Loading...
Report OFFICE COPYFP) ab�� dOD�� • 1°I80 s' J D .P\f-- PRIME ELECTRICAL SERVICES, LLC. RECEIVED Electrical 1 Communications♦ Life Safety* Security♦ CCTV PO Box 872395 Vancouver,WA 98687•Phone(360)335-3565 MAY 62020 OR CCB#217825♦ WA#PRIMEES822BE CITY OF TiGARD BUILDING DIVISION FIRE ALARM SYSTEM SUBMITTAL DURHAM ELEMENTARY SCHOOL 7980 SW Durham Rd. Tigard, OR 97224 March 30, 2020 Proposed by Prime Electrical Services PO 20-161 Project Manager: Oleg Primachenko Honeywell I Intelligent Fire Panel with Voice saENT KNIGHT 6820EVS Emergency Voice System and Fire Alarm MBE Control. Panel. The 6820EVS is a fire alarm control panel(FACP)and emergency mass = — — notification system conveniently integrated and housed in one panel,and = _ meets the requirements for mass notification as described in UL 2572. The 6820EVS is a direct replacement for the 5820XL-EVS panel.The 6820EVS can be configured to achieve an overall point capacity of up to 1110 points and connect up to 17 panels in a single communications link. The 6820EVS has one built-in signaling line circuit(SLC),which can 6820EVS support 159(SK)System Sensor®sensors and 159 SK modules or 127 buildings where new wiring is not allowed,or to (SD)Hochiki"devices per loop.To increase point capability,additional SLC provide an easy install fire system for new loops can be added using the 6815 SLC expander for SK devices or the construction projects.SWIFT devices can be 5815XL expander for SD devices,increasing the point capacity to a combined with other hard-wired 6820EVS maximum of 1110 points for SK devices and 635 points for SD devices. compatible devices. Three additional SLCs are needed to reach 1110 points(SK devices).Four The 6820EVS has a form-C trouble relay,and two additional SLCs are needed to reach 635 points(SD devices). programmable form-C relays,along with powerful The common communications and annunciation link allows up to 17 features such as drift compensation,pre-trouble panels to be connected via copper or fiber optic cable.A designated panel maintenance alert,a built-in sensor test to is configured as the communicator for all panels in the link for convenient comply with NFPA 72 calibration testing single-point communications.It also has a built-in,dual-line POTs and IP requirements,and calibration trouble alert.The communicator with optional cellular reporting available. 6820EVS supports a variety of devices,including the 6860,5860,and 6855 remote annunciators, The emergency communication system operations include an onboard 5824 serial parallel printer interface module(for supervised microphone,and all-call and non-active call buttons can printing system reports),the 5496 NAC expander, quickly select all active or all non-active output groups.The system also 5895XL power module,and SK or SD devices. allows for ECS messages to take priority over fire. The panel also has four user-programmable SWIFT" wireless compatibility provides options for wireless detection buttons which are idealfor programming simple, through a Class A mesh network.It is ideal for hard-to-wire locations, complex,and routine tasks. FEATURES & BENEFITS • Up to 1110 points for • 15 recordable one • Built-in annunciator • JumpStart®auto • Programmable date greater design minute messages can with a large 160 programming feature setting for automatic flexibility.Additional be mapped to eight character,4 x40 LCD for easy programming and Daylight Saving SLCs can be added different EVS buttons display • Built-in dual path Time changes until maximum point • Built-in USB interface • Four user- POTS and IP • Flexput®circuits can levels are reached for convenient programmable communications with be individually • Connect up to 17 programming buttons minimize time optional cellular programmed to panels on one site with spent executing models available for function as • Convenient convenient single- field-upgradeable complex or routine reliable backup notification circuits, point access; tasks reporting auxiliary power firmware compatible with mixed 16 built-in speaker outputs,or initiating •FACP models group switches; circuits that support expandable to 32 both 2-and 4-wire smoke detectors ( SIGNAL LINE CIRCUIT(SLC) alarm, supervisory,system trouble, Suitable for automatic,manual,waterflow, sprinkler supervisory(DACT non-coded) The 6815 signal line circuit(SLC) system silenced and system power. signaling services. supports multiple device types of SK System operations include silencing UL Listed:S2766 protocol,while the 5815XL signal tine alarms and troubles,resetting alarms CSFM 7165-0559:0500 circuit(SLC)supports multiple device and the display of alarm troubles and FDNY COA#6249 types of SD protocol.You cannot mix memory.The system's non-volatile event FM approved SD and SK SLC devices on a FACP. history buffer stores 1,000 events for UL listed for Continuous or ANSI 520Hz viewing from the built-in or remote speaker tones that meet NFPA 72 Low The 6820EVS has one built-in annunciator.System operations can be Frequency Signal Requirements for signaling line circuit(SLC)which initiated with a mechanical firefighter's Sleeping Areas when used with the EVS- supports multiple devices.Additional key or a valid 4-to 7-digit operator's INT50W or EVS-100W amplifiers and points can be added using up to three code. compatible speakers 6815 SLC expanders to increase overall capacity to 1,110 maximum PROGRAMMING ORDERING INFORMATION points(SK devices)or by adding The 6820EVS system offers several 6820EVS:Emergency Communication up to four 5815XL SLC expanders options to simplify and speed-up System with FACP.(Red cabinet). to reach 635 maximum points(SD programming.JumpStart° COMPATIBLE ANNUNCIATORS devices).The number of SLCs which AutoProg ramming minimizes can be used within one system is programming required to start a new 6860:4x40 LCD remote fire annunciator (4 tines and up to 160 characters)per only limited by point count.(See the system.The built-in keypad,or the 6860, system;four programmable buttons Manual for additional information.) 5860 or 6855 remote annunciators give you on-site access to current system 5860:4x20 LCD remote fire annunciator. The 6820EVS SLC loops support 5860 is gray;5860R is red programming.Programming can also be multiple device types,maintenance 6855:4x20 LCD remote fire annunciator accomplished using the Windows°- alerts,and a built-in sensor test to 5865-3/5865-4:LED annunciators can comply with NFPA 72 calibration based Honeywell Fire Software Suite (HFSS)program. display up to 30 LEDs(15 red and 15 testing requirements. yellow).The 5865-4 has key switches for SOFTWARE TOOLS INDICATOR LIGHTS silence and reset,and a system trouble SKST:Silent Knight Selection Toot LED. • General Alarm(Red):Flashes if in provides the installer or design architect 5880:The 5880 LED/10 module alarm;solid when alarm is silenced with a Windows®software system • Supervisory(Yellow):Flashes if a configuration tool to create a detailed Bill has 40 programmable LED outputs and supervisory condition exists;solid eight supervised dry contact inputs of Material(BOM)and battery when supervisory is silenced which are useful for custom applications. calculations. • System Troubles(Yellow):Flashes You can use up to eight 5880 modules HFSS:Honeywell Fire Software Suite if a trouble condition exists;solid on one control panel for maximum provides communication and panel when trouble is silenced flexibility. • System Silenced(Yellow):On programming,detector status,event when an alarm,trouble or history and additional data.Requires a 6820EVS COMPATIBLE DEVICES AND PC running Microsoft®Windows®. ACCESSORIES supervisory condition has been See the data sheets listed below for a silenced but not yet cleared ADDITIONAL INFORMATION complete listing of the SK,SD or SWIFT • System Power(Green):Flashes for Twisted-unshielded pair wire is devices. AC failure;solid when power recommended.The 6820EVS also has 53623:SK Devices Data Sheet 53624:SD Devices Data Sheet systems are normal 13 preset notification cadence patterns 350614,350616&350618:SWIFT (including ANSI 3.41). wireless devices USER INTERFACE For a complete and current listing of The 6820EVS built-in 4 x 40 AGENCY LISTINGS AND APPROVALS compatible devices and accessories,visit annunciator with 160 character LCD NFPA 13,NFPA 15,NFPA 16,NFPA 70, www.silentknight.com display and large easy-to-use tactile NFPA 72:Central station;remote Important:You cannot mix SK and SD Signaling;Local Protective Signalingdevices in the same fire alarm system. touchpad can be used for system 9 g: operation,programming and Systems;Auxiliary Protected Premises maintenance.It has five LEDs for Unit;Water Deluge releasing service. Page 2 of 4—351606:B 9/26/2018 • SK COMPATIBLE ADDRESSABLE B200S-LF:Low-frequency intelligent WSK-PHOTO-T:Wireless Multi-criteria DEVICES sounder base photoelectric smoke detector with thermal SK-ACCLIMATE:Multi criteria B224RB(-IV;WH):Relay base detection(135°Ffixed temperture)and photoelectric smoke detector with thermal B224RB: Relay base B510W 4"base 135°F fixed temperature B224B1(-IV;WH):Isolatorbase WSK-H EAT:Wireless Heat,(135°F fixed SK-BEAM:Reflected beam smoke detector B224B1: Isolator base temperture)and B510W 4"base without test feature WSK-HEAT-ROR:Wireless heat,ROR SK-BEAM-T:Reflected beam smoke SD COMPATIBLE ADDRESSABLE (135°F fixed temperture)and B510W 4" detector with test feature DEVICES base SK-CONTROL:Supervised control module SD505-6AB:Addressable 6"base WSK-MONITOR:Wireless monitor module SK-CONTROL-6:Six circuit supervised SD505-6IB:Addressable 6"short circuit WSK-RELAY:Wireless relay module control module isolator base SD505-6RB:Addressable 6"relay base W-USB:SWIFT Tools USB transceiver used SK-DUCT:Photoelectric duct smoke for communication with SWIFT devices detector with extended air speed range SD505-6SB:Addressable 6"sounder base SK-FIRE-CO:Four criteria fire and carbon SD500-AIM:Addressable input module SBUS ACCESSORIES monoxide detector (switch input) 6815:Each Single Line Circuit allows for SK-HEAT:Fixed thermal detector(135°F) SD500-ANM:Addressable notification an additional 159 SK modules and 159 SK SK-H EAT-W:Fixed thermal detector module sensors to be added to the system-up to (135°F),white SD500-ARM: Addressable relay module 1,110 total points.Supports System Sensor SK-HEAT-ROR:Fixed rate of rise detector SD505-DTS-K: Remote test switch and SK devices only. LED indicator for the SD505-DUCTR 5815XL:Each Single Line Circuit provides (135°F) SD505-DUCT:Addressable Duct Smoke an additional 127 SD devices to be added to SK-HEAT-ROR-W:Fixed rate of rise Detector. the system-for a maximum of 635 points. detector(135°F),white SD505-DUCTR:Addressable Duct Supports SD devices only. SK-HEAT-HT:Fixed high temperature Detector housing with relay base. 5496:A 6 amp notification power expander thermal detector(190°F) SD505-HEAT:Absolute temperature heat with four power-limited notification SK-HEAT-HT-W:Fixed high temperature detector.Trip point range from 135°F-150° appliance circuit outputs. thermal detector(190°F),white F(0°C-37°C). 5883:Relay Interface.Provides 10 Form C SK-ISO:Fault isolator module SD500-LIM:Addressable Line isolator relays. SK-MINIMON:Mini monitor module module 5824:Serial/Parallel Printer Interface SK-MONITOR:Monitor module SD500-MIM:Addressable Mini input Module for printer connection. SK-MONITOR-2:Dual input monitor monitor module(switch input) 5895XL:Power Supply with six Flexput'' module SD505-PHOTO:Photoelectric smoke circuits,and two Form C relays.Max.16 per SK-MON-10:10 input monitor module detector system. SK-PHOTO:Photoelectric smoke detector SD500-PSI-PSDA:Addressable Single or 5815RMK:Remote mounting kit. SK-PHOTO-W:Photoelectric smoke dual action pull station Dimensions 10 3/8"W x 10-3/16"H x 3"D detector,white SD500-SDM:Addressable smoke detector SK-PHOTO-T:Photoelectric smoke detector module EVS ACCESSORIES with thermal(135°F fixed temperature) EVS-50W:50 Watt Amplifier* AUDIBLE/VISIBLE DEVICES These AV EVS-125W:125 Watt Amplifier* SK-PHOTO-T-W:Photoelectric smoke devices are all 2-wire.Color:"R"indicates EVS-100W:50/100 Watt Amplifier* detector with thermal(135°F fixed red;"W"denotes white.For a complete EVS-100WBU:External Backup Amplifier temperature),white listing of Silent Knight AV devices go to EVS-INT5OW:50 Watt Internal Amplifier SK-PHOTOR:Photoelectric detector withw silentkni ht.com. remote test capability 9 EVS-CE4:Circuit Audio Expander SK-PHOTO-R-W:Photoelectric detector CHSRL/CHSWL:Wall chime/strobe EVS-SW24:24 Switch Expander with remote test capability,white CHSCRL/CHSCWL:Ceiling chime/strobe EVS-VCM:Voice Control Module SK-PULL-SA:Addressable single action CHRL/CHWL:Wall chime EVS-LOC:Local Operator Console** pull station HRL/HWL:Wall horn *Support for up to four amplifiers;500W SK-PULL-DA:Addressable dual action pull P2RL/P2WL:Wall horn/strobe maximum.Each amplifier has four built-in station SK-RELAY:Addressable relay module SK- PC2RL/PC2WL:Ceiling horn/strobe speaker circuits expandable to eight. RELAY-6:Addressable Six relay control SRL/SWL:Wall strobe **Supports up to four EVS-LOCs module SCRL/CCWL:Ceiling strobe SK-RELAYMON-2:Addressable Dual SPSCRL/SPSCWL:Ceiling speaker/strobe COMMUNICATION OPTIONS relay/monitor module CELL-CAB-SK:Cellular communicator, SK-ZONE:Addressable zone interface SPSRL/SPSWL:Wall speaker/strobe module SPRL/SPWL:Walt speaker metal enclosure with lock/key* SK-ZONE-6:Six zone interface module SPCRL/SPCWL:Ceiling speaker CELL-MOD:Cellular communicator,plastic enclosure* B300-6(-IV):6"base for SK-W Series B210LP:6"mounting base SWIFT WIRELESS DEVICES *Sole path,powered by panel. B501(-BL;IV;WHITE):4"flangeless base SWIFT is only compatible with System IPGSM-4G:Dual path fire alarm B501:4"Flangeless mounting base Sensor(SK)devices.It is not compatible communicator,cellular and/or IP(primary B200S(-IV,-WH):Intelligent sounder base with Hochiki(SD)devices. or backup,selectable) B200S:Intelligent sounder base SK-IP-2:Remote reporting via the Internet. g WSK-WGI:Wireless Gateway Requires a VisorAlarm' receiver at the B200S-LF(-IV,-WH):Low-Frequency WSK-PHOTO:Wireless Photoelectric smoke central station intelligent sounder base detector Page 3 of 4—351606:B 9/26/2018 6820EVS Technical Specifications MISC.ACCESSORIES ELECTRICAL Flexput",Honeywell", SK-NIC:Network Interface Card.Provides a 6820EVS Primary AC:120AC @ 60Hz,3.34Totat JumpStart ,Silent Knight , common communications link for the 6820EVS. Accessory Load:6A®27.4VDC power-limited SWIFT,and System (Panels cannot be linked together for peer-to-peer Standby Current:190mA Sensor'are registered networking). trademarks of Honeywell Alarm Current:250mA International Inc. SK-NIC-KIT:Installation Accessory Kit Battery Charging Capacity:7 to 35AH SK-FML:Fiber Optic Multi Mode,transmitter and Hochiki"is a registered Battery Size:18AH max.allowed in control panel trademark of Hochiki receiver cabinet.Larger capacity batteries can be housed in Corporation.Microsoft" SK-FSL:Fiber-Optic Single Mode RBB:Remote RBB accessory cabinet. and Windows'are battery box accessory cabinet or batteries that are registered trademarks of too large to fit in the FACP cabinet.Dimensions:16" Microsoft Corporation. Wx 10"H x 6"D(406mm W x 254mm H x 152mm Six conductor wiring:4 SBUS and 2 Voice Bus D). This document is not SK-SCK:Seismic Compliance Kit used to securely FLEpXPUUT®CIRCUITS intended to be used for fasten batteries to the fire anel. Six programmable circuits which can be installation purposes.We p programmed individually as: try to keep our product information up-to PHYSICAL Notification Appliance Circuits:3A @ 27.4VDC date and accurate.We per circuit,power-limited(with a panel maximum cannot cover all specific Overall Dimensions:21.59"W x 28.1"H x 5.05"D current of 6A) applications or anticipate Shipping Weight:50 lbs. Auxiliary Power Circuits:3A®27.4VDC per circuit, all requirements.All specifications are subject Color:Red power-limited to change without notice. Initiating Circuits(Circuits 5 and 6 Only):100mA ENVIRONMENTAL @ 27.4VDC per circuit,powerlimited For Technical Sup port, Operating Temperature:32°F to 120°F (0°C to 800-446-6444. 49°C) Supports Class B(Style 4)and Class A(Style 6) Humidity:0 to 93°/o relative humidity(non- configuration for SLC,SBUS,and Flexput circuits condensing WIRING:See the product manual for wiring details Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472 Honeywell 800-328-0103 351606 I B 109/18 www.silentknight.com SILENT ©2018 Honeywell International Inc. iliaKNIGHT r _ Honeywell SILENT KNIGHT 5860 Remote Annunciator The 5860 remote annunciator,can be used to operate and program Honeywell Silent Knight fire alarm control panels(FACPs)from anywhere within the system. 5x .. w., The 5860 features include an 80-character backlit LCD providing easy-to understand system messages.The annunciator is ergonomically designed `: , N w A with over-sized buttons for the most frequently used features,like Reset .- < .7 a s and Silence. x 8 y In addition to status messages displayed on the LCD,there are five LEDs for alarm,supervisory,trouble,silence,and AC power status. The 5860 annunciator is available in gray to match virtually any decor and 5860/5860R red for applications where the annunciator must stand out.The annunciator enclosure can be surface or flush mounted.A trim ring kit is available for surface mounting. COMPATIBILITY The 5860 is compatible with the following Honeywell Silent Knight FACPs: 6820:Addressable fire alarm control panel with up to 1,110 addressable points 6820EVS:Addressable fire alarm control panel with an emergency communication systems and up to 1,110 addressable points 6808:Addressable fire alarm control panel with up to 198 addressable points 6700:Addressable fire alarm control panel with up to 100 addressable points 5820XL:Addressable fire alarm control panel 5820XL-EVS:Addressable fire alarm control panel with an emergency communication systems 5808:Addressable fire alarm control panel 5700:Addressable fire alarm control panel FEATURES & BENEFITS • 80-character backlit • Support for • Five Status LEDs • Accommodates wiring • Accepts user codes or LCD display(4 lines simultaneous use of • Available in red or light lengths up to 6000 ft. fire fighter's key with 20 characters per multiple 5860s gray color from the control panel • Larger keypad buttons line) • Easily view current for added design and makes it easier to • Tactile/audible status by alarms, install flexibility maneuver for system feedback when a key is supervisories,or reset and silencing pressed on the troubles annunciator • Uses the RS-485 SBUS to interface with the panel 5860 Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit www.silentknight.com. Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Wire Runs Up to 6000 Feet From FACP Silent Knight and • Honeywell'are registered trademarks of Honeywell International,Inc. �_ _� .04 4".0 U U E E E SBUS w*04a q fis= �0"® w ► t# +�4""". , fit This document is not intended to be used for 5860 5860 5860 installation purposes.We try to keep our product •Up to Eight 5860s Per 5700 or 6700 System information up-to •Up to 12 5860s Per 5808,6808,5820XL,or 5820XL-EVS System date and accurate.We •Up to 16 5860s per 6820 or 6820EVS System cannot cover all specific Compatible Silent Knight FACP applications or anticipate all requirements.All specifications are subject to change without notice. For Technical Support, 5860 Features call 800 446 6444. PHYSICAL ORDERING INFORMATION Dimensions:9.1"W x 7.4"H x 1.5"D(23.1W x 18.8H x 5860:Remote Annunciator,four line(4x20)LCD 3.8D cm) annunciator with 20 characters per line.Gray Shipping Weight:2.8 lbs(1.3 kg) 5860R:Remote Annunciator,four line(4x20)LCD Color:5860R:Red;5860:Gray annunciator with 20 characters per line.Red ENVIRONMENTAL ACCESSORIES Operating Temperature:32°F to 120°F(0°C to 5860TR:Red Trim Ring for surface mounting 49°C) 5860TG:Gray Trim Ring for surface mounting Humidity:10%-93%non-condensing) AGENCY LISTINGS AND APPROVALS ELECTRICAL UL listed Operating Voltage:24VDC CSFM approved Standby Current:20mA Meets NFPA 72 requirements Alarm Current:25mA FM approved MEA approved For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3502241 Rev J 1 12/17 UM SILENT 800-328-0103 ©2017 Honeywell International Inc. Ilind KNIGHT -71 hill Honeywell DSILENT• KNIGHT EVS-100W Intelligent 50/100 Watt Amplfier with optional backup Amplifier The EVS-100W is an intelligent 50/100 watt amplifier for use with Version 14.0 or newer 5820XL-EVS or the 6820EVS.The EVS-100W is used to amplify audio message for distribution throughout a facility.The EVS- 100W is capable of producing up to 100 watts of audio power and has the ability to provide an option for 50 watts of backup power. Description The EVS-100W has its own power supply with battery backup and eight speaker circuits.The EVS-1O0W is fully supervised by the main panel for trouble conditions EVS-100W Amplifier Configurations: • 50 watts with 50 watts as backup. • 100 watt single channel. • 1OO watt single channel with 50 watts backup using EVS-100WBU COMPATIBILITY The EVS-1O0W is compatible with the following Honeywell Silent Knight Series FACPs: • 682OEVS:Addressable fire alarm control panel with an emergency voice system,up to 1,110 addressable points,and four programmable buttons that can be programmed for routine or complex tasks • 582OXL-EVS:Addressable fire alarm control panetwith an emergency voice systems and up to 792 addressable points FEATURES & BENEFITS • Built in backup • Amplifier Bandwidth • Can be mounted up to • UL listed for • 120 VAC or 240 VAC amplifier test feature 400 Hz to 4000 Hz 6000 feet away from Continuous or ANSI operation allows you to • Six-wire connection to 5820XL-EVS or 520Hz speaker tones physically test that the 6820EVS control that meet NFPA72 EVS system:Two-wires backup amplifier is for the voice bus and panel Low Frequency Signal operating properly four-wires for the • UL 864 and UL 2572 Requirements for • Up to four amplifiers SBUS connections Sleeping Areas.See the FACP manual fora per 5820XL-EVS or list of compatible 6820EVS distributed speakers between up to 32 audio circuits • EVS-100W Technical Specifications Fora complete listing of all compliance approvals and PHYSICAL ORDERING INFORMATION certifications,please visit Flush Mount Dimensions:14.5"W x 24.75"H x EVS-100W:Intelligent 50/100 Watt Amplifier www.sitentknight.com. 3.4"D(36.8 W x 62.9 H x 8.7 D cm) Microsoft,Windows,and Overall Dimensions:16.1"W x 26.5"H x 4.1"D(40.6 ACCESSORIES the Windows Logo are Wx 66.7 H x 10.5 D cm) EVS-100WBU:External Backup Amplifier registered trademarks or trademarks of Color:Red. RBB:Remote Battery Box Accessory Cabinet.Use Microsoft Corporation. for backup batteries up to 35AH ENVIRONMENTAL Silent Knight`°'and Operating Temperature:32°F—120°F(0°C— AGENCY LISTINGS AND APPROVALS Honeywell'are registered 49°C) UL 