Report (2) Date r n " D as5� `
02/24/2021 OFFICE COPY RECE
Project Name
Templeton Pre K Johnson •+.
p MAY � � zoz�
Project Number Controls
MM10082002 CITY OF TIGARD
Client/Purchaser BUILDING DIVISION
Submittal Summary Page
Qty Tag# Model# Description
2 RTU-7, 8 ZJ120N24R4B5ECA3A2 10 Ton, Single Packaged R-410A Air Conditioner, High Efficiency,
Two Stage Cooling, 12.0 EER, 240 MBH Input Aluminized Steel,
Two Stage Gas Heat, 460-3-60
• Dry Bulb Low Leak Economizer w/Barometric Relief and Hoods
(Bottom or Horizontal End Return Only)with Economizer Fault
Detection & Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,
California Title 24, AMCA 511).
•3 HP High Static Belt Drive Blower
•4" Pleated Filters (MERV 13)
• IntelliSpeed control of the VFD based on stages of cooling
(Provides Single Zone VAV Fan Operation as defined by ASHRAE
90.1 section 6.4.3.10)
• Smart Equipment Controller including Discharge Air, Return Air,
and Outdoor Air Temperature Sensors. BACNet MS/TP, Modbus and
N2 Communication Card.
• Non-Powered Convenience Outlet
• HACR Circuit Breaker/Disconnect
• Return Air Smoke Detector(Bottom return only)
• Micro-Channel "all-aluminum"condenser coil, Copper
tube/aluminum fin evaporator coil
y • Composite Drain Pan- Front Connection
2 RTU-7, 8 S1-A52 Belt for 8.5 and 10 Ton High Static Field Installed Drive
2PE04704746 Power Exhaust 460V without Baro Relief
2 RTU-7, 8 1 RC0471 Roof Curb- 14" High, Flat, Uninsulated, Full Perimeter(Shipped
Knocked Down)
Equipment start-up and commissioning by a factory trained technician is recommended.
Contact your supplying distributor or sales representative for additional information &guidance.
ZEWARNING:Cancer and Reproductive Harm-www.P65Warnings.ca.gov
Information is subject to change without notice.Check local codes. Printed 02/24/2021
� York® Sun TM Pro 3-12.5 Ton Page:
,., YORK® Package
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Cooling Performance
Total gross capacity 132.9 MBH t j
Sensible gross capacity 97.4 MBH • I, '
Total net capacity 122.2 MBH <'i j I'
Sensible net capacity 86.7 MBH
Efficiency(at ARI) 12.00 EER
Integrated eff.(at ARI) 14.60 IEER ( :, r
Ambient DB temp. 91.2 °F
Entering DB temp. 80.0 °F 1 ) •
Entering WB temp. 67.0 °F
Leaving DB temp. 57.5 °F t
Leaving WB temp. 56.4 °F -,
Power input(w/o blower) 8.66 kW
Sound power 83 dB(A)
Refrigerant
Refrigerant type R-410A
Sys1 7 lbs 12 oz
Sys2 7 lbs 10 oz
Gas Heating Performance 10 Ton
Entering DB temp. 60 °F • York Sun Pro units are manufactured at an ISO 9001 registered facility and
Heating output capacity(Max) 192 MBH each rooftop is completely computer-run tested prior to shipment.
Supply air 4000 CFM Unit Features
Heating input capacity(Max) 240 MBH
Leaving DB temp. 104.4 °F • Two Stage Cooling
Air temp.rise 44.4 °F • 240 MBH Input Aluminized Steel,Two Stage Gas Heat
SSE 80.0 % • Full perimeter base rails with built in rigging capabilities
Stages 2 • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours
Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards)
Supply air 4000 CFM • Scroll Compressor[s]
Ext.static pressure 1.0 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Hoods(Bottom or
Addl.Unit Losses(Options/Accessories) 0.9 IWG Horizontal End Return Only)with Economizer Fault Detection&Diagnostic
Blower speed 1340 RPM (Meets ASHRAE 90.1-2013, IECC 2015,Califomia Title 24,AMCA 511).
Max BHP of Motor(including service factor) 3.45 HP • Slide-out Blower/3 HP Belt Drive Motor Assembly
Duct location Bottom
Motor rating 3.00 HP • Unit Ships with 4"Pleated Filters(MERV 13)
Actual required BHP 3.37 HP • Solid Core Liquid Line Filter Driers
Power input 3.14 kW • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters.
Elevation 108 ft. • Non-Powered Convenience Outlet
Drive type BELT • Short Circuit Current:5kA RMS Symmetrical
Requires field supplied drive true • Through-the-Curb and Through-the-Base Utility Connections
Electrical Data • Single Point Power Connection
Power supply 460-3-60 • HACR Circuit Breaker/Disconnect
Unit min circuit ampacity 24.3 Amps • Retum Air Smoke Detector
Unit max over-current protection 30 Amps • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin
Dimensions&Weight evaporator coil
Hgt 51 in. Len 89 in. Wth 59 in. • Composite Drain Pan-Front Connection
Weight with factory installed options 1275 lbs. • Tool-free maintenance with features like hinged doors for all-access panels,
Clearances slide-out blower and blower motor tray
Right 12 in. Front 36 in. Rear 36 in. BAS Controller
Top 72 in. Bottom 0 in. Left 36 in. • IntelliSpeed control of the VFD based on stages of cooling.Provides Single
Note: Please refer to the tech guide for listed maximum static pressures Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10.
(— \) • Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Aslijoffl CERTIFIED,. ur
'nunv3 Sir . •---- ! Air Temperature Sensors.BACNet MS/TP,Modbus and N2 communication
US .,°..w^,, card.
Standard Unit Controller: Smart Equipment Control Board
• Safety Monitoring-Monitors the High and Low-Pressure Switches,the
Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Failures,Safety Lockouts and Repeated Limit Switch Trips.
Warranty
• One(1)Year Limited Warranty on the Complete Unit
• Five(5)Year Warranty-Compressors and Electric Heater Elements
• Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger
Information is subject to change without notice.Check local codes. Printed 02/24/2021
n York® SunTM Pro 3-12.5 Ton Page:4
YORK® Package
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#: RTU-7,8 System: ZJ120N24R4B5ECA3A2
Factory Installed Options
ZJ120N24R4B5ECA3A2
Equipment Options Option(s) Selected
Single Packaged R-410A Air Conditioner, High
Product Category: ZJ Efficiency
12.0 EER
10 Ton
Nominal Cooling Capacity: 120
Two Stage Cooling
Heat Type and Nominal Heat Capacity: N24 240 MBH Input Aluminized Steel,Two Stage Gas Heat
3 HP High Static Belt Drive Blower
IntelliSpeed control of the VFD based on stages of
Blower Option: R
cooling(Provides Single Zone VAV Fan Operation as
defined by ASHRAE 90.1 section 6.4.3.10)
Voltage: 4 460-3-60
Dry Bulb Low Leak Economizer w/Barometric Relief and
Hoods(Bottom or Horizontal End Return Only)with
Outside Air Option: B Economizer Fault Detection &Diagnostic(Meets
ASHRAE 90.1-2013, IECC 2015, California Title 24,
AMCA 511).
Non-Powered Convenience Outlet
z Service Options: 5 ,,.
Zbi ' ¢!.. . , ,,... ,. ..,s� .'."`"" HACR Circuit Breaker/Disconnect
Sensor Options: E
Return Air Smoke Detector(Bottom return only)
Micro-Channel"all-aluminum"condenser coil, Copper
Refrigeration: A
tube/aluminum fin evaporator coil
4"Pleated Filters (MERV 13)
Smart Equipment Controller including Discharge Air,
Additional Options: 3 Return Air, and Outdoor Air Temperature Sensors.
BACNet MS/TP, Modbus and N2 Communication Card.
Cabinet Options: A Composite Drain Pan-Front Connection
Product Generation: 2
Field Installed Accessories
O 1BD0408 - Burglar Bars (32.0 Ibs) 0 1 CV0412 -Concentric 0 1CV0426- Concentric
O 1 CG0420-Coil Guard (27.0 Ibs) Diffuser,Side Discharge,20RD Diffuser,Specialty,24X24
O 1CV0403 - Concentric 0 1CV0413 - Concentric 0 1FE0412 - Flue Exhaust
Diffuser,Flush Mount,20RD Diffuser,Side Discharge,18X28 Extension Kit(14.0 Ibs)
O 1CV0404 - Concentric 0 1CV0414 - Concentric 0 1FF0414- 2" Only Metal Filter
Diffuser,Flush Mount,18X28 Diffuser,Side Discharge,18X32 Frame Kit (16.0 Ibs)
O 1CV0405- Concentric 0 1CV0420 -Concentric
Diffuser,Flush Mount,18X32 Diffuser,Specialty,24X24
Information is subject to change without notice.Check local codes. Printed 02/24/2021
York® Sun TM Pro 3-12.5 Ton Page:
., 5
YO R K Package .
