Input 0.25 0.46 0.53 0.65 1.07 1.04 1.11 1.09 0.93 0.12
89.6E 73.4E TC 6.18 10.31 11.33 13.02 13.05 11.76 11.09 9.66 7.35 2.09
(32C) (23C) SC 4.37 7.29 7.67 7.83 7.88 7.35 7.11 6.58 5.68 1.54
Input 0.37 0.67 0.78 0.95 1.11 1.07 1.14 1.11 0.96 0.12
TC 7.16 7.31 8.03 9.23 8.72 8.75 9.83 8.31 7.07 4.56
69.8E 59F
SC 6.21 6.40 6.74 6.87 6.70 6.71 7.24 6.48 5.89 4.56
(21C) (15C) Input 0.31 0.32 0.37 0.45 0.59 0.73 1.10 1.02 1.01 0.79
75.2E 62,6p TC 7.64 7.80 8.57 9.85 9.58 11.84 10.69 9.07 7.76 5.02
SC 6. 3 7.07 6.43 5.02
12 (24C) (17C) Input 0.31 0.32 0.38 0.46 0.60 1.12 1.1122 1.03 1.02 0.79
(208-230V) 80.6F 66.2F TC 8.
7.0316 8.337.25 9.157.63 10.5 7.78 99.857.55 12.718.9 11.58.37 99.767.56 8.456.94 5.
5.5959
SC
(27C) (19C) Input 0.32 0.33 0.39 0.47 0.56 1.15 1.15 1.04 1.03 0.80
89.6E 73.4E TC 11.48 11.72 12.88 14.80 14.83 14.65 13.37 11.35 9.92 6.56
(23C) SC 8.37 8.63 9.08 9.27 9.28 9.26 8.80 8.04 7.41 6.18
(32C) Input 0.73 0.75 0.88 1.07 1.07 1.22 1.22 1.09 1.07 0.81
69.8F 59F TC 7.85 11.21 12.32 14.16 13.32 17.55 15.92 13.84 11.90 7.57
(21 C) (15C) SC 6.86 9.80 10.32 10.53 10.16 12.14 11.37 10.38 9.52 7.34
Input 0.26 0.40 0.46 0.57 0.80 1.63 1.59 1.48 1.47 1.15
752E 62.6F TC 7.28 10.41 11.44 13.15 14.28 18.35 16.97 14.93 13.03 8.51
(24C) (17C) SC 6.75 9.64 10.15 10.36 10.91 12.73 12.10 11.18 10.36 8.27
18 Input 0.21 0.33 0.38 0.47 0.80 1.65 1.62 1.52 1.49 1.16
(208-230V) 80.6E 66.2F TC 7.38 10.55 11.59 13.32 15.17 18.99 17.75 15.98 14.10 9.36
(27C) (1 gC) SC 6.85 9.79 10.31 10.52 11.60 13.18 12.69 11.92 11.17 9.16
Input 0.21 0.33 0.38 0.46 0.81 1.69 1.65 1.55 1.52 1.17
89.6E 73.4E TC 7.41 10.59 11.64 13.38 19.66 19.99 18.99 17.42 15.97 11.05
(32C) (23C) SC 6.52 9.32 9.81 10.01 12.92 13.07 12.70 12.14 11.65 10.14
Input 0.21 0.33 0.38 0.46 1.41 1.71 1.69 1.60 1.57 1.19
69.8F 59F TC 15.64 15.96 17.54 20.16 22.14 24.70 22.98 21.84 18.64 15.25
SC 13.33 13.75 14.47 14.77 15.55 16.90 16.00 15.46 13.86 12.45
(21C) (15C) Input 0.69 0.71 0.83 1.01 1.68 2.54 2.56 2.77 2.57 2.38
752E 62.6E TC 16.64 16.98 18.66 21.45 22.46 25.97 24.36 23.34 20.30 15.40
SC 14.17 14.61 15.38 15.69 16.13 17.9 17.06 16.52 15.11 13.01
24 (24C) (17C) Input 0.71 0.73 0.85 1.03 1.54 2.58 2.60 2.82 2.63 2.22
(2°8-23" 80.6F 662F TC 17.62 17.98 19.75 22.70 23.55 27.04 25.57 24.49 21.09 15.40
SC 14.96 15.42 16.23 16.56 16.88 18.44 17.80 17.35 15.88 13.52
(27C) (19C) Input 0.72 0.74 0.86 1.05 1.55 2.61 2.63 2.87 2.57 2.07
89.6E 73.4E TC 19.18 19.57 21.50 24.72 28.40 28.70 27.34 26.59 22.98 18.01
(32C) (23C) Input
15.19 15.66 16.48 16.82 18.15 18.26 17.76 17.51 16.18 14.41
Input 0.73 0.75 0.87 1.07 2.25 2.67 2.69 2.94 2.53 2.13
LEGEND
DB-Dry Bulb
WB-Wet Bulb
TC-Total Net Capacity(1000BTU/hour)
SC-Sensible Capacity(1000BTU/hour)
Input-Total Power(kW)
11
COOLING PERFORMANCE DATA - (HEAT PUMP)
COOLING OUTDOOR CONDITIONS(DB)
MODEL Indoor(D�Conditions OF 5F 17F 47F 77F 86F 95F 104F 113F 122F •
DB WB (-17C) (-15C) (-8C) (8C) (25C) (30C) (35C) (40C) (45C) (50C)
69.8E 59F TC 4.58 5.10 5.95 10.20 10.83 10.26 9.28 8.33 7.39 6.44
(21 C) (15C) SC 3.48 3.98 4.76 7.24 7.90 7.70 7.52 7.08 6.65 6.12
