1) Vesda-VEP-A10-P-Aspirating Smoke Detector
2) Vesda-VPS100-US-120-Vesda Power Supply 120v
VESDA-E VEP •xtralis
VEP-A00-1P, VEP-A00-P, VEP-A10-P
The VESDA-E VEP series of smoke detectors bring the latest
and most advanced detection technology to provide very early
warning and the best nuisance alarm rejection to a wide range
of applications. Built on the Flair detection technology and years
of application experience,VEP detectors achieve consistent
performance over their lifetime via absolute calibration.In addition,
the VEP delivers a range of revolutionary features that provide user
value.
Flair Detection Technology
Flair is the revolutionary detection chamber that forms the core of the VESDA-E VEP,providing higher stability and
increased longevity.Direct imaging of the sampled particles using a CMOS imager combined with multiple photo-
diodes allows better detection and fewer nuisance alarms.
Installation, Commissioning and Operation
VESDA-E VEP is equipped with a powerful aspirator that enables use of a total of 130m(427ft)of sampling pipe
in the one pipe model and 560m(1,837ft)of pipe in the four pipe model.Out of box operation is made possible
with AutoConfig which allows airflow normalisation and AutoLearn Smoke and Flow to be initiated from within the
detector.VEP is fully supported by the ASPIRE and Xtralis VSC software applications which facilitate ease of pipe
network design,system commissioning and maintenance.
VESDAnetTM
VESDA devices communicate on VESDAnet which provides a robust bi-directional communication network allowing
continued redundant operation even during single point wiring failures.VESDAnet enables primary reporting,
centralized configuration,control,maintenance and monitoring.
Ethernet connectivity
VESDA-E detectors offer connectivity to corporate networks via Ethernet,allowing for devices installed with Xtralis
monitoring and configuration software to connect to the detector.
Backward Compatibility
VESDA-E VEP is compatible with existing VESDA installations.The detector occupies the same mounting footprint,
pipe,conduit and electrical connector positioning as VESDA VLP.VEP is also compatible with existing VESDAnet
installations allowing monitoring of both VESDA-E and legacy detectors via the latest iVESDA application.
s MIAMMISMWOMMI100F5W01, 3PO4.414,,a wn5 a=.}'4b'.;ru.,+x'trr'*4i'RY k'A .cnr,,,ViNti,A,..tit :G"`d./t414)4„v ?...e Yik.KOPIA;N5^s £
Features stick
• Suitable for Class 1 Division 2 applications-Groups A,B,C&D • Two programmable GPIs(1 monitored)for flexible remote control
• One and four pipe models for different applications • Field replaceable sub-assemblies enable faster service and
• Flair detection technology delivers reliable very early warning in a maximum uptime
wide range of environments with minimal nuisance alarms Listings /Approvals
• Multi stage filtration and optical protection with clean air barriers UL
ensures lifetime detection performance • ULC
• Four alarm levels and a wide sensitivity range deliver optimum • CSFM
protection for the widest range of applications • FM
• Intuitive LCD icon display provides instant status information for VdS
immediate response • NF-SSI(www.marque-nfcom)
• Flow fault thresholds per port accommodate varying airflow • VNIIPO
conditions • CE
• Smart on-board filter retains dust count and remaining filter life ActivFire
for predictable maintenance • CCC
• Extensive event log(20,000 events)for event analysis and system . EN 54-20,ISO 7240-20
diagnostics Four Pipe VEP
• AutoLearn° smoke and flow for reliable and rapid commissioning EN 54-20,ISO 7240-20
• Referencing to accommodate external environmental conditions - Class A(40 holes/Fire 1-0.028%obs/m)
to minimise nuisance alarms - Class B(80 holes/Fire 1-0.027%oobs/m)
• Backward compatible with VLP and VESDAnet - Class C(100 holes/Fire 1=0.056%obs/m)
• Remote monitoring with iVESDA for system review and proactive Classification of any configuration is determined using ASPIRE.
maintenance
• Ethernet for connectivity with Xtralis software for configuration, Regional approvals listings and regulatory compliance vary between product
secondary monitoring and maintenance models.Refer to www.xtralis.com for the latest product approvals matrix.
