Loading...
Plans (5) Markup Legend SPRINKLER SYMBOL DEFINITION COLOR/LINETYPE LEGEND '' S / \ / \ SENJU Model RC-RES Residential Flat Concealed Pendent SS8464 BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). ‘imt f o Delete Line / \`/ v \ TT.), 0 - - - 11 K=4.9,162F°,7/16"Orifice,Maximum Spacing 16'x16' GREEN LINES=INTERLEVEL CONNECTIONS/SUPPLY. w u MAXIMUM SPACING(TYP) RC-RES-16 Sprinkler head demand: 13 gpm @ 7.04 BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. O a z = 1/2"PIPE SIZE s,2 2 Add Line SPRINKLER MODEL(TYP) w HEAD SYMBOL(TYP) SENJU Model RC-RES Residential Flat Concealed Pendent SS8464 — — =3/4"PIPE SIZE a °u 0 - - - 2 K=4.9,162F°,7/16"Orifice,Maximum Spacing 18'x18' —— ¢m w Add Tee = 1"PIPE SIZE .: u 1 RC-RES-18 Sprinkler head demand: 17 gpm @ 12 O = 1-1/4"PIPE SIZE W iwLL w o 0 Add Elbow L. - - SENJU Model RC-RES205 Residential Flat Concealed Pendent SS8464 fCis u z g l 0 - 1 K=4.9,205E°,7/16"Orifice,Maximum Spacing 14'x14' 1°' Add Coupling I I RC-RES-14-205 Sprinkler head demand: 13 gpm @ 7.04 �v9 o3 ,,m; SENJU Model RC-RES205 Residential Flat Concealed Pendent SS8464 W 9 w RECEIVED °�~ Add Head 1- -- 3- - - 1K=4.9,205E°,7/16"Orifice,Maximum Spacing 16'x16' + I RC-RES-16-205 Sprinkler head demand: 14 gpm @ 8.2 2 o= Delete Head 3-JXXX�XXX q 4z:-�M� �_` 2 1st Floor 1�'�t�(1 A 7 7.7 _ o m t- I 4 2nd Floor •„(�1 (C .i .�w a 00 o 2gy Move Head 6 4th Floor 'Zorin°ovr O O v,VZCa�-.- Uponor15 TOTAL CITY OF TIGARD yLLxF=r�v.=� Note:All revisions must be reviewed by a;r F o Table F002-1 ^_oo v>o � 3nyi BUILDING DIVISION �o'2a ,� Multipurpose Fire Safety Systems Z o s<-? a`o The Uponor Residential Fire Safety System is a residential fire protections Z c z o z A C1.1 system installed in combination with the cold side of the domestic potable , - t >,.o<-a 8¢ water system. Only licensed contractors trained by Uponor can install this i y.........` �:,� ! ,_ 1 I - o a a w� AM system. / 4 \T, i.-9' 4.,,. f 3 d`� Q '- c`Z 7,0, ,,o 3 z C f J f Fo What to do if Changes are Required Dec( O I 1 d q1 {� ° - a a m E If any features or obstructions require the addition or deletion of sprinkler i I �. ,Patio. H z a .c z° o v heads,or significant relocation of sprinkler heads,contact the Uponor Design ! ®1 i 6 I it 4-64-0 SIP 'I '8 a z o 8 6 c.'., Department to determine if observed changes require a redesign _a_.b I 5-0#O Si _, I l i^;-,-,4 _ _ �.� Srn ctZ f _, ¢ c i_ , 4;z t d (888.594.7726). r- C 1I _, I 1 rasD o o r MOST HYDRAULICALLY REMOTE HEADS El y-1 _ !� 79 10, � ` irk a > < i i ow� _ + ' ! --1-1t w CIF I i °z 5 �x z d o h �1 _ _ ,v f r !1"AQUAPEX INTERLEVEL ryo s o o y _ HEAD# GPM PRESSURE REQ'D AT STREET -- I CONNECTIONS FROM FIRST m / c o a g m o c»,c W. 4.1 HEAD H.4 17 54.2 /' 6 r- -; i {FLOOR TO SECOND FLOOR `O _Ls 1 / _, G a V a o m 2 HEAD H.3&H.2 26.2556 73.33 ' i 1 fJ' a' Esr3w 1"z 1'AQUAPEX INTERLEVEL �i{�-fteh fl" ( Kit hen e a c; C CONNECTIONS FROM .{• •] I I tr R• >: - ( T o o z SECOND FLOOR TO THIRD \ 21 -�.! � i 4-� -_ 3'6 �� I t �i 1 ( Fv,h �d a �.z c z`a w FLOOR �� \ -�- _ {� / • I { •�t ' ►,? 17 -18 IVI.�.�. I 7l uai \\ \\ ! I : it t..-� 5SHELV Il �/LI, / ♦ . I i +N SU lte / + \ i i 16FT= ' .� F'S 7I 2-4 �� bl t sIM T.58 ��ze \ _ l t•- ''',an it *G 1:' 1418.. Q " NT.60 T.5, g I here by certify that this plan,specification, }\ - Q 1l. 412. D3 Bath TT��'� [ or report was prepared by me or under my CITY OF TIGARD \\ N L C! 11 I $t ' +g/ i direct supervision and that 1 am NICET K i0�, a •E U�T+ON tr",Lt Certified. A [] �/ �r7�� 1T aaa...rrr... .5 --A. I+ I SYSTEM\ I = 1-1/4"AQUAPEX TO pproved [xl \\ v TS TYP ��-+ *' I°s4�f 1( F.6 x3A`SHOWER j lr 5 SYSTEM Contitionally Approved [ , i RAU10' - i1 kii �F, r TOWEL ! ( Tim W McDonald Dale: 5 7• Q If RING { _ L S•P1D Fr N fi t ( NICET Certification No.150393 \ \T.43 /'� • ' - L Water-Based 5 stems Layout-Level III For only the work a s described i n: i \ I P P'I Il 7uy I ♦ �'„ •' r t � S S.1 MAIN SHUTOFF Certification Expires:June 1,2022 to PERMIT NO 1ngrooPo oa 3 3s" {F 12 F.3F.10 F 1 I11; ,13p�U� j � �J VALVE LOCATION , BtNG i 9 5• N 7 .. r, o`(i 8,D" F ! wAl u ER ?' I "1 --- I f M See Letter to: Follow [ ) 1 q _ - ti _ _ �— { 2 8 2 SULA Att ,f t; I ] 1 147T.48' 4�f 1: t •• � 15.' 