Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General NOTICE
The Series TY-B Sprinklers described " " -
Description herein must be installed and maintained _, ,
in compliance with this document, as
The TYCO Series TY-B, 5.6 K-factor, well as with the applicable standards -
Upright(TY315)and Pendent(TY325) of the National Fire Protection Associa i — ?
-
Sprinklers described in this data sheet tion,in addition to the standards of any I ` !" . 41;1
are standard response, standard cover- other authorities having jurisdiction.
age, decorative 5 mm glass bulb type Failure to do so may impair the perfor- 1111111 R
spray sprinklers designed for use in mance of these devices. _;. \
light, ordinary, or extra hazard, corn- -
mercial occupancies such as banks, The owner is responsible for maintain-
hotels, shopping malls, factories, ing their fire protection system and
refineries, and chemical plants. devices in proper operating condition.
The installing contractor or sprinkler
The recessed version of the Series manufacturer should be contacted with
TY-B Pendent Sprinkler, where appli- any questions.
cable,is intended for use in areas with a
finished ceiling.This recessed pendent
sprinkler uses one of the following: Sprinkler - _,. .
• A two-piece Style 15 Recessed Identification
Escutcheon with recessed adjust- ..
ment up to 5/8 inch (15,9 mm) from Numbers (SINS)
the flush pendent position.
• A two-piece Style 20 Recessed TY315 Upright 5.6K, 1/2"NPT
Escutcheon with recessed adjust- TY325 Pendent 5.6K, 1/2"NPT y' r
ment up to 1/2 inch (12,7 mm)from x
the flush pendent position. Technical
The adjustment provided by the Temperature Ratings
Recessed Escutcheon reduces the Data 135°F(57°C)
accuracy to which the fixed pipe drops 155°F(68°C)
to the sprinklers must be cut. Approvals 175°F(79°C)
UL and C-UL Listed 200°F(93°C)
Intermediate level versions of Series FM, LPCB,and VdS Approved 286°F(141°C)
TY-B Sprinklers are described in CE Certified 360°F(182°C)t
Technical Data Sheet TFP352.Sprinkler
guards and shields are described in Sprinklers with Polyester Finish are t UL,C-UL,and VdS Approved only
Technical Data Sheet TFP780. UL and C-UL Listed as Corrosion- Finishes
Resistant Sprinklers.
Sprinkler: Refer to Table A
Maximum Working Pressure Recessed Escutcheon:White Coated,
175 psi(12.1 bar) Chrome Plated, or Brass Plated
250 psi(17.2 bar)'
'The maximum working pressure of 250 psi Physical Characteristics
(17.2 bar)only applies to the listing by Un- Frame Bronze
IMPORTANT derwriters Laboratories, Inc.(UL). Button Brass/Copper
Always refer to Technical Data Discharge Coefficient Sealing Assembly Stainless
Sheet TFP700 for the "INSTALLER K=5.6 GPM/psi iz(80,6 LPM/bar 2) Steel w/TEFLON
WARNING" that provides cau- Bulb Glass
tions with respect to handling and Compression Screw Bronze
installation of sprinkler systems and Deflector Bronze
components.Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4 FEBRUARY 2014 TFP152
f
TFP152
Page 2 of 4 f
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* _ ter,....„ 1 I
5 _I 7/16"
(11,1 mm)
4 NOMINAL 2'" II _Li h
'' , MAKE-IN (50,81 mm)
2' �r 2" �� (�/ 1-3/8"
3 ill w
j! trt (50,8Imm) (34,9mm) WRENCH
y t 1 I FLATS
1 S 1
1/2" NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TV-B UPRIGHT(TY315)AND PENDENT(TY325)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE
el Operation Installation
The glass bulb contains a fluid which The TYCO Series TY-B, 5.6 K-factor,
WRENCH RECESS expands when exposed to heat.When Upright(TY315) and Pendent(TY325)
(USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor-
END"A") fluid expands sufficiently to shatter the dance with this section. :.
glass bulb, allowing the sprinkler to
activate and water to flow. General Instructions
FIGURE 2 Do not install any bulb type sprinkler if
W-TYPE 6 the bulb is cracked or there is a loss of
SPRINKLER WRENCH Design liquid from the bulb.With the sprinkler
held horizontally, a small air bubble
WRENCH Criteria should be present.The diameter of the
RECESS The TYCO Series TY-B, 5.6 K-factor, air bubbler theap 135°F (57°telyC)
) to6 inch
(1,6 mm) for 135°F (57°C) to 3/32
r Upright (TY315)and Pendent (TY325) inch (2,4 mm) for the 360°F (182°C)
Sprinklers are intended for fire protec- temperature ratings.