• USB for PC configuration,and firmware upgrade using a memory
VESDA-E VEP •
4) xtralis
TEC - LAICAL SPECIFICATIONS
Specifications 3.5" Display
One Pipe VEP Four Pipe VEP
Supply Voltage 18-30 VDC(24 V Nominal) el VEP,'Of Zone Number]A Zune Name
Power Consumption® 0.1100% l:
24VDC VEP-A00-1P VEP-A00-P VEP-A10-P
Aspirator Setting Fixed 1 5 1 5 ® '1* Flo
Power(Quiescent) 8.8 W 7.0 W 8.8 W 8.2 W 10.0 W i`/ �.,
Power an Alarm) 9.6 W 7.8 W 9.6 W 10.4 W 11.6 W
Dimensions(WHD) 350mmmx225 min x135mm(13.8inx8.9inx5.3in)
Weight 4.4 kg(9.7 lbs) 4.4 kg(9.7 lbs) 4.5 kg(9.9 lbs)
LED Description
Ambient:0°C to 39°C(32°F to 102°F)
Sampled Air:-20°C to 60°C(-4°F to 140°F) fl Fire 2
Operating Conditions Tested to:-20°C to 55°C(-4°F to 131°F)
UL:-20°C to 50°C(-4°F to 122°F) IlaFire 1
Humidity:50/0to 950/0 RH.non-condensing --
i
1.000 mz A Action
Area Coverage 2,000 m2(21,520 sq.ft) --
(10.760 sq.ft)
0 Alert
Min.airflow per pipe 15 Vrn
_._._' Pipe Length(Linear) 100 m(328 ft) 280 m(919 ft) CI Disabled
Pipe Length(Branched) 130 m(427 ft) 560 m(1.837 ft) Ii Fault
1 Pipe 1 Pipe 2 Pipe 3 Pipe 4 Pipe
Power
Pipe lengths depending on 1__........__....._....-
number of pipes in use 100 m (328 ft) 110 m 100 rn 80 m 70 m
(361 ft) (328 ft) (262 ft) (230 ft)
StaX PSU PSU.Auto Pipe Clean Home Page
No.of holes(A/B/C) 30/40/45 40/80/100 Icon on Display Description
Computer design tool ASPIRE r Smoke and Alarm Threshold Levels
Inlet:External diameter 25 mm or 1.05 in(3/4 in IPS) - -
Pipe Exhaust:External diameter 25 mm or 1.05 in(3/4 in IPS)via ✓') Detector OK
adaptor - --
7 programmable relays(latching or non-latching states) Detector Fault
Relays ----
Contacts rated 2 A a 30 VDC(Resistive)
IP rating IP40 Aspirator Fault
Cable access 4 x 26 mm(1.02 in)cable entries Airflow Fault
Cable termination Screw Terminal blocks 0.2-2.5 sq mm(24-14 AWG) Power Fault
Dynamic Range 0.000%/m to 320/0/m(0.00000/0/ft to 10%/ft) --
Sensitivity Range 0.005 to 20%obs/m(0.0016%to 6.25We obs/ft) • Filter Fault
Alert:0.005%to 2.0%obs/m(0.0016%to 0.625%obs/ft) AGO Smoke Chamber Fault
Threshold setting range Action:0.005%to 2.00/0obs/m(0.0016%to0.6253/c obs/ft) r
Firel:0.010%to 2.0/o obs/m(0.0031/o to 0.6255/o obs/ft)
Fi re2:0.0200/0 to 20.00/0 obs/m(0.0063%to 6.25%obs/ft) oga VESDAnet Fault
Event log:Up to 20,000 eventsIV StaX Module Fault
Smoke level,user actions,alarms and faults with time and
Software features date stamp
AutoLearn:Detector learns Alarm Thresholds and Flow Fault
thresholds by monitoring the environment. Ordering Information
Ordering Code Description
Spare Parts VEP-A00-1P VESDA-E VEP with LEDs,I pipe.Plastic Enclosure
VSP-960 VESDA-E Mounting Bracket VSP-964-03 /ESDA-E Smoke Detection Chamber VEP-A00-P VESDA-E VEP with LEDs.4 pipe.Plastic Enclosure
i -_.._- -AAK3
--- -- ----- VESDA-E VEP with 3.5'Display.4 pipe,Plastic
VSP-961 VESDA-E Exhaust adaptor US VSP-965 VESDA-E Sampling Module VEP-AIO-P Enclosure
VSP-962 , VESDA-E Filter VSP-968 VESDA-E VEP-A00-P/1P Front Cover
Plastic(LEDs) Approvals Compliance
- - VESDA-E`✓EP-AIO-P Front Cover VSP-962-20 VESDA-E Filter-20 Pieces VSP-969 Plastic(3.5'Display) Please refer to the Product Guide for details
VSP-963 VESDA-E Aspirator VKT 850 VESDA-E VEP Demo Kit regarding compliant design,installation and
�__. - commissioning.
VSP-964 VESDA-E Smoke Detection Chamber
www.xtralis.com
geci-
_ , ✓ou ,,-.r:!_= Oti. x-r-cate is'e p'J - 13u[ - .mute ,. <<e , ..;f.:- sny
` .Jdii-
Power Supply
VESDA Accessories VPS-100US & VPS-300US
The VESDA Power Supply is capable of Features
providing operating power including battery • Input 120VAC/60Hz
backup for the entire VESDA Laser Smoke
Detector product line.The VESDA Power • 1.5 amp continuous supply current at
Supply has been designed to power a single 27.6VDC
unit to multiple units depending on application • Filtered and electronically regulated
needs. It provides 24 volt operating power ' output
to the VESDA system as well as a battery xtr, - • AC fail supervision
charger function which supervises and • Low AC (brown-out)supervision
maintains the standby batteries. Consult
"Power Supply Capabilities"for details. • Battery supervision
Installation • Built-in charger for sealed lead acid
or gel-type batteries
The VESDA Power Supply models VPS-100US and VPS300US are power-limited • Automatic switch over to standby
power supplies.They convert 120VAC/60Hz input into 24 VDC power-limited battery when AC fails
outputs.The VPS units are intended for use in applications requiring UL, ULC and • AC input LED indicator
CSFM listing for fire protection signalling.
The VPS-100US or VPS-300US shall be installed in accordance with the National
Electric Code(NFPA 70)and in accordance with any local regulations. See wiring Listings/Approvals
diagrams for proper assembly.
• UL 1481 listed
Fault Reporting • ULC
A Power Supply Fault indicator is provided via a dry relay contact(Form C),which • FM (for VPS-100US)
changes state due to the following conditions: • CSFM
• AC input loss
• Low AC input voltage(Brown-out)
• Loss of battery voltage
• A short circuit of the battery leads
• A short circuit of any of the DC power outputs
Power Supply Capabilities
VESDA VLP or LaserSCANNER*
VPS-100US-XXX provides power for: 1 VESDA VLP or LaserSCANNER, or up to
5 remote(single box)units, or 1 subrack assembly.
Battery requirements: (2) 12 volt/12 Amp-hour batteries.
VPS-300US-XXX provides power for: up to 3 VESDA VLP or LaserSCANNER
detectors,or up to 15 remote(single box)units,or up to 3 subrack assemblies.
Battery requirements:
• 2 detectors or 2 subracks or 10 remotes require(4) 12volt/12 Amp-hour batteries
• 3 detectors or 3 subracks or 15 remotes require(6) 12volt/12 Amp-hour batteries
VESDA VLC*
VPS-100US-XXX provides power for: up to 2 VESDA VLC detectors, or up to
5 remote(single box)units,or 1 subrack assembly.
Battery requirements: (2) 12volt/12 Amphour batteries.
VPS-3000S-XXX provides power for: up to 6 VESDA VLC detectors,or up to t Must be confirmed with a battery calculation
compliant with local fire protection codes and
15 Remote(single box)units,or up to 3 subrack assemblies. Battery requirements: standards.
• 4 detectors or 2 subracks or 10 remotes require(4) 12volt/12 Amp-hour To facilitate the calculation of the back up battery
batteries size,refer to the Battery Calculator(Document
21062),available from Xtralis Partner Extranet
• 6 detectors or 3 subracks or 15 remotes require(6) 12volt/12 Amp-hour (www.xtralis.com)
batteries
VESDA
by•xtralis
Power Supply
VESDA Accessories VPS-100US & VPS-300US
VESDA VLF-250* Specifications
VPS-1000S-XXX provides power for 2 VESDA VLF-250 detectors, or up to Components
5 remote(single box)units,or 1 sub rack assembly. The VPS-100US consists of three main components:
Battery requirements: (2) 12 volt/ 12 Amp-hour batteries. the mounting enclosure,the transformer and the main
VPS-300US-XXX provides power for 6 VESDA VLF-250 detectors, or up to circuit board.It uses two backup batteries(supplied
15 remote(single box)units,or 3 sub rack assemblies. Battery requirements: separately).
The VPS300US consists of one VPS-100US Power
• 4 detectors or 2 sub racks or 10 remotes require(4) 12 Volt/ 12 Amp-hour Supply and one VBC-001 Battery Cabinet.Together
batteries the two units can hold up to 6 batteries(supplied
• 6 detectors or 3 sub racks or 15 remotes require(6) 12 Volt/ 12 Amp-hour separately).
