Loading...
Report HE-L2o22--00 (z (5575 74111 AJ Co, GENERAC° y cn RECEIVED Protector® QS PROTECTOR® QS SERIES o • CD eries FEB� 17202t Standby Generators CITY OF TIGARD Liquid-Cooled Gaseous Engine 3UILDING DIVISION 1 of 9 INCLUDES: Standby Power Rating • Two Line LCD Multilingual Digital Evolution Model RG022 (Aluminum - Bisque) -22 kW 60 Hz Controller(English/Spanish/French/ Model RG027 (Aluminum - Bisque) -27 kW 60 Hz Portuguese)with external viewing window for Model RG032 (Aluminum - Bisque) -32 kW 60 Hz easy indication of generator status and Model RG038 (Aluminum - Bisque) -38 kW 60 Hz breaker position. • True Power Electrical Technology • Isochronous Electronic Governor • Sound Attenuated Enclosure —_ F OENEpert • Closed Coolant Recovery System =111 _ • Smart Battery Charger • —_• UV/Ozone Resistant Hoses I • ±1%Voltage Regulationinumaimiamia • Natural Gas or LP Operation • 5 Year Limited Warranty • UL 2200 Listed • • SwRi® listed (NFPA37, clause 4.1.4.1.2) C (T1) . 6Bp1LT QUIET TEST Generator can be installed a minimum 18" domesik aM foreign pats distance from combustible wall* Meets EPA Emission Regulations *Only if located away from doors,windows,and fresh air intakes, 22&27 kW are CA/MA emissions compliant 32&38 kW not for sale in CA/MA and unless otherwise directed by local codes.Please review install guide for more details. FEATURES O INNOVATIVE DESIGN& PROTOTYPE TESTING are key components of 0 SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE GENERAC'S success in "IMPROVING POWER BY DESIGN." But it doesn't REGULATION.This state-of-the-art power maximizing regulation system is stop there. Total commitment to component testing, reliability testing, standard on all Generac models.It provides optimized FAST RESPONSE to environmental testing, destruction and life testing, plus testing to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY applicable CSA,NEMA, EGSA,and other standards,allows you to choose by electronically torque-matching the surge loads to the engine. Digital GENERAC POWER SYSTEMS with the confidence that these systems will voltage regulation at ±1%. provide superior performance. O TEST CRITERIA: 0 SINGLE SOURCE SERVICE RESPONSE from Generac's extensive dealer ✓ PROTOTYPE TESTED ✓ NEMA MG1-22 EVALUATION network provides parts and service know-how for the entire unit, from the v SYSTEM TORSIONAL TESTED ✓ MOTOR STARTING ABILITY engine to the smallest electronic component. O GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is the GENERAC product line is offered with its own transfer systems and controls for total system compatibility. GENERAC 'so , 4 N GENERAa a, y 22 • 27 • 32 • 38 application & engineering data o GENERATOR SPECIFICATIONS ENGINE SPECIFICATIONS:22,27,32&38 kW U + a' Type Synchronous Make Generac 0 Rotor Insulation Class H(22&27 kW)or Model In-line F(32&38 kW) Cylinders 4 Stator Insulation Class H Displacement(Liters) 2.4 2 of 9 Telephone Interference Factor(TIF) <50 Bore(in/mm) 3.41/86.5 Alternator Output Leads 1-Phase 4 wire Stroke(in/mm) 3.94/100 Alternator Output Leads 3-Phase 6 wire Compression Ratio 9.5:1 Bearings Sealed Ball Naturally Aspirated(22&27 kW) Coupling Flexible Disc or Intake Air System Turbocharged/Aftercooled Excitation System Direct (32&38 kW) VOLTAGE REGULATION Lifter Type Hydraulic Type Electronic Sensing Single Phase ENGINE LUBRICATION SYSTEM Oil Pump Type Gear Regulation ±1% Oil Filter Type Full flow spin-on cartridge GOVERNOR SPECIFICATIONS Crankcase Capacity(qVl) 4/3.8(22,27,32&38 kW) Type Electronic ENGINE COOLING SYSTEM Frequency Regulation Isochronous Type Closed Steady State Regulation ±0.25% Water Pump Belt driven ELECTRICAL SYSTEM Fan Speed(rpm) 1980-22&27 kW 1500-32&38kW Battery Charge Alternator 12 Volt 30 Amp 22&27 kW)or Static Battery Charger 2.5 Amp Fan Diameter(in/mm) 181/459.7 P2/558(8(32&38 kW) Recommended Battery(battery not included) Group 26(22,27,32&38 kW) Fan Mode Pusher(22&27 kW)or System Voltage 12 Volts Puller(32&38 kW) FUEL SYSTEM GENERATOR FEATURES Fuel Type Natural gas,propane vapor Revolving field heavy duty generator Directly connected to the engine Carburetor Down Draft Operating temperature rise 120°C above a 40°C ambient Secondary Fuel Regulator Standard Class H insulation is NEMA rated Class F insulation is NEMA rated Fuel Shut Oft Solenoid Standard All models fully prototyped tested Operating Fuel Pressure 5-14"water column/9-26 mm HG LP Fuel Pressure 11-14"Water Column ENCLOSURE FEATURES NG Fuel Pressure 5-14"Water Column Aluminum weather protective Ensures protection against mother nature. enclosure Electrostatically applied textured epoxy paint for added du- rability. Enclosed critical grade muf-Quiet,critical grade muffler is mounted inside the unit to fler prevent injuries. Small,compact,attractive Makes for an easy,eye appealing installation. SAE Sound attenuated enclosure ensures quiet operation. (All ratings in accordance with BS5514,IS03046,IS08528,SAE J1349 and DIN6271) GENERACCD _... N N 22 • 27 • 32 • 38 operating data scgt GENERATOR OUTPUT VOLTAGE/kW-60 Hz o U . 