864 and UL 2572 trademarks of Honeywell International,Inc. Humidity:10%—93%non-condensing Meets the requirements for NFPA 72 Local Protective Signaling Systems&Emergency This document is not ELECTRICAL Communication Systems. intended to be used for Primary AC:120VAC @ 60Hz;240VAC @ 50Hz CSFM:7165-0559:0500 installation purposes.We tryto keep our product Standby Current:EVS-100W 25V 110mA;EVS- information up-to 100W 70.7V 110mA date and accurate.We Alarm Current:EVS-100W 25V,1.2 A;EVS-100W cannot cover all specific 70.7V,1.4 A applications or anticipate all requirements.All Total Power:100 W®25 VRMS or 70.7 VRMS specifications are subject •Circuit 1-4:50 W max. to change without notice. •Circuit 5-8:50 W max. For Technical Main EVS Panel SBUS Standby&Alarm:10mA Support,Please call Battery Charging Capacity:7-35AH 800-446-6444. Battery Size:18AH max allowed in cabinet.Use RBB accessory cabinet for larger batteries up to 35 AH per system. Voice Integration Wiring: • Six conductor • Two voice bus • Four SBUS For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight Honeywell 12 Clintonville Road SILENT Northford,CT 06472 Doc 3509611 Rev El 05/18 avictrr 800-328-0103 ©2018 Honeywell International Inc. Honeywell SILENT cm KNIGHT 5496 Intelligent Power Module The 5496 intelligent power module is the most cost-effective power supply available today.It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor°,Gentex°, AMSECO,and Wheelock°.The 5496's advanced microprocessor design is years ahead of the competition.Its switch mode power supply design is up to 50%more efficient than competitive linear mode power supplies. The 5496 is a 6 amp notification power expander that provides its own AC power connection,battery charging circuit,and backup battery for use with the Honeywell Silent Knight series fire alarm control panels(FACPs).The 5496 is the cost-effective solution for powering notification appliances required by the Americans with Disabilities Act (ADA).The 5496 has built-in ANSI cadence pattern.The output circuits can be programmed as notification appliance circuits,or as auxiliary power(configurable for constant,resettable,or door holder power). Ikitl s,'■ Compatibility 5496 The 5496 is compatible with the following Honeywell Silent Knight FACPs: • 6820/6820EVS • 5820XL/5820XL-EVS • 6808 • 6700 • 5808 • 5700 FEATURES & BENEFITS • UL Listed for 6 amps • Built-in • NACs are • Communicates to the • Lightweight design of notification power synchronization for programmable as FACP via 4-wire SBUS adds to ease of • Power su l s appliances from notification appliance (wire runs up to 6000 installation and pp y Gentex,AMSECO, circuits,or as auxiliary ft) reduces shipping advanced switch mode System Sensor,and power to be used as costs design reduces • AC loss delay option damaging heat and Wheelock constant,resettable, shuts off power to • ANSI Cadence pattern manages power up to • Four power-limited or door holder power non-essential high output capability 50%more efficiently notification outputs;2 • 3 amps per output current accessories built-in than other systems Class A or 4 Class B,or circuit like magnetic door • UL 864,1481&1971 1 Class A and 2 Class holders • 24 VDC filtered output • Ground fault detector listed voltage •• CSFM approved MEA approved • OSHPD(CA) OSP-0065-10(see accessories) 5496 Technical Specifications For a complete listing of all compliance approvals and certifications,please visit 4 Outputs Programmable www.silentknight.com. as Notification Appliance Circuits, or as Auxiliary Power Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Output 1 , j SBUS Communication Microsoft Corporation. To a Compatible Silent Knight FACP System Sensor'and Output 2 Honeywell'are registered ► trademarks of Honeywell Output 3 . International,Inc This document is not intended to be used for Output 4 A40installation purposes.We try to keep our product information up-to Auxiliary Power Can Be date and accurate.We cannot cover all specific Programmed To Be Constant, applications or anticipate Resettable, or Door Holder Power all requirements.All specifications are subject to change without notice. For Technical Support, PHYSICAL required on each Class B circuit call800-446-6444 Overall Dimensions:16"H x 12.25"W x 3"D(40.6 x Battery Charging Capacity:7.0—35.OAH 30.9 x 7.6 cm) Shipping Weight:8.71bs ORDERING INFORMATION 5496:Intelligent Power Module ENVIRONMENTAL Operating Temperature:32°F to 120°F (0°C to ACCESSORIES 49°C) RBB: Remote Battery Box Accessory Cabinet.16" Humidity:10 to 93%relative humidity(non- W x 10"H x 6"D(406 mm Wx 254 mm H x 152 mm condensing) D) SK-SCK: Seismic Compliance Kit ELECTRICAL: AC Input:120VAC at 2.7A AGENCY LISTINGS AND APPROVALS Output:24VDC at 6A • CSFM approved Standby&Alarm Current:10mA Notification/Aux.Power Circuits:4 • NFPA72 Output Configuration: 2 Class A(Style Z) • UL listed 4 Class B(Style Y) • FM approved 1 Class A&2 Class B Amps Per Output Circuit:3.0(6.0 amps total) • City of NY:429-90-E Vol XIV Notification Circuit Output:20.4—27.3VDC @ 3.0A each End-of-Line Resistance:4.7k W EOL resistor For more information Learn more about Silent Knight's Product and other products available by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 800 328 0103 Doc 3503871 Rev FI 11/17 SILENT www.silentknight.com ©2017 Honeywell International Inc. kJ KNIGHT Honeywell ® SILENT' KNIGHT SK-ISO Intelligent Fault Isolator Module The SK-ISO is an addressable line isolator module for use with the Honeywell Silent Knight Series fire alarm control panels(FACPs). The SK-ISO acts as an automatic switch that opens when the line voltage on the signaling line circuit(SLC)loop drops below four volts.Isolator modules should be spaced between groups of sensors or modules in a loop to protect the rest of the loop.If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them.The remaining units on the SLC loop continue to fully operate.No more than 25 devices are recommended for each group. SK-ISO INSTALLATION The SK-ISO mounts directly into a 4"square electrical box.The box must have a minimum depth of 2-1/8".A surface mount electrical box(System Sensor°PN SMB500)is available from Silent Knight. FEATURES & BENEFITS • Panel controlled • Protects the modules • SEMS screws for easy status LED that on the SLC loop so wiringUL Listed flashes green in other devices continue • CSFM Listed ati normal state and is to operate solid red in alarm • FM Approved • Standard 4 inch • Isolates short circuits electrical box on an SLC loop mounting 'it • • SK-ISO Technical Specifications For a complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:4.5"H x 4"W x 0.25"D(11.4 x 10.2 x SK-ISO:Line isolation module 6cm) Microsoft,Windows,and Shipping Weight:6.3 oz(196 g) ACCESSORIES the Windows Logo are registered trademarks SM6500:4"Square Surface Mount Electrical Box or trademarks of ELECTRICAL Microsoft Corporation. Operating Voltage:15—32 VDC COMPATIBILITY Standby Current:450 µA max(not isolating;relay The SK-ISO is compatible with the following Sennss r'Knight, e Sens and Honeywell' closed) Honeywell Silent Knight fire alarm control panels: are registered Isolation Current:5mA max 6820:Addressable fire alarm control panel trademarks of Honeywell Fault Detection Delay:250ms min. 6820EVS:Addressable fire alarm control panel International,Inc. Fault Detection Threshold:4V with an emergency voice system. This document is not Line Restoration Threshold:7V 6808:Addressable fire alarm control panel intended to be used for 6700:Addressable fire alarm control panel installation purposes.We try to keep our product ENVIRONMENTAL 5700:Addressable fire alarm control panel information up-to Operating Temperature:32°F—120°F(0°C— 5808:Addressable fire alarm control panel date and accurate.We 49°C) 5820XL:Addressable fire alarm control panel cannot cover all specific Humidity:100/0—93%non-condensing 5820XL-EVS:Addressable fire alarm control panel applications or anticipate all requirements.All with an emergency voice system specifications are subject to change without notice. For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501341 Rev F 111/17 EMI SILENT 800-328-0103 ©2017 Honeywell International Inc. KNIGHT Honeywell ® SILENT'KNIGHT SK-MONITOR Intelligent Monitor Module The SK-MONITOR is an addressable monitor module for use with Honeywell Silent Knight Series fire alarm control panels(FACPs).The SK-MONITOR is intended for use in intelligent,two-wire systems,where individual address of each module is selected using the built-in rotary switches. M The SK-MONITOR supports Class A supervised or Class B supervised s_ 411. ^e.. wiring to the load device.Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. INSTALLATION The SK-MONITOR mounts directly into a 4"square electrical box.The box must have a minimum depth of 2-1/8".A surface mount electrical box (System Sensor°PN SMB500)is available from Silent Knight. SK-MONITOR i#a ,;!Al FEATURES & BENEFITS 'E • Panel controlled • UL Listed • Single contact monitor • Support for Class A status LED that • Rotary address < and Class B wiring flashes green in switches for fast normal state and is installation • Fully supervised solid red in alarm 1 • SEMS screws for easy -,� wiring .j? • SK-MONITOR Technical Specifications For a complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Height:4.5"H x 4"W x 1.25"D(11.4 X 10.2 X 3cm) SK-MONITOR:Monitor Module Microsoft,Windows,and Shipping Weight:6.3 oz(196 g) the Windows Logo are ACCESSORIES. registered trademarks ELECTRICAL SM B500:4"Square surface mount electrical box or trademarks of Operating Voltage:15—32VDC Microsoft Corporation. Current Draw(LED on):5.0mA max COMPATIBILITY Silent Knight`°',System Operating Current(LED flashing):375µA The SK-MONITOR is compatible with the Sensor'and Honeywell° Standby Current:400 µA max @ 24 VDC(one following Honeywell Silent Knight fire alarm are registered control panels: trademarks of Honeywell communication every 5 sec with 47K EOL);550 µA Y max 24 VDC(one communication every 5 sec 6820:Addressable fire alarm control panel International,Inc. with EOL<1K) 6820EVS:Addressable fire alarm control panel This document is not 5.5 mA(with LED latched on) with an emergency mass notification system. intended to be used for LED Current:5.5 mA(with LED latched on) 6808:Addressable fire alarm control panel installation purposes.We End-of-Line Resistance:47K S2 6700:Addressable fire alarm control panel try to keep our product information up-to Initiating Device Circuit Wiring Resistance:1,500 5700:Addressable fire alarm control panel date and accurate.We S2 max 5808:Addressable fire alarm control panel cannot cover all specific SLC Loop Resistance:40 S2 max. 5820XL:Addressable fire alarm control panel applications or anticipate all requirements.All ENVIRONMENTAL 5820XL-EVS:Addressable fire alarm control panel specifications are subject with an emergency mass notification system to chan ewithoutnotice. Operating Temperature:32°F—120°F(0°C— g 49°C) For Technical Support, Humidity:10%-93%non-condensing cell 800 446 6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501311 Rev G 111/17 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT Honeywell ®SILENT KNIGHT SK-MINIMON Intelligent Mini Monitor Module The SK-MINIMON is an addressable monitor modules for use with the Honeywell Silent Knight fire alarm control panels(FACPs).The SK- MINIMON acts as an interface to contact devices,such as waterflow