RED HAWK FIRE PROTECTION, LLC
3801 Fruit Valley Rd.
Vancouver, WA 98660
(360) 984-3712 RECEIVED
FEB 12022
GUY OF TIGARD
lupLDlnlr, nlvnslo0
))),
•fifrei6 Xplaire
FIRE SPRINKLER
EQUIPMENT SUBMITTAL
FOR
PROVIDENCE CREDENA MAIL ORDER PHARMACY T.I.
PORTLAND, OR
• RHFP JOB NO. 240295
TABLE OF CONTENTS RED HAWK
1J1 FIRE PROTECTION, LLC
Section 1 - Pipe and Fittings
Description Comments
schedule 40 Blk. Pipe
Victaulic 920 Threaded&Grooved Mecanical Tee
Section 2 - Hangers and Sway Bracing
Description Comments
Erico Hanger Ring
Sammy_Sidewinders
Section 5 - Fire Sprinklers
Description Comments
Tyco TY-B Standard Response Upright/Pendent_K=5.6
Tyco DS-1 Dry Pendent_K=5.6
Comparative Specification Data
Specification A53 NPS 1/0-26 STD,XS and XXS,ANSI Schedules 10 through 160
110 Covers Seamless and Welded,Black and hot-dipped galvanized nominal(average)wall pipe for coiling,bending,flanging and
Scope other special purposes and is suitable for welding.Continuous-Welded pipe is not intended for flanging.Purpose for which pipe is
intended should be stated on the order
Kinds of Steel Permitted Open-hearth
for Pipe Material Basic-Oxygen
Electric-Furnace
Hot-Dipped Galvanized Sets standards for coating of pipe with zinc inside and outside by the hot-dipped process.Weight of coaling must not average
less than 1.5 oz per square foot and not less than 1.6 oz per sq foot
Permissible Variations in The minimum wall thickness at any point shall not be more than 12.5%under the normal wall thickness specified
Wall Thickness
CMax% MnMax% PMax% SMax%
Seamless or ERW
Chemical Requirements Grade A 0.25 0.95 0.05 0.06
Grade B 0.30 1.20 0.05 0.06
Continuous Weld - - 0.06 0.06
Seamless and Electric
resistance-welded
Tensile Requirements Grade A Grade B
Tensile Strength,Min psi 45,000 48,000 60,000
Yield Strength,Min psi 25,000 30,000 35,000
Hydrostatic Testing Hydrostatic inspection test procedures for plain end and threaded and coupled pipe are specified.Hydrostatic pressure shall be
maintained for not less than 5 seconds for all sizes of seamless and electric resistance weld pipe
Permissible Variations in Plus or Minus 10%
Weight per Foot
Outside Diameter at any point shall not vary from standard specified more than-
Permissible Variations in For NPS 1 1/2 and Smaller Sizes For NPS 2 and Larger Sizes
Outside Diameter 1/64"over 1/32"under 1%over 1%under
Tensile Test-Transverse required on ERW for NPS 8 and larger
Banding Test(Cold)-STD and XS-NPS 2 and under XXS-NPS 1 1/4 and under
ilkMechanical Tests Dearee of Bend Diameter of Mandrel
Specified For Normal A53 Uses 90 12 x nom dia of pipe
For Close Coiling 180 8 x nom dia of pipe
Flattening Test-NPS 2 and larger STD and XS.(Not required for XXS Pipe)
Seamless and Electric-Resistance-Welded Bending,flattening,tensile on one length of pipe from each lot of 500
lengths or less of a size
Number of Tests Required
Continuous-Weld-Bending,Flattening,Tensile NPS 1 1/2 or smaller NPS 2&Lamer
one/25 long one/50 tons
Standard Weight
Single Random-15'-22'may be jointers.If plain ends 5%may be 12'-16'
Double Random-Shortest Length 22',minimum average for order 35'
Lengths Extra Strong&Double Extra Strong
Single Random-12'-22'.5%may be 6'-12'
Double Random-(XS and lighter)-Shortest Length 22".Minimum average for order 35'
Lengths longer than since random with wall thinness heaver than XS subject to negotiation
Rolled,Stamped,or Stenciled(Mfgr's option)
Required Markings on Name or brand of manufacturer
Each Length
(On tags attached to each Kind of pipe that is,Continuous Welded,Electric-Resistance-Welded A,Electric-Resistance-Weeded B, Seamless A;or
bundle in case of bundled Seamless B:XS for double extra strong
pipe) ASTM A 53
Length of Pipe
Couplings-Applied handling tight.Couplings 2"and smaller,straight tapped other sizes type
Thread Protection-Applied to pipe 4"and larger
General Installation End Finish(Unless otherwise specified)-STD or XS or wall thickness less than 0.500 in.(Excluding XXS);plain end beveled.All
XXS and wall thicknesses over 0.500 in.Plain end square cut.
S
NOTE: This information is from ASTM Standards.
Please refer to the specific Standard or Specification for complete details
Comparative Specification Data
Specification A135 NPS 1/4-30",Schedules 10,40 and XL THD Lightwall
Scope Covers two grades of electric-resistance welded steel pipe.Grade A is adapted for flanging and bending and is suitable for
welding.Purpose for which pipe is intended should be stated on order
Kinds of Steel Permitted Open-hearth
for Pipe Material Basic-Oxygen
Electric-Furnace
Permissible Variations in The minimum wall thickness at any point shall not be more than 12.5%under the normal wall thickness specified.Threadable,
Wall Thickness lightwall(XL)must meet manufacturers minimums.
C Max% Mn Max% P Max% S Max%
Chemical Requirements Grade A 0.25 0.95 0.05 0.06
Grade B 0.30 1.20 0.05 0.06
Grade A Grade B
Tensile Strength,Min psi 48,000 60,000
Yield Strength,Min psi 30,000 35,000
Hydrostatic inspection test procedures for plain end and threaded are specified.Hydrostatic pressure shall be maintained for not
Hydrostatic Testing less than 5 seconds for all sizes of electric resistance weld pipe.Non-Destructive electric test should be in accordance with
practices E213,method E273 or proactive E213
Permissible Variations in Plus or Minus 10%Schedule 10
Weight per Foot Plus 10%minus 3 1/2%Schedule 40
Permissible Variations in Plus or Minus 1%
Outside Diameter
Mechanical Tests Tensile Test-Transverse returned on pipe NPS 8 and larger
Specified Flattening Test-Three steps required with weld located 8"or 90*from the line of direction of force required
Number of Tests Required Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style
Lengths Pipe shall be furnished in 38"with a minimum of 20 ft.Pipe furnished to schedule 10 shall be in a specified length between 15
and 22 ft.
Required Markings on Rolled,Stamped,or Stenciled(Mfgr's option)
Each Length Name or brand of manufacturer
(On tags attached to each Kind of pipe that is,Electric-Resistance-Welded A,Electric-Welded B,same schedule wall thickness,schedule 10 or 40,NL
bundle in case of bundled ASTM A135
pipe) Length of Pipe
General Information End Finish may be plain end beveled or plain end square cut _
•
NOTE: This information is from ASTM Standards.
Please refer to the specific Standard or Specification for complete details
Comparative Specification Data
Specification A795 NPS 1/2-10"Schedule 10 and Schedule 40
1111 Covers Seamless and welded,black and hot-dipped galvanized nominal wall pipe for coiling,bending,flanging and is suitable
COpa for welding.Pipe ordered for this specification is intended to be used in fire protection systems
Kinds of Steel Permitted Open-hearth
for Pipe Material Basic-Oxygen
Electric-Furnace
Sets standards for coating of pipe with zinc inside and outside by the hot-dipped process.Weight of coating must not average
Hot-Dipped Galvanized less than 1.5 oz per square foot and not less than 1.6 oz per sq foot
Permissible Variations in The minimum wall thickness at any point shall not be more than 12.5%under the normal wall thickness.
Wall Thickness
C Max°/Q MnMax% PMax% SMax%
Seamless or ERW
Chemical Requirements Grade A 0.25 0.95 0.05 0.06
Grade B 0.30 1.20 0.05 0.06
Continuous Weld - - 0.06 0.06
Hydrostatic inspection test procedures for plain end and threaded are specified. Hydrostatic pressure shall be maintained for not
Hydrostatic Testing less than 5 seconds for all sizes of seamless and electric resistance weld pipe.Non destructive electric test in accordance with
practices E213 or E309
Permissible Variations in Plus or Minus 5%
Weight per Foot
Permissible Variations in Outside Diameter at any point shall not vary from standard specified more than-
Outside Diameter For NPS 1 1/2 and Smaller Sizes For NIPS 2 and Larger Sizes
1/64"over 1/32"under 1%over 1%under
Number of Tests Flattening-Tests are to be performed on electric-resistance welded pipe,and furnace welded pipe.
Required
Lengths Unless specified,pipe shall be furnished on single random lengths of 16 to 22 ft.
Rolled,Stamped,or Stenciled(Mfgr's option)
Required Markings on Name or brand of manufacturer
ch Length Electric-Resistance-Welded A,Electric-Resistance-Weeded B,Seamless A
n tags attached to each
bundle in case of bundled Seamless B,Grade A or B for type E or S pipe,wall thickness schedule ASTM A795,the letters NHII Not hydrostatically tested
Pipe)
Length of Pipe
General Installation End finish may be plain end beveled or plain end square cut
•
NOTE: This information is from ASTM Standards.
Please refer to the specific Standard or Specification for complete details
CARBONS - - .• -:•r *wrirmill
Mechanical-1F' Bolted Branch Outlets 0 m Q (UdS) LPCB
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STYLES 920 AND 920N
•
Victaulic Mechanical-To Outlet provides a direct branch connection at any location a hole can
be cut in pipe. The hole is cut oversize to receive a "holefinder"locating collar which secures
the outlet in position permanently.A pressure responsive gasket seals on the pipe O.D.
Cross-type connections can be achieved by utilizing two upper housings of the same style and
size,with the same or differing branch size connections. NOTE: Style 920 and Style 920N 411
housings cannot be mated to each other to achieve a cross connection.
Style 920 and Style 920N Mechanical-T outlets are available with grooved or female threaded STYLES 920 AND 920N STYLE 920 CROSS
outlet.Specify choice on order. Units are supplied painted with plated bolts.Galvanized hous- PATENTED
ings are available,supplied with plated bolts.
All sizes of Style 920 and 920N are rated at 500 psi/3450 kPa working pressure on Schedule
10 and 40 carbon steel pipe.They may also be used on high density polyethylene or poly-
butylene(HDPE)pipe. Pressure ratings on HDPE are dependent on the pipe rating. Contact
Victaulic for ratings on other pipe. Style 920 and 920N are not recommended for use on
PVC plastic pipe.
Standard piping practices dictate that the Mechanical-T Styles 920 and 920N must be
installed so that the main and branch connections are a true 90°angle when permanently
attached to the pipeline surface.
Additionally,the Vic-Tap II®hole cutting tool,which allows for hole cutting capabilities on pressurized
systems, utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic-Ball Valve to
create the Style 931 Vic-Tap II Mechanical-T unit.See page 8 for further information.
MATERIAL SPECIFICATIONS Housing/Coating:Ductile iron conforming to ASTM A-536,grade 65-45-12,with orange enamel
coating. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special
request.
• Optional: Hot dipped galvanized
Gasket: (Specify choice*)
• Grade"E" EPDM
EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C.
Recommended for cold and hot water service within the specified temperature range plus a
variety of dilute acids,oil-free air and many chemical services. UL Classified in accordance
with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C. NOT RECOMMENDED FOR
PETROLEUM SERVICES.
• Grade"T"nitrite
Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C.
Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the
specified temperature range. Not recommended for hot water services over+150°F/+66°C or
for hot dry air over+140°F/+60°C.
*Services listed are General Service Recommendations only. It should be noted that there are
services for which these gaskets are not recommended. Reference should always be made to
the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a
listing of services which are not recommended.
Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
REV M
CARBON STEEL PIPE- HOLE CUT PRODUCTS 11.V IIG
1111e1rrhan ral-T® Belted Branch Outlets
STYLES 920 AND 920N
•
DIMENSIONS
Style I Max.Work App,o.
Size No. Pressure@ Dimensions Weight Each
Run x branch " V n IS le Female
Nominal Size r T-^ Thd W Y Z Thd. Grv.
Y .--Z->. Inches orY'psi +0.13 Inches Inches Inches Inches Inches Inches Lbs. Lbs.
min 920N kPa -0.00 min min min mm min min kg kg
r er'- 1 2 x 1/2(a)° 920N 500 1.50 2.00 2.53 - 1.61 5.35 2.75 3.1
V 50 15 3450 38.1 51 64 - 41 136 70
/i 1.5 -
n �'� ur' 3/4(a)° 920N 500 1.50 1.97 2.53 1.61 5.35 2.75 3.1
M,_ 4 W 20 3450 38.1 50 64 - 41 136 70 1.5
1(a)En 500 1.50 1.85 2.53 1.61 5.35 2.75 3.0
25 920N 3450 38.1 47 64 41 136 70 1.4
114(8)to 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2
GROOVED OUTLET 32 3450 44.5 52 70 76 41 136 76 1.7 1.5
11/2(a)to 920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.2
40 3450 44.5 52 70 79 41 136 83 1.7 1.5
c Y > A z 21 IS(a)40 500 1.50 2.21 2.74 - 1.82 5.64 2.75 3.0 _
65 x 15 920N 3450 38.1 56 70 46 143 70 1.4
t PINW
�',(a)§a 920N 500 1.50 2.18 2.74 - 1.82 5.64 2.75 3.0 _
V III rGr T 20 3450 38.1 55 70 46 143 70 1.4
1 1(a)§° 500 1.50 2.06 2.74 _ 1.82 5.64 2.75 2.9= � ,��'. 25 920N 3450 38.1 52 70 46 143 70 1.4
I Pk t(a)° g20N 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.2
1-1 32 3450 44.5 58 76 83 46 160 76 1.7 1.5
FEMALE THREADED OUTLET 1 1/2t(a)a 920N 500 2.00 2.28 3.00 3.25 1.82 6.26 3.25 3.6 3.3
40 3450 50.8 58 76 83 46 159 83 1.7 1.6
Y:(a) 300 150 2.22 2.75 _ 2.25 6.46 3.18 3.9 -
76.1 x 15 920N 2065 38.1 56 70 - 57 164 81 1.8
• Provides a direct branch connection at Y(a) 920N 300 150 2.19 2.75 2.25 6.46 3.18 3.9
any location where a hole can be cut 20 2065 38.1 56 70 - 57 164 81 1.8
in the pipe 1(a) 920N 300 1.50 2.07 2.75 _ 225 6.46 3.18 3.8 -
25 2065 38.1 53 70 57 164 81 1.7 11,
• A pressure responsive gasket provides 11/4(a)0 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.c0 3.5 3.2
the seal 32 3450 44.5 58 76 84 49 160 76 1.6 1.5
1 Yi(a)0 920N 500 2.00 2.28 3,00 3.31 1.92 6.29 3.25 3.5 3.3
• Request Publication 11.03 for 40 3450 50.8 58 76 84 49 160 83 1.6 1.5
Mechanical-T cross assemblies 3 'k(a)° 500 1.50 2.52 3.05 _ 2.28 6.15 2.75 3.4 _
80 x 15 920N 3450 38.1 64 ' 78 58 156 70 1.6
• Pressure rated up to 500 psi/3450kPa /(a)° 920N 500 1.50 2.49 3.05 2.28 6.15 2.75 34
on steel pipe; also available for use 20 3450 38.1 63 78 - 58 156 70. 1.6
with HDPE pipe 1(a) 920N 500 1.50 2.38 3.06 2.28 6.15 2.75 3.3
25 3450 38.1 61 78 58 156 70 1.6
• Sizes from 2 x 1/2"/50 x 15mm 1'Aa(a)to g20N 500 1.75 2.55 3.25 3.56 2.28 6.15 300 3.8 3.7
through 8 x 4"/200 x 100mm 32(b) 3450 44.5 65 83 90 58 156 76 1.8 1.8
1'h(a)ta,, 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8
40(b) 3450 50.8 71 89 90 58 156 83 1.9 1.8
2(a)a 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6
50 3450 63.5 70 89 90 58 172 99 2.3 2.1
31/2 2 500 2.50 3.00 3.75 2.44 6.72 3.88 3.8
90 x 50 920N 3450 63.5 76 95 62 171 99 1.8
IMPORTANT NOTES: TABLE CONTINUED ON PG.3 _
Style 920 and Style 920N housings cannot be '*Center of run to engaged pipe end,female threaded outlet only(dimensions approximate).
mated to one another t Available with grooved or female threaded outlet.Specify choice on order.
to achieve cross connections. t Center of run to end of fitting.
It Female threaded outlets are available to NPT and BSPT specifications.
@ See page 7 for Fire Protection approvals and pressure ratings.
(a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order.
(b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order.
§Vds approved for fire protection services
a LPCB approved for fire protection services
0 Approved for use in China by Tianjin Approvals Company.
•
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iCtauII :'
11.02 2
CARBON STEEL PIPE- HOLE CUT PRODUCTS 1 1•UL
MprhaniiraI-T® Bolted Branch Out!P
STYLES 920 AND 920N
•
__
DIMENSIONS
Style Max.Work Approx.
Size No. Pressure@ Dimensions Weight Each
h
nal.ranc Size. T*- W S
Inches or psi +013 Inches inches')nches Inches Inches Inch-@s "Bs.""