tion systems designed in accordance
t with the standard installation rules A leak-tight 1/2 inch NPT sprinkler
recognized by the applicable Listing joint should be obtained by applying a
or Approval agency (e.g., UL Listing minimum-to-maximum torque of 7 to 14
is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels
13, and FM Approval is based on the of torque may distort the sprinkler inlet
PUSH WRENCH requirements of the FM Loss Preven- and cause leakage or impairment of the
tion Data Sheets). Only the Style 15 sprinkler.
IN TO ENSURE or Style 20 Recessed Escutcheon, as
ENGAGEMENT y Do not attempt to compensate for
WITH SPRINKLER applicable, is to be used for recessed insufficient adjustment in the escutch-
WRENCHING AREA pendent installations. eon plate by under-or over-tightening
FIGURE 3 the sprinkler. Readjust the position of
W-TYPE 7 RECESSED the sprinkler fitting to suit.
SPRINKLER WRENCH Upright and Pendent Sprinklers
The Series TY-B Upright and Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position; install upright
sprinklers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFP152
Page 3 of 4
Step 3. Tighten the sprinkler into the 2-7/8" DIA.
sprinkler fitting using only the W-Type (73,0 mm)
6 Sprinkler Wrench (Figure 2). With
reference to Figure 1,apply the W-Type 2-1/4" DIA.
• 6 Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm) -
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to SPRINKLER
19,0 Nm). FITTING
5/8" (15,9 mm)
Recessed Pendent Sprinklers , _ FLUSH
The Series TY-B Recessed Pendent 3/8±5/16"
Sprinklers must be installed in accor- (9,5±7,9 mm) % CI I '/
dance with the following instructions. } t
Step A.After installing the Style 15 or MOUNTING 1/8" i
Style 20 Mounting Plate,as applicable, SURFACE over the sprinkler threads and with I (3,2 mm)
pipe-thread sealant applied to the pipe CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
threads, hand-tighten the sprinkler into TY-B PLATE 3/4"
the sprinkler fitting. (19,1 mm)
Step B. Tighten the sprinkler into the FIGURE 4
Step B. fittinght using onln the W-Type SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325)
7spri Recessed Sprinkleruin Wrench (Figure WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
3).With reference to Figure 1,apply the RECESSED ESCUTCHEON
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque 2-7/8° DIA.
-
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm)
Nm). FACE OF
Step C.After the ceiling is installed or SPRINKLER F 2-1/4° DIA.
the finish coat is applied, slide on the FITTING (57,2 mm)
Style 15 or Style 20 Closure over the 5/16±1/4"
Series TY-B Sprinkler and push the (7,9±6,4 mm) 1/2" (12,7 mm)
Closure over the Mounting Plate untilIN FLUSH
its flange contacts the ceiling. _1 �' 7 +�
Care and f / i — 1/8„ l
Maintenance MOUNTINGU 10 I (3,2 mm)
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent(TY325) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
Sprinklers must be maintained and ser- TY-B PLATE 7/8"(22,2 mm)
viced in accordance with this section. FIGURE 5
Before closing a fire protection system SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325)
main control valve for maintenance WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
work on the fire protection system RECESSED ESCUTCHEON
that it controls, obtain permission to
shut down the affected fire protection Modified sprinklers must be replaced. The owner is responsible for the
system from the proper authorities Sprinklers that have been exposed to inspection,testing,and maintenance of
and notify all personnel who may be corrosive products of combustion, but their fire protection system and devices
affected by this action. have not operated, should be replaced in compliance with this document, as
Absence of the outer piece of an if they cannot be completely cleaned by well as with the applicable standards
escutcheon, which is used to cover wiping the sprinkler with a cloth or by of the National Fire Protection Associa-
a clearance hole, can delay sprinkler brushing it with a soft bristle brush. tion (e.g., NFPA 25), in addition to the
operation in a fire situation. Care must be exercised to avoid dam-
age standards of any other authorities hav-
to the sprinklers - before, during, ing jurisdiction. Contact the installing
The owner must assure that thep contractor or sprinkler manufacturer
s rinklers are not used for hanging and after installation. Sprinklers dam-
p 9 9 aged by dropping, striking, wrench regarding any questions.