0) kW LPG Amp LPG kW Nat.Gas Amp Nat.Gas CB Size(Both) o a 120/240 V,10,1.0 pf 22 92 22 92 100 RG022 120/208 V,30,0.8 pf 22 76 22 76 80 120/240 V,30,0.8 pf 22 66 22 66 80 3 of 9 120/240 V,10,1.0 pf 27 113 25 104 125 RG027 120/208 V,30,0.8 pf 27 94 25 87 100 120/240 V,30,0.8 pf 27 81 25 75 90 120/240 V,10,1.0 pf 32 133 32 133 150 120/208 V,30,0.8 pf 32 111 32 111 125 RG032 120/240 V,30,0.8 pf 32 96 32 96 100 277/480 V,30,0.8 pf 32 48 32 48 60 120/240 V,10,1.0 pf 38 158 38 158 175 RG038 120/208 V,30,0.8 pf 38 132 38 132 150 120/240 V,30,0.8 pf 38 114 38 114 125 277/480 V,30,0.8 pf 38 57 38 57 60 SURGE CAPACITY IN AMPS ENGINE FUEL CONSUMPTION Voltage Dip @<.4 pf Natural Gas Propane 15% 30% (ft3/hr) (m3/hr) (gal/hr) (ft3/hr) (I/hr) 120/240 V,10 55 135 Exercise cycle 42 1.2 0.44 16 1.7 RG022 120/208 V,30 40 92 25%of rated load 100 2.8 1.1 40 4.2 120/240 V,30 35 80 RG022 50%of rated load 190 5.4 2.1 75 7.8 120/240 V,10 62 170 75%of rated load 255 7.2 2.8 101 10.5 RG027 120/208 V,30 70 120 100%of rated load 316 9 3.4 125 13 120/240 V,30 61 103 Exercise cycle 42 1.2 0.44 16 1.7 120/240 V,10 75 180 25%of rated load 108 3.1 1.2 43 4.5 120/208 V,30 87 210 RG027 50%of rated load 197 5.6 2.1 78 8.1 RG032 120/240 V,30 75 182 75%of rated load 287 8.2 3.1 114 11.8 277/480 V,30 36 87 100%of rated load 359 10.2 3.9 143 14.8 120/240 V,10 75 180 Exercise cycle 79 2,2 0.8 30 3.2 120/208 V,30 87 210 25%of rated load 144 4.1 1.7 60 6.3 RG038 120/240 V,30 75 182 RG032 50%of rated load 226 6.4 2.7 97 10.3 277/480 V,30 36 87 75%of rated load 298 6.4 3.7 132 13.9 100%of rated load 375 10.6 4.6 166 17.5 Note:Fuel pipe must be sized for full load. Exercise cycle 83 2.3 0.9 31 3.2 For Btu content,multiply ft3/hr x 2520(LP)or ft3/hr x 1000(NG) 25%of rated load 162 4.6 1.7 62 6.6 For megajoule content,multiply m3/hr x 93.15(LP)or m3/hr x 37.26(NG) RG038 50%of rated load 255 7.2 2.9 103 10.8 75%of rated load 345 9.8 4 142 15 Refer to"Emissions Data Sheets"for maximum fuel flow for EPA and SCAQMD permitting purposes. 100%of rated load 437 12.4 5.2 185 19 STANDBY RATING:Standby ratings apply to installations served by a reliable utility source.The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating.Ratings are in accordance with ISO-3046-1.Design and specifications are subject to change without notice. 1 GENERAC® N N 22 • 27 • 32 • 38 operating data • t ENGINE COOLING °= 22kW 27kW 32&38kW a Air flow(inlet air including alternator and combustion air in cfm/cmm) 2400/68 2400/68 2200/62.3 System coolant capacity(gal/liters) 2.5/9.5 2.5/9.5 2.5/9.5 Heat rejection to coolant(BTU per hr/MJ per hr) 99,000/104.5 105,000/110.8 145,000/153 4 of 9 Maximum operation air temperature on radiator(°C/°F) 60/150 Maximum ambient temperature(°C/°F) 50/140 COMBUSTION REQUIREMENTS Flow at rated power(cfm/cmm) 68/1.9 68/1.9 106/3 SOUND EMISSIONS Sound output in dB(A)at 23 ft(7 m)with generator in exercise mode° 61 61 58 Sound output in dB(A)at 23 ft(7 m)with generator operating at normal load" 70 70 64 EXHAUST Exhaust flow at rated output(cfm/cmm) 165/4.7 180/5.1 300/8.5 Exhaust temperature at muffler outlet(°C/°F) 482/900 538/1000 579/1075 ENGINE PARAMETERS Rated Synchronous rpm 1800 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3%for every 10°C above 25°C or 1.65%for every 10°F above 77°F Altitude Deration(22&27 kW) 1%for every 100 m above 183 m or 3%for every 1000 ft above 600 ft Altitude Deration(32&38 kW) 1%for every 100 m above 915 m or 3%for every 1000 ft above 3000 ft CONTROLLER FEATURES Two-Line Plain Text LCD Display Simple user interface for ease of operation. Mode Switch: Auto Automatic Start on Utility failure.7 day exerciser Off Stops unit.Power is removed.Control and charger still operate. Manual Start with starter control,unit stays on.If utility fails,transfer to load takes place. Programmable start delay between 10-30 seconds 10 sec standard Engine Start Sequence Cyclic cranking:16 sec on,7 rest(90 sec maximum duration) Engine Warm-up 5 sec Engine Cool-Down 1 min Starter Lock-out Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger Standard Automatic Voltage Regulation with Over and Under Voltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard,72 Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard Failure to Transfer Protection Standard Low Battery Protection Standard 50 Event Run Log... Standard Future Set Capable Exerciser Standard Incorrect Wiring Protection Standard Internal Fault Protection Standard Common External Fault Capability Standard Governor Failure Protection Standard e GENERAC' cu y 22 • 27 • 32 • 38 available accessories u • Model # Product Description CD 0 i 0_ Generac's Mobile Link allows you to check the status of your generator from Mobile Link®4G LTE anywhere that you have access to an Internet connection from a PC or with G0071690 Cellular Accessory any smart device.You will even be notified when a change in the generator's 5 of 9 status occurs via e-mail or text message.Note:Harness Adapter Kit required. Available in the U.S.only. Kit, Adapter Mobile The Harness Adapter Kit is required to make liquid-cooled units compatible G006478-0 Link L/C (Required with Mobile Link®. for QT and RG Series) G005630-1 -22,27,32&38 If the temperature regularly falls below 32°F(0°C), install a cold weather kit kW Cold Weather Kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. G00561 6-0-22,27,32&38 Extreme Cold Recommended where the temperature regularly falls below 32°F(0°C)for kW Weather Kit extended periods of time. For liquid cooled units only. G005651-0 Base Plug Kit Add base plugs to the base of the generator to keep out debris. If the generator enclosure is scratched