FPs ao'► i- di 31 ci p00 ;W Duv('tc4ui cZc1 attic RPCF" srpAR Worldwide Cont"aaf`S"" Fire Protection www.tyco-fire.com Products Series TY-B - 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General ambient temperature,concentration of chemicals, and gas/chemical velocity, Description should be considered, as a minimum, along with the corrosive nature of the TYCO Series TY-B, 2.8, 5.6, and 8.0 chemical to which the sprinklers will be K-factor, Upright and Pendent Sprin- exposed. klers described in this technical data An intermediate level version of the sheet are standard response,standard Series TY-B Pendent Sprinkler can be r J I coverage decorative 5 mm glass bulb obtained by utilizing the Series TY-B ri type spray sprinklers designed for use in Pendent Sprinkler in combination with light,ordinary,or extra hazard,commer- the Model S2 Shield. ` cial occupancies such as banks,hotels, �. , shopping malls,factories,refineries,and NOTICE chemical plants. The Series TY-B Sprinklers described The recessed version of the Series TY-B herein must be installed and maintained Pendent Sprinkler,where applicable, is in compliance with this document, as intended for use in areas with a finished well as with the applicable standards of ceiling. It uses a two-piece Style 10(1/2 the National Fire Protection Association inch NPT) or Style 40 (3/4 inch NPT) (NFPA), in addition to the standards of Recessed Escutcheon.The Recessed any other authorities having jurisdiction. Escutcheon provides 1/2 inch(12,7 mm) Failure to do so may impair the perfor- of recessed adjustment or up to 3/4 inch mance of these devices. (19,1 mm)of total adjustment from the flush pendent position.The adjustment The owner is responsible for maintaining provided by the Recessed Escutcheon their fire protection system and devices " reduces the accuracy to which the fixed in proper operating condition. Contract pipe drops to the sprinklers must be cut. the installing contractor or product manufacturer with any questions. Corrosion resistant coatings, where applicable,are utilized to extend the life Sprinkler of copper alloy sprinklers beyond that p which would otherwise be obtained Identification when exposed to corrosive atmo- coads. Although corrosion resistant Numbers (SINs) coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing TY1151 - Upright 2.8K,1/2"NPT is not representative of all possible TY1251 - Pendent 2.8K,1/2"NPT corrosive atmospheres.Consequently, TY3151 - Upright 5.6K,1/2"NPT it is recommended that the end user TY3251- Pendent 5.6K,1/2"NPT be consulted with respect to the suit- TY4151 - Upright 8.0K,3/4"NPT ability of these coatings for any given TY4251 - Pendent 8.0K,3/4"NPT corrosive environment. The effects of TY4851 - Upright 8.0K,1/2"NPT TY4951 - Pendent 8.0K,1/2"NPT IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cau- tions with respect to handling and installation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 NOVEMBER 2014 TFP151 TFP151 Page 2 of 8 CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 7 3 - Sealing 6 - Deflector* �'i'�"" ""�'�'� t P Assembly 7 - Bushing 7/16" ----- t 1 4 Bulb (11,1 mm) �i— 2-1/4" �� 3 gill NOMINAL 1 (57,2 mm) ; `= MAKE IN 2 *Temperature rating is II 2-3/16" 1 9/16" indicated on Deflector. � + 4 (55,6 mm) I (39,7 mm) . r 5 ** Pipe thread connections per ISO 7-1 can be fi-t. ................... 6* provided on special 1/2"NPT** f WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 1 SERIES TY-B UPRIGHT(TY1151)AND PENDENT(TY1251)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1 7/16" ':m._ 3 NMOAKE NL2 2-3/16" 2-3/16" 1-1/2"(55,6 mm) 1iiu111111 4 (55,6 mm) (38,1 mm) 5 6* 1/2"NPT** f WRENCH STYLE 10 - 2-7/8"(73,0 mm)DIA. - FLATS RECESSED • UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE • - TFP151 Page 3 of 8 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1 1/2" (12,7 mm) iir 3 NOMINAL T 2-5/16" Z2 MAKE-IN (58,7 mm) _ 21/4" ' 1 9/16" � 4 (57,2 mm) (39,7 mm) 5 ....A._., , II _____-- 3/4" NPT** I WRENCH STYLE 40 [ 2-7/8"(73,0 mm)DIA. 6* FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT, STANDARD RESPONSE CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 Sealing 6 Deflector* Assembly 7/162-1 3 4 - Bulb (11,1 mm) I I t (57,2/mm) 2 NOMINAL MAKE-IN *Temperature rating is 2-3/16" 1-9/16" 4 indicated on Deflector. (55,6 mm) I I (39,7 mm) . ----5 ** Pipe thread connections -- per ISO 7-1 can be 6* provided on special 1/2"NPT** f WRENCH request. FLATS • UPRIGHT PENDENT CROSS SECTION FIGURE 4 SERIES TY-B UPRIGHT(TY4851)AND PENDENT(TY4951)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE TFP151 Page 4 of 8 BULB SPRINKLER FINISH(8) K SPRINKLER TEMPERATURE LIQUID TYPE RATING COLOR NATURAL CHROME LEAD WAX WAX-OVER-LEAD BRASS PLATED POLYESTER*** COATED COATED COATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red 2.8 (Tand 1) 175°F(79°C) Yellow 1,2,3 1/2 PENT N/A PENDENT NPT ENDS 1) 200°F(93°C) Green Figure 1 286°F(141°C) Blue 360°F(182°C) Mauve 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY3151) 1,2,3,5 1,2,3,5 and 175°F(79°C) Yellow PENDENT 1,2,3,4,5,6,7 1,2,3,5 (ENDEN) 200°F(93°C) Green Figure 2 286°F(141°C) Blue 1** 2** 3** 5** 1*^ 2** 3** 5*» 5.6 1/2" 360°F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4,5 175°F(79°C) Yellow N/A (TY3251)* Figure 5 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY4151)and 175°F(79°C) Yellow 1,2,3,5 1,2,5 PENDENT 1,2,3,4,5,6,7 1,2,5 (ENDEN) 200°F(93°C) Green Figure 3 286°F(141°C) Blue 1»* 2** 3** 5** 1*" 2** 5** 8.0 3/4- 360°F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4,5 175°F(79°C) Yellow N/A (TY4251)* Figure 6 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red 8 0 (TY4851) and 175°F(79°C) Yellow 1/2 PENDENT 1,2,3,4,5,6 N/A NPT (TY4951) 200°F(93°C) Green Figure 4 286°F(141°C) Blue 360°F(182°C) Mauve Notes: 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL) 3. Approved by FM Global(FM Approvals) 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03) 5. Approved by the City of New York under MEA 354-01-E 6. VdS Approved(For details contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05) 8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion- Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion-Resistant Sprinklers. Installed with Style 10(1/2-NPT)or Style 40(3/4-NPT)3/4.Total Adjustment Recessed Escutcheon,as applicable 150°F(66°C)maximum ceiling temperature —Frame and deflector only N/A-Not Applicable TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS LABORATORY LISTINGS AND APPROVALS WW ,, TFP151 Page 5 of 8 SPRINKLER FINISH K TYPE NATURAL CHROME LEAD WAX WAX-OVER-LEAD BRASS PLATED POLYESTER' COATED COATED COATED 2.8 UPRIGHT(TY1151) 1/2" and 175 psi(12,1 bar) N/A NPT PENDENT(TY1251) UPRIGHT(TY3151) and 5.6 PENDENT(TY3251) 250 psi(17,2 bar)(a) 1/2" OR NPT 175 psi(12,1 bar) RECESSED PENDENT (TY3251) UPRIGHT(TY4151) and 175 psi(12,1 bar) 8.0 PENDENT(TY4251) 3/4" NPT RECESSED PENDENT 175 psi(12,1 bar) N/A (TY4251) p 8.0 UPRIGHT(TY4851) 1/2" and 175 psi(12,1 bar) NPT PENDENT(TY4951) Notes: a. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL),the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL),and the Approval by the City of New York. Frame and deflector only N/A-Not Applicable TABLE B SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS MAXIMUM WORKING PRESSURE Technical Physical Characteristics Design Frame Bronze Data Button Brass/Copper Criteria Sealing Assembly Beryllium Nickel Approvals w/TEFLON TYCO Series TY-B, 2.8, 5.6, and UL and C-UL Listed Bulb Glass 8.0 K-factor, Upright and Pendent FM Approved Compression Screw Bronze Sprinklers are intended for fire protec- LPCB Approved Deflector Copper tion systems designed in accordance VdS Approved Bushing(K=2.8) Bronze with the standard installation rules NYC Approved recognized by the applicable Listing (Refer to Table A for complete ap- Operation or Approval agency(e.g., UL Listing is proval information, including corro based on the requirements of NFPA sion-resis-tant status.) The glass bulb contains a fluid which 13, and FM Approval is based on the expands when exposed to heat.When requirements of the FM Global Loss Maximum Working Pressure the rated temperature is reached, the Prevention Data Sheets).Only the Style Refer to Table B. fluid expands sufficiently to shatter the 10 or 40 Recessed Escutcheon, as Discharge Coefficient glass bulb, allowing the sprinkler to applicable, is to be used for recessed K=2.8 gpm/psi1/2(40,3 Ipm/bars/2) activate and water to flow. pendent installations. K=5.6 gpm/psi1/2(80,6 Ipm/bar1/2) K=8.0 gpm/psi1/2(115,2 Ipm/bar1/2) Temperature Ratings Refer to Table A. Finishes Sprinkler: Refer to Table C. Recessed Escutcheon: Signal or Pure White,Jet Black,Chrome Plated, or Natural Brass . w, TFP151 Page 6 of 8 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) WRENCH RECESS FACE OF (57,2 mm) MOUNTING (END"A" USED FOR SPRINKLER PLATE ^ 1/2" NPT MODELS) FITTING �� / 1/8" P (3,2 mm) WRENCH RECESS (END"B"USED FOR j 3/4"NPT MODELS) - FIGURE 7 MOUNTING W-TYPE 6 SURFACE •—;-- r SPRINKLER WRENCH CLOSURE SERIES 1-1/4"(31,8 mm) WRENCH TY-B 3/4"(19,1 mm) RECESS FIGURE 5 SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY �, WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT /ice fr STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA. �r t 5/8±1/4"_ (73,0 mm) 3/4"(19,1 mm) kii.dir (15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) PUSH WRENCH FACE OF (57,2 mm) MOUNTING IN TO ENSURE ENGAGEMENT SPRINKLER PLATE WITH SPRINKLER FITTING WRENCHING AREA / 1/8" (3,2 mm)i . FIGURE 8 W-TYPE 7 RECESSED . 