any objects and that the sprinklers are
only cleaned by means of gently dust- twist/slippage, or the like, must be Automatic sprinklers are recommended
ing with a feather duster; otherwise, replaced. Also, replace any sprinkler to be inspected,tested,and maintained
non operation in the event of a fire or that has a cracked bulb or that has lost by a qualified Inspection Service in
inadvertent operation may result. liquid from its bulb. (Ref. Installation accordance with local requirements
Section.) and/or national codes.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro Thereafter, annual inspections per
sion must be replaced. NFPA 25 are required;however, instead
of inspecting from the floor level, a
Automatic sprinklers must never be random sampling of close-up visual
painted, plated, coated, or otherwise inspections should be made.
altered after leaving the factory.
TFP152
Page 4 of 4
P/N* 77 - XXX - X - XXX
I I
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
570 5.6K UPRIGHT(1/2"NPT) TY315 1 NATURAL BRASS 135 135°F(57°C)
571 5.6K PENDENT(1/2"NPT) TY325 g PURE WHITE(RAL9010)°° 155 155°F(68°C)
POLYESTER
'Use suffix"1'for ISO 7-1 connection; SIGNAL WHITE(RAL9003)
for example,77-570-4-175-1 4 POLYESTER 175 175°F(79°C)
9 CHROME PLATED 200 200°F(93°C)
"Eastern Hemisphere sales only P86 286°F(141°C)
360 360°F(182°C)
000 OPEN°°
'••OPEN indicates sprinkler
assembly without Glass Bulb,
Button,and Sealing Assembly
TABLE A
SERIES TV-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited Ordering •
Warranty Procedure
For warranty terms and conditions,visit Contact your local distributor for avail-
www.tyco-fire.com. ability.When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-B Upright or Pen-
dent(specify)Sprinkler, SIN (specify),
K=5.6, Standard Response, (specify)
temperature rating,(specify)finish, P/N
(specify,refer to Table A)
Recessed Escutcheon
Specify:Style 15 Recessed Escutcheon
with(specify')finish, P/N(specify`)
Specify:Style 20 Recessed Escutcheon
with(specify")finish, P/N(specify')
'Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright®2014 Tyco Fire Products,LP. All rights reserved. tyco
TEFLON is trademark of The DuPont Corporation, Fire Protection Products
fr
ECEIVE
t AAR ME Worldwide I www.tyco-fire.com
Co® Contacts
y a� GE, UP`if OFTIGARG
3UILDING DIVISION
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE -. ..
The TYCO Series TY-FRB Sprinklers at
"'." $r7N
Description described herein must be installed
and maintained in compliance with f.
AP..
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the
Upright (TY313) and Pendent (TY323) applicable standards of the National
Sprinklers described in this data sheet Fire Protection Association,in addition t, `it }
are quick response,standard coverage, to the standards of any other authori-
decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so ,;
sprinklers designed for use in light or may impair the performance of these - \
ordinary hazard,commercial occupan- devices.
cies such as banks, hotels, and shop- The owner is responsible for main- . -- _
ping malls. taining their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable,is intended for use in areas tor or product manufacturer with any
with a finished ceiling. This recessed questions.
pendent sprinkler uses one of the .
following: Sprinkler
• A two-piece Style 15 Recessed ,
Escutcheon with recessed adjust- Identification v_. ,
mentftup t e in. siti mm) from Number (SIN)the flush pendent position.
• A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT
Escutcheon with recessed adjust- " • `.
ment up to 1/2 in. (12,7 mm) from TY323 Pendent 5.6K, 1/2 in. NPT
the flush pendent position. Technical
The adjustment provided by the Data Operation
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat.When
Refer to Table A the rated temperature is reached, the
Intermediate level versions of Series fluid expands sufficiently to shatter the
TY-FRB Sprinklers are described in Maximum Working Pressure glass bulb, allowing the sprinkler to
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) activate and water to flow.
kler guards and shields are described 250 psi(17.2 bare
in Technical Data Sheet TFP7eO. 'The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries,Inc.(UL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psi' (60,6 LPM/bars) The TYCO Series TY-FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information. tion systems designed in accordance
Always refer to Technical Data Finishes Sprinkler: the standard installation rules
Sprinkler:Refer to Table B recognized bythe applicable Listingor
Sheet TFP700 for the "INSTALLER 9 PP
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and com-
Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets). Only the Style 15 or Style
- a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
it to operate prematurely. Compression Screw Bronze
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
e
TFP172
Page 2 of 4
i•
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
* 1
6_
5- n 7/16" 1 \ \
(11,1 mm)
4 NOMINAL 2° 0 Nil
MAKE-IN (50,8 mm)
2� T.-.1' N'N 1 /
ii FA 2" "� 1I/ 1-3/8"
3 (50,8 mm) 1 (34,9 mm)
4 WRENCH
FLATS
1 '
t 1/2" NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. -
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
el Installation Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
027.'