Input 0.21 0.23 0.29 0.62 0.83 1.18 1.25 1.10 0.95 0.80
75 2� 62.6E TC 4.68 5.20 6.08 10.41 11.05 10.47 9.47 8.50 7.54 6.57
(24C) (17C) SC 3.56 4.06 4.86 7.39 8.06 7.85 7.67 7.23 6.78 6.24
09 Input 0.21 0.23 0.29 0.62 0.84 1.19 1.27 1.11 0.96 0.81
(115V) 80.6E 86.2F TC 4.77 5.31 6.20 10.62 11.2 110.69 9.67 8.68 7.69 6.70
(27C) (19C) SC 3.62 3.68 4.93 7.54 8.19 7.77 7.81 7.36 6.91 6.37
Input 0.21 0.23 0.30 0.63 0.85 1.20 1.28 1.13 0.97 0.82
89.6E 73.4E TC 5.06 5.63 6.57 11.26 11.95 11.33 10.24 9.20 8.15 7.11
(32C) (23C) SC 3.77 3.82 5.13 7.84 8.52 8.08 8.12 7.66 7.19 6.62
Input 0.22 0.24 0.31 0.66 0.89 1.26 1.34 1.18 1.02 0.86
69.8F 59F TC 5.34 5.56 6.48 10.38 11.60 12.91 11.93 10.98 10.04 9.09
C) (15C) SC 4.06 4.34 5.18 7.37 8.47 9.68 9.67 9.34 9.03 8.63
(21Input 0.27 0.28 0.33 0.66 0.94 1.25 1.23 1.08 0.93 0.78
75 2� 62.6E TC 5.45 5.67 6.61 10.59 11.84 13.18 12.18 11.21 10.24 9.27
(24C) (17C) SC 4.14 4.42 5.29 7.52 8.64 9.88 9.86 9.53 9.22 8.81
12 Input 0.28 0.29 0.33 0.67 0.95 1.26 1.24 1.09 0.94 0.79
(115V) 80.6F 66.2F TC 5.56 5.79 6.74 10.81 12.08 13.45 12.42 11.44 10.45 9.46
(27C) (1 gC) SC 3.73 3.77 4.48 7.66 9.2.8 8.88 8.02 7.48 6.93 6.38
Input 0.28 0.29 0.34 0.68 0.96 1.28 1.26 1.10 0.95 0.79
89.6E 73.4E TC 5.89 6.13 7.15 11.46 12.80 14.25 13.17 12.12 11.08 10.03
(32C) (23C) SC 3.88 3.92 4.66 7.97 9.65 9.24 8.34 7.78 7.21 6.64
Input 0.29 0.30 0.35 0.71 1.00 1.34 1.32 1.16 0.99 0.83
69.8F 59F TC 4.35 4.67 5.53 8.12 10.78 10.56 9.62 7.63 6.11 4.45
SC 3.31 3.64 4.43 5.76 7.87 7.92 7.79 6.49 5.50 4.23
(21C) (15C) Input 0.22 0.24 0.27 0.31 0.53 0.77 0.83 1.08 0.96 0.83
75.2F 62,6p TC 4.44 4.77 5.65 8.28 11.00 10.77 9.82 7.79 6.23 4.54
(24C) (17C) SC 3.37 3.72 4.52 5.88 8.03 8.08 7.95 6.62 5.61 4.32
09 Input 0.22 0.24 0.28 0.31 0.54 0.78 0.84 1.09 0.97 0.84
(208-230V) 80.6F 66.2F TC 4.53 4.86 5.76 8.45 11.23 10.99 10.0 57.95 6.36 4.64
(27C) (19C) SC 3.71 3.90 4.02 6.19 7.38 7.62 7.51 5.95 4.73 3.33
Input 0.22 0.24 0.28 0.32 0.54 0.79 0.85 1.11 0.98 0.85
89.6E 73.4E TC 4.80 5.15 6.11 8.96 11.90 11.65 10.62 8.42 6.74 4.91
(32C) (23C) SC 3.86 4.06 4.18 6.44 7.68 7.93 7.81 6.18 4.92 3.46
Input 0.23 0.25 0.29 0.33 0.57 0.83 0.89 1.16 1.03 0.89
69.8E TC 5.15 5.27 6.67 9.71 11.88 12.91 11.93 10.98 10.03 9.09
(21 C) (1 ) SC 3.91 4.11 5.33 6.89 8.68 9.68 9.66 9.34 9.03 8.63
Input 0.25 0.26 0.31 0.56 0.74 1.15 1.13 1.08 0.93 0.78
75.2E 62.6E TC 5.25 5.38 6.80 9.90 12.13 13.17 12.17 11.21 10.24 9.27
(24C) (17C) SC 3.99 4.19 5.44 7.03 8.85 9.88 9.86 9.53 9.22 8.81
12 Input 0.25 0.27 0.32 0.57 0.75 1.16 1.14 1.09 0.94 0.78
(2°8-23°V) 80.6F 66.2F TC 5.36 5.48 6.94 10.11 12.37 13.44 12.42 11.4 110.45 9.46
(27C) (19C) SC 3.77 3.77 5.38 8.06 8.88 8.88 8.02 7.47 6.93 6.38
Input 0.25 0.27 0.32 0.57 0.75 1.17 1.15 1.10 0.95 0.79
89.6E 73.4F TC 5.68 5.81 7.36 10.71 13.12 14.25 13.17 12.12 11.08 10.03
SC 3.92 3.92 5.59 8.38 9.23 9.23 8.34 7.77 7.20 6.64
(32C)
(23C)
Input 0.26 0.28 0.34 0.60 0.79 1.23 1.21 1.15 0.99 0.83
69.8F 59F TC 8.36 8.76 10.16 17.40 18.79 18.40 17.40 15.43 12.68 8.41
SC 6.35 6.84 8.13 12.35 13.72 13.80 14.10 13.11 11.42 7.99
(21C) (15C) Input 0.36 0.40 0.54 0.74 1.53 1.39 1.69 1.69 1.68 1.19
