Series TY-FRB, 5.6 K-factor DIVISION
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The TYCO Series TY-FRB Sprinklers �f"'u Ilta
Description described herein must be installed ,.
and maintained in compliance with /n . 4
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the ,.
Upright (TY313) and Pendent (TY323) applicable standards of the NationalSprinklers described in this data sheet Fire Protection Association,in addition . „ ,
are quick response,standard coverage, to the standards of any other authori- it `
decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so �" I
sprinklers designed for use in light or may impair the performance of these f= -/
ordinary hazard,commercial occupan- devices.
cies such as banks, hotels, and shop- -
ping malls. The owner is responsible for main- —
taining their fire protection system
The recessed version of the Series and devices in proper operating con-
f,,:\'1 . '
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable, is intended for use in areas tor or product manufacturer with any t`
with a finished ceiling. This recessed questions. j,
pendent sprinkler uses one of the
following: Sprinkler ° . 1,
r
• A two-piece Style 15 Recessed i`�s` 'i ;r i �
Escutcheon with recessed adjust- Identification `"4,.S -0 �£lr
i fit ;1 rrl a
ment up to 5/8 in. (15,9 mm) from
�, ' r` /
the flush pendent position. Number (SIN)
• A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT '
Escutcheon with recessed adjust TY323. . . .Pendent 5.6K, 1/2 in. NPT 1'
ment up to 1/2 in. (12,7 mm) from ' .�'
the flush pendent position. Technical
The adjustment provided by the Operation
Recessed Escutcheon reduces the Data
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat. When
Intermediate level versions of Series Refer to Table A the rated temperature is reached, the
TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently to shatter the
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to
kler guards and shields are described 250 psi(17.2 bar)* activate and water to flow.
in Technical Data Sheet TFP78O. `The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries,Inc.(UL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psis=(80,6 LPM/bars) The TYCO Series TY FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information, tion systems designed in accordance
s refer to Technical Data Finishes
Always Sprinkler: Refer to Table B with the standard installation rules
Sheet TFP700 for the "INSTALLER recognized by the applicable Listing or
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and com- Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style
a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
it to operate prematurely. Compression Screw Bronze
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* cr,..... 1 I
��;5 7/16"
_ (11,1 mm)
I NOMINAL 2° I
4 MAKE IN (50,8 mm) 1 /
2 R*to 2„ 11
I 1 3/8.
W,, 77r (50,8 mm) (34,9 mm)
3 / , WRENCH
1 � FLATS
i 1/2" NPT** DEFLECTOR* 2-7/8"(73.0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
Ll applied to the pipe threads, hand-
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FIGURE 2 Do not install any bulb-type sprin-
W-TYPE to Figure 1, apply the W-Type 6
W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb.With the Torque sprinklers 7 to 14 lb-ft (9,5 to
sprinkler held horizontally, a small air 19,0 N•m).
bubble should be present. The diam- Recessed Pendent Sprinklers
WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor-
3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions.
temperature ratings.
��>s Step A. After installing the Style 15
A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
014f lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the
`�� 11 of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairment Step B. Tighten the sprinkler into the
PUSH WRENCH of the sprinkler. sprinkler fitting using only the W-Type
IN TO ENSURE Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WITH SPRINKLER eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench
WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
W-TYPE7 RECESSED
Upright and Pendent Sprinklers Step C. After ceiling installation and
SPRINKLER WRENCH
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.
TFP172
Page 3 of 4
Care and 2-7/8" DIA.
Maintenance (73,0 mm)
2-1/4" DIA.
The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm)
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm)
viced in accordance with this section.
FLUSH
Before closing a fire protection system 3/8±5/16" ,,�-II
main control valve for maintenance (9,5±7,9 mm) 11 work on the fire protection system
that it controls, obtain permission to f /
shut down the affected fire protection MOUNTING 1/8"
systems from the proper authorities SURFACE (3,2 mm)
and notify all personnel who may be
affected by this action. CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
TY-FRB PLATE 3/4"(19,1 mm)
Absence of the outer piece of an
escutcheon, which is used to cover FIGURE 4
a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
The owner must assure that the sprin RECESSED ESCUTCHEON
klers are not used for hanging any
objects and that the sprinklers are only 2-7/8" DIA. _
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA.
vertent operation may result. FITTING (57,2 mm)
Sprinklers which are found to be 5/16±1/4"
leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm)
corrosion must be replaced. + FLUSH
Automatic sprinklers must never be
painted, plated, coated, or other- / \ ,7: 1
wise altered after leaving the factory. t , ,
Modified sprinklers must be replaced. MOUNTING 1/8"
Sprinklers that have been exposed to SURFACE (3,2 mm)—
corrosive products of combustion, but
have not operated,should be replaced
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
klers damaged by dropping, striking,
wrench twist/slippage,or the like,must Lim%ted Recessed Escutcheon
be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has eon with(specify*)finish,P/N(specify`)
lost liquid from its bulb. (Ref. Installa- Warranty
tion Section.) Specify: Style 20 Recessed Escutch-
For warranty terms and conditions,visit eon with(specify*)finish, P/N(specify*)
The owner is responsible for the www.tyco-fire.com.
inspection,testing,and maintenance of *Refer to Technical Data Sheet TFP770
their fire protection system and devices Sprinkler Wrench
in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench,
well as with the applicable standards Procedure P/N 56-000-6-387
of the National Fire Protection Asso Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order, indicate
having jurisdiction. Contact the install- the full product name and Part Number
ing contractor or product manufacturer (P/N).
with any questions.
Automatic sprinkler systems are rec- Sprinkler Assemblies with NPT
ommended to be inspected, tested, SSpread ConnectionsY
and maintained by a qualified lnspec- pendent
(specify)es FRB Upright or
N
tion Service in accordance with local Pendey) . , QuickSprinkler,p SIN
requirements and/or national codes. (specify), K=5.6, Response,
(specify) temperature rating, (specify)
finish, P/N(specify, refer to Table A).
TFP172
Page4of4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERC
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
PENDENT(TY323) 200°F(93°C) Green
5.6 286°F(141°C) Blue
1/2 in.NPT —
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 1,2,3,4
(TY323) 175°F(79°C) Yellow
Figures 4a and 5b — —
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories.Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C)
POLYESTER
Notes: SIGNAL WHITE(RAL9003)a. Use suffix"I"for ISO 7-1 connection;for example, 4 175 175°F(79°C
( )POLYESTER
77-370-4-175-I
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 CHROME PLATED 286 286°F(141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 04
t 1 0 2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson /
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA we registered trademarks of National Fire Protection Association; Controls
TEFLON is a registered trademark of DuPont