Note:The VESDA Power Supply uses sealed acid,
batteries 12VDC,12 Amp/hour batteries.To order,use part
VESDA VLF-500* number VBT-012(minimum 2).
VPS-1000S-XXX provides power for 1 VESDA VLF-500 detector,or up to 5 remote Input
(single box)units, or 1 sub rack assembly. 120 vac(+1 o•ie/-lser); 60Hz;1.4 amp max.
Battery requirements: (2) 12 volt/12 Amp-hour batteries. Output
27.6 VDC(Nominal)1.5 Amps(Max.)
VPS-3000S-XXX provides power for 3 VESDA VLF-500 detectors,or up to Max.output Current when a single 24 VDC output is
15 remote(single box)units, or 3 sub rack assemblies. Battery requirements: used:
• 2 detectors or 2 sub racks or 10 remotes require(4) 12 Volt/ 12 Amp-hour 1.2 amps
batteries Max.output when the three 24 VDC outputs are used:
0.500
• 3 detectors or 3 sub racks or 15 remotes require(6) 12 Volt/ 12 Amp-hour Amps per output
Dimensions(WHD)
batteries 13.9 in.x 9 in.x 4.5 in.
Weight
♦° POWER SUPPLY ° 1 VPS-100 US 10Ibs.without batteries
0 DO *17 VBC-001 sibs.without batteries
�J ti l Transformer 1
Power r ® •°u1 0 rtll -- 1%/ Operating Temperature
limited 1 ;o„ 0• 121 ,� Power supply ambient:32°to 120°F
outputs
fr r:a13 �, '^°ale�"w •,• "" To 120VAC/60HZ Humidity:10-95%RH,non-condensing
I au I OM Connect to dedicated
0 -BAT. o branch circuit for fire Humidity
alarm use 10-95%RH,non-condensing
Trouble Relay
Common trouble relay rated 2A @ 30VDC
Q+b Battery 0 Battery (Form C:NO/NC)
12V/12AH 12V/12AH
During normal operation,the power supply Fault
1!,
�I�p �� Reporting Relay is energized.
Cable Access
3/4"knockouts in various positions
VPS-10o us Cable Termination
Screw terminal blocks
4 30-12 AWG
ili
p 12 V/12 BatteryAH 12 V/12 O BatteryAH Ordering Information
c) _ 0(�— PIN Description Requirements
VPS-100US-XXX Power Supply Use XXX field
to specify input
voltage:120 or
220 VAC
VPS-3000S-XXX Power Supply Use XXX field
0 p Battery Q a Battery Model VPS- to specify input
12 V/VAN 12 V/12 AH 100US-XXX voltage:120 or
U i 1 0
and Battery 220 VAC
p p Cabinet model
VBC-001
vac-001 VBT-012 Battery, Minimum of 2
sealed lead required
acid,12 VDC,
12 Amp/hr
www.xtralis.com
UK and Europe+44 1442 242 330 Tdhe Americas+1 800 229 4434
Middle East+962 6 588 5622 Asia+86 21 5240 0077 Australia and New Zealand+61 3 9936 7000
The contents of this document are provided on an"as is"basis.No representation or warranty(either express or implied)is made as to the completeness,
accuracywithout or reliability n ti the contentsepta of this ise documentedThe, manufacturer reserves the right,to change uns orfspecifications mp)without obligation
VESDA
and hntafurther tact.Except as otherwise se areeall warranties,express or the ight including without limitation any implied warranties of
merchantability and to71-for a panicular purpose are T,PNr/ s)y excluded.
Xtralis,the Xtralis logo,The Sooner You Know,VESDA-E,VESDA,ICAM,_CO,Oslo,HeiTel,ADPRO,IntrusionTrace,LoiterTrace,ClientTrace,
SmokeTrace,X0a,XOh,iTrace,iCommand,Respond,iCommission,iPIR,and FMST are trademarks and/or registered trademarks of Xtralis and/or its l.,subsidiaries in the United States and/or other countries.Other brand names mentioned herein are for identification purposes only and may be trademarks by• Xtralis
of their respective hoiderts).Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/
or label.
This document is subject to copyright owned by Xtralis.You agree not to copy,communicate to the public,adapt,distribute,transfer,sell,modify or
publish any contents of this document without the express prior written consent of Xtralis.
Doc.13986 03 Part:18624