1i AM sIM � � for i m i U " W Job Address: 13 0 ao so, I c,'°o•J P t i SEE sHT.UT ' - - I i .t•- j WOOD TREAD.MAX / , t : I r ~ IM' Q FOR STAIR +—y r 44 a RISER 8'(ADD OR L. //: ' (,F f �By" / `?1 >. , DETAT`52 ' 4, I4' ( [ REMOVE STEPS AS 3 5 tf8}''E_ .33'-- ce V r N `�J• L Date i✓ _ U �-r— REQUIRED PER SITE H'-"{SEE z`O o • y. ! ® 5 ? L I t FOB z n I tb- `i ,/ { CONDITION) I) + r t I' DET j" a o _ '" t /�✓,Y' f MAX 2 TREADS { t 1 LL.. J a a jI `°Na igli aill. Wil a CIcg CI v ��N �c�«—, r\ J ? ®SIM.1 Car t w y c 1-1/4"AQUAPEX { u. / LC*WALL AT { ( ? + Garage '� - WM ■a ) " CURRENT STATIC i 1/4"AQUAPEX RISER FLFv=ioa TO SYSTEM 1 o f ( INSULATE {39N0BsZ " \,jlIIZI g , rv' o L ._� WALL FINISH 3'a`G.W.B. a Lt FLOOR OVER CEILING FINISH is I a ( TYPE'X`G.W.B_ .- RAC u a a o w r UNHEA7Ep ! ! / V WATER PRESSURE IN I Z STATIC: 95 si PRESSURE GAUGE I SPACE ` s_- -. �� WRAP AMS E OW /� • h SYS O O O o a o_ z O P it_ TO HOT WATER { \`----_---- SYS-1,M.._. + p(•RE I 1 +Rff) I ' ' Fz O vl 1 1/4"PRV CASH ACME HEATER \ ri •\`�41x wrw(OR EQUIVALENT) LIVII1g y-�F•a3 �� �'� ' CE:.7iG LEVEL I lir (�" 4 6PSI LOSS FLOWING 26 GPM 'RCitEJ-16 ii 1\; +NSUtATFLOOR ABOVE j� I� • 1. LL ^ 0. w w 80ps RES 16oRaELa I \ _. / 2 fic T.5511 2 ®® I F--1 Li rn PRV Set Pressure I. �l 9 T-'_ I �\ B-0 7,Sit]ND 1'-JO' 3'-113�4' S }6yGT-SY- ? lJ O 1'WATER METER _ __ I _ i' l L INSULATE II \� * 11 0 O o NFPA 13D STANDARD LOSS -- -_ 7 +f(OOR OVER I I . -_---, ' - i S 3PSI LOSS FLOWING 26GPM Ec .�� 1 7`. 8 WALLA VE \ !JhHEATEO / Ili /' Porch '`?I o p~O n II - - p4 Ba L� SPACE 3 1 , n x m un SHUT OFF VALVE 1 =iy y',((� i-` ��1 b! ;o i-> "' CURB STOP - S.1 -.L-_ I L•'::}.LL'h--� •..•..••• C `C, t- \ -_. _..___ _FLOOR ABOVE_m_.. .__._ __ ( " �'-u�'h. t 7fi S III 5-0g051 m ut 1PSI LOSS UI P E \ 3/4"AQUAPEX INTERLEVEL m . O O m K m In.+°'. STREET - 1 ROOF h _ tt CONNECTIONS FROM FIRST � �•. 1 - r W '1 FLOOR TO SECOND FLOORS _— ?m m w 112, STTOPO1PSt LOSS .�TION I llir MI6, -an l Milll U 3 y s s a o CORPdouw�a °z L — (� -eII!• MTR 100'OF ( 2 \ SECOND FLOOR �\ FIRST FLOOR M IN R ® 3•� FLFv-95 i i/a"AQUAPEX SHEET DESCRIPTION FLEV 95' = 1 n F100 FIRST FLOOR AND 1"COPPER-K F� / �/A 11 �O / i,/^11 y I-OII / `t1 r f 1 SECOND FLOOR SHEET NUMBER (1003 WATER SERVICE DETAIL 5 B 5 15 ill 5 NTS 4 D © UPONOR - CONFIDENTIAL F100 „„___ _________. _ Markup Legend SPRINKLER SYMBOL DEFINITION %COLOR/LINETYPE LEGEND 1 Delete Line OO XXX-XX BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). o GREEN LINES=INTERLEVEL CONNECTIONS/SUPPLY, BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. o MAXIMUM SPACING(TYP) = 1/2"PIPE SIZE a o Add Line SPRINKLER MODEL(TYP) J,'S-O HEAD SYMBOL(TYP) —•— =3/4"PIPE SIZE a. Add Tee ` I I CO` .. = 1"PIPE SIZE N n uI = 1-1/4"PIPE SIZE Add Elbow H • W y.�n Nj J w z za W tiw3 Add Coupling ' I 2•4 N o N W Q W Add Head -,e--@--A.3` 0 ITi-iu Delete Head -(X)- of z YLLi I-wi XI --8 o y�', zx3r y` Move Head -O�`O- mod, „veztm;B3 ',a QOUYp� ¢''6V OS524 Gv' Note:All revisions must be reviewed by Uponor Iw-°' w I^ a., o Table F002-3 W! zoos Q dee°za�rcc.,, Si Multipurpose Fire Safety Systems 0 0 a 0 F N 5 a 5 C The Uponor Residential Fire Safety System is a residential fire protections x z E p 0 a a 0 o m y G system installed in combination with the cold side of the domestic potable W m g �'5 F�,a a water system. Only licensed contractors trained by Uponor can install thisEliq F z E7a0',,; system. 5`..6 F4 ';',4 What to do if Changes are Required W ca��au.1W`v Ji Ns If any features or obstructions require the addition or deletion of sprinkler YA x v,0`o 2 o i 0 e u' v C''2, '3ao"So heads,or significant relocation of sprinkler heads,contact the Uponor Design 0 z r u,I Z 3 a x x" Department to determine if observed changes require a redesign z z 0- w o p d_o r (888.594.7726). `"°oC�d awl ftln 1 i } -k .- 7041,x0x ) gz'g;W ao�"� � Cz II I d., ` I 'B��zyy0 °Oro _... _.. �. . I. ._..._._.. EG iEtS II I o S s m� U a u y... 1 YYYS i I I 2t7D , 6'LL '� os � it I J OTYP. u E�i u z t! 12"COLD WATERA UAPEX \ °i� __ __ I .,,,, z'ao 0057 w 11C)- i t INTERLEVEL CONNECTION ll I 0 0 Q 6,9 4 �Q Q w 340 Q AT 1 � 5.6 5L i i / FROM THIRD FLOOR TO ATTIC I ilk / -' -_____.