75.2E 62,6p TC 8.53 8.94 10.37 17.75 19.18 18.78 17.76 15.74 12.94 8.58
SC 6.48 6.98 8.30 12.60 14.00 14.08 14.38 13.38 11.65 8.15
18 (24C) (17C) Input 0.37 0.40 0.54 0.75 1.54 1.40 1.70 1.70 1.70 1.20
(208-230V) 80.6F 662F TC 8.70 9.12 10.58 18.11 19.57 19.16 18.12 16.06 13.21 8.76
(27C) (19C) SC 3.84 4.00 8.46 13.64 15.09 13.19 15.12 13.58 11.12 7.29
Input 0.37 0.41 0.55 0.75 1.56 1.41 1.72 1.72 1.72 121
89.6E 73.4E TC 9.23 9.67 11.22 19.20 20.74 20.31 19.21 17.03 14.00 9.28
(32C) (2 ) SC 4.00 4.16 8.80 14.18 15.69 13.71 15.73 14.12 11.57 7.58
Input 0.39 0.43 0.58 0.79 1.63 1.48 1.81 1.81 1.80 127
69.8E 59F TC 9.98 10.40 17.56 25.67 27.64 25.84 21.98 18.15 13.25 7.50
(21 C) (15C) SC 7.59 8.11 14.05 18.23 20.18 19.38 17.80 15.43 11.92 7.12
Input 1.20 1.24 1.37 1.57 1.96 2.57 2.55 2.40 2.19 2.04
75.2E 62,6p TC 10.19 10.61 17.92 26.20 28.20 26.37 22.43 18.52 13.52 7.65
24 (24C) (17C) SC 7.74 8.28 14.33 18.60 20.59 19.78 18.17 15.74 12.17 7.27
Input 1.21 1.26 1.39 1.59 1.97 2.60 2.58 2.42 2.21 2.06
(208-23911) 80.6F 66.2F TC 10.39 10.83 18.28 26.73 28.78 26.91 22.89 18.90 13.80 7.81
(27C) (1 gC) SC 3.44 3.47 14.58 17.15 19.14 16.54 14.68 14.13 10.23 5.68
Input 1.22 1.27 1.40 1.61 1.99 2.62 2.60 2.45 2.24 2.08
89.6E 73.4F TC 11.02 11.48 19.38 28.33 30.51 28.52 24.26 20.03 14.62 8.28
SC 3.58 3.61 15.16 17.83 19.91 17.20 15.27 14.70 10.64 5.91
(32C)
(23C)
Input 1.28 1.33 1.47 1.69 2.09 2.75 2.73 2.57 2.35 2.19
LEGEND
DB-Dry Bulb
WB-Wet Bulb
TC-Total Net Capacity(1000BTURwur)
SC-Sensible Capacity(1000BTU/hour)
Input-Total Power(kW)
12
a
HEATING PERFORMANCE DATA - (HEAT PUMP)
HEATING; OUTDOOR CONDITIONS(DB)
MODEL INDOOR CONDITIONS(DB) OF 5F 17F 19.4E 24.8E 32F 392E 44.6E 53.6E
(-17C) (-15C) (-8C) (-7C) (-4C) (OC) (4C) (7C) (12C)
TC 5.63 6.16 7.08 7.93 8.40 8.85 9.59 10.18 10.81
59F(15C) Input 0.95 0.95 0.93 0.97 0.99 1.02 1.02 1.03 1.06
COP 1.74 1.91 2.23 2.40 2.49 2.54 2.77 2.91 3.00
IC 5.60 6.13 6.86 7.55 8.37 9.37 10.26 11.69 12.70
64AF(18C) Input 1.04 1.01 1.02 1.04 0.90 0.81 0.92 1.12 1.09
09 COP 1.58 1.79 1.97 2.12 2.72 3.40 3.26 3.07 3.41
(115V) TC 5.58 6.10 6.83 7.53 8.35 9.35 10.23 11.66 12.67
89F(20.5C) Input 1.13 1.09 1.11 1.13 0.99 0.90 1.01 1.20 1.18
COP '' 1.45 1.63 1.80 1.95 2.47 3.05 2.96 2.84 3.15
TC '' 4.68 5.31 5.93 6.66 7.55 8.31 8.73 9.22 9.55
71.8E(22C) Input 0.81 0.84 0.89 0.92 0.92 1.09 1.11 1.13 1.02
COP 1.70 1.86 1.94 2.13 2.42 2.25 2.31 2.39 2.74
TC 5.65 6.37 7.89 8.78 9.55 10.55 11.46 12.45 12.89
59F(15C) Input 0.82 0.88 0.90 0.92 0.99 0.99 1.15 1.21 1.01
COP 2.03 2.11 2.57 2.79 2.84 3.11 2.92 3.01 3.73
TC 5.45 5.47 6.69 7.58 8.35 9.35 11.26 12.11 12.84
64AF(18C) Input 0.80 0.86 0.88 0.90 0.97 0.97 1.20 1.24 1.06
12 COP 2.00 1.86 2.23 2.46 2.53 2.82 2.75 2.87 3.54
(115V) TC 5.25 5.37 5.89 6.78 7.55 8.55 11.16 12.03 12.75
69F(20.5C) Input 0.78 0.84 0.86 0.88 0.95 0.95 1.21 1.26 1.07
COP 1.96 1.87 2.01 2.25 2.34 2.63 2.70 2.80 3.48
TC 5.20 6.32 7.56 8.54 9.51 10.21 10.99 11.88 12.49
71.6F(22C) Input 0.84 0.81 0.85 0.87 1.00 0.90 1.03 1.10 1.10
COP 1.81 2.28 2.61 2.87 2.80 3.32 3.12 3.18 3.33