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FIGURE 2 Do not install any bulb-type sprin- erence to Figure 1, apply the W-Type 6
W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 lb-ft (9,5 to
sprinkler held horizontally, a small air 19,0 N•m).
bubble should be present. The diam- Recessed Pendent Sprinklers
WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor-
/ 3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions.
temperature ratings.Or". it Step A. After installing the Style 15
A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the
of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairment P 9 p .
of the sprinkler. Ste B. Ti hten the s rinkler into the
PUSH WRENCH
IN TO ENSURE sprinkler fitting using only the W-Type
ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WRENCHING AREA eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
W-TYPE 7 RECESSED
SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.
t
4.
TFP172
Page 3 of 4
i
Care and 2-7/8" DIA. -
(73,0 mm)
Maintenance 2-1/4" DIA.
• The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm)
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8" (15,9 mm)
viced in accordance with this section. + \ No FLUSH
Before closing a fire protection system 3/8±5/16"
I
main control valve for maintenance (9,5±7,9 mm) "f EA ) r
work on the fire protection system f /
that it controls, obtain permission to � � 1/8"
shut down the affected fire protection MOUNTING I
SURFACE 3,2 mm)
systems from the proper authorities
and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
affected by this action. TY-FRB PLATE
Absence of the outer piece of an
escutcheon, which is used to cover FIGURE4
a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only 2-7/8" DIA.
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER 2-1/4" DIA. _
vertent operation may result. FITTING r (57,2 mm)
Sprinklers which are found to be
P 5/16±1/4" 1 1/2"(12,7 mm)
leaking or exhibiting visible signs of (7,9±6,4 mm)
corrosion must be replaced. m FLUSH
Automatic sprinklers must never be I ' ,7- + 1
painted, plated, coated, or other- Tou___--- --1
wise altered after leaving the factory. } / 1/8"
Modified sprinklers must be replaced. MOUNTING (3,2 mm)J
Sprinklers that have been exposed to SURFACE
corrosive products of combustion, but
have not operated,should be replaced
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
klers damaged by dropping, striking,
wrench twist/slippage,or the like,must Recessed Escutcheon
be replaced. Also, replace any sprin- Limited Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has eon with(specify*)finish, P/N(specify*)
lost liquid from its bulb. (Ref. Installa- Warranty
tion Section.) Specify: Style 20 Recessed Escutch-
For warranty terms and conditions,visit eon with(specify*)finish, P/N(specify')
The owner is responsible for the www.tyco-fire.com.p y *Refer to Technical Data Sheet TFP770
inspection,testing,and maintenance of
their fire protection system and devices Sprinkler Wrench
in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench,
well as with the applicable standards Procedure P/N 56-000-6-387
of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order,indicate
having jurisdiction. Contact the install- the full product name and Part Number
ing contractor or product manufacturer (P/N).
with any questions.
systems are rec- Sprinkler Assemblies with NPT
sprinklerAutomatic
y Thread Connections
ommended to be inspected, tested, Specify: Series TY-FRB Upright or
and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN
tion Service in accordance with local (specify), K=5.6, Quick Response,
requirements and/or national codes. (specify)temperature rating, (specify)
, finish, P/N (specify,refer to Table A).
s
TFP172
Page 4 of 4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERC
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
PENDENT 200°F(93°C) Green
5.6 (TY323)
1/2 in.NPT 286°F(141°C) Blue
135°F(57°C) Orange
RECESSEPENDENT
P 155°F(68°C) Red
(TY323) 175°F(79°C) Yellow 1,2,3,4
Figures 4e and 5b
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories,Inc.,ILL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed.the sprinklers are UL end C-UL Listed as Corrosion-Resistant Sprinklers,
a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)8 155 155°F(68°C)
POLYESTER
Notes: SIGNAL WHITE(RAL9003)
a. Use suffix°I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C)
77-370-4-175-I
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 CHROME PLATED 286 286°F(141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION