Loading...
Report OD66a 1 SUBMITTAL REVIEW APPROVAL GENERAL COMPLIANCE ONLY ❑ APPROVED ❑ APPROVED AS CORRECTED APPROVED AS CORRECTED RESUMIT FILE COPY ❑ DISAPPROVED O REVIEWED FOR INFORMATION BY: Jeff Welter DATE: 09/23/20 QMacDonald-Miller COMMENTS: 1 . REVISE STACK HEIGHT TO 10' ABOVE ROOF. . SUBMITTAL Job Name: Hood Fan Elevation: (ft) 108 Date: 9/10/2020 Revised Submitted By: Chris Hessick 09/10/2020 12:13:40 PM JOHNSON AIR PRODUCTS 2220 SE 9TH AVE PO BOX 15098 PORTLAND, OR 97293 US Phone: (503)234-5071 Fax: (503)233-0451 Email Address: chessick@johnsonair.com GREENHECK Building Value in Air. • P.O. Box 410 Schofield, WI 54476 (715)359-6171 FAX(715)355-2399 www.greenheck.com Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 1 of 8 alGREENHECK Printed D Job: Hood Fann Building Value in Air. Mark: LHEF Model: FJC-308-BI Performance Model: FJC-308-BI Quantity 1 Centrifugal Utility Fume Exhaust Fan Volume(CFM) 650 Total External SP(in.wg) 1.5 Operating Power(hp) 0.35 Required Power(hp) 0.35 Operating Performance Fan RPM 2216 2 5 1.5 Max Fan RPM 3371 Elevation(ft) 108 216 `—RPM Start-up Temp.(F) 70 Operating Temp.(F) 70 2.0 1.2 • Fan Configuration Size 8 Wheel Type BI rzo • Arrangement 10 . 1.5 S 0az, .9 ta Rotation CW — Discharge Position UB N a a� IT Construction Type PermaLock u�i o Discharge Type Fixed Nozzle N 1.0 0.6 n Spark Resistance None .- a) Scroll Material Steel p Wheel Material Aluminum co �ro 0.5 -------- - ----- 0.3 Inlet Cone Material Steel • Equipment Weights • c° �et� Fan(LMD)(Ib) 125 ©o cN P. Motor/Drive(lb) 21 _ Accessories(lb) 1 0.0 0.0 Misc Fan Data 0 2 4 6 8 10 12 Nozzle OV(ft/min) 1,091 Volume (GEM)x 100 Static Efficiency(%) 49 Tip Speed(ft/min) 6,093 Effective Plume Ht.(ft) 8.78 -------------- - Calculation Method 1 Momentum Flux Operating Bhp point Motor and Drives '`; Operating point at Total External SP Motor I Included Fan curve Size(hp) 1/2 - - - -System curve RPM 1725 Brake horsepower curve Enclosure ODP V/C/P 460/60/3 Frame Size 56 Max Frame Size 145 Location Centered Pulley Type Constant Drive Loss(%) 10.1 Drives Standard Drive Service Factor 1.5 NEC FLA*(Amps) 1.1 MCA / Sound Power by Octave Band WORIDWIDE CERTIr1ED Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones RRTIR� - Inlet 77 78 72 72 72 68 62 56 76 64 12.9 �� in *FLA-based on tables 150 or 148 of National Electrical Code 2002.Actual motor FLA may vary,for sizing thermal overload,consult fE1KORlORCE factory_ LwA-A weighted sound power level,based on ANSI S1.4 moremrnr v.,, dBA-A weighted sound pressure level,based on 11.5 dB attenuation per octave band at 5 ft-dBA levels are not licensed by AMCA International non cowmen .9% I Sones-calculated using AMCA 301 at 5 ft niocinnon 0 rnnnnnonm Inc 9 Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 2 of 8 ®GREENHECK Printed Date: 09/10/2020 Job: Hood Fan Building Value in Air. Mark: L H E F Model: FJC-308-BI Model: FJC-308-BI Centrifugal Utility Fume Exhaust Fan Standard Construction Features: HOUSING:Coated steel frame,scroll and stack-Bolted frame construction-Perma-Lock sealed scroll- Rectangular discharge stack-Adjustable motor plate-Corrosion resistant fasteners BEARINGS,SHAFT and WHEEL:Air handling quality,self-aligning,ball bearing in pillow block housing-L(10)80,000 bearing life-Polished,solid steel shaft-Backward inclined centrifugal wheel Selected Options &Accessories: Motor with Class B or Greater Insulation Standard Drives Finish-Coated Coated with Permatector,Concrete Gray-RAL 7023, Fan and Attached Accessories Switch-NEMA-3R,Toggle, For Indoor or Outdoor Use,Ship Separate Discharge Position-UB Wheel Type-BI Bearings-L(10)Life of 80k Hours UL/cUL-705-Power Ventilators Polished Steel Shaft Direct Mount Isolators, Isolator-Spring, Restrained, 1 Inch Access Door-Bolted Drain Connection-1"Drain Hole, Unthreaded Tie Down Points(set of 4) Inlet Connection-Slip Fit Outlet Connection-Slip Fit Weatherhood-Steel Unit Warranty: 1 Yr(Standard) Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 3 of 8 �GREENHECK Printed Date:Job: Hood Fan Building Value in Air. Mark: LHEF Model: FJC-308-BI Model: FJC-308-BI Centrifugal Utility Fume Exhaust Fan 0 13.23 431b8 441W INLET OD A / N \IpHnI 6.98 96 INLET CONNECTION 00.56 3 f — ei 4 Holes —19.88 — r- FAN Milt I GUY WIRES BY OTHERS WITH /—GUY WIRES BY OTHERS WITH j SELECTED TIE DOWN POINTS SELECTED TIE DOWN POINTS 62.25 90.20 WEATHERHOOD— 1 SHIPPING SPLIT 7.18 14.77 8.00 DRAIN L END VIEW 20.30 SIDE VIEW 'SIDE VIEW IS VIEWED FROM DRIVE SIDE 'FANS ARE SUBJECT TO 3.125 INCH TOLERANCE 'DUE TO CONTINUAL IMPROVEMENTS DIMENSIONS MAY CHANGE Notes:All dimensions shown are in units of in. Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 4 of 8 1 GREENHECK Printed Date: 09/10/2020 Job: Hood Fan ® Building Value in Air. Mark: LHEF Model: FJC-308-BI Isolators Type: Spring, Restrained, 1 Inch Standard Construction Features: Designed for horizontal and vertical restraint. Housings can be bolted or welded to supporting structure. Housings may be used for blocking during installation. Springs are color coded or identified to indicate load capacity. Neoprene pad for noise reduction. Fan Configuration Model: FJC-308-BI Discharge Position: UB Arrangement: 10 Class: - Rotation: CW Motor Frame Size: 56 Motor Position: Centered Isolator/Deflection: Spring, Restrained, 1 Inch Isolator Color A: Green Isolator Color B: Green Isolator Color C: Green Isolator Color D: Green 0 0.44 1 (10 3 0 0.5 BOLT - 3-AXIS NEOPRENE 1 SNUBBER 6 OPERATING HEIGHT NEOPRENE PAD 0.38] 5.93 7.31 Notes:All dimensions shown are in units of in. • **Isolator dimensions may vary with all aluminum,aluminum airstream,or Spark A construction, external inlet vane damper or with an outlet damper accessory. Consult factory for details. Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 5 of 8 af GREENHECK Printed Date: 09/10/2020 Job: Hood Fan Building Value►nA►r. Mark: LHEF Model: FJC-308-BI FJC-308-BI Min/Max Fan Curve Performance Requested Actual External Total Fan Operating Volume Volume SP SP RPM Power (CFM) (CFM) (in.wg) (in.wg) (hp) 650 650 1.5 1.5 2216 0.35 6 1 .8 • 3_� 3?1_�RP • 5 1 .5 • 4 FRP 1 .2 L 2 3 -.2.496--FRp 0.9 92 2216 FRAM EL 121- 2216 0.6 ts a . Ca• cn . 699 ' RPM. . . 0 --- ='- --- 0.0 0 2 4 6 8 10 12 14 16 Volume (CFM) x 100 Operating Bhp point , Operating point at Total External SP Construction Limit Motor/System Limit Fan curve Min FRPM - - - - System curve • Brake horsepower curve Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 6 of 8 OGREENHECK Printed Date:Job0 Hood Fan Building Value in Air. Mark: LHEF Model: FJC-308-BI Warranty - 1 Yr (Standard) WARRANTY AND LIABILITY: SELLER warrants to Buyer that products manufactured are free from defects in material and workmanship for a period of 1 Yr(Standard)from the date of shipment. SELLER's obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment(or at the option of SELLER parts therefore)for all Seller's products not conforming to this warranty and which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. SELLER may make further warranty protection available on an optional extra-cost basis and which must be authorized and in writing. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by SELLER prove defective during this period, they should be returned to the nearest authorized motor service station. SELLER will not be responsible for any removal or installation costs. Electrical components, excluding motors, are warranted only to the extent warranted by the original manufacturer. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of the electrical goods sold, SELLER will pass through such warranties to Buyer. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 7 of 8 GREENHECK Printed Date: 09/10/2020 Job: Hood Fan Building Value in Air. Mark: LHEF Model: FJC-308-BI AMCA WORLDWIDE CERTIFIED RRTIRGS R > ( ERroRrnQii E AIR (Gk. AIOVEAIEAT w nen CAATROt .n-go n;soclnTIOA 'co u1TERAnTIOAnI. Inc. AMCA Licensed for Air Performance. Power rating (BHP/kW) includes transmission losses. Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). Generated by:chessick@johnsonair.com CAPS 4.33.970 A:\ChrisHessick\Hood Fan.gfcj Page 8 of 8