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
O 1GP0405- Gas Piping Kit for 0 S1-03102529000- Non- 0 S1-NSB8BHN043-0-Wall
Bottom Gas Supply Connection Networking Wall Sensor-Allows Temperature and 3% Relative
with External Shut-Off(includes: remote sensing and control from Humidity Combined Sensor, No
Internal gas pipe, fittings, gas cock single or multiple zones. (0.2 Ibs) Display, BLACK, NO JCI LOGO,
& panel gaskets) (10.0 Ibs) 0 S1-03102529004 - Non- NS8000 Series (0.4 Ibs)
O 1HA0442 - High Altitude Kit for Networking Wall Sensor with 0 S1-NSB8BHN141-0-Wall
Natural Gas (1.0 Ibs) Over-ride button-Allows remote Temperature and 3% Relative
O 1 HA0443 - High Altitude Kit for sensing and control from single or Humidity Combined Sensor,
Propane (1.0 Ibs) multiple zones. Override allows Warmer/Cooler Display, WHITE,
O 1 HG0411 - Hail Guard Kit- setpoint to be overridden for 2 NO JCI LOGO, NS8000 Series
Diamond Pattern (37.0 Ibs) hour time period. (0.2 Ibs) (0.4 Ibs)
O 1HG0432- Hail Guard Kit- 0 S1-03102529006- Non- 0 S1-NSB8BHN143-0-Wall
Provent Style (25.0 Ibs) Networking Wall Sensor with Temperature and 3% Relative
O 1NP0459 - Natural Gas to Setpoint Adjustment and Over-ride Humidity Combined Sensor,
Propane Conversion Kit(2-Stage) Button-Allows remote sensing Warmer/Cooler Display, BLACK,
(2.0 Ibs) and control from single or multiple NO JCI LOGO, NS8000 Series
O 1 RC0470- Roof Curb-8" High, zones. Allows setpoint to be (0.4 Ibs)
Flat, Uninsulated, Full Perimeter adjusted ± 5° F. Override allows 0 S1-NSB8BHN240-0-Wall
(Shipped Knocked Down) (135.0 setpoint to be overridden for 2 Temperature and 3% Relative
Ibs) hour time period. (0.2 Ibs) Humidity Combined Sensor, Full
•_1RC0471 Roof Curb 14" High, 0 S1-ADDWIRE -Add-a-Wire allows Display, WHITE, JCI LOGO,
Flat, Uninsulated, Full Pcrimctcr 5-wire thermostats to use only 4 NS8000 Series (0.4 Ibs)
wires. (0.3 Ibs) 0 S1-NSB8BHN241-0-Wall
Ibs) 0 S1-CTSDTS-CTS Wired Temperature and 3% Relative
O 1 RC0472- Roof Curb, Transition- Temperature Sensor for Humidity Combined Sensor, Full
Sunline 7.5T thru 12.5T to Pro thermostat I Duct*Also works for Display, WHITE, NO JCI LOGO,
3.0T thru 12.5T(Shipped LX Series (0.3 Ibs) NS8000 Series (0.4 Ibs)
Assembled) (200.0 Ibs) 0 S1-CTSHTS- CTS Hardwired 0 S1-NSB8BHN243-0 -Wall
O 1 RC0476- Roof Curb-24" High, Temperature Sensor for CTS Temperature and 3% Relative
Flat, Uninsulated, Full Perimeter Thermostats*Works with LX Humidity Combined Sensor, Full
(Shipped Knocked Down) (135.0 series as well (0.2 Ibs) Display, BLACK, NO JCI LOGO,
Ibs) 0 S1-CTSPLATE-Wall Plate for NS8000 Series (0.4 Ibs)
O 1WC0412 -Wooden Crate (445.0 CTS Thermostats*Also works for 0 S1-NSB8BPN240-0 -Wall
Ibs) new platform LX series models Temperature and 2% Relative
O 2AP0402 -Air Proving Switch (1.0 below(0.0 Ibs) Humidity Combined Sensor, Full
Ibs) 0 S1-CTSWFTS-CTS Temperature Display, WHITE, JCI LOGO,
O 2AQ04700524- CO2 Space Sensor with WiFi for CTS NS8000 Series (0.4 Ibs)
Sensor-Wall Mount Accessory Thermostats*Also works with LX 0 S1-NSB8BPN241-0 -Wall
(5.0 Ibs) Series (0.1 Ibs) Temperature and 2% Relative
O 2AQ04700624-CO2 Unit Mount 0 S1-LXLOCK-Locking Ring For Humidity Combined Sensor, Full
Accessory(4.6 Ibs) LX-Series Thermostats (0.4 Ibs) Display, WHITE, NO JCI LOGO,
O 2EC0401 - Kit, Single Enthalpy 0 S1-LXPLATE-Wall Plate For LX- NS8000 Series (0.4 Ibs)
Field Installed (1.0 Ibs) Series Thermostats(0.0 Ibs) 0 S1-NSB8BPN243-0-Wall
O 2EC0402- Kit, Dual Enthalpy 0 S1-LXWFM - For LX Series Temperature and 2% Relative
Field Installed (Includes two Thermostats-WiFi Humidity Combined Sensor, Full
humidity sensors) (1.0 Ibs) Communication (1.0 Ibs) Display, BLACK, NO JCI LOGO,
O 2LA04702412- Low Ambient Kit 0 S1-MP-PRTKIT-OP- MAP NS8000 Series(0.4 Ibs)
(2.2 Ibs) (Multiple Access Portal) Gateway 0 S1-NSB8BTN041-0-Wall
• 2PE04704746- Power Exhaust Kit- Replacement MAP gateway Temperature Sensor, No Display,
460V without Baro Relief protective case, lanyard and WHITE, NO JCI LOGO, NS8000
Downflow or Horizontal (19.0 Ibs) communication cable. Use only to Series (0.4 Ibs)
O 2SD04700824-Smoke Detector replace worn or damaged 0 S1-NSB8BTN043-0 -Wall
Kit w/Mounting Hardware for components. (0.3 Ibs) Temperature Sensor, No Display,
Supply Air(Horizontal/Downflow) 0 S1-NSB8BHN041-0 -Wall BLACK, NO JCI LOGO, NS8000
Only (9.4 Ibs) Temperature and 3% Relative Series (0.4 Ibs)
• S1-02815208000- Blower Sheave Humidity Combined Sensor, No
for 8.5 and 10 Ton High Static Display, WHITE, NO JCI LOGO,
Field Installed Drive (2.8 Ibs) NS8000 Series (0.4 Ibs)
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Vbir±>« #Jffe sf.0 I{JJn:ddw N rlJaiu.tfd/.'JlJshu/1M#ifiYllY' w VyuKglNy kNJ)JN 3iJYbrdeer atsaldi.,r .r r>.r.,r.a:,,.r...
York® Sun TM Pro 3-12.5 Ton Page:6
yoRK® Package
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#: RTU-7,8 System: ZJ120N24R4B5ECA3A2
O S1-NSB8BTN141-0-Wall 0 S1-TEC3022-14-000- 7 DAY 0 S1-TEC3612-14-000-7 DAY
Temperature Sensor, PROGRAMMABLE PROGRAMMABLE
Warmer/Cooler Display, WHITE, THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
NO JCI LOGO, NS8000 Series WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
(0.4 Ibs) FCUNAV, 0-10VDC PROP, FCUNAV, ON/OFF OR
O S1-NSB8BTN143-0-Wall DEHUMID, FULL COLOR, FLOATING, DEHUMID, FULL
Temperature Sensor, WHITE, JCI LOGO (0.8 Ibs) COLOR, WHITE, JCI LOGO (0.8
Warmer/Cooler Display, BLACK, 0 S1-TEC3022-16-000 - 7 DAY Ibs)
NO JCI LOGO, NS8000 Series PROGRAMMABLE 0 S1-TEC3612-16-000-7 DAY
(0.4 Ibs) THERMOSTAT, ZIGBEE PRO PROGRAMMABLE
O S1-NSB8BTN240-0 -Wall WIRELESS COMMUNICATION, THERMOSTAT, OPTIONAL MSTP
Temperature Sensor, Full Display, FCUNAV, 0-10VDC PROP, OR N2 COMMUNICATION,
WHITE, JCI LOGO, NS8000 DEHUMID, FULL COLOR, FCUNAV, ON/OFF OR
Series (0.4 Ibs) WHITE, NO LOGO (0.8 Ibs) FLOATING, DEHUMID, FULL
O S1-NSB8BTN241-0 -Wall 0 S1-TEC3023-14-000- 7 DAY COLOR, WHITE, NO LOGO (1.0
Temperature Sensor, Full Display, PROGRAMMABLE Ibs)
WHITE, NO JCI LOGO, NS8000 THERMOSTAT, ZIGBEE PRO 0 S1-TEC3613-14-000 -7 DAY
Series (0.4 Ibs) WIRELESS COMMUNICATION, PROGRAMMABLE
O S1-NSB8BTN243-0 -Wall FCUNAV, 0-10VDC PROP, OCC THERMOSTAT, OPTIONAL MSTP
Temperature Sensor, Full Display, & DEHUMID, FULL COLOR, OR N2 COMMUNICATION,
BLACK, NO JCI LOGO, NS8000 WHITE, JCI LOGO (0.8 Ibs) FCUNAV, ON/OFF OR
Series (0.4 Ibs) 0 S1-TEC3023-16-000 - 7 DAY FLOATING, OCC & DEHUMID,
O S1-TEC3012-14-000 - 7 DAY PROGRAMMABLE FULL COLOR, WHITE, JCI LOGO
PROGRAMMABLE THERMOSTAT, ZIGBEE PRO (0.8 Ibs)
THERMOSTAT, ZIGBEE PRO WIRELESS COMMUNICATION, 0 S1-TEC3613-16-000-7 DAY
WIRELESS COMMUNICATION, FCUNAV, 0-10VDC PROP, OCC PROGRAMMABLE
FCUNAV, ON/OFF OR & DEHUMID, FULL COLOR, THERMOSTAT, OPTIONAL MSTP
FLOATING, DEHUMID, FULL WHITE, NO LOGO (0.8 Ibs) OR N2 COMMUNICATION,
COLOR, WHITE, JCI LOGO (0.8 0 S1-TEC3030-14-000 - 7 DAY FCUNAV, ON/OFF OR
Ibs) PROGRAMMABLE FLOATING, OCC & DEHUMID,
O S1-TEC3012-16-000 - 7 DAY THERMOSTAT, ZIGBEE PRO FULL COLOR, WHITE, NO LOGO
PROGRAMMABLE WIRELESS COMMUNICATION, (0.8 Ibs)
THERMOSTAT, ZIGBEE PRO RTU/HEAT PUMP WITH 0 S1-TEC3622-14-000 -7 DAY
WIRELESS COMMUNICATION, ECON,FULL COLOR, WHITE, JCI PROGRAMMABLE
FCUNAV, ON/OFF OR LOGO (0.8 Ibs) THERMOSTAT, OPTIONAL MSTP
FLOATING, DEHUMID, FULL 0 S1-TEC3030-16-000-7 DAY OR N2 COMMUNICATION,
COLOR, WHITE, NO LOGO (0.8 PROGRAMMABLE FCUNAV, 0-10VDC PROP,
Ibs) THERMOSTAT, ZIGBEE PRO DEHUMID, FULL COLOR,
O S1-TEC3013-14-000 - 7 DAY WIRELESS COMMUNICATION, WHITE, JCI LOGO (0.8 Ibs)
PROGRAMMABLE RTU/HEAT PUMP WITH ECON, 0 S1-TEC3622-16-000- 7 DAY
THERMOSTAT, ZIGBEE PRO AND FULL COLOR, WHITE, NO PROGRAMMABLE
WIRELESS COMMUNICATION, LOGO (0.8 Ibs) THERMOSTAT, OPTIONAL MSTP
FCUNAV, ON/OFF OR 0 S1-TEC3031-14-000- 7 DAY OR N2 COMMUNICATION,
FLOATING, OCC & DEHUMID, PROGRAMMABLE FCUNAV, 0-10VDC PROP,
FULL COLOR, WHITE, JCI LOGO THERMOSTAT, ZIGBEE PRO DEHUMID, FULL COLOR,
(0.8 Ibs) WIRELESS COMMUNICATION, WHITE, NO LOGO (0.8 Ibs)
0 S1-TEC3013-16-000- 7 DAY RTU/HEAT PUMP WITH ECON, 0 S1-TEC3623-14-000 -7 DAY
PROGRAMMABLE OCC SENSOR, FULL COLOR, PROGRAMMABLE
THERMOSTAT, ZIGBEE PRO WHITE, JCI LOGO (0.8 Ibs) THERMOSTAT, OPTIONAL MSTP
WIRELESS COMMUNICATION, 0 S1-TEC3031-16-000 - 7 DAY OR N2 COMMUNICATION,
FCUNAV, ON/OFF OR PROGRAMMABLE FCUNAV, 0-10VDC PROP, OCC
FLOATING, OCC & DEHUMID, THERMOSTAT, ZIGBEE PRO & DEHUMID, FULL COLOR,
FULL COLOR, WHITE, NO LOGO WIRELESS COMMUNICATION, WHITE, JCI LOGO (0.8 Ibs)
(0.8 Ibs) RTU/HEAT PUMP WITH ECON,
OCC SENSOR, FULL COLOR,
WHITE, NO LOGO (0.8 Ibs)
Information is subject to change without notice.Check local codes. Printed 02/24/2021
York® Sun TM Pro 3-12.5 Ton Page:T
YORK® Package
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#: RTU-7,8 System: ZJ120N24R4B5ECA3A2
O S1-TEC3623-16-000- 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
FCUNAV, 0-10VDC PROP, OCC
& DEHUMID, FULL COLOR,
WHITE, NO LOGO (0.8 Ibs)
O S1-TEC3630-14-000- 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
RTU/HEAT PUMP WITH
ECON,FULL COLOR, WHITE, JCI
LOGO (0.8 Ibs)
O S1-TEC3630-16-000- 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
RTU/HEAT PUMP WITH
ECON,FULL COLOR, WHITE, NO
LOGO (0.8 Ibs)
O S1-TEC3631-14-000- 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
RTU/HEAT PUMP WITH ECON,
OCC SENSOR, FULL COLOR,
WHITE, JCI LOGO (0.8 Ibs)
O S1-TEC3631-16-000- 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
RTU/HEAT PUMP WITH ECON,
OCC SENSOR, FULL COLOR,
WHITE, NO LOGO (0.8 Ibs)
O S1-YK-MAP1810-0P- MAP
(Multiple Access Portal) Gateway-
For use with SimplicitySE Control.
