THE ACTIVATION OF A DUCT
S / SMOKE DETECTOR SHALL
ACTIVATE A VISIBLE AND
7� 32 _nSeS Ct�f' LE SUPERVISORY
SIGNAL AIB AT A CONSTANTLY
� DY1
ATTENDED LOCATION
/� C3f ( 1 ,( OMSC 606.4.1
<� PJ I ❑ �� / r3
I � _
OFFICE CaPv
OF TIGARD,,
laic-r- FUR CODE COMPL3ANCE
P Approoed: "NI
C 1
C. I
permit#: m,
Adclres u
Suite#s
N Sn�r Data
U
00
o co:00
00
tr) o :D0 M N
0 ; coLLI v O
00 /" Q
In
1 X I Ventilation Requirements- based on 2019 GMSC table 403.3 Q
L) O
RTU1 and 2 single zone retail (n
12000 sft breathable zoneU
L L
Persons-7.5 cfm X 15p/1000sft= 1350 cfm M M
-i Area-0.12 cfm/sft= 1440 cfm = 2 CSA
Vbz =2790 cfm v N F—
Ez = 0.8 (supply and return in ceiling) N 0
Voz= 3488 cfm
O \ ` PJ p A RTU1 and 2 (each)- L 0
SA = 8000 cfm M
RA= 6200 cfm
OSA= 1800 cfm
Latimer HVAC
0
01 HEATING•VENTILATION•AIR CONDITIONING
Z
V Scooe of Work
0- m °' m
I J PJ OD Latimer HVAC will perform the following scope of work:
00
o j 01. Provide and install new rooftop gaspack unit on existing curb. Use curb clips. Replacing existing
v / units like for like.
2. Gas piping final connection at new RTU.
i w g
00
Enuioment Schedule
RTU7,2-. Trane YSD240G4RLC- 20-ton nominal. 460/3/60- 52 MCA, 70 MOCP. 255.72 Mbtu gross
cooling- 10 EER, 12.4 leer. 250,000 Btu input gas. 80%TE. 8000 cfm. 5HP indoor fan motorincludes !
i' economizer, power exhaust, smoke detectors.
1
Net weight of new unit = 1977# net. Old unit- 2025#. i
f '
Mechanical General Notes:
j 1. Cooling equipment does not exceed the load of the calculated requirement.
t -- -- —
--:� 2. Existing programmable thermostat. 5 degree deadband minimum. 7 day. Microprocessor. Set program for
night 3. Fanmotor energy
does not exceed allowable,first available above BHP.
4. Max leakage rate of OSA or exhaust dampers to be 4 cfm/sft @ 1.0 sp.
5. Provide O and M to building owner.
a
4A)
M 1 .