Plans (6) Markup Legend / , / \ SPRINKLER SYMBOL DEFINITION COLOR/LINETYPE LEGEND x /^\\/ v \ SENJU Model RC-RES Residential Flat Concealed Pendent SS8464 BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). W o Delete Line OO X XX-XX ® - - - 1 1 K=4.9,162F°,7/16"Orifice,Maximum Spacing 16'x16' GREEENLIINES=INTERLEVEL CONNECTIONS/SUPPLY. Sprinkler head demand: 13 gpm @ 7.04 BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. >^o MAXIMUM SPACING(TYP) RC-RES-16 = 1/2"PIPE SIZE w~°a Add Line — — SPRINKLER MODEL(TYP) SENJU Model RC-RES Residential Flat Concealed Pendent SS8464 ._ =3/4"PIPE SIZE o.~ HEAD SYMBOL(TYP) si u 1 - 2 K=4.9,162F°,7/16"Orifice,Maximum Spacing 18'x18' —— = 1"PIPE SIZE „`ul Add Tee I I 1 0 RC-RES-18 Sprinkler head demand: 17 gpm @ 12 — CO `' = 1-1/4"PIPE SIZE W;1 W o �v ap Add Elbow SENJU Model RC-RES205 Residential Flat Concealed Pendent SS8464 c °0 a 0 - - - 1 K=4.9,205F°,7/16"Orifice,Maximum Spacing 14'x14' a w v w 3 W U Add Coupling I I RC-RES-14-205 Sprinkler head demand: 13 gpm @ 7.04 IX m SENJU Model RC-RES205 Residential Flat Concealed Pendent SS8464 m CO<W Add Head -@\--j--6`- ® - - - 1 K=4.9 205F°,7/16"Orifice,Maximum Spacing 16'x16' RECEIVED J ~W 3 RC-RES-16-205 i � � Sprinkler head demand: 14 gpm @ 8.2 0� z W�o � y F Delete Head --lXl- .s F�-goG°. ll�"'ll -�o 2 1st Floor �pp�, th !}A^ v6Ug��E1aOv,z�"v' , 1 ,,,,--„1 , 4 2nd Floor 4A 2 - i 0 Move Head - - -O- 6 3rd Floor p - b N z }�", g W o 3 4th Floor ..,. yd.o9.E r�+�Sm OO Note:All revisions must be reviewed by Uponor 15 TOTAL u o 2 o u'"o s z5 i CITY OF TIGARD 4,2`M.E, Table F002-i c o 9 qg s' r e t z Multipurpose Fire Safety Systems BUILDING DIVISION �Zpo-4Oia a= The Uponor Residential Fire Safety System is a residential fire protections z .. system installed in combination with the cold side of the domestic potable i E o Olmw$ ° zr aQ, water system. Only licensed contractors trained by Uponor can install this � ✓-' '"�" T-��-� - • pyZ o d..z s`�a o� r CM system. VT i L• \tT . T-9• I{ 4..T. 3'-C .-_-' z a z o-. o z 5 f o What to do if Changes are Required ! i Dec 'e' I a B © fVA za v,�o50-ogd vu 9 Q gS 1 i • . I Patio ' Q , ci ►l e=5 ,ion az E any features or obstructions require the addition or deletion of sprinkler • I I I'I i I , 4-e1-0 St A! 0 m z m p z '� N;o U w heads,or significant relocation of sprinkler heads,contact the Uponor Design -}-- -i ! I Sa&0 SL .,_ _ 1 „„ Sm{G� i jj y w,"x o o=1;-.; Department to determine if observed changes require a redesign i -" art— ••f I �, `��W 1 ! 6 f b^q�y 0 3-.,n 6 a a r (888.594.7726). t i C 4 I I I 1 2 em 1 8 W a c w 2 9 2 0 1 IQ __� ( m�zna,,.f az n��_ MOST HYDRAULICALLY REMOTE HEADS °N-� ( 1"AQUAPEX INTERLEVEL - Q Ai ( o'o`z m 5 o ° r o HEAD# GPM PRESSURE REQ'D AT STREET I CONNECTIONS FROM FIRST •V. / i I J o m m o n 8_s . el b ,FLOOR TO SECOND FLOOR ,� _ I ' } ` U - el 1 HEAD H.4 17 54.2 �(� 5 ` ® X. I `^ l., ' / -�. S d g 4 Q 2 HEAD H.3&H.2 26.2556 73.33 1'AQUAPEX INTERLEVEL y / I S.° Kit l Ief1E'tue Mr y r y ,0 CONNECTIONS FROM f I I 1. Ei Ali •1 0 o z 0,:,,,,,,. w SECOND FLOOR TO THIRD \ : / I ' :18 M.I•LI .;i I FLOOR \� \ )' // i j ems= V..fi' r ! t° \ —I w I i wf/' r i Suite =} "4� \� v i 55HFL5 I // 5 ` L� I I - �1 \N \ ,ii ---I. - 161Fr'��/ �' _._ , 54M _ 11 • ..�.� ' 'fir e' I ni 1 here by certify that this Ian,specification, \ III \ •"ill 1 an '^ rv; ��. ... T T.5 , t h p p CITY OF TIGARD \ N \ Bath \T 69- SYSTEMCeect supervision or report was preparedd by that I am NICunder my � _ - , r! RA FlT�'"� j direct supervision and that[am NICET \ \ ' ~ � �r E ao FT' ED N \4 I��_ 3` ..�' F.7 __.__' 1 •-p--� PAS I 11/4"AQUAPEX TO h Approved Approved [�C) \ , ���� a 7. , T ., I �i F.6 34`SHOWER 1 �2 I�* -_ SYSTEM Contitionaily [ , I ~\ .... " + TOWEL O �aJ Tim W McDonald Date: �� .1(3' 0 i RING I , ____ `� I NICET Certification No.150393 t•1 \ I .43 5 TPt,,. /-+a I� v i _ -W ' Water-Based Systems Layout-Level III E For only the work a s described i n• I I T 4o. S I; ��m S 1 MAIN SHUTOFF Certification Expires:June 1,2022 m PERMIT NO.AI 5 r$o 2 o — 0 0 330 4F.12 F.�3F. 0 F`9 j fl ING 9 5 3 I NSU A.U .I R VALVE LOCATION o 0 rLB ...._.