(0.2 Ibs)
O S1-YK-MAP1810-0S-Stationary
MAP Gateway(Includes MAP
Gateway, Field Bus Adapter,
Mounting Bracket and 100 to 240
VAC Power Supply). US-
compatible counties. (1.9 Ibs)
• S1-A52- Belt for 8.5 and 10 Ton
High Static Field Installed Drive
(0.4 Ibs)
Information is subject to change without notice.Check local codes. Printed 02/24/2021
I
lig!yo RK® York® Sun TM Pro 3-12.5 Ton Package Page:8 +
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Consolidated Drawing
1 2 3 4 5 6 I 8 9 IS ll 12 13 14 IS 16
NOTES: OPERAf ING CENTER Of own'(. FOR OUTDOOR USE ONLY.. TONNAGE EMIT NOTES:
P 11NAE) LO.AIION 1948E UNIT, 4 POINT CORNER LOADS IL8S1 184,8E ON117
2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. 32.67 6.5 Stag 030 1A611. 40[19161 25[6351 245 11111 197 1891 262 11191 327 11481 N 3. MIN CLEARANCES TO BE: [829,8) 1.5 28/78 080[4901 39 1190,41 241608,61 245 11111 181(661 281 112131 165 11641 N
RIGHT SI2E: 12 (305] 1 8.5 26/2N 084 14221 38 1865,21 24 1609,61 255(1161 93 1861 274 01 41 361 11641
LEFT SIDE: 36 (915] 6.83 _ :0 WE2_ 0651492E 34115861 2516351 1311111/ 59190E 2141124E __.. 355(1111._
[119,51� 5.5 21/01, 001 14581 ,16 1963,27 21 1609 61 235[I07F 11 119E 253[1161_�342 E1561_
FRONT: 36 [9151 C 0)165103 1501E 36 1965,21 241809 6] 251 L112F 12 WI , 279 1127) .575.17701.
REAR: 36 19151. 24 38 0f..I 8 5 25/20 030 145 1 38U5 1 24 1609,61 240[109[_ 79 181 261 11181 350 11591
TOP 72 11830] (619,21 I+ 1 n 2N/2U 090 14941 38 1966.21 24 1608,61 254[II 1 89 1861 276 11251 311 11681
6.
BOTTOM: C 103
5..... Ll/2N...___030 1461 391190,61 25[6351 245TIIII 51 187E t6 [1161 343 11511__._.____
1.5 735 IN 0 14761 39 f990,6I 25 16351 280 f113) 45 189E 269
01201 540 11541
3 4. TO REMOVE THE SLIDE CUT DRAIN PAN, A REAR CLEARANCE Of A 6.5 14(1 AAA
14611 361965,21 2A 1609 61 i41 [I121 184 1841 268[1227 360 11631 J
60 in (1525 Nuns IS REQUIRED. IF SPACE IS UNAVAILABLE, THE c 23r2W 0'0 1485E 341950,61 24 1609,61 245 11111 111 161) Ci81€261 35t 11621
18.00 -�+-7.84
DRAIN PAN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING 8 5 dip IP.RK_ 200[[5441 38 1965,2E 255 1641,11 291[u5r P21 .100E 291 [1321 390 nm�
THE CORNER WALL. €457,2] [199,I 1 6,5 26540 o40 E4901 38 I(963, 25[§311 Arm-GI 1145"S91' j6 Jul) 357 1162I
5. FOR SMALLER SERVICE AND OPERATIONAL. CLEARANCES , I 6,15 7.5 XP/AA 000 T4041 .__58. 9652E 231584,2I, .243.[1101 181 1821 284[1291 361 11781
CONTACT YOUR S DESIGNED ENGINEERING DEPARTMET' [814,41 81
4 [171,61 8.�10 APIAA__.195 5isi.._...:819s3,�i._-sus[141,71 282[.1.il.. _,g9s_[ssi_.._...,,_275I.6i 369 11671
6. DOWHFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY
ROOF CURB ONLY IF UNIT IS MOUNTED SIDE SUPPLY, IT
9
N IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED DY 24.24 _„ £ __ _____ IC. 8,25
CROSS BRACES, AS DONE ON ACCESSORY RWF CURBS. S ALTERNATE CONDENSATION DRAIN• au
-
615,61 R l 266.7E I 1463,63
7. SIDE DUCT FLANGES ARE 0 75' HIGH. (FROM MTB, • C U -
BOTTOM DUCTS DO NOT HAVE FLANGES. F �( ,l ���! :.1111111011111....
FLANGES T 24,00 t isiravi
8. MINIMUM CONDENSATION TRAP HEIGHT SNAIL BE 1,5 TIMES U 27,5s' " (609,61 <• 77�?�s R
THE LOWEST NEGATIVE. STATIC. .4_ ' R L698,51 L
9. DIMENSIONS IN 1 1 ARE IN MILLIMETERS OR KILOGRAMS. N IY i ROW s
G 10, OPTIONECONOMIZ. COIL GUARDS,ER, DISCONNECTPSWITCH,HCONVENGAS IENCEEAT, LEFT 'OL LET ..... ._.....� .., ) ' ° �;> (463,6] „ R C78T 6J.25 G
AND BAROMETRIC RELIEF AUG FRESH AIR HOOTS SHOWN. I •
21.00 . t ids ___� N
A 20.39 ____.______ �1l J !II_%
SUPPLY EY.CEPT XPIRA (NEAT PUMP? UNITS. � !9 14 S'111 Y [533 4U ,� � �[51� 07 CSS161 26.14 ,21 1 435aT-� DIRECTION OF AIRFLOW :� :�. [ 5FOSO 447 r Ci F
CENTER OF GRAVITY �• PRONT BOTTOM GAS �o�T�urr�rrrr6t «'
[361,6] - 16.39 OTTOM ENTRY SUPPLY ENTRY y52.00 [50.81 -2.88
18.06 1416,41 c [ 361,II 28.25 31.63 -, I13,21
POWCR {i2.50 163,.E
[458,8] 18.89 CONTROL. 3X 00.875 [22,231 [717,61 [883,4]
M [419,97 r REAR....IPARIIAL...YEWI
OUTSIDE A.IR (INTAKE HOOD NOT SHOWN IN THIS VIEW]
E INTAKE: HOOD\ DISCONNECT SWITCH COVE' 88.18 E
(OPTIONAL) \ {OPTIONAL) (2239,01
■ POWER ENTRY 02.50 103,51- 0
� � MIIIIIIIIIIIIL 1 AS INLET (1475,51
25.72 • .._.... l - T---•-,
653,3: ECONOMI2EA 9 LOWER ACCESS
p I CTL('AN L1I
(OPTIONAL) FIL'1ERt -CONP'IEUSON _5 COOP.ESS0 CONTROL ENTRY 0 0.875 [ 22,c31-- ACCEss it► 1- - D
CS j)rj• POWER ENTRY 02.50 (63,5)------ 3 - -
•: T M mmilm mm 1= 50.15 -
. oan. .lRi6N.•
-r�r rw 11289,1Edvff ,x,,,' 6ARERETRIL RELIEF 0OOD1- ' -r. )... _ .... _
( E. POWER(OPTIONAL)
[ •�4 I l
C nn -__- na (OPTIONALI .CI - - _EC. ._ _ C
CONVENIENCE OUTLET COVER I f "-V- --"--
LEE7...MEN {OPTIONAL) f 21.31 ` -y l 2 I9 I*-- 11.38 38 "• •-
L Ems . _ bS
1693,13 SEE DETAIL A FOR 5z8.21 1 (289,13 - - \
CONVENIENCE OUTLET DRAIN LOCATION EXHAUST( A 59.00
POWER ENTRY 00.875 (22,231 FLUE --S [1498,6T
314' FPT ----------89.00 -___.........___......,...._..__..,._, __._.M..i `-COIL GUARD
6
[2260,61 FRCH TEN RECLAIM (OPTIONAL) e
(OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEWS
•
8 x DATE REVISION RECORD EC NO :Nit El('ENG 3x IRO AN616 l80JOC,CRI+LL a.wxie-.r x xEs�x*[s eACC xAi3u EN[tli xr R[ux.t0 A«o«0 PLxxrAs�Ox 647E`Y AH0 AEr
1 tl t 6x.IIi LO 0 F rtOWt[iH fx I y 'xOtE W T OrIiI�XLo[A«* i!xL CN.IRACT{A;Si C$PFR
5.37 A 02 I 20 NEW DRAWING (FROM UST PREIS F.50HI 15788 LOP.RCN SAA 65 339 0«u9'4FIA o x Irrou uus «s e0xr a.' BfXF131 .01
[136,41 aUMI MESS 0n[nitt trECirrn SIT FLAT 50 AP wTR[(TOT NONOTPAEPPLrICABLE
A I`_' f 'I I ................... .............. ............. ........ ....... .......... ... K G:¢W'CIK ILK[PI.CIAA NE 912..4 , �. SITE A
_t ._..._6.L�1.._._..._....:::. ..._.jl f i 0581s, $C1 616 N0. REV.SUBMITTAL DWG, PRO
l COIL,
DNN t to 611..F0 TN Pl9{L[NCIAAL, 2 1}
� � ENN R w601A a[I:.m TNREE PILE[ _ a.A10 JOHNSON N CONTROLS 5883785
ENG S.OM 921rN AMU= I r UNITARY PRODUCTS GROUP A
SCALE 0.300 NFO 01441l 8 ARE.41NGi[a NORMAN,off 73069 PART
..CA[f.t D75 90 NM SCALE MIT N-1µi"10 j)F--
I 2 3 4 5 6 7 A 9 10 II 12 13 14 15 16
Information is subject to change without notice.Check local codes. Printed 02/24/2021
® York® SunTM age:9
ir4 Y�RK n TM Pro 3-12.5 TononPacka9►e .
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#: RTU-7,8 System: ZJ120N24R4B5ECA3A2
Component Locations
Cooling With Gas Heat(6.5 Through 10 Tons)
Smart EquipmentTM control board Filter access Filter drier
w/screw connector for T-stat Disconnect location (solid core)
o tional disconnect switch) (2"or 4"filter options)
wiring and network connections ( P
Terminal block for Micro-Channel Aluminum
hi-voltage connection �r Tube/Aluminum Fin
Condenser
nameplate Second model
�/ a
inside hinged : Slide-out motor and
access panel t ''� � _ °'''� ' blowerassemblyfor
easy adjustment
Dual stage 6 - -� � � ,,,
and service
cooling for it € Belt-drive
maximum �. 9' ' blower motor
comfort ) �-, t ',y j VFD location(optional)
l Power ventor motor
Compressor#2 �� `'' � � � ,�"
access(high- K r -""gyp •
,, { a �„ 20-gauge aluminized
efficiency 4 " 'steel tubular heat
compressor) � `
'� --, exchanger for long life
xs (stainless steel option)
rs- fir .-
�'r � Two-stage gas
Base rails wlforklift heating to maintain
slots(three sides) +'" warm,comfortable
" Slide-out drain pan
and lifting holes temperature
with 1"NPT,
Roof curbs in eight-and female connection Intelligent control
fourteen-inch heights.Roof board for safe and
curbs for transitioning from efficient operation
York SunlineTM footprint to Side entry power Compressor#1 access
Toolless and control wiring (high-efficiency compressor)
the ZH/ZJ/ZR/ZU/ZW/ZK door latch
Series footprints knockouts
are also available(field installed accessory)
Printed 02/24/2021 Information is subject to change without notice.Check local codes.