TC 7.28 7.70 8.53 9.43 10.05 10.45 11.33 11.92 12.68
59F(15C) Input 1.17 1.14 1.15 1.17 1.03 0.94 0.95 1.02 1.12
COP 1.82 1.99 2.17 2.35 2.85 3.26 3.49 3.44 3.32
TC 6.08 6.50 7.33 8.23 8.85 9.85 11.13 11.72 12.48
64.4F(18C) Input 1.15 1.12 1.13 1.15 1.01 0.92 1.00 1.07 1.17
09 COP 1.55 1.71 1.90 2.09 2.56 3.14 3.25 3.22 3.12
(208-230V) TC 5.28 5.70 6.53 7.43 8.05 9.05 10.03 11.63 12.38
69F(20SC) Input 1.13 1.10 1.11 1.13 0.99 0.90 1.01 1.08 1.18
COP 1.37 1.52 1.72 1.92 2.38 2.95 2.90 3.16 3.07
TC 6.43 8.95 7.68 8.58 8.90 9.30 10.14 11.13 12.29
71.6F(22C) Input 1.06 1.03 1.20 1.23 1.08 0.98 1.02 1.09 1.19
COP 1.78 1.99 1.87 2.05 2.42 2.78 2.90 3.00 3.02
IC 7.91 8.89 9.84 10.87 11.11 11.35 11.86 12.41 13.00
59F(15C) Input 0.83 1.27 0.81 1.37 0.90 1.01 1.17 1.51 1.04
COP 2.79 2.06 3.54 2.32 3.61 3.30 2.98 2.41 3.66
TC 6.33 7.65 8.06 9.56 9.83 10.53 11.38 12.03 12.74
64.4F(18C) Input 0.85 0.82 0.84 0.86 0.92 0.83 1.19 1.53 1.51
12 COP 2.17 2.74 2.83 3.26 3.12 3.72 2.81 2.31 2.47
(206-230V) TC 5.55 6.07 6.98 8.08 8.95 10.55 12.20 13.65 14.06
69F(20.5C) Input 0.88 0.84 0.86 0.88 0.95 0.85 1.21 1.55 1.54
COP 1.86 2.11 2.38 2.69 2.78 3.63 2.96 2.58 2.68
TC 4.58 5.35 5.95 7.12 7.92 8.94 10.48 11.52 12.38
71.6F(22C) Input 0.86 0.79 0.84 0.86 0.93 0.98 1.20 1.54 1.16
COP 1.56 1.99 2.07 2.42 2.50 2.67 2.57 2.20 , 3.14
TC 9.03 10.18 11.43 12.37 13.33 14.90 16.83 18.03 18.59
59F(15C) Input 2.33 5.12 2.12 5.25 1.92 5.03 1.71 1.61 5.06
COP 1.14 1.99 1.58 2.36 2.04 2.26 2.88 3.29 3.68
TC 8.55 10.05 11.95 12.45 13.45 15.65 16.85 18.15 18.17
64.4F(18C) Input 2.35 2.25 2.15 2.04 1.94 '' 1.84 1.73 1.63 1.62
18 COP 1.07 1.31 1.63 1.79 2.03 2.50 2.85 3.26 3.29
(208-230V) TC 8.47 9.67 11.87 12.47 13.37 15.57 16.87 18.07 18.09
69F(20.5C) Input 2.37 2.27 2.17 2.07 1.96 1.86 1.76 1.65 1.84
COP 1.05 1.25 1.61 1.77 2.00 2.48 2.82 3.20 3.23
TC 7.85 8.78 11.25 12.50 13.35 14.74 18.85 18.05 18.18
71.6F(22C) Input 2.36 5.02 2.15 5.47 1.95 5.41 1.74 1.64 5.52 I
COP 0.97 1.75 1.53 2.29 2.01 2.72 2.84 3.23 3.29
TC 14.08 16.77 19.76 21.26 23.01 24.12 25.70 26.17 26.60
59F(15C) Input 2.60 2.88 2.76 2.83 2.62 2.44 2.47 2.33 2.82
COP 1.59 1.71 2.10 2.10 2.57 2.08 3.05 3.29 3.00
TC 13.36 15.13 19.00 21.27 22.02 23.36 24.43 25.67 26.69
64.4E(18C) Input 2.83 3.08 2.88 2.74 2.68 2.72 2.58 2.43 2.25
24 COP 1.38 1.44 1.93 2.27 2.41 2.52 2.78 3.10 3.47
(208-230V) TC 12.60 14.92 18.50 20.79 21.22 22.45 23.69 24.52 25.29
69F(20 SC) Input 2.89 3.17 2.92 2.83 2.77 2.83 2.66 2.52 2.43
Fin
COP 1.28 1.38 1.8B 2.15 2.25 2.32 2.61 2.85 3.05
TC 11.87 15.37 19.07 21.85 22.82 23.37 24.48 25.44 27.45
71.6F(22C) Input 2.98 2.75 3.25 2.82 2.95 2.88 2.81 2.88 2.88
COP 1.17 1.64 1.72 2.27 2.27 2.56 2.55 2.59 2.79
DB-Dry Bulb
TC-Total Net Capacity(1000BTU/hour)
Input-Total Power(kW)
COP-W/W
i
13
APPLICATION DATA
UNIT SELECTION METERING DEVICES
Select equipment that either matches or supports slightly more than The outdoor unit has an electronic expansion valve to manage the
the anticipated peak load. This provides better humidity control, refrigerant flow of the connected fan coil.
fewer unit cycles,and less part—load operation.