--�_a� 2 NIN. I ,.,,r , - , f..... / X 1 q pF :7 I l� ,i 'n ANCE,� EGRESS BELOW a'i I Maste 1 t 8 °'( °ss — I / Bedroom / P :80711 V / I H1- ;I \ X— I here by certify that this plan,specification, 22x30 ' (j1'TT I /K y�� y'R"'+"'ES...- a+ 'a_ IAlk or report was prepared by me or under my P ATTIC 8 „; i , direct supervision and that I am NICET D RMER HATCH-ACCESS . / 1 N 1 4- I . Certified. ( } �� AL -:CKNESS I" • R ( I / z as1 %CA { L ! I ,2A, '4 'R•,. , _ Tim W McDonald Date: m L • \-� It 555fF •% I 1 NICET Certification No.150393 / _ �i i ! ' ( o' Water-Based Systems Layout-Level III 2 T.16 �2 © 28'ra 49 v ,4� , 1 Certification Expires:lune 1,2022 O D4 f e iiiii iisi t ,: � I� M,Bat'� � li z fI !Wig] 1"AQUAPEX INTERLEVEL i t!!1: V TFRHIRD �?% `C=% •�I m. W` - ' 1 - ; SEE Shf(U2 1 Ie 1 /FOR STTA•— roI ;; , °iARLs\ ' ,' \1' m r i,i I F->,5•19►��•_21isiimi 4-205 1 Ce d / �t F • ,i l k, ' 3�� Bats{!,�,e It -�- ,, L.G. m , I l W wnu nr__ 't 1 ES- • 11! i{I "I 45 FT'Tow t o R - E - 6 < m N o II Dt39`ABOVE / 1 •� I ..a 0 ~ F NOSING -�'_Si L, �1,1 )'. i' 5�!)8& 1■ i 0�, LLJ ® \ LOW WALL S - � 1��j/I e SHOWER is! 1 t�. _ I 'Q' +39'•F.F.— T t li e. __. 2Sx30 tcNlC CONNECTIONS FROM THIRD v r 548 PASS '$ `` "' in LE- V V a ut ACCESS HATCH,— S O \ Q / ( _ - 4 r '5' `'\ 5-b fs• ASS 1 (f•� r a o V 1"A UAPEX INTERLEVEL ' T O G Oa �tC RES 16 I 1 `_ 5!M FLOOR TO ATTIC 1 i T' L d- O O J o o O (ATTIC) I ' 8 RADON i ` iHIC Ess IF:., © \ a ,n 24$f AT o4 REDUCTION; �` ,-r r� ; / C N Y1a' 30"M,N. fATTTCS SYSTEM j e I 5�.. � tf}I ,q CLEAlROANCE �, / I i H- T.5}g./ 3.,y t IJI;S�B `I 3.,318• �� r'� CA g ACCESS Q 1 = f� ` RC-RES-16 a Ik\ a V PER R80„ -_ TYP® I ( RC RES 16 I 0 % 0 EGRESS DORMER 1 5 I ' IA1 �I 4 i ABedroom 2 / Di Bedroom 3 Q o 0 o E O s-v 1-0 s I I 7 vF i �1 — -�� -j Q � z>2°, w f5wE', O EGRESS — 1 o o m `o I d' Qw t /QQ/rr'�� '� ti.q •* "- � . 5....... T IC EGRESS • {- N V f =z 5-0 U5L I m,Qs=LL L' ROOF LOW I 5-0 1-0 SL W I--I z z H 5 F __ I V) wow g_ F�a _. I C / 2 ATTIC PLAN 1 THIRD FL THIRD FLLOOROORA ANNDD OOR SHHD 101 ) F101 ATTIC PLAN _/ 1/4„ = 1 -0„ 1/4 = 1 -0„ SHEET NUMBER 5 0 5 15 7 1111111111111 © UPONOR - CONFIDENTIAL F101 F ,...,�'^^xs0^ "-"__,.s�W _.._ „. ,,• ,.. .,.----- ______ , 0.,,0_.o...000,..._.____ - ..._. A Markup Legend SPRINKLER SYMBOL DEFINITION COLOR/LINETYPE LEGEND 1.15-1 %NsiI BLUE LINES=FEED TO FIXTURES(BATH,SHOWER,ETC.). f o Delete Line f/^\\\/� XXX-XX GREEN LINES=INTERLEVEL CONNECTIONS/SUPPLY. w Q BLACK LINES=SPRINKLER HEAD TO SPRINKLER HEAD. CO J MAXIMUM SPACING(TYP) =1/2"PIPE SIZE !:!Add Line — — — — — SPRINKLER MODEL(TYP) fHEAD SYMBOL(TYP) ��'. =3/4"PIPE SIZE OuAdd Tee III =1"PIPE SIZEO v Immo = 1-1/4"PIPE SIZE W 3'w o Add Elbow ` V v w z °za Add Coupling I I = =allo •., N; � O, Add Head - 1 C'a~W; I Delete Head a Move Head - - -6�VFY Naz.cozyy i.'y'. o pa04tp Note:All revisions must be reviewed by Uponor O �Fx0§=FFF'cx U o S, o �' u „8g, °,204, Table F002-1 demo oyz o r_rg ooz0`� a`rn � Multipurpose Fire Safety Systems zg�o� a g c �=o The Uponor Residential Fire Safety System is a residential fire protections 5 6 a o o p 1,1 y i system installed in combination with the cold side of the domestic potable >w B ; a S'"'•;a W 1,14 z B! water system. Only licensed contractors trained by Uponor can install this 1"AQUAPEX INTERLEVEL Z =z �^H% i°g�g� system. CONNECTIONS FROM ` 1"AQUAPEX INTERLEVEL wiQ z F z z z m a S 3'^ SECOND FLOOR TO THIRD \ CONNECTIONS FROM FIRST J cai h°o F rc 3 f i w o What to do If Changes are Required 4 FLOOR % FLOOR TO SECOND FLOOR \ V 'a C3 m a, %h: i, \ y Wy fc aui.� If any features or obstructions require the addition or deletion of sprinkler \ 41 a w°o y u a 2 m y heads,or significant relocation of sprinkler heads,contact the Uponor Design / \\ - I ..