erit+ 41 , switches and pull stations.The SK-MINIMON supports Class B supervised wiring to the load device.Conventional4-wire smoke detectors can be monitored for alarm and trouble conditions The SK-MINIMON can be mounted in a single gang junction box directly behind the monitored device.Its small size and light weight allow it to be installed without rigid mounting requirements. SK-MINIMON INSTALLATION The SK-MINIMON can be mounted in a single gang junction box directly behind the monitored device.Its smallsize and tight weight allow it to be installed without rigid mounting requirements. FEATURES & BENEFITS • Single contact monitor • Rotary address • SK-Minimon support switches for fast for Class B(Style B) installation contact monitor wiring • UL Listed • Small and lightweight • CSFM Listed size allows for flexible • FM Approved mounting options • SK-MINIMON Technical Specifications For a complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:2.75"W x 1.3"H x 0.5"D SK-MINIMON:Mini monitoring module Microsoft,Windows,and Weight:1.2 oz(37 g) the Windows Logo are COMPATIBILITY registered trademarks ELECTRICAL The SK-MINIMON is compatible with the or trademarks of Operating Voltage:15—32VDC following Honeywell Silent Knight fire alarm Microsoft Corporation. SLC Standby and Alarm Current:350 µA control panels: Silent Knight',System End-of-Line Resistance:47K S2 6820:Addressable fire alarm control panel Sensor'and Honeywell' Initiating device circuit wiring resistance:1,50052 6820EVS:Addressable fire alarm control panel are registered max with an emergency voice system. trademarks of Honeywell 6808:Addressable fire alarm control panel International,Inc. SLC loop resistance:4052 max Wire Length:6"min. 6700:Addressable fire alarm control panel This document is not 5700:Addressable fire alarm control panel intended to be used for ENVIRONMENTAL 5808:Addressable fire alarm control panel installation purposes.We try to keep our product Operating Temperature:32°F—1200 F(0°C— 5820XL:Addressable fire alarm control panel information up-to 49°C) 5820XL-EVS:Addressable fire alarm control panel date and accurate.We Humidity:10%-93%non-condensing with an emergency voice system cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 350133l Rev G 111/17 ®SILENT" 800-328-0103 ©2017 Honeywell International Inc. KNIGHT �Illi�rllll► ---.14411411111- Honeywell SILENT.IGHT®KN SK-RELAY Intelligent Relay Module The SK-RELAY is an addressable relay module for use with Honeywell Silent Knight Series fire alarm control panels(FACPs).The SK-RELAY allows a Silent Knight FACP to switch discrete contacts by code command.The relay contains two isolated sets of Form C contacts,which operate as a DPDT switch.No supervision is provided for the notification appliance circuit. Honeywell S{LE\I The SK-RELAY contacts can be used for virtually any normally open or normally closed application.Each SK-RELAY is programmed with a unique signaling tine circuit(SLC)loop address.When an event occurs that controls the SK-RELAY,the relay is triggered by the FACP. INSTALLATION The SK-RELAY mounts directly into a 4"square electrical box.The box must SK-RELAY have a minimum depth of 2-1/8".A surface mount electrical box(System Sensor®PN SMB500)is available from Silent Knight. FEATURES & BENEFITS • Two sets of Form C • Panel controlled • Polling LED visible contacts status LED that through the cover • Rotary address flashes green in plate switches for fast normal state and is • SEMS screws for easy installation solid red in alarm wiring • Contacts are rated for • Relay programming is • UL Listed a variety of amps(see completely flexible- Specifications) can be mapped to zone conditions SK-RELAY Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. 4.675"H x 4.275"Wx 1.4"D SK-RELAY:Relay Module Shipping Weight:6.3 oz(196 g) Microsoft,Windows,and ACCESSORIES. the Windows Logo are ELECTRICAL registered trademarks SMB500:4"Square Surface Mount Electrical Box or trademarks of Operating Voltage:15—32 VDC CB500:Module Barrier Microsoft Corporation. End-of-Line Resistance:Not used SLC Standby&Alarm Current:.255mA max @ COMPATIBILITY Silent Knight,System Sensor and Honeywell' 24VDC(one communication every 5 sec with LED The SK-RELAY is compatible with the following are registered enabled) Honeywell Silent Knight fire alarm control panels: trademarks of Honeywell 6820:Addressable fire alarm control panel International,Inc. ENVIRONMENTAL 6820EVS:Addressable fire alarm control panel This document is not Operating Temperature:32°F—120°F(0°C— with an emergency mass notification system. intended to be used for 49°C) 6808:Addressable fire alarm control panel installation purposes.We Humidity:10%—93%non-condensing 6700:Addressable fire alarm control panel try to keep our product information up-to RELAY CONTACT RATINGS 5700:Addressable fire alarm control panel date and accurate.We 3.OA 30VDC resistive 5808:Addressable fire alarm control panel cannot cover all specific 5820XL:Addressable fire alarm control panel applications or anticipate O.9A @ 110VDC resistive all requirements.All 0.9A 125VAC resistive 5820XL-EVS:Addressable fire alarm control panel specifications are subject with an emergency mass notification system. to change without notice. 0.5A @ 125VAC inductive(PF=.35) O.7A @ 75VAC inductive(PF=.35) For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501271 Rev G1 11/17 rmSILENT" 800-328-0103 ©2017 Honeywell International Inc. bid KNIGHT SK- PHOTO -W Addressable Photoelectric Smoke Detectors The Silent Knight° SK-PHOTO-W Series feature a modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. - = The SK-PHOTO-W Series intelligent plug-in smoke detectors are designed for both performance and aesthetics,and are direct replacements for the SK-PHOTO Series detectors.A new modern,sleek,contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards.The SK-PHOTO-W Series detector sensitivity can be programmed in the control panel software.Sensitivity is continuously monitored and reported to the panel.Point ID capability allows each detector's address to be set with rotary,decimal address switches,providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level.Dual electronic thermistors add 135°F(57°C)fixed temperature thermal sensing on the SK-PHOTO-T-W. The SK-PHOTO-R-W is a remote test capable detector for use with DNR Series duct detector housings. Fst FEATURES AND BENEFITS • Designed to meet UL 1268 7th Edition steady red in Alarm • Sealed against back pressure • Sleek and stylish contemporary design • Integral communications and built-in • Plugs into separate base for ease of • Stable communication technique with device-type identification installation and maintenance noise immunity • Remote test feature from the panel • Expanded color options • Addressable by device • Built-in functional test switch activated by • SEMS screws for wiring of the separate base • Rotary,decimal addressing(Refer to the external magnet • Optional remote,single-gang LED { Silent Knight panel manuals for device • Walk test with address display(an address accessory capacity) of 121 will blink the detector LED 12- • Optional sounder,relay,and isolator bases '`. • Two-wire SLC connection (pause)-1) • LEDs blink every time the unit is polled • Low standby current • 360°-field viewing angle of the visual alarm • Built-in tamper-resistant feature t't indicators(two bi-color LEDs);LEDs blink • Designed for direct-surface or electrical- Honeywell green in Normal condition and turn on box mounting SILENT �+ 3'v to ®SIL KNIGHT xx=+ • • ' INSTALLATION B200SR-LF-WH:White,Low Frequency Intelligent sounder base The SK-PHOTO-W Series plug-in intelligent thermal detectors use a for retrofit applications separate base to simplify installation,service,and maintenance. B200SR-LF-IV:Ivory,Low Frequency Intelligent sounder base for Installation instructions are shipped with each detector. retrofit applications Mount base(all base types)on an electrical backbox which is at B224RB-WH:White,plug-in System Sensor°relay base least 1.5"(3.81 cm)deep.For a chart of compatible junction boxes, B224RB-IV:Ivory,plug-in System Sensor relay base see SK-61045. B224BI-WH:White,plug-in System Sensor isolator detector base Note:Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required.Wiring"T-taps"or branches B224BI-IV:Ivory,plug-in System Sensor isolator detector base are permitted for Style 4(Class"B")wiring. ACCESSORIES Note:When using relay or sounder bases,consult the SK-ISO TR300:White,replacement flange for B210LP or B300-6 bases installation sheet 156 3627 for device limitations between isolator TR300-IV:Ivory,replacement flange for B210LP or B300-6 bases modules and isolator bases. RA100Z(A):Remote 3-32 VDC LED annunciator,mounts to a U.S. OPERATION single-gang electrical box,for use with B501 and B300-6 bases Each SK-PHOTO-W Series detector uses one of the panel's addresses only (total limit is panel dependent)on the Signaling Line Circuit(SLC).It M02-04-00:Test magnet responds to regular polls from the control panel and reports its type and the status.If it receives a test command from the panel(or a local M02-09-00:Test magnet with telescoping handle magnet test),it stimulates its electronics and reports an alarm.It blinks CK300:White,detector color kit,pack of 10 its LEDs when polled and turns the LEDs on when commanded by the CK300-IV:Ivory,detector color kit,pack of 10 panel.The SK-PHOTO-W Series offers features and performance that CK300-BL:Black,detector color kit,pack of 10 represent the latest in smoke detector technology. PRODUCT LINE INFORMATION Note:"-IV"suffix indicates ivory color. SK-PHOTO-W:White,low-profile photoelectric sensor SK-PHOTO-T-W:White,same as SK-PHOTO-W but includes a built-in 135°F(57°C)fixed-temperature thermal device SK-PHOTO-R-W:White,low-profile intelligent photoelectric sensor, remote test capable,for use with DNR/DNRW B300-6:White,standard flanged low-profile mounting base B300-6-BP:Bulk pack of B300-6,package contains 10 B300-6-IV:Ivory,standard flanged low-profile mounting base B501-WHITE:White,standard European flangeless mounting base B501-BL:Black,standard European flangeless mounting base B501-IV:Ivory,standard European flangeless mounting base 13501-WHITE-BP:Bulk pack of B501-WHITE,contains 10 B200S-WH:White,Intelligent,programmable sounder base B200S-IV:Ivory,Intelligent,programmable sounder base B200SR-WH:White,Intelligent sounder base for retrofit applications B200SR-IV:Ivory,Intelligent sounder base for retrofit applications B200S-LF-WH:White,Low Frequency Intelligent,programmable sounder base B200S-LF-IV:Ivory,Low Frequency Intelligent,programmable sounder base Page 2 of 3—351634:B•7/1/2019 SK-PHOTO-W SERIES TECHNICAL SPECIFICATIONS • PHYSICAL/ENVIRONMENTAL DETECTOR SPACING AND Sensitivity: APPLICATIONS Silent Knight' and System Sensor' o Silent Knight recommends spacing are registered trademarks of - UL Applications:0.5 0/o to 4.0/o per foot Honeywell International,Inc. obscuration. detectors in compliance with NFPA72.In - ULC Applications:0.5%to 3.5%perfoot lowairflowapplicationswith smooth ceiling, This document is not intended to be obscuration space detectors 30 feet(9.1m).For specific used for installation purposes.We information regarding detector spacing, try to keep our product information Size:2.0"(5.3 cm)high;base determines placement,and special applications refer to diameter up-to-date and accurate.We cannot NFPA 72.ASystem Smoke Detector cover all specific applications or - B300-6:6.1"(15.6 cm)diameter Application Guide,document A05-1003,is anticipate all requirements.All - B501:4"(10.2 cm)diameter available at www.systemsensor.com. specifications are subject to change For a complete list of detector bases,see AGENCY LISTINGS AND without notice. SK-61045. APPROVALS Country of origin: Mexico Shipping weight:3.4 oz.