Report f--ECZO22- cv/1S
`1FFICE COPY
Unit Report For 48FC-6T-E-3PH
Unit Parameters Dimensions(ft.in.)&Weight(lb.)"""
Unit Model. 48FCEMO7A2A5-0A0A0 Unit Length 6'2.375"
Unit Size 07(6 Tons) Unit Width 3'10.625"
Volts-Phase-Hertz. 208-3-60 Unit Height 3'5.375"
Heating Type. Gas ••• Total Operating Weight 562 lb
Duct Cfg. Vertical Supply/Vertical Return
Medium Heat "' Weights and Dimensions are approximate. Weight does
Single Circuit,Two Stage Cooling(07 only) not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Return Air Filter Type. Throwaway
Return Air Filter Quantity- 4
Return Air Filter Size 16 x 16 x 2
Unit Configuration
Direct Drive-EcoBlue-Medium Static
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
in
9
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48FCEMO7A2A5-0A0A0 Rooftop Unit 1
Base Unit
Direct Drive-EcoBlue-Medium Static
None
RECEIVED
VIUY
BUILDiiy„.
Packaged Rooftop Builder 1.49n Page 1 of 7
Certified Drawing for 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
THIS DOCUMENT IS TXE PROPERTY OF UTC CLIIMTE.CONTROES SUNNI59Idl DF THfsf ORAYTN65 OR DOEDM[NTS
NOTES: Gill{Ef 3 SECURITY AND f3 OELIYEMEO UPON TXE CAREERS COEDETEAS NOES MDT CCESTITUTE PART TRACT.WIUCE OR
UNIT J R THAT THE CONTENTS TILL NOT RF OI SCLOSED DR USES ACCEPTANCE ER CONTRACT.
1, DIMENSIONS ARE IN INCHES, DIMENSIONS 33 3/B 18 5/8 0NANWurairR-WITHOUT WRITTEN CONSCSO.
IN[ I ARE IN MILLIMETERS. 48FC++01 [8411 14721
2.& CENTER OF GRAVITY 48F0+05 33[8171 3/a 14l311]1 CONNECTION SIZES
l8 33-3/8 A 1 3/8' [35]DIA FIELD POWER SUPPLY HOLE
48FC++06 33 318 14 1/8 18483
3 DIRECTION OF AIR FLOW [847] [3771 B 2' [501 DIA POWER SUPPLY KNOCKOUT
IBFC++01 41 3/8 IB 5/e 32-1/8 —
-- C 1 3/4' [51]DIA GAUGE ACCESS PLUG
4.- ALL VIEW DRAWN USING 3RD ANGLE [1051] l4721 — (OTT) ' ECONOMIZER HOOD
(OPTIONAL) 16 D 7/8' [221 DIA FIELD CONTROL WIRING HOLE
[407] E 3/4'-14 NPT CONDENSATE DRAIN
f—25-5/8
16521 P 1/2'-14 APT GAS CONNECTION
RETURN AIR 6 2 1/2' [641 DIA POWER SUPPLY KNOCKOUT
11. /�—�,\
�� ,g C— WIIIII THRU-THE-BASE CHART
/� / 10-I/8 RETURN
THESE HOLES REQUIRED FOR USE
� [2T71 AIR CABTWR008A00, 009A00
lll- ,( 10
1 11��1�llIlIL THREADED WIRE REO'D HOLE
"[II'l�`t""�\�\W/i, ql, •• CONDUIT SIZE USE SIZES(MAX.)
44-1/8 \����� - 29-1/2 % 1/2' 24V 7/8• [22.2]
[1120.91 ` E ALT. - [7481 Y 3/4' POWER 7-1lE' [28.61
CONDENSATE 11-3/4 2+ (009A00) 1/2' FPT 6AS 1-1/8' [28.61
�2 DRAIN OPENING [451] FOR'TARO-THE-BASEPAN•FACTORY OPTION.
" IN BASEPAN SUPPLY 26-5/8 FITTINGS FOR ONLY A. Y, d Z ARE PROVIDED
AIR SUPPLY
14-1/2 A F' /;+--��. [6751 AIR + (008A00)PROVIDES 3/4'FPT TRRU CURB
[369] 12-1/2 11-1/2 - SEE THRU THE— �R FLANGE d FITTING.
1318 1 12931 BASE CHART N .
•
10-1/8- 2%23-3/4 - 3-1/4--- 6-1/4
[256] 06031 1611 [1581
4LUE 12-1/B
0011 HOOD I[3071 A
% L-2%25 — 18-3/8
[6351 [466]
24 4-5/8 TOP
[1181 E STD.
CONDENSATE 10-7/8 f 1
LECTRICAL DRAIN [2751 y 125]
DISCONNECT L
'N ' LOCATION . °( �----- �—{ ILTER
CONDENSER �I A,B,G OPTIONAL�F CONTROL BOX
COIL ( FACTORY ACCESS PANEL 25-3R
INSTALLED INDOOR BLOWERMOW 51-3/8 i[653]
I DISCONNECT ACCESS PANEL • -_[PLY] RETUA
OPTIONALI, ,� SUPPLY AIR
FACTORY • {1111111
• •i AIR ___--E
INSTALLED-------------- - ------------- ------ --
OUTLET , I� Ilk '14V' 6 [302] li , OUTSIDE
JOI �I —_ Ir 539149476-5/8 11-1 _ Q AI�
__ .-- -IMI — M-il . El") JO i."••...! . oex.! inniimii. .,.misinimi
HANDLE 5-3/4 MIMI 6-3/8 7 5-3/4
3-3/4 46-5/8 - 2 [1 d6] [161] [177] [146]
[
[95] 1141861 30-7/8 — (21411]
[7661 26-1/6
[682]
LEFT 98 — 31
1100 BAROMETRIC
1689] [786] RELIEF
FRONT SUPPLY * FLOW
AIR RETURN
RIGHT
AIR
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 04-07 SINGLE PACKAGE ELECTRICAL REV
U.S. ECCN:NSR 1 OF 3 09/07/18 06/22/78
COOLING WITH GAS HEAT 68TC003093 A
Packaged Rooftop Builder 1.49n Page 2 of 7
•
Certified Drawing for 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
Ca Yie' lSS RS[5 I Pq SC0 Eg°74 €1 OAc cal iN MTM
42O
STD. UNIT CORNER CORNER CORNER CORNER C.6. HEIGHT OryyT�y.M� RTx9uT WRITTEN cOREAT.
UNIT WEIGHT R WEIGHT OA) WEIGHT l81 WEIGHT(Cl WEIGHT(D)
LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y I
48FCRX04 482 219 113 51 116 53 128 58 125 57 37 5/8[9561 24 9/16[624] 18 1/4[4641
48FCRR05 543 246 138 63 133 60 133 60 138 63 36 1/2[927]_23 3/8 [594] 18 [457]
48FCRM06 556 252 142 64 136 62 136 62 142 64 36 1/2[9271 23 3/8 [594] 18 [4571
48FC.R07 607 275 162 73 152 69 141 64 151 66 36 [914] 22 1/2 [572] 19 3/8[492]
R STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. --�
FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
r --_�--_ BACK
R12 1/2 WITH ECONOMIZER
BACK [3181 \ .
CORNER A WITHOUT 1 ECONOMIZER HOOD
CORNER 8 ECONOMIZER OPTIONAL DOOR (OPTIONAL) '
II, SWING
�--� •
�� 0
.n/ & 1 ) i,
�lt,f RIGHT -a««OMI � qT Itio 111.
\
•
T. .
CORNER D ' 1 CORNER C LEFT
u
R
TOP — 74-5/8
Hass] FRONT
L 1_
' ` NOTES:
EJ _-= 1. FOR ALL MINIMUM CLEARANCES LOCAL CODES OR JURISDICTIONS MAY PREVAIL.
1 ( I 11 Z aEJvtARCE
SERVICE WITH SERVICE WITH E1PERATFNO
CO[C
o Q — SURFACE UC11NE MOM NONComunvE BARRER CLEARANCE
FRONT 48 [1219mm] 36 [914mm1 18 [457mm]
4L�Z-ei=����7�' 1 ci LEFT 48 [1219mm] 42 E1067mm] 18 [457mm]
FRONT BACK 48 [1219mm) 42 I1067mmI 18 [457mm]--.-
BACK W/FLOOD 36 [914mm1 36 I914mm) 18 [457mm]
RIGHT 36 [914mm) 36 [914mm] 18 E457mm1
TOP 72 [1829mm] 12 [1829mm] 72 [1829mm1
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 04-07 SINGLE PACKAGE ELECTRICAL REV
48TC003093
U.S. ECCN:NSR 2 OF 3 09/07/18 06/22/18 COOLING WITH GAS HEAT A
Packaged Rooftop Builder 1.49n Page 3 of 7
Certified Drawing for 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
Cc Yr,RG'J`TS SC r T S D TXT K CCW CW OO SE XOXT
KNMT S
ONXXI....WITHOUi WRITTEN CONSENT.
71-1/8
[1805.3]
(INSIDE THE BASE RAIL A SKIRT)
I
e 1,
(<<vvAKlln; -1 A .
\\ /_ 41-1/4
-�� C) (INSIDE TEA BASTE RAILS)
/
02-1/4
i \ :X'll 'I/
\, i / 2%1-3/4
INSIDE BASERAIL DIMENSIONS u6]
Mill
2%1-7/8 i
BOTTOM [48]
aTA�Ni
1-3/8 2% 1
3-1/4 [36] [25]
[82] 2%3/4
3-7/8 [18]
DETAIL C [99]
TYP 4 PLCS
y
FILTER ACCESS PANEL COMP. CONDENSER CONTROL BOB INDOOR BLOWER
(TOOL-LESS) ACCESS COIL ACCESS PANEL ACCESS PANEL
. PANEL
O cN
• INDOOR COIL �] IIiiiI . r ,
ACCESS PANEL _ s/ SEE DETAIL C
C� 0 1-7/8
[47.6] yi
x go o 1 f . .. f i X. - 1 o 6�S ■i�� it��m�li grin !Q i r �1 , 1 i,`p d,0
BACK LEFT f 3-va .J B
182.01 [1509.0] z-3/2-3/[61.SI
7-1/8 TOP CURB
FRONT [180.7] WIDTH
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 04-07 SINGLE PACKAGE ELECTRICAL REV
48TC003093
U.S. ECCN:NSR 3 OF 3 09/07/18 06/22/18 COOLING WITH GAS HEAT A
z
Packaged Rooftop Builder 1.49n Page 4 of 7
Performance Summary For 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
Part Number:48FCEMO7A2A5-0A0A0
ARI EER. 12.00
Base Unit Dimensions
Unit Length. 74.4 in
Unit Width. 46.6 in
Unit Height 41.4 in
Operating Weight
Base Unit Weight 562 lb
Total Operating Weight 562 lb
Unit
Unit Voltage-Phase-Hertz. 208-3-60
Air Discharge. Vertical
Fan Drive Type. Direct
Actual Airflow. 2100 CFM
Site Altitude 39 ft
Cooling Performance
Condenser Entering Air DB. 90.0 F
Evaporator Entering Air DB. 78.8 F
Evaporator Entering Air WB. 64.6 F
Entering Air Enthalpy. 29.62 BTU/lb
Evaporator Leaving Air DB. 54.4 F
Evaporator Leaving Air WB. 53.3 F
Evaporator Leaving Air Enthalpy. 22.17 BTU/lb
Gross Cooling Capacity. 70.27 MBH
Gross Sensible Capacity. 55.23 MBH
Compressor Power Input 4.92 kW
Coil Bypass Factor 0.087
Mixed Air
Outdoor Air Airflow. 420 CFM
Outdoor Air DB. 90.0 F
Outdoor Air WB. 67.0 F
Outdoor Air Htg. Temp• 22.0 F
Return Air DB. 76.0 F
Return Air WB. 64.0 F
Return Air Htg.Temp• 70.0 F
Heating Performance
Heating Airflow. 2100 CFM
Entering Air Temp 60.4 F
Leaving Air Temp. 99.3 F
Gas Heating Input Capacity- 82.0/110.0 MBH
Gas Heating Output Capacity. 65.0/88.0 MBH
Temperature Rise. 38.9 F
Thermal Efficiency(%). 80.0
Supply Fan
External Static Pressure. 0.50 in wg
Fan RPM• 1956
Fan Power 0.79 BHP
NOTE- Selected IFM RPM Range: 253 -2530
Electrical Data
Voltage Range. 187-253
Compressor#1 RLA. 17.5
Packaged Rooftop Builder 1.49n Page 5 of 7
Performance Summary For 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
Compressor#1 LRA• 136
Indoor Fan Motor Type. MED
Indoor Fan Motor FLA. 4.5
Combustion Fan Motor FLA(ea). 0.48
Power Supply MCA. 28
Power Supply MOCP(Fuse or HACR). 45
Disconnect Size FLA- 27
Disconnect Size LRA. 146
Electrical Convenience Outlet None
Outdoor Fan [Qty/FLA(ea)]. 1 /1.5
Control Panel SCCR:5kA RMS at Rated Symmetrical Voltage
Acoustics
A_Weighted. 79.0 db
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA 85.6
125 Hz NA NA 84.7
250 Hz NA NA 80.5
500 Hz NA NA 76.0
1000 Hz NA NA 72.4
2000 Hz NA NA 68.0
4000 Hz NA NA 62.8
8000 Hz NA NA 59.3
Advanced Acoustics
0
V. J C
Advanced Accoustics Parameters
1. Unit height above ground. 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction. 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k ' 2k 4k 8k Overall
A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.252.348.143.640.035.630.426.956.8Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Packaged Rooftop Builder 1.49n Page 6 of 7
Performance Summary For 48FC-6T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:13PM
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Fan Curve
2.0 000 RPM 2200 RPM 28 RPM
2400 PPM 2600 •M
1.9
1.8
1.7 1R0f1 RPM
1.6
1.5
1.4 ...'DIIP
1600 RPM
61.3
•1.2 ,
1.1 1400 RPM ,11 SC
1.0-r l �
��alf�0.9
a.
U 0.8 1200 RPM - ---------
115 0.7 0 BHP
0.6
1000 RPM iOB •
0.5
:.P
0.4 800 RPM P
0.3
02 600RPM
0.1
0.0 I l I t I I I I I
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Airflow(CFM-thousands)
RPM=1956 BHP=0.79 Maximum RPM=2836 Maximum BHP=3.00
SC-System Curve RP-Rated Point
Packaged Rooftop Builder 1.49n Page 7 of 7