+.7 m i m o i B°z=uui Department to determine if observed changes require a redesign \% /( \ . ! - ' z o c o �'U • {{ F (888.594.7726)• \\ .. , Deck i 1 0 I� ® , ?a w ? g t y c g c i o t-ea"h X0X �� ri- )1 \ ii /f i s4 St Patio atiy c°mC�,">u' a -,,,,..,= --'rtxl=' ---" \\ I 5-04C SL ^ t SFTn,22 ' z a'g o zo vW`i m vS 1/2"COLD WATER AQUAPE( 1 EGP SS L •• , I I -- o y o z m w o" o INTERLEVEL CONNECTION. ' i \\ (' -•••••••,••.••••• -•.1..... - ? - ',.��ma ''w z y t Np D2 / FROM THIRD FLOOR TO ATR \ € I yb t a Ji:hJiI 0 I / \ \� iI \ I B = �1 77 999 DI Ht ( 4 . / � __ a w- EGRESS I 30'MN \ , n I I Master/�i / ROOFLI' AV (� ti T �I i A� II I Q F CLEARAt. I S: BELOW - I A05 1 Bedr m 1 \ I V© I„ i i \t �. \ K'tchenate oM 4 ilak I PER R80 \ ` \ H.4/ / .-.--I 1.__._-"4t'' • ,� 2 I n'! R�1• -tfiBr R 8 ( ATTIC `ti' \A 4. - 3' RE 1 i �9� \ I �� r� ' - I 05I I1 \ ,ite r,I ll9NAN j (ATTIC) 2200 • , _ ..... +1`_ I ' -? .•-� / \t S�SNE,YES i �� RJR L 1-1/4"AQUAPEX TO I I \ Suite f� I her report was by certify prepared this bY me or specification, my ACCESS ''� f / or I k HATCH EF r}•WALL ICK ES• -- I6 i-- I I sHCW direct supervision and that I am NICET y1 1 �l j I _T 58 <T.56 ME Certified. l .✓ H'1 ROOF 7 r ti - SH ER 1 — Si _ I .5.7 D I ._.� i1M',,� BEIOW C �_�• ' ^�� • 2X34 ." ' �I` + - SYSTEM i T Bdth c D3 d _ e, r97 i so `s..��� -- ............ I I .I �. TKif. i II \� � .. wl N _ Tim W McDonald Date: 1 STEM I I j A . / ( [ G {..{ • �., `��x- • ____ - 1 T� p SYSTEM r 40 FT'�� NICET Certification No.150393 ® 12 T.16 1 (4`F-T'- il� J. MAIN SHUTOFF �I r +�� 72 i I \ 1" , 7 I t I - Water-Based Systems Layout-Level III '� _ ftt !!� ( ' �y� jMillr" I VALVE LOCATIONITS "f f < 60°x34•SHO F•6 Certification Expires:June 1,2022 ^ :`�� A / 1 ' I T,2"I iilFrl �Q hze•r3�4 TOWEL rI. 2`- ,+ 1 . �.u'�-- TYP. ,f y � o . ACC SS/ - I RING \ \M I _ ,�,,, i II . I I ®„I • n a II o T.4 i , L. M T.21 4 f k b [e .c190 a n I u • MEN� jl l a 1 F.11 ring ,12 rs —� •� W T.20, f_.%1 _tr r m i I WALLF fl" D j to 2 y °i 8 5 3y 9 2 - _-,{ __. -_- _. a .- - -_ �� t 4 8'-" _ m UNDEAF rn (Ir r ( .. SEES T.UI T,18 l —. �_ I I`- ` i_ \ 1 n _ -'�'t w i. - - 1 RWAY i ,l _ -"EOR TAM !, iic/1 lr 4 4 ` 1• .N= _ 1 . ` r--r/Fh - _ f v FU /I -T -.I ,t :%, -DETAILS .�� I � r r e Iir 41c ' i g ,nBath ; 3a + 0T.49T.48T," 'i a 51_.� W o �`j� o. 1 I (/F RC S 1" 0 T 5 i - T`23 =E16��Lo Au T o �(lYll�eti `, 4.�, 4s F /1! T.51 It}�r, ti �T:l LI ' { -v- `,may .y �:� i I I l I I 1 I! Q= 1 \ y \ !I / -_-N6 tNG, / I t I r �.7� �_-.1 ..,I {; 1 - SH;tTt2� :., III .T, ! WOOD TREAD,MAX- a u�i ` I {I 1 •5 TUB& a I I "`4• ii FOR STAIR I 1 H RISER 8°(ADD OR a t7 m n o '' ?(( 1 LOW WW I .t R i ) �" SHOWER 1 ,� 3_• I' v ,. I T 1 EA1fS / ',--3 I .3 l'. T'l t7 9 4 REMOVE STEPSAS W i.'' f -. `i AT r3 - �® I i �`i .mom -- \(1 1P fir , 1•JL _ I yI ®I{ REQUIRED PER SITE _� t ' I s"-X C [ ONDITION \.- Q 1 u k � I I i II + L MAX z TREADS g 5 ('I_ mint F I i LL ' I I 1-- CCA 3 SS ACTCH I !t ��}' _\-- �-� 6 -- i - z i v a m iv b I i I .!//��a ml S D B PASS _ ?: If YI , Cd{'IM y G 0 Ism 5fM. ) RC-RES-16�} 1"A UAPE%INTERLEVEL , Q- ASS-.-.. •' " 39:Ail T• Di 11 _ _ ! ce Q i i i~O w iwrl M RADON-- {ATTIC) Q n 4 t i 45� ! 4 1-Z(NE55 S-- a` I 1 I 1 Gariige I/� O O o a n ai REDUCTION .. ( 34 5 N , ONNECTIONS FROM THIRF.1 I S i , " �,y i I t--,_,jNOSlMG I INSULATE WALL FINISH)§'G W B y, p O V� FLOOR TO ATTIC !!! _ U (ATTIC) t \, I A FLOOR OVER ' ( I ` CE:UNG FlNISH ya' - > ui I Ji "• -Ya \3,S - \\ UNHEATED / \ Y TYPE X"G W.B ^ w a 6 C f NO Ce; 3-3fg 4 3 9 C.p } 5 H.9 9 x \ i:'ACE i g '1 . HRETAPE ALLE W13 11 T Q /Y h S STEM \' 16 WRAP BEAM58ELOW w v 1 -YP NO RC-RES-16 • -� RC-RES-16 r 94 �" \ 0 =,/ II ..... " C (,r) ` -- PER R807.i 1 , 'pi living CEILING LEVEL - DORMER - NSUL0.TE FLOOR ABOVE EGRESS I Bedroom 3 (5`i\Bedroom 2 / -- �i I( \ Q O s —i G— — 1 O1 .t RG 16 RC RE /1._ �r=, _ o 2� a g c S 6 O SL - - -,/ T 5 2-6 F �� L t„1_ 0 ri n, _--- i _� /. i I• \� 3/Q�AQUAPEX INTERLEV S I 1 Az I ei WNW Di 1 o O / 1 EGRESS O/ CONNECTIONS FROM FIRS i 4 ' �vl 8-0;a SOHO �- Q Y iA R BELO { 1 WS,IATE FL R TO SECOND FLOOR r- k - f y I FLOOR OVER; `\ i',i ( m 1=m ui n m t \ UNHEATED i I O WAIABOVE (ihlr I Porch I m "' "" EGRESS lI I i SPACE _. ATJP _ ,� I i O•p Lhhh. 3-e tD Sl '." fi I `---_ _�_ _\ , I < m .. =w w " i 5-d 5L ROOF'BELOW i 1 a.t.. I 4 FLOOR ABOVE £ m _w o i r-_1 I. . �1;•s 1 1 — itlV � � 'mwF= I I I 5.0{OA ( 7-05-p%OX ry r r . z I i f i I� G3w 5_< n -,n✓- I ',.. rsY-• ...,. 