or damaged,it is important to touch-up G005703-0-Bisque Paint Kit the paint to protect from future corrosion.The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure. G005656-0 22&27 kW Scheduled The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware G005984-0 32&38 kW Maintenance Kit necessary to perform complete maintenance on Generac liquid-cooled generators. G006664-0 Local Wireless Completely wireless and battery powered,Generac's wireless remote monitor Monitor provides you with instant status information without ever leaving the house. G006665-0 Wireless Remote Recommended for use with the Wireless Remote on units up to 60 kW, Extension Harness required for use on units 70 kW or greater. Smart Management Modules are used in conjunction with the Automatic G006873-0 Smart Management Transfer Switch to increase its power management capabilities. It provides Module (50 Amps) additional power management flexibility not found in any other power management system. E-stop toggle switch E-stop allows for immediate fuel shutoff and generator shutdown in the event G007993-0 for residential installs of an emergency. to NEC2017 E-Stop resettable G006510 0 switch for commer- E-stop allows for immediate fuel shutoff and generator shutdown in the event cial installs to of an emergency. NEC2020 The Wi-Fi enabled LP fuel level monitor provides constant monitoring of the Wi-Fi LP Fuel Level connected LP fuel tank.Monitoring the LP tank's fuel level is an important step G007005-0 in making sure your generator is ready to run during an unexpected power Monitor failure.Status alerts are available through a free application to notify when your LP tank is in need of a refill. N cn Protector® QS Series 1a o IV : N an QO o IV . SERVICE ITEM 2.41 0) NOTES: O) Pr OIL FLL CAP EITHER SIDE . RADIATOR/EXHAUST OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1092(43")WIDE X 1885(74.2")LONG. DISCHARGE AIR AIR INTAKE OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. n (BOTH SIDES) (BOTH SIDES) OIL DRAM HOSE LEFT SIDE 2.ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE 1 BATTERY 12 GRP 26 RADIATOR DRAIN LEFT SIDE AND SERVICING.THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT ^ V COOLANT RECOVERY BOTTLE LEFT SIDEAPPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, IDRADIATOR Flu CAP ROOF TOP STATE,AND LOCAL CODES. NEGATIVE GROUND AIR CLEANER ELEMENT LEFT SIDE SPARK PLUGS LEFT SIDE 3.CONTROL PANEL/CIRCUIT BREAKER INFORMATION: PM:077483 -SEE SPECIFICATION SHEET OR OWNERS MANUAL REMOVE COVE• MUFFLER SEE NOTE 11 -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. FOR ACCESS TO -- -.�. 4.REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS , RADIATOR FILL CAP II DRIVE BELT EITHER SIDE FAN BELT SEE NOTE 11 THE STUB-UP AREAS AS FOLLOWS: -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION I • BATTERY LEFT SIDE NEUTRAL CONNECTION,BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. REFERENCE OWNERS MANUAL -LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. FOR PERIODIC REPLACEMENT 5.CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 427 ] PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND [16.8] RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. } r .. 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 8.MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 (USE STANDARD SAE TORQUE SPECS) —►I141 9.MUST ALLOW FREE FLOW OF INTAKE AIR,DISCHARGE AIR AND EXHAUST.SEE SPEC — I 629.9[24.8] SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. [5.6] CENTER OF GRAVITY 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE (SEE NOTE 5) AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. , TOP VIEW 11.EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE, REMOVE FRONT PANEL TO ACCESS. EXHAUST MUFFLHR ENCLOSED WITHIN CIRCUIT BREAM• GENERATOR ENCLOSURE SEE NOTE 3 631 [24.8]—or- DOOR TYP •( 'SW 4 V' t P z C n REAR ENCLOSURE SIW•TAN T t • 980 COVER PANEL Is 1 ; [38.6] .r SEE NOTE 4 ; VICE ACTION LATCH, RADIATOR/EXHAUST j i ' 6 1,. OVERALL e = DISCHARGE AIR U., i' It .. ONE PER DOOR, HEIGHT a 1 - USTOMERACCESS 48 k' ¢ ONE LIFT OFF 4 s € ASSEMBLY,CONTROL (1 9] A �;i DOOR PER SIDE L i e .► ;.., MO ' PANEL ACCESS, TYP A, Abr. I ,4 OF GENERATOR BATTERY CHARGERlkk 1 � LOCATED WITHIN T "atr A 1040 .1 SEE NOTE 4 1 48 [40.9] f—776 [30.6] 45----• 1490 [58.7]TYP 'ij OVERALL WIDTH . 1580[622] It 91 FUEL LINE CONNECTION [1.8] 3/4"NPT FEMALE COUPLING REAR VIEW TYP OVERALL LENGTH LEFT SIDE VIEW WEIGHT DATA RIGHT SIDE VIEW WEIGHT WEIGHT ENGINE/KW ENCLOSURE SHIPPING WEIGHT GENSET ONLY SHIPPING SKID R KVA MATERIAL KG BS] KGILBSJ KG ILBSI 2.PH2SE I7/KVA =� SINGLE PHASE 17./KVA(50H2) AL 410.519051 30]66] 4401971J 'w THREE PHASE 22KVA(50HZ) V 241 27KW(60HZ) Om* SINGLE PHASE 21.BKVA(50HZ) AL 426[9401 30 IRE 456[1006] DIMENSIONS:MM[INCH] THREE PHASE 27KVA(50H2) CO ZPAWN 0� m g n n .4 N fact 13.5 X 29.5 N MOUNTING SLOTS 'NOTE-STUB-UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. Pk • •:rV'''Mn :O • 4 4444�00' 674 I :^•r�?rg��h [26.5] �Oy;N -104.5 [4.11] 111 'STUB-UP I AREA 28 9 51 [1.1] 1001111 [A] [2.0] [3.9] `STUB-UP AREA - - 1370[54.0] ► 210[8.3] -EMOVABLE TOP VIEW STUB-UP COVER 735 [28.9]:111111111.111111111111Fill 96 [3.8] F 45 [1.8]TYP - r- 1380[54.3]TYP 27 [1.0)-- - 723 [28.5]TYP TYP MOUNTING SLOT CENTERS 1.1 MOUNTING SLOT CENTERS 776 [30.6] 1580[62.2] LEFT SIDE VIEW REAR VIEW �• y DIMENSIONS:MM[INCH] cQ O P.F o. 301 co n N 0 Protector® OS Series s Protector® QS Series Lo CD CO ,y N 10 Re * COCD Co CD SERVICE ITEM 24L NOTES: Iry P— RADIATOR/EXHAUST OIL FILL CAP EITHER SIDE W DISCHARGE AIR AIR INTAKE OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1194(47")WIDE X 2255(88.8")LONG. (BOTH SIDES) (BOTH SIDES OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. O° A OIL DRAIN HOSE RIGHT SIDE 2,ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE RADIATOR DRAIN HOSE LEFT SIDE AND SERVICING.THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT p COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, -4—768 [30.2]—0- RADIATOR FILL CAP ACCESS ROOF TOP STATE,AND LOCAL CODES. IV — CENTER OF GRAVITY AIR CLEANER ELEMENT RIGHT SIDE 3.CONTROL PANEL/CIRCUIT BREAKER INFORMATION: 167 SEE NOTE 5 SPARK PLUGS LEFT SIDE -SEE SPECIFICATION SHEET OR OWNERS MANUAL [6.6] MUFFLER SEE NOTE 11 -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. < x 1x DRIVE BELT EITHER SIDE 4.REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS 1. -' THE STUB-UP AREAS AS FOLLOWS: FAN BELT SEE NOTE 11 • j BATTERY LEFT SIDE -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,NEUTRAL 535 CONNECTION,AND BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. [21.1] REFERENCE OWNERS MANUAL -LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. m FOR PERIODIC REPLACEMENT 5.(UCENTERSESTANDARD OF GRAVITY AND WEIGHT MAYSPECS) CHANGE DUE TO UNIT OPTIONS. PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 8.MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 2.5"O.D.EXHAUST SAE TORQUE OUTLET 9.MUST ALLOW FREE FLOW OF INTAKE AIR,DISCHARGE AIR AND EXHAUST.SEE SPEC SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE REMOVE COVE' TOP VIEW BATTERY 12V,GRP 26 AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. FOR ACCESS TO NEGATIVE GROUND 11.EXHAUST MUFFLER AND FAN BELT ARE ENCLOSED WITHIN GENERATOR ENCLOSURE, RADIATOR FILL CAP P/N:077483 REMOVE FRONT PANEL TO ACCESS. VICE ACTION LATCH, MUFFLER ONE PER DOOR, ENCLOSED WITHIN CIRCUIT BREAKE" 'kl—759 [29.9] ONE LIFT OFF GENERATOR ENCLOSURE SEE NOTE 3 DOOR TYP ADOOR PER SIDE All OF GENERATOR n -� 4 REAR ENCLOSURE -:,--9, J /EXHAUST E ] COVER PANEL s'''-='-it''''; ',---- - - ' 'i"- =; -•-•;' Z "21k ' , 1171[46.1] SEENOTE4 OVERALL _ 1I .- RADIATORJEXHAUST DISCHARGE AIR ? HEIGHT USTOMERACCESS "°`' "'� r 1 r ASSEMBLY,CONTROL "�,�q. " x a PANEL ACCESS, " T` •r BATTERY CHARGER • SLOCATED EE NOTE 41THIN 50 [2.0] 888 [35.0] 47 ' 1857 [73.1]TYP it 58 FUEL LINE CONNECTIO 1000 [39.4] OVERALL WIDTH [1.8] 1950 [76.8] [2.3] 3/4"NPT FEMALE COUPLING LEFT SIDE VIEW REA VIEW TYPOVERALL LENGTH TYPyrt, CO ril LIFTING PROVISIONS RIGHT SIDE VIEW (4 PLACES) ilIT 2 SEE NOTES 5,7 AND _ CENTER OF GRAVITY DIMENSIONS WEIGHT DATA O WEIGHT WEIGHT • ENCLOSURE SHIPPING WEIGHT ENGINEIKW MATERIAL GENSE70NLY SHIPPING SKID KG[LBS] KG[LBS] KG[LBS] C 2.4L 32KW AL 556[1225] 44[98] 600[13231 DIMENSIONS:MM[INCH] � 2 4L 38KW AL 560[1235] 44[98] 605 113331 O . 0 m z N A Re To `„'13.5 X 29.5 00 MOUNTING SLOTS *NOTE-STUB-UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. — 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. N . OO C CD PC) n 1 V) F(D N 786 [30.9] C) D 162 [6.4] m - . STUB-UP AREA m C - ✓ v. . � 9 [.4] .. 12 [.5] D. CD 51 [2.0] 162 [6.4] P. *STUB-UP °_ R AREA REMOVABLE STUB-UP ACCESS COVER ' • (SHIPPED LOOSE WITH GENERATOR) w 1733 [68.2] ID"'D ► 217 [8.5] Co• cr, TO BE INSTALLED DURING GENERATOR - TOP VIEW INSTALLATION iD o N 850 [33.5] j g. o Sc s 116 [4.6] o L25 -0. f*I 838 [33.0]TYP o a��i 50 TYP 1750 [68.9]TYP [1.0] MOUNTING CENTERS m m [2.0] MOUNTING SLOTS TYP co ? 888 [35.0] ► o c f" 1950 [76.8] �• CI)_' * REAR VIEWo o LEFT SIDE VIEW co co cn co o fy co H 1153 Na o 2 o Co to s Protector® OS Series c0 GENERAC® , , O IS Serie SERIE PROTECTOR® QS IL im Protector® QS Generadores de reserva y Motor a gas enfriado por liquido 1 de 9 INCLUYE: Clasificacion de alimentacion de reserva Modelo RG022 (Aluminio- Bisque) -22 kW 60 Hz • Controlador digital multilingue con pantalla LCD de dos Modelo RG027 (Aluminio- Bisque) - 27 kW 60 Hz lineas Evolution'"" (ingles,espanol,fiancés y portugues) con ventana de visualizacion externa para indicar Modelo RG032 (Aluminio- Bisque) -32 kW 60 Hz facilmente el estado del generador y la posicion del Modelo RG038 (Aluminio- Bisque) -38 kW 60 Hz disyuntor. • Tecnologia electrica True Power'" • Regulador electronico isocrono _ __ __-,--- • Gabinete con ruido atenuado • Sistema cerrado de recuperacion de refrigerante _� • Cargador de bateria inteligente _ • Mangueras resistentes al ozono y los rayos ultravioleta —Ei.— • Regulacion de voltaje de ± 1 % _ iii• Funcionamiento con gas natural o propano liquido ®■®ni` • Garantia limitada de 5 arms • En la lista UL 2200 • El generador indicado en la lista SwRi® (NFPA37, T QUIET TEST clausula 4.1.4.1.2)se puede instalar a una distancia c E 1 us iiii) minima de 18 pulg. (457 mm)de una pared cor,-„on,.s„.c., combustible* Cumple con los reglamentos de emisiones de la EPA 22 y 27 kW cumplen con las normas de emisiones de CA/MA *Unicamente si se ubica lejos de puertas,ventanas y entradas de aire 32 y 38 kW no se venden en CA/MA fresco y a menos que los codigos locales indiquen to contrario.Revise la guia de instalacion para obtener mas detalles. CARACTERISTICAS O DISENO INNOVAOOR Y PRUEBAS DE PROTOTIPOS son componentes slave del 0 REGULACION DE VOLTAJE CON FRECUENCIA COMPENSADA DE ESTADO exito de GENERAC a la hora de "MEJORAR LA ALIMENTACION A TRAVES DEL SOLIDI).Este sistema de regulaciOn de vanguardia que aumenta la alimentacibn DISENO". Pero eso no es todo. Un compromiso total con las pruebas de esta incorporado de manera estandar en todos los modelos Generac. Proporciona n componentes,de confiabilidad,ambientales,de vida util y destrucciOn,edemas de una RESPUESTA RAPIDA optimizada ante las condiciones de carga cambiantes y las pruebas de las normas CSA, NEMA,EGSA correspondientes y otras normas,le una CAPACIDAD MAXIMA DE ARRANQUE DEL MOTOR mediante la concordancia de 4. permiten elegir los productos de GENERAC POWER SYSTEMS con la confianza de par de torsion electrOnica de las cargas de sobrevoltaje transitorio hacia el motor. que estos sistemas le proporcionaran un rendimiento superior. RegulaciOn de voltaje digital en±1%. {j. 1 O CRITERIOS DE PRUEBA: 0 RESPUESTA DE SERVICIO DE UNA SOLA FUENTE de la amplia red de ✓PROTOTIPO PROBADO EVALUACION NEMA MG1-22 concesionaros de Generac, quienes proporcionan conocimientos tecnicos de ✓TORSION DEL SISTEMA PROBADA CAPACIDAD DE ARRANQUE servicio y piezas de toda la unidad,desde el motor hasta el componente electrOnico DEL MOTOR mas pequeno. r, j 0 INTERRUPTORES DE TRANSFERENCIA GENERAC. Vida Otil prolongada y :_ confiabilidad son sinOnimos de GENERAC POWER SYSTEMS. Un motivo para este f confianza es que la linea de productos de GENERAC incluye sus propios controles y slstemas de transferencia,to que ofrece una complete compatibilidad del sistema. ln f GENERAC® 'so °afl r w. VD GENERAC' a 22 • 27 • 32 • 38 datos de ingenieria y aplicacion 15 r a ESPECIFICACIONES DEL GENERADOR ESPECIFICACIONES DEL MOTOR:22,27,32 y 38 kW °1 Tipo Sfncrono as P Marca Generac y H(22 y 27 kW)o Modelo En linea Clase de aislamiento del rotor F(32 y 38 kW) Cilindros 4 Clase de aislamiento del estator H Desplazamiento(litros) 2,4 2 de 9 Factor de interferencia teletdnica(FIT) <50 Diametro interior(pulg./mm) 3,41/86,5 Conductores de salida del alternador monofasicos 4 hilos Carrera(pulg./mm) 3,94/100 Conductores de salida del alternador trifasicos 6 Silos Proporci6n de compresidn 9,5:1 Cojinetes Bola sellada Con aspiracide natural(22 y 27 kW) Acoplamiento Disco flexible o Sistema de entrada de aire con turbocompresor/posenfriador Sistema de excitacide Directo (32 y 38 kW) REGULACION DE VOLTAJE Tipo de elevador Hidraulico Tipo Electrdnica Deteccidn Monofasico SISTEMA DE LUBRICACION DEL MOTOR Tip de bomba de aceite Engranajes Regulaci6n ±1% Cartucho enroscable de flujo Tipo de filtro de aceite ESPECIFICACIONES DEL REGULADOR completo Capacidad del carter(qVL) 4/3,8(22,27,32 y 38 kW) Tipo Electrdnica SISTEMA DE ENFRIAMIENTO DEL MOTOR Regulaci6n de frecuencia Isbcrona Tipo Cerrado Regulaci6n de estado estable ±0,25% Bomba de aqua Accionada por correa SISTEMA ELECTRICO Velocidad del ventilador(rpm) 1980-22 y 27 kW 1500-32y38kW Alternador de carga de baterfa 12 voltios 30 amperios Diametro del ventilador(pulg./mm) 18,1/459,7(22 y 27 kW)o Cargador de bateria estatico 2,5 amperios 22/558,8(32 y 38 kW) Bateria recomendada(no incluida) Grupo 26(22,27,32 y 38 kW) Propulsor(22 y 27 kW)o Modo de ventilador extractor(32 y 38 kW) Voltaje del sistema 12 voltios CARACTERISTICAS DEL GENERADOR SISTEMA DE COMBUSTIBLE Tipo de combustible Gas natural,vapor de propano Generador de campo giratorio para servicio pesado Se conecta directamente al motor Carburador Tiro hacia abajo Aumento de temperatura de funcionamiento de 216°F(120°C)sobre una temperatura Regulador de combustible secundario Estandar ambiente de 104°F(40°C) Aislamiento clase H con clasificaciOn NEMA Solenoide de cierre de combustible Estandar Aislamiento clase F con clasificaciOn NEMA 5 a 14 pulg.de columna de aqua/ Todos los modelos desarrollados a partir de prototipos completamente probados Preside de funcionamiento del combustible 9 a 26 mm HG CARACTERISTICAS DEL GABINETE Preside de combustible de PL 11 a 14 pulg.de columna de agua/ Garantiza protecci6n contra las inclemencias del tiempo. 21 a 26 mm HG Gabinete de protecci6n contra Pintura epoxi texturada aplicada de manera electrostatics 5 a 14 pulg.de columna de agua/ la intemperie de aluminio para una mayor durabilidad. Preside de combustible de GN 9 a 26 mm HG Silenciador de grado critico El silenciador de grado critico y silencioso esta montado al contenido interior de la unidad para evitar lesiones. Pequena,compacts y Contribuye a una instalacidn facil y atractiva. atractiva SAE Gabinete con ruido atenuado que garantiza un funcionamiento silencioso. (Todas las clasificaciones estan de acuerdo con las normal BS5514,IS03046,IS08528,SAE J1349 y DIN6271) :,- ''w:iazeS.Ya.A iFalkku..M€kWN M FHdA...a HtiEbfteAfh+tk .f A sftf,..:.. f GENERAC N 22 • 27 • 32 • 38 datos de funcionamiento s VOLTAJE DE SALIDA DEL GENERADOR/kW-60 Hz n a) kW gas PL Amperios gas PL kW gas nat. Amperios gas nat. Taman()del disyuntor Si (ambos) 120/240 V,1 0,1,0 pf 22 92 22 92 100 RG022 120/208 V,3 0,0,8 pf 22 76 22 76 80 3 de 9 120/240 V,3 0,0,8 pf 22 66 22 66 80 120/240 V,1 0,1,0 pf 27 113 25 104 125 RG027 120/208 V,3 0,0,8 pf 27 94 25 87 100 120/240 V,3 0,0,8 pf 27 81 25 75 90 120/240 V,1 0,1,0 pf 32 133 32 133 150 120/208 V,3 0,0,8 pf 32 111 