For units used in spaces with high sensible loads,base equipment DRAIN CONNECTIONS
selection on unit sensible load,not on total anticipated load.Adjust Install drains to meet the local sanitation codes.
for anticipated room wet bulb temperature to avoid undersizing the
equipment. REFRIGERANT LINES
UNIT MOUNTING (OUTDOOR) General refrigerant line sizing:
Refer to the unit's installation instructions for further details. 1. The outdoor units are shipped with a full charge of R410A
Unit leveling—For reliable operation,units should be level in all refrigerant.All charges,line sizing,and capacities are based on
planes. runs of 25 ft.(7.6 m).For runs over 25 ft.(7.6 m),review the
Clearance—Minimum clearance(see Fig.4)must be provided Long Line Applications section for the proper charge
for airflow.The condensing units are designed for free—flow adjustments.
application.Air inlets and outlets should not be restricted. 2. Refrigerant lines should not be buried in the ground. If it is
Unit location—A location which is convenient to installation and necessary to bury the lines,do not bury more than 36—in(914
not exposed to strong winds.A location that can bear the weight of mm). Provide a minimum 6—in (152 mm) vertical rise to the
the outdoor unit and where the outdoor unit can be mounted in a service valves to prevent refrigerant migration.
level position. 3. Both lines must be insulated.Use a minimum of 1/2—in.
Do not install the indoor or outdoor units in a location with special (12.7 mm)thick insulation.Closed—cell insulation is
environmental conditions. For those applications, contact your recommended in all long—line applications.
sales representative. 4. Special consideration should be given to isolating the
interconnecting tubing from the building structure.Isolate the
SYSTEM OPERATING CONDITIONS tubing so vibration or noise is not transmitted into the
OPERATING RANGE structure.
MIN/MAX°F(°C) Long Line Applications:
COOLING HEATING 1. No change in line sizing is required.
Outdoor DB 0—122(-17—50) 0—86(-17—30) 2. Add refrigerant per the Additional Charge table.
NOTE:Reference the product installation instructions for more
information.
ADDITIONAL CHARGE
TOTAL LINE ADDTIONAL CHARGE,oz/ft.FT.(m)
UNIT LENGTH ft.(m)
SIZE Min Max 10-25 >25-82 >82-98 >98-164
(3-8) (8-25) (25-30) (30-50)
9
82(25)
12 0.16
18 10(3) None
98(30) 0.16 ;a .+d
24 164(50) 0.32 0.32 0.32
14
,
WIRING CAUTION
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use Electrical EQUIPMENT DAMAGE HAZARD
Data table MCA (minimum circuit amps) and MOCP(maximum
over current protection) to correctly size the wires and the Failure to follow this caution may result in equipment
disconnect fuse or breakers respectively. damage or improper operation.
Per the caution note,only stranded copper conductors with a 600 Wires should be sized based on NEC and local codes.
volt insulation rating wire must be used. Use copper conductors only with a 600 volt insulation
Reconunended Connection Method for Power and rating wire.
Communication Wiring:
The main power is supplied to the outdoor unit.The field supplied
14/3 stranded wire with ground with a 600 volt insulation rating, a CAUTION
power/communication wiring from the outdoor unit to indoor unit
consists of four(4) wires and provides the power for the indoor
unit.Two wires are line voltage AC power,one is communication EQUIPMENT DAMAGE HAZARD
wiring(S)and the other is a ground wire.Wiring between indoor Failure to follow this caution may result in equipment damage
and outdoor unit is polarity sensitive.The use of BX wire is NOT or improper operation.
recommended. Be sure to comply with local codes while running wire from
If installed in a high Electromagnetic field (EMF) area and the indoor unit to the outdoor unit.
communication issues exists,a 14/2 stranded shielded wire can be Every wire must be connected firmly.Loose wiring may cause
used to replace L2/N and(S)between outdoor unit and indoor unit the terminal to overheat or result in unit malfunction. A fire
landing the shield onto ground in the outdoor unit only. hazard may also exist.Ensure all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
15
AIR FLOW DATA
P COOLING ONLY
F 38MHRC Unit Size 9K(115V) 12K(115V) 9K(208/230V) 12K(208/230V) 18K(208/230V) 24K(208/230V) -
Outdoor(CFM) 506 506 506 506 518 553
HEAT PUMP
38MHRO Unit Size 9K(115V) 12K(115V) 9K(208/230V) 12K(208/230V) 18K(208/230V) 24K(208/230V)
Outdoor(CFM) 506 506 506 506 518 553
SOUND DATA
COOLING ONLY
38MHRC Unit Size 9K 12K 9K 12K 18K 24K
(115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Outdoor Sound Pressure Level dB(A) 50.5 52 53 54 57 59.5
Outdoor Sound Power Level dB(A) 62.8 63.3 62.5 63.9 65.9 66
HEAT PUMP
38MHRQ Unit Slice (115V)
12K 9K 12K 18K 24K
(115V) (115V) (208/230V) (2081230V) (208/230V) (208/230V)
Outdoor Sound Pressure Level dB(A) 52 53 54 53 57 60.1
Outdoor Sound Power Level dB(A) 62.9 63.5 62.8 64.1 65.7 66.2
SOUND PRESSURE IN OCTAVE BANDS
COOLING ONLY
Frequency(Hz) 63 125 250 500 1000 2000 4000 6300 8000
9K(115) Cooling dB(A) 56.6 56.4 51.8 48.4 45.9 40.6 34.4 28.9 56.6
12K(115) Cooling dB(A) 60.2 57.3 52.0 49.9 45.9 41.1 35.6 30.1 60.2
9K(208V) Cooling dB(A) 60.7 56.6 54.3 49.2 46.8 42.1 36.6 30.8 60.7
12K(208V) Cooling dB(A) 54.0 59.1 53.8 54.2 49.8 42.0 36.3 30.9 54.0
18K(208V) Cooling dB(A) 63.8 66.7 58.8 54.6 52.5 48.0 43.4 36.1 63.8
24K(208V) Cooling dB(A) 58.8 64.1 59.2 55.0 52.0 47.5 44.6 39.5 58.8
,ta HEAT PUMP
F'. Frequency(Hz) 63 125 250 500 1000 2000 4000 8000
9K(115) Cooling dB(A) 54.1 55.8 51.2 48.7 46.8 42.5 34.8 28.3
Heating dB(A) 52.9 58.6 51.7 49.9 50.3 43.0 38.5 33.3
Cooling dB(A) 52.6 56.9 56.6 53.3 48.7 42.1 37.4 34.0
12K(115) Heating dB(A) 59.9 55.5 54.0 50.6 46.8 42.2 36.1 31.5
Cooling dB(A) 59.3 56.9 53.1 50.8 46.4 42.6 36.4 30.3
9K(208V) Heating dB(A) 57.8 56.3 55.1 51.7 47.9 44.5 38.7 33.6
12K(208V) Cooling dB(A) 64.8 57.3 55.7 53.3 51.1 48.1 42.6 36.1
€; Heating dB(A) 56.8 56.9 57.8 53.2 49.3 44.6 39.2 31.8
.1 Cooling dB(A) 54.1 55.8 51.2 48.7 46.8 42.5 34.8 28.3
18K(208V)
!; Heating dB(A) 52.9 58.6 51.7 49.9 50.3 43.0 38.5 33.3
Cooling dB(A) 52.6 56.9 56.6 53.3 48.7 42.1 37.4 34.0
24K(208V) Heating dB(A) 59.9 55.5 54.0 50.6 46.8 42.2 36.1 31.5
;11
i
t
r
i
(
16
1
ur+ru+t+etrituwarxr+aaattxauwnuu+x+ttxwcour,WiWtituxutuxuNYuaewuxaatNtax+xt xutAru++u++atttt+x+ax+uwtrku# a NOliti�tYifiWisut.:x .., , ,.,. r„ir,,. , :n , .r,..,n n art,.r+a. -.H Haug x a u-uaarr u.u,..>. anu>r„
OUTDOOR UNIT SOUND PRESSURE TEST CONDITIONS
Outdoor Unit
Microphone
3.3 ft. (lm)
NOTE:H=0.5 x Height of outdoor unit
INDOOR CONDITION OUTDOOR CONDITION
DB WB DB WB
Cooling 80.6F(27C) 66.2F(19C) 95F(35C) 75.2F(24C)
Heating 68F(20C) 59F(15C) 44.6F(7C) 42.8F(6C)
ELECTRICAL DATA
Outdoor Unit Size 9K 12K 9K 12K 18K 24K
Cooling Only Volts-PH-Hz (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Max-Min* 127-104 127-104 253-187 253-187 253-187 253-187
Oper.Voltage
MCA 13 13 7 7 11 16
Power Supply MOCP 20 20 15 15 15 25
Compressor RLA 9 9.5 4.5 4.5 7 11
FLA 0.6 0.6 0.4 0.4 0.5 0.6 i
Outdoor Fan Motor Rated HP 0.054 0.054 0.054 0.054 0.065 0.068
Output 40 40 40 40 48 45
Outdoor Unit Size 9K 12K 9K 12K 18K 24K
Heat Pump Volts-PH-Hz (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Max-Min* 127-104 127-104 253-187 253-187 253-187 253-187
Oper.Voltage
Power Supply MCA 13 13 8 10 15 18
MOCP 20 20 15 15 20 25
Compressor RLA 9 9.5 5.5 6.8 10.5 12
FLA 0.7 0.7 0.4 0.4 0.6 0.6
Outdoor Fan Motor Rated HP 0.043 0.043 0.043 0.043 0.065 0.085 f
Output 32 32 32 32 48 63 99
*Permissible limits of the voltage range at which the unit will operate satisfactorily. f
LEGEND
FLA—Full Load Amps
MCA—Minimum Circuit Amps
RLA—Rated Load Amps
17
WIRING DIAGRAMS
16022000B23477 3 •
S f YELLOW OR BLACK
w
U '� J f � j O n
n6 � m i_...__..___, w m
m m
NOTE:The connection wires for the - REACTOR g Y/G Y/G
reactor and the capacitor should be m" ^Y C z L N S L N Y/G
the same color;either black or brown. m 3 00 e I e j e
_ — — z_i BROWN BLACK GRAY
oz — 115VAC
1 no,
� CN 1A m POWER SUPPLY
Ia1av Y/GLLa IBROWNIBLACK'GRAY
Z Z Z o1I 2 3
LI TO INDOOR UNIT
r 2 O OPTONAL
0 ? /al400
r------------OPTIONAL ---------
BLUE _ z CRANKCASE
RED � z O HEATER
—o
BLACK
U V W — OPTIONAL:
° AC-FAN
COMPRESSO Z o
OY/G CN 21 CN 7
Ice ° o °°I 0 0 0
Notes:
,3 This symbol indicates the element
g 6 1 -FAN is optional,the actual shape shall
prevail.
g , OPTIONAL:
m DC-FAN
L�
t Y/�
CODE PART NAME CODE PART NAME
Input: 115V high voltage connector with CN1 A UN/signal/groundCN21 Input: temperature acquisition(0-5VDC)
CN7 Output:0-320VDC to control DC FAN CN25 Output:0-115 VAC to control AC FAN
CN4_1 CN4_2 Output:115VAC High voltage connector for Connector for electronic expansion
CN4_3 CN4_4 power factor corrector(PFC) CN31 valve(0-12VDC)
CN17 Output: 115VAC to control crankcase heater CN60 Output:115 VAC to control 4-way valve
Fig.5—Wiring Diagram Sizes 09K-12K(115V)
18
WIRING DIAGRAMS (CONTINUED)
Notes: 16022000623476
This symbol indicates the element Y/G BLUE YELLOW OR BLACK BLUE OR BLACK
is optional,the actual shape shall Y/G i
prevail.
BROWN RED
L1 L2 S L1 L2
CN 1A e e e' ¶ e Yro
INDO UNIT POWER SUPPLY
OPTIONAL
REACTOR CN 60 0
1005AL BLUE 0 1 y, 4-WAY
CN 17 O OPTI NAL CRANKCASE
— MAIN RED -HEATER
BLUE I BOARD
BLUE z
W
OPTIONAL —^'
>0
n 11
z Z Z
BLUE
CN 25 0 5 n rD'
m / 3 —Q o z
0 3
— Y/G`='
BLACK
CN 21 CN 7
U V W loco 0 ooi o 0 0
COMPRESSOR
3_
� m
Y/G o 1 CDC-FA�
O m ` - OPTIONAL:
1 O DC-FAN
L_R oYIG
CODE PART NAME CODE PART NAME
Input: 220V high voltage connector with Input: temperature sensor connector(0-5V DC)
CN1A UN/signal/Around CN21
CN7 Output:0-320V DC to connect DC FAN CN25 Output:0-220V AC to connect AC FAN
CN9-CN32 To connect PFC reactor CN50 Output:0-320V AC to connect compressor
CN 17 Output:220V AC to connect crankcase heater CN60 Output:0-220V AC to connect 4-way valve
Fig.6-Wiring Diagram-Sizes 09K,12K(230V)
19
•
WIRING DIAGRAMS (CONTINUED)
'UTDOO' Applicable to ; �UTDDDR Applicable to
YIG DC F the units adopting I AC FAN o the units adopting
5DC motor only i in a AC motor only
'
3/ �
II BLUE
BROWN
ICN4141 f
HEATER 1 I---.5N CN1
OPTIONALthe electric CN13J BLUE
heating belt of compressor CN 12C1
BLUE
REACTOR
OPTIONAL: 3 0 CN60 OUTDOOR BLUE BLUE
MAIN U(C 1
QCN6-S PCB CN30 v=1 RED 2 BLEPCK
Q CN8 CN3 We 3—
OQ CN7 BLACK
LSS BLUE(BLACK) CN17
Y/G cc m cc Q CN2 i CN1 CN10: W V_ U
BLACK 'I000 a- COMPRESSOR
t
(YELLOW) WHITE in 6
in m
OUTDOORAMBIENT rm O
REB TEMPERANRESENSOR Y/G
B_ACK(BLUE)
rill" o CONDENSER DISCHARGE SENSOR
11 L2 S L1 L2 TEMPERATURESENSOR
Y/G
(5 L1 L21 0
..
TO INDOOR UNIT POWER SUPPLY OUTDOOR WIRING DIAGRAM
CODE PART NAME CODE PART NAME
Input: 230V high voltage connector with
CN3 L1/L2/signal/ground CN5 Output:0-220VAC to control AC FAN
Output:PWM for UVW to control
CN30 Compressor(0-320VAC) CN1 6 Output:220V AC to control crankcase heater
CN1 7 Input:Temperature acquisition(0-5VDC) CN60 Output:0-220V AC to control 4-way valve
CN414 Output:0-320VDC to control DC FAN CN121CN13 Output:Connection of the high voltage(REACTOR)
Fig.7—Wiring Diagram Sizes 18K—24K(Heat Pump Units)
20
WIRING DIAGRAMS (CONTINUED)
16022000B23636 Y/G_Y/G BLACK
BLUE
1 , I !, BLUE
According to the real objects BROWN , RED
00 2 S 1 L2
— _ —
S Y�G Li L L
CN 3 -1_ e e e e e
OPTIONAL} _. -. L1 L2 — Y/G
INDOOR UNIT
p,gri IF AL POWER SUPPLY
Blue 2 OO l';<i. ea
al P IO NAI
_..— OUTDOOR Red 2 0 / rRANK ASE
BLUE BLURED E ,,i NZ n MAIN
RED _ BLACK' ! NZ N PCB
........