1 1 n 6 f YID ® '1 1 p o z d o u g v 4 ATTIC PLAN 3 THIRD FLOOR 2 SECOND FLOOR 1 FIRST FLOOR IT SHEETDESDPLANON MIRRORED PLAN ALL FLOORS F102 1/4" = 11_O11 F10/ 1/4" = 1t_Ott \.102 1/41t = 11_O11 1o2 1/4" = 1 -0 t tt SHEET NUMBER 5 D 5 15 mmm!�U z4"=1-0 F© UPONOR - CONFIDENTIAL • ITM Senju RC-RES:Open Web Truss/TJI Construction Insulation Recommendations See General Notes 8.2.5.8 for Architectural ATM GENERAL NOTES: In areas subject to freezing,care should be taken In unheated attic spaces n ProPEX LF Brass Fire to cover Uponor AquaPEX tubing completely with Insulation. Insulation Feature Requirements u+ Sprinkler Adapter Tee should follow the guidelines of the insulation manufacturer. See Uponor z 1. THIS SYSTEM IS DESIGNED AS PER NFPA 13D 2019 EDITION AS A RESIDENTIAL MULTIPURPOSE SYSTEM Fire Sprinkler Adapter - - T f 8 SECTION 3.3.12.3. Blocking Maybe __ Document"Uponor AquaSAFE Attic Insulation Guidli s package for attic /' O Required.If n -Puss-on Nut installation guidelines(Provided in Contractors Documents package or online -3////// w 2. UPONOR COMPANY RESERVES THE EXCLUSIVE RIGHTS TO ALL DETAILS AND DRAWINGS AS SHOWN ON Blocking is Used, - 1 I/q"Min. at vnvw.Uponorpro.com). i [ 2.1 z THIS SHEET. THESE DETAILS AND DRAWINGS ARE PROPRIETARY INFORMATION OF UPONOR COMPANY AND Use The 2 Top I 1 "Max. a Screw Holes. ■ ■ Planter Box Window,Bay Window or Similar Feature. f UNAUTHORIZED USE MAY BE SUBJECT TO PROSECUTION TO THE FULL EXTENT OF THE LAW. i I I 4 Bottom of mounting Extreme Temperature Installations y C 6'" o `-L f' racket to Face of Truss If no additinal floor area Is created No Additional Sprinkler is Required. ^C�u AquaSAFE Residential Fire Safety systems are often installed in attics or ¢rn ut 3. THE DESIGN OF THIS SYSTEM IS DICTATED BY SPECIFIC CEILING HEIGHTS AND ROOM SIZES, IT IS THE Fire Sprinkler Adallte W other areas exposed to temperature extremes of heat and/or cold. Follow 8'- O RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE CONDITIONS SHOWN ON THESE p p 0"or less �+ry u Mounting Bracket the recommended extreme weather installation instructions to isolate and / w rn> PLANS ARE EXACTLY AS THEY EXIST IN THE FIELD. DEVIATIONS FROM THE DESIGN MAY CAUSE THE I ���� I w;a. O SYSTEM TO BE UNABLE TO CONTROL A FIRE.IF THE BUILDING CONSTRUCTION DIFFERS FROM THE FIRE protect system components from extreme temperatures. Because this or less 6 V w en.. SPRINKLER PLAN,CONTACT THE SYSTEM DESIGNER IMMEDIATELY. 3-610 x 1 1/2" 1111 IIMIIMiwIn_ system also delivers domestic cold water directly to plumbing fixtures, 9'-0"or less ® 5,01`,n z d Full Course - Uponor highly recommends that you protect the tubing with adequate / �' _ m m n 4. THIS SYSTEM AND THE ACCOMPANYING HYDRAULIC CALCULATIONS ARE DESIGNED IN COMPLIANCE WITH insulation in warm weather areas to minimize heating of the cold water wt m o w 3 Thread Screws E IMF NFPA 13D 2019 EDITION. In Bottom Holes , Supply' o'� e w 3 N W 5. "STAND-ALONE"OR"MULTIPURPOSE,WET PIPE"SYSTEMS ARE PERMITTED TO ONLY USE ANTI-FREEZE - Installation methods include,but are not limited to: n o °O m m m'ngg S LISTED FOR USE IN NEW SPRINKLER SYSTEMS. _ • Tenting over the fire sprinkler piping. O'^t-w 3 Lead-FreQ Flat • Additional layers of batt insulation. If additional floor area is created.Cannot exceed 18 ft2,be more than 2'-0" a 6. MODIFICATIONS ARE PROHIBITED.SPRINKLERS THAT HAVE BEEN PAINTED,CAULKED,MODIFIED OR Concealed Senju Concealed Flat • Increased depth of blown-in insulation. deep,more than 9'-0"wide and be with In the coverage area of the a - o u, Sprinkler Head Cover Plate sprinkler.No Additional Sprinkler is Required. z 5 i 4 o DAMAGED MUST BE REPLACED. �a 7. A SINGLE CONTROL VALVE ARRANGED TO SHUT OFF BOTH THE DOMESTIC SYSTEM AND THE SPRINKLER Caution: If you will be installing spray foam insulation,make sure to g i. Y.