It"' Y s A Z e mm 920N kPa -0.00 mm mm mm mm mm mm kg
_ �1 TABLE CONTINUED FROM PAGE 2
Ak 4
r; V �` 4 x h(a) 920N 500 L50 3.03 3.56 - 2.69 701 2.75 3.7 -
tit ' �-~ Iasi 1 `1 Pi 1� 100 _15 3450 38.1 77 90 68 178 70 1.8
sA(a)❑ 500 1.50 3.00 3.56 2.69 7.01 2 75 3.7 -
I�- -- } dO II 20 920N 3450 381 76 90 68 178 70 1.8
1 � y L 1(a)0 920N 500 1.50 2.88 3.56 _ 2.69 701 275 3.6 _
25 3450 38.1 73 90 68 178 70 1.8
GROOVED OUTLET I'/a(a)to 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 300 4.0 3.6
32(b) 3450 44.5 78 96 102 68 178 76 1.9 1.8
1'h(a)to 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9
4----Y 1 r z sl 40(b) 3450 508 83 102 102 68 178 83 20. 1.9
Pig + 2(a)to 920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6
50 3450 63.5 83 102 102 68 178 99 2.3 2.1
1 Ag .11111111111P1110
•"-"" tal• 7 .-7(Fill 21/2(a)t 920 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0
65 3450 69.9 73 102 102 68 186 118 2.6 2.3
- - ` 500 2.75 2.88 _ 400 2.69 7.34 463 _ 64
76.1 mm: 920
y j I -I 3450 69.9 73 102 68 186 118 2.9
1 L 3(a)t 500 3.50 3.31 4.50 4.12 2.69 7.73 512 84 6.4
80 920 3450 88.9 84 114 105 68 196 130 3.8 2.9
FEMALE THREADED OUTLET
PA(alti 500 1.75 3.08 3.78 - 2.63 7.64 3.05 50 -
108.0 x 32 920N 3450 44.5 78 96 67 194 78 23
1 h(a)o 920N 500 2.00 3.28 4.00 - 2.63 7.64 3.25 5 0
• Provides a direct branch connection at 40 3450 50.8 83 102 67 194 83 2.3
any location where a hole can be cut 2(a) 9zoN 500 2.50 3.25 4.00 2,63 7.64 400 4.0 -
III In the pipe 50 3450 63.5 83 102 - 67 194 102 19
76.1 mm 920 500 2?5 2.88 4.00 4.00 2.63 7.64 4.29 8.0 7.8
• A pressure responsive gasket provides 3450 69.9 73 102 102 67 194 109 36 3.5
the seal 3(a) 920 500 3.50 3.31 4.50 4.50 2.63 7.63 4.88 6.8 6.5
80 3450 88.9 84 114 114 67 194 124 3.1 3.0
• Request Publication 11.03 for 5 1'h(a)t 500 2.00 4.03 475 4.75 3.16 9.70 3.69 74 7.6
Mechanical-T cross assemblies 125 x 40 920 3450 50.8 102 121 121 80 246 94 3.4 3.4
2(a)t 500 2.50 4,00 475 4.75 3.16 9.70 438 8.2 80
• Pressure rated up to 500 psi/3450kPa 50 920 3450 63.5 102 121 121 80 246 , 111 3.7 3.6
on steel pipe; also available for use 21/2(a)t 920 500 2.75 3.63 475 4.75 3.16 9.70 463 8.3 7.9
with HDPE pipe 65 3450 69.9 92 121 121 80 246 118 3.8 3.6
76.1 mm• 920 500 2.75 375 - 475 3.16 9.70 4.63 _ 8.0
• Sizes from 2 x 'W/50 x 15mm 3450 69.9 95 121 80 246 118 36
through 8 x 47200 x 100mm 3(a)t I 920 500 3.50 3.81 500 4.63 3.16 9.70 5.31 8.4 8.8
80 3450 88.9 97 127 118 80 246 135 3.8 4.0
2 500 2.50 3.75 4.50 - 3.17 8.00 3.88 8.0 _
133.0 x 50 920N 3450 63.595 114 81 203 99 3.6
3 920 500 3.50 3.81 5.00 _ 3.00 9.46 5.31 8 0 -
80 3450 88.9 97 127 76 240 135 3.6
TABLE CONTINUED ON PG.4
IMPORTANT NOTES: "Center of run to engaged pipe end,female threaded outlet only(dimensions approximate).
Style 920 and Style 920N housings cannot be t Available with grooved or female threaded outlet.Specify choice on order.
mated to one another # Center of run to end of fitting.
to achieve cross connections.
# Female threaded outlets are available to NPT and BSPT specifications.
eti See page 7 for Fire Protection approvals and pressure ratings.
(a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order.
(b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order.
§Vds approved for fire protection services
0 LPCB approved for fire protection services
0 Approved for use in China by Tianjin Approvals Company.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.W 2012 VICTAULIC COMPANY ALL RIGHTS RESERVED. til�tau1I C
RFV M
CARBON STEEL PIPE- HOLE CUT PRODUCTS 11.V L
Mechanir..al-T° Bolted Branch ()utletc
STYLES 920 AND 920N
411,
DIMENSIONS
Style Max.Work Approx.
Size No. Pressure@ Dimensions Weight Each
Hole
e Diameter T`" �'W •
Z �Y inches or "psi +0.13 Inches Inches ‘Inches Inches Inches Inches LM. Lhs.
x Y r 14 Z---A.
mm 920N P. -0.00 mm mm mm mm mm mm kg kg
NM
} TABLE CONTINUED FROM PAGE 3
�� IV 1397 x 1 t 920N 500 2.00 3.78 4.50 3.30 8.23 3.25 7.0
nit '.......•'.......• rift t ril 40 3450 50.8 96 114 84 209 83 3.2 _
M 0 4 2 t 920N 500 2.50 • 3.75 4.50 3.30 8.23 3.88 9.0
50 3450 635 95 114 84 209 99 4.1
6 x 1 1/4(a) 920N 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 5.1 4.8
150 32(b) 3450 44.5 112 130 130 . 96 232 83 2,3 2.2
GROOVED OUTLET 11 (a)tra 920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 5.1
40(b) 3450 50.8 112 130 130 96 232 83 2.4 2.3
2(a)to 020N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6
< Y la-z 0 50 3450 63.5 111 130 130 96 232 99 2.7 2.5
1 I 2 V 020 500 2.75 4.01 5.13 512 3.69 10.51 4.63 8.3 7.6
+r+ 65 3450 69.9 110 130 130 94 267 118 3.8 3.4
V �-" T 500 2.75 4.15 _ 5.21 3.69 10.51 4.63 _ 8.4
at rn T ur 76.1 mm r� 920 3450 69.9 105 132 94 267 118 3.8
i p>- 14-t
3(a)t 920 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.4
y ( 80 3450 88.9 110 140 130 94 267 135 4.5 3.8
1--1 4(a)to 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1
100 920 3450 114.3 97 146 137 94 267 159 4.6 4.6
FEMALE THREADED OUTLET 1 h(a) 500 2.00 4.41 5.13 3.63 • 9.40 3.25 7.8 -
159.0 x 40 920N 3450 50.8 112 130 92 239 83 3.5
2(a) 500 2.50 4.38 5.13 _ 3.63 9.40 3.88 8.0 -
• Provides a direct branch connection at 50 920N 3450 63.5 111 130 92 239 99 3.6
any location where a hole can be cut 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 9.5
76.1 mm 920 in the pipe 3450 69.9 111 140 130 92 239 118 4.3 4.3
3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.0 • j
• A pressure responsive gasket provides 80 920 3450 88.9 110 140 130 92 239 135 3.7 6.4
the seal 108.0mm 920 500 4.50 4.45 5.38 3.63 9.40 6.12 10.0
3450 114.3 113 137 92 239 155 4.5
• Request Publication 11.03 for 4 500 4.50 3.81 5.75 3.63 9.40 6.25 18.0
Mechanical-T cross assemblies 100 920 3450 114.3 96.80 146 - 92 239 159 8.2
TABLE CONTINUED ON PG.5
• Pressure rated up to 500 psi/3450 kPa •+Center of run to engaged pipe end,female threaded outlet only(dimensions approximate).
on steel pipe; also available for use t Available with grooved or female threaded outlet.Specify choice on order.
with HDPE pipe # Center of run to end of fitting.
• Sizes from 2 x 1 750 x 15mm # Female threaded outlets are available to NPT and BSPT specifications.
through 8 x 47200 x 100 mm @ See page 7 for Fire Protection approvals and pressure ratings.
(a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order.
(b)For 76.1 mm threaded outlet,specify 2/'BSPT clearly on order.
§Vds approved for fire protection services
❑LPCB approved for fire protection services
IMPORTANT NOTES: 0 Approved for use in China by Tianjin Approvals Company.
Style 920 and Style 920N housings cannot be
mated to one another
to achieve cross connections.
•
www.victaulic.com _
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. rCtalJ l rC:
11.02 4
CARBON STEEL PIPE-HOLE CUT PRODUCTS 1 I.•UL
Mechanical-T® Bolted Bran(
STYLES 920 AND 920N
•
DIMENSIONS
Style Max.Work A aura c.
Size No. Pressure@ Dimensions Weight Each
y un x Branch V-?# V i Female
,Nominal Size 920 ,-T" Thd. Gee. W Y Z Thd. Grv.
Inches or psi `F0..1 Inches Inches Inches Inches Inches Inches Lbs. Lbs.
Y r <--Z->
mm 920N kPa -0.00 mm mm mm mm mm mm kg kg
_ TABLE CONTINUED FROM PAGE 4
/�� 1 500 1.50 3.88 4.56 _ 3.79 9.34 2.75 8.0
V.1.
a 165.1 x 920N
to0 uu I(!ii 25 3450 38.1 99 113 97 237 2 3.6
,� 1 r/as( 920N 500 1.75 4.43 5.13 _ 3.79 9.34 3.25 8.4 _
- T 32 3450 44.5 113 130 96 237 83 3.8
,� � w V .._
1'h(a)to 500 2.00 441 5.13 513 3.79 9.34 3.25 8.4 5.4
y 40 920N 3450 50.8 112 130 130 96 237 83 3.8 24
GROOVED OUTLET 2(a)t 920N 500 2.50 4.38 5.13 5.13 3.79 9.34 3.88 8.5 6.0
50 3450 63.5 111 130 130 96 237 99 3.9 2.7
76.1 mm 920 500 2.75 401 5.13 5.21 3.63 10.51 4.63 8.6 7.6
1 Y rk Z 3450 69.9 110 130 132 92 267 118 3.9 3.4
3(a)t 0 920 500 3 50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4
80 3450 889 110 140 130 92 267 135 4.6 3.8
V Ai rti r r L 4(a)Ta 500 1.50 3.81 5.75 5.38 3.63 10.51 61.5295 10.5 8.4
TI� 100 920 3450 114.3 97 146 137 92 267 4.8 3.8
-gip a - 8 x 2(a)t 920 500 2.75 544 6.19 6.25 4.81 12.42 4.50 11.6 11.6
� �� I 200 50 3450 69.9 138 157 159 122 316 114 5.3 5.3
J 1 2 h(a)t 920 500 2.75 5.07 6.19 6.19 4.81 '.2.42 4.50 11.6 11.6
65 3450 69.9 129 157 157 122 316 114 5.3 5.3
FEMALE THREADED OUTLET 76.1
--"---
76.1 mm a 920 500 2.75 5.25 6.25 4.81 12 42 4 56 11.6
3450 699 133 159 122 316 116 5.3
3(a)td 500 3.50 5.31 6.50 6.50 4.81 12.42 531 12.6 11.6
• Provides a direct branch connection at 80 920 3450 88.9 135 165 165 122 316 135 5.7 5.3
any location where a hole can be cut 4(a)to 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5
• in the pipe 100 3450 114.3 122 171 162 122 316 159 6.9 5.7
`*Center of run to engaged pipe end,female threaded outlet only(dimensions approximate).
• A pressure responsive gasket provides t Available with grooved or female threaded outlet.Specify choice on order.
the seal # Center of run to end of fitting.
• Request Publication 11.03 for # Female threaded outlets are available to NPT and BSPT specifications.
Mechanical-T cross assemblies @ See page 7 for Fire Protection approvals and pressure ratings.'
• Pressure rated up to 500 psi/3450 kPa (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order.
on steel pipe; also available for use (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order.
with HDPE pipe §Vds approved for fire protection services
a LPCB approved for fire protection services
• Sizes from 2 x t "/50 x 15mm 0 Approved for use in China by Tianjin Approvals Company.
through 8 x 4"/200 x 100mm
IMPORTANT NOTES:
Style 920 and Style 920N housings
cannot be mated to each other to
achieve cross connections.
•
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iCtauliC
RFV M
CARBON STEEL PIPE- HOLE CUT PRODUCTS I 1.V L
Mechanical-T® Bolted Branch Outlets
STYLES 920 AND 920N
11,
FLOW DATA Flow test data has shown that the total head loss between point(1)and(2)for the Style 920,920N
and 929 Mechanical-To fittings can best be expressed in terms of the pressure difference across the
inlet and branch.The pressure difference can be obtained from the relationship below.
Q Cv and Kv Values
Values for flow of water at+60°F/+16°C are shown in the table below.
Formulas for Cv/K,Values:
/�J►��
4P = Q'
C Where:
Q=Flow(GPM) 1F = Ky Where:
1`1 U AP=Pressure Drop(psi) AP=Pressure Drop(bat)
algi Q = C x DP C =Flow Coefficient Q = K, x DP
K,=Flow Coefficient
Exaggerated for clarity
Eqvalent Length of
Oiliet Size Schedule
40arbon Steel Pipe
(pUL 213,Sec.16)
OUTLET SIZE C=120)t FT C,/K,Values
yPoNiE1Yu * N etC+R.NM}'�'
NOMINAL ACTUAL
DIAMETER I O.D.
In/nun 1 Inimm GROOVED THREADED ROOVED THREADED
yz 0.840 11
15 21.3 2 94
zk 1.050 _ q _ 16
20 26.7 j 13.7
1 1.315 8 21
25 33.7 1.8
1 2 48
32 42.7.7 5 h 6 42.9 41.1Ilk
1'h 1.900 53 53
40 98.3 11 11 45.4 45.4
2 2.375 112 104
50 60.3 9 10 yz 96 89.1
2' 2.875 119 150
65 73.0 20 12 h 102 128.5
76.1 mm 3.000 16* - 161
76.1 138.1 _
3 3.500 r 249 237
80 88.9 14 15!z 213.4 203.1
4 4.500 421 401
100 114.3 20 22 360.8 343.6
t Hazen-Williams coefficient of friction is 120.
*Pipe with a wall thickness of 0.165in./4.2mm.
•
•
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2012 VICTAULIC COMPANY ALL RIGHTS RESERVED. iCtauI11.
11.02 6 RFV Ai!
CARBON STEEL PIPE- HOLE CUT PRODUCTS J. 'L a V L
Mechanical-T® Bolted Branch Outlets
STYLES 920 AND 920N
•
FIRE PROTECTION APPROVALS
AND PRESSURE RATINGS
The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to
change and/or additions by the approvals agencies.Contact Victaulic for performance on other pipe and the latest listings and approvals.
Approval Agency
Run Size Outlet Size Pipe Rated Working Pressures-psi/kPa
` Actual' _ lids
Nominal Outside •
- --
Size Diameter I
Inches/ram Inches/mm Inches/mm S ule UL ULC FM LPCB (Style 920) (Style 920N)
21/2-6 2.875-6.625 All 10.40 400 400 400 290 232 362
65-150 _ 73.0-168.3 2755 2755 2755 1999 1599 2496
21/2-4 2.875-4.500 All DF 300 300 300 290 232 362
65-100 73.0-114.3 2065 2065 2065 1999 1599 2496
21/2-4 2.875-4.500 All SF 300 300 300 290 232 362
65-100 73.0-114.3 2065 2065 2065 1999 1599 2496
6 6.625 3,4 10 300 300 250 290 232 362
150 168.3 2065 2065 1724 1999 1599 2496
6 6.625 3,4 30,40 300 300 300 290 232 362
150 168.3 2065 2065 2065 1999 1599 2496
8 -- 8.625 21/2 10,40 400 _ _ 145 —
200 219,1 2755 1000
8 8.625 34 10 300 _ 250 — 145 _
200 219.1 2065 1724 1000
8 8.625 3,4 30,40 300 — 300 — 145 —
200 219.1 2065 2065 1000
NOTES:
10 refers to Listed/Approved Schedule 10 steel sprinkler pipe.
• 40 refers to Listed/Approved Schedule 40 steel sprinkler pipe.
DF refers to Listed/Approved Dyna-Flow steel sprinkler pipe manufactured by American Tube Company.
SF refers to Listed/Approved Super-Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation.
VIC-TAP II HOLE CUTTING TOOL FOR The Vic-Tap II hole cutting tool is designed for use with the Style 931 Vic-Tap II Mechanical-T unit,
4-8"/100-200 MM CARBON STEEL PIPE which is a combination of the Style 920 Mechanical-T and Series 726 Vic-Ball Valve.The Vic-Tap II
is capable of tapping into carbon steel pipe systems under pressures up to 500psi/3450kPa.
The Style 931 Vic-Tap II Mechanical-T unit is a full port ball valve which can be mounted on 47100mm,
57125mm,67150mm and 8"/200 mm diameter pipe.The Style 931 comes with a 21/2"/65mm
r
grooved outlet
The drill motor is an electric motor with ground fault circuit interrupter(GFCI) in accordance with
" safety codes.
.f a. -,- For more information,refer to publication 24.01.
III
t_
t
a
•
www.victaulic.com \ICta u ll i
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
RFV M
CARBON STEEL. PIPE - HOLE CUT PRODUCTS , V
Mechar ical-T° Bolted Branch Outlets
STYLES 920 AND 920N
•
INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data,and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the
right to change product specifications,designs and standard equipment without notice and without
incurring obligations.
111
For complete contact information,visit www.victaulic.com
11.02 1480 REV M UPDATED 03/2012 ictaulic
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
11.02 L.
115 Standard Duty Loop Hanger
Y 9l
1
F RR t
0
F i
ill
The 115 Standard Duty Loop Hanger is ideal for suspending stationary, non-insulated pipe lines, including CPVC pipes, in fire
sprinkler systems.A knurled insert nut helps simplify vertical adjustments and flared edges on the base(1/2"to 4" sizes) help
protect pipes from coming into contact with any sharp edges of the hanger.
• Flared edges help prevent any sharp surfaces from coming into contact with the pipe(1/2"to 4" sizes)
• Retained insert nut helps ensure the loop hanger and insert nut stay together
• Recommended for the suspension of stationary non-insulated pipe lines
• Manufactured to use the minimum rod size permitted by NFPA®for fire sprinkler piping
• Conforms with Federal Specification WW-H-171 (Type 101, Manufacturers Standardization Society(MSS)SP-58(Type 10)
f RS
oB A
,
Material:Steel
Finish: Pregalvanized C ® US
APPROVED
Part Number Pipe Size Outer Diameter Rod Size Static Load
OD RS A B C F Certifications
1150050EG 1/2" 0.840" 3/8" 2 13/16" 11/8" 1" 300 lb cULus
1150075EG 3/4" 1.050" 3/8" 3" 1 3/16" 15/16" 300 Lb cULus,FM
1150100EG 1" 1.315" 3/8" 31/4" 1 3/8" 15/16" 300 lb cULus,FM
1150125EG 1 1/4" 1.660" 3/8" 3 9/16" 1 1/2" 15/16" 300 Lb cULus,FM
1150150EG 1 1/2" 1.900" 3/8" 313/16" 1 5/8" 15/16" 300 lb cULus,FM
1150200EG 2" 2.375" 3/8" 4 1/4" 1 7/8" 15/16" 300 lb cULus,FM
1150250EG 2 1/2' 2.875" 3/8" 59/16" 213/16" 19/16" 525 lb cULus,FM
1150300E0 3" 3,500" 3/8" 6 9/16" 31/2" 1 15/16" 525 lb cULus,FM
1150350EG 3 1/2" 4.000" 3/8" 71/16" 33/4" 115/16" 5851b cULus,FM
1150400EG 4" 4.500" 3/8" 7 9/16" 4" 1 15/16" 6501b cULus,FM
1150500EG 5" 5.563" 1/2" 913/16" 43/4" 21/4" 1,000 lb cULus,FM
1150600EG 6" 6.625" 1/2" 115/16" 6 5/16" 35/16" 1,000 lb cULus,FM
1150800EG 8" 8.625' 1/2" 12 7/8" 6 7/8" 2 7/8" 1,000 lb cULus,FM
•
litIDY + PENTAIR
•
FM is a registered certification mark of FM Approvals LLC,LTD.NFPA is a registered trademark of National Fire Protection Association,Inc.UL,UR.cUL,cUR,cULus and cURus are
registered certification marks of UL LLC.
WARNING
Pentair products shall be installed and used only as indicated in Pentair's product instruction sheets and training materials.Instruction sheets are available at erico.pentair.com and
from your Pentair customer service representative.Improper installation,misuse,misapplication or other failure to completely follow Pentair's instructions and warnings may cause
product malfunction,property damage,serious bodily injury and death and/or void your warranty.
®2017 Pentair All rights reserved
Pentair,CADDY,CAL/WELD,CRITEC,ERICO,ERIFLEX,ERITECH and LENTON are owned by Pentair or its global affiliates.
All other trademarks are the property of their respective owners.Pentair reserves the right to change specifications without prior notice.
I '
CADDY + PENTAIR
.. ...-" _, .7..„
__ .., .
. ._...,„
, „
. , -,....
AkirmBUildex. .
... SAmmYS
.... 2012 PRODUCT CATALOG
www.itwbuildex.com 800-BUILDEX
Ii\ .;....: , \ \Ilk\ ,\ \,,, \ II ) , i, , ,. /
� `.- _
7\ , , ,,, , ,
,4,,,\,,\,!:, \\k,„,N.,,p044k‘I.,..v. ,.. .
/lk,,,,,
`� K '!i IiN,„
fr' 'f0fAillr -i 1
M1' �° ,. .,� +r x+ t ,/ o4
, ` r
`.1!> /
w
6
"Ai
" r 3,,,w
x
1
TABLE OF CONTENTS
Sammys')for Wood 4
Sidewinder for Wood 5
Sammys Swivel Head'for Wood 5
Sammys®for Steel 6
ilk
Sidewinder®for Steel 7
Sammys Swivel Head"for Steel 7
Sammy X-Press® 8
Sammy X-Press Sidewinder' 8
Sammy X-Press Swivel"" 9
Sammy X-Press It° Installation Tool 9
Sammys®for Concrete 10
Sidewinder®for Concrete 10
Sammys Swivel Head' for Concrete 11
Concrete/Wood Installation Kit 11
Sammys Toggle' 12
Ceiling Screws 12
Dektite®Pipe Flashing 13
Speedy Pole Tool" 13
Spot Rite Level' 13 11110
Approvals and Listings 14
Special Notes 15
Warranty • Disclaimer of Warranty
Proper fastener connection design takes in to account where and how fasteners are used.Allowance for special characteristics in materials,differences in materials,differences
in types of materials being joined,unique or unusual environmental service or installation conditions and the safety factors required by anticipating normal or short term loading
conditions must be considered.Due to possible differences in specifications,applications,and interpretation of results,purchasers and specifiers must make their own evaluation
of the products,to determine the suitability of these products for intended use.All warranties of Buildex products,expressed or implied,including the warranties of merchantabilty
and fitness for particular purposes are specifically excluded except for the following:Buildex will repair or replace any product which,within twelve months after sale by Buildex or
its distributors,is found by Buildex to be defective in material or workmanship-normal wear and tear accepted.This is the sole warranty of Buildex and the sole remedy available to
distributor or buyer.Buildex shall not be liable for any injury,loss or damage,direct,indirect,or consequential,arising out of the use of,or the inability to use,any Buildex product.
For the most up to date information,visit www.itwbuildex.com
MIIIIMMINMIIIMMIIMMI
INSTALLATION INSTRUCTIONS FOR WOOD & STEEL
STALLATION STEP - r INTO WOOD&STEEL: INSTALLATION STEPS HORIZONTALINTO WOOD&STEEL:
1.Insert the appropriate nut driver into a 3/8"or 1/2"portable drill. 1.Insert the appropriate nut driver into a 3/8"or 1/2'portable drill.
2.Insert the SAMMYS into the#14(black)nut driver(p/n 8113910).Drill 2.Insert the SAMMYS into the#14SW(red)nut driver(p/n 8114910).With drill
should be in a vertical position. unit in a horizontal position and at a right angle to the structural member,
begin installation.
3.Push the face of the nut driver tight to the member.Begin installation when
the nut driver spins freely on the SAMMYS,stop drill and remove. 3.When the nut driver spins freely on the SAMMYS,stop the drill and
remove.
4.The SAMMYS is now ready to receive 1/4",3/8',1/2"or metric
all thread rod,bolt stock.(The 1/2"requires the#14SW red nut driver) 4.The unit is now ready to receive 1/4",3/8',M10,M8 or metric all thread rod or
bolt stock.
Note:When installing DSTR,follow the above instructions,then add retainer
nut and torque to 20 foot lbs.for maximumpullout in puffin steel. Note:When installing SWDR,follow the above instructions,then add retainer
nut and torque to 20 foot lbs.for maximum pullout in puffin steel.
MUM = M, _ .�
m H
-,,-, 1m
,wi,„ 7 ,,„ , :.:.
INSTALLATION INSTRUCTIONS FOR CONCRETE
INSTALLATION STEPS- ; INTO CONCRETE: INSTALLATION STEPS-,igigaiiiiiii INTO CONCRETE:
1.Using an SDS 250 carbide tip bit or a HEX RECEIVER with a #250 1.Using an SDS 250 carbide tip bit or a HEX RECEIVER with a #250
carbide tip bit,pre-drill the concrete member to a depth of 2"with a carbide tip bit,pre-drill the concrete member to a depth of 2"with a hammer/
hammer/rotary hammer drill set on impact mode. rotary hammer drill set on impact mode.
2.After pre-drilling has been completed,install the SLEEVE TOOL over 2.After pre-drilling has been completed,install the SLEEVE TOOL
the bit(the bit should remain in the drill),and insert the#14(black) over the bit(the bit should remain in the drill),and insert the#14SW(red)
nut driver(p/n 8113910)into the opposite end(see Vertical Installation nut driver(p/n 8114910)into the opposite end.
note above).
3.Insert the SWC screw into the nut driver.
3.Insert the CST screw into the nut driver.
4.Place tip of screw into the pre-drilled hole,turn impact/drill unit to
4.Place tip of screw into the pre-drilled hole,turn impact/drill unit to drill drill mode and begin insertion.When the nut driver spins free on the
mode and begin insertion.When the nut driver spins freely on the SWC screw,installation is complete.Stop and remove drill.
CST screw,installation is complete.Stop and remove drill.
5.The SWC screw is ready to receive 1/4",3/8"or metric all thread rod
5.The concrete screw is ready to receive 1/4',3/8",1/2",or metric all or bolt stock.
thread rod or bolt stock.(#14SW red nut driver used with 1/2"screw)
Note:Use a 1200 maximum RPM drill for installation.
Note:Use a 1200 maximum RPM drill for installation.
Note:Do not install concrete screws while the drill unit is in impact mode-
Note:Do not install concrete screws while the drill unit is in impact mode— doing so will destroy the pullout factor of the fastener
doing so will destroy the pullout factor of the screw.
A A j 4 r-74,--, A . -1,1 '3.,11,,,
III
SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe Installation each time.When the face of the driver comes into
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.
3 To find a distributor near you,call 800-BUILDEX
SAMMYS® FOR WOOD
SAMMYS' FOR WOOD - Vertical Application
Application Product Features
Not less man
2'nominalwidth
Wood Flowing •No re•drillin re ulred.
p g q
4(1-12")r
•Quick to install using the Sammy
Not Ins man Nut Driver with an 18V cordless
a nominal drilUdriver.
thickness(2-1/2')
(depth or side wood dot I
of vertical member) •Saves time from traditional
,
Double Sheehodk
For vertical use• Ceiling •Reduces installation costs.
•
install in center of lower lace. -
•
•
Minimum 2'embedment inPo base •Manufactured in the U.S.A.
rcaleeal tin 1JFPA 13 compliance. Composite I Truss
Consult truss manufacturer far
Til
s recommended installation point.
Pre-drilling may be rsquw^n for GST
25-380.Tool acadaWe 09 page f t
iiiWatch a video dopTsl ffiian al
www.nwbundex.com)
Approvals Rod Pad Model Screw Ultimate UL Test FM Test Box Case
Size Number Descriptions Fallout(I—) Load(ibs) Load(ibs) Qty Qty
VERTICAL MOU ;!. . '• ..„. ......",. ._ .^
114" 8002957 GST 100 1l4 x 1" 270(3/4"Ply)
25 125
670 (314"Ply)
114" 8003957 GST 200 114 x 2" 1760 (Fir) 25 125
3/8" 8007957 GST 10 1/4 x 1" 670 (3116"GSB) 300 25 125
670 (314'Ply)
3/8" 8008957 GST20 1/4x2" 1760 (Fir) 850 1475 25 125
318" 8068925 GST20-SS 114x2" 1760 (Fir) 850 25 125
#14 Black 3/8" 8009925 GST25.380 3/8x2-1/2" 2113(Fir) 1500 25 125
Nut Driver (� ' 3/8" 8010957 GST 30 114 x 3" 2060 (Fir) 1500 1475 25 125
Part#8113910 - 3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125
1/2" 8013925 GST 2 1/4 x 2" 1760 (Fir) 25 125
i —._
1/2" 8015925 GST 3 1/4 x 3" 2275 (Fir) 25 125
#14 SW Red
Nut Driver
Part#8114910
_ % is S
SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut dryer for installations.
For the most up to date information,visit www.itwbuildex.com 4
...........
. cz,AAHme
SIDEWINDER® FOR WOOD -Horizontal Application
Application Product Features
•
• Not less than 2"nominal width •No pre-drilling required.
(1-1/2")up to 3-112"pipe;not less than
3'(2.1/7)nominal width 4"a 5'pipe ••Quick to install using the Sammy
1 —► Floor mist Nut Driver with an 18V cordless
•
Minimum 2-1I2"from bottom for
dReduces llldriver.i
•
March lines.Minimum 3'horn bot-
tam for main lines.Exception:This •Saves time from traditiona
requirement shall not apply to 2"or methods
thicker nailing strips resting on top of
steel beams.
installation costs.
•Manufactured in the U.S.A.
Composite I Truss
l
ceunsult truss manufacturer for
recommended installation paint.
•
•
'Pre.dnCmg may 6e requited ton Model-
SWG 253a0.To.available on page 11.
(( Watch a video demonsfabon at
E 'www.itwbuifdem.com li
Approvals Rod Part Model $co w r Ultimate UL Test Box Case
Size Number Descriptions Pullout(Ibs) Load(Ibs) Qty Qty
HORIZONTAL MOUNT
—
114" 8019957 SWG 200 1/4 x 2" 1725 (Fir) 25 125
All _ _ 3/8" 8020957 SWG 10 1/4 x 1" 622 (Fir) 300 25 125
r) 318" 6021957 SWG 20 114 x 2" 1725 (Fir) 1050 25 125
Q 318" 8073925 SWG 20-SS 1!4 x 2" 1725 (Fir) 850 25 125
n 3/87 8022925 SWG 25-380 3/8 x 2-1/2" 2249 (Fir) 1500 25 125
#14 SW Red _ 3/8" 8023925 SWG 30 1/4 x 3" 1884 (Fir) 25 125
Nut Driver
Part#8114910 'May require pre-drilling,consult joist manufacturer.
SAMMYS SWIVEL HEAD'"' FOR WOOD - Swivel Application ,
Application Product Features
.�2.r: MAP •Eliminates distortion of threaded rod.
•Accommodates up to 3 6"x 12 pitch roof.
•
•
• •Allows 17°deflection from vertical,
wwu-4
' •Saves time from traditional methods.
i
.!i'"» •Reduces installation costs. ,,
-= eu:o-. xaaner ia r
" •Manufactured in the U.S.A. •
r
Rod Part Screw Ultimate UL Test Load FM Test Min Box Case
Approvals Model
Size Number Descriptions Pullout(Ibs) (Ibs) Load(Ibs) Thickness Qty Qty
#14 Black SWIVEL MOUNT
Nut Driver -L, ". 318" 8139957 SH-GST 20 114 x 2' 1257(Fir) 1050 1475 25 125
Part#8113910 ; 1903 Dim.Lumber
.0" 3/8" 8269957 SH-GST/CST 20 5116 x 1314" 1406 @ 45°off vertical 1500 25 125
Dim.Lumber 850 @ 45°
i _
903 Dim.Lumber
1/2' 8303957 SH-GSTICST 2.0 5/16 x 1-3/4" 1406 @ 45°off vertical 25 125
Dim.Lumber
'May require pre-drilling:consult Joist manufacturer.
#14 SH Orange •
Nut Driver
Part#8273910 C C.
•
5 To find a distributor near you,call 800-BUILDEX
1
SAMMYS° FOR STEEL
SAMMYS® FOR STEEL - Vertical Application
Application Product Features
•Made with Teksa self-drilling fasteners-
no pre-drilling required.
--il-A_ •Installs into steel range from
0 20 gauge-112"thicknesses.
' l' { t •Saves time from traditional methods.
•Reduces installation costs.
Ail/
Quick to install using the Sammys Nut
WOE WODriver with an 13V cordless drill/driver.
H 7:
j$ •A standard screwgun with a depth sensitive
€ nosepiece should be used to install Teks.
_. For optimal fastener performance,the
screwgun should be a minimum of 6 amps
and have an RPM range of 0-2500.
•
N® ��y�1N� 'Manufactured in the U.SA.
pFRt.- SEA . mvAnvk.h -
Approvals Rod Part Model Screw Ultimate UL Test FM Test Min Max Box Case
Size Number Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Thick Thick Qty Qty
—
VERTICAL MOUNT
114" 8024957 DSTR 100' 1f4-20 x 1"TEKS 3 1510 (20 ga) .036"-20 ga 3116" 25 125
1l4° 8025957 DST 100 1/474 z 1"TEKS 3 446 (20 ga.) .036"-20 ga 3/16" 25 125
1/4" 8026957 DST 150 114-14 x 1-1/2'TEKS 3 970 (16ga.) .036"-20ga 3/16" 25 125
1l4' 8027957 DST 200 114-14 x 2"TEKS 3 446(20 ga.) .036"•20 ga 3116° 25 125
1/4" 8030957 TEK 500 12-24 x 1.1/2"TEKS 5 3125 (3116") .188"-3116" 112" 25 125
Q" 318' 8038957 DSTR i' 1/4-20 x 1"TEKS 3 1510 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125
9- ;" 318" 8037957 DSTR 1-1/2' 12-24 x 1-1/2"TEKS 5 1510 (3/16") 1500 1475 .060"-16 ga. 1/2" 25 125
.Q- 3M" 8039957 DSTR 516" 5/16-18 x 1.1/4"TEKS 3 2200 (20 ga.) 1500 1475 .036"-20 ga 3116" 25 125
3/8" 8040957 DST 10 1/4-14 x 1'TEKS 3 446 (20 ga.)970 (16 ga.) .036"-20 ga 3116" 25 125
446
3/8" 8077925 DST 10-SS 1/4-14 x 1"TEKS 3 (20 ga-) .036"-20 ga 3/16" 25 125
970(16 ga.)
3/8" 8041957 DST 15 1/4-14 x 1-1/2"TEKS 3 446 (20 ga.) .036"-20 ga 3/16" 25 125
#14 Black 970 (18 ga.)
Nut Driver 446 (20 ga.)
Part#8113910 3i6" 8078925 DST 15-SS 1/4-14 x 1-112"TEKS 3 970 (16 ga.) .036"-20 ga 3116" 25 125
3I8" 8042957 DST 20 114-14 x 2'TEKS 3 446 (20 ga.) .036"•20 ga 3116" 25 125
970 (16 ga.)
318' 8044957 DST 30 1/4-14 x 3"TEKS 3 446(20 ga.) .036"-20 ga 3/16" 25 125
970(16 ga.)
a ` 3/8' 8045957 DST 516 5/16-18 x 1-114"TEKS 3 1500 (3116") 1500 1475 .125"-118" 3116" 25 125
_ Q.".% 3/8' 6046957 TEK 50 12-24 x 1-112"TEKS 5 3125 (3/16') 1500 1475 .250'-1M" 1/2' 25 125
112" 8031925 DST 2.0 1/4-14 x 2"TEKS 3 446 (20 ga.) .188"-3/16" 1/4" 25 125
970 (16ga.)
_ 1/2' 8033925 DSTR 1.0` 114-20 x 1"TEKS 3 1510(20 ga.) .036"-20 ga 3/16" 25 125
1/2" 8034925 DSTR 5.16' 5/16-18 x 1-1/4"TEKS 3 2220 (20 ga.) .036"-20 ga 3/16" 25 125
1/2" 8035925 DST 5,16 5116.18 x 1-1/4"TEKS 3 1500 (3/16) .125'-1/8" 3/16° 25 125
_ 1/2" 8036925 TEK 5.0 12-24 x 1-112"TEKS 5 3125 (3116") .188"-3/16" 1/2" 25 125
#14 SW Red 'Includes retaining nut
Nut Driver
Part#8114910 •
. SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation
ti ]J ®III f $$� each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins
l/ wauru,ueo u SA \ �•�w2+ free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.
For the most up to date information,visit www.itwbuildex.com 6
Imimisiiimillimiumm
OA tG�i111�iIt 7,0
SIDEWINDERr FOR STEEL -Horizontal Application
Application Product Features
•Made with Tekse self-drilling fasteners-no pre-drilling required.
•Installs into steel range from 20 gauge-1/2"thicknesses.
11 ��y ®0111046 •A standard screwgun with a depth sensitive nosepiece should be used to
f' 1 y7 install Teks.For optimal fastener performance,the screwgun should be a
- - minimum of 6 amps and have an RPM range of 0-2500.
,1,i •Saves time from traditional methods. N.
Tg •Reduces installation costs. 4
•Quick to install using the Sammys Nut Driver with an 4
18Vcordlessdrill/drives airne video demonstration)o"er
•Manufactured in the U.S.A.
i' www.itwbUHdex.cam V
Approvals Rod Part Model Screw Ultimate UL Test FM Test Min Max Box Case
Size Number Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Thickness Thickness Qty Qty
114" 8047957 SWD 100 114-14 x 1"TEKS 3 1477 (16 9a) 050"-16 ga 3/16' 25 125
1/4" 8049957 SWDR 100• 1/4-20 x 1'TEKS 3 1900 (20 ga.) .036"-20 ga 3/16" 25 125
3/8" 8050957 SWD 10 1/4-14 x 1"TEKS 3 1477 (16 ga.) .060"-16 ga 3/16" 25 125
318" 8080925 SWD 10-SS 1/4.14 x 1'TEKS 3 1477 (16 ga.) .080"-16 ga 3116" 25 125
- 3/8" 8052957 SWD 20 1/4-14 x 2"TEKS 3 1477 (16 ga.) .060"-16 ga 3/16' 25 125
Q.` ' 3/8' 8055957 SWDR 1* 1/4-20 x 1"TEKS 3 1900 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125
#14 SW Red Q.-'" 3/8" 8054957 SWDR 1-1/2' 12-24 x 1-1/2"TEKS 5 2375 (3/16") 1500 1475 .188"-3/16" 1/2" 25 125
Nut Driver •Q•-''S" 3/8" 8056957 SWDR 516' 5/18-18 x 1-1/4'TEKS 3 2480 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125
Part#8114910_ 3/8" 8057957 SWT 15 12-24 x 1-1/2"TEKS 5 2375(3/16") .188"-3/16" 1/2" 25 125
*Includes retaining nut
SAMMYS SWIVEL HEAD'"' FOR STEEL - Swivel Application
Application Product Features a
•Eliminates distortion of threaded rod in sloped roof applications.
4N..401
_
i •Accommodates 3-1/2 x 12 pitch. .
•Installs into angled z-purlin;allows threaded rod to hang plumb.
1 •Allows 17°deflection from vertical.
i 'Manufactured in the U.S.A.
-i1 welchavideo „„eshetbnffi
1 .. www.lrwbulldex.com)
ek
Approvals Rod Part Model Screw Ultimate UL Test FM Test Min Max Box Case
Size Number Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Thick Thick Qty Qty
_ SWIVEL MOUNT ;_..
#14 Black ti< _�� 1/4-20 X 1"
Nut Driver - Q' . 3/8" 8137957 SH-DSTR 1' TEKS 3 3220(3/161 1500 1475 .035' 3116" 25 125
Part It 8113910
2368(1/2"steel Vertical)
x 1-314" 1306(45°off Vertical) 1500(Vertical) 4'
111 i a
3/8° 8268957 SH-TEK 50 TEKS 5 2281(3/16"HSS) 850(45°off Vertical) 2-1/2" 3/16" 112" 25 125
1585(3/16"HSS 45°off Vertical)
2368(1/2"steel Vertical)
112" 8270957 SH-TEK 5.0 12-24 x 1.3/4" 1306(45°off Vertical) 3/16" 1/2" 25 125
TEKS 5 2281(3116"HSS)
le
#14 SH Orange 1585(3/16"HSS 45°off Vertical)
Nut Driver — r.
Part#8273910 'Does not comply with ROHS requirements/Includes retaining nut
7 To find a distributor near you,call 800-BUILDEX
I
SAMMY X-PRESS° Installs into Metal Deck, Purlln, or Tubular Steel
SAMMY X-PRESS® - Vertical Application
Application Product Features
•The Sammy X-Press expands to provide •Less jobsite material needed.
direct vertical attachment in:�Xp� • light gauge steel deck or purlin No retaining nut required.
(22 ga.-118").
•Provides design flexibility.
•., •Installs in seconds with Sammy X-Press It Tool,
saving time&installation costs. •Manufactured in the U.S.A.
•Use in applications where access to the back of
•
the installed fastener is prohibited.ie.metal roof
deck,tubular steel,or vapor barrier fabric. , Warcn a t+rrro ewnonwaem ar
• www.i8112dexn"n0
Approvals Rod Part Model Descri lion Ultimate UL Test UL Min FM Test FM Min Max Box Case Application
Site Number P Pullout(Ibs) Load(Ibs) Thick Load(Ibs) Thick Thick Qty Qty
VER.eY - . .,
e, lT .gw.FR,: 14
,Q 114' 8181922 XP 200 Sammy 1146(22 ga) 185(Luminaire) 0'27" .125' 25 125 Metal Deck
X-Press 200 250(Luminaire) OS"o"
850(216"Pipe) .027" 940(2"Pipe) .029'
®.-.i+2 318" 8150922 XP 20 X��Sy� 1146(22 9a) 250(Luminaire) .Ogg^ 1475(4"Pipe) .104' .125° 25 125 Metal Deck
283(Conduit&Cable) .029"
1500(4"Pipe) .060'
Q.•%� 318' 8153922 XP 35 Sammy 1783(18 ga) 165(Luminaire) .029' 940 (2"Pipe) .029' .125° 25 125 Pullin
X•Press 35 250(Luminaire) .056° 1475(4'Pipe) 104"
416(Conduit&Cable) .059°
Metal
Pre-Pour Structural Concrete@ 3000 psi (Pre-P
— Q- 318' 8150922 XP 20 Sammy
X Press 20 1146(22ga) 850(255 Pipe) 25 125 Metal Deck
Post-Pour Range II LWC.5 35 PCF(Ibs/8') (Post-Pour)
Pre•Pour Structural Concrete @ 30D0 psi Posl•Pour Range It LWCS 35 PCF(Ibs/k')
a `S�..y �::y (
�rL �. t� t..J V J �j�/ � � .. t� 4 J V
SAMMY X-PRESS SIDEWINDEIV - Horizontal Application
Application Product Features
•The Sammy X-Press Sidewinder expands to •Less jobsite material needed.
I provide horizontal attachment in:
e.w a •- -16 ga•3/16°steel-puffin,tubular steel. •No retaining nut required.
suer-
— r t •Installs in seconds with Sammy X-Press Ito Tool, •Provides design Flexibility.
saving time&installation costs.
ii •Manufactured in the U.S.A.
•Use in applications where access to the back of
the installed fastener is prohibited;ie.metal roof
(SWXP) deck,tubular steel,or vapor barrier fabric.
4#1*was arMao demonetneanar
www.Itwbullldex.com)
Rod Part Ultimate UL Test UL Min FM Test Max Box Case Application
Approvals Size Number Model Description
Pullout(Ibs) Load(Ibs) Thick Load(Ibs) Thick Qty Qty
HORIZONTAL MOUNT
1250(3%'Pipe)
Sidewinder
I. 318" 8293957 SWXP 35 X-Press 35 1798(16ga) 80(Luminaire) .059' .125" 25 125 Pull
416(Conduit&Cable)
0 ' rS
MP NUFVCIl'REo u sA
For the most up to date information,visit www.itwbuildex.com 8
mummommusasommi
,, A llY N\i'_?Z' II.
SAMMY X-PRESS SWIVEL*" - Swivel Application
Application Prod:::;g4:59;ures
° • y X--Press Swivel allows you •Less jobsite material needed.
mb inexbeme roof pitches:���aee,,, nz-pudin •Noretainingnutrequired.r' n metal deck(or 12l12 pitch
Al
fog Provides design fir:
exibility.
(SXP) Dart •Installs in seconds with Sammy X-Press IF Tool,
G/' saving time&installation costs. •Manufactured in the U.S.A.
j� N
OR
t !ANI" the in installed
where access to the back of
pr�L •Use inappl
y "'►.' fastener is prohibited.ie,metal roof warcn a e. ,—,a�„eu�A;
RiOOT PICKS deck,tubular steel,or vapor barrier fabric. www.lrwbuimex.com
Approvals Rod Part Model Description Ultimate UL Test UL Min FM Test FM Min Max Box Case Application ......„
Size Number Pullout(Ibs) Load(Ibs) Thick Load(Ibs) Thick Thick Qty Qty
750(2 Pipe)
Swivel 1061(22 ga Vert) 170 Vertical(Luminaire)
�'``) '° 3/8" 8294922 SXP 20 X Press 20 829(45°Off Vert) 80 @ 45"(Laminate) .029" 635(2"Pipe) .029' .125" 25 125 Metal Deck IN
283 Vertical(Conduit&Cable) 4
233 @ 45°(Conduit&Cable) 4
1250(3-1/2"Pipe) IN
250 Vertical(Luminaire)
.®-. ib" 3/8" 8295922 SXP 35 +Ivel 1675(16 ga Ven) 80 90° Luminaire �'
X-Press 35 1558(89°Off Ved) 500@Vertical(Conduit)&Cable(
.059 635 (2"Pipet .029" .125" 25 125 Purim
333 @ 89°(Conduit&Cable) 0
a
41) Swivel 1061(22 ga Vert)
1l2" 8272957 SXP 2.0 X-Press 20 829(45°Off Vert) .02T' .125° 25 125 Metal Deck
1r2" 8271957 SXP 3.5 Swivel 1675(16 ga Vert) �• 125° 25 125 TurinX-Press 3.5 1558(89°OR Vert) a.
SAMMY X-PRESS IT' Installation Tool '
Application Product Features
The Sammy)(Pressexpands to provide
direct vertical attachment in:
1kmetal deck(22-16 gauge) ..
-z-purlin(18-16 gauge)
g
raw ' •Manufactured in the U.S.A.
Iy •• Watch tlamaieLatmn of
wwd wwbud
.•. dex.com
Part Number Model Description Qty
8194910 UXPIT' Universal X-Press It Tool 1 "
8152910 XPDB 25/64"Drill Bit 1
"Tool Includes:Sleeve,Bit Receiver,Hex Wrench,and 25/64"Drill Bit.
•
46
r.
9 To find a distributor near you.call BOO.BUILDEX
1
SAMMYS® FOR CONCRETE
SAMMYS® FOR CONCRETE - Vertical Application
Application Product Features
15
r.
•Easy two step process(Drill hole&
'0_. \--,,,._
�c �, drive Sammys concrete anchor).
a 4 0 , y;pre-drilled pilot hole required.
` e wav oa0� '1 Concrete Installation Tool availaMefor
)I Q' a one tool installation process.
,o ao ,Q •Manufactured in the U.S.A.
iao
fit
•••k:• J•' da •'��L jJ .5�' ' :r_ia °L, f.,ttf:.
Y! • .� Y r • • a.
e"•• WePoh a video demansfselm at)
�wwwidwbuildexcom)
Approvals Rod Part Model Screw Ultimate FM Test Box Case
Size Number Descriptions Pullout(ibs)` Load fibs) Qty Qty
#14 Black 1/4" 8058957 CST 200 5/16 x 1-34' 2400 25 125
Nut Driver .44, 3/8" 8059957 CST 20 5/16 x 1-3/4" 2400 1475 25 125
Pettit 8113910 -"- 3/8' 8145925 CST 20-SS 5/16x1-3/4" 2400 25 125
#14SW Red
Nut Driver 112" 8060925 CST 2 6116 x 13/4" 2400 25 125
Part#8114910
'Tested in 3000 PSI concrete
SIDEWINDER' FOR CONCRETE - Horizontal Application
Application Product Features
i ° •Easy two step process(Drill hole&drive Sammys
e o 4. r p concrete anchor).
io_ri p p°Doe ' '' •'A"pre-drilled pilot hole required.
f7 < •Concrete Installation Tool available for a one tool
K `7d o C installation process.
P' P° ° r
a p G r np7o4' Manufactured in the U.S.A.
. {gy : u° qo
- Wat &video demenshefloc ai
wwwilwbuildex.com
Approvals Rod Part Model Screw Ultimate FM Test Box Case
Sae Number Descriptions Pullout Ohs)" Load fibs) Qty Qty
HORIZONTAL MOUNT
j U4" 6062957 SWC 200 5116 x 1-3/4" 2450 25 125
iL 3!8" 8061957 SWC 20 5116 x 1.314" 2450 1475 25 125
'Tested in 3000 PSI concrete
#14SW Red
Nut Driver
Part#8114910
SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation ID
c1 \,�/ oHs each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins
ewurmcnmEo es a free.Installation is then complete,Warranty requires the use of the appropriate nut driver for installations.
Forthe most up to date information,visit www.itwbuildex.corn 10
izAl71aiv
•
' SAMMYS SWIVEL HEAD"' FOR CONCRETE - Swivel Application
Application Product Features
•Installs vertically and swivels up to 89°in wood&
•• .- z concrete structures,
P'f P••�?�aA° p°I •Eliminates distortion of threaded rod.
's: Qy o
•1/4"pre-drilled pilot hole required.
•Concrete installation tool available for a one piece
installation process.
t •Manufactured in the U.S.A.Et\I%r
Approvals Rod Part Model Screw Ultimate Box Case
Size Number Descriptions Pullout Obsp Qty Qty
2537 in 3000 psi concrete
318" 8269957 SH-GST/CST 20 5/16 x 1.3/4• 1459 @ 45"off vertical in 3000 psi concrete 25 1°
2852 in 6000 psi concrete
1636 @ 45"off vertical in 6000 psi concrete
— `'r '-' ^�' - 2537 in 3000 psi concrete
5
1459 @ 45°off vertical in 3000 psi concrete
1/2" 8303957 SH-GSTICST 2.0 5116 x 1.3i4" 2852 in 6000 psi concrete 25 125
#14 SH Orange
411 Nut Driver 1636 @ 45°off vertical in 6000 psi concrete
Part 4 8273910_
Note:UL Listed for wood-see pages `Tested in 3000 PSI concrete ^•••••
4
N
CONCRETE I WOOD INSTALLATION KIT 4
t
Application 2
C
Rotary Hammer Drill into concrete Hammer Drill into concrete (;
(b)(b)
(g) (d) .�(hi ' `� or "VI (h) +�immial� � ��
MMIIII
JF
Part Number Description Each Qty •
8122910 Concrete Installation Kit(a)
Kit includes the following items:
8113910 #14 Black Nut Driver(b) 1
8114910 #14 SW Red Nut Driver(c) 1
8116910 #250 Bit(1/4")(d) 1
8117910 SDS Bit(1/4")(e) 1
8118910 7/32 Wood Bit(f) 1
8120910 HEX 250 Bit Receiver(1/4")(g) 1
8098910 SL 250 Sleeve(h) 1
• 8121910 SDS B250 Bit Receiver(1/4")* 1
`Only sold separately-not included in kit.
lei
11 To find a distributor near you,call 800-BUILDEX
1
ACCESSORIES
SAMMYS TOGGLE"
Application Installation Steps
tle
1.Pre-drill a 5/6'hole with a regular drill orhole saw.
Ili
f t ^ 2.Insert SST screw into#14 black nut drives With wing nut and
n_:_,
i
C washer on bolt,insect wing nut through surface,and begin
installation.
3.When bolt is secure and nut driver spins free,stop drill motor
and remove.
Pre-Cast
Hollow Core 4.SST screw is now ready to receive 1/4",3/8",or Metric all
Concrete thread rod or boll stock.
ii•
i--
I
Rod Size Part Number Model Screw Descriptions Ultimate Pullout(Ibs) Box Qty Case Qty
1l4" 8063925 SST 300 1/4 x 3" 450 (Lath 8 Plaster) 25 125
404 (2 Layers 5/8 Rods)
3/8' 8064925 SST 30 i l4 x 3" 450 (Lath&Plaster) 25 125
#14 Black — 404 (2 Layers 5/8 Rock)
Nut Driver
Part#8113910
Application Product Features
•3/16"eyelet to accommodate common wire size.
- •ICC approvals can be found at
"' ''"- www.ltwbuildex.com under Evaluation
Report#ER-5367.
oil i
7 Use the
,Il
Soeedy Pole Tool"
A for easy installation
of ceiling screws
without ladders
or scaffolding!
(see pg 13 for details)
Approvals Substrate Part Model Point Description Overal Total Ultimate ax ICC Test Box Case
Number Length Pullout(Ibs) G.uge Load(Ibs) Qty Qty
ICC STEEL 8107957 CWSD 1' Teks 1/4 x 1" 2' 472 (20 ga) 16 ga. 170 (20 ga.) 25 125
ICC STEEL 8190957 CWSD 15' Gimlet 1!4 x 1-112' 2-3/4" 472 (20 9a) 20 ga. 170 (20 ga.) 25 125
WOOD Teks 1393(Fir)
ICC STEEL 8108957 CWSD 2* Teks 1/4 x 2' 3-114" 472(20 ga) 16 ga. 170(20 ga.) 25 125
CWIT ICC 8110910 CWIT Installation Tool 1
Installation Tool 'Does not comply with ROHS requirements
Part#8110910
For the most up to date information,visit www.itwbuildex.com 12
miimiiii
gAMIATVO'" 11.-
DEKTITE® PIPE FLASHING
Application Product Features
•Complies with NFPA 13 Code Changes.
s STAY !UP TO •Flashing for dry pendant sprinklers subject to
F-DEKTITE extreme temperature changes.
CODE! •One piece construction is easy to install.
'{ CLEAI1AIICE •Pipe diameter markings ensure accurate fit.
more efficient way
_< XOLE to flash your •EPDM temperature range of-65°F to+250°F.
refrigeration/freexer unite;.
INSULATED
FREEZER 1
STRUCTURE
4 E-DRY SPRINKLER
Part Number Description Pipe Outside Diameter Dektite Base Diameter Dektite Height Box Qty
4001910 Mini 1/4"-1-1/8" 3-1/2" 1-3/4" 20
4003910 1 1/4"•2" 4.3/4" 3" 10
4004910 2 1-3/4"-3-1/4" 6-1/4• 4" 10
SPEEDY POLE TOOL' & UNIVERSAL SOCKET KIT
Universal Pole Tool Socket Kit(8129910)Includes: Product Features
._'"•"'- - - •Adaptor Plug(a) •The Pole Tool and Universal Socket Kit
'° •Socket Driver for SAMMYS(b) provide easy and safe installation for.
•Socket Driver far Ceiling Wire Screws(c)
(a) 'Socket Driver for 1/4"Standard Nut Drivers(d) -Sammys -Jack Chain
1 •Stud Plug for Viper or Ladd Powder Actuated Attachment(e) -Threaded Rod -Wire
I''i -Pencil Rod -Screws
f• ',talk (Items not sold seperate/y) -Ceiling Screws
', k (e) -: (b)(a WetMewtleo Eem°nsbatlonei •Ideal for retrofit and hard"to-reach projects in Ali
www.i[Wbuildex.com, wood and steel.
Part Number Description Box Qty
8123910 Pole Tool 6'(3'-6') 1 �•�.
8124910 Pole Tool 12'(4'-12') 1 V
8125910 Pole Tool 18'(6'-18') 1 4
8126910 Pole Tool 24'(8'•24') 1 wei
s,
8127910 Sammys Socket Driver 1 C
8128910 Ceiling Wire Socket Driver for wire and chain 1 V
s 8129910 Universal Pole Tool Socket Kit • V
4
SPOT-RITE LEVEL' C
Part Number Model Ea.Qty Product Features Q
`r
ate. 8130910 Spot Rite Level 1 •1l2",3/4°,and 1"threading
-. �r
we
•Magnetic strip for ease of use
- /,� �- •Pocket Sized
• �. ,, t .
IPA \ •Lightweight
•3-vial design for measurement of 0°,45°,and 90°angles
0.4 •
E;
•
13 To find a distributor near you,call 800-BUILDEX
APPROVALS
Part Model Rod Size Mount UL Max UL Test UL Min Wood FM Max FM Test FM Min Wor
Number Direction Pipe Size Load fibs) Pipe Size Load fibs)
SAMMYS FOR WOOD-PIPE HANGER07957 GST to
8020957 SWG 10
80 3/8" Vertical CPVC 1.112" 300 1-1/2°
3/8" Horizontal CPVC 1-i12" 300 1-1/2"
8008957 GST20
8068925 GST20•SS
8010957 OST 30
3/8" Vertical 2-1l2" 850 1-1/2" 4" 1475 1-112"
318" Vertical 2-112" 850 1-112"
3/8" Vertical4" 1500 1.1/' 4" 1475 14/2"
8009925 GST25380 3/8" Vertical 4" 1500 i-1/2"
8022925 SWG 25-380
3/8° Horizontal 3-if2"-4'" 1500 1-112"
8021957 SWG 20 3/8" Horizontal 2-1/2"•3°" 1050 1-1/2"
8073925 SWG20-SS 3/8" Horizontal 2-112" 850 1.1/2"
8269957 SH-GSTICST 20 3/8" 45°Angle off Vertical 2.112" 850 1.1/2"
8269957 SH-GST/CST 20 3/8" 45°Angle off Vertical 4" 1500 1.1/2'
8139957 SH-GST 20 3/8" 17°Angle off Vertical 3" 1050 1-1/2" 4" 1a75 1-1/2"
SAMMYS FOR STEEL•PIPE HANGER -,.. Min Steel Thick 1.11.1111 Max Steel Thick
8038'357 DSTR 1 318' Vertical 4" 1500 .035° 4' 1475 .105'
8037957 DSTR 1-112 318" Vertical 4° 1500 .035" 4" 1475 .105°
8039957 DSTR 516 3/8" Vertical 4" 1500 .037" 4' 1475 .105"
8045957 DST 516 3/8" Vertical 4" 1500 .188" 4" 1475 .188"
8046957 TEK 50 3/8" Vertical 4" 1500 .250" 4" 1475 .188°
8055957 SWDR 1 318" Horizontal 4" 1500 .037" 4" 1475 .060"
8056957 SWDR 516 3/8° Horizontal 4' 1500 .037° 4" 1475 .060"
8054957 SWDR 1-1/2 3/8" Horizontal 4' 1500 .037" 4° 1475 .060"
8137957 SH-DSTR 1 3I8" 17°Angle off Vertical 4" 1500 .035" 4" 1475 .105"
8268957 SH-TEK50 3/8" Vertical 2-112" 850
70°Angle o8 Vertcal 4" 1500
8150922 XP 20 3/8° Vertical 2.112" 850 .02 2" 940 .029°
7"
4" 1475 .105"
8153922 XP 35 3/8" Vertical 4" 1500 .060" 2" 940 .029"
4" 1475 .125"
8294922 SXP 20 3/8" Vertical or up to 45° 2" 750 .027" 2" 635 .029'
8295922 SXP 35 3/8" Vertical or up to 89° 3-1/2" 1250 .060" 0 635 .029".
8293957 SWXP35 3/8" Horizontal 3-1/2" 1250 .080"
SAMMYS FOR CONCRETE-PIPE HANGER
8059957 CST 20 318" Vertical 4" 1475 3000
8061957 SWC 20 3/8" Horizontal 4" 1475 3000
8150922 XP 20 3/8" Vertical 2-1/2" 850 Pre-Pour Structural @ 3000psi
8150922 XP 20 3/8° Vertical 2-1/2' 850 Post-Pour Range II LWC s 35 PCF(Ibs/fi)
Part Model Rod Mount UL Load UL Min Steel
Number Size Direction Rating(Ihs) Thickness
SAMMYS FOR STEEL-LUMINAIRE FITTING
185 027"
8150922 XP20 3/8° Vertical 250 .035"
185 .027"
8153922 XP 35 3/8' Vertical P50 .035°
185 .027"
8181922 XP200 1/4" Vertical 250 .035"
Vertical 170 .027"
8294922 SXP 20 318" 45° g0 .027"
Vertical 250 .060"
8295922 SXP 35 318" 90° 80 Ogg
8293957 SWXP35 3/8" Horizontal 80 .060"
Part Rod Mount UL Load UL ick.Steel
Listed
Model
Number Size Direction Ryating(Ibs) ThickneThickness
'SAMMYS FOR STEEL-CONDUIT, ' -" --r+
8150922 XP 20 3/8" Vertical 283 .027" Max 4 trade size EMT,RMC,and IMC 8 5 trade size rigid PVC conduit
8153922 XP 35 3/8" Vertical 500 .060" Max 4 trade size EMT&6 trade sze RMC.IMC,and rigid PVC conduit
8294922 SXP 20 3/8" Vertical 283 .027° Max 4 trade size EMT,RMC,and IMC&5 trade size rigid PVC conduit
8295922 SXP 35 3/8" Vertical 500 .060" Max 4 trade size EMT&6 trade sze RMC,IMC,and rigid PVC conduit
8293957 SWXP 35 318° Horizontal 500 .060" Max 4 trade size EMT&6 trade sze RMC,IMC,and rigid PVC conduit
8149957 CZ2000 114'or 3/8' Onto Vertical Rod UL Listed 4516-Cable Hanger,Cat.No.C-72000 Plenum Rated,
Complies W!NEC Standards
Gauge No. 22 ga. 20 ga. 18 ga. 16 ga. 14 ga. 12 ga. 118" 3/16" 114
Nominal Decimal Equivalent .030" .036" .048" .060° .075" .105° .125" .188" .250"
'SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-112" UL compliance with NEC Standards.
-SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4° UL and FM tests were performed in compliance with NFPA 13 Standards.
"SWG 20 Maxmum pipe size in composite wood joist allowed by UL is 2-112" Fastening requirement:5 times weight of water-filled schedule 40 pipe plus 250 pounds.
-SWG 20Madmum, e size in wood timber or•,'st allowed UL is 3*
For the most up to date information,visit www.itwbuildex.com 14
SPECIAL NOTES •
•
Engineering Note •
In 1996,the anchors listed by UL were tested in plate steel that measured.188"and.118".Subsequent testing was done for z-puriin applications in May 1997 using(.037")or 20
gauge steel.Most recently in 2008,testing with the new Sammy X-Press was completed using(.030")or 22 gauge steel metal deck.
Sammys®Nut Drivers
Special nut drivers were designed to be used with Sammys.When the appropriate nut drivers are used for installation,the driver spins freely on the screw after installation is
complete and eliminates the expected wrist snap,reduces over-torque,and prevents screw failure.
Steel Screws
Due to variations in hardness of certain metals,it should be noted that our self-drilling screws for steel will experience different drill speeds.500-1500 RPM drill speed should be
used.
Metric Products
Metric versions of the Sammy anchors are available at www.itwbuildex.com
Sammys for Seismic
Please visit www.itwbuildex.com for our current Seismic product offerring.
Vibratory Environments
For attaching or anchoring in high vibratory environments,special care should be taken not just for building attachments but also for the hangers or assemblies being supported.
Consult local code authorities for accepted anchoring devices.
Composite Joist/Truss
Truss manufacturers vary installation recommendations for composite joist.UL testing was completed to validate that Sammys and Sidewinders SWG 20 and SWG 25-380 can
be installed into the top cord of a truss.Sammy GST 20 can be installed into the center of the lower cord of a composite joist.Penetration of the upright center web is permitted by
t
some joist manufacturers.Consult truss manufacturer for recommended installation point.
Pre-drilling may be required by joist manufacturers.If so,pre-drill pilot hole 118"smaller than root diameter of fastener.
Consult the table below:
Model Root Diameter Hale Size
GST 20 .182" 1/8"
GST25-380 .280" 7/32"
SWG 20 .182" 1/8'
410 SWG 25-380 .280" 7/32"
To increase efficiency of the installation process,sleeve tools,bit receivers,and wood bits are available for pre-drilling.
NFPA/NEC Standards
All UL and FM testing complies with NFPA 13 and NEC standards.Check with your local(AHJ)Authority Having Jurisdiction to confirm application and usage.
UL Listings/FM Approvals
UL and FM reports are available at www.itwbuildex.com
UL us
M4FEP
ALSO LU1MO AS COW.AND CABLE MERO:PR M" " •
PPE
POO LIMAS Mk MGM MUM LUPMER
NCI
Technical Drawings
Technical drawings are available and can be downloaded at www.itwbuildex.com in the following formats:.dwg,.dxf,and.igs.
Manufactured in the U.S.A.Products NM
A
Contact Information NLONUFAGIVIED
°s
Technical Assistance:(800)BUILDEX Option#6(x 3259) P'
Customer Service:(800)BUILDEX Option#1
V
•
C
a
a
a
Q
15 To find a distributor near you,call 800-BUILDEX
' *r• . f
CATALOG ISSUE 4. , ( S-_
2012 . . .
� ‘ /
BUILDING IDEAS THAT WORK FOR OVER 40 YEARS!
QUALITY0
.. ,, ,..,. .
„... , , i.,
,..,,.
,�, At ITW Buildex we pride ourselves on serving the construction industry for
Nr.,s L,. over 40 years with innovative,quality products that help our customers save
`,,.., •,.,.' Lf' time and money. We are commited to our customers by providing world
�"•1 •� U 4 class customer service and technical support.We are here to help!
... /,
1/4..,_
\.,. L 1/4..i ' ./_.
1/4,-
1,. 4..., \..r •L./
` • `., \4 ` ,
.. 1/ 4/'. V
-- `,I 1/4...,
`...i 1 L
Li \..' \.
Li \,
S. ‘ii . `i u
— `/ hiloioaa
aii
wBuildex
4 49 W. Bryn Mawr Ave.
Itasca, IL 60143
(P)800-BUILDEX
;' (F)630-595-3549
?`i'www.itwbuildex.com
F
-£ Sammys°,Sammy X•Press`.Sammy*Press -,Sidewinder.Sammy X-Preas Swivel".
:` >a^ Sammy*Press Sidewinder`.Tapwn°,Sammy Sadd `,Speedy Pale Trot.Spot-Rite Level',
Oektile'.Swivel Head'".Sammys Toggle`.and leks'am trademarks of lbwis Tool Works Inca
ncklle°,a reg sl:r d trademark of Deks hdusines Ply Lid,
5201'11W Bupt a ad IL,als Taalw,rks H-.
Worldwide
• www.tyco-fire.com
t coo Contacts y
Series TY-6 - 2.8, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
IMPORTANT The TY-B Recessed Pendent Sprinkler,
where applicable,is intended for use in -. ",,:.- ^> "
Refer to Technical Data Sheet
areas with a finished ceiling. It uses a ,�'°
TFP2300 for warnings pertaining to two-piece Style 10(1/2 in. NPT)or Style G "` `i
regulatory and health information. 40(3/4 in. NPT)Recessed Escutcheon. '
Always refer to Technical Data The Recessed Escutcheon provides i •
Sheet TFP700 for the "INSTALLER 1/2 in. (12,7 mm) of recessed adjust- {
WARNING" that provides cautions ment or up to 3/4 in. (19,1 mm)of total
with respect to handling and instal- adjustment from the flush pendent 1
lation of sprinkler systems and com- position. The adjustment provided by
ponents. Improper handling and the Recessed Escutcheon reduces the
installation can permanently damage accuracy to which the fixed pipe drops
a sprinkler system or its compo- to the sprinklers must be cut.
nents and cause the sprinkler to fail Corrosion-resistant coatings, where 1
to operate in a fire situation or cause applicable, are utilized to extend
it to operate prematurely the life of copper alloy sprinklers
beyond what would be obtained
Scan the OR code or enter the URL when exposed to corrosive atmo-
in a web browser to access the most spheres. Although corrosion-resistant
coated sprinklers have passed the
up-to-date electronic version of this ('
document. Data rates may apply. standard corrosion tests of the g
cable approval agencies, the testinsting _
=..,-
1 , o is not representative of all possible
corrosive atmospheres. Consequently,
it is recommended that the end-user be The owner is responsible for maintain-
• 1 consulted about the suitability of these ing their fire protection system and
y •� Ii•• • t coatings for any given corrosive envi- devices in proper operating condi-
•
r r ronment. The effects of ambient tern- tion. Contract the installing contrac-
Y CVperature, concentration of chemicals, tor or product manufacturer with any
and gas/chemical velocity, should be questions.
i•. J• considered as a minimum, along with
• 1 NFPA prohibits installation of in.
the corrosive nature of the chemical to NPT sprinklers with K-factors greater
1 - ' 0 which the sprinklers will be exposed. than 5.6 in new construction. They are
An intermediate level version of the intended for retrofit in existing sprinkler
Series TY-B Pendent Sprinkler can be systems only
docs.jci.com/tycofire/ obtained by utilizing the Series TY-B
series-ty-b-2-8_5-6-and-8k Pendent Sprinkler in combination with Sprinkler
the Model S2 Shield.
General NOTICE Identification
The Series TY-B 2.8,5.6,and 8.0 K-fac
Description tor, Upright, Pendent, and Recessed Numbers (SIN)
Pendent Sprinklers described herein TY1151 . . . Upright 2.8K, 1/2 in. NPT
The TYCO Series TY-B 2.8, 5.6, must be installed and maintained in TY1251 . . .Pendent 2.8K, 1/2 in. NPT
and 8.0 K-factor, Upright, Pendent, compliance with this document,as well TY3151 . . . Upright 5.6K, 1/2 in. NPT
and Recessed Pendent Sprin- as with the applicable standards of the TY3251 . . .Pendent 5.6K, 1/2 in. NPT
klers described herein are standard National Fire Protection Association
response, standard coverage,decora- TY4151 . . . Upright 8.0K, 3/4 in. NPT
tive 5 mm glass bulb-type spray sprin- (NFPA), in addition to the standards of TY4251 . . .Pendent 8.0K,3/4 in. NPT
anklers.They are designed for use in light, Failure to do so may im other authorities pair the the perfor-
ordinary, urisdiction. TY4851 . . . Upright 8.0K, 1/2 in. NPT
or extra-hazard commercial TY4951 . . .Pendent 8.0K, 1/2 in. NPT
occupancies such as banks, hotels,•
shopping malls, factories, refineries, mance of these devices.
and chemical plants.
Page 1 of 10 NOVEMBER 2021 TFP151
TFP151 '
Page 2 of 10
CEILING PLATE 1 - Frame 5 - Compression
•
SEATING SURFACE 2 - Button Screw
7 3 Sealing 6 Deflector*
T1i Assembly 7 - Bushing
61111
___,..._________
_____
1 4 - Bulb
git
7/16" �; \�
(11,1 mm)
2-1/4" 3
NOMINAL A # (57,2 mm) �r
'IC
MAKE-IN I 2 *Temperature rating is
r�l 2-3/16" 111 ' 1-9116" 4 indicated on Deflector.
(55,6 mm) I (39,7 mm)
. 5 ** Pipe thread connections
\ •W� per ISO 7-1 can be
/%fl!ti�\ .v< . 6* provided on special
1/2"NPT** T WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 1
SERIES TY-B UPRIGHT(TY1151)AND PENDENT(TY1251)SPRINKLERS
2.8 K-FACTOR, 1/2 IN. NPT, STANDARD RESPONSE
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
6L 1. AV, _ 1
W 7/16' iu�-- iffl 3
t10MINAL A �% • !� 2
MAKE-IN (556/m) I1;IMAI
2-3/16" tit
4� j (55,6 mm) '� 38 1/mm 6.
� � ilk
1/2"NPT** I WRENCH STYLE 10 I- 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH 1/2" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression *Temperature
FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector* on Deflector.
Ai,'//77PTIIP'INNt
F\
i
1
gill (11,11mm) o�1 1 3
NOMINAL 1 2-3/16" O: 10 �` �"2
(.. MAKE-IN I (55,6 mm) lir
1 4
__� 2-3/16" 1-1/2" '
(55,6 mm) (38,1 mm) , ,I
8
STYLE 10 2-7/8" (73,0 mm)DIA. --- —
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
POLY-STAINLESS FINISH ONLY
FIGURE 2
SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS
5.6 K FACTOR, 1/2 IN.NPT, STANDARD RESPONSE
0
• TFP151
Page 3 of 10
S *Temperature rating ** Pipe thread connections per 1 Frame 3 Sealing 5 Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
1/2" �= 3
(12,7 mm) Ill
NOMINAL I—I } 2-5/16" 1116111z - 2
MAKE-IN I (58,7 mm)
�— 4
2-1/4" I
1-9/16"
(57,2 mm) (39,7 mm)
. --- 5
6
3/4" NPT** t WRENCH STYLE 40 1- 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH 3/4" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression *Temperature
FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector* on Deflector.
_ fa
AP' 1
r
1/2" � 52
(12,7 m"m)NOMINAL ` 2
I MAKE-IN (58,7 mm) ç
` �\`1 4
= 2-1/4" 1-9/16"
(57,2 mm) (39,7 mm)
5
STYLE 40 2-7/8"(73,0 mm)DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
POLY-STAINLESS FINISH ONLY
FIGURE 3
SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251) SPRINKLERS
8.0 K-FACTOR, 3/4 IN. NPT, STANDARD RESPONSE
CEILING PLA/-f-TE 1 - Frame 5 - Compression
________._
___
___
SEATING SURFACE 2 - Button Screw
1 3 Sealing 6 Deflector*
i ze Assembly
i-r�- t'� y 3
6 4 Bulb
A6"
11,17/1mm 2-1/4" i*( ) 4 (57,2 mm) �1 2
NOMINAL MAKE-IN *Temperature rating is
r�r 2-3/16" I� 1-9/16" 4 indicated on Deflector.
(55,6 mm) (39,7 mm)
.--' 7 5 ** Pipe thread connections
\ -_- ,fi�r per ISO 7-1 can be
6* provided on special
1/2"NPT** WRENCH request.
UPRIGHT FLATS PENDENT CROSS SECTION
FIGURE 4
SERIES TY-B UPRIGHT(TY4851)AND PENDENT(TY4951)SPRINKLERS
8.0 K-FACTOR, 1/2 IN.NPT, STANDARD RESPONSE
•
TFP151 •
Page 4 of 10
2-7/8" DIA. 2-7/8"DIA.-
-
5/8t1/4" (73,0 mm) 3/4"(19,1 mm) 5/8t1/4" (73.0 mm) 3/4'(19,1 mm) 11110
(15,9±6,4 mm) 1/4'(6,4 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm)
�_ 2-1/4"DIA. y (57,2 mm)
FACE OF (57,2 mm) MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
/ (3,2 mm) /i r 1 ,
a_i_ (3,2 mm)
I —,l �q
L, \
MOUNTINGlit 1
" f MOUNTING t
SURFACE �Imt SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY B 3/4"(19,1 mm) TY B 13/16"(20,6 mm)
FIGURE 5 FIGURE 6
SERIES TY-B RECESSED PENDENT SPRINKLER SERIES TY-B RECESSED PENDENT SPRINKLER
ASSEMBLY WITH TWO-PIECE 3/4 IN. TOTAL ASSEMBLY WITH TWO-PIECE 3/4 IN. TOTAL
ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN.NPT 8.0 K-FACTOR,3/4 IN.NPT
c, Technical Operation
Data The glass bulb contains a fluid which
WRENCH RECESS expands when exposed to heat.When
(END"A"USED FOR Approvals the rated temperature is reached, the
„1010/6"°°
1/2"NPT MODELS) UL and C-UL Listed fluid expands sufficiently to shatter the
FM,LPCB,VdS,and NYC Approved glass bulb, allowing the sprinkler to •
See Tables A,B and C for complete approval activate and water to flow.
WRENCH RECESS information, including corrosion-resistant
(END"B"USED FOR status. Design
3/4"NPT MODELS) Maximum Working Pressure Criteria
See Table D
FIGURE 7 Discharge Coefficient
W-TYPE 6 m s (40,3 L The TYCO Series TY-B 2.8, 5.6, and
K=2.8
SPRINKLER WRENCH gp /pip Pm/barn=) 8.0 K-factor, Upright, Pendent, and
K=5.6 gpm/psis(80,6 Lpm/bar1/2) Recessed Pendent Sprinklers are
K=8.0 gpm/psiY(115,2 Lpm/bar'h) intended for fire protection systems
WRENCH Temperature Ratings designed in accordance with the stan-
RECESS See Tables A,B and C dard installation rules recognized by
Finishes the applicable Listing or Approval
agency, such as UL Listing based on
-tom Sprinkler:See Table E the requirements of NFPA 13 and FM
11 Recessed Escutcheon:Signal or Pure White, Approval based on the requirements
Grey Aluminum,Jet Black,Chrome Plated, of the FM Global Loss Prevention Data
or Natural Brass Sheets. Use only the Style 10 or 40
Physical Characteristics Recessed Escutcheon, as applicable,
�,�, Frame Bronze for recessed pendent installations.
Button Brass/Copper
PUSH WRENCH Sealing Assembly..Beryllium Nickel w/TEFLON
IN TO ENSURE Bulb Glass
ENGAGEMENT Compression Screw Bronze
WITH SPRINKLER Deflector Copper
WRENCHING AREA Bushing(K=2.8) Bronze
FIGURE 8 Poly-Stainless
W-TYPE 7 RECESSED Physical Characteristics
SPRINKLER WRENCH Frame Bronze
Button L316 Stainless Steel'
Bulb Glass
Compression Screw L316 Stainless Steel'
Deflector Copper/Bronze
Sealing Assembly.Gold Plated Beryllium Nickel
w/TEFLONIII
'Type L316 stainless steel(UNS 31603)per ASTM
A479/479M or BS EN 1008 WN1.4404.
TFP151
Page 5 of 10
Bulb Sprinkler Finish8
• K-Factor Sprinkler Temperature Liquid Wax-Over-
Type Rating Color Natural Chrome Pol ester Pol Stainless° Lead Wax Lead
Brass Plated y y Coated Coated Coated
135°F(57°C) Orange
Upright 155°F(68°C) Red
(TY1151)
2.8 and 175°F(79°C) Yellow 1,2,3
1/2 in. N/A N/A:
NPT Pendent 200°F(93°C) Green
(TY1251)
Figure 1 286°F(141°C) Blue
360°F(182°C) Mauve 1,2
NOTES
1. Listed by Underwriters Laboratories,Inc.(UL).
2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL).
3. Approved by FM Global(FM Approvals).
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03).
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved.(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05)
8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as
Corrosion-Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as
Corrosion-Resistant Sprinklers.
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable
b. 150°F(66°C)maximum ceiling temperature
c. Frame and deflector only
d. Not Applicable(N/A)
TABLE A
SERIES TY-B 2.8 K-FACTOR UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
Sprinkler Temperature
Bulb Sprinkler Finish('
K-Factor Liquid Wax-Over-
Type Rating Color Natural Chrome Polyester' Poly-Stainless Lead Wax Lead
•
Brass PlatedCoated Coated Coated
135°F(57°C) Orange
155°F(68°C) Red
Upright 1,2,3,5 1,2,3,5
(TY3151) 175°F(79°C) Yellow 1,2,3,5,6 1,2 1,2,3,5
Figure 2 200°F(93°C) Green
286°F(141°C) Blue 1b,2b,3b,5b lb,2b,3b,5b
360°F(182°C) Mauve N/A
135°F(57°C) Orange
155°F(68°C) Red 1,2,3,5 1,2,3,5
5.6 Pendent 175°F(79°C) Yellow
1/2 in. (TY3251) 1,2,3,5,6 1,2 1,2,3,5
NPT Figure 2 200°F(93°C) Green
286°F(141°C) Blue lb,2b,3b,5b ib,2b,3b,5b
360°F(182°C) Mauve N/A
135°F(57°C) Orange
Recessed 155°F(68°C) Red 1,2,3,5
(Pendent 175°F(79°C) Yellow 1,2 N/A
Figure 5 200°F(93°C) Green
286°F(141°C) Blue 1,2
NOTES
1. Listed by Underwriters Laboratories,Inc.(UL),
2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL).
3. Approved by FM Global(FM Approvals).
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03).
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved.(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05)
8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as
Corrosion-Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as
Corrosion-Resistant Sprinklers.
• a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 In.Total Adjustment Recessed Escutcheon,as applicable
b. 150°F(66°C)maximum ceiling temperature
c. Frame and deflector only
d. Not Applicable(N/A)
TABLE B
SERIES TY-B 5.6 K-FACTOR UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP151 •
Page 6 of 10
•
Sprinkler Temperature
Bulb Sprinkler Finish8
K-Factor Liquid Wax-Over-
• Type Rating Color Natural Chrome polyesters.Poly-Stainless° Lead W'ax Lead
Brass Plated Coated Coated Coated
135°F(57°C) Orange
Upright 155°F(68°C) Red
(TY4151) 1,2,3,5 1,2,5
and 175°F(79°C) Yellow
1,2,3,4,5,6,7 1, 2 1,2,5
Pendent
Pende1t 200°F(93°C) Green
8.0 • Figure 3 286°F(141°C) Blue lb,2b,3b, 5b 1b,2b, 5b
3/4 in. 360°F(182°C) Mauve N/A
NPT •
135°F(57°C) Orange
Recessed 155°F(68°C) Red
Pendent 1, 2,3,4,5
(TY4251 175°F(79°C) Yellow 1,2 N/A
Figure 6 200°F(93°C) Green
286°F(141°C) Blue 1,2
•
135°F(57°C) Orange
Upright 155°F(68°C) Red
(TY4851)
8.0 and 175°F(79°C) Yellow
1/2 in. Pendent1,2,3,4,5,6 N/A N/A
NPT 1t 200°F(93°C) Green
Figure 4 286°F(141°C) Blue
•360°F(182°C) Mauve
NOTES
1. Listed by Underwriters Laboratories,Inc.(UL).
2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL).
3. Approved by FM Global(FM Approvals).
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03).
5. Approved by the City of New York under MEA 354-01-E-
•
6. VdS Approved.(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05)
8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as
Corrosion-Resistant Sprinklers,Where Lead Coated,Wax Coated,and Wax-over-Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as
Corrosion-Resistant Sprinklers.
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable
b. 150'F(66"C)maximum ceiling temperature
a. Frame and deflector only
d. Not Applicable(N/A)
TABLE C
SERIES TY-B 8.0 K-FACTOR UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP151
Page 7 of 10
• Sprinkler Finish
K-Factor Type Natural Chrome Lead Wax Wax-Over-Lead
Brass Plated Polyesters Coated Coated Coated
2.8 Upright(TY1151)
1/2 in. and 175 psi(12,1 bar) N/A3
NPT Pendent(TY1251)
Upright(TY3151)
and
5.6 Pendent(TY3251) 250 psi(17,2 bar)2
1/2 in. or
NPT 175 psi(12,1 bar)
Recessed Pendent
(TY3251)
Upright(TY4151)
and 175 psi(12,1 bar)
8.0 Pendent(TY4251)
3/4 in.
NPT
Recessed Pendent 175 psi(12,1 bar) N/A
(TY4251)
8.0 Upright(TY4851)
1/2 in. and 175 psi(12,1 bar)
NPT Pendent(TY4951)
NOTES
• 1. Frame and deflector only
2. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL),the Listing by Underwriters Laboratories,Inc.for use in
Canada(C-UL),and the Approval by the City of New York.
3. Not Applicable(N/A)
TABLE D
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
MAXIMUM WORKING PRESSURE
0
TFP151
Page 8 of 10
Installation • Before wrench tightening the sprin-
kler, adjust the jaws of the wrench Care and410
The TYCO Series TY-B 2.8, 5.6, and to contact only the sprinkler wrench Maintenance
8.0 K-factor, Upright, Pendent, and flats.
Recessed Pendent Sprinklers must • After wrench tightening the sprin- The TYCO Series TY-B 2.8, 5.6, and
be installed in accordance with this kler, loosen the wrench jaws before 8.0 K-factor, Upright, Pendent, and
section. removing the wrench. Recessed Pendent Sprinklers must be
General Instructions After Installation maintained and serviced in accordance
Do not install any bulb type sprinkler After installation, complete the with this section.
if the bulb is cracked or there is a loss following: Before closing a fire protection system
of liquid from the bulb. With the sprin- • Inspect the sprinkler wrench flats main control valve for maintenance
kler held horizontally,a small air bubble and frame arms and retouch (repair) work on the fire protection system
should be present.The diameter of the the wax coating whenever the coat- that it controls, obtain permission to
air bubble is approximately 1/16 in. ing has been damaged and bare shut down the affected fire protection
(1,6 mm) for the 135°F (57°C) to metal is exposed. system from the proper authorities
3/32 in.(2,4 mm)for the 360°F(182°C) . Retouch the wax coating on the and notify all personnel who may be
temperature ratings. wrench flats by gently applying a affected by this action.
A leak-tight 1/2 in. NPT sprinkler heated 1/8 in. diameter steel rod The owner must assure that the sprin-
joint should be obtained by apply- to the damaged areas of wax, to klers are not used for hanging any
ing a minimum-to-maximum torque of smooth it back over areas where objects and that the sprinklers are only
7 to 14 lb-ft (9,5 to 19,0 N•m). Obtain bare metal is exposed. cleaned by means of gently dusting
a leak-tight 3/4 in. NPT sprinkler joint with a feather duster; otherwise, non-
by applying a minimum to maximum NOTICE operation in the event of a fire or inad-
torque of 10 to 20 lb-ft (13,4 to Only retouching of the wax coating vertent operation may result.
26,8 N•m). Higher levels of torque may applied to the wrench flats and frame Absence of an escutcheon, which is
distort the sprinkler inlet and cause arms is permitted, and the retouching used to cover a clearance, may delay
leakage or impairment of the sprinkler. is to be performed only at the time of the time to sprinkler operation in a fire
Do not attempt to compensate for the initial sprinkler installation. situation.
insufficient adjustment in the escutch- The steel rod should be heated only to Sprinklers which are found to be
eon plate by under- or over-tightening the point it can begin to melt the wax, leaking or exhibiting visible signs of
the sprinkler. Readjust the position of and appropriate precautions need to be corrosion must be replaced.
the sprinkler fitting to suit. taken when handling the heated rod in
Series TY-B Upright and Pendent order to prevent the installer from being Automatic sprinklers
coated, o must
never other-
Sprinklers Sprinklers Installation burned, paintedwise altered after leaving the factory.
The Series TY-B Upright and Pendent Series TY-B Recessed Pendent Modified sprinklers must be replaced.
Sprinklers must be installed in accor- Sprinklers Sprinklers that have been exposed to
dance with the following instructions: The Series TY-B Recessed Pendent corrosive products of combustion,but
Step 1.Install pendent sprinklers in the Sprinklers must be installed in actor- have not operated,should be replaced
pendent position. Install upright sprin- dance with the following instructions: if they cannot be completely cleaned
klers in the upright position. Step 1. After installing the Style 10 by wiping the sprinkler with a cloth or
Step 2. With pipe thread sealant or 40 Mounting Plate, as applicable, by brushing it with a soft bristle brush.
applied to the pipe threads, hand- over the sprinkler threads and with Care must be exercised to avoid
tighten the sprinkler into the sprinkler pipe thread sealant applied to the pipe damage to the sprinklers before,
fitting. threads, hand-tighten the sprinkler into during, and after installation. Sprin-
the sprinkler fitting. klers damaged by dropping, strik-
Step 3. Tighten the sprinkler into the Step 2. Tighten the sprinkler into the ing, wrench twist/slippage, or the like,
sprinkler fitting using only the W-Type 6 Sprinkler Wrench, see Figure 7. sprinkler fitting using only the W-T must be replaced. Replace any sprin-
For wax-coated sprinklers, use an Recessed Sprinkler Wrench,see Figure kler that has a cracked bulb or that has
8 or 10 in. adjustable wrench. With 8.With reference to Figure 3 or 4,apply lolost li Section.id from its bulb.See the Instal-
reference to Figure 1 to 4, apply the the W-Type 7 Recessed Sprinkler
W-Type 6 Recessed Sprinkler Wrench wrench to the sprinkler wrench flats. The owner is responsible for the
or an adjustable wrench,as applicable, Step 3.After the ceiling is installed or inspection,testing,and maintenance of
to the sprinkler wrench flats. the finish coat is applied, slide on the their fire protection system and devices
Wax Coated Sprinklers Style 10 or 40 Closure over the Series in
pliance wkh the applicable
this document,
standardsent, as
When installingwax-coated sprinklers
TY-B Recessed Pendent Sprinkler PP
P and push the Closure over the Mount- of the National Fire Protection Associ-
with an adjustable wrench,take care to ing Plate until its flange contacts the ation such as NFPA 25, in addition to
prevent damage to the wax coating on ceiling' standards of any other authorities
n
the sprinkler wrench flats or frame arms g' having jurisdiction.Contact the install-
and, consequently, exposure of bare ing contractor or product manufacturer
metal to the corrosive environment: with any questions.
• Open the jaws of the wrench suffi- Automatic sprinkler are recommended
ciently wide to pass over the wrench to be inspected,tested,and maintained
flats without damaging the wax by a qualified Inspection Service in
coating. accordance with local requirements
and/or national codes.
TFP151
Page 9 of 10
• P/N 57 - XXX - X - XXX
SIN SPRINKLER TEMPERATURE
RATING
FINISH
530 2.8K UPRIGHT(1/2 in.NPT) TY1151 1 NATURAL BRASS 135 135°F(57°C)
531 2.8K PENDENT(1/2 in.NPT) TY1251 POLY-STAINLESS GREY 155 155°F(68°C)
2 ALUMINUM(RAL9007)1
POLYESTER
175 175°F(79°C)
570 5.6K UPRIGHT(1/2 in.NPT) TY3151 PURE WHITE(RAL9010)2
3 POLYESTER 200 200°F(93°C)
571 5.6K PENDENT(1/2 In.NPT) TY3251 SIGNAL WHITE(RAL9003)
4 POLYESTER 286 286°F(141°C)
590 8.0K UPRIGHT(3/4 in.NPT) TY4151 JET BLACK(RAL9005)3
5 POLYESTER
591 8.0K PENDENT(3/4 in.NPT) TY4251 360 360°F(182°C)
6 WAX COATED
560 8.0K UPRIGHT(1/2 in.NPT) TY4851 286°F(141°C)MAX 000 OPEN4
7 LEAD COATED
561 8.0K PENDENT(1/2 in.NPT) TY4951
8 WAX-OVER-LEAD
286°F(141°C)MAX
9 CHROME PLATED
NOTES
1. Only available on TY3151,TY3251,TY4151,and TY4251.
• ino2. Eastern Hemisphere sales .
3. Available in only 8.0K,
155°F(68°C)or 200°F(93°C);requires lead time to manufacture.
4. Available only for 8.0 K-factor TY4151 end TY4251 for use in deluge systems("OPEN"indicates sprinkler assembly without glass bulb,button,and sealing assembly).
TABLE E
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited OrderingWax Sticks(for retouching wrench-
damaged wax coating)
WarrantyProcedure Specify: (specify color, below) Color-
coded Wax Sticks for retouching
For warranty terms and conditions,visit Contact your local distributor for avail- (specify temperature rating) tempera-
www.tyco-fire.com. ability.When placing an order, indicate ture-rated Series TY-B Sprinklers, P/N
the full product name and Part Number (specify)
(P/N). Black for 135°F(57°C) P/N 56-065-1-135
Red for 155°F(68°C) P/N 56-065-1-155
Sprinkler Assemblies with Yellow for 175°F(79°C) P/N 56-065-1-175
NPT Thread Connections Blue for 200°F(93°C)
Specify: Series TY-B (specify SIN), and 286°F(141°C) P/N 56-065-1-286
(specify K-factor), (specify Upright Note: Each wax stick is suitable for
or Pendent) Sprinkler with (specify) retouching up to 25 sprinklers.
temperature rating, (specify) finish or The wax used for 286°F(141°C)sprinklers
coating, P/N (See Table E) is the same as for 200°F(93°C)sprinklers.
Recessed Escutcheon Therefore, the 286°F (141°C) sprinkler
Specify: Style (10 or 40) Recessed is limited to the same maximum ceiling
Escutcheon with (specify`) finish, P/N temperature as the 200°F(93°C)sprinkler
(specify`) which is 150°F(66°C).
•Refer to Technical Data Sheet TFP770
Sprinkler Wrenches
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
• Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
CO� Worldwide Contacts www.tyco-fire.com
• ty
Series DS-1 - 5.6 K-factor, Dry-type Sprinklers
Pendent, Upright, and Horizontal Sidewall
Standard Response, Standard Coverage
General NOTICE
Series DS-1 Dry-type Sprinklers t
Description described herein must be installed
and maintained in compliance with this
TYCO Series DS-1 5.6K Pendent, document,as well as with the applica-
Upright,and Horizontal Sidewall,Stan- ble standards of the NATIONAL FIRE
dard Response(5 mm bulb),Standard PROTECTION ASSOCIATION (NFPA),
Coverage Dry-type Sprinklers are dec in addition to the standards of any other
orative glass bulb automatic sprinklers authorities having jurisdiction. Failure
typically used where: to do so may impair the performance I
• pendent sprinklers are required of these devices. q
on dry pipe systems that are The owner is responsible for main-
exposed to freezing temperatures taining their fire protection system
(for example, sprinkler drops from and devices in proper operating con-
ill, ,
unheated portions of buildings) dition. Contact the installing contrac-
• sprinklers and/or a portion of the for or product manufacturer with any
connecting piping may be exposed questions.
to freezing temperatures (for Series DS-1 Dry-type Sprinklers must
410 example, sprinkler drops from wet only be installed in fittings that meet
systems into freezers, or horizontal the requirements of the Design Crite-
piping extensions through a wall to ria section.
protect unheated areas of a building
such as loading docks,overhangs, Sprinkler
and building exteriors)
• sprinklers are used on systems that Identification/ -t
are seasonably nably drainedto avoid Numbers (SINS)freezing (for example,
vacation
resort areas) TY3255-Pendent
TY3155-Upright
TY3355-Horizontal Sidewall
Discharge Coefficient
Technical
K=5.6 gpm/psis(80.6 1pm Ipm/bares)
Data Temperature Ratings
See Tables A and B.
Approvals Finishes
UL and C-UL Listed Sprinkler:See Table D.
FM Approved Escutcheon:See Table D.
NYC Approved Physical Characteristics
• under MEA 352-01-E Inlet Copper
IMPORTANT LPCB Approved Plug Copper
Refer to Technical Data Sheet • Reference No.094a/11 Yoke Stainless Steel
TFP2300 for warnings pertaining to CE Certified Casing Galvanized Carbon Steel
Insert Bronze
regulatory and health information. • Certificate of Conformity Bulb Seat Stainless Steel
Always refer to Technical Data No.2831-CPR-S2015 Bulb(5 mm dia.) Glass
Sheet TFP700 for the "INSTALLER See Tables A and B for details. Compression Screw Bronze
WARNING" thatprovides cautionsWorking Deflectore Bronze
Maximum Pressure Frame Bronze
with respect to handling and instal- 175 psi(12,1 bar) Guide Tube Stainless Steel
lation of sprinkler systems and coin- Inlet Thread Connections Water Tube Stainless Steel
• ponents. Improper handling and Spring Stainless Steel
installation can permanently damage nR
1
N Sealing Assembly..Beryllium Nickel w/TEFLON
a sprinkler system or its compo- Escutcheon....Carbon Steel or Stainless Steel
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 SEPTEMBER 2021 TFP500
TFP500
Page 2 of 10
SPRINKLER ESCUTCHEON TEMPERATURE BULB SPRINKLER FINISH •
TYPE TYPE RATING COLOR CODE NATURAL CHROME POLYESTER*
BRASS PLATED
135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow 1,2,3,4,5 1,2,4,5
STANDARD
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve 1,2,3 1,2
135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow 1,2,3,5 1,2,5
RECESSED
200°F(93°C) Green
286°F(141°C) Blue 1,2
PENDENT 360°F(182°C) Mauve N/A
(TY3255) 135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow
DEEP
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve 1,2,3,4,5 1, 2,4,5
135°F(57°C) Orange
155°F(68°C) Red
WITHOUT 175°F(79°C) Yellow
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve 1,2,3 1,2
135°F(57°C) Orange
155°F(68°C) Red
UPRIGHT 175°F(79°C) Yellow 1,2,3,4,5 1,2, 4,5
(TY3155) WITHOUT 200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve 1,2,3 1,2
Notes:
1. Listed by Underwriters Laboratories,Inc.(UL),maximum order length of 48 in.
2. Listed by Underwriters Laboratories for use in Canada(C-UL),maximum order length of 48 in.
3. Approved by FM Global(FM Approvals),maximum order length of 48 in.
4. Loss Prevention Certification Board(LPCB)and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
Frame and deflector only
N/A-Not Applicable
TABLE A
SERIES DS-1 PENDENT& UPRIGHT DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP500
Page 3 of 10
SPRINKLER FINISH
• SPRINKLER ESCUTCHEON TEMPERATURE BULB
TYPE TYPE RATING COLOR CODE NATURAL CHROME POLYESTER***
BRASS PLATED
135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow
STANDARD
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve
135°F(57°C) Orange
155°F(68°C) Red
HSW" 175°F(79°C) Yellow 1** 2",3*** 4,5 P*,2**,4,5
(TY3355) DEEP
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve
135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow
WITHOUT
200°F(93°C) Green
286°F(141°C) Blue
360°F(182°C) Mauve 1",2'",5 1** 2**
Notes:
1. Listed by Underwriters Laboratories,Inc.(UL),maximum order length of 48 In.
2. Listed by Underwriters Laboratories for use in Canada(C-UL),maximum order length of 48 in.
3. Approved by FM Global(FM Approvals),maximum order length of 48 in,
4. Loss Prevention Certification Board(LPCB)and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
Horizontal sidewall with top of deflector-to-ceiling distance of 4 to 12 In.(100 to 300 mm)
Light and ordinary hazard occupancies only
— Light hazard occupancies only
"" Frame and deflector only TABLE B
SERIES DS-1 HORIZONTAL SIDEWALL(HSW) DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
PLUG WITH 9" --- INLET
SEALING lirASSEMBLY if WRENCH
E YOKE RECESS
■r�
SPRING t/
�i%.��; INLET
• ` BAND
WATER WRENCH O
TUBE 1 CASING FLAT
a
GUIDE k il Z INSERT PUSH WRENCH
TUBE -11 IN TO ENSURE
` ENGAGEMENT
BULB WITH SPRINKLER
FRAME � 'i `� SEAT WRENCHING AREA
t r FIGURE 2
«( W-TYPE 7
VENT HOLE
*RI 5 mm BULB WRENCH
rI COMPRESSION
. DEFLECTOR �.� SCREW
FIGURE 1
SERIES DS-1 DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
ASSEMBLY
TFP500
Page 4 of 10
SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN •
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF FACE OF FACE OF \
SPRINKLER SPRINKLER SPRINKLER \
FITTING FITTING FITTING }}}
\ L_ _2 \ 1. \ _L_ JI
ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2"DIA.
2-3/4"to 48" 1-3/4"DIA. 3-3/4"to 48" 1/2°to 46" (88,9 mm)
(69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) (12,7 to 1168,4 mm) 2 11/2"DIA.
IN 1/4"(6,4 mm) IN 1/4"(6,4 mm) 2-1/4"DIA. IN 1/4"(6,4 mm) 3,5 mm)-IINCREMENTS INCREMENTS (57,2 mm) INCREMENTS
ni FACE OF % I III .
�d' --- CEILING
FACE OF _� FACE OF
CEILING I _u
W
CEILING ,�"1
4-1/4"±1/8"
— (108,0±3,2 mm)
2-3/16"±1/8" 3" DIA. 1-3/8"±1/8" 2-7/8" DIA. ' '
(55,6±3,2 mm) ,(76,2 mm) (34,9±3,2 mm) (73,0 mm) ! 11_
FIGURE 4
FIGURE 3 PENDENT(TY3255) FIGURE 5
PENDENT(TY3255) WITH STANDARD PENDENT(TY3255)
WITH STANDARD ESCUTCHEON RECESSED ESCUTCHEON WITH DEEP ESCUTCHEON
SPRINKLER FITTING /
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
FACE OF } •SPRINKLER
FITTING
\ L- ORDER LENGTHS:
t 5'to 48"
(127,0 to 1219,2 mm)
ORDER LENGTHS: IN 1/4"(6,4 mm)
5"to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS FACE OF
1 SPFITTINGRINKLER
MINIMUM \ ,-
1-3/4"(44,5 mm) /"DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 6 FIGURE 7
PENDENT(TY3255) UPRIGHT(TY3155)
WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON
•
TFP500
Page 5 of 10
• ORDER LENGTHS: Operation
2-3/4"to 48"(69,9 to 1219,2 mm)
IN 1/4"(6,4 mm)INCREMENTS 2 3/8" 1/8" When TYCO Series DS-1 5.6K Pendent,
I (60,3±3,2 mm) Upright,and Horizontal Sidewall,Stan-
FACE OF FACE OF dard Response, Standard Coverage
SPRINKLER MOUNTING Dry-type Sprinklers are in service,
FITTING SURFACE water is prevented from entering the
N assembly by the Plug with Sealing
IAssembly(see Figure 1) in the Inlet of
�II�I������P� _ 1 the sprinkler.
I �I_ DIA. glass The bulb contains a fluid that
expands when exposed to heat.When
3.5° the rated temperature is reached, the
1-3/4"DIA. SI fluid expands sufficiently to shatter
(REFER TO DESIGN CENTERLINE 5/16"
SPRINKLER FITTING (44,5 mm) \ the glass bulb, and the Bulb Seat is CRITERIA SECTION) OF WATERWAY (7,9 mm) released.
FIGURES The compressed Spring is then able
HORIZONTAL SIDEWALL(TY3355) to expand and push the Water Tube as
WITH STANDARD ESCUTCHEON well as the Guide Tube outward. This
action simultaneously pulls inward on
the Yoke, withdrawing the Plug with
ORDER LENGTHS: Sealing Assembly from the Inlet,allow-
1/2"to 45-3/4"(12,7 to 1162,1 mm) ing the sprinkler to activate and flow
IN 1/4"(6,4 mm)INCREMENTS water.