- BLACK
n:°_,
qmPRESSOR
VW _, vo
Yellow Z z
Z 0 s
l.n 0 \-V ' �7 i
Oo 3 .7-1Y/GS
Y/G CN 17 CN 414
boo 0 0 0 0 1 0 0 0 Notes:
This symbol indicates
1 tl
_ g `- J 3 the element is optional,
m DC-FAN the actual shape shall
z m.Y1 OPTIONAL: prevail.
TP T3"' T4A' DC-FAN
CODE PART NAME CODE PART NAME
CN3 Input: 220V high voltage connector with L1/L2/signal/ground CN5 Output:0-22OVAC to control AC FAN
Output:PWM for UVW to control
CN21 Compressor(0-320VAC) CN1 6 Output:220V AC to control crankcase heater
CN17 Input:Temperature acquisition(0-5VDC) CN60 Output:0-220V AC to control 4-way valve
CN414 Output:0-320VDC to control DC FAN
Fig.8—Wiring Diagram Sizes 18K—24K(Cooling Only Units)
21
r
f GUIDE SPECIFICATIONS •
HORIZONTAL DISCHARGE OUTDOOR UNITS
I' Size Range:3/4 to 2 Ton Nominal Cooling and Heating Capacity •
Model Number:38MHR
PART 1 —GENERAL D. Compressor:
1.01 System Description 1. Compressor is the fully hermetic rotary type.
a y2. Compressor is equipped with an oil system, operating oil
A. Outdoor air—cooled split system compressor sections suitableti charge,and a motor.
for on—the—ground,rooftop, wall hung or balcony mounting.
'r Units consist of a rotary compressor, an air—cooled coil, 3. Motor is NEMA rated class E, suitable for operation in a
propeller—type draw—through outdoor fan, reversing valve refrigerant atmosphere.
(HP),accumulator(HP units),metering device(s),and a control 4. Compressor assembly is installed on rubber vibration
box.Units discharge air horizontally as shown on the contract isolators.
drawings. Units function as the outdoor component of an E. Outdoor Coil:
air—to—air cooling only,or heat pump system. The coil is constructed of aluminum blue hydrophilic pre—coated
B. Units are to be used in a refrigeration circuit matched to fins mechanically bonded to seamless copper tubes, which are
`I ductless heat pump fan coil units. cleaned,dehydrated,and sealed.
`'
i 1.02 Agency Listings F. Refrigeration Components:
A. Unit construction complies with ANSUASHRAE 15, latest Refrigerant circuit components include a brass external liquid line
r' revision,and with the NEC. service valve with service gage port connections,a suction line
1 revision,and with the NEC.
B. Units are evaluated in accordance with UL standard 1995. service valve with a service gage connection port,service gage port
connections on compressor suction and discharge lines with Schrader
C. Units are listed in the CEC directory. type fittings with brass caps,accumulator,reversing valve.
D. Unit cabinet is capable of withstanding 500—hour salt spray test G. Controls and Safeties:
per Federal Test Standard No. 141(method 6061). Operating controls and safeties are factory selected,assembled,and
E. Air—cooled condenser coils are leak tested at 550 prig. tested.The minimum control functions include the following:
1.03 Delivery,Storage,And Handling 1. Controls:
r, Units are shipped in one piece and are stored and handled per unit a. A time delay control sequence is provided standard through
manufacturer's recommendations. the fan coil board
I'
1.04 Warranty(For Inclusion By Specifying Engineer) b. Automatic outdoor fan motor protection.
2. Safeties:
l PART 2—PRODUCTS a. System diagnostics
2,01 Equipment b. Compressor motor current and temperature overload
i protection
± A. General: Outdoor fan failure protection.
Factory assembled,single piece,air—cooled outdoor unit. c.H. Electrical
ff! Contained within the unit enclosure is all the factory wiring, Requirements:
piping,controls,and the compressor. 1. Unit operates on single—phase, 60 Hz power at 115V for
B. Unit Cabinet: unit sizes 09-12 and 208/230V for unit sizes 09, 12, 18,
and 24 as specified.
1. Uit truedf lnid el, nrid 2. Unit electrical power has a single point connection.
andnit coatedcab ne withis cons a bakedct—enamelo ga va finish ze on ste the bo insidede an ze d
11 outside(PANTONE 7527U). 3. Unit Control voltage to the indoor fan coil is 0-15V DC.
A 2. Unit access panels is removable with minimal screws and 4. All power and control wiring must be installed per NEC
',4 provides full access to the compressor, fan, and control and all local electrical codes.
components. 5. The unit has high and low voltage terminal block
II 3. The outdoor compartment is isolated and has an acoustic connections.
ji lining to assure quiet operation.
li C. Fans:
1. Outdoor fans are the direct drive propeller type, and
discharges air horizontally. Fans draw air through the
t outdoor coil.
11 2. Outdoor fan motors are totally enclosed, single phase motors
with class E insulation and permanently lubricated ball
11 bearings.Motor shall be protected by internal thermal overload
_1 protection.
11
3. The shaft has inherent corrosion resistance.
4. Fan blades are non—metallic and statically and dynamically
balanced.
11 5. Outdoor fan openings are equipped with a PVC metal/mesh
tiicoated protection grille over the fan.
22
it
4
c:2017 Bryant Heating&Cooling Systems•7310 W.Morris St.•Indianapolis,IN 46231 Edition Date:06/17 Catalog No. PDS38MHR-02
Manufacturer reserves the right to discontinue,or change at any time,specifications or designs without notice and without incurring obligations. Replaces:PDS38MHR—01
24
4"X3 " BOLT INTO 4X4
AT EACH CORNER
6 " LAG INTO EXISTING ROOF JOIST
1 iz
e/ AT EACH CORNER
CD- CONDENSER
4X4