°6 a o I"- SYSTEM SHALL BE INSTALLED. Senju RC-RES:Traditional Wood Framing Construction Protect all components during application.Consult with the spray foam '� s p r °'y m c w manufacturer to ensure compatibility with all products before application. NFPA 130 Table 7.5.6.3 Distances From d N< >. ii z } Heat Sources ' z°eow�Eu� 8. OWNERS MANUAL MUST BE PROVIDED TO THE OWNER. m m o[?i,g 1 i t-`^rc m, Consultation with local building officials is encouraged to ensure compliance r a F4°�r o 9. AT THE MAIN SHUT OFF VALVE,A TAG OR A SIGN STATING THE FOLLOWING IS REQUIRED;"WARNING:THE ProPEX LF Brass Fire with local building codes. c<�m F u o 3-] OrdinaryIntermediate S D N W V 5 a WATER SYSTEM FOR THIS HOME SUPPLIES FIRE SPRINKLERS THAT REQUIRE CERTAIN FLOWS AND Sprinkler Adapter Tee Fire Sprinkler Adapter o p i P P Neat Source Temp. Temp. d s a - 7d _ PRESSURES TO FIGHT A FIRE.DEVICES THAT RESTRICT THE FLOW OR DECREASE THE PRESSURE OR i. G Push-on Nut 133°-170° 175•-224• z o 9yB m�' �'(=''�z z AUTOMATICALLY SHUT OFF THE WATER TO THE FIRE SPRINKLER SYSTEM,SUCH AS WATER SOFTENERS, QQ °'2 a ❑ a g FILTRATION SYSTEMS AND AUTOMATIC SHUT OFF VALVES,SHALL NOT BE ADDED TO THIS SYSTEM r Bending PEX Tubing Side of Fireplace 36" 12" g'�p o°51°o rc WITHOUT REVIEW OF THE FIRE SPRINKLER SYSTEM BY A FIRE PROTECTION SPECIALIST.DO NOT REMOVE 1 1 K.Min. The minimum bend radius of Uponor PEX tubing in any direction Is six times Front of Fireplace 60" 36" W m p m 0,a,6"'". THIS SIGN". - 1 'Max. the outside diameter(6 x OD). °.. a 5 i Fire Sprin<ler Adapter .. Bottom<f mounting Bend supports are available for 3/8",1/2",3/4"and 1"Uponor AquaPEX Wood Buminq Stove 42" 12" w a c i i v,g H a 9 y 10. ALL INTERIOR PIPING TO BE UPONOR"AquaPEX®"UNLESS NOTED. Mounting Bracket `__' Bracket m'ace of Truss tubing to facilitate 90-degree rigid bends. Kitchen Range 18" 9" g i a C p z w q 2-610 x 1 1/2" �¢ O Recommended TubingLength Between Fittings HotWalAir Oven 18" 9" LJ g a 2 0 a m w a s 11. UPONOR"AquaPEX"TUBING TO BE SUPPORTED PER NFPA 13D AND MANUFACTURER'S RECOMMENDATIONS. Ul z.u a a,1 .,n• 9 9 Hot Flues 18" 9" °rc y ..'" Full Course a i 12. MINIMUM SPACING BETWEEN SPRINKLERS IS 8'-0" REFER TO SPACING CHARTS FOR MAXIMUM SPACING Thread Sc rews } Fitting Size Minimum Tubing Length Uninsulated Heat Ducts 18" 9" 0 m i 1 a i F o = 'l-� l,-d �r sr-F aoa Io us BETWEEN SPRINKLERS AND FROM WALLS.SPRINKLER HEAD MANUFACTURERS MAY HAVE MORE In Top Holes tJ iL_!g f-J 3/8"ProPEX Fitting 2" Uninsulated Hot Water Pipes 12" 6" �y r 6 pz J RESTRICTIVE SPACING LIMITATIONS. ��7 Side of Hot Air Diffuser 24" 12" o n y °o i a o,g c in c 1/2"ProPEX Fitting 2^ qW - \ Front of Hot Air Diffuser 36" 18" '°� F S o 5-a 13. SPRINKLERS ARE NOT NECESSARILY CENTERED IN ROOMS DUE TO LIGHT FIXTURES OR OTHER CEILING ������o��- e a a` i Y1 ° MOUNTED OBSTRUCTIONS. .-ern 3/4"ProPEX Fitting 3" Hot Water Heater 6" 3° `m' o v`°d u`i Lead-Free-Flat. .c,0 n 8.. y i n r C Concealer Sen]u 'r" " } 1"ProPEX Fitting 3 1/2" Furnace 6" 3" O o m 4 8 a i-5.2 14. THE PLUMBING TIE IN CONNECTIONS ARE SCHEMATIC IN NATURE AND CAN BE INSTALLED OFF THE Concealed Fla[ W m a x ^°�z.. SPRINKLER LOOP ANYWHERE BETWEEN SPRINKLER TO SPRINKLER CONNECTION. Sprinkler Head Cover Plate 1 1/4"ProPEX Fitting 4 1/2" SOW-250W Light Fixture 6" 3" w °u v, °o m m •.. - 250W-499W Light Fixture 12" 6" _u F f 3 F„',m g r,x _ 1 15. THIS SUGGESTED LAYOUT IS BASED UPON INFORMATION PROVIDED BY OTHERS. CHANGES IN aa i 5'z 6 c X am O S i i CONSTRUCTION OR FIELD CONDITIONS MAY OCCUR WHICH MAY REQUIRE CHANGES TO THE LAYOUT. IT IS F h y F z2 u b`�F ii a w Exposed Installation Requirements. \ in THE RESPONSIBILITY OF THE INSTALLER TO NOTIFY UPONOR TECHNICAL SERVICES OF SUCH CHANGES. Uponor AquaPEX'"tubing(white)and ProPEX'"[EP Fittings and ProPEXTm I 16. NFPA 13D 8.2.5*OBSTRUCTIONS TO RESIDENTIAL SPRINKLERS Brass Fittings are approved for exposed installation where the following • 8.2.5.7* SHADOW AREAS SHALL BE PERMITTED IN THE PROTECTION AREA OF A SPRINKLER AS LONG AS conditions are met(UL 1821 Approved) THE CUMULATIVE DRY AREAS DO NOT EXCEED 15 FT.PER SPRINKLER. ft17 • 8.2.5.8 SMALL AREAS CREATED BY ARCHITECTURAL FEATURES,SUCH AS PLANTER BOX WINDOWS,BAY Exposed Wood Joist Ceiling Assemblies. N I here by certify that this plan,specification, WINDOWS,AND SIMILAR FEATURES,SHALL BE EVALUATED AS FOLLOWS: 1. Joists are of dimensional lumber,engineered wood or wood I-joist. 