Loading...
Report rPS222-6CC/(7 RECEIVED CO® � 7 Zoa� Worldwide www.tyco-fire.com ttsiContacts CITY OF TIGARD 11 ")LDINIG DIVISION' Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB SprinklersIrv-r ,,., ' Description described herein must be installed i .. and maintained in compliance with The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the Upright (TY313) and Pendent (TY323) applicable standards of the National t . i 1 Sprinklers described in this data sheet Fire Protection Association, in addition it.' '* are quick response,standard coverage, to the standards of any other authori- decorative 3 mm glass bulb-type spray ties having jurisdiction.Failure to do so ,,, sprinklers designed for use in light or may impair the performance of these 4, ordinary hazard,commercial occupan- devices. cies such as banks, hotels, and shop- ping malls. The owner is responsible for main- - taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- €tt applicable,is intended for use in areas tor or product manufacturer with any ' ,i 14 with a finished ceiling. This recessed questions. pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed Escutcheon with recessed adjust- Identification , ment up to 5/8 in. (15,9 mm) from '' �` the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed TY313. . . . Upright 5.6K,1/2 in. NPT , Escutcheon with recessed adjust �; ,t s ment up to 1/2 in. (12,7 mm) from TY323. . . .Pendent 5.6K,1/2 in.NPT the flush pendent position. Technical The adjustment provided by the Operation Recessed Escutcheon reduces the Data accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Refer to Table A the rated temperature is reached, the Intermediate level versions of Series fluid expands sufficiently to shatter the TY-FRB Sprinklers are described in Maximum Working Pressure glass bulb, allowing the sprinkler to Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) kler guards and shields are described 250 psi(17.2 bar)' activate and water to flow. in Technical Data Sheet TFP780. •The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psi'%(80,6 LPM/bar'i) The TYCO Series TY-FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Always refer to Technical Data Finishes Sprinkler: the standard installation rules Sheet TFP700 for the "INSTALLER Sprinkler:Refer to Table B recognized by the applicable Listing or WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and corn- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations. to operate in a fire situation or cause Bulb Glass It to operate prematurely. Compression Screw Bronze Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* �r IH 5 -/ 7/16 \ i' 11,1 mm 4 NOMINAL 2" ��fi2IR MAKE IN (5 ,8 mm) L�r g' 2 1 3/83 (50,8mm) (34,9 mm) ENCHATS - 1/2"NPT** DEFLECTOR* - 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant Lo applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the ....... END"A") dance with this section. sprinkler fitting using only the W-Type .� General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE2 Do not install any bulb-type sprin erence to Figure 1,apply the W-Type 6 W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH a loss of liquid from the bulb.With the Torque sprinklers 7 to 14 lb-ft (9,5 to sprinkler held horizontally, a small air 19,0 N•m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor- 3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions. /,,� temperature ratings. Step A. After installing the Style 15 A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the should be obtained by applying a sprinkler threads,and with pipe-thread minimum to maximum torque of 7 to sealant applied to the pipe threads, �, 14 Ib ft(9,5 to 19,0 N m). Higher levels hand tighten the sprinkler into the ` of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairment Step B.Tighten the sprinkler into the PUSH WRENCH of the sprinkler. IN TO ENSURE sprinkler fitting using only the W-Type ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WRENCHING AREA eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m). W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and The Series TY-FRB Upright and finishing,slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. pendent position. Install upright sprin- klers in the upright position. TFP172 Page 3 of 4 Care and 2-7/8"DIA. _ (73,0 mm) Maintenance 2-1/4"DIA. — The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. i' 1 NI FLUSH Before closing a fire protection system 3/8±5/16" —� main control valve for maintenance (9,5±7,9 mm) 1 471 a '/ / work on the fire protection system } / J� that it controls, obtain permission to '•' shut down the affected fire protection MOUNTING 3 21/m Im systems from the proper authorities SURFACE ( ) and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TY FRB PLATE Absence of the outer piece of an 3/4"(19,1 mm) escutcheon, which is used to cover FIGURE 4 a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only 2-7/8"DIA. _ cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA. vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" 12,7 leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"( mm) corrosion must be replaced. FLUSH Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. } / i Modified sprinklers must be replaced. MOUNTING 1/8" Sprinklers that have been exposed to SURFACE (3,2 mm) corrosive products of combustion, but have not operated,should be replaced if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Limited Recessed Escutcheon be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has Warranty eon with(specify")finish,P/N(specify*) lost liquid from its bulb. (Ref. Installa- 7 Specify: Style 20 Recessed Escutch- tion Section.) For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify*) The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices Ordering Sprinkler Wrench in compliance with this document, as Specify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order,indicate having jurisdiction.Contact the install- the full product name and Part Number ing contractor or product manufacturer (p/N) with any questions. Automatic sprinkler systems are rec- Sprinkler Assemblies with NPT ommended to be inspected, tested, Sread Connections or and maintained by a qualified Inspec- Specify:PendentSeries TY-FRB Upright IN tion Service in accordance with local K=5.6,(sp5 QuickSprinkler,p SIN requirements and/or national codes. (specify),) mea Response, (specify) temperature rating, (specify) finish, P/N (specify,refer to Table A). TFP172 Page 4 of 4 SPRINKLER FINISH(See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERc FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY313) and 175°F(79°C) Yellow 1,2,3,4,5,6 PENDENT 200°F(93°C) Green 5.6 (TY323) 1/2 in.NPT 286°F(141°C) Blue 135°F(57°C) Orange RECESSED )PENDENT (155°F 68°C Red TY323 ( ) 175°F(79°C) Yellow 1,2,3,4 Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable. c. Frame and Deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/Na 77 — XXX — X — XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS • 370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C) POLYESTER Notes: SIGNAL WHITE(RAL9003) a. Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C) 77-370-4-175-I 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYESTER 9 CHROME PLATED 286 286°F(141°C) • Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION • 1400 Pennbrook Parkway,Lansdale,PA 19446 1 Telephone+1-215-362-0700 ^ ^ I f��' C 2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Joh11So11 k`(/ NATIONAL FIRE PROTECTION ASSOCIATION end NEPA are registered trademarks of National Fire Protection Association; Controls TEFLON is a registered trademark of DuPont