24 7 SPRINKLER WRENCH \ f Installation MOUNTING SURFACE ! TYCO Series TY-B, 2.8, 5.6, and 8.0 K-factor, Upright and Pendent Sprin- CLOSURE SERIES 1-5/16"(33,3 mm) klers must be installed in accordance TY-B 13/16"(20,6 mm) with this section. FIGURE 6 General Instructions SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY Do not install any bulb type sprinkler if WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT the bulb is cracked or there is a loss of STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT liquid from the bulb.With the sprinkler held horizontally, a small air bubble should be present.The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 360°F (182°C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Obtain a leak-tight 3/4 inch NPT sprinkler joint by applying a minimum to maximum torque of 10 to 20 ft.-lbs. (13,4 to 26,8 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insuf- ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. TFP151 Page 7 of 8 Upright and Pendent Sprinklers Recessed Pendent Sprinklers Care must be exercised to avoid dam- The Series TY-B Upright and Pendent The Series TY-B Recessed Pendent age to the sprinklers before,during,and • Sprinklers must be installed in accor- Sprinklers must be installed in accor- after installation. Sprinklers damaged dance with the following instructions: dance with the following instructions: by dropping, striking, wrench twist/ Note:Install pendent sprinklers in the Step A. After installing the Style 10 slippage,or the like,must be replaced. pendent position;install upright sprin- or 40 Mounting Plate, as applicable, Also, replace any sprinkler that has a klers in the upright position. over the sprinkler threads and with cracked bulb or that has lost liquid from pipe thread sealant applied to the pipe its bulb.(Refer to Installation Section.) Step 1.With pipe thread sealant applied threads, hand-tighten the sprinkler into The owner is responsible for the inspec- to the pipe threads, hand-tighten the the sprinkler fitting. sprinkler into the sprinkler fitting. p g• tion,testing, and maintenance of their Step B. Tighten the sprinkler into the fire protection system and devices in Step 2. Tighten the sprinkler into the compliance with this document, as sprinkler fitting using only the W-Type sprinkler fitting using only the W-Type well as with the applicable standards 6 Sprinkler Wrench (Figure 7. For 7 Recessed Sprinkler Wrench (Figure p ( g ) 8).With reference to Figure 3 or 4,the of the National Fire Protection Asso- wax-coated sprinklers, use an 8 or 10 W-Type 7 Recessed Sprinkler Wrench ciation (e.g., NFPA 25), in addition to inch adjustable wrench.With reference the standards of any other authorities to Figures 1 through 4, the W-Type is to be applied to the sprinkler wrench having jurisdiction.Contact the installing 7 Recessed Sprinkler Wrench or an flats. contractor or product manufacturer with adjustable wrench, as applicable, is to Step C.After the ceiling is installed or any questions. be applied to the sprinkler wrench flats. the finish coat is applied, slide on the Automatic sprinklers are recommended When installing wax-coated sprinklers Style 10 or 40 Closure over the Series to be inspected,tested,and maintained with an adjustable wrench, exercise TY-B Sprinkler and push the Closure over the Mounting Plate until its flange by a qualified Inspection Service in care to prevent damage to the wax contacts the ceiling. accordance with local requirements coating on the sprinkler wrench flats and/or national codes. or frame arms and, consequently, exposure of bare metal to the corrosive Care and environment. Open the jaws of the wrench sufficiently wide to pass over Maintenance the wrench flats without damaging the wax coating. Before wrench tightening TYCO