'x el ar report was prepared by me or under my (1)WHERE NO ADDITIONAL FLOOR AREA IS CREATED BY THE ARCHITECTURAL FEATURE,NO 2. Joist are of depths from 6-16 inches(152-204 min). direct supervision and that I am NICET ADDITIONAL SPRINKLER PROTECTION IS REQUIRED. 3. Joist are of spacin from 12-24 Inches 305-610 ming . )on center. Certified. (2)WHERE ADDITIONAL FLOOR AREA IS CREATED BY AN ARCHITECTURAL FEATURE,NO ADDITIONAL 4. Joists can be exposed after installation, � SPRINKLER PROTECTION IS REQUIRED,PROVIDED ALL OF THE FOLLOWING CONDITIONS ARE MET; 5. Metal pipe hangers spaced at maximum 24 inches(610 mm)on center (a)THE FLOOR AREA SHALL NOT EXCEED 18 FTa(1.7 M2) are used. 1.55" , 1.66" (b)THE FLOOR AREA SHALL NOT BE GREATER THAN 24 INCHES IN DEPTH AT THE DEEPEST POINT OF 6. Listed residential automatic sprinklers of maximum activation Tim W McDonald Date: THE ARCHITECTURAL FEATURE TO THE PLANE OF THE PRIMARY WALL WHERE MEASURED temperature rating of 155°F(68°C). zn -4"Hanger 1"Hanger NICET Certification No.150393 ALONG THE FINISHED FLOOR. Water-Based Systems Layout-Level III m (c)THE FLOOR SHALL NOT BE GREATER THAN 9FT IN LENGTH WHERE MEASURED ALONG THE PLANE OF THE PRIMARY WALL. Tubing Support Spacing: Certification Expires:June 1,2022 (d)MEASURED FROM THE DEEPEST POINT OF THE ARCHITECTURAL FEATURE TO THE SPRINKLER Metal Tubing Support. (Anchor AquaPEX Tubing Securely Enough to Support the Tubing,Yet Relaxes I. Metal tubing supports designed for plastic tubing shall be used. Enough to Allow the Tubingto Expand and Contract SHALL NOT EXCEED THE MAXIMUM LISTED SPACING OF THE SPRINKLER. 9 P ) 2. (3)THE HYDRAULIC DESIGN SHALL NOT BE REQUIRED TO CONSIDER THE AREA CREATED BY THE Do not use supports that will damage the tubing.Inspect metal ARCHITECTURAL FEATURE. supports for sharp edges. 1. Along Horizontal Runs,Install Supports Every 32",if Horizontal Runs are 3. Do not rigidly anchor Uponor AquaPEXT.tubing with supports.Allow Continuously Supported,Place Tubing Supports at Six-Foot Intervals. LLJ v�i 17. NFPA 13D 8.3 LOCATION OF SPRINKLERS. enough tubing for freedom of movement to expand and contract. 2. Along Vertical Runs,Install Supports Every Four to Five Feet,at Each o • 8.3.1 SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE OMISSION IS PERMITTED BY 8.3.2 Floor and at a Mid-story Guide. iS z v • THROUGH 8.3.8. • 8.3.2 SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF 55 FT°(5.1 Ma)AND LESS In-line Flow Test Q 5 w n • 8.3.3 SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES CLOSETS,LINEN CLOSETS,AND PANTRIES THAT The In-line Flow Test can be constructed on site. It performs a flow test to o'^ MEET ALL OF THE FOLLOWING CONDITIONS: High Upstream Pressure ensure proper system operation and flow(see Figure F001-8). ce u=e q (1)THE AREA OF THE SPACE DOES NOT EXCEED 24 FT°(2.2 Ma). p pressure exceeds 80 psi a pressure reducing valve may z z n n n ' If the upstream (2)THE WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE ¢ need to be installed. Some jurisdictions may require a pressure reducing ss S S m MATERIALS AS DEFINED IN NFPA 220,STANDARD ON TYPES OF BUILDING CONSTRUCTION. ce +¢o N\ ` • 8.3.4* SPRINKLERS SHALL NOT BE REQUIRED IN GARAGES,OPEN ATTACHED PORCHES,CARPORTS,AND valve regardless of upstream pressure. Uponor AquaPEX - a t9 m ry o.+ • SIMILAR STRUCTURES Tubing / LLI of • 8.3.5 SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT STORAGE,PENTHOUSE w EQUIPMENT ROOMS,ELEVATOR MACHINE ROOMS,CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND % f CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT,FLOOR/CEILING SPACES,ELEVATOR SHAFTS, " / w z CRAWL SPACES,AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING . � O o / r z o I M M!... �l j LL z�'6zoriir E "` PURPOSES. W C Co $o� o,, <, -" • 8.3.5.1 SUCH SPACES THAT CONTAIN FUEL-FIRED EQUIPMENT SHALL ALSO COMPLY WITH 8.3.5.1.1 OR _ � n8.3.5.1.2. o J=m N II N • 8.3.5.1.1 WHERE THE FUEL-FIRED EQUIPMENT IS