}.I B 8 l• B D" [ , F.1 F13 1 See Letter to: Follow r 4 F I I STAiR:AV mt_ , qq ii‘ Attach [ j 47T.4:F�49 T.5o �� 1 s 1 05, ill sM � e� I 1,1 . i W T a t li M 4 -!' �^ I / \T.514 II ® .�,� � $tin I i v i I U Job Address:13o,-es, 6 W Av 8 4 814 r SEE I I r' +!. I , WOOD TRLAD.MAX. r li Q f I li \ I i t i"li fw o I Ff`- I a. RISER 8'WDD OR ,� y h Fi t a O m u' G Date. 6 I Y_,,`2 I f _3-4�'_ I I I i REMOVE STEPS AS 111 fi�' 1 p ( 3'-i' r F I SFf z'O o �J• �I �.5� I "'.` _ '�E��'I� REQUIRED PER SITE 11 VP i[- i I (rOR z m n 8 Ce I ✓'t"; I MAX.2 TREADS ni I� �ap i 4-✓ Ili '.t a t>¢7 Ef', o" r_ �_----., i st a 1. t' s,M i =� ,tea. mILI w.,—� Dt 1 Car Ia �,` \ q�YwaLLpT ' " li j Garage " ��t 1_1/4„AQUAPEX ( _y +?9"ABOVE - \i' I I "_r .. / I o ..a o TO SYSTEM 'I INSULATEOR NO J WALL FINtSN 3,'G.W.B. CURRENT STATIC 1 1/4"AQUAPEX RISER = ! FLOOR OVER ( �' lI CE!11NG F NISN I 15 � a$ V ' _ Ce 0�/ a z a m o_ `° WATER PRESSURE r I UNHEATED I ryl I TYPE• X GW,e. r+- if"< -tRAC (Y O z ¢H w ,`'.A PRESSURE GAUGE ` \L__"SPACE )L. SYS M-s ` �j� 1 FIRETAPE Ac..OWe K E. ! • �. a I,mod, I SREVSD W �• O o o a z wo STATIC: 95p6i TO HOT WATER " WRAF BEAMS BELOW I 8 �, q i ' 1 1/4(PRE CASH ACME I HEATER \ ' CEillNG LEVFI G I I v 1 O m (OR EQUIVALENT) F, Living'-. t � 1 1 *�i " 6PSI LOSS FLOWING 26 GPM rt '� F +NSllLATE FLOOR ABOVE . _ J2 t. I ': a ° RC=RES-16 \ r—• , oo S 1ifi. T.55 f�\I p � //* A F 1 k W L.L > c PRV set psi essure ; 3 t1 Rf' I /I rr'11 al 1O II NSULATE _ Q I sal-•s6 N 0 o` 1"WATER METER - 7 ------- 0 5 NFPA 13D STANDARD LOSS %E. _4 (>� 8 / ,\ I NHEA D I 1i, \ / 0 3PSI LOSS FLOWING 26GPM WALL ABOVE C SPACE j \\ Porch i g.! o o 0 �,a 0. III 4 , _� _ / � o o' SHUT OFF VALVE r ` � � i -' 1 � � FLOOR ABOVE ��r 7- t � w w n i w CURB STOP - S'1 ••.•• •... —� 3/4'AQUAPEX _ I i ce m 1=m,n-a `' 1PSI LOSS 1-� 7-0<_-p XOz • SO�CSL I \ 'AQUA INTERLEVEL/ i 1 88 ✓m (OI �+ _ �: 0 I ' +s,BEL.Jw -' CONNECTIONS FROM FIRST (,fE�y.•' I 1 O '••� Q w .. m r 0 STREET Jt=Il l .� I .._ { FLOOR TO SECOND FLOOR s--'- t-i— ---- r f----mac N 9 E m z s w a I�11. i ; I \ �J V m 0 LL CORPORATION I I W I A 3 s s¢ STOP 1PSI LOSS Il�r� V 2 0 '6 2.p O / MAIN % �-,:il°• Eq 100QF 2 SECOND FLOOR FIRST FLOOR ` `�V " z r ELEV..' 1 1/4"AQUAPEX t ______ SHERSTFOORAND DESCRIPTION " 35'OF F100, 1/4" = y 1-On \F100 1/4" = 11_On FISECOND FLOOR 1"COPPER-K 1 e SHEET NUMBER g 5 0 5 15 3.2,, ~\ WATER SERVICE DETAIL Ell =Ell �/ NTS © UPONOR - CONFIDENTIAL F100 ,, _ r __„ _ _. . . .,... .... _. __ . 2 'L Markup Legend SPRINKLER SYMBOL DEFINITION COLOR/LINETYPE LEGEND ` z ' \ / \ BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). f o / f v \ OO XXX-XX GREEN LINES=INTERLEVEL CONNECTIONS/SUPPLY, O �', Delete Line MAXIMUM SPACING(TYP) BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. a z = 1/2"PIPE SIZE >r,g Add Line — SPRINKLER MODEL(TYP) a"a O HEAD SYMBOL(TYP) J ...� =3/4"PIPE SIZE 'a"W u d Add Tee I I 'i = 1"PIPE SIZE O N r+u,T a>� I = 1-1/4"PIPE SIZE W;LL w 2 Add Elbow O r«v N zo =aNaIAdd Coupling I I t7 F. .«3 VtNm`W o�l-w3 Add Head -@--�.2\--0.3\- Delete Head -I X I- q� z x m z r- x Y Move Head -O- - , Ci s- t-',11V.,a'< ‘,Y2,4o1gaz x aFmo Note:All revisions must be reviewed by Uponor u 5,c fO g -8 3 Table F002-1. o o m 0�5 y F H Multipurpose Fire Safety Systems pzpLLme�o0 00 �_o The Uponor Residential Fire Safety System is a residential fire protections 5 O c A.S °o 2 H a system installed in combination with the cold side of the domestic potable iu m o m m c,�4 z Fz , , water system. Only licensed contractors trained by Uponor can install this a z system. g z 2zI9P4'41<< s� �U,� m3Z9g0 What to do if Changes are Required VI z y cni o f g U i o g g"J y If any features or obstructions require the addition or deletion of sprinkler al S a i m o= a o o a,,u heads,or significant relocation of sprinkler heads,contact the Uponor Design �i 0 z z u o��J�r a Department to determine if observed changes require a redesign 5 n t- o U 5 t i a w -i (888.594.7726). �am1ow F'u$�m o d'L cP.Fx '�za II 1 I I H 7-04bX0X I I g'5.;so c -on -'---_. _ i. . _ - a t.. i,,,,•,.,.,.. 1 i c'u r w m a m'o 5 o i=j I ! I EGmc55 C2omz o� z,, J. • 20D m \ I wjy - pom; t( O+' 7YP— el TYP, 5u.