(95 g) These listings and approvals apply to the Operating temperature range: modules specified in this document.ln some • SK-PHOTO-W:32°F to 122°F(0°C to 50°C) cases,certain modules or applications may • SK-PHOTO-T-W:32°Fto 100°F(0°C to not be listed by certain approval agencies,or 38°C) listing may be in process.Consult factory for • SK-PHOTO-R-W installed in a DNR/DNRW: latest listing status. -4°F to 158°F(-20°C to 70°C) • UL Listed:S6173 UL/ULC Listed Velocity Range:0-4000 ft/ • FM Approved min.(1219.2 m/min.),suitable for • CSFM:7272-0559:0512 installation in ducts Relative humidity:10%—930/0 non- condensing Thermal ratings:fixed-temperature set point 135°F(57°C),rate-of-rise detection 15°F(8.3°C)per minute,high temperature heat 190°F(88°C) ELECTRICAL SPECIFICATIONS Voltage range:15-32 volts DC peak Standby current(max.avg.):200pA @ 24 VDC(one communication every 5 seconds with LED enabled) Max current:4.5 mA @ 24 VDC("ON") Honeywell Silent Knight Clintonville Road Northford, Honeywell orthford,CT 06472-1610 203.484.7161 351634 I B 107/19 ral SILENT' www.silentknight.com ©2019 Honeywell International Inc. 1164 KNIGHT SK- H EAT-1W SERIES Addressable Heat Detectors The Silent Knight° SK-HEAT-W Series heat detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and advanced thermal technologies make the SK-HEAT-W Series ideal for both system operation and building design. The series includes a 135°F/57°C fixed-temperature,rate-of-rise,and a 180°F/88°C fixed high-temperature detectors and are direct replacements for the SK-HEAT Series heat detectors.The point ID address,set using rotary decimal switches,provide specific detector locations.These thermal detectors provide effective,intelligent property protection in a variety of applications. • SK-H EAT-W offers 135°F fixed thermal detection. • SK-HEAT-ROR-W offers 135°F fixed and rate-of-rise thermal detection. • SK-HEAT-HT-W provides fixed high-temperature detection at 190°F. FEATURES AND BENEFITS • Designed to meet UL 268 7th Edition • 360°-field viewing angle of the visual alarm • Designed for direct-surface or electrical- • Sleek and stylish contemporary design indicators(two bi-color LEDs);LEDs blink box mounting • Advanced thermal technology for fast green in Normal condition and turn on • Sealed against back pressure response steady red in Alarm • Plugs into separate base for ease of • Fixed temperature model(SK-HEAT-W) • Integral communications and built-in installation and maintenance factory preset to 135°F(57°C) device type identification • SEMS screws for wiring of the separate base • Rate-of-rise model(SK-HEAT-ROR-W), • Remote test feature from the panel • Optional remote,single-gang LED 15°F(8.3°C)per minute • Built-in functional test switch activated by accessory • High temperature model(SK-HEAT-HT-W) external magnet • Optional sounder,relay,and isolator bases factory preset to 190°F(88°C) • Walk test with address display(an address • Optional flanged surface mounting kit • Addressable by device of 121 will blink the detector LED 12- • Rotary,decimal addressing(Refer to the (pause)-1) Silent Knight panel manuals for device • Low standby current capacity) • Built-in tamper-resistant feature Honeywell • Two-wire SLC connection • LEDs blink every time the unit is polled SILENT' ®KNIGHT APPLICATIONS B200SR-LF-IV:Ivory,Low Frequency Intelligent sounder base for • Use thermal detectors for protection of property.For further retrofit applications information,refer to manual 156-6529,Applications Manual for B224RB-WH:White,plug-in System Sensors relay base System Smoke Detectors,which provides detailed information on B224RB-IV:Ivory,plug-in System Sensor relay base detector spacing,placement,zoning,wiring,and special applications. B224BI-WH:White,plug-in System Sensor isolator detector base B224BI-IV:Ivory,plug-in System Sensor isolator detector base INSTALLATION The SK-HEAT-W Series plug-in intelligent thermal detectors use a ACCESSORIES separate base to simplify installation,service,and maintenance. TR300:White,replacement flange for B210LP or B300-6 bases Installation instructions are shipped with each detector. TR300-IV:Ivory,replacement flange for B210LP or B300-6 bases Mount base(all base types)on an electrical backbox which is at RA100Z(A):Remote 3-32 VDC LED annunciator,mounts to a U.S. least 1.5"(3.81 cm)deep.For a chart of compatible junction boxes, single-gang electrical box,for use with B501 and B300-6 bases see SK-61045. only Note:Because of the inherent supervision provided bythe SLC loop, M02-04-00:Test magnet end-of-line resistors are not required.Wiring"T-taps"or branches M02-09-00:Test magnet with telescoping handle are permitted for Style 4(Class"B")wiring. Note:When using relay or sounder bases,consult the SK-ISO CK300:White,detector color kit,pack of 10 installation sheet 156-3627 for device limitations between isolator CK300-IV:Ivory,detector color kit,pack of 10 modules and isolator bases. CK300-BL:Black,detector color kit,pack of 10 PRODUCT LINE INFORMATION SK-HEAT-W:White,low-profile intelligent 135°F fixed thermal sensor SK-HEAT-ROR-W:White,low-profile intelligent rate-of-rise thermal sensor SK-HEAT-HT-W:White,low-profile intelligent 190°F fixed thermal sensor B300-6:White,standard flanged low-profile mounting base B300-6-BP:Bulk pack of B300-6,package contains 10 B300-6-IV:Ivory,standard flanged low-profile mounting base B501-WHITE:White,standard European flangeless mounting base B501-BL:Black,standard European flangeless mounting base B501-IV:Ivory,standard European flangeless mounting base B501-WHITE-BP:Bulk pack of B501-WHITE,contains 10 B200S-WH:White,Intelligent,programmable sounder base B200S-IV:Ivory,Intelligent,programmable sounder base B200SR-WH:White,Intelligent sounder base for retrofit applications B200SR-IV:Ivory,Intelligent sounder base for retrofit applications B200S-LF-WH:White,Low Frequency Intelligent,programmable sounder base B200S-LF-IV:Ivory,Low Frequency Intelligent,programmable sounder base B200SR-LF-WH:White,Low Frequency Intelligent sounder base for retrofit applications Page 2 of 3—351637:B•7/1/2019 SK-HEAT-W SERIES TECHNICAL SPECIFICATIONS PHYSICAL/ENVIRONMENTAL AGENCY LISTINGS AND Size:2.0'(5.3 cm)high;base determines APPROVALS Silent Knight and System Sensor' diameter These listings and approvals apply to the are registered trademarks of moduless ecified in this document.ln some Honeywell International,Inc. -8300-6:6.1"(15.6 cm)diameter p -B501:4"(10.2 cm)diameter cases,certain modules or applications may This document is not intended to be not be listed by certain approval agencies,or used for installation We For a complete list of detector bases,see listing may be in process.Consult factory for purposes. SK-61045. try to keep our product information latest listing status. up-to-date and accurate.We cannot Operating temperature range:SK HEAT W, • UL Listed:S6228 cover all specific applications or SK HEAT ROR W: 4°Fto 100°F • FM Approved anticipate all requirements.All ( 20°Cto 38°C) • CSFM:7270-0559:0511 specifications are subject to change SK-HEAT-HT-W:-4°F to 150°F(-20°C to without notice. 66°C) Country of origin:Mexico Detector spacing:UL approved for 50 ft. (15.24 m)center to center;FM approved for 25 x 25 ft.(7.62 x 7.62 m)spacing Relative humidity:10%—93%non- condensing Thermal ratings:Fixed-temperature set point 135°F(57°C),rate-of-rise detection 15°F(8.3°C)per minute,high temperature heat 190°F(88°C) ELECTRICAL SPECIFICATIONS Voltage range:15-32 volts DC peak Standby current(max.avg.):200uA @ 24 VDC(one communication every 5 seconds with LED enabled) LED current(max.):4.5mA @ 24 VDC("ON") Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472-1610 203.484.7161 351637 I B 1 07/19 SILENT www.silentknight.com 02019 Honeywell International Inc. ®KNIGHT Honeywell ®SILENT' KNIGHT SK-DUCT Intelligent Air Duct Smoke Detector The SK-DUCT Intelligent air duct smoke detector is used with SK-PHOTOR (included)for detecting smoke and products of combustion present in air moving through an HVAC air handling system.When smoke is detected in a duct,the unit communicates the condition to the Honeywell Silent Knight control panel.The panel,in turn,depending on programming and wiring, turns off fans,blowers,and other devices.The duct housing allows for mounting of SK-RELAY addressable relay module. The Model SK-DUCT Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke.It provides early detection of smoke and products of combustion present in air moving through HVAC ducts in "s°` °`' °' SK-DUCT Commercial and Industrial applications. The SK-DUCT is in a heavy duty gray steel back box with a clear cover.It features a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct.It installs quickly and easily. The unit senses smoke in the most challenging conditions,operating in airflow speeds of 100 to 4000 feet per minute,temperatures of-4°F to 158°F,and a humidity range of 0 to 95 percent(non-condensing). FEATURES & BENEFITS • Versatile mounting • Rugged steel back box • Patented sampling options:square or with clear plastic cover tube installs from rectangular Easy to clean front or back of the •configuration detector with no tools • Large terminal required • New Cover tamper connection screws signal • Available space within • Transparent cover for housing to • LED alarm indication convenient visual accommodate and communication inspection mounting of relay on sensor head module • Detects and limits the • UL listed spread of smoke • SK-DUCT Technical. Specifications Fora complete listing of all PHYSICAL IMPORTANT NOTES: compliance approvals and (Rectangular):14.38"(37 cm)L X 5"(12.7 cm)W X •The use of either RTS151 or RTS151KEY certifications,please visit www.silentknight.com. 2.5"(6.6 cm)D requires the installation of an accessory coil, (Square):7.75"(19.7cm)L x 9"(22.9cm)W x 2.5"D DCOIL,sold separately.Please refer to the Microsoft,Windows,and (6.35cm) SK-DUCT installation instructions for more the Windows Logo are registered trademarks Weight:l.6lb(0.73kg) information or trademarks of •The RTS151/RTS151KEY test coil circuit Microsoft Corporation. ELECTRICAL(using SK-Photo or SK-PhotoR) requires an external 24VDC power supply which Operating Voltage:15-32 VDC must be UL listed. Silent Knight,System Sensor'and Honeywell' Standby Current:300 µA @ 24 VDC max. ACCESSORY CURRENT LOADS AT 24VDC are registered Alarm Current:6.5 mA @ 24 VDC max(with LED Device Standby Alarm trademarks of Honeywell on) International,Inc. RA100Z OmA 12mA Max. This document is not ENVIRONMENTAL RTS151 OmA 12mA Max intended to be used for Operating Temperature:-4°F-158°F(-20°C- installation purposes.We 70°C) RTS151KEY 12mA 12mA Max tryto keep our product Humidity:0%-95%(non-condensing) information up-to date and accurate.We COMPATIBILITY cannot cover all specific AIR VELOCITY The SK-DUCT is compatible with the following applications or anticipate 100 to 4000 ft/min: (0.5-20.3 m/sec.) Honeywell Silent Knight fire alarm control panels: all requirements.All 6820:Addressable fire alarm control panel specifications are subject ORDERING INFORMATION to change without notice. 