3e York® Sun TM Pro 3-12.5 Ton Page: 10
YORK Package
9►
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Low Leak Downflow Economizer
Low Leak Downflow Economizer(shown with optional Power Exhaust)
`: ,,,,,
''
� Z - �— #s
� ,� Fresh Air Hood
-''t 9 ! (included)
�.,, '! i �j f ! /
-...ram. !
_ Imo;
moil I
,....,. ....."..,- ....r...3.: ii
•-4,...4.-.-...z.--.~.-4-. I ! i• .; -____..,--r'''''' ; • ---- ---------=---
`'��"tea-zzit ---•
0111/
, Lj iii•-;.--- - -:10 .' t.110"11-;
,, I-v.—_ 1 V 1
/ is ,�., J..
Low Leak Economizer(included) / .. _
Power Exhaust(options!) /
Barometric I
Relief Damper Barometric Relief
1 (included) Hood (included)
Low leak economizers are capable achieving low
leakage rates of 3 cfm/sq. ft at 1"of static pressure,
meeting or exceeding the following standards:
ASHRAE 90.1-2010
ASHRAE 62
AMCA 511 (licensed as Class 1A damper)
International Energy Conservation Code (IECC)
California Title 24
The outdoor intake opening shall be covered with a
rain hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is
also possible. Dampers shall fully close on power loss.
Information is subject to change without notice.Check local codes. Printed 02/24/2021
I I i%® York® Sun TM Pro 3-12.5 Ton
Package Page: 1/
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Seismic Certification
036-21806-001-0120
‘1))1LNG 1 VMC GROUP Johnson k
ITHE POWER OF TOGETHER"' Controls
CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
Certification No.
A
D VMA-52939-01 C (Revision 0)
/
Expiration Date: 9/30/2022
Certification Parameters:
The nonstructural products(mechanical and/or electrical components)listed on this certificate are CERTIFIED'FOR SEISMIC APPLICATIONS in
accordance with the following building code2 releases.
IBC 2009,2012,2015,2018
The following model designations,options,and accessories are included in this certification.Reference report number VMA-52939-01 as issued
by The VMC Group for a complete list of certified models,included accessories/options,and certified installation methods.
Johnson Controls;Packaged Rooftop Air Handlers
Predator Series; 3.0-12.5 Tons
The above referenced equipment is APPROVED for seismic application when properly installed',used as intended,and contains a Seismic
Certification Label referencing this Certificate of Compliance'.As limited by the tabulated values,below grade,grade,and roof-level installations,
installations in essential facilities,for life safety applications,and/or of equipment containing hazardous contents are permitted and included in
this certification with an Equipment Importance Factor assigned as IP 1.5.The equipment is qualified by successful seismic shake table testing
at the nationally recognized Dynamic Certification Laboratories under the review of the ISO Accredited Product Certification Agency,The VMC
Group.
Certified Seismic Design Levels8
Importance Ip<_1.5 z/h<_1.0 z/h=0.0
Certified ' Soil Classes A-E
IBC Risk Categories I-IV
Design Categories A-F Sos 52.000 g Sos 52.000 g
The qualified seismic design level stated is the lowest for all series this certificate covers.For more information,see the certified product tables on page 2.
Certified Seismic Installation Methods
Directly To Rigid Curb/Rail Directly To Curb/Rail With Isolation
HEADQUARTERS
113 Main Street CALIFORNIA • TEXAS thevmcgroup.com
Bloomingdale,NJ 07403 180 Promenade Circle 11930 Brittmoore Park Drive
Phone:973.838.1780 Suite 300 Houston,TX 77041 ADVANCED (( -))DCL
Toll Free 800 569 8423 Sacramento.CA 95834 Phone 713.466.0003 ANfi16RATON
Fax:973.492.8430 Phone:916.634.7771 Fax:713.466.1355 co.noxsxrs- LT=FI
102S-103387 Rev15 Page 1 of 3
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Y O RK® York® Sun TM Pro 3-12.5 Ton
Package Page: 12
.
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Seismic Certification
036-21806-001-0120
ii))111e
f.bar VMC GROUP Johnson 0
THE POWER OF TOGETHER" Controls
CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
Certified Product Table:
Series._ Model - : Cooling Tonnage Length fin] i Width(uti 14eigltt[ilt l r .1ri e 1 �''
r,,
Z*/Z**/JA3 037 3 980
(Short) Z*/Z**/JA4 049 ; 4 960
1 42 I
Z*R**/JA5 061 5 1070
XP/XA/J06 078 970
i 6.5 i t i
Z#/Z##/J06 078 51 1090 .
•
i-
•
I XP/XA/J07 090 I 42 920
7.5 i 89 r 2.5
Z#/Z##/J07 090 1081
E •
XP/XA/J08 102 1135
i i-
•
(Standard) 8.5
Z#/Z##/J08 102 1200
i
XP/XA/J10 120 rt 59 : 1135 2.0
Z#/Z##/J10 120 1200
XP/XA/J12 150 1510
12.5 1 :..._._._.. i l
Z#/Z##/J12 150 51 1600
+ -I
ZT/ZV 078 6.5
1550
ZT/ZV 090 7.5 119.5 • 2.0
i i
(Ultra i ZT/ZV 102 8.5 1575
High r• ZTRV 120 10 1470 I
Efficiency) i. -; •
i l
•
ZT/ZV 150 12.5 •
1680
1.Allowable values for '=H,J,R,T
2.Allowable Values for"**"=U,W,K,V
3.Allowable values for'#-=H,J,R,F
4.Allowable Values for"##"=S,U,W,K
s777"^C/ q:v44 s, i a
Group type , Sos(Z/h=0) , S s(z/h 1) A r.,,ar , Amy An 4 r., A
Seismic i AC156 ; 2.00 2.00 f 3.20 2.40 1.33 ; 0.53 ; 1.50
This certification includes packaged rooftops and factory supplied accessories and options. The packaged rooftop and applicable accessories
and options shall be a catalogue design and factory supplied. The packaged rooftop shall be installed and attached to the building structure
per the manufacturer's supplied seismic installation instructions.For a list of certified configurations and options please directly contact the
manufacturer.This certification excludes all non-factory supplied accessories and options,including but not limited to isolation/restraint
devices,other electrical/mechanical components and all connections for electrical,fuel,heating or cooling fluid,or other pipe/conduit
connections and configurations not detailed in the above charts. Flexibility in the connections must be maintained as to not transmit load into
the equipment. Design specials are outside the scope of this certification.
LI m ` ► 7 VMA-52939-01 C(Revision 0)
Issue Date:Monday,September 30,2019
Revision Date:Monday,September 30,2019
Expiration Date:Friday,September 30,2022
102S-103387 Rev15 Page 2 of 3
Information is subject to change without notice.Check local codes. Printed 02/24/2021
York® Sun TM Pro 3-12.5 Ton Page: 13
YORK Package
Single Package R-410A Air Conditioner
Project Name: Templeton Pre K Unit Model#: ZJ120N24R4B5ECA3A2
Quantity: 2 Tag#:RTU-7,8 System: ZJ120N24R4B5ECA3A2
Seismic Certification
036-21806-001-0120
J")))VMC GROUP Johnson
THE POWER OF TOGETHER- Controls
CERTIFICATE OF COMPLIANCE
SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
Notes&Comments:
1.All equipment listed herein successfully passed the seismic acceptance criteria for shake testing non-structural components and systems as set forth in the ICC
AC-156.The Test Response Spectrum(TRS)enveloped the Required Response Spectrum(RRS)for all units tested.The units cited in this certification were
representative sample(s)of a contingent of models and all remained captive and structurally sound after the seismic shake simulation.The units also remained
functionally operational after the simulation testing as functional testing was completed by the equipment manufacturer before and after the seismic simulations.
Although a seismic qualified unit inherently contains some wind resisting capacity,that capacity is undetermined and is excluded from this certification.Snow/Ice
loads have been neglected and thus limit the unit to be installed both indoors(covered by an independent protective structure)and out of doors(exposed to
accumulating snow/ice)for ground snow loads no greater than 30 psf for all applications.
2.The following building codes are addressed under this certification:
IBC 2018 referencing ASCE7-16 and ICC-ES AC-156
IBC 2015 referencing ASCE7-10 and ICC-ES AC-156
IBC 2012 referencing ASCE7-10 and ICC-ES AC-156
IBC 2009 referencing ASCE7-05 and ICC-ES AC-156
3.Refer to the manufacturer supplied installation drawings for anchor requirements and mounting considerations for seismic applications.Required anchor locations,
size,style,and load capacities(tension and shear)may be specified on the installation drawings or specified by a 3rd party.Mounting requirement details such as
anchor brand,type,embedment depth,edge spacing,anchor-to-anchor spacing,concrete strength,special inspection,wall design,and attachment to non-building
structures must be outlined and approved by the Engineer of Record for the project or building.Structural walls,structural floors,and housekeeping pads must also be
seismically designed and approved by the project or building Structural Engineer of Record to withstand the seismic anchor loads as defined on the installation
drawings.The installing contractor is responsible for observing the installation detailed in the seismic installation drawings and the proper installation of all anchors
and mounting hardware.
4.For this certificate and certification to remain valid,this certificate must correspond to the'Seismic Certification Label"found affixed to the unit by the factory.The
label ensures the manufacturer built the unit in conformance to the IBC seismic design criteria set forth by the Certified Seismic Qualification Agency,The VMC Group,
and meets the seismic design levels claimed by this certificate.
5.Mechanical,Electrical,and Plumbing connections to the equipment must be flexibly attached as to not transfer load through the connection.The structural integrity of
any conduit,cable trays,piping,ductwork and/or flexible connections is the responsibility of others.This certification does not guarantee the equipment will remain
compliant to NEMA,IP,UL,or CSA standards after a seismic event.
6.This certificate applies to units manufactured at
5005 Interstate Drive,Norman,OK 73069
7.This certification follows The VMC Group's ISO-17065 Scheme.
8.The qualified seismic design level stated is the lowest for all series this certificate covers.For more information,see the certified product tables on page 2.
John P.Giuliano,PE
President,The VMC Group
AM I
VMA-52939-01C(Revision 0)
ACCREDITED Issue Date:Monday,September 30,2019 \
Revision Date:Monday,September 30,2019
Expiration Date:Friday,September 30,2022
102S-103387 Rev1 5 Page 3 of 3
Information is subject to change without notice.Check local codes. Printed 02/24/2021
OPTIONS: DIMENSIONED ANO TOLERENCED PER ANSI Y16.SM 1912 REVISIONS
MATERIAL: 18ga.GALV STEEL REV. ECOR DESCRIPTION DATE APPROVED
INSULATED PANELS (WHERE REQUIRED) Attu: 1 INITIAL DRAWING 5/14/2005
1"1-1/2LB DUCT INSULATION (R VALUE 3.85) 2 CHANGE HT TO 10"
GASKET PROVIDED WITH CURB
1 1/2"ADDED TO EXISTING CURB O.D. Tag: ' 3 CHANGE HT TO 12"
4 UPDATE TOP BRACE SIZE 11/19/11 00
48" - Approval: 5 UPDATE 3X3 DESIGN 1/2/2019 HMH
28" -
RETURN
22"—.{
SUPPLY
VERT AI •
+ 'r
&SUPPORT • `R r
40,0"
32 _ _ ,-
;, ,-.40:0,06.'"'• ''',
1
INSULATED \\ �`
.. _ COVER • ice" ..':- . ',,,,,,,, ,,,,,,,_ _
�„
I L 1 r
INSULATED - 64 1/2" �"—
COVER - 46 va^ -/
- 441/4" - �`"
21/4" -231/2" �. ,
INSULATED
1 } COVER
26" RETURN SUPPLY
63 1/4"
I.
