Report /!//7 �jPrt t3Gl/2 F 2O22-XJ Oj
OFFICE COPY
AFP Systems, Inc.
Automatic Fire Protection RECEIVED
19435 SW 129'h Avenue
a o Tualatin,OR. 97062 FEB 1 4 2022
SYSTEMS (503)692-9284
(503)692-1186 fax (;ITY OF TIGARD
4)9F : UILDING DIVISION
SUBMITTAL
Project Name:
NW Fencing TI
11117 SW Greenburg Rd.
Tigard, OR 97223
For:
Robinson Construction
co®tq
Worldwide www.tyco-fire.com
Contacts
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The TYCO Series TY-FRB Sprinklers - - IS
Description described herein must be installed1.
and maintained in compliance with
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the £
Upright (TY313) and Pendent (TY323) applicable standards of the National ti
Sprinklers described in this data sheet Fire Protection Association,in addition
are quick response,standard coverage, to the standards of any other authori-
decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so
sprinklers designed for use in light or may impair the performance of these " *max °`'"
ordinary hazard,commercial occupan- devices.
cies such as banks, hotels, and shop- :24-
The owner is responsible for main ' -.,
ping malls. taining their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable, is intended for use in areas tor or product manufacturer with any }
with a finished ceiling. This recessed questions.
pendent sprinkler uses one of the ,,, . .
following: Sprinkler
• A two-piece Style 15 Recessed Identification f V.a ""00)
Escutcheon with recessed adjust ;q ,--
ment
up to e in. siti mm) from Number (SIN) .l
the flush pendent position.
• A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT , or',
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from TY323. . . .Pendent 5.6K, 1/2 in. NPT
the flush pendent position. Technical
The adjustment provided by the Operation
Recessed Escutcheon reduces the Data
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat.When
Intermediate level versions of Series Refer to Table A the rated temperature is reached, the
fluTY-FRB Sprinklers are described in Maximum Working Pressure glass expands sufficientlyw nthe to shatter the
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) bulb, allowing sprinkler to
kler guards and shields are described 250 psi(17.2 bar)* activate and water to flow.
in Technical Data Sheet TFP780. •The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries.Inc.(UL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psi%(80,6 LPM/bar'%) The TYCO Series TY-FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information. tion systems designed in accordance
Finishes
Always refer to Technical Data Sprinkler:Refer to Table B with the standard installation rules
Sheet TFP700 for the "INSTALLER recognized by the applicable Listing or
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and corn- Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style
a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
it to operate prematurely. Compression Screw Bronze
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
rTFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* I
/I ri' \ 1 \ i
�/ 7/16"
(11,1 mm)
4 i
NOMINAL 2" (
MAKE-IN (50,82 mm) 1 '1
2 r r 1 a 2" �Il (li 1-3/8" �1
3 W, (50,8 mm) (34,9 mm)
1 ` I FLATS
H P j1 } /
1/2"NPT** DEFLECTOR* 1- 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
L� applied to the pipe threads, hand-
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
"'I General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FIGURE 2 Do not install any bulb-type sprin erence to Figure 1,apply the W-Type 6
I W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 lb-ft (9,5 to
sprinkler held horizontally, a small air 19,0 N m).
bubble should be present. The diam- Recessed Pendent Sprinklers
WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor-
3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions.
14-f temperature ratings. Step A. After installing the Style 15
A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
I should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
CI
14 Ib ft(9,5 to 19,0 N m). Higher levels hand tighten the sprinkler into the
`� of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairment PUSH WRENCH of the sprinkler. Step B. Tighten the sprinkler into the
IN TO ENSURE sprinkler fitting using only the W-Type
ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WRENCHING AREA eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
W-TYPE 7 RECESSED
SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.
TFP1T2
Page 3 of 4
—
Care and 2-7/8" DIA. -
(73,0 mm)
Maintenance 2-1/4" DIA.
The TYCO Series TY-FRB,5.6 K-factor, FACE OF - (57,2 mm)
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm)
viced in accordance with this section. + \ NE FLUSH
Before closing a fire protection system 3/8±5/16" ' �
main control valve for maintenance (9,5±7,9 mm) Az7it i \1v
work on the fire protection system f /
that it controls, obtain permission to '_, 1/8,
shut down the affected fire protection MOUNTING (3,2 mm)
systems from the proper authorities SURFACE
and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
affected by this action.
TY-FRB PLATE 3/4'(19,1 mm)
Absence of the outer piece of an
escutcheon, which is used to cover FIGURE 4
a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any —
objects and that the sprinklers are only 2-7/8" DIA. -
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER 2-1/4" DIA.
vertent operation may result. FITTING (57,2 mm)
Sprinklers which are found to be 5/16±1/4"
leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm)
corrosion must be replaced. + um FLUSH
Automatic sprinklers must never be 1 . ,.
plated, coated, or other- d \-
painted,wise altered after leaving the factory. /
Modified sprinklers must be replaced. MOUNTING 1/8'Sprinklers that have been exposed to SURFACE (3,2 mm)
corrosive products of combustion, but _
have not operated,should be replaced
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
klers damaged by dropping, striking,
wrench twist/slippage,or the like,must Limited Recessed Escutcheon
be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has warrant eon with(specify`)finish,P/N(specify`)
lost liquid from its bulb. (Ref. Installa- Y Specify: Style 20 Recessed Escutch-
tion Section.) For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify*)
The owner is responsible for the www.tyco-fire.com. "Refer to Technical Data Sheet TFP770
inspection,testing,and maintenance of
their fire protection system and devices Ordering Sprinkler Wrench
in compliance with this document, as Specify: W-Type 6 Sprinkler Wrench,
well as with the applicable standards Procedure P/N 56-000-6-387
of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order,indicate
having jurisdiction. Contact the install- the full product name and Part Number
ing contractor or product manufacturer (P/N).
with any questions.
Sprinkler Assemblies with NPT
Automatic sprinkler systems are rec- Thread Connections
ommended to be inspected, tested, Specify: Series TY-FRB Upright or
and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN
tion Service in accordance with local (specify), K=5.6, Quick Response,
requirements and/or national codes. (specify)temperature rating, (specify)
finish, P/N (specify, refer to Table A).
TFP172
Page 4 of 4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERc
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
PENDENT(TY323) 200°F(93°C) Green
5.6 286'F(141°C) Blue
1/2 in.NPT
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
TY323 1,2,3,4
( ) 175°F(79°C) Yellow
Figures 4a and 5b
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
•
371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C)
POLYESTER
Notes: SIGNAL WHITE(RAL9003)
a. Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C)
77-370-4-175-I
•
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 . CHROME PLATED 286 286°F(141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Op/02018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls
TEFLON Is a registered trademark of DuPont Controls
u. .
Vico Fire & Building
Products
rapid response
HOME FIRE SPRINKLER SYSTEM
Technical Services:Tel: (800)381-9312/Fax: (800)791-5500
BlazeMaster
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General Technical
Description Data
Tyco Fire & Building Products (TFBP) Sizes
BlazeMaster CPVC Pipe and Fittings 3/4"to 3"
are designed exclusively for use in wet Maximum Working Pressure
pipe automatic fire sprinkler systems. 175 psi ;
They are made from a specially devel-
oped thermoplastic compound corn- Approvals
posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County,
chloride(CPVC) resin and state of the LPCB,MEA,and the City of Los Ange-
art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu-
CPVC products are easier to install ary 2005 "Installation Instruction &
than traditional steel pipe systems, Technical Handbook" for exact list- ,
and at the same time,provide superior ing/approval information.) •
heat resistance and strength as corn- Manufacture Source
pared to traditional CPVC and PVC U.S.A.
piping materials used in the plumbing
trade. Various adapters are available Material
to connect CPVC pipe to metallic pip . Pipe: ASTM F442, SDR 13.5
ing. All female pipe thread adapters
have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and
Grooved adapters connect directly to ASTM F439(Sch. 80),ASTM F1970
grooved end valves and metallic pipe,
with flexible grooved end couplings. Color
Orange
WARNING
Tyco Fire& Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
BlazeMastere is a registered trademark
of Noveon IP Holding Corp.
Page 1 of 6 JANUARY, 2006 TFP1915
Page 2 of 6 TFP1915
NOMINAL AVERAGE AVERAGE WEIGHT WATER FT.OF PIPE WEIGHT PER LIFT
SIZE O D. 1.D lbs./ft FILLED WEIGHT PER LIFT lbs.
lbs./ft.
3/4" 1.050" 0.874" 018 0.44 7875 1339
1" 1.315" 1.101' 0.26 0.67 5040 1320
1-1/4" 1.660" 1.394" 0.42 1.08 2835 1191
1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213
2" 2.375" 2.003" 0.84 2.20 1260 1084
2-1/2" 2.875" 2.423" 126 3.26 1215 1531
3" 3.500" 2.952" 1.87 4 83 720 1344
FIGURE 1—PIPE DIMENSIONS
Installation Care and
Tyco Fire and Building Products Maintenance
(TFBP) BlazeMaster CPVC Pipe and
Fittings are to be installed in accord- The owner is responsible for the fin-
ance with IH-1900, Rev. 0, January spection, testing, and maintenance of
2005"Installation Instruction&Techni- their fire protection system and de-
cal Handbook". vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
NOTES
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls,permission to shut
down the affected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central sta-
tion alarms.
t E/Wa101i4 vii;w M.44,4,, ,Aavev xb it-Ake io10 s04,4.ii •w+w,u<d m rF..x.r N..i.A.a .'x'x.6414isre#u40-NOw ..,,,
TFP1915 Page 3 of 6
FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT
TYPE NUMBER (T/O) (lb.)
TEE 80000 3/4" 5/8" 40 0.11
i 1L T/O 80001 1" 11/16" 40 0.19
.�,j/ 80002 1-1/4" 7/8" 40 0.26
80003 1-1/2" 1-1/16" 80 0.51
80004 2" 1-3/8" 80 0.90
.J•�f•
80005 2-1/2" 1-9/16" 80 1.59
T/O ■■ T!O 80006 3" 13/16" 80 2.41
XxYxZ X Y Z
80132 3/4"x 3/4"x 1" 3/4" 3/4" 5/8" 40 0.14
80133 1"x 3/4"x 3/4" 9/16" 9/16" 3/4" 40 0.14
80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17
80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16
80135 1-1/4"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21
80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22
80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26
REDUCING TEE 80261 1-1/4"x 1-1/4"x 3/4" 5/8" 5/8" 7/8" 40 0.23
80262 1-1/4"x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26
Z 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" 1" 80 0.43
INF T/O
1 80140 1-1/2"x 1-1A"x 3/4" 9/16" 9/16" 1" 80 0.36
,a4` m 80141 1-1/2"x 1-1/4"x 1" 9/16" 9/16" 1-1/16" 80 0.38
80263 1-1/2"x 1-1/2"x 3/4" 9/16" 9/16" 1" 80 0.36
X 111111111111111 Y
80264 1-1/2"x 1-1/2"x 1" 9/16" 9/16" 1-1/16" 80 0.38
��J'�I'w 80275 1-1/2"x 1-1/2"x 1-1/4" 7/8" 7/8" 1" 80 0 45
T/O •• T/O 80265 2"x 2"x 3/4" 3/4" 3/4" 1-3/8" 80 0.61
80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66
80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74
80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78
80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43
80272 2-1/2"x 2-1/2"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46
80273 2-1/2"x 2-1/2"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48
80276 2-1/2"x 2-1/2"x 2" 1-9/16" 1-9/16" 1-9/16" 80 1.50
80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28
80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25
80269 3"x 3"x 2-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.44
CROSS&REDUCING CROSS 80009 3/4" 9/16" 40 0.13
J..'- T/O 80010 11/16" 40 0.34
80011 1-1/4" 15/16" 40 0.34
.4iiI ■ 80012 1-1/2" 1-1/16" 80 0.67
M80013 2" 1-5/16" 80 1.00
80014 2-1/2" 1-9/16" 80 1.91
II„II T/O 80008 3" 1-13/16" 80 2.89
T/O • T/O 80015 1"x 1"x 3/4"x 3/4" 7/8" 40 0.28
80025 3/4" 5/8" 40 0.09
90°ELBOW&
REDUCING ELBOW 80026 1" 3/4" 40 0.14
80027 1-1/4" 7/8" 40 0.21
X 80028 1-1/2" 1-1/16" 80 0.40
�„i T/O 80029 2" 1-5/16" 80 0.79
j�� 80030 2-1/2" 1-9/16" 80 1 14
�':. 80031 3" 1-13/16" 80 1.82
•••��41'•Y X x Y X Y
T/O
80032 1"x 314" 11/16" 13/16" 40 0 16
FIGURE 2-FITTING DIMENSIONS(Part 1 of 4)
Page 4 of 6 TFP1915
FITTING PART NOMINAL TAKE-OUT WEIGHT
TYPE NUMBER NOMINAL SIZE (T/O) SCHD. (lb.)
45°ELBOW 80050 3/4" 3/8" 40 0.08
I/O -- 80051 1" 3/8" 40 0.11
4,_ 80052 1-1/4" 3/4" 40 0.20
4' p�� 80053 1-1/2" 1/2" 80 0.31
41. 80054 2" 3/4" 80 0.56
T/O ♦ r
ill
dirilnimmum 80055 2-1/2" 13/16" 80 0.89
80056 3" 1" 80 1.19
80075 3/4" 1/8" 40 0.07
COUPLING& 80076 1" 1/8" 40 0.11
REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12
80078 1-1/2" 3/16" 80 0.25
IIII 80079 2" 3/16" 80 0.38
80080 2-1/2" 1/4" 80 0.67
T/0 80081 3" 3/16" 80 0.91
80220 1"x 3/4" 1/8" 40 0 08
80200 1"x 3/4" 7/16" 40 0.04
80201 1-1/4"x 3/4" 1/2" 40 0.11
80202 1-1/4"x 1" 5/16" 40 0 12
80203 1-1/2"x 3/4" 5/8" 80 0.16
80204 1-1/2"x 1" 1/2" 80 0.14
REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17
80206 2"x 3/4" 13/16" 80 0.27
..,Armiln 80207 2"x 1" 11/16" 80 0.26
80208 2"x 1-1/4" 9/16" 80 0.24
i• 80209 2"x 1-1/2" 7/16" 80 0.19
-I T/O 80215 2-1/2"x 1" 15/16" 80 0.42
80214 2-1/2"x 1-1/4" 13/16" 80 0.45
80213 2-1/2"x 1-1/2" 11/16" 80 0.46
80211 2-1/2"x 2" 5/8" 80 0.29
80210 3"x 2" 3/4" 80 0.72
80212 3"x 2-1/2" 1/2" 80 0.47
CAP 80100 3/4" 5/16" 40 0.04
80101 1" 3/8" 40 0.06
Nt/ 80102 1-1/4" 7/16" 40 0.10
1 80103 1-1/2" 11/16" 80 020
...../ 80104 2" 5/8" 80 0.31
T/O -- 80105 2-1/2" 7/8" 80 0 58
80106 3" 1" 80 0.88
GROOVED T/O PIPE O.D.
COUPLING ADAPTER
80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78
ittl.... N
■ 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 80 0.95
I` PIPE 80162 2"x 2"Groove 2-5/16" 2"(2.375") 80 1.42
O.D
•
80163 2-1/2"x 2-1/2"Groove 2-5/16" 2-1/2"(2.875") 80 2.28
IMAIIII1610' 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00
-T/O-- 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28
FIGURE 2-FITTING DIMENSIONS(Part 2 of 4)
t.3 ,6 imei t 0-. 7W'4`..t',4x.,i...1tx.Y,nM.w++'urorfixa JraYfA AMANS HWA6f `M.R.V ..... a0,..V .141.€.”Vavi -,. .. i+.ifOttH.,fte. ,
TFP1915 Page 5 of 6
FITTING PART NOMINAL TAKE-OUT WEIGHT
TYPE NUMBER NOMINAL SIZE (T/O) SCHD. (lb.)
SPRINKLER HEAD
ADAPTER
80175E 3/4"x 1/2"NPT 7/16" 80 0.20
80176E 1x 1/2"NPT 7/16" 80 0.22
I,i
1Yuu 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16
.�Sri
80179 1"x 3/4"NPT 13l16" 40 0.43
T/O
SPRINKLER HEAD
ADAPTER
��T r
��" 80175W 3/4"x 1/2"NPT 1/2" 40 0'19
�YYY
80176W 1"x 1/2"NPT 1/2" 40 0 18
T/O
SPRINKLER HEAD
ADAPTER(SPIGOT)
fferot , 80177L 3/4"x 1/2"NPT 1/2" 40 0.16
IIIIIl��� 80178 1"x 1/2"NPT 9/16" 40 0.20
��ii 80180 1"x 3/4"NPT 7/8" 40 0.40
—I T/O
FEMALE ADAPTER
`������ 80142 3/4"x 3/4"NPT 13/16" 40 0 41
80145 1'x 1"NPT
I
���� 80146 1-1/4"x 1-1/4"NPT 7/8"
1-1/8" 40
40 0.63
1.03
80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42
wiii��i\ \ 80148 2"x 2"NPT 1-11/16" 80 2.66
T/O
MALE ADAPTER
I1IVV 80157
80158 3/4''x 1"NPTPT 1153/8" 40
40 0 56
T/O—I
XxYxZ X Y Z
SPRINKLER HEAD
ADAPTER TEE 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22
Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29
`p=`o T/O 80249 1"x 1"x 1"NPT 15/16" 15/16" 1-9/16" 40 0.73
1k_.el
_��„`_— 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16" 40 0 30
1111- 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5/16" 40 0.31
80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43
....
III.........www........:
IIIII._ Y 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46
T/O • T/O 80258 2"x 1-1/2"x 1/2"NPT 1/2" 5/8" 1-11/16" 80 0.56
80253 2"x 2"x 1/2"NPT 1/2" 1/2" 1-11/16" 80 0.62
FIGURE 2—FITTING DIMENSIONS (Part 3 of 4)
Page 6 of 6 TFP1915
FITTING PART NOMINAL TAKE-OUT WEIGHT
TYPE NUMBER NOMINAL SIZE SCHD.
(T/O)
(lb.)
BACK-TO-BACK TEE X x Y x 2 X Y,Z
X
T/O�,,,`—
Y ��"'III= �'ll" 80459 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0 48
111111116.1111.11111 Z 80460 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0 46
...✓I�rApS:11:
T/O �•• T/O
BACK-TO-BACK CROSS X x Y x Z x W X,Y Z,W
X
IlL
T/O
_I NI ii
,��J�� ��,W 80462 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0 46
�'�� 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47
T/O II
T/O T/O
SPRINKLER HEAD X x Y X Y
ADAPTER 90°ELBOW
Y
i�LIO T/O
i �.1
MI
I80199 3/4"x 1/2"NPT 9/16" 1" 40 0.20
80198 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26
.'- X 80196 1"x 3/4"NPT 1-1/16" 1-7/16" 40 0.26
--- T/O
FIGURE 2—FITTING DIMENSIONS(Part 4 of 4)
Limited by TFBP to be defective shall be either of merchantability and fitness for a par-
repaired or replaced, at TFBP's sole ticular purpose.
Warranty option. TFBP neither assumes, nor This limited warranty sets forth the ex-
authorizes any person to assume for it, clusive remedy for claims based on
any other obligation in connection with failure of or defect in products, materi-
Products manufactured by Tyco Fire& the sale of products or parts of prod-
Building
Products (TFBP) are war- ucts.TFBP shall not be responsible for als or components, whether the claim
ranted solely to the original Buyer for sprinkler system design errors or inac is made in contract, tort, strict liability
ten(10)years against defects in mate- curate or incomplete information sup- or any other legal theory.
rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex-
and properly installed and maintained sentatives. tent permitted by law. The invalidity, in
under normal use and service. This In no event shall TFBP be liable, in whole or part, of any portion of this
warranty will expire ten (10) years warranty will not affect the remainder.
from date of shipment by TFBP. No contract, tort, strict liability or under
warranty is given for products or corn- any other legal theory, for incidental,
ponents manufactured by companies indirect,special or consequential dam
not affiliated by ownership with TFBP ages, including but not limited to labor
or for products and components which charges, regardless of whether TFBP
have been subject to misuse,improper was informed about the possibility of
installation, corrosion, or which have such damages, and in no event shall
not been installed, maintained, modi- TFBP's liability exceed an amount
fied or repaired in accordance with ap- equal to the sales price.
plicable Standards of the National Fire The foregoing warranty is made in lieu
Protection Association, and/or the of any and all other warranties, ex-
standards of any other Authorities press or implied. including warranties
Having Jurisdiction. Materials found
1
TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
CPVC (:))4.NviL
Fig. 184 (Formerly Afcon Fig. 515) Double Offset Hanger and Restrainer
Size Range:3/4"through 1"
Material: Carbon Steel ,
Finish:Pre-Galvanized per ASTM A653 c 13 US
Service: 111. LISTED
• Hanger and surge restraint for horizontal CPVC piping when installed on
the side of the supporting structure.
• Listed with hardware provided on structural wood beams and composite
wood beams(1"minimum).For wood structures with less than 1"thickness,wood ,
blocks may be placed on the backside of the wood structure.#14x1"fastener pro- .''
obi
vided must be fully engaged in the wood block.
• May be installed with concrete,steel,and other structural members with fasteners which
comply with the requirements of NFPA 13.
Approvals:cULus Listed
Installation:
• Slide CPVC pipe through the double offset hanger and restrainer.
• Secure the hanger to the supporting structure with the screws provided or with listed fasteners.
Features:
• Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion.
• Easily attaches to wood structure with#14 x 1"hex washer head self-threading screw supplied with product.No pre-drilling
required.
• Bottom of pipe is offset 1'/2' from the structure.Eliminates wooden spacer blocks
Ordering:Specify CPVC pipe size,figure number and description.
0 C x2 O CPVC Pipe MEE
e
f B Structure
PØ
r ive
Fasteners x2 j
•
igr Fig. 184
A 0 1111111111111
FIG. 184: DIMENSIONS (IN) • WEIGHT(LBS)
CPVC A B aC H L Max. Hanger Approx.
Pipe Size Spacing (FT.) Weight/100
3/4 1'/2 1'/2 1/4 31/8 5/e 5 V2 17
1 11A 11/2 1/4 3'/e 5'/e 6 17
PROJECT INFORMATION APPROVAL STAMP
Project: Approved
Address: ['Approved as noted
Contractor: Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18