°uMM 4S g zzu t 1/2"COLD WATER AQUAPEX I I �j I 55Sef� 6 o�a�u^,a,a Tiq I / INTERLEVEL CONNECTION I ( 7 / F�o,'.ti Fc°�du�?`��F SdP E AT 5't Si. { FROM THIRD FLOOR TO ATTIC I 4 I Master , I gi n NIN. _--1 i-_- / N �`•-CIO RGIOF ANCE, EGRESS I O — i / § BE>.oW BeC1100IT1 \. .E55 ' H.4 / I :807.1 I 16 /~ 7 9 tWESil0,,, 'I' Q 1^ I here by certify that this plan,specification, i a 22v30 WT"fK) t TaW�� a E_Y" or report was prepared by me or under my ` •® ACCESS // / l \ !, ! Certified direct Pervasion and that 1 am NICET I _ DQRMER HATCH--T( '0 I / 1 .-.��, '-VA, CKNESS b 1 ROOF) O H•1 I i I ( i 4 4'�etr . e,.4N l) Tim W McDonald Date: RY(1«DO[d / ( SM "JER REDU� I I ' I` NICET CertWater-Based Systems No.150393 Layout - ,� — r 1 -. \--- T.16[�a=I" c 24. „s"49 _ _ SYSTE f !4I S I Certification dEx Expires:lune 1,2022 Level III `A*rK fir, M�Bat'= i�p hiltia I 1"AQUAPEX INTERLEVEL \ -' I udCEi5_ eD -n ( ... - ___ I CONNECTIONS FROM �� i•a- CO 4 ''Q , y+�/ry( SECOND FLOOR TO THIRD LLJ t nH� � (♦'J1Yt+�' .(� I FLOOR T. , wart IT.21 ,t i sEESTfu{` ita 1 '� 1 T.20 i : , s -----FOR STAIR U = T.18 `_ — gi ire °c "� ���__� Q ;w EE SR TAil1� `' Val "—" \i#{1, 4S.,y. ..�.,�.�1'�j�.�.'d�al►� -14-205 a w DIITAILS \ 1 JZ4 , 1 I\ i 1- Bath R�}Ia/�� ..— II Ce Z z^ a _ tC�}RES 1� [ 1I I I ' _, Yl LJu 'I oC a o M m © I LI Nvpit(,AT .• I#i.1 '� ( 4r 45 Fr J,(- q ii II T >ri rv'2' „39'ABOVE �� lli ro a"+� i. -1 •� i I a c9�n LLJ NOSINGr Fr { / B&• Imo(,,ry l� . I / 1 w r /SHOWER I�(E > 4 LOW WALL � , ,� 1 , — ( f i o _i % 12 Fr' - 'z c~i6 utv�i .(5. H•3/22�0 ATSI,C u i \\� 1"AQUAPEX INTERLEVEL / - ` >a� O $a a 5°w n ACCESS HATCH\ I i O - CONNECTIONS FROM THIRD N ( 5-0ekPA55 .' .-.F o 0 o J O i m I AC-RES-16 xM' FLOOR TO ATTIC a y WW��y ll �k �---ilik, V V a s n z "i (ATTIC) ( \__..RADON I ( �' THIC NESS /s4 "" f 5' 59 B�PA55® I T'I O_ u 24 SF AT ' REDUCTION - r > .n - 30'MIN. (ATTIC) SYSTEM i m 480'. I > / 4 3'SY'/ 3'-9y,,p 'liat: (y43 3-35 1 I..V LJ /t1 CCLEARANCE NO 491 j 1 'f 8II.A}. g H.O B ~�\ B V ACCESS . — VP.e t I, RC RES 16 l 8 RC-RES-16 EGRESS h DORMER ! - 4 \Bedroom 2 / I Bedroom 3 P _i 00 n 5-6 pA 1 {i _ l LLOF> o ( • I # i O 0 („(� m m,n 491 Aft I EGRESS t e j :.�'- ( I 7 EGRESS m i- �, 5^O dSL 1 I s o LL o SL lI NJ =mo ROOF IIELOW 5-0 SD St LLI y 3 ~ "' C a O i1 1 s wS 2� ATTIC PLAN 1 THIRD FLOOR SHEET DESCRIPTION THIRD FLOOR AND - ATTIC PLAN (;1°1 1/4" = 11-0" i i FO10% 1/4" = 11-0tf SHEET NUMBER mama iMMINIIIIIIIIIIIIIIMINIIm m 5 0 5 15_ _ 1/4"=1'-0- L © UPON OR — CONFIDENTIAL F101 K +^" ^,ream-%-+-,.r+w.;wx:'^ ...> Markup Legend SPRINKLER SYMBOL DEFINITION COLOR/LINETYPE LEGEND z //C�� BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). z o \ / \ 0 XXX-XX GREEN LINES=INTERLEVEL CONNECTIONS/SUPPLY, Cill Delete Line � � � ' f MAXIMUM SPACING(TYP) BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. a z = 1/2"PIPE SIZE ""o Add line — SPRINKLER MODEL(TYP) a^',O HEAD SYMBOL(TYP) . =3/4"PIPE SIZE 0.a @a T = 1"PIPE SIZE O N 0 Add Tee I I I -- "'' =1-1/4"PIPE SIZE e, w o H � °'no Add Elbow moo =t'mno3 Add Coupling I I 27-.z„'+ o� ylNZs W�w3 Add Head -,E) -•E)--E.3\- Delete Head -1X1- t a oy p y z LL, ,!°t �� o0 3 .���� NPnyo2om Q?cw. Move Head -O O K y z r Q QyyQayw y> nWtVQFZ'+y� mp Note:All revisions must be reviewed by Uponor e s a c. Table F002-1 d Tel a i- i wr 3 3 ooa9Fy zyz Multipurpose Fire Safety Systems a z z a o o s o � c The Uponor Residential Fire Safety System is a residential fire protections 7 5 S o 2 zd o F w a 4 z system installed in combination with the cold side of the domestic potable IY e n S >., z c.z 3' 0 water system. Only licensed contractors trained by Uponor can install this 1"AQUAPEX INTERLEVEL ` I H 3=o a d=' -n£'a',-o d system. SECOND FLOOR EL CONNECTIONS TOTHIRD \ CONNECTIONS FROMVF FIST a~a°°°r-1 a.o n i S F FLOOR \ FLOOR TO SECOND FLOOR \ V z u ti i-3 w,�v a What to do if Changes are Required / \ if,) � 0 o f q z o p n "' If any features or obstructions require the addition or deletion of sprinkler \ A G m i y a o s 2 a c z c v:, heads,or significant relocation of sprinkler heads,contact the Uponor Design \\ / f 06 _ c F >o 9 a Department to determine if observed changes require a redesign \:/ I /' \ Jf' i - ---=- 1( s $E''o 4 U 4_o p L a 5 t. (888.594.7726). / //i \ \ go ' 20A eck I . y Patio I© 2 I z 3 q3`'F 7-0 4',XOX �_ + 1 , a I �4-5 9 X ; w'o w > I? � o=�.'• A I 5-0 SL SFr1GI2 -..,, y°<a S I C .O1 1/2"COLD WATER AQUAPE% ! ES' S - - "�'- I.�adsp- — C y y w ou o o'>>0 INTERLEVEL CONNECTION \ \�,1 I / FROM THIRD FLOOR TO Ai'TIC\ TYP. � e 0 / 1 \ \iioa v_ / ,! - �\ '[ J 4 L--7 GGilUd !_!! / `i / \ — I oww ( i� —I 5605L 1 iSSFA 1 / \ / I \ `'Iry f " 7 \I- \ i! fN ` e W I // 30'MIf A Master/ RQdF t9t (\ e \ ' L!/ J 0�� u z o m< EGRESS BELOW I xa . I O �R \I \ K'tchen.tte cLEARAN — �/ No \ , Bedroom / r \ I v�.z l{ 1/ ! / //, ACCES \ .._. H.4 \ •-6.\ _., r 10 '{,' I'� IkI ') I M.�.�... r:Mr: TWe i (ATTIC) 2zx3a t� 9� A I R R 16iuite �� - m. by certify p p L ACCESS )_ D \ _� 1 16 E •f3 /- '�' I •�W,{},-. �— I I 1 here certi that this Ian,specification, -1+ Ant V t /'�-- �` ii. M�-- or report was prepared by me or under my Dogo, HATCH ' �� X'WAL ICE ES' / \' 1 jlN 4HCw direct supervision and that I am N[CET �- ■ \ SM Certified. T56 I t H.1 ROOF ' C •-e-- :� r�`jj�� n • �1 �' I v`i SYSTEM QUAPEX TO .59 V' 19 i ! i t ,r, � BELOW w < . .... Ir���'. azx3a".. N © iiJ• • '- I i • � T.60� Da TION J <'j'<_ q ..•.. SHOWER •�r L I N Bath Tim W McDonald Date • Y 1 t I -'� STEM�1 'I _� •,�t'/ t - I `ti Rt. a �� a - r y it •'• '=v '•- .�5 S , `33A < SYSTEM 40 FT'- 1.11 J NICET Certification No.150393 m m T.16 I ► `1,FT,T' 7�1 �' 4 ?L •y MAIN SHUTOFF Water Based Systems Layout Level III E fl D4, < i T 7 \ t itt• y�-1 ,.Sy�, ��3'I,t" < VALVE LOCATION •--'1 4'4"'1''�' 160y134°sH0 II F.6 Certification Expires.June 1,2022 I �"" s ' .T 1 '� T 2 T 26 �p Beath<. mEL 2' �•`� .���T TYP. 1 Z ncc SS/ I Ali64# o RING I �;,.'lidsT IION 'I �.,� Ali T 21 t ie � �19 SiESHT lFT2 'ea if- I T., 1 I� _ 2.4 ��• F.11 F�10F.3 F.12i ° i 1 W o T 20 4 - '4 F3R STARS C <'i� 'ai I,1 PLUMBING i. r r: ! `4 ,e 2"-7}' t=.g• 5-} 9Yz m Li m jr- -'I • t SEE T.Ut - DE'FArIS C r (....); ��__...�+- I_ _ B o^ f i '" 1 ® yyh TN, UNDER c7 � �- ¢-'ti i`� WALL "YI112Vr- _- ry I 'L- SI RWAY m r — FC AIR T.18 ��` �4 . +� tif J � y — —I—� IH , UMW a _— f � iii`i_"; -DE'FA LS 11 �r-I�/ L"'� 32 S. VoG Ir - _ . "` 1 3 �� •���- �-- a f n v. f, 1 'T S1 T.48T.4 1 I'I 1 1 ' sIM iE1.. ry w /11 i er" ©Bath -f d , 1 i1 p! �e t„..„,,owEL n; 'GRES 1• -�" 8 tjj r v' ' \ II �+- I Y Nt ALL T ) 1 �"' , 1111,11 ���� � I .••K 45 FT' - lI! -R■ �\T. 1 i i I Y 4 aaililli j�^^ a z o n I, RC'E 10 t � � I .- • ry! „f E sHT-U72' I 1 _ __ r� f WOOD TREAD,Max. a oN1 + --P<1B NG� I' I�1 'S'TUB&�) ;`i I FOR STAIR 1 ,�i RISERWOO B"(ADD M ¢1 u+ry R\ } /' LOW WAIT ® iI • -.- tR Nq , SHOWER---� �. E. _�� _ i VI - t I REMOVE STEPS AS w ,,• .: _. .,_a-r \Ij ► NM _ JL I �.�!.t 0 I REQUIRED PER SITE > ` 'ErAT r3F- ,� ____ t R i/ ' '1�I� i CONDITION) f (x / ,�,,,.� .-. 3 t S&P '1} ( I I I MAX 2 TREADS . ---___ _,f,�} H.3 � _ —� 3sv a 1?FT c <' _ - ; t o ! I �'+, e o It 2 �\� i / � � - 508PA55 � ' t 1 — t �l a~ �t 1CaF.. as zoo L CCES�7C @ II 15 FTC I ,�... \ 51M C. M. m (SIM / RC -16� 1"AQUAPEX INTERLEVEL I 5-08 ASS iq5,,, q� "ALL- 0 11i „� I ro 'ALL T a�r \ ,N ! I ro` II„r`f Y-- Garage @ ri. O o o a~=u• (ATTIC) CONNECTIONS FROM THIRD ® / G THICNESS �#- .39 .:•, ' I ■ ,^ V V V~¢a v, o (REOIiCi'KN•! 24 SF AT FLOOR TO ATTIC < 4 r - , __NOANC• i INSULATE __t. WALL FINISH%'G.W.B. V/ ,1 O SYSTEM �." \\ FLOOR OVER CEILING FINISH Ys" ut (A771C) 3C"MIN. I 3' , { �t • "<l I1.� .1 I \\ UNHEATED / _ry ! 1 TYPE'%'G.W.B. > y CLEARANCE 8 2 2 Y �8 - °nns SPACE �C e FIRETAP€ALL G.W.B. w NO 1 t � .8 ' ♦ h _.-SYSTEM 1-- - _ W oG e i �,{ -' 5-16 WRAP BEAMS BELow ACCESS ( I /RGRES-16 � RC -16 TI54 • _ 'Living \ ' '�/ !I ` m hSULATEFl LEVEL VE 3 ' TYR 0 PER R807:1 � . CER4NG LEVEL DORMER EGRESS I I Bedroom 3 5 \ Bedroom 2 / 1 -R SE i , R i �8A 9 c -- ...2 L_.—..,..-_� ...._._ / rJ --' BELOW i RC-RE - -+-- 2-6 F ._ _- - miC1 2{ C] ,o z F n 5-63�51 / _- J(/�'' .5 T f \~ CONNECTIONS/4,AQU FROML FIRST/ 12 54Ety 1 +'° �® D'. oOO I ' i _ r i�O :-( t $Yt �3-1*4 '140' N 8-0 7-0 SChfD "� } Q w r) O' \ 4 5 "' 1 EGRESS Da L q Ft.... ER /r____. h__ _ '_ __ y FLOORTO SECOND FLOOR w -._ __—( f m ro ' ..: '1 E FA \ -EATED I T P. - 1,--' Porch l O LL ro m -... i EcSkh3 I. —� 5-0 Sl -t'-- I! Yt.PACE �� ABOVE_ � / N1 is z~ F.o 40 �y� ; w B 4 _ _ I 1. 1 § FL000 ABOVE m LL o r0 T3 sL ROOF'BELOW I L { + - _ __-_._ _.rro. -- . -- - z p t 1 1 _ I -_-.-. S-0' St 1 �� / \may—^`. F-_© 8B 3 /, L: U S G . HE 4 ATTIC PLAN 3 THIRD FLOOR SECOND FLOOR 1 FIRST FLOOR SHEETDESPLANON J MIRRORED AFLOORS N 102 Ef t tt F102 „ „ F102 i „ , „ F102 i/^ = i _0 1/^ = -0 \ / i/^ = v _o i/^It _ i t_Ot/ SHEET NUMBER 1 Y 1 `t \ /. 1 "f 5 1 `t 0 1 5 15 1/4'=1•-D• 1 0 2 'g O UPONOR - CONFIDENTIAL F I- Senju RC-RES:Open Web Truss/TJI Construction Insulation Recommendations AquaSAFETM GENERAL NOTES: to areas subject to freezing,care should be taken in unheated attic spaces See General Notes 8.2.5.8 for Architectural ProPEX LF Brass Fire [o cover Uponor AquaPEX tubing completely with insulation. Insulation Feature Requirements Sprinkler Adapter Tee should follow the guidelines of the insulation manufacturer. See Uponor ` f g 1. THIS SYSTEM IS DESIGNED AS PER NFPA 130 2019 EDITION AS A RESIDENTIAL MULTIPURPOSE SYSTEM Blocking Maybe Fire Sprinkler Adapter Document"Uponor AquaSAFE Attic Insulation Guidlines"for attic O - O SECTION 3.3.12.3. -- - P on Nut w Required.If - installation guidelines(Provided in Contractors Documents package or online d Blocking is Used, . G 1 at www.Uponorpro.com). O 2. UPONOR COMPANY RESERVES THE EXCLUSIVE RIGHTS TO ALL DETAILS AND DRAWINGS AS SHOWN ON - _��. �"Min. t I >n z THIS SHEET. THESE DETAILS AND DRAWINGS ARE PROPRIETARY INFORMATION OF UPONOR COMPANY AND Use The 2 Top 1:"Max. C w n g Screw Holes. i c / Bottom of Mounting Planter Box Window,Bay Window or Similar Feature. n`!D O UNAUTHORIZED USE MAY BE SUBJECT TO PROSECUTION TO THE FULL EXTENT OF THE LAW. r -1C / g Extreme Temperature Installations If no additinai floor area is created No Additional Sprinkler is Required. ^®�? I 11 bracket Co Face or Truss AquaSAFE Residential Fire Safety systems are often installed in attics or Q w¢ 3. THE DESIGN Of THIS SYSTEM IS DICTATED BY SPECIFIC CEILING HEIGHTS AND ROOM SIZES. IT IS THE Fire Sprinkler Ada{Ste other areas exposed to temperature extremes of heat and/or cold. Follow 8'-0"or less O N n u RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE CONDITIONS SHOWN ON THESE Mounting Bracket i the recommended extreme weather installation instructions to isolate and / w m PLANS ARE EXACTLY AS THEY EXIST IN THE FIELD. DEVIATIONS FROM THE DESIGN MAY CAUSE THE _ W u w O SYSTEM TO BE UNABLE TO CONTROL A FIRE.IF THE BUILDING CONSTRUCTION DIFFERS FROM THE FIRE protect system components from extreme temperatures. Because this RC-RES16 N z system also delivers domestic cold water directly to plumbing fixtures, 9'-0"or less ® t n Z•a SPRINKLER PLAN,CONTACT THE SYSTEM DESIGNER IMMEDIATELY. 3-#10 x I 1/2" W. }• w a n I -I - } Uponor highly recommends that you protect the tubing with adequate / -I Full Course I I W ut 3 4. THIS SYSTEM AND THE ACCOMPANYING HYDRAULIC CALCULATIONS ARE DESIGNED IN COMPLIANCE WITH insulation in warm weather areas to minimize heating of the cold water `o N e w NFPA 13D 2019 EDITION. Thread Strews l� =v O 3 supply. In Bottom Holes i7;th w 3 o y o " m 5. "STAND-ALONE"OR"MULTIPURPOSE,WET PIPE"SYSTEMS ARE PERMITTED TO ONLY USE ANTI-FREEZE • \ - \ Installation methods include,but are not limited to: `v o m W on m W LISTED FOR USE IN NEW SPRINKLER SYSTEMS. Tenting over the fire sprinkler piping. C u'F W 3 Lead-Free Flat - ,_ Additional layers of batt insulation. If additional floor area is created.Cannot exceed 18�,be more than 2'-0" Concealer Senju \ 'r" ' " • Increased depth of blown-in insulation. more than 9'-O"wide and be with In the coverage area of the ' a 'w 6. MODIFICATIONS ARE PROHIBITED.SPRINKLERS THAT HAVE BEEN PAINTED,CAULKED,MODIFIED OR Concealed Fla[ deep, 9 DAMAGED MUST BE REPLACED. Sprinkler Head Cover Plate sprinkler.No Additional Sprinkler is Required. ooa i o F.1 m-. Caution: If you will be installing spray foam insulation,make sure to a o S y m r 2 7. A SINGLE CONTROL VALVE ARRANGED TO SHUT OFF BOTH THE DOMESTIC SYSTEM AND THE SPRINKLER g pp spray i G o m- i w protect all Components Burin application.Consult with the s ra foam -z s m °s m SYSTEM SHALL BE INSTALLED. Senju RC-RES:Traditional Wood Framing Construction manufacturer to ensure compatibility with all products before application. NFPA 13D Table 7.5.6.3 Distances From m y�.>,�d a ovr Heat Sources Ye,o,z.'"o� a�w 8. OWNERS MANUAL MUST BE PROVIDED TO THE OWNER. m o V o a z i m Consultation with local building officials is encouraged to ensure compliance ' y w a r_ o 9. AT THE MAIN SHUT OFF VALVE,A TAG OR A SIGN STATING THE FOLLOWING IS REQUIRED;"WARNING:THE ProPEX LF Brass Fire with local building codes. o c m u o 3 WATER SYSTEM FOR THIS HOME SUPPLIES FIRE SPRINKLERS THAT REQUIRE CERTAIN FLOWS AND SprinklerFire Spr,nklcr Adapter Ordinary Intermediate a.,'n p o t i j w U PRESSURES TO FIGHT A FIRE.DEVICES THAT RESTRICT THE FLOW OR DECREASE THE PRESSURE OR Adapter Tee Heat Source Temp. Temp. m c m f y 8 8 i t o Push-on Nut o�" �� 135•-170° 175°-225° -fit _ AUTOMATICALLY SHUT OFF THE WATER TO THE FIRE SPRINKLER SYSTEM,SUCH AS WATER SOFTENERS, 9 ° o G °c e Bending PEX Tubing Side of Fireplace 36" 12" ; m m -o- y FILTRATION SYSTEMS AND AUTOMATIC SHUT OFF VALVES,SHALL NOT BE ADDED TO THIS SYSTEM t p gin an direction is six times UI or w a i F r a a W WITHOUT REVIEW OF THE FIRE SPRINKLER SYSTEM BY A FIRE PROTECTION SPECIALIST.DO NOT REMOVE -{ 1 K.Min. The minimum bend radius of Uponor PEX Lubin y Front of Fireplace 60" 36" W m o m h>h 24 3 THIS SIGN". ..� - - 1 2 Max. the outside diameter(6 x OD). <z o a z u� Fire S Bottom cf Mounting Wood Burning Stove 42" 12" M a o�a i c. ' z prin der Adapter g Bend supports are available for 3/8",1/2",3/4"and 1"Uponor AquaPEX z z^:z g 41 a 0 10. ALL INTERIOR PIPING TO BE UPONOR"A uaPEX®"UNLESS NOTED. Mounting Bracket Bracket to°ace of Truss tubingto facilitate 90-degree rigid bends. Kitchen Range 18" 9" Q F<h p 2 o z q gr gi J z°�.aimg {���/y�\ II \ Wall Oven 18" 9" Nae� awa�°�o�,adyQ / -U \ Fittings _Hot Air Flues 18" 9" Vl's8 u8Emiq8ma N2yu 11. UPONOR"AquaPEX"TUBING TO BE SUPPORTED PER NFPA 13D AND MANUFACTURER'S RECOMMENDATIONS. 2-#10 x 1 1/2" l 111 Recommended Tubing Length Between r'^ a'u d o" a c:- Full Course (- } Fitting Size Minimum Len th Uninsulated Heat Ducts 18" 9" G"5 v6'o z n. s m a o z x 12. MINIMUM SPACING BETWEEN SPRINKLERS IS 8'-0" REFER TO SPACING CHARTS FOR MAXIMUM SPACING Thread Strews 7 I Tubing g z F-x 2 o d o H BETWEEN SPRINKLERS AND FROM WALLS.SPRINKLER HEAD MANUFACTURERS MAY HAVE MORE In Top Holes t, 11_I/ (_J Uninsulated Hot Water Pipes 12" 6" 8 F 6 m 2 5 c a E 3/8"ProPEX Fitting 2" a 8 3 8 8 Z u a 2 2 RESTRICTIVE SPACING LIMITATIONS. _ Side of Hot Air Diffuser 24" 12" o a ❑m c- °�.f. m 1/2"ProPEX Fitting 2" 36" 18" 5 W mom-f 0, S'.C S m \. - _• \ Front of Hot Air Diffuser 13. SPRINKLERS ARE NOT NECESSARILY CENTERED IN ROOMS DUE TO UGKi FIXTURES OR OTHER CEILING 3/4"ProPEX Fitting6" 3" ad c 5 , o f°�o y w a h MOUNTED OBSTRUCTIONS. ' - Y 3" Hot Water Heater o=o y m'O m'o v,u m o Lead-FrI d s . .:-.�r r l ; 1"ProPEX Fitting3 1/2" Furnace 6" 3" r w o y >'�'>< 14. THE PLUMBING TIE IN CONNECTIONS ARE SCHEMATIC IN NATURE AND CAN BE INSTALLED OFF THE Concealed Sen]u \ Concealed Fla[ c p -a x m u z ". Sprinkler Head 50W-250W Light Fixture 6" 3" >�+ €v,o z B m SPRINKLER LOOP ANYWHERE BETWEEN SPRINKLER TO SPRINKLER CONNECTION. Cover Plate 1 1/4"ProPEX Fitting 4 1/2" 9 2"'^ ° o°� a 250W-499W Light Fixture 12" 6" y= t=3 n w l o o i^ � 15. THIS SUGGESTED LAYOUT IS BASED UPON INFORMATION PROVIDED BY OTHERS. CHANGES IN u},i 3 o ow v,.,,a w CONSTRUCTION OR FIELD CONDITIONS MAY OCCUR WHICH MAY REQUIRE CHANGES TO THE LAYOUT. IT IS \ h`�'Rz 9 ti o`�`a Exposed Installation Requirements. in' THE RESPONSIBILITY Of THE INSTALLER TO NOTIFY UPONOR TECHNICAL SERVICES OF SUCH CHANGES. Uponor AquaPEX tubing(white)and ProPEXT^EP Fittings and ProPEX'" I 16. NFPA 13D 8.2.5.OBSTRUCTIONS TO RESIDENTIAL SPRINKLERS Brass Fittings are approved for exposed installation where the following • 8.2.5.7. SHADOW AREAS SHALL BE PERMITTED IN THE PROTECTION AREA OF A SPRINKLER AS LONG AS conditions are met.(UL 1821 Approvetl) THE CUMULATIVE DRY AREAS DO NOT EXCEED 15 FT.PER SPRINKLER. c rl �/p p am • 8.2.5.8 SMALL AREAS CREATED BY ARCHITECTURAL FEATURES,SUCH AS PLANTER BOX WINDOWS,BAY Exposed Wood Joist Ceiling Assemblies. o n ��/ o I here by certify that this plan,specification, WINDOWS,AND SIMILAR FEATURES,SHALL BE EVALUATED AS FOLLOWS: 1. Joists are of dimensional lumber,engineered wood or wood I-joist. `� II or report was prepared by me or under my (1)WHERE NO ADDITIONAL FLOOR AREA IS CREATED BY THE ARCHITECTURAL FEATURE,NO 2. Joist are of depths from 6-16 inches(152-204 min). /////��I m direct supervision and that I am NICET ADDITIONAL SPRINKLER PROTECTION IS REQUIRED. 3. Joist are of spacing from 12-24 inches(305-610 min)on center. U Certified. (2)WHERE ADDITIONAL FLOOR AREA IS CREATED BY AN ARCHITECTURAL FEATURE,NO ADDITIONAL 4. Joists can be exposed after installation. t7❑ SPRINKLER PROTECTION IS REQUIRED,PROVIDED ALL OF THE FOLLOWING CONDITIONS ARE MET; 5. Metal pipe hangers spaced at maximum 24 inches(610 min)on center \ i (a)THE FLOOR AREA SHALL NOT EXCEED 18 FT.(1.7 M°) are used. 1.55" 1.66" Tim W McDonald Date: (b)THE FLOOR AREA SHALL NOT BE GREATER THAN 24 INCHES IN DEPTH AT THE DEEPEST POINT OF 6. Listed residential automatic sprinklers of maximum activation THE ARCHITECTURAL FEATURE TO THE PLANE OF THE PRIMARY WALL WHERE MEASURED temperature rating of 155AF(680C). Z"-ir,Hanger 1" Hanger NICET Certification No.150393 ALONG THE FINISHED FLOOR. Water-Based Systems Layout-Level III A (c)THE FLOOR SHALL NOT BE GREATER THAN 9FT IN LENGTH WHERE MEASURED ALONG THE Certification Expires:June 1,2022 m PLANE OF THE PRIMARY WALL. Metal TubingSupport. Tubing Support Spacing: (d)MEASURED FROM THE DEEPEST POINT OF THE ARCHITECTURAL FEATURE TO THE SPRINKLER PP (Anchor AquaPEX Tubing Tubing Securely Enough to Support the Tubing,Yet Relaxed `o SHALL NOT EXCEED THE MAXIMUM LISTED SPACING OF THE SPRINKLER. 1. Metal tubing supports designed mfoa plastic tubing shallp ct used. Enough to Allow the to Expand and Contract) (3)THE HYDRAULIC DESIGN SHALL NOT BE REQUIRED TO CONSIDER THE AREA CREATED BY THE 2. Do not use supports that will damage the tubing.Inspect metal ARCHITECTURAL FEATURE. supports for sharp edges. 1. Along Horizontal Runs,Install Supports Every 32",if Horizontal Runs are 3. Do not rigidly anchor Uponor AquaPEX'"tubing with supports.Allow Continuously Supported,Place Tubing Supports at Six-Foot Intervals. LLJ il 17. NFPA 13D 8.3 LOCATION OF SPRINKLERS. enough tubing for freedom of movement to expand and contract. 2. Along Vertical Runs,Install Supports Every Four to Five Feet,at Each Floor • 8.3.1 SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE OMISSION IS PERMITTED BY 8.3.2 Mid-story Guide. U 2 oor an at a v THROUGH 8.3.8. / m 8.3.2 SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF 55 FT°(5.1 M°)AND LESS In-line Flow Test C`I u,w w • 8.3.3 SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES CLOSETS,LINEN CLOSETS,AND PANTRIES THAT The In-line Flow Test can be constructed on site. It performs a flow test to .0. MEET ALL OF THE FOLLOWING CONDITIONS: High Upstream Pressure ensure proper system operation and flow(see Figure F001-II). L.L. _ (1)THE AREA OF THE SPACE DOES NOT EXCEED 24 FT.(2.2 M°). p p pressurereducing valve may z z^ If the upstream pressure exceeds 80 psi aequir pre V (2)THE WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE ti 'n.a o i needce lytr ge Bless of sSt ea jurisdictions may require a pressure reducing >,.�e m MATERIALS AS DEFINED IN NFPA 220,STANDARD ON TYPES OF BUILDING CONSTRUCTION. �¢ valve regardless of upstream pressure. Tubing AquaPEX ¢ld ` • S.MI SPRINKLERS SHALL NOT BE REQUIRED IN GARAGES,OPEN ATTACHED PORCHES,CARPORTS,AND Tubing Z/% LIJ ry o • SIMILAR STRUCTURES o • 8.3.5 SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT STORAGE,PENTHOUSE % w cEQUIPMENT ROOMS,ELEVATOR MACHINE ROOMS,CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND O e CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT,FLOOR/CEILING SPACES,ELEVATOR SHAFTS, z o CRAWL SPACES,AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING j Ii II / 0 y a F aj e PURPOSES. ! j % z u u a m • 8.3.5.1 SUCH SPACES THAT CONTAIN FUEL-FIRED EQUIPMENT SHALL ALSO COMPLY WITH 8.3.5.1.1 OR !-- ----- ---:_ -- `-' a z G¢O , m 8.3.5.1.2. _'III-. �� /1 .Ok. oOo °xmor - • 8.3.5.1.1 WHERE THE FUEL-FIRED EQUIPMENT IS ABOVE ALL OF THE OCCUPIED AREAS OF THE DWELLING Male Threaded Coupling iW ProPEX Fire y I v u a a`A zp O " UNIT,NO SPRINKLER PROTECTIONQ SHALL BE REQUIRED IN THE CONCEALED SPACE. _DJI Sprinkler Adapter > �/ N. ut u • 8.3.5.1.2 WHERE FUEL-FIRED EQUIPMENT IS BELOW OR ON THE SAME LEVEL AS OCCUPIED AREAS OF THE j 'a DWELLING UNIT,AT LEAST ONE QUICKRESPONSE INTERMEDIATE TEMPERATURE SPRINKLER SHALL BE 11 W T K o' INSTALLED ABOVE THEE EQUIPMENT OR AT THE WALL SEPARATING THE SPACE WITH THE FUEL-FIRED Male Threaded Coupling 1"Bail Valve V r Q �� To Hot Water Heater ,r.r m EQUIPMENT FROM THE OCCUPIED SPACE. • Female Threaded Ce v ��// 8.3.6 SPRINKLERS SHALL NOT BE REQUIRED IN UNHEATED ENCLOSURES AT THE BUILDING AT L,L O • - _ Tee with Water 0 o c ENTRANCES/EXITS AS LONG AS THE DWELLING UNIT HAS ANOTHER ENTRANCE/EXIT. _ w I ®' i Gauge j Pressure ¢ 8.3.7 SPRINKLERS SHALL NOT BE REQUIRED FOR CEILING POCKETS THAT MEET THE FOLLOWING « SprinklerO z i- E a • = Pressure Gauge Orifice (Optional) 1 o O O CONDITIONS: Ti rn' it 11 (1)THE TOTAL VOLUME OF ALL UNPROTECTED CEILING POCKETS IN A COMPARTMENT DOES NOT EXCEED fi S < } I 8 z m a r. w 100 FT.(2.83 Ma). E 2 \ W (2)THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING POCKET IS PROTECTED BY THE SPRINKLERS I. Flow Test O m z: o AT THE LOWER CEILING ELEVATION. tt n ,...,,,°. To ensure the system provides enough water for proper fire sprinkler omi m or'i:.. mLL c (3)*THE INTERIOR FINISH OF THE UNPROTECTED CEILING POCKET EXCLUDING DECORATIVE a performance,you should conduct a flow verification test. .. - o LL Uponor Warning Signs �rt £ > t= o TREATMENTSNOT E NONCOMBUSTIBLE O LIMITED-COMBUSTIBLE RMITE MATERIAL.O HAVE L I' Note: The NFPA 13D Installation Standard does not require flow N V o m 0 C g LL o (4)SKYLIGHTS NOT EXCEEDING 32 FT.(2.97 M° SHALL BE PERMITTED TO A PLASTIC COVER. � I • ) verification. F..I z w G w 8.3.8 SPRINKLERS SHALL NOT BE REQUIRED IN CLOSETS IN GARAGES AND EXTERIOR CLOSETS .I, i I 1 I^ o x S g m (REGARDLESS OF SIZE)LOCATED ON EXTERIOR BALCONIES,EXTERIOR BREEZEWAYS/CORRIDORS,OR _ a -- Pressure Reducing LLJ y' 3 w" ¢Before performing a Flow verification test,confirm the water pressures by o qa i=i=� ACCESSED FROM OUTDOORS WHERE THE CLOSET DOES NOT HAVE DOORS OR UNPROTECTED z Valve contacting the Water and Sewer Department of your local city. Ensure the 5 0 u d z PENETRATIONS DIRECTLY INTO THE DWELUNG UNIT. • _ available water pressure matches the pressure used in the system design. I" • 8.3.9 SPRINKLERS SHALL BE INSTALLED IN ANY CLOSET USED FOR HEATING AND/OR AIR-CONDITIONING SHEET DESCRIPTION o EQUIPMENT,WASHERS AND/OR DRYERS,OR WATER HEATERS EXCEPT AS ALLOWED BY 8.3.8. ` I Note:The sprinkler plan indicates the most hydraulically remote sprinkler < LO Main Fire Sprinkler your(or pair of klers). For test requirements on other sprinklers,consult GENERAL NOTES&DETAILS ate, 18. INSULATION GUIDE LINES PER NFPA 13D. 9.1.1°WET PIPE SYSTEMS. A WET PIPE SYSTEM SHALL BE PERMITTED TO BE TO BE USED WHERE ALL Shut-off Valve local code. Note: It is a good idea to notifythe fire inspector at least 24 hours prior to PIPING IS INSTALLED IN AREAS NOT SUBJECT TO FREEZING,INCLUDING AREAS PROPERLY INSULATED TO 9 P MAINTAIN 40oF. performing a flow verification test.This may speed up the Inspection •• A.9.1.1 IN AREAS SUBJECT TO FREEZING,CARE SHOULD BE TAKEN IN UNHEATED ATTIC SPACES TO process and eliminate the need to repeat[he test for the inspector. SHEET NUMBER no COVER SPRINKLER PIPING COMPLETELY WITH INSULATION. INSTALLATION SHOULD FOLLOW THE Note: See"AquaSAFE Flow Test Instruction Sheet"(Provided in GUIDELINES OF THE INSULATION MANUFACTURER.FIGURE A.9.1.1(A)THROUGH FIGURE A.9.1.1(F) ' Contractors Documents package or online at www.Uponorpro.com)for i SHOW SEVERAL METHODS THAT CAN BE CONSIDERED. THESE ARE FOR ILLUSTRATIVE PURPOSES ONLY. --- more information on Flow Test Setup,Assembly,Performing the Test and U CONSULTATION WITH THE GENERAL CONTRACTOR AND/OR OWNER IS RECOMMENDED TO ENSURE r PROPER METHODS AND MATERIALS ARE USED TO MAKE SURE 45°F WILL BE MAINTAINED. I Troubleshooting. If there are any questions please contact Uponor. e psi © UPONOR - CONFIDENTIAL FO 0 1 Fg PRV Set Pressure I- 1