32 111 125 RG032 120/240 V,3 0,0,8 pf 32 96 32 96 100 277/480 V,3 0,0,8 pf 32 48 32 48 60 120/240 V,1 0,1,0 pf 38 158 38 158 175 120/208 V,3 0,0,8 pf 38 132 38 132 150 RG038 120/240 V,3 0,0,8 pf 38 114 38 114 125 277/480 V,3 0,0,8 pf 38 57 38 57 60 CAPACIDAD DE SOBREVOLTAJE TRANSITORIO EN CONSUMO DE COMBUSTIBLE DEL MOTOR AMPERIOS Gas natural Propane Caida de voltaje a<0,4 pf (pie3/h) (m3/h) (gal/h) (pie3/h) (Uh) 15% 30% Ciclo de ejercitacien 42 1,2 0,44 16 1,7 ,'' 120/240 V,1 0 55 135 25%de la carga nominal 100 2,8 1,1 40 4,2 RG022 120/208 V,3 0 40 92 RG022 50%de la carga nominal 190 5,4 2,1 75 7,8 120/240 V,3 0 35 80 75%de la carga nominal 255 7,2 2,8 101 10,5 120/240 V,1 0 62 170 100%de la carga nominal 316 9 3,4 125 13 RG027 120/208 V,3 0 70 120 Ciclo de ejercitaci6n 42 1,2 0,44 16 1,7 120/240 V,3 0 61 103 25%de la carga nominal 108 3,1 1,2 43 4,5 120/240 V,1 0 75 180 RG027 50%de la carga nominal 197 5,6 2,1 78 8,1 t 120/208 V,3 0 87 210 75%de la carga nominal 287 8,2 3,1 114 11,8 RG032 120/240 V,3 0 75 182 100%de la carga nominal 359 10,2 3,9 143 14,8 C 277/480 V,3 0 36 87 Ciclo de ejercitaci6n 79 2,2 0,8 30 3,2 120/240 V,1 0 75 180 25%de la carga nominal 144 4,1 1,7 60 6,3 120/208 V,3 0 87 210 RG032 50%de la carga nominal 226 6,4 2,7 97 10,3 RG038 120/240 V,3 0 75 182 75%de la carga nominal 298 6,4 3,7 132 13,9 277/480 V,3 0 36 87 100%de la carga nominal 375 10,6 4,6 166 17,5 Ciclo de ejercitaciOn 83 2,3 0,9 31 3,2 Nota:La tuberia de combustible debe estar dimensionada para carga plena. 25%de la carga nominal 162 4,6 1,7 62 6,6 Pam el contenido de BTU,multiplique pie3/h x 2520(PL)o pie3/h x 1000(GN). RG038 50%de la carga nominal 255 7,2 2,9 103 10,8 Para el contenido de megajulios,multiplique m3/h x 93,15(PL)o m3/h x 37,26(GN). 75%de la carga nominal 345 9,8 4 142 15 Consulte la"Hojas de dabs de emisiones"para conocer el flujo de combustible 100%de la carga nominal 437 12,4 5,2 185 19 maximo para fines de permisos de EPA y SCAOMD. CLASIFICACION DE RESERVA:Las clasificaciones de reserva aplican a instalaciones alimentadas por una Puente confiable del servicio publico.La clasificaci6n de reserva se aplica a distintas cargas por la duraci6n de un corte de alimentaciOn.No hay capacidades de sobrecarga para esta clasificaciOn.Las clasificaciones son conforme a la ISO-3046-1.El diseflo y las especificaciones est5n sujetos a cambios sin previo aviso. y GENERAC' Cr 22 • 27 • 32 • 38 datos de funcionamiento 03 ENFRIAMIENTO DEL MOTOR 22 kW 27 kW 32 y 38 kW y Flujo de aire(entrada de aire que incluye alternador y aire de combustirin en pie3/min/m3/min) 2400/68 2400/68 2200/62,3 Capacidad de refrigerante del sistema(gal/litros) 2,5/9,5 2,5/9,5 2,5/9,5 Disipacidn del calor al refrigerante(BTU por hora/MJ por hora) 99.000/104,5 105.000/110,8 145.000/153 4 de 9 Temperatura maxima del aire de funcionamiento en el radiador(°F/°C) 150/60 Temperatura ambiente maxima(°F/°C) 140/50 REQUISITOS DE COMBUSTION Flujo a la potencia nominal(pie3/min/m3/min) 68/1,9 68/1,9 106/3 EMISIONES ACUSTICAS Salida de ruido en dB(A)a 23 pies(7 m)con el generador en modo de ejercitaciOn* 61 61 58 Salida de ruido en dB(A)a 23 pies(7 m)con el generador funcionando con carga normal" 70 70 64 ESCAPE Flujo de escape en la salida nominal(pie3/min/m3/min) 165/4,7 180/5,1 300/8,5 Temperatura del escape en la salida del silenciador(°F/°C) 900/482 1000/538 1075/579 PARAMETROS DEL MOTOR Rpm sincronas nominales 1800 • AJUSTE DE ENERGIA PARA CONDICIONES AMBIENTALES ReducciOn de potencia por temperatura 1,65%por cada 10°F sobre 77°F o 3%por cada 10°C sobre 25°C ReducciOn de potencia por altura(22 y 27 kW) 3%por cada 1000 pies sobre 600 pies o 1 %por cada 100 m sobre 183 m ReducciOn de potencia por altura(32 y 38 kW) 3%por cada 1000 pies sobre 3000 pies o 1 %por cada 100 m sobre 915 m CARACTERISTICAS DEL CONTROLADOR Pantalla LCD de texto piano y dos Ifneas Interfaz de usuario simple para una operaci6n facil. Interruptor de modo: Auto(Automatico) Arranque automatico en falla de energia electrica.Ejercitador de 7 Was Off(Apagado) La unidad se detiene.Se elimina la alimentaci6n.El control y cargador siguen en funcionamiento. Manual Arranque con control de arrancador,la unidad permanece encendida. Si hay una falla de energia electrica,se produce la transferencia a carga. Retardo de arranque programable entre 10 y 30 segundos 10 s estandar Secuencia de arranque del motor Arranque cfclico:16 s encendido,7 en descanso(duraciOn maxima de 90 s) Calentamiento del motor 5 s Enfriamiento del motor 1 min Bloqueo del arrancador El arrancador no se puede volver a arrancar hasta 5 s despues de que el motor se haya detenido. Cargador de baterfa inteligente Estandar RegulaciOn de voltaje automatica con protecciOn de subvoltaje y sobrevoltaje Estandar Desconexi6n automatica por baja presiOn del aceite Estandar Desconexi6n por exceso de velocidad Estandar,72 Hz Desconexi6n por temperatura alta Estandar Protecci6n de falla de arranque Estandar Seguridad protegida con fusibles Estandar Protecci6n de falla de transferencia Estandar ProtecciOn de baterfa baja Estandar Registro de funcionamiento de 50 eventos Estandar Ejercitador con capacidad de ajuste en el futuro Estandar ProtecciOn de cableado incorrecto Estandar Protecci6n de falla interna Estandar , Capacidad de falla externa comun Estandar ProtecciOn de falla del regulador Estandar GENERAC® 22 • 27 • 32 • 38 accesorios disponibles L 0 N.