80 5/8" 1
I- 93" "1 I- 50 1/2"
5,. 1
H
5" 12"
I
94 1/2" l7 Trr 64 3/4" A
CURB SHOWN IS CDI STANDARD CONFIGURATION CDI RESERVES THE RIGHT TO CHANGE THEREINS IS THEG ONTHE INFORMATION CONTAINED os APPROVALS DATE mLDmE NAML.
THEREIN IS THE CONFIDENTIAL,PROPRIETARY °.. hhorn
LAYOUT WITHOUT NOTIFICATION.IF CURB IS NEEDED IN A DIFFERENT CONFIGURATION WFORMATIONOFCRYSTALDISTRIBUTION INC
m^e vts/2ots 1-5010-5035
8 MAY NOT BE USED OR REPRODUCED
WITHOUT THE APPROVAL OF CRYSTAL DISTRIBUTION,INC. ' °
CDI MUST BE NOTIFIED PRIOR TO PLACING AN ORDER. ALL RIGHTS RESERVED DIMENSIONS ARE AS FOLLOWS:1.00 In I25.40 mm)
"VERIFY EXISTING CURB OD 11110...,� N Contact U6 APPROXIMATE mo,.
*VERIFY SUPPLY AND RETURN OPENINGS �'', . CURB WEIGHT(LDS.)
EV
OPERATIONAL HEIGHT OF CDI ADAPTER IS 3"LESS THAN OVERALL CURB HEIGHT •NOTE ANY CHANGES °•�" /z." �-t cm WWW.Cdicums.com R1.
SHOWN. *CALL WITH ANY QUESTIONS "" s of 121.74
•FAX BACK IF DRAWING IS OK AS IS *Ea * ."_",..7 Y,.^ 1-888-234-7001 acALE. 1:24 I sHEEr: 1 of 12
S:\CURBS CURB ADAPTERS\STOCK CURBS HEM\1-5010-5035-HEM\
DIMENSIONED AND TOLERENCED PER ANSI Y14.5M-1982
Attn: YORK Tag:
DCG 090/150 B3 CH 120
-- 64 1/2"
48 1/4" --
44 1/4"
f 23 1/2"
f
26"
RETURN SUPPLY
AIR AIR
L
63 1/4"
3"
4"
93" -
* Verify existing curb OD
* Verify supply and return openings
* Note any changes
DIMENSIONSARE 3RDANGLE * Call with any questions
AS FOLLOWS: PRO.�ECTION
i.aaa�
�sw,mml * Fax back if drawing is OK as is
CHANGED DUCT RACE
04 CONFIGURATION 7/17/08 APPROVALS DATE TITLE:
03 UPDATED ADDRESS 7/5/06 DRANK T.COY 7/17/08 UNITARY PRODUCTS
CHECKED
CHANGED DIMENSION STYLE TO ROOF CURB
2 INSIDE OF R&S OPENINGS 12/8/04 menu;
FILE NAME: DRAWING NO.: REV:
01 N Ti AL DESIGN 1'/8/01 MG �^r LK RIVER,MN 55330 7560 TYLER ST NW 50 0 5010 04
REV DESCRIPTION DATE APPROVED `, E
763)391-7790 EGG#:
(763)3917851 SCALE:1.20 SHEET 1 OF 1
aaaaa4,6 iau:r,t+a f,,ifrr4ll Ii..OWIllNlFN.14.4 .I N rve, r .r f ,, a ., , "ti.et)+4! afttiduauI !rr .. r r x.1 It le r.. Slxa>a3 3rf Hr,e r„ ,r,. . ....... .... ........
DIMENSIONED AND TOLERENCED PER ANSI Y14.5M-1982
Attn: YORK Tag:
PREDATOR DM/DL 090-150
1 RC0471
48'
28" i 1 3/4"TYP.
22" 2"TYP.
./e
RETURN SUPPLY
32" AIR AIR
INSULATED
COVER 50 1/2'I
I
INSULATE/
COVER
/ / /
80 5/8" '''l
* Verify existing curb OD
* Verify supply and return openings
* Note any changes
A=OLLOWSARE PRDOJENGLE CTION * Call with any questions
J * Fax back if drawing is OK as is
APPROVALS DATE TITLE:
DRAWN: mgreenwood 10/5/2011 YORK
CHECKED:
03 UPDATE BRACES 10/5/11 MWG ROOF CURB
MONT.
02 UPDATED ADDRESS 7/5/06 AL FILENAME: DRAWING NO.: REV:
C D r ELK
17560RIVER TYLERMN ST N55330 W 5035 5035 03
01 ,
INITIAL DESIGN 1 1/8/Ol MWG 763)391-7790
Eco it:
REV. DESCRIPTION DATE APPROVED (763)3917851 SCALE:1:16 SHEET:1 OF 1
Page: 15
Date
02/24/2021 01(
Project NameTempleton Pre K
Johnson �
Project Number Controls
M M 10082002
Client/Purchaser
Guide Specification Summary Page
Product Series Models and Unit Tags
York®Sun TM Pro 3-12.5 Ton Package ZJ120N24R4B5ECA3A2 RTU-7, 8
Information is subject to change without notice.Check local codes. Printed 02/24/2021
•
•
yoRK® Specification for Page: 16
York® Sun TM ProoRKo
GENERAL removing panels or creating bypass of the coils.
Condensate pan shall be slide out design, constructed of
TM
York®Sun Pro units are convertible single packages a non corrosive material, internally sloped and
with a common footprint cabinet and common roof curb conforming to ASHRAE 62-B9 standards. Condensate
for all 6-1/2 through 12-1/2 ton models. All have two connection shall be a minimum of/4" I.D. female and be
compressors with independent R-410A refrigeration rigid mount connection.
circuits to provide 2 stages of cooling. The units were
designed for light commercial applications and can be INDOOR(EVAPORATOR) FAN ASSEMBLY
easily installed on a roof curb, slab, or frame.All units
are self contained and assembled on rigid full perimeter Fan shall be a belt drive assembly and include an
base rails allowing for 3-way forklift access and adjustable pitch motor pulley. Job site selected brake
overhead rigging. Every unit is completely charged with horsepower shall not exceed the motors nameplate
R-410A, wired, piped, and tested at the factory to horsepower rating plus the service factor. Units shall be
provide a quick and easy field installation. All units are designed to operate within the service factor. Fan wheel
convertible between side and down airflow. Independent shall be double inlet type with forward curve blades,
economizer designs are used on side and down dynamically balanced to operate smoothly throughout
discharge applications, as well as all tonnage sizes. the entire range of operation. Airflow design shall be
Predator®units are available in the following constant volume. Bearings shall be sealed and
configurations: cooling only, cooling with electric heat, permanently lubricated for longer life and no
cooling with gas heat, reheat only, reheat with electric maintenance. Entire blower assembly and motor shall be
heat and reheat with gas heat. Electric heaters are slide out design.
available as factory-installed options or field-installed OUTDOOR(CONDENSER) FAN ASSEMBLY
accessories.
DESCRIPTION The outdoor fans shall be of the direct drive type,
discharge air vertically, have aluminum blades riveted to
Units shall be factory assembled, single package, corrosion resistant steel spider brackets and shall be
(Elec/Elec, Gas/Elec), designed for outdoor installation. dynamically balanced for smooth operation. The outdoor
They shall have built in field convertible duct connections fan motors shall have permanently lubricated bearings
for down discharge supply/return or horizontal discharge internally protected against overload conditions and
supply/return and be available with factory installed staged independently. A cleaning window shall be
options or field installed accessories. The units shall be provided on two sides of the units for coil cleaning.
factory wired, piped and charged with R-410A refrigerant REFRIGERANT COMPONENTS
and factory tested prior to shipment. All unit wiring shall
be both numbered and color coded. The cooling Compressors:
performance shall be rated in accordance with DOE and
AHRI test procedures. Units shall be CSA certified to a. Shall be fully hermetic type, direct drive, internally
ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 protected with internal high-pressure relief and over
standards. temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of+ or
UNIT CABINET — 10% of the unit nameplate voltage.
Unit cabinet shall be constructed of galvanized steel with b. Shall have internal spring isolation and sound
exterior surfaces coated with a non-chalking, powder muffling to minimize vibration and noise, and be
paint finish, certified at a 750-hour salt spray test per externally isolated on a dedicated, independent
ASTM-B117 standards. Indoor blower sections shall be mounting.
insulated with up to 1"thick insulation coated on the
airside. Either aluminum foil faced or elastometric rubber Coils:
insulation shall be used in the unit's compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with toolless
access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable
transit of equipment, overhead rigging, fork truck access
and proper sealing on roof curb applications. Disposable
2"filters shall be furnished as standard and be
accessible through hinged access door. Fan
performance measuring ports shall be provided on the
outside of the cabinet to allow accurate air
measurements of evaporator fan performance without
Information is subject to change without notice.Check local codes. Printed 02/24/2021
yrç Guide Specification for Page:17
York® Sun TM Pro
a. Evaporator coils shall have aluminum plate fins Heat exchanger and exhaust system shall be
mechanically bonded to seamless internally enhanced constructed of aluminized steel, and be designed with
copper tubes with all joints brazed. Special Phenolic induced draft combustion with post purge logic, energy
coating shall be available as a factory option. saving direct spark ignition, and redundant main gas
b. Evaporator coils shall be of the direct expansion, draw- valve. The heat exchanger shall be of the tubular type,
thru design. constructed of T1-40 aluminized steel for corrosion
resistance and allowing minimum mixed air entering
c. Condenser coils shall have aluminum plate fins temperature of 40°F. Burners shall be of the in-shot
mechanically bonded to seamless internally enhanced type, constructed of aluminum-coated steel. All gas
copper tubes with all joints brazed or Micro-Channel piping shall enter the unit cabinet at a single location,
aluminum tube, aluminum fins. through either the side or bottom, without any field
d. Condenser coils shall be of the draw-thru design. modifications. An integrated control board shall provide
timed control of evaporator fan functioning and burner
Refrigerant Circuit and Refrigerant Safety Components ignition. Heating section shall be provided with the
shall include: following minimum protection:
a. Independent fixed-orifice or thermally operated a. Primary and auxiliary high-temperature limit switches.
expansion devices. b. Induced draft pressure sensor.
b. Solid core filter drier/strainer to eliminate any moisture c. Flame roll out switch (manual reset).
or foreign matter. d. Flame proving controls.
c. Accessible service gage connections on both suction e. All two stage gas units shall have two independent
and discharge lines to charge, evacuate, and measure stages of capacity(70% or 75% 1st stage, 100% 2nd
refrigerant pressure during any necessary servicing or stage)3 through 5 ton and (60% 1st stage, 100% 2nd
troubleshooting, without losing charge.
stage)6-1/2 through 12-1/2 ton.
d. The unit shall have two independent refrigerant
circuits,equally split in 50%capacity increments. UNIT OPERATING CHARACTERISTICS
Unit Controls: Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria
a. Unit shall be complete with self-contained low-voltage of AHRI Standard 340/360. The compressor, with
control circuit protected by a resettable circuit breaker standard controls, shall be capable of operation down to
on the 24-volt transformer side. 0°F outdoor temperature. Unit shall be provided with fan
b. Unit shall incorporate a lockout circuit which provides time delay to prevent cold air delivery before heat
reset capability at the space thermostat or base unit exchanger warms up. (Gas heat only)
should any of the following standard safety devices trip
and shut off compressor: ELECTRICAL REQUIREMENTS -All unit power wiring
• Loss-of-charge/Low-pressure switch. shall enter unit cabinet at a single factory provided
location and be capable of side or bottom entry to
• High-pressure switch. minimize roof penetrations and avoid unit field
• Freeze condition sensor on evaporator coil. If any modifications. Separate side and bottom openings shall
of these safety devices trip, the LCD screen will be provided for the control wiring.
display the alarm message.
STANDARD LIMITED WARRANTIES -Compressor—5
c. Unit shall incorporate"AUTO RESET"compressor Years, Heat Exchanger— 10 Years, Elect. Heat Elem. —5
over temperature, over current protection. Years, Parts— 1 Year.
d. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy FACTORY INSTALLED OPTIONAL OUTDOOR AIR
hook-up. (Shall be made available by either/or):
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down
to a selectable value as low as 0°F.
g. Control board shall monitor each refrigerant safety
switch independently.
GAS HEATING SECTION
Information is subject to change without notice.Check local codes. Printed 02/24/2021
YRK® Guide Specification for Page: 18
O York® Sun TM Pro
• DRY BULB AUTOMATIC ECONOMIZER—Outdoor
and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor
air intake dampers shall be designed to meet ASHRAE
90.1, AMCA 511 Class 1A damper, and the
International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates
of 3 CFM/sq. ft. at 1"of static pressure. Changeover
from compressor to economizer operation shall be
provided by an integral electronic enthalpy control that
feeds input into the basic module. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided.
Simultaneous economizer/compressor operation is
also possible. Dampers shall fully close on power
loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• Alternate Indoor Blower Motor—For applications
with high restrictions, units are available with optional
indoor blower motors that provide higher static output
and/or higher airflow.
• IntelliSpeedTM Supply Fan Control Option
(ASHRAE 90.1 compliant, section 6.4.3.10)—Units
configured with the IntelliSpeedT"" Supply Fan Option
will contain a VFD for variable volume supply fan
operation. This option allows the supply fan RPM to
vary based on the number of compressors or heating
stages energized. The economizer's minimum position
will also be configurable to vary based on the supply
fan VFD frequency output.
• Non-Powered Convenience Outlet—Unit is provided
with a non-powered 120VAC GFCI outlet with cover on
the corner of the unit housing the compressors.
• BAS Controls— Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• Smoke Detector—A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
FIELD INSTALLED OPTIONS
• Roof Curb— 14" high, full perimeter knockdown curb,
with hinged design for quick assembly.
• Power Exhaust-This accessory installs in the unit
with a down flow economizer and is duct mounted in
horizontal applications. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page: 19
Date •
02/24/2021 Project NameJohnson 04(0
Templeton Pre K
Project Number Controls
MM10082002
Client/Purchaser
Control Summary Page
Control Models and Unit Tags
BACnet MSTP,Mdbs,N2 COM Card ZJ120N24R4B5ECA3A2 RTU-7, 8
Information is subject to change without notice.Check local codes. Printed 02/24/2021
SSE Guide Spec Page:20
f ®YORK®
23 09 23 Direct-digital Control system for HVAC
23 09 23. 13 Decentralized,Rooftop Units:
23 09 23. 13.A. Unit Control Board
1. ASHRAE 62-2001compliant. BTL certified.
2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal.
3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non-
condensing),with a storage temperature range from-40F to 194F;5-95%RH(non-condensing).
4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board
and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs.
5. Controller shall accept the followinginputs:space temperature,return air temperature sensor,setpointadjustment,outdoor air
temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single
and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors,
FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality,
System purge.
6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and
be Demand Control Ventilation(DCV)ready.
7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/
exhaust/reversing valve/dehumidify/occupied.
8. Unit shall provide surge protection for the controller through a circuit breaker.
9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster.
10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation.
11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the
following standard safety devices trip and shut off compressor. If any of these safety devices trip,the LCD screen will display
alarm message indicating the specific safety device that caused the lockout.
a. Loss of charge/Low-pressure switch.
b. High-pressure switch.
c. Freeze condition sensor on evaporator coil.
12. Unit control board must support each usage case:
a. Conventional thermostat with low voltage input terminals for easy installation
b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control
board to compare with associated setpoints
c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building
automation/management system
13. Anti-short cycle and low voltage protection features included.
14. Internal occupied/unoccupied scheduling
15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F.
16. Shall allow for start-up,commissioning,troubleshooting, parameter adjustment,setpoint adjustment via onboard
display and navigable menu with no additional interface tool or controls technician required.
17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating
cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test.
18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between
them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up, commissioning,
troubleshooting, parameter adjustment,setpoint adjustment.
19. Local embedded trending and scheduling.Trending data and occupancy scheduling predefined from the factory.
Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device
(cellular phone, laptop,tablet)
20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable.These
include but are not limited to:
a. Demand Ventilation Mode—enable or disable
b. Operational Setpoint—display current value
c. Supply Air Temperature(SAT)—display current value
d. Return Air Temperature(RAT)—display current value
Information is subject to change without notice.Check local codes. Printed 02/24/2021
SSE Guide Spec Page:21
YORK®
e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network
Sensor,or FC Bus communicated value
f. Return Air Humidity(RAH)—display current value
g. Operational outdoor Air Temperature(OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer
board and OprOAT only if economizer is present
h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards
OAH 0-10VDC input or FC Bus communicated value
i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer
boards OAQ 0-10VDC input or FC Bus communicated value
j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board
IAQ 0-10VDC input, SA Bus Network Sensor,or FC Bus communicated value
21. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone Fan
b. Cooling
c. Heating
d. Economizer
e. Demand Ventilation
f. Power Exhaust
g. Sensors
h. Network
22. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone—Occupied status
b. Indoor Fan status
c. Cooling status
d. Heating status
e. Economizer indication whether free-cooling is available or not
f. Enabling or disabling of Demand Ventilation
g. Power Exhaust
1) Enable/disable hot-gas reheat if available
2) Warmup/Cooldown
3) Title 24 Load Shed
4) Defrost
23. A menu shall display and allow modification to the following operations and settings:
a. Firmware version(of UCB, Economizer, other peripheral boards)
b. Setting time zone
c. Network information
1) Device name that will appear on the FC Bus
2) Selection of communication protocol
3) Operational Baud Rate
4) Device ID
24. A menu shall display and allow modification to the following operations and settings:
a. Version of firmware
b. Ability to Load new firmware
c. Create a backup file of the firmware and parameter setting via USB port
d. Restore factory default parameter values and setup
e. Full and Partial Cloning of parameter setpoints from or to other units
f. Data trend exporting
25. A menu shall display and allow modification to the following operations and settings:
Information is subject to change without notice.Check local codes. Printed 02/24/2021
yoRK® SSE Guide Spec Page:22
a. Unit serial number, model number and name
b. Ability to reset Lockouts
c. Controller name
d. Displays the current values of all setpoints in use
e. Displays all current values for the indoor and outdoor zones
f. Displays current values related to:
1) Indoor Fan
2) Cooling
3) Heating
4) Heat Pump operation
5) Economizer operation
6) Power Exhaust
7) Demand Ventilation
8) Air monitoring station
9) Hot Gas Reheat
10) Smoke Control
g. Current information for inputs; including
1) Sensors
2) Coil Sensors
3) Thermostat
4) Binary Inputs
5) Unit Protection
6) Network Inputs
7) All outputs(relay and binary)
h. Self-Test
1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning
characteristics of the system at time of startup and commissioning.
23 09 23. 13.B. Auxiliary Control Boards
1. ASHRAE 62-2001 compliant. BTL certified.
2. Economizer controller CEC Title 24 Compliant
a. Display alarms if the following occur
1) Economizer is economizing when conditions do not support
2) Economizer is not economizing when conditions do support
3) Damper Stuck
4) Excess Outdoor Air
5) Failed Sensor
3. Refrigeration Fault Detection &Diagnostics
a. There is insufficient refrigerant in any circuit
b. There is excessive refrigerant in any circuit
c. There is excessive refrigerant flow
d. There is insufficient refrigerant flow(restriction)
e. Inefficient compressor
f. Insufficient High-side heat transfer
g. Excessive High-side heat transfer(low ambient control problem, low AP)
h. Insufficient Low-side heat transfer
i. Excessive Low-side heat transfer
Information is subject to change without notice.Check local codes. Printed 02/24/2021
;t.
SSE Guide Spec Page:23
YORK®
j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if
refrigerant level is very low in the system)
k. Sensor fault-Sensor data is not available
I. The unit is off
m. The ambient temperature is too low
n. The ambient temperature is too high
o. The return air wet-bulb temperature is too low
p. The return air wet-bulb temperature is too high
q. Sensor fault-The condensing temperature is lower than the ambient temperature(Could also be triggered when
the condenser is wet)
r. The suction line temperature is less than the evaporator temperature
s. The evaporator temperature is greater than the ambient temperature
t. The liquid temperature is lower than the ambient temperature
u. Sensor fault-Suction temperature or ambient temperature is invalid
v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid
w. Sensor fault-The liquid pressure or suction pressure is invalid
x. Sensor fault-The suction line temperature is invalid
y. The return air dry-bulb temperature is too low
z. The return air dry-bulb temperature is too high
aa. The Efficiency Index is below 75%of ideal
bb. The Capacity Index is below 75%of ideal
23 09 23. 13.0 Remote Accessibility:
1. ASHRAE 62-2001 compliant. BTL certified.
2. Provide the ability to adjust parameter values, setpoints, limits remotely
3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS)
4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page:24
START-UP & SERVICE DATA INSTRUCTION
COMMERCIAL PACKAGE UNITS
3.0 To 40.0 TONS
START-UP CHECKLIST
Date:
Job Name:
Customer Name:
Address:
City: State: Zip:
Model Number: Serial Number:
Qualified Start-up Technician: Signature:
HVAC Contractor: Phone:
Address:
Contractor's E-mail Address:
Electrical Contractor: Phone:
Distributor Name: Phone:
WARRANTY STATEMENT This start-up sheet covers all startup check points common to all
package equipment.In addition it covers essential startup check
Johnson Controls/UPG is confident that this equipment will points for a number of common installation options. Depending
operate to the owner's satisfaction if the proper procedures are upon the particular unit being started not all sections of this startup
followed and checks are made at initial start-up.This confidence is sheet will apply.Complete those sections applicable and use the
supported by the 30 day dealer protection coverage portion of our notes section to record any additional information pertinent to your
standard warranty policy which states that Johnson Controls/UPG particular installation.
will cover parts and labor on new equipment start-up failures that Warranty claims are to be made through the distributor from whom
are caused by a defect in factory workmanship or material,for a the equipment was purchased.
period of 30 days from installation. Refer to current standard
warranty policy and warranty manual found on UPGnet for details. EQUIPMENT STARTUP
In the event that communication with Johnson Controls/UPG is
required regarding technical and/or warranty concerns,all parties Use the local LCD or Mobile Access Portal(MAP)Gateway to
to the discussion should have a copy of the equipment start-up complete the start-up.
sheet for reference.A copy of the original start-up sheet should be A copy of the completed start-up sheet should be kept on file
filed with the Technical Services Department. by the distributor providing the equipment and a copy sent to:
The packaged unit is available in constant or variable air volume Johnson Controls/UPG
versions with a large variety of custom options and accessories Technical Services Department
available.Therefore,some variation in the startup procedure will 5005 York Drive
exist depending upon the products capacity,control system, Norman,OK 73069
options and accessories installed.
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page:25
SAFETY WARNINGS
The inspections and recording of data outlined in this procedure AWARNING
are required for start-up of Johnson Controls/UPG's packaged
products. Industry recognized safety standards and practices Lethal voltages are present during some start-up
must be observed at all times.General industry knowledge and checks. Extreme caution must be used at all times.
experience are required to assure technician safety. It is the
responsibility of the technician to assess all potential dangers
and take all steps warranted to perform the work in a safe AWARNING
manner. By addressing those potential dangers, prior to
beginning any work,the technician can perform the work in a
safe manner with minimal risk of injury. Moving parts may be exposed during some startup
checks. Extreme caution must be used at all times.
NOTE: Read and review this entire document before beginning
any of the startup procedures.
DESIGN APPLICATION INFORMATION
This information will be available from the specifying engineer full open position and the frequency drive is operating at 60 HZ.
who selected the equipment.If the system is a VAV system the Do not proceed with the equipment start-up without the
CFM will be the airflow when the remote VAV boxes are in the design CFM information.
Design Supply Air CFM: Design Return Air CFM:
Design Outdoor Air CFM At Minimum Position:
Total External Static Pressure:
Supply Static Pressure:
Return Static Pressure:
Design Building Static Pressure:
Outside Air Dilution:Economizer Position Percentage: _ CFM:
Supply Gas Pressure After Regulator W/o Heat Active Inches
ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER:
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page:26
REFERENCE
General Inspection Completed See Notes
Unit inspected for shipping,storage,or rigging damage ❑ ❑
Unit installed with proper clearances 0 0
Unit installed within slope limitations ❑ 0
Refrigeration system checked for gross leaks(presence of oil) 0 ❑
Terminal screws and wiring connections checked for tightness ❑ 0
Filters installed correctly and clean 0 0
Economizer hoods installed in operating position 0 ❑
Condensate drain trapped properly, refer to Installation Manual 0 0
Economizer damper linkage tight 0 ❑
Gas Heat vent hood installed ❑ 0
All field wiring(power and control)complete 0 0
Air Moving Inspection Completed See Notes
Alignment of drive components 0 0
Belt tension adjusted properly 0 0
Blower pulleys tight on shaft bearing set screws tight,wheel tight to shaft 0 0
Pressure switch or transducer tubing installed properly ❑ 0
Exhaust Inspection Powered 0 Barometric Relief 0 Com pleted See Notes
Check hub for tightness ❑ 0
Check fan blade for clearance ❑ 0
Check for proper rotation ❑ 0
Check for proper mounting(screen faces towards unit) 0 0
Prove operation by increasing minimum setting on economizer ❑ 0
Economizer Inspection Standard 0 BAS 0 Corn pleted See Notes
CO2 sensor installed Yes 0 No 0 0 0
Check economizer setting(Reference SSE Control Board LCD menu location) 0 0
Prove economizer open/close through SSE Board Setting 0 0
Reheat Mode Normal 0 or Alternate 0 Not Applicable 0
Humidity Sensor(2SH0401)
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page:27
Operating Measurements -Air Flow
Fan operates with proper rotation ID Fans 0 Exh.Fans 0 Cond. Fans❑
Pressure drop across dry evaporator coil(At maximum design CFM)1 IWC
External Static Pressure IVVC
Return Static Pressure IWC
Supply Static Pressure IWC
Supply Air CFM Using Dry Coil Chart CFM
Final Adjusted Supply Air CFM2 CFM
1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential.
2. Was a motor pulley adjustment or change required to obtain the correct airflow?
Was it necessary to increase of decrease the airflow to meet the design conditions?
If the motor pulley size was changed,measure the outside diameters of the motor and blower pulleys and record those diameters here;
Blower Motor HP FLA RPM
Pulley Pitch Diameter Turns Out Final Turns Out
Blower Pulley Pitch Diameter Fixed Sheave
ELECTRICAL DATA
T1 -T2 Volts T2-T3 Volts
Control Voltage Volts T1 -T3 Volts
Device Nameplate Measured
List All Three Amperages
Supply Fan Motorl,2 AMPS AMPS
Exhaust Motor(Dampers 100%) AMPS AMPS
Condenser Fan#1 AMPS AMPS
Condenser Fan#2(if equipped) AMPS AMPS
Condenser Fan#3(if equipped) AMPS AMPS
Condenser Fan#4(if equipped) AMPS AMPS
Compressor#1 AMPS AMPS
Compressor#2(if equipped) AMPS AMPS
Compressor#3(if equipped) AMPS AMPS
Compressor#4(if equipped) AMPS AMPS
1. VAV units with heat section-simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position.
2. VAV units without heat section-VAV boxes must be set to maximum design airflow position.
Information is subject to change without notice.Check local codes. Printed 02/24/2021
%.
Page:28
OPERATING MEASUREMENTS -COOLING
Discharge Discharge Liquid Line 2 Suction Suction
Stage Pressure Temp. Temp.1 Subcooling Pressure Temp. Superheat
First # ° #' °
Second(if equipped) # #- 0
Third(if equipped) # 0
0
#- 0 0
Fourth(if equipped) # # 0 °
Reheat 1st Stage # 00 # o °
1. Liquid temperature should be taken before filter/drier.
2. Subtract 10 psi from discharge pressure for estimated liquid line pressure
Outside air temperature °F db °F wb %RH
Return Air Temperature °F db °F wb %RH
Mixed Air Temperature °F db °F wb %RH
Supply Air Temperature °F db °F wb %RH
REFRIGERANT SAFETIES
Action Completed See Notes
Prove Compressor Rotation(3 phase only)by gauge pressure 0 0
Prove High Pressure Safety,All Systems 0 ❑
Prove Law Pressure Safety,All Systems 0 0
OPERATING MEASUREMENTS -GAS HEATING
Fuel Type: ❑ Natural Gas 0 LP Gas
Action Completed See Notes
Check for gas leaks 0 0
Prove Ventor Motor Operation ❑ ❑
Prove Primary Safety Operation 0 0
Prove Auxiliary Safety Operation 0 0
Prove Rollout Switch Operation 0 0
Prove Smoke Detector Operation 0 0
Stage 1 IWC 0
Manifold Pressure Stage 2(If Equipped) IWC 0
Stage 3(If Equipped) IWC 0
Supply gas pressure at full fire IWC ❑
Check temperature rise1 D measured at full fire °F 0
1. Input X Eff.(BTU output)
1.08 X Temp.Rise
Information is subject to change without notice.Check local codes. Printed 02/24/2021
Page:29
OPERATIONAL MEASUREMENTS -STAGING CONTROLS
Verify Proper Operation of Heating/Cooling Staging Controls
Create a cooling demand at the Thermostat, BAS System or Simplicity SE
Verify that cooling/economizer stages are energized. ❑
Create a heating demand at the Thermostat, BAS System or Simplicity SE
Verify that heating stages are energized. 0
Verify Proper Operation of the Variable Frequency Drive(If Required)
Verify that motor speed modulates with duct pressure change. ❑
FINAL -INSPECTION
Verify that all operational control set points have been set to desired value ❑
Scroll through all setpoints and change as may be necessary to suit the occupant requirements.
Verify that all option parameters are correct
Scroll through all option parameters and ensure that all installed options are enabled in the software and all 0
others are disabled in the software. (Factory software settings should match the installed options)
Verify that all access panels have been closed and secured ❑
OBSERVED PRODUCT DIFFICIENCIES & CONCERNS:
Information is subject to change without notice.Check local codes. Printed 02/24/2021
OFFIC L u 't Printed Date: 03/05/2021
IGREENHECK Job: Templeton Pre-K Conference Center
Building Value in Air. Mark: EDH
OFFICE COPY Model: IDHE
Model: IDHE
Ratings and General Construction
Airflow Direction: Universal Control Box Offset: Universal Control Voltage: 24 VAC
Deration: None Element Wire: 80/20 Heater Control: SCR
Heater Type: Slip In Heater Voltage/Phase: 480/3 Recess(in.): None
Stainless Hardware: Yes Power Fusing: No Preference
Accessories
Airflow Switch: Non-Adjustable Control Transformer: Unfused Disconnect Switch: Yes
Thermostat: None Fan Interlock: No Vapor Barrier: No
Dust Tight Box: No Pilot Light: None Time Delay Relay: None
FLIP HEATER TO Application & Design
ACHIEVE RIGHT OFFSET
The IDHE series is a custom duct heater featuring
R' unparalleled installation flexibility in a compact package.
• The IDHE has the following features:
•Universal airflow:The IDHE can be installed in any of the
Sifollowing six orientations:
/ BD Horizontal duct: RECEIVED
,. •Right or left side of duct
[->"
r\ •Right or left-hand control cabinet orientation
•Airflow from right or left MAY 17 2021
Vertical duct:
•Right or left side of duct CITY OF TIGARD
H le
•Top or bottom control cabinet orientation
•Upward or downward airflow BUILDING DIVISION
Other standard features include:
TYPE S •Hinged control cabinet cover-Standard
SLIP-IN OFFSET LEFT •UL zero clearance rating-Standard
STANDARD •Low pressure loss element assembly-Standard
•This drawing shows a general damper configuration and is not
intended to depict the exact configuration of all dampers
in this submittal.
•All dimensions shown are in units of in.
•Slip In heaters are nominally undersized 0.250 in.wide and
0.125 in.high.
Row Width:Height Power Dimension Dimension Dimension Dimension Dimension Dimension Dimension
ID Tag Quantity in. in Kilowatts Stages Amps FusingQ(in.) Z(in.) BD(in.) U(in.) N(in.) R(in.) T m.
( ) ( ) ( )
8-1 EDH-1-101 1 12.00012.000 6 1 7.217 No 17 13.938 7.6 6 10 1 1
8-2 EDH-1-102 1 10.00010.000 3 1 3.608 No 19 11.938 7.6 6 12 1 1
8-3 EDH-1-103 1 10.00010.000 4 1 4.811 No 19 11.938 7.6 6 12 1 1
8-4 EDH-1-105 1 10.00010.000 3 1 3.608 No ▪ 19 11.938 7.6 6 12 1 1
8-5 EDH-1-106 1 10.00010.000 3 1 3.608 No _ 19 11.938 7.6 6 12 1 1
8-6 EDH-1-107 1 36.000 8.000 12 1 14.434 No 21 9.938 7.6 6 14 1 1
8-7 EDH-1-108 1 36.000 8.000 9 1 10.825 No 21 9.938 7.6 6 14 1 1
8-8 EDH-1-109 1 36.000 8.000 12 1 14.434 No 21 9.938 7.6 6 i 14 1 1
8-9 EDH-1-110 1 36.000 8.000 12 1 14.434 No 21 9.938 7.6 6 14 1 1
8-10 EDH-1-111 1 36.000 8.000 12 1 14.434 No • 21 9.938 7.6 6 14 1 1
8-11 EDH-1-112 1 36.000 8.000 5 1 6.014 No 21 9.938 7.6 6 14 1 1
8-12EDH-1-113 1 20.000 8.000 7 1 8.42 No 21 9.938 7.6 6 14 1 1
Total Qty: 12
Generated by:renkelis@ajohnsonair.com
CAPS 4.34.1178 Y:\ChrisHessick\Secured Jobs 2021\S-Z\Templeton Pre-K Conference Center.gfcj Page 2 of 3
EIPrinted Date: 03/05/2021
GREENHECK Job: Templeton Pre-K Conference Center
Building Value in Air. Mark: E D H
Model: IDHE
Minimum CFM*
Inlet Air Temp(F) -25 0 20 40 60 70 80 100
Row ID 8-1 93 111 135 165 211 243 284 418
Row ID 8-2 47 56 67 82 105 121 142 209
Row ID 8-3 62 74 90 110 141 162 189 279
Row ID 8-4 47 56 67 82 105 121 142 209
Row ID 8-5 47 56 67 82 105 121 142 209
Row ID 8-6 186 223 269 330 422 486 568 837
Row ID 8-7 140 167 202 247 316 364 426 628
Row ID 8-8 186 223 269 330 422 486 568 837
Row ID 8-9 186 223 269 330 422 486 568 837
Row ID 8-10 186 223 269 330 422 486 568 837
Row ID 8-11 78 93 '112 137 176 202 237 349
Row ID 8-12 109 130 1157 192 246 283 332 488
*Minimum air flow values are determined with uniform air volume across the face of heater coils. If air flow is not consistent across heater coils at
minimum values,localized hotspots may occur and cause temperature overload to trip.
Minimum FPM*
Inlet Air Temp(F) -25 0 20 40 60 70 80 100
Row ID 8-1 93 111 '135 165 211 243 284 418
Row ID 8-2 67 80 97 119 152 175 205 301
Row ID 8-3 89 107 '129 158 203 233 273 402
Row ID 8-4 67 80 97 119 152 175 205 301
Row ID 8-5 67 80 97 119 152 175 205 301
Row ID 8-6 93 111 '135 165 211 243 284 418
Row ID 8-7 70 84 '101 124 158 182 213 314
Row ID 8-8 93 111 '135 165 211 243 284 418
Row ID 8-9 93 111 '135 165 211 243 284 418
Row ID 8-10 93 111 '135 165 211 243 284 418
Row ID 8-11 39 46 56 69 88 101 118 174
Row ID 8-12 98 117 '141 173 222 255 298 439
*Minimum air flow values are determined with uniform air flow across the face of heater coils. If air flow is not consistent across heater coils at minimum
values,localized hotspots may occur and cause temperature overload to trip.
Generated by:renkelis@ajohnsonair.com
CAPS 4.34.1178 Y:\ChrisHessick\Secured Jobs 2021\S-Z\Templeton Pre-K Conference Center.gfcj Page 3 of 3
7
7
7
D AGRAV GQ 310
OPTIONS FOR CONTROL
COM 1
24 VAC 2
2-10 VDC 3 -�
4
1
2 TO 10 VDC i — N. ••••• •• NE N. 1.7
STAND ALONE THERMOSTAT / SIGNAL
(24VAC POWERS T'STAT) / INTERFACE
/ MODULE
- 1 --
2
3 -- '\ 2 i o o f I 1
4 ' 3 '
/2 TO 10 VDC FROM
BUILDING AUTOMATION SYSTEM \ 4 L——__I
i
1 I
I I
JUMPER 2 //
+ 3 i
4
4 TO 20 mA FROM D.D.C.
BUILDING AUTOMATION SYSTEM
\ T-RNAL -_-AT-R
POWER TERMINAL W R \ G AS P =Q .. R = D
BOARD
(OR OPTIONAL
11 DISCONNECT
SWITCH
Li S-- S , By TAB =0R A
L2 c -L = CTR CAL RAT \ GS
l
L3 Q\c
— 11111•111MMINNI MI M
L__,__J
O GND.
3 - .D - AS -
- L= CTR CAL CO \ \ =CT 0\ S =OR
A DLCT - -AT=R WIT- A \
L-CTRO\ C ST' D CO\ TROLLER ,
SCR OR SCR V= R \ I = R CO \ TROD.
This print and the confidential business information which it
GREENHECK contains are the property of Greenheck Fan Corporation of
Schofield, WI. It is loaned for confidential use by recipient solely to
further the business interests of Greenheck and is subject to return
rI
on request and with the mutual understanding that it will not be
icon in nnv mnnnor rlofrim onf nl fn fho inf orocfc of (�roonhon,
JGREENHECK Airflow Switch-M
Prevents heater from being energized when the fang
is not on. Non adjustable airflow switch requires a � �
minimum of.07 in. we pressure.
P;,
[ REENHECK Control Transformer
Utilized when control voltage differs from line
voltage. Primary over current protection. Class 1
units must have primary side protection by fusing.
Class 2 units have internal protection and do not
require additional fusing unless specified.
�' v 3 xi
,lei ,,.
1-74 GREENHECK Disconnect Switch
Available unfus e door inelo king discand
switch (m aximum 38 4AMPS. ¥ .
\ \
« «+ƒ
/a.. .
. ��.
��.
y. p >
fGREENHECK Solid State Relay (SCR or SSR)
Solid state relays(SCRs or SSR) provide the finest -
in electric duct heater control. 100% solid state - .,. - -°
stepless modulation. Noiseless. Power and heat
output precision.
-t
r
1: 7,,' 11 ', ,''''
# ,�,R Ff6
Y cf $
i $
4 b
,
CEILING HEATERS •
CDF SERIES UH-1-101
COMMERCIAL DOWNFLOW CEILING HEATER
t�F� ' e S
;
IDEAL SPACES ■ CDFSE "surface enclosures"are designed to mount flat on the ceiling
• Bathrooms • Lobbies and extend only 6 in. into the room
• Offices • Waiting Rooms ■ CCFRE "recessed enclosures" have no protrusions outside recess box,
• Conference • Entrance Ways allowing the heater to recess only 7 in. into ceiling space. Mounts in
Rooms T-Bar or permanent ceiling with trim ring
■ 208V and 240V heaters can be field-converted from single-to three-
COLORS phase operation. 5,000-watt heater can be field-converted to 3,800 or
• Navajo White • Northern White 2,500 watts and 4,000-watt heater to 3,000 or 2,000 watts
RECESSED ■ BMS-compatible with use of relays
• 23-3/4"W x 23-3/4"L x 7" D • Three adjustable airflow patterns from 14 ft. ceilings: wide, narrow or
asymmetrical patterns
TEMP RANGE • Automatic fan delay eliminates cold drafts on start-up and discharges
• 45°-90°F residual heat from the heater body during shut down
CFM ■ Automatic thermal cutout: shuts off the heater in the event of over-
heating and reactivates heater when temperature returns to normal
• 300
IS Easy installation:Thumb pins align and temporarily hold enclosure
cover to heating section freeing both hands to finish installation
1_4-----------\ x....,,,i ,,,‘,. y
12:MIN.riVil/'{ __ �'' 4�.5*3
g:tii .(4IIMM�� 24'MI!j l :,yx4,i 1 y/'
M6Y.(4KW)
`'i y'- . ,, g33(•C"....+�Y 24"MIN(5M)
',A5YEAR ' WALL YEAR 2 MIN(KMn
za°MiN.(5Kw WALL
C (21 us WARRANTY WARRANTY WALL WALL
ELEMENT WORKMANSHIP
I •
www.qmarkmep.com
For Technical Services, Call 800-642-4328 MARK
ITEM#QFLY CDF_1217-1 A Marey Engineered Products Brand
e
CEILING HEATERS
CDF SERIES
COMMERCIAL DOWNFLOW CEILING HEATER
MODELS &SPECIFICATIONS
CATALOG I BTU/HR SHIP WT.
NUMBER UPC MOUNTING KW (O�) AMPS VOLTS , PHASE I CFM (LBS.)
CDF548 6 85360 01510 1 19.2/14.2/9.6 208 1-3
COF542 6 85360 01508 8 4/3/2 13.7/10.2/6.8 16.7/12.5/8.3 240 1-3 300 27
CDF547 6 85360 01509 5 14.4/10.8/7.2 277 1
CDF558 6 85360 01513 2 Heater Section Only 24/18.3/12 208 1-3
CDF552 6 85360 01511 8 5/3.8/2.5 17,1/13/8.5 20.8/15.8/10.4 240 1-3 300 27
CDF557 6 85360 01512 5 18.1/13.7/9 277 1
ACCESSORIES
CATALOG UPC DESCRIPTION SHIP WT.
NUMBER (LBS.)
CDFSE 6 85360 01501 9 Surface Mounting Enclosure Only-To Be Used With Above Heater Sections. 10
CDFRE 6 85360 01498 2 Recess Mounting Enclosure Only-To Be Used With Above Heater Sections. 18
CDFSENW 6 85360 14961 5 Surface mounted Northern White-To Be Used With Above Heater Section. 10
Dim.20"L x 16-1/2"W x 5-3/4"D.
CDFRENW 6 85360 14963 9 Recessed mounted Northern White-To Be Used With Above Heater Sections. 18
Dim.23-3/4"L x 23-3/4"W x 7"D.
CDFT 6 85360 01503 3 Thermostat SPST Range 45 to 95'F. 1
COF24R 6 85360 01507 1 Relay(Time Delay 45-60 sec.to close when energized)requires 24 volt supply from remote source. 1
CDFR12 6 85360 01500 2 Relay(Time Delay 45-60 sec.to close when energized)requires 120 volt supply from remote source. 1
CDFDS 6 85360 01496 8 Power Disconnect Switch(3-Pole)30 amps.600 volts,30,60 Hz' 1
CDSTK 6 85360 01504 0 Trim Ring for mounting on permanent ceiling(cannot be factory installed). 1
CDFTR4 6 85360 01505 7 208/240V Primary Transformer/24V sec.and 24V holding coil control relay. 1
CDFTR7 6 85360 01506 4 277V.Primary Transformer/24V sec.and 24V holding coil control relay. 1
NOTE:Factory-wired for highest wattage,field-convertible to lower wattages.Factory-wired 1-PH,field convertible to 3-PH dual-phase units,maximum amp draw is listed.Amperage shown is for single phase.For
factory installation of above controls,additional charges apply.
ADJUSTABLE AIRFLOW OPTIONS
WIDE PATTERN ..41111hillb.. Iddillikb..
(24x8 ft.coverage)
In standard ceiling
matfAvarapplications(8-10 ft.), n fM ysEd er
heater disperses the f �� ASYMMETRICAL
or erY�
air to give a gentle, ' ,, PATTERN
less pronounced pattern 24x8 ft. 17z10 ft. (17x10 ft.coverage)
while circulating all the coverage coverage Heated air is directed
air from floor to ceiling. in a specific direction,
allowing the heater
to be located where
NARROW space allows,with the
PATTERN 111111111111•11! ■I111 heated air delivered to
(8x8 ft.coverage)e) s �i-=f //
where it is required.
For high ceiling
r
applications(11-14 ft.), `'
fan concentrates the 8x8 ft. 17x10 ft.
heated air to ensure full coverage coverage
penetration to the floor level.
•
www.gmarkmep.com
For Technical Services, Call 800-642-4328 MARK
ITEM#QFLY CDF_1217-1 A Marley Engineered Products Brand