I _ 4-1/4"±1/8"
2-1/2"DIA. FACE OF (108,0±3,2 mm) Design
FACE OF (63,5 mm) MOUNTING
SPRINKLER SURFACE Criteria
FITTING 1
TYCO Series DS-1 5.6K Pendent,
Upright,and Horizontal Sidewall,Stan-
dard Response, Standard Coverage
(���������������,1 �11: (88,9 mm) Dry-type Sprinklers are intended for
• ' � �1L� / 3.5° T use in fire sprinkler systems designed
SPRINKLER FITTING O in accordance with the standard instal-
(REFER TO DESIGN CENTERLINE 5/16" lation rules recognized by the appli-
CRITERIA SECTION) OF WATERWAY (7,9 mm) cable listing or approval agency (for
example, UL Listing is based on NFPA
FIGURE 9 13 requirements). For more information
HORIZONTAL SIDEWALL(TY3355) on LPCB Approval, contact Johnson
WITH DEEP ESCUTCHEON Controls at the following office:
Kopersteden 1
ORDER LENGTHS: 7547 TJ Enschede
5-1/2"to 48"(139,7 to 1219,2 mm) - The Netherlands
IN 1/4"(6,4 mm)INCREMENTS MINIMUM Tel: +31-(0)53-428-4444
2-1/4"(57,2 mm) Fax: +31-(0)53-428-3377
FACE OF DEFLECTOR TO Sprinkler Fittings
SPRINKLER MOUNTING Install 1 in. NPT Series DS-1 Dry-type
FITTING SURFACE Sprinklers in the 1 in.NPT outlet or run
of the following fittings:
• malleable or ductile iron threaded
--_,ey: r
tee fittings that meet the imen-
/ sional requirements of ANSI B16.3
-, 3.5°\ 5/16" (Class 150)
SPRINKLER FITTING (7,9 mm) • cast iron threaded tee fittings that
(REFER TO DESIGN CENTERLINE meet the dimensional requirements
CRITERIA SECTION) OF WATERWAY of ANSI B16.4(Class 125)
FIGURE 10 Do not install Series DS-1 Dry-type
HORIZONTAL SIDEWALL (TY3355) Sprinklers into elbow fittings.The Inlet
WITHOUT ESCUTCHEON of the sprinkler can contact the interior
of the elbow.
The unused outlet of the threaded tee is•
plugged as shown in Figure 12.
TFP500
Page 6 of 10
Temperatures for Heated Area(1) Drainage •
In accordance with the minimum
Ambient Temperature 40°F 50°F 60°F requirements of the NATIONAL FIRE
Exposed to (4°C) (10°C) (16°C) PROTECTION ASSOCIATION for dry
Discharge End of Sprinkler Minimum Exposed Barrel Length(z), pipe sprinkler systems, branch, cross,
and feed-main piping connected to Dry
in. Sprinklers and subject to freezing tem-
(f1f11) peratures must be pitched for proper
40°F 0 0 0 drainage.
(4°C) Exposure Length
30°F 0 0 0 When using Dry Sprinklers in wet pipe
(-1°C) sprinkler systems to protect areas
20°F 4 subject to freezing temperatures, use
(-7°C) (100) 0 0 Table C to determine a sprinkler's
o°F 8 1 appropriate exposed barrel length to
1
(-10 con-
(-12°C) (200) (25)10 prevent water from freezing in the con-
necting pipes due to conduction. The
0°F 12 3 exposed barrel length measurement
(-18°C) (305) (75) 0 must be taken from the face of the
10°F 14 4 1 sprinkler fitting to the surface of the
(-23°C) (355) (100) (25) structure or insulation that is exposed
to the heated area. See Figure 11 for
-20°F 14 6 3 an example.
(-29°C) (355) (150) (75)
For protected area temperatures
-30°F 16 8 4 between those given above, the
(-34°C) (405) (200) (100) minimum recommended length from
40°F 18 8 4 the face of the fitting to the outside of
(-40°C) (455) (200) (100) the protected area may be determined
by interpolating between the indicated
-50°F 20 10 6 values.
(-46°C) (510) (255) (150)
Clearance Space
-60°F 20 10 6
(-51°C) (510) (255) (150) connecting ng an with b 13, when
an area subject to freez-
Notes: ing and an area containing a wet pipe
1. For protected area temperatures that occur between values listed above,use the next cooler temperature. sprinkler system,the clearance space
2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph).
TABLE C around the sprinkler barrel of dry-type
em-
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS sprinklers differences mf t b cesled. Due to ttwo
MINIMUM RECOMMENDED LENGTHS areas, th ontialfbetweenefrtwo
areas, the potential for the formation
of condensation in the sprinkler and
You can also install Series DS-1 Dry- For dry pipe system installations, subsequent ice build-up is increased.If
type Sprinklers in the 1 in. NPT outlet use only the side outlet of maximum this condensation is not controlled,ice
of a GRINNELL Figure 730 Mechanical 2 1/2 in. reducing tee when locat- build-up can occur that might damage
Tee and GRINNELL G-FIRE Figure 522; ing Series DS-1 Dry-type Sprinklers the dry-type sprinkler and/or prevent
however,the use of the Figure 730 Tee directly below the branchline; other- proper operation in a fire situation.
and Figure 522 for this arrangement is wise, use the configuration shown in Use of the Model DSB-2 DrySprinkler
limited to wet pipe systems. Figure 12 to assure complete water P
drainage from above Series DS-1 Boot,described in technical data sheet
The configuration shown in Figure 13 Dry-type Sprinklers and the branch- TFP591 and shown in Figures 14 and
is only applicable for wet pipe systems line. Failure to do so may result in pipe 15,can provide the recommended seal.
where the sprinkler fitting and water- freezing and water damage.
filled pipe above the sprinkler fitting
are not subject to freezing and where
the length of the dry-type sprinkler has NOTICE
the minimum exposure length depicted Do not install Series DS-1 Dry-type
in Figure 11. See the Exposure Length Sprinklers into any other type fitting.
section. Failure to use the appropriate fitting
For wet pipe system installations of may result in one of the following:
1 in. NPT Series DS-1 Dry-Type Sprin- • failure of the sprinkler to operate
klers connected to CPVC piping, use properly due to formation of ice
only the following TYCO CPVC fittings: over the Inlet Plug or binding of the
• 1 in. x 1 in. NPT Female Adapter Inlet Plug
(P/N 80145) • insufficient engagement of the
• 1 in.x 1 in.x 1 in.NPT Sprinkler Head Inlet pipe-threads with consequent
Adapter Tee(P/N 80249) leakage1111
TFP500
Page 7 of 10
• __ _ RUN
FACE OF OUTLET TO WET SIDE
SPRINKLER _ E-PLUGGED SYSTEM OUTLET
9!)FITTING -1 SPRINKLER PLUGGED
FITTING HEATED
HEATED EXPOSURE TO DRY (SEE DESIGN
AREA LENGTH SYSTEM
CRITERIA AREA
(SEE DESIGN SECTION)
DSB-2 CRITERIA AREA DSB-2 SPRINKLER
INTENDED SECTION) SUBJECT DSB-2 FITTING
INTENDED INTENDED
FOR FREEZER TOFOR FREEZER (SEE DESIGN
STRUCTURES FREEZING FOR FREEZER STRUCTURES CRITERIA
STRUCTURES SECTION)
FIGURE 12 FIGURE 13
FIGURE 11 SPRINKLER FITTING SPRINKLER FITTING
EXPOSURE LENGTH UNHEATED AREA HEATED AREA
STRAP TIES 1-3/4" DIA.
p
(ENDS ON (44,5 mm)
OPPOSING CLEARANCE INSULATED
SIDES OF HOLE FREEZER
BOOT) ADHESIVE STRUCTURE
DSB-2 BOOT
, No
•Ii
DSB-2
ADHESIVE BOOT I
. 1-3/4" DIA. 1�
(44.5 mm) ihmry4it7�1l� 1
CLEARANCE
HOLE 1�
NSULATED t /
FREEZER 1 /
STRUCTURE STRAP TIES
Mil DS-1 (ENDS ON DS-1
SHOWN WITH
II ---`_SHOWN WITH OPPOSING STANDARD
STANDARD SIDES OF ESCUTCHEON
ESCUTCHEON BOOT)
FIGURE 14 FIGURE 15
MODEL DSB-2 DRY SPRINKLER MODEL DSB-2 DRY SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-1 DRY-TYPE SPRINKLER DS-1 DRY-TYPE SPRINKLER
TFP500
Page 8 of 10
Installation Note: If sprinkler removal becomes have not operated,should be replaced
necessary, remove the sprinkler using if they cannot be completely cleaned
TYCO Series DS-1 5.6K Pendent, the same wrenching method noted by wiping the sprinkler with a cloth or
Upright,and Horizontal Sidewall,Stan- above.Sprinkler removal is easier when by brushing it with a soft bristle brush.
a non-hardening sealant was used
dard Response, Standard Coverage Care must be exercised to avoid
Dry-type Sprinklers must be installed and torque guidelines were followed. damage to the sprinklers before,
in accordance with this section. After removal, inspect the sprinkler for during, and after installation. Sprin-
damage. klers damaged by dropping, striking,
General Instructions Step 3. After installing the ceiling or wrench twist/slippage,or the like,must
Series DS-1 Dry-type Sprinklers must wall and applying a ceiling finish,slide be replaced.Also,replace any sprinkler
only be installed in fittings that meet on the outer piece of the escutch- that has a cracked bulb or that has lost
the requirements of the Design Cri- eon until it comes in contact with the liquid from its bulb.See the Installation
teria section. See the Design Criteria ceiling/wall. Do not lift the ceiling panel section.
section for other important require- out of its normal position.
ments regarding piping design and The owner is responsible for the
sealing of the clearance space around When using the Deep Escutcheon, inspection,testing,and maintenance of
the Sprinkler Casing. hold the outer piece in contact with the their fire protection system and devices
DDo not any sprinkler mounting surface(ceiling or wall).Then in compliance with this document, as
o the install bulb-typeo thereis a loss rotate the inner piece approximately 1/4 well as with the applicable standards
if bulbiscracked bulb. is sprin- turn with respect to the outer piece, of the NATIONAL FIRE PROTECTION
oof liquid fromo he horizontally, small With air to hold the Deep Escutcheon firmly ASSOCIATION, such as NFPA 25, in
kler helde be present.onta The diameter bubbleo the together. addition to the standards of any other
shoair bubble is approximately 1/16 in. authorities having jurisdiction.Contact
(1,6 mm)for the 135°F(57°C) rating to Care and the installing contractor or product
1/8 in. (3,2 mm)for the 360°F(182°C) manufacturer with any questions.
rating. Maintenance Automatic sprinkler systems are rec-
ommended to be inspected, tested,
Obtain a leak-tight 1 in. NPT sprinkler TYCO Series DS-1 5.6K Pendent, and maintained by a qualified Inspec-
joint by applying a minimum-to-maxi- Upright, and Horizontal Sidewall, tion Service in accordance with local
mum torque of 20 to 30 lb-ft (26,8 to Standard Response, Standard Cover- requirements and/or national codes.
40,2 N•m). Higher levels of torque may age Dry-type Sprinklers must be main-
distort the sprinkler Inlet with conse- tained and serviced in accordance with
quent leakage or impairment of the this section. •
sprinkler. Before closing a fire protection system
Do not attempt to compensate for main control valve for maintenance
insufficient adjustment in an Escutch- work on the fire protection system
eon Plate by under or over-tightening that it controls, obtain permission to
the Sprinkler. Re-adjust the position of shut down the affected fire protection
the sprinkler fitting to suit. systems from the proper authorities
Notes: and notify all personnel who may be
• Install pendent sprinklers only in affected by this action.
the pendent position;install upright Absence of the outer piece of an
sprinklers only in the upright posi- escutcheon, which is used to cover a
tion. The deflector of a pendent or clearance hole, may delay the time to
upright sprinkler is to be parallel to sprinkler operation in a fire situation.
the ceiling. A Vent Hole is provided in the Bulb
• Install horizontal sidewall sprinklers Seat(see Figure 1)to indicate if the Dry
in the horizontal position with their Sprinkler is remaining dry. Evidence of
centerline of waterway perpendicu- leakage from the Vent Hole indicates
lar to the back wall and parallel to potential leakage past the Inlet seal
the ceiling. Ensure the word "TOP" and the need to remove the sprinkler
on the Deflector faces the ceiling. to determine the cause of leakage;
Step 1. With a non-hardening pipe- for example, an improper installation
thread sealant such as TEFLON applied or an ice plug. Close the fire protec-
to the inlet threads, hand-tighten the tion system control valve and drain the
sprinkler into the sprinkler fitting. system before removing the sprinkler.
Step 2. Wrench-tighten the sprinkler Sprinklers which are found to be
using either: leaking or exhibiting visible signs of
• a pipe wrench on the Inlet Band or corrosion must be replaced.
the Casing, see Figure 1 Automatic sprinklers must never be
• the W-Type 7 Sprinkler Wrench on painted, plated, coated, or other-
the Wrench 7Fl see Figure 2 wise altered after leaving the factory.
Modified sprinklers must be replaced.
Apply the wrench recess of the W-Type Sprinklers that have been exposed to •
7 Sprinkler Wrench to the wrench flat. corrosive products of combustion, but
TFP500
Page 9 of 10
• P/N* 60 - XXX - X - XXX
SPRINKLER ESCUTCHEON
SIN FINISH FINISHI1)
Pendent with TY3255 SIGNAL WHITE
96 Standard Escutcheon(1 in.NPT) (Figure 3) 0 PLAT (RAL9003)
ED
Pendent with TY3255 POLYESTER
93 Deep Escutcheon(1 in.NPT) (Figure 5) SIGNAL WHITE
NATURAL
(RAL9003)
97 Pendent with TY3255 1 BRASS POLYESTER
Recessed Escutcheon(1 in.NPT) (Figure 4)
Pendent without TY3255 NATURAL BRASS
92 Escutcheon(1 in.NPT) (Figure 6) 2 BRASS PLATED
Sidewall with TY3355 SIGNAL WHITE SIGNAL WHITE
94 4 (RAL9003) (RAL9003)
Standard Escutcheon(1 in.NPT) (Figure 8) POLYESTER POLYESTER
Sidewall with TY3355
53
Deep Escutcheon(1 in.NPT) (Figure 9) 8 CHROME STAINLESS
PLATED STEEL
54 Sidewall without TY3355
Escutcheon(1 in.NPT) (Figure 10) 9 CHROME CHROME
PLATED PLATED
98 Upright without TY3155
Escutcheon(1 in.NPT) (Figure 7) TEMPERATURE ORDER
RATING(2) LENGTH(a1
Notes:
1. Escutcheon Finish applies to sprinklers provided with escutcheons. 0 135°F(57°C) 055 5.50 in.
2. 360°F(182°C)temperature rating applies to non-recessed sprinkler
• assemblies.
3. Dry-type Sprinklers are furnished based upon"Order Length"as mea-
sured per Figures 3 through 10,as applicable,and for each individual
sprinkler where it is to be installed.After the measurement is taken, 2 175°F(79°C) 180 18.00 in.
round it to the nearest 1/4 in.increment.
• Use Prefix"I"for ISO 7-R 1 Connection(for example,1-60-961-1-180).
3 200°F(93°C) 187 18.75 in.
4 286°F(141°C) 372 37.25 in.
5 360°F(182°C) 480 48.00 in.
TABLE D
SERIES DS-1 DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE
PART NUMBER SELECTION
TFP500
Page 10 of 10
Limited • Order Length: Replacement Escutcheons
Dry-type Sprinklers are furnished Order replacement escutcheons
Warrantybased upon Order Length as mea- separately.
sured per Figures 3 through 10, as Note:Style 10 Recessed Escutcheons
For warranty terms and conditions,visit applicable.After the measurement is are shipped as assemblies comprised
www.tyco-fire.com. taken, round it to the nearest 1/4 in. of closure ring and mounting plate. The
increment. included mounting plate is not used
Ordering • Inlet Connections: for Dry Type Sprinkler applications,
1 in.NPT discard accordingly.
Procedure (Standard) Specify:(specify type),(specify)finish,
ISO 7-R 1 P/N(specify):
Contact your local distributor for avail- (For information on ISO Inlet Thread Recessed(Style 10)
ability. When placing an order, indi- Connections, contact your Johnson Brass Plated 56-701-2-010
cate the full product name, including Controls Sales Representative.) Signal White(RAL9003) 56-701-4-010
description and part number(P/N). . Temperature Rating Chrome Plated 56-701-9-010
Dry-type Sprinklers • Sprinkler Finish Standard(Push-On)
When ordering Series DS-1 5.6K p White Color 91-106-0-007
Pendent,Upright,and Horizontal Side- • Escutcheon Type and Finish, as Brass Plated 91-108-2-007
wall, Standard Response, Standard applicable Chrome Plated 91-106-9-007
Coverage Dry-type Sprinklers,specify P/N from Table D Deep
the following information: Brass Plated 91-107-2-010
Part numbers are for 1 in. NPT stan- White 91-107-4-007
• SIN: dard order sprinklers. Orders for Chrome Plated 91-107-9-007
TY3255-Pendent all other sprinkler assemblies must Sprinkler Wrench
TY3155- Upright be accompanied by a complete Specify W-Type 7 Sprinkler Wrench,
TY3355-Horizontal Sidewall description. P/N 56-850-4-001
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This part number includes one(1)Boot,
two(2)Strap Ties,and 1/3 oz of Adhe-
sive (a sufficient quantity for installing fi
one boot).
•
1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+l-215-362.0700 j
o 2021 Johnson Controls.All rights reserved.All speclticallon.end other information shown were current se of document revision date end are subject to duns.',Mhos.notice. Johnson aii,
NATIONAL FIRE PROTECTION ASSOCIATION and NFPAare reclelered trademarks of National Fire Protector Association; Controls
TEFLON its batlemarklO el The Cmoure Company FC,LLC