Report r?S 2-oaa 0e0S-0
g0b5" 1401\1-A-'Z(
'',"IHJEIVED
tllcu
Worldwide
4 www.tyco-fire.com
uHA� 1 �U2'� Contacts
ullY OF TIGA D
'_.UILDING DIVISION
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The TYCO Series TY-FRB Sprinklers
Description described herein must be installed
and maintained in compliance with erll ' —
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the
Upright (TY313) and Pendent (TY323) applicable standards of the National
Sprinklers described in this data sheet Fire Protection Association,in addition E ' .7
are quick response,standard coverage, to the standards of any other authori-
decorative 3 mm glass bulb-type spray ties having jurisdiction.Failure to do so i I
sprinklers designed for use in light or may impair the performance of these T- -
ordinary hazard,commercial occupan- devices. #;_:
cies such as banks, hotels, and shop- The owner is responsible for main- t
ping malls. taming their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable,is intended for use in areas for or product manufacturer with any
with a finished ceiling. This recessed questions.
pendent sprinkler uses one of the —�
following: Sprinkler k
k
• A two-piece Style 15 Recessed x
Escutcheon with recessed adjust- Identification
ment up to 5/8 in. (15,9 mm) from
the flush pendent position. Number (SIN)
• A two-piece Style 20 Recessed TY313. . .. Upright 5.6K, 1/2 in. NPT r
Escutcheon with recessed adjust- TY323. . ..Pendent 5.6K, 1/2 in.NPT
ment up to 1/2 in. (12,7 mm) from
the flush pendent position. Technical
The adjustment provided by the Data Operation
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat.When
Refer to Table A the rated temperature is reached, the
Intermediate level versions of Series fluid expands sufficiently to shatter the
TY-FRB Sprinklers are described in Maximum Working Pressure glass bulb, allowing the sprinkler to
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) activate and water to flow.
kler guards and shields are described 250 psi(17.2 bar)'
in Technical Data Sheet TFP780. .The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries.Inc.CUL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psiv(80,6 LPM/bar'h) The TYCO Series TY-FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information. tion systems designed in accordance
Always refer to Technical Data Finishes with the standard installation rules
Y Sprinkler:Refer to Table B recognized the applicable Listingor
Sheet TFP700 for the "INSTALLER 9 by PP
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and corn- Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style
a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
nents and cause the sprinkler to fail Sealing Assembly ...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
Compression Screw Bronze
it to operate prematurely.
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
• TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* _
firri
5 �I 7/16" Y 1 _-="-- /
(11,1 mm)
4 NOMINAL 2" 0 (I f mr
MAKE-IN pli
I (50,8 m'm) L
2 D `Y 2" 1-3/8" ,
(50,8 mm) (34,9 mm) \ vivo
3 F. WRENCH
F FLATS
1/2" NPT** DEFLECTOR* --- 2-7/8"(73,0 mm)DIA. -
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
The TYCO Series TY FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
,.../141-...
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
• FIGURE 2 Do not install any bulb-type sprin erence to Figure 1,apply the W-Type 6
W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb.With the Torque sprinklers 7 to 14 lb-ft (9,5 to
sprinkler held horizontally, a small air 19,0 N•m).
WRENCH bubble should be present. The diam- Recessed Pendent Sprinklers
RECESS eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor-
3/32 in.(2,4 mm)for the 286°F(141°C) dance with the following instructions.
`�,f temperature ratings. Step A. After installing the Style 15
Jai A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
5 It 14 lb-ft(9,5 to 19,0 N•m).Higher levels hand-tighten the sprinkler into the
,- , of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairment StepTighten
PUSH WRENCH of the sprinkler. B. the sprinkler
rinkler into the
INTO ENSURE sprinkler fitting using only the W-Type
ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WRENCHING AREA eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
W-TYPE 7 RECESSED
SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.
TFP172
Page 3 of 4
Care and 2-7/6"DIA.
(73,0 mm)
Maintenance
2-1/4"DIA.
The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm)
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8" (15,9 mm)
viced in accordance with this section. + ` - FLUSH
Before closing a fire protection system 3/8x5/16"
main control valve for maintenance (9,5±7,9 mm) :24 'F
work on the fire protection system } / i�
that it controls, obtain permission to ,_� J
shut down the affected fire protection MOUNTING 3,1/8""m
systems from the proper authorities SURFACE ( )
and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
affected by this action. Tv-FRB PLATE
3/4"(19,1 mm)
Absence of the outer piece of an FIGURE 4
escutcheon, which is used to cover
a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only 2-7/8"DIA.
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER _ 2-1/4"DIA.
vertent operation may result. FITTING (57,2 mm)
Sprinklers which are found to be 5/16±1/4" 12,7
leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"( mm)
corrosion must be replaced. + mi FLUSH
Automatic sprinklers must never be e. —1 1 . .7 l
painted, plated, coated, or other- /J.,
wise altered after leaving the factory. } /
Modified sprinklers must be replaced. MOUNTING imp 1/8"
Sprinklers that have been exposed to SURFACE (3,2 mm)
corrosive products of combustion,but
have not operated,should be replaced J
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8'(34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON j
klers damaged by dropping, striking,
wrench twist/slippage,or the like,must Limited Recessed Escutcheon
be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has eon with(specify")finish,P/N(specify")
lost liquid from its bulb. (Ref. Installs- Warranty Specify: Style 20 Recessed Escutch-
tion Section.) For warranty terms and conditions,visit eon with(specify")finish,P/N(specify")
The owner is responsible for the www.tyco-fire.com. 'Refer to Technical Data Sheet TFP770
inspection,testing,and maintenance of
their fire protection system and devices Ordering Sprinkler Wrench
in compliance with this document, as Specify: W-Type 6 Sprinkler Wrench,
well as with the applicable standards P/N 56-000-6-387
of the National Fire Protection Asso- Procedure
Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order,indicate
having jurisdiction.Contact the install- the full product name and Part Number
ing contractor or product manufacturer (P/N).
with any questions.
Sprinkler Assemblies with NPT
Automatic sprinkler systems are rec- Thread Connections
ommended to be inspected, tested, Specify: Series TY-FRB Upright or
and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN
tion Service in accordance with local (specify), K=5.6, Quick Response,
requirements and/or national codes. (specify) temperature rating, (specify)
finish, P/N(specify,refer to Table A).
TFP172
Page 4 of 4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER°
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
PENDENT(TY323) 200°F(93°C) Green
5.6 286°F(141°C) Blue
1/2 in.NPT
135°F(57°C) Orange
RECESSED PENDENT 155°F(68°C) Red
(TY323) 175°F(79°C) Yellow 1,2,3,4
Figures 4a and 5b
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E,
5. VdS Approved(For details,contact Johnson Controls,Enschede.Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15(1/2 In.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 M.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C)
POLYESTER
Notes: SIGNAL WHITE(RAL9003)
a Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C)
77-370-4-175-I
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 CHROME PLATED 286 286°F(141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
0101eJelsn.m Centrals.All rights reserved.All specifications and other information shown were current as rot document revision date and are subject to change without notice. Johnson
NATIONAL FIRE PROTECTION AStOCWtIN and NFPP are registered t,ademal.of Nalcrel Fire Pmmcran Asseae°°n: Controls
s
TEFLON it arOINNed trademark or DuPont ` 1'L1