° de modelo Producto Descripcion a, CO Mobile Link de Generac le permite revisar el estado de su generador desde cualquier Accesorio para celular Mobile lugar con acceso a conexiOn de Internet desde una computadora o con un G0071690 Link®4G LTE dispositivo mOvil.Incluso,se le notificara cuando haya un cambio en el estado del generador por correo electrOnico o mensaje de texto.Nota:Se requiere un kit de 5 de 9 adaptador de mazo de cables. Disponible solo en EE.UU. Kit,adaptador Mobile Link UC El kit adaptador de mazo de cables es necesario para hacer que las unidades G006478 0 (necesario para las series QT y enfriadas por liquido sean compatibles con Mobile Link®. RG) G005630 1 22,27,32 y Si la temperatura normalmente disminuye a menos de 32°F(0°C),instale un kit para 38 kW Kit para climas fries climas frios para mantener una temperatura Optima de la bateria.El kit consta de un calentador de bateria con un termostato integrado en la envoltura. G005616-0-22,27,32 y Kit para climas extremadamente Recomendado en lugares donde la temperatura normalmente disminuye a menos de 38 kW frios 32°F(0°C)por periodos prolongados.Solo para unidades enfriadas por liquido. G005651-0 Kit de tapones de base Agregue tapones de base en la base para impedir que entren residues al generador. Si el gabinete del generador se raya o dana,es importante retocar la pintura para G005703-0-Bisque Kit de pintura protegerlo contra la corrosion futura.El kit de pintura incluye la pintura necesaria para mantener o retocar adecuadamente el gabinete de un generador. G005656 0 22 y 27 kW Kit de mantenimiento prLos kits de mantenimiento programado para generadores enfriados por liquido G005984-0 32 y 38 kW Kit de made ofrecen todas las piezas metalicas necesarias para realizar un completo mantenimiento en los generadores enfriados por liquido de Generac. El monitor inalambrico de Generac,completamente inalambrico y alimentado por G006664-0 Monitor inalambrico local bateria,le proporciona informaci6n instantanea del estado sin necesidad de salir de casa. G006665 0 Maze de cables de extensi6n del Recomendado para use con el control remote inalambrico en unidades de hasta control remoto inalambrico 60 kW,obligatorio para unidades de 70 kW o mas. Los mOdulos de administraci6n inteligente se usan en conjunto con el interruptor de G006873-0 MOdulo de administraci6n transferencia automatica para aumentar las capacidades de administraciOn de inteligente(50 amperios) alimentaciOn.Proporciona flexibilidad de administraci6n de alimentaciOn adicional que no se encuentra en ningun otro sistema de administraci6n de alimentaciOn. Interruptor basculante de parada G007993 0 de emergencia para La parada de emergencia permite apagar el generador y cortar el suministro de instalaciones residenciales combustible inmediatamente en caso de una emergencia. conforme a NEC2017 Interruptor con restablecimiento G006510 0 de parada de emergencia para La parada de emergencia permite apagar el generador y cortar el suministro de instalaciones comerciales combustible inmediatamente en case de una emergencia. conforme a NEC2020 El monitor Wi-Fi de nivel de combustible PL proporciona un monitoreo constante del tanque de combustible PL conectado. El monitoreo del nivel de combustible del G007005 0 Monitor Wi-Fi de nivel de tanque de PL es un paso importante para asegurarse de que el generador este listo combustible PL para funcionar durante una interrupciOn de alimentaciOn inesperada.Se dispone de alertas de estado por medio de una aplicaciOn gratuita,para proporcionar una notificaci6n cuando el tanque de PL requiere relleno. CL Serie Protector® CIS um -n N 0 N o N co SERVICE ITEM 2.4L NOTES: IV OIL FILL CAP EITHER SIDE RADIATOR/EXHAUST OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1092(43")WIDE X 1885(74.2")LONG. C7 DISCHARGE AIR AIR INTAKE OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. (BOTH SIDES) (BOTH SIDES) OIL DRAIN HOSE LEFT SIDE 2.ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE -- BATTERY 12 — RADIATOR DRAIN LEFT SIDE AND SERVICING.THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT GRP 26V COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, CDRADIATOR FILL CAP ROOF TOR STATE,AND LOCAL CODES. NEGATIVE GROUND 3.CONTROL PANEL I CIRCUIT BREAKER INFORMATION: IV PM'.077483 AIR CLEANER ELEMENT LEFT SIDE -SEE SPECIFICATION SHEET OR OWNERS MANUAL REMOVE COVE- SPARK PLUGS LEFT SIDE -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. FOR ACCESS TO t' -- MUFFLER SEE NOTE 11 4 REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS RADIATOR FILL CAP t DRIVE BELT EITHER SIDE THE STUB-UP AREAS AS FOLLOWS FAN BELT SEE NOTE 11 -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION L _ BATTERY LEFT SIDE NEUTRAL CONNECTION,BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. HI REFERENCE OWNERS MANUAL -LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. y FOR PERIODIC REPLACEMENT 5 CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 427 PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND [16 8] `'-- .' RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. A JOM 111F- 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 8.MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 (USE STANDARD SAE TORQUE SPECS) —.-1141 9.MUST ALLOW FREE FLOW OF INTAKE AIR DISCHARGE AIR AND EXHAUST.SEE SPEC [5.6] 629.9[24.8] —1.1 SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. CENTER OF GRAVITY 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE (SEE NOTE 5) AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. TOP VIEW 11.EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE, REMOVE FRONT PANEL TO ACCESS. EXHAUST MUFFLE- ENCLOSED WITHIN CIRCUIT BREAKE- GENERATOR ENCLOSURE SEE NOTE 3 631 [24.8] .� _ -y DOOR TYP ■ 4 i SI i` r 1 ;or a. REAR ENCLOSURE T a fix, I rc " - 980 COVER PANEL , „, E y °"1 SEE NOTE 4 '' RADIATORIEXHAUST IHA `'.^ g I a„f, [38.6] ,®.,"' VICE ACTION LATCH, r DISCHARGE AIR >N - 1°°: OVERALL : ONE PER DOOR, . jk, s HEIGHT USTOMER ACCESS 48 m`; Ti, ONE LIFT OFF S • 1 ASSEMBLY CONTROL (1 y V_ DOOR PER SIDE z ]s a �. I,� 51, Y PANEL ACCESS, TYP]� 9 .F OF GENERATOR BATTERY CHARGER LOCATED WITHIN T'• A' 1040 SEE NOTE 4 48 [40.9] 776 [30.6] 45—N. 1490 [58.7]TYP q OVERALL WIDTH [1.91 FUEL LINE CONNECTION [7.8] 1580[62.2] 3/4"NPT FEMALE COUPLING REAR VIEW TYP OVERALL LENGTH s t LEFT SIDE VIEW WEIGHT DATA RIGHT SIDE VIEW Q_. E ENGINE/KW ENCLOSURE WEIGHT WEIGHT SHIPPING WEIGHT /� KVA MATERIAL GENSET ONLY SHIPPING SKID KG[LBS] C I• i KG[LBS] KG[LBS] /TD I2AL 22KW(60HZ) •Y E SINGLE PHASE 174KVA(50HZ) AL 4105[905] 30[66] 440[971] .T THREE PHASE 221(VA(50HZ) O Y:g 24L 27KW(60HZ) SINGLE PHASE 21.6KVA(50H2) AL 426(940] 30[66] 456[1006] DIMENSIONS:MM[INCH] C. m THREE PHASE 27KVA(50HZ) ... CD ; Z m CO XI DO D r % r N N 1< IV 13.5 X 29.5 y MOUNTING SLOTS 'NOTE-STUB-LIP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. S� lf.Qti, . ?0•;.}.{r;.S':•aJ:F 674 `••'.d;{:5.+.+'.L}; [26.5] STUB-UP . ; .•yy, AREA ----I. 9 51 .. 28[1.1] 100 [.4] [2.0] [3.9] 'STUB-UP AREA 1370[54.0] ► 210[8.3] EMOVABLE STUB-UP COVER TOP VIEW 735 [28.9]PIIIIIIIIMAIII=11111101 'ALA 96 [3.8] 27 [1.0] 0- k. 723 [28.5]TYP ►{ 45 [1.8]TYP- -- I� 1380[54.3]TYP i TYP MOUNTING SLOT CENTERS MOUNTING SLOT CENTERS 776 [30.6] • 1580[62.2] REAR VIEW LEFT SIDE VIEW Q y• CD=t 0 Q' O o � m DIMENSIONS:MM[INCH] CD0 O • co =co Ce) m N C 33 N n Cap O. v = v CL Serie Protector® OS so Serie Protector® QS 4n w 57.0 N "c o w Co co SERVICE ITEM 2.4L IV RADIATOR/EXHAUST OIL FILL CAP ETHER SIDE NOTES: 00 DISCHARGE AIR AIR INTAKE OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1194(47")WIDE X 2255(88.8")LONG. 60 (BOTH SIDES) (BOTH SIDES OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. A OIL DRAIN HOSE RIGHT SIDE 2.ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE RADIATOR DRAM HOSE LEFT SIDE AND SERVICING.THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT cz- COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, CD "4-768 [30.2] RADIATOR FILL CAP ACCESS ROOF TOP STATE,AND LOCAL CODES. — CENTER OF GRAVITY AIR CLEANER ELEMENT RIGHT SIDE 3.CONTROL PANEL/CIRCUIT BREAKER INFORMATION: 167 SEE NOTE 5 SPARK PLUGS LEFT SIDE -SEE SPECIFICATION SHEET OR OWNERS MANUAL [6 6] MUFFLER SEE NOTE 11 -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. I 1 DRIVE BELT EITHER SIDE 4.REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS ffi 4 �Ong za !�,; i' FAN BELT SEE NOTE 11 THE STUB-UP AREAS AS FOLLOWS: 4 =' BATTERY LEFT SIDE -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,NEUTRAL 535 CONNECTION,AND BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. [21.1] REFERENCE OWNERS MANUAL LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. a FOR PERIODIC REPLACEMENT 5.CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. ' PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND ii, RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. • 8.MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 2.5"O.D.EXHAUST 4. (USE STANDARD SAE TORQUE SPECS) OUTLET 9.MUST ALLOW FREE FLOW OF INTAKE AIR,DISCHARGE AIR AND EXHAUST.SEE SPEC SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. / 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE REMOVE COVER/ TOP VIEW 1ATTERY 12V,GRP 26 AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. FOR ACCESS TO NEGATIVE GROUND 11.EXHAUST MUFFLER AND FAN BELT ARE ENCLOSED WITHIN GENERATOR ENCLOSURE, RADIATOR FILL CAP P/N:077483 REMOVE FRONT PANEL TO ACCESS. VICE ACTION LATCH, HAUST MUFFLER ONE PER DOOR, ENCLOSED WITHIN CIRCUIT BREAKE 759 [29.9]----► ONE LIFT OFF GENERATOR ENCLOSURE SEE NOTE 3 DOOR TYP DOOR PER SIDE OF GENERATOR v r - REAR ENCLOSURE Viz ` . 3 COVER PANEL C I t rsn 'I _;�'' 1171[46.1] SEENOTE4 LL . Fp RADIATOR/EXHAUST s - "`'` ! OVERALL ' : HEIGHT i �� DISCHARGE AIR USTOMER ACCESS ... . 44. ASSEMBLY,CONTROL _ t PANEL ACCESS, • { BATTERY CHARGER -, � LOCATED WITHIN • SEE NOTE 4 A • 50 [2.0] Imo--888 [35.0]—NJ 47 _ 1857 [73.1]TYP CD FUEL LINE CONNECTIO 1000 [39.4] OVERALL WIDTH T[11. ] 1950 [76.8] [2.3] =t 03/4"NPT FEMALE COUPLING LEFT SIDE VIEW REAR VIEW OVERALL LENGTH TYP 0 LIFTING PROVISIONS RIGHT SIDE VIEW (4 PLACES) CD 1 1 2 SEE NOTES 5,7 AND CENTER OF GRAVITY DIMENSIONS M WEIGHT DATA WEIGHT WEIGHT SHIPPING WEIGHT ENGINEMW ENCLOSURE MATERIw GENSET ONLY SHIPPING SKID cm Ti KG[LBS] KG[LBS] KG BS] 2.41 32KW AL 556[1225] 44[98] 600[1323] DIMENSIONS:MM(INCH] CM 2.4L 38KW AL 560[1235] 44[981 605]1333] C, 1 0 m c..., 2 N m 33 w n 13.5X29.5 O0 () MOUNTING SLOTS *NOTE-STUB-UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. Pr 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. N O co n m '`. ,;- 786 co ,e. [30.9] co 3 N o