Series TY-B, 2.8, 5.6, and 8.0 the sprinkler, adjust the jaws of the K-factor, Upright and Pendent Sprin- wrench to contact only the sprinkler klers must be maintained and serviced wrench flats.After wrench tightening the in accordance with this section. sprinkler,loosen the wrench jaws before Before closing a fire protection system removing the wrench. main control valve for maintenance After installation, inspect the sprinkler work on the fire protection system that wrench flats and frame arms and it controls, obtain permission to shut retouch(repair)the wax coating when- down the affected fire protection system • ever the coating has been damaged and from the proper authorities and notify all bare metal is exposed.Retouch the wax personnel who may be affected by this coating on the wrench flats by gently action. applying a heated 1/8 inch diameter The owner must assure that the steel rod to the damaged areas of wax, sprinklers are not used for hanging to smooth it back over areas where bare any objects and that the sprinklers are metal is exposed. only cleaned by means of gently dust- ing with a feather duster; otherwise, NOTICE non-operation in the event of a fire or Only retouching of the wax coating inadvertent operation may result. applied to the wrench flats and frame Absence of an escutcheon, which is arms is permitted,and the retouching is used to cover a clearance, may delay to be performed only at the time of the the time to sprinkler operation in a fire initial sprinkler installation. situation. The steel rod should be heated only Sprinklers which are found to be leaking to the point at which it can begin to or exhibiting visible signs of corrosion melt the wax, and appropriate precau- must be replaced. tions need to be taken when handling the heated rod in order to prevent the Automatic sprinklers must never be installer from being burned. painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated,should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. TFP151 Page 8 of 8 P/N 57 - XXX - X - XXX I I SIN SPRINKLER TEMPERATURE FINISH RATING 530 2.8K UPRIGHT(1/2"NPT) TY1151 1 NATURAL BRASS 135 135°F(57°C) 531 2.8K PENDENT(1/2"NPT) TY1251 3 PURE WHITE(RAL9010)* 155 155°F(68°C) POLYESTER 570 5.6K UPRIGHT(1/2"NPT) TY3151 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER 571 5.6K PENDENT(1/2"NPT) TY3251 5 JET BLACK(RAL9005)*" 200 200°F(93°C) POLYESTER 590 8.0K UPRIGHT(3/4"NPT) TY4151 6 WAX COATED 286 286°F(141°C) 286°F(141°C)MAX 591 8.0K PENDENT(3/4"NPT) TY4251 7 LEAD COATED 360 360°F(182°C) 560 8.0K UPRIGHT(1/2"NPT) TY4851 8 WAX-OVER-LEAD 000 OPEN*** 286°F(141°C)MAX 561 8.0K PENDENT(1/2"NPT) TY4951 9 CHROME PLATED Notes: " Eastern Hemisphere sales only "* Available in only 8.0K,155°F(68°C)or 200°F(93°C); requires lead time to manufacture ***Available only for 8.0 K-factor TY4151 and TY4251 for use in deluge systems ("OPEN" indicates sprinkler assembly without glass bulb, button,and sealing assembly) TABLE C SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Wax Sticks (for retouching wrench-damaged Warranty Procedure wax coating) Specify:(specify color, below)Colored For warranty terms and conditions,visit Contact your local distributor for Coded Wax Stick for retouching(specify www.tyco-fire.com. availability. When placing an order, temperature rating)temperature-rated indicate the full product name and Part Series TY-B Sprinklers, P/N(specify) Number(P/N). Black for 135°F(57°C) P/N 56-065-1-135 Red for 155°F(68°C) P/N 56-065-1-155 Sprinkler Assemblies with Yellow for 175°F(79°C) P/N 56-065-1-175 NPT Thread Connections Blue for 200°F(93°C) and 286°F(141°C) P/N 56-065-1-286 Specify: Series TY-B (specify SIN), (specify K-factor), (specify Upright Note: Each wax stick is suitable for or Pendent) Sprinkler with (specify) retouching up to 25 sprinklers. temperature rating, (specify) finish or coating, P/N(Refer to Table C) Note: The wax used for 286°F (141°C) sprinklers is the same as for 200°F(93°C) Recessed Escutcheon sprinklers,and,therefore,the286°F(141°C) Specify: Style (10 or 40) Recessed sprinkler is limited to the same maximum Escutcheon with(specify)finish, P/N* ceiling temperature as the 200°F(93°C) *Refer to Technical Data Sheet TFP770 sprinkler(i.e., 150°F166°C]). Sprinkler Wrenches Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 • GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. VI �.`CO TEFLON is trademark of the DuPont Corporation. Fire Protection Products