ABOVE ALL OF THE OCCUPIED AREAS OF THE DWELLING Male Threaded Couplingow ProPEX Fire Ce 1- CO u ¢a N z0 p UNIT,NO SPRINKLER PROTECTION SHALL BE REQUIRED IN THE CONCEALED SPACE. _g�. Sprinkler Adapter N m u • 8.3.5.1.2 WHERE FUEL-FIRED EQUIPMENT IS BELOW OR ON THE SAME LEVEL AS OCCUPIED AREAS OF THE a DWELLING UNIT,AT LEAST ONE QUICKRESPONSE INTERMEDIATE TEMPERATURE SPRINKLER SHALL BE - 1"Ball Valve i`I in c INSTALLED ABOVE THE EQUIPMENT OR AT THE WALL SEPARATING THE SPACE WITH THE FUEL-FIRED --_r. To Hot Water Heater Male Threaded Coupling - 01 m EQUIPMENT FROM THE OCCUPIED SPACE. ir Female Threaded �-+ 0 • 8.3.6 SPRINKLERS SHALL NOT BE REQUIRED IN UNHEATED ENCLOSURES AT THE BUILDING AT = Tee with Water O 0 ENTRANCES/EXITS AS LONG AS THE DWELLING UNIT HAS ANOTHER ENTRANCE/EXIT. E I r ' Pressure Gauge• O ¢ 0 • 8.3.7 SPRINKLERS SHALL NOT BE REQUIRED FOR CEILING POCKETS THAT MEET THE FOLLOWING N a el Pressure Gauge Sprinkler Orifice (Optional) H LL o o C C ii CONDITIONS: (1)THE TOTAL VOLUME OF ALL UNPROTECTED CEILING POCKETS IN A COMPARTMENT DOES NOT EXCEED 1- Q o Y m a w 100 FTs(2.83 Ma). E " I Flow Test ` x "m'" (2)THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING POCKET IS PROTECTED BY THE SPRINKLERS c O 50 w-ti To ensure the system provides enough water for proper fire sprinkler O m r m ut AT THE LOWER CEILING ELEVATION. performance,you should conduct a flow verification test. �{ F (3)*THE INTERIOR FINISH OF THE UNPROTECTED CEILING POCKET EXCLUDING DECORATIVE _ Uponor Warning Signs �l m w F TREATMENTS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIAL. 0 I' Note: The NFPA 13D Installation Standard does not require flow ( i f r1 a c z=w ¢O (4)SKYLIGHTS NOT EXCEEDING 32 FT°(2.97 Ma)SHALL BE PERMITTED TO HAVE A PLASTIC COVER. - verification. , V \.J m p F,$LL • 8.3.8 SPRINKLERS SHALL NOT BE REQUIRED IN CLOSETS IN GARAGES AND EXTERIOR CLOSETS F-i z K 22 (REGARDLESS OF SIZE)LOCATED ON EXTERIOR BALCONIES,EXTERIOR BREEZEWAYS/CORRIDORS,OR i -- Pressure Reducing W 3 w ie _ Before performing aa flow verification test,confirm the water pressures by F O Valve G ACCESSED FROM OUTDOORS WHERE THE CLOSET DOES NOT HAVE DOORS OR UNPROTECTED z ©,' contacting the Water and Sewer Department of your local city. Ensure the a p d z Li PENETRATIONS DIRECTLY INTO THE DWELLING UNIT. _ available water pressure matches the pressure used in the system design. 8.3.9 SPRINKLERS SHALL BE INSTALLED IN ANY CLOSET USED FOR HEATING AND/OR AIR-CONDITIONING SHEET DESCRIPTION L= EQUIPMENT,WASHERS AND/OR DRYERS,OR WATER HEATERS EXCEPT AS ALLOWED BY 8.3.8. - ,I Note: The sprinkler plan indicates the most hydraulically remote sprinkler 41 - (or pair of sprinklers). For test requirements on other sprinklers,consult GENERAL NOTES&DETAILS Main FireSprinkler 18. INSULATION GUIDE LINES PER NFPA 13D. ¢ � Shut-off Valve Your local code. o: e • 9.1.1*WET PIPE SYSTEMS. A WET PIPE SYSTEM SHALL BE PERMITTED TO BE TO BE USED WHERE ALL PIPING IS INSTALLED IN AREAS NOT SUBJECT TO FREEZING,INCLUDING AREAS PROPERLY INSULATED TO Note: It is a good idea to notify the fire inspector at least 24 hours prior to MAINTAIN 40°F. process inn a flow verification test.This may speed up the inspection •• A.9.1.1 IN AREAS SUBJECT TO FREEZING,CARE SHOULD BE TAKEN IN UNHEATED ATTIC SPACES TO process and eliminate the need to repeat the test for the inspector. SHEET NUMBER COVER SPRINKLER PIPING COMPLETELY WITH INSULATION. INSTALLATION SHOULD FOLLOW THE Note: See"AquaSAFE Flow Test Instruction Sheet"(Provided in '� GUIDELINES OF THE INSULATION MANUFACTURER.FIGURE A.9.1.1(A)THROUGH FIGURE A.9.1.1(F) Contractors Documents package or online at www.Uponorpro.eom)for 5 f SHOW SEVERAL METHODS THAT CAN BE CONSIDERED. THESE ARE FOR ILLUSTRATIVE PURPOSES ONLY. I --- - - --� more information on Flow Test Setup,Assembly,Performing the Test and u CONSULTATION WITH THE GENERAL CONTRACTOR AND/OR OWNER IS RECOMMENDED TO ENSURE L PROPER METHODS AND MATERIALS ARE USED TO MAKE SURE 40°F WILL BE MAINTAINED. Troubleshooting. If there are any questions please contact Uponor. o psi © UPONOR - CONFIDENTIAL FO 0 1 PRV Set Pressure F