6820EVS:Addressable fire alarm control panel SK-DUCT: Intelligent non-relay duct smoke with an emergency mass notification system. For Technical Support, detector 6808:Addressable fire alarm control panel call 446 6444. SK-PHOTO: Addressable Photo Detector 6700:Addressable fire alarm control panel SK-PHOTOR: Addressable Photo Detector with 5700:Addressable fire alarm control panel remote test capability(included with SK-Duct) SK-RELAY: Addressable Relay Module,must be 5808:Addressable fire alarm control panel added if relay function is required,(fits in housing) 5820XL:Addressable fire alarm control panel 5820XL-EVS:Addressable fire alarm control panel ACCESSORIES with an emergency mass notification system. DST1: Metal Sampling Tube Duct Width up to 1' DST1.5: Metal Sampling Tube Duct Widths 1'-2' DST3:Metal Sampling Tube Duct Widths 2'-4' DST5: Metal Sampling Tube Duct Widths 4'-8' DST10: Metal Sampling Tube Duct Widths 8'-12' DH4000E-1: Weatherproof Enclosure ETX: Metal Exhaust Tube Duct width 1' RA100Z: Remote LED Annunciator DCOIL: Duct accessory coil,required if using with SK-PHOTO and not SK-PHOTOR(included)with SK-DUCT RTS151: Magnetic Remote Test station RTS151KEY: Key-Activated Remote Test station M02-04-00 Test Magnet P48-21-00 Replacement End Cap for Metal Sampling Tube APA151:Remote annunciator with piezo alarm For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Hon eywe Set Kdight Honeywell 12 Clintonville Road Northford,CT 06472 Doc 3501221 Rev F 111/17 800-328-0103 ©2017 Honeywell International Inc. ®SILENT KNIGHT Honeywell ®KNIGHT SK-PULL-SA / SK-PU LL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to FIRE activate the station.The SK-PULL-DA is a dual action pull station requiring y two motions to active the station.The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel(FACP). LIF PULL DOWN Extremely easy to operate,the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal.The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. Honeywell �- INSTALLATION The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O SK-PULL-SA surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13"(5.40 cm)or double gang or 4"(10.61 cm)square electrical box.You can also use the optional(System Sensor®PN BG-TR) trim ring if the station is being semi-flush mounted. FIRE PUSH IN I PULL DOWN Honeywell - i• SK-PULL-DA FEATURES & BENEFITS • Installer can open • Key operated test and • Meets the Americans • Reliable analog • Handle latches in station without reset lock using lock with Disabilities Act communications for down position and the causing an alarm plate actuator Accessibility trouble-free operation word Activated condition Guidelines(ADAAG) appears,clearly • Key matches • Braille text on station • Dual-color LED is compatible FACP controls and operating handle indicating the station visible through handle locks mechanisms has been pulled guidelines(Section • Rotary address of station blinks green •• Meets ADA 4.1.3[13]) switches for fast UL Listed,including to indicate normal UL 38,Standard of requirement for 5 lbs installation operation and remains maximum pull force to • Shell,door,and handle Manually Actuated steady red in an alarm active molded from durable Signaling System condition LEXAN' • CSFM Listed • MEA Listed * • SK-PULL-SA / SK-PULL-DA Technical Specifications For a complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:5.5"H x 4"W x 1.45"D(14 x 10.2 x SK-Pull-SA:Single Action Pull Station 3.7cm) Microsoft,Windows,and SK-Putt-DA:Dual Action Pull Station the Windows Logo are Housing Material:LEXAN polycarbonate resin registered trademarks Bi-Colored LED: ACCESSORIES or trademarks of Blinking Green:Normal BG-TR:Optional trim ring. Microsoft Corporation. Steady Red:Alarm SB-I/O:Surface backbox,indoor/outdoor. Silent Knight,System Switch:Single pole,single throw(SPST)normally *Unless otherwise noted,specifications apply to Sensory and Honeywell' open(N/O)switch which closes upon activation of SK-Pull-SA and SK-Pull-DA are registered the pull station trademarks of Honeywell COMPATIBILITY International,Inc. ELECTRICAL The SK-PULL-SA AND SK-PULL-DA are This document is not Operating Voltage:15—32VDC compatible with the following Honeywell Silent intended to be used for SLC Standby and Alarm Current:350µA Knight fire alarm control panels: installation purposes.We 6820:Addressable fire alarm control panel try to keep our product Wire Gauge:Up to 12AWG(3.1 mm2) p information up-to 682OEVS:Addressable fire alarm control panel date and accurate.We ENVIRONMENTAL with an emergency voice system. cannot cover all specific Operating Temperature:32°F—120°F(0°C— 6808:Addressable fire alarm control panel applications or anticipate 49°C) 6700:Addressable fire alarm control panel all requirements.All specifications are subject Humidity:10%—93%non-condensing 5700:Addressable fire alarm control panel to change without notice. 5808:Addressable fire alarm control panel For Technical Support, 5820XL:Addressable fire alarm control panel cati800-446-6444. 582OXL-EVS:Addressable fire alarm control panel with an emergency voice system For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501351 Rev E 111/17 ®SILENT' 800-328-0103 ©2017 Honeywell International Inc. KNIGHT *Th, SYSTEM SENSOR' Indoor Selectable- pry Output Speaker ,, Strobes and Dual - .44.. Voltage Evacuation Speakers for Ceiling Applications . 117 iir.;000) System Sensor L-Series selectable-output speaker strobes 11110 and dual-voltage evacuation speakers can reduce ground / ► faults and enable faster installation with lower current draw and modern aesthetics. System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates, • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers.In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on ceiling units: feedback to ensure that wiring is properly connected,rotary switches 15,30,75,95, 115, 150,and 177 to select voltage and power settings,and 7 field-selectable candela settings for both wall and ceiling speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the SP speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage(25 sound output while still offering high volume sound output for use in and 70.7 Vrms)and power settings(1/4,1/2, 1 and 2 watts) high ambient noise applications. • Speakers offer high fidelity and high volume sound output L-Series makes installation easy • 520 Hz+/-10%square wave tone capable with compatible FACP •Attach a universal mounting plate to a 4 x 4 x 21/e inch back box. • Compatible with System Sensor synchronization protocol Flush-mount applications do not require an extension ring. • Electrical compatibility with existing SpectrAlert and SpectrAlert •Connect the notification appliance circuit or speaker wiring to the Advance products terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Tamper-resistant construction inserting the product tabs into the mounting plate grooves.Hinge • Updated modern aesthetics the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. SIGNALING 3-- APPROVED I- I LISTED S4048 FM approved except 7320-1653.0505 for ALERT models 3057493 AVDS866-03.03/23/2018•Page 1 • L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150, 177. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms.It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 411/16 x 21/e-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in,25 mm With Surface Mount Back Box 6.9 in, 176 mm 3.5 in,89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in,73 mm With Surface Mount Back Box 6.9 in, 176 mm 5.37 in, 136 mm *When using 12AWG, 14 AWG,or adding extra wires in the box,a deeper box or extension ring is recommended. Electrical/Operating Specifications Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 VDC/FWR 1,2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz3 Power IA,1/2, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd. 3.520 Hz+/-10%square wave tone capable with compatible FACP. AVDS866-03.03/23/2018•Page 2 - UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) 8 to 17.5 Volts 16 to 33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Ceiling-Mount Speaker Sound Output Setting UL Reverberant(dBA @10 ft) UL Anechoic(dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Ceiling-Mount Speaker Strobe Sound Output Setting UL Reverberant(dBA @10 ft) UL Anechoic(dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 L-Series Dimensions 1.0" 1.63" 6.8"die. (25.4 mm) (41.66mm) (173 mm) t i __ 17_ ///i \. \.\ I'Ir •III Ili-1 111 111 11-. I7II7111l' i ':I�IIf1.' i��� 11rA11111 17.I 1\-"1 1�11/Il/ A0543-00 Ceiling Speaker 2.87" 1.63. 6.8"dia. -� (726 mm) I y (41.66 mm) (173mm) 1.76" J- (44.7 mm) 4 y nor � ci1i4�•i if•+ .. ..m w * \ 0 li\•1` �r(..:111.711,!,,ir.,i I,l•, , ,..,„\ ia,0: SA4 11 ,11 „„/..„,„ ...,,N.„.„?....,„, _,, l� -i y_,..i A0544-00 Ceiling Speaker Strobe AVDS866-03.03(23/2018•Page 3 - Surface Mounting 1 ��� 1s 4:>"5" J . I'V" . .lt iil- --....— „,,,,..;‘;:::::.,:,,, T8 0 81"-;„‘Immikiin d , „„„ . . .„ . k„ ,A, , v,,,,,,• , l�, f • q l I/.� ' ..H O 'Ipa*. pp A0504-01 pf.. •� A0520-01 Ceiling Speaker with Surface Mount Back Box Ceiling Speaker Strobe with Surface Mount Back Box t0oo � le" o \ ''''r 61' '':i4'i;:"Illti.:11:::::".------1 .----47---:----':..,., ,.47 P:1,(111:t:111'1',,,,I.,,..71,7/1*-1,.-4,::.,,,::c.."7,,,,.,,,•., ...,,,,,,.,,..,,,,;.:"..,...,., A0542-00 s.r Ceiling Speaker Strobe with Trim Ring and 4"Square Electrical Box `L-Series Ordering Information Ceding Mount White Red Description SPCWL SPCRL Speaker only SPSCWL SPSCRL Speaker Strobe SPSCWL-P — Plain,Speaker Strobe SPSCWL-SP — Fuego,Speaker Strobe SPSCWL-CLR-ALERT — Alert,Speaker Strobe,Clear Lens Accessories White Red Description SBBCWL SBBCRL Universal Ceiling Surface Mount Back Box TRC-2W TRC-2 Universal Ceiling Trim Ring *� SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 02018 System Sensor. Phone:800-SENSOR2•Fax:630-377-6495 Product specificatons subject to change without notice.Veit systemsensor.com SENSOR for current product information,Including the latest version of this data sheet. www.systemsensor.com AVDS866-03.03/23/2018 *Th, SYSTEM SENSOR Indoor Selectable- Output Speaker Strobes and Dual Voltage Evacuation „� ' Speakers for Wall Applications The SpectrAlert°Advance selectable output speaker strobes and dual-voltage evacuation speakers can reduce SPECTiwert ground faults and enable faster installation. __ o v .a► ilu c E Features The SpectrAlert Advance Series of speakers and speaker • Plug-in design and protective cover reduce ground faults strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting • Universal mounting plate with an onboard shorting spring tests plates,dress the wires,and confirm wiring continuity before plugging wiring continuity before installation in the speakers. In addition,a protective plastic cover prevents • No extension ring required nicked wires by covering exposed speaker components. • Field selectable candela settings: Standard: 15, 15/75,30,75,95, 110, 115 These devices also enable faster installations by providing instant High: 135, 150, 177,185 feedback to ensure that wiring is properly connected,rotary switches to select voltage and power settings,and 11 field-selectable candela • Automatic selection of 12-or 24-volt operation at 15 settings for both wall and ceiling speaker strobes. and 15/75 candela • Rotary switch simplifies field selection of speaker voltage The low total harmonic distortion of the SP speaker offers high fidelity (25 and 70.7 Vrms)and power settings(1/4,Y, 1 and 2 watts) sound output while the SPV speaker offers high volume sound output • SP speakers offer high fidelity sound output for use in high ambient noise applications. • SPV speakers offer high volume sound output SpectrAlert Advance makes installation easy • Compatible with System Sensor synchronization protocol •Attach a universal mounting plate to a 4 x 4 x 21i8 inch back box. • Electrical compatibility with existing SpectrAlert products Flush-mount applications do not require an extension ring. •Connect the notification appliance circuit or speaker wiring to the • Tamper-resistant construction terminals on the mounting plate. • Listed for ceiling or wall mounting •Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves.Hinge the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. Agency Listings SIGNALING CIS,Eo ( ) aMEA S4048 7320-1653,201 10-08-E .1.1111111111110 SpectrAlert Advance Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also, SpectrAlert Advance speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified, unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110,115, 135, 150, 177, 185. Speaker The speaker shall be a System Sensor SpectrAlert Advance model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms.It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor SpectrAlert Advance model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 41 V16 x 41 V16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non- condensing Dimensions,Wall-Mount Length Width Depth SP Speaker 6 in, 152 mm 5 in, 127 mm 2.8 in,71 mm SPV Speaker 6 in, 152 mm 5 in,127 mm 2.9 in,74 mm With Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 3.4 in,86 mm SPS Speaker/Strobe 6 in, 152 mm 5.1 in, 127 mm 4.7 in, 119 mm (including lens and speaker) With Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 5.325 in, 135 mm Electrical/Operating Specifications Nominal Voltage(speakers) 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC/ FWR or regulated 24 DC/FWR Operating Voltage Range(includes fire 8 to 17.5 V(12 V alarm panels with built in sync) nominal)or 16 to 33V (24 V nominal) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33V(24 V nominal) Frequency Range 400 to 4000 Hz Power 1, 1,2 watts UL Current Draw Data - UL Max.Strobe Current Draw(mA RMS) 8 to 17.5 Volts 16 to 33 Volts Candela DC FWR DC FWR Standard 15 123 128 66 71 Candela Range 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 Sound Output UL Reverberant(dBA @ 10 ft.) 2W 1W '/s W '/4 W Wall-Mount SP Series 86 83 80 77 Wall-Mount SPV Series 90 87 84 81 Wall-Mount SPS Series 85 82 79 76 Wall-Mount SPSV Series 89 86 83 80 Dimensions 5.00" .97---1.84=- 5.00" 2.83"" 1.604H.84= IFIJIlI i&: 1 "::::: 111.11 •11, ,,,-�- o� -► , Wall-Mount SP Speaker Wall-Mount SPS Speaker Strobe • Surface Mounting —� I ,r1. I. ® "eE. r IN •''.--- „„„......., a--' ing . „ .....m ..-..:.--.: 0 111 , ., LI% , -- .. IE.__ ID ........ ,‘, . . _______. 11111=t— 0 .c 0.. ��- „I, ". I` �t;_if,is Ill 41 �1,., 7. i�( ��Am,4.:.8 — -........r..--,' __- Wall-Mount Speaker Strobe with SBBSPR Surface Mount Back 1 Ordering Infor, ation for SpectrAlert®Advance Speakers and Speaker Strobes Wall Mount White Red Description SPW SPR Speaker only SPWV SPRV Speaker only,High dB SPSW SPSR Speaker Strobe,Standard cd SPSW-P SPSR-P Plain Speaker Strobe,Standard cd SPSW-ALERT — Speaker Strobe,Standard cd,Amber Lens SPSW-CLR-ALERT — Speaker Strobe,Standard cd,Clear Lens SPSWH SPSRH Speaker Strobe,High cd SPSWH-P — Plain Speaker Strobe,High cd SPSWV SPSRV Speaker Strobe,Standard cd,High dB SPSWV-P SPSRV-P Plain Speaker Strobe,Standard cd,High dB Accessories White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPW SBBSPR Surface Mount Back Box for Speakers and Speaker Strobes TRW TR Wall Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on the cover) "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135,150,177,and 185 candela settings. *T SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 02015 System Sensor. �� SEwSORe Phone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to change without notice.Visitsystemsensor.com for current product information,including the latest version of this data sheet. www.systemsensor.com AVDS11602.2/15 * SYSTEM $ SENSOR Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications lications ay System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. ' Features The System Sensor L-Series offers the most versatile and • Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry with lower current draws and modern aesthetics.With white and red • Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor • Automatic selection of 12-or 24-volt operation L-Series can meet virtually any application requirement. at 15 and 30 candela The entire L-Series product line of ceiling-mount strobes and horn • Field-selectable candela settings on ceiling units: 15,30,75,95, 115, 150,and 177 strobes include a variety of features that increase their application versatility while simplifying installation.All devices feature a plug-in • Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations • Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time- • Universal mounting plate for ceiling units consuming ground faults. • Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal before device installation mounting plate so installers can mount them to a wide array of back • Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring,installers can test wiring Advance devices continuity before the device is installed. • Compatible with MDL3 sync module Installers can also easily adapt devices to a suit a wide range of • Listed for ceiling mounting only application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with two volume selections. Agency Listings SIGNALING 11> (b) LISTED APPROVED r I S5512 FM approved except 7125-1653.0504 S4011 for ALERT models 7135-1653.0503 3057383 AVDS868-02•12/01/2017•Page 3 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double- gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150,and 177. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9"diameter x 3.4"high(175 mm diameter x 86 mm high) (SBBCRL,SBBCWL) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS868-02.12/01/2017•Page 2 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 87 41 60 Temporal High 39 44 54 Range 30 153 63 86 Temporal Low 28 32 54 75 N/A 111 142 Non-Temporal High 43 47 54 95 N/A 134 164 Non-Temporal Low 29 32 54 115 N/A 158 191 3.1 KHz Temporal High 39 41 54 150 N/A 189 228 3.1 KHz Temporal Low 29 32 54 177 N/A 226 264 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 ` UL Max.Current Draw(mA RMS),Ceiling Horn Strobe,Candela Range(15-177 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 T 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data Horn Strobe Output(dBA) 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 AVDS868-02•12/01/2017•Page 3 • L-Series Dimensions 2.47 (62.7 mm) 1.37 (34.8 mm) 6.92"diam. 2.5„ 6.83'diam. (173 mm) (175.77 mm) (64 mm)1 oNOT Meta rr I.n) II r 8 0 o\, �_ 1 1 C 0 8 og ../ A0545-00 A0546-00 Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box _ 11 `e� ���� �� ® ' i"hi' ce-- No , tv i ticlast ',„c, ) 3 C) 1 1.0-f--, ,,--i.1.-,411-1--p, ® ni , i e;_____60-0 , 71 I s ��71.a� �,07 84\— 8_. , lo „., g �1c • tlmoi A0494-01 A0531-01 2-Wire Ceiling Mount Horn Strobes 4-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box with Ceiling Surface Mount Back Box L-Series Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes PC2RL 2-Wire,Horn Strobe,Red SCRL Strobe,Red PC2WL 2-Wire,Horn Strobe,White SCWL Strobe,White PC4RL 4-Wire,Horn Strobe,Red SCWL-CLR-ALERT Strobe,White,ALERT PC4WL 4-Wire,Horn Strobe,White Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box,Red SBBCWL Ceiling Surface Mount Back Box,White For a ceiling-listed horn-only device,see AVDS865"Indoor Selectable- Output Horns,Strobes,and Horn Strobes for Wall Applications". *� SYSTEM 02017 System Sensor. �� SENSOR' 3825 Ohio Avenue•St.Charles, IL 60174 Product specificationssubiecttochangewithoutnotice.Visitsthisdaensor.com Phone:800-SENSOR2•Fax:630-377-6495 for current product information.Including the latest version of this data sheet. AVDS868-02.12/01/2017 • *Th, SYSTEM 1111 �,.. SENSOR' F F R Indoor Selectable- E E Output Horns, Strobes, and F f \ � Horn Strobes for 11 Wall Applications E -# - SpectrAlertx Advance audible visible notification products SPECTR9gert are rich with features guaranteed to cut installation times a IIN c and maximize profits. Features The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance • Automatic selection of 12-or 24-volt operation at can meet virtually any application requirement. 15 and 15/75 candela Like the entire SpectrAlert Advance product line,wall-mount horns, • Field-selectable candela settings on wall units: 15, 15/75, 30,75,95, 110, 115,135, 150, 177,and 185 strobes,and horn strobes include a variety of features that increase their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating • Universal mounting plate for wall units costly and time-consuming ground faults. • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage,SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring continuity before the device is installed. • Compatible with MDL3 sync module • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings SIGNALING r ` 412) ® MEA LISTED APVROVED approved �126 1653,186(horn strobes) 54011(chimes,horn strobes,horns) 3023572 MEA452-05-E chime strobes) $5512(stobes) 7135-1653�169(horns,chimes) SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuif°Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15,15/75,30,75,95, 110, 115, 135, 150,177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS) 5.7"L x 4.8"W x 0.35"D(145 mm L x 122 mm W x 9 mm D) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 86 96 96 3 Temporal Low 71 71 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 73 74 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 74 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobes. SpectrAlert Advance Dimensions 4.7" 2.5=---► .lei MT ip ■ ® ,. MA5.6" 1.1 Wall-mount horn strobes SpectrAlert Advance Ordering Information Model Description Model Description Wall Horn Strobes Wall Strobes(cont.) P2R 2-Wire Horn Strobe,Standard cd,Red SRH Strobe,High cd,Red P2R-P 2-Wire Horn Strobe,Standard cd.Red,Plain SRH-P Strobe,High cd,Red,Plain P2R-SP 2-Wire Horn Strobe,Standard cd,Red,"FUEGO" SRH-SP Strobe,High cd,Red,"FUEGO" P2RH 2-Wire Horn Strobe,High cd,Red SW Strobe,Standard cd,White P2RH-P 2-Wire Horn Strobe,High cd,Red,Plain SW-P Strobe,Standard cd,White,Plain P2W 2-Wire Horn Strobe,Standard cd,White SWH Strobe,High cd,White P2W-P 2-Wire Horn Strobe,Standard cd,White,Plain SWH-P Strobe,High cd,White,Plain P2WH 2-Wire Horn Strobe,High cd,White Horns P2WH-P 2-Wire Horn Strobe,High cd,White,Plain HR Horn,Red P4R 4-Wire Horn Strobe,Standard cd,Red HW Horn,White P4R-P 4-Wire Horn Strobe,Standard cd,Red,Plain Accessories P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red P4W 4-Wire Horn Strobe,Standard cd,White SBBR Indoor Surface Mount Back Box,Red Wall Strobes SBBW Indoor Surface Mount Back Box,White SR Strobe,Standard cd,Red SR-P Strobe,Standard cd,Red,Plain SR-SP Strobe,Standard cd,Red,"FUEGO" Notes: All-P models have a plain housing(no"FIRE"marking on cover) All-SP models have"FUEGO"marking on cover "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135,150,177,and 185 candela settings. �� SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 e2014 System Sensor. �� SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 Product entpricatio intormecttochangewithoutnotice.Visitsystemsensoccom t for current product information,including the latest version of this data sheet. www.systemsensor.com AVD510201.1/14 Ac OX SRD System Record Documents BY SPACE AGE ELECTRONICS Store important system documents in a secure location with a cabinet built specifically to meet the SYSTEM RECORD requirements of NFPA 72 7.7.2.4. DOCUMENTS The number one goal at Space Age is to manufacture code 4, � : ry compliant solutions, and the SRD is just that. NFPA 72 7.7.2.1 states, "With every new system, a documentation cabinet shall be installed at the system control unit or other approved location at the protected premises." s The SRD includes our innovative 8GB flash drive slide tab that allows the user to select a USB-C or Micro USB connector to access records electronically(See NFPA 72 7.5.6.7). %%40 FEATURES Mp0E1Ntsp 18 gauge stainless steel SPECIFICATIONS SINCE construction with red powder coat and white The SRD System Record Documents Box shall be UL Listed, lettering constructed of 18 gauge cold rolled steel. It shall have a * powder coat finish.The cover shall be permanently screed with Dimensions are 12"wide x 1" high lettering "SYSTEM RECORD DOCUMENTS" with white 13" tall and 2 1/4" deep indelible ink.The access door shall be locked with a 3/4" barrel LISTED • Stainless steel piano hinge lock and there will be a 12" stainless steel piano hinge.The SRD Two key ring hooks to hold C will have a minimum of 8 gigabyte digital flash memory drive A' system keys with a slide tab that allows user to select USB-C or Micro USB F� connector for uploading and downloading information.The • Business card holder for key enclosure will supply 4 mounting holes. Inside will contacts accommodate standard 8 1/2" x 11" manuals and document • Slide tab allows user to records. A legend sheet will be attached to the door for system select USB-C or Micro USB required documentation, key contacts and system information. connector to download The enclosure shall also provide 2 key ring holders with a from 8GB digital flash location to mount standard business cards for key contact memory personnel. CUSTOM COLORS AND BRANDING AVAILABLE Pg. 1/2 • AeiOX DIMENSIONS 2.35 --- -12.00------ - .75 10.25 6..' 1.63 11i 1 J � �� ,► I l RECORD 9.75 13.00 12.59 13.16 1.63 ` } 0.2 `11.75- ORDERING INFORMATION P/N#SSU00689 System Record Documents Cabinet- Red P/N#SS000690 System Record Documents Cabinet- Red with your custom screened logo PIN#SSU01689 System Record Documents Cabinet- Black P/N#SSU01690 System Record Documents Cabinet- Black with your custom screened logo www.1 sae.com toll free 1.800.486.1723 I fax 508.485.4740 ©Copyright 2018 Space Age Electronics,Inc. This document to change without notice LT10641 Rev.B ""' MINA �� " P g I subjectg I I N O Pg.2/2 , W E'0WES?5' ic '" - y H I l [ t . 1 Cl. ,A) ,i4Vi"c2ftii, itte , s aed ieca,Sf ------"" 4tfrW e a3lttP<Y' pt n Q Wm al Inmrgenry lailiafll li § + DE .ate&ren ` '' 0 Pugmse Lighting Aci.mdr aw+w L PS-e2yoF1 MOP- <n..mv.H, v , 75, Nu .eve tj 1 -r.eo-a°+° FEATURES PS-i 21 0 12V 7.0 AH @ 20-hr. • Absorbent Glass Mat(AGM)technology for 12V 6.5 AH @ 10-hr. superior performance Rechargeable Sealed Lead Acid Battery • Valve regulated,maintenance free spill proof construction PS - General Purpose Series • Power/volume ratio yielding excellent energy density TERMINALS:(mm) • Rugged vibration and impact resistant ABS case and cover Ft: Quick disconnect tabs, F2: Quick disconnect tabs, 0.187"x 0.032"-Mate with 0.250"x 0.032"-Mate with • Gas recombination technology AMP.INC.FASTON"187"series AMP.INC FASTON"250"series • 5 year design life -+I I4-2.5 -2.5 tins, OR . APPROVALS sz I. -I • Approved for transport by air. D.O.T.,I.A.T.A.,F.A.A. s.as-►I + 3.4 14- and C.A.B.certified-- a . 7.95-► i • �°' ti�.o...�.������� r..��.9 '0�0 • U.L.recognized Torque Not Applicable Torque-Not Applicable • IS09001:2015-Quality management systems DIMENSIONS:inch(mm) PERFORMANCE SPECIFICATIONS T L: 5.95(151) Nominal Voltage 12 volts(6 cells) W: 2.56(65) - e H: 3.70(94) Nominal Capacity W HT:3.86(98) 20-hr. (350mA to 10.50 volts) 7.00 AH - ® Tolerances are+/•0.04 in. 10-hr. (650mA to 10.50 volts) 6.50 AH 1I (+/- mm)and0.0E in. 2 (+/- mm)forrheight 5-hr. (1.2A to 10.20 volts) 6.00 AH dimensions.All data subject 1-hr. (4.5A to 9.00 volts) 4.50 AH to change without notice. Approximate Weight 4.80 lbs.(2.18 kg) 11 , I l I I 1 1 I Internal Resistance(approx.) 23.0 milliohms aealet errpeehN s a° Max Short-Duration Discharge Current(10 Sec.) 70.0 amperes POWER_ SOMC MODEL P5-1270 F1 ° OZWr HT H 12 Volt 1.0Amp Hr . Shelf Life(%of nominal capacity at 68°F(20°C) a _ 1 Month 97% ° 911 3 Month 91% ntnt....«......=,...°.-...... -.-. -- 6 Month 83% I.' L '1 Operating Temperature Range Charge 5°F(-15°C)to 122°F(50°C) Discharge -4°F(-20°C)to 140°F(60°C) CORPORATE HEADQUARTERS POWER-SONIC EUROPE LIMITED Case ABS Plastic (USA AND INTERNATIONAL EXCLUDING EMEA) (EMEA-EUROPE,MIDDLE EAST AND AFRICA) Power-Sonic Corporation 3 Buckingham Square, Power Sonic Chargers PSC-12800A-C 7550 Panasonic Way,San Diego, Hurricane Way,Wickford, PSC-121000-PC California 92154 Essex SS11 8YQ T: +1(619)661 2020 T: +44(0)1268 560686 F: +1(619)661 3650 F: +44(0)1268 560902 E: customer-service@power-sonic.com E: salesEMEA@power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Manual,as published on our website. 0 2018.Power-Sonic Corporation.All rights reserved.All trademarks are the property of their respective owners. O,YY A, C O n Icet O All data subject to change w0hout notice.E&0.E N J '1 y W POWER�7 SON/C W H . I I IU,I LLr „,, I LW," SOW f IONS 1 . PS-1270 12Y65AH@10-hr. Rechargeable Sealed Lead Acid Battery PS - General Purpose Series SHELF LIFE&STORAGE LIFE CHARACTERISTICS IN STAND-BY USE 1 100 Charging isnot Ambient Temperature 20°C(68°F) a4 _ necessary unless 100 - 100%of capacity O is required. 80 1 80 cc 5°C Charging before c _ use is necessary 60 41°F to he recover I O ( ) P full capacity. Float Charging Voltage c 60 40 -, 2.25-2.30V/Cell >, 40°C 30°C 20°C 20 's 40 (104°F)—(86°F) (68°F) 0 I I I 0 1 2 3 4 5 co v 0 Years 0 2 4 6 8 10 12 14 16 18 20 Standing Period(Months) CHARGING CHARGERS Cycle Applications:Apply constant voltage charge at Power Sonic offers a wide range of chargers suitable 2.35v/c—2.45v/c(14.1 —14.7v for 12v Monobloc)at 20°C. for batteries with a variety of capacities. Initial charging current should be set at less than 0.25C Please refer to our website for more information on Amps.Switch to float charge to avoid overcharging. our switch mode and transformer type chargers. "Float"or"Stand-By"Service:Apply constant voltage Please contact our technical department for advice if charge of 2.25v/c—2.30v/c(13.5 to 13.8 volts for 12v you have difficulty in locating a suitable charger. Monobloc at 20°C.When held at this voltage,the battery will seek its own current level and maintain itself in a fully charged condition. FURTHER INFORMATION Temperature Compensation:Charging Voltage for both Please refer to our website www.power-sonic.com Cyclic and Standby applications should be regulated in for a complete range of useful downloads,such as relation to ambient temperature.As temperature rises product catalogs,material safety data sheets(MSDS), charging voltage should be reduced to prevent overcharge ISO certification,etc. and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors,see Power Sonic Technical Manual/ «rr" ,,k, A t r,,,..' ` Power Sonic Charger specifications. APPLICATIONS • General purpose • Medical --,( 8.atr°" • Emergency lighting • Fire and security toi/ER Jam'aN MopEL Ps a a7a r+ r"d: yr CORPORATE HEADQUARTERS POWER-SONIC EUROPE LIMITED (USA AND INTERNATIONAL EXCLUDING EMEA) (EMEA-EUROPE,MIDDLE EAST AND AFRICA) - ' Power-Sonic Corporation 3 Buckingham Square, 7550 Panasonic Way,San Diego, Hurricane Way,Wickford, California 92154 Essex SS11 8YQ T: +1(619)661 2020 T: +44(0)1268 560686 F: +1(619)661 3650 F: +44(0)1268 560902 E: customer-service@power-sonic.com E: salesEMEA@power-sonic.com To ensure safe end efficient operation always refer to the latest edition of our Technical Manuel,as published on our website. „ �+ „ ®2018.PowerSonic Corporation.All rights reserved.All trademarks are the property of their respective owners. O W r $O 1 1 I C.C O 1 1�y�1 All data subject to change without notice.E&O.E w mot. Col W r 1:)1WRV7 SON CC y y 1 RUSTED BATTERY SOLUTIONS PS-1 27O 12V65AN@ 0-hr. Rechargeable Sealed Lead Acid Battery PS - General Purpose Series SHELF LIFE&STORAGE LIFE CHARACTERISTICS IN STAND-BY USE 100 Charging isnot Ambient Temperature 20°C(68°F) 8P necessary unless 100 h; 100%ofcapacity o , , is required. °ri 80 80 cc 5°C 1- Charging before C '' use Is necessary 60 o C (41°F)— to help recover °. ` full capacity. Float Charging Voltage c 60 40 a, 2.25-2.30 V/Cell ce _ 20 40°C 30°C 20°C Zi 0r CI (10 i°F)—(86°F) (6 i F) 0 A 0 1 2 3 4 5 0 2 4 6 8 10 12 14 16 18 20 Years Standing Period(Months) RECEIVED CHARGING CHARGERS MAY 6 2020 Cycle Applications:Apply constant voltage charge at Power Sonic offers a wide range of chargers suitable 2.35v/c—2.45v/c(14.1 —14.7v for 12v Monobloc)at 20°C. for batteries with a variety of capacities. CIIIIITY� (O F TIGARD Initial charging current should be set at less than 0.25C please refer to our website for more inf�rti9ti�l bP DIVISION Amps.Switch to float charge to avoid overcharging. our switch mode and transformer type chargers. "Float"or"Stand-By"Service:Apply constant voltage Please contact our technical department for advice if charge of 2.25v/c—2.30v/c(13.5 to 13.8 volts for 12v Monobloc at 20°C.When held at this voltage,the battery you have difficulty in locating a suitable charger. will seek its own current level and maintain itself in a fully charged condition. FURTHER INFORMATION Temperature Compensation:Charging Voltage for both Please refer to our website www.power-sonic.com Cyclic and Standby applications should be regulated in for a complete range of useful downloads,such as relation to ambient temperature.As temperature rises product catalogs,material safety data sheets(MSDS), charging voltage should be reduced to prevent overcharge ISO certification,etc. and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors,see Power Sonic Technical Manual/ Power Sonic Charger specifications. APPLICATIONS 3 • General purpose • Medical 1 f•'„ • Emergency lighting • Fire and security, , ,+ �- -'r '' ""` ',: a.earrw+a CORPORATE HEADQUARTERS POWER-SONIC EUROPE LIMITED ,u (USA AND INTERNATIONAL EXCLUDING EMEA) (EMEA-EUROPE,MIDDLE EAST AND AFRICA) `. _ ----- Power-Sonic Corporation 3 Buckingham Square, x' 7550 Panasonic Way,San Diego, Hurricane Way,Wickford, California 92154 Essex SS11 8YQ T: +1(619)661 2020 T: +44(0)1268 560686 F: +1(619)661 3650 F: +44(0)1268 560902 E: customer-service@power-sonic.com E: salesEMEA@power-sonic.com To ensure safe and efficient operation always refer to the latest edition of our Technical Mama',as published on our website �+ „ ®2018.Power-Sonic Corporation.All rights reserved.All trademarks are the property of their respective owners. p O W O C S O 1 1 I C.C O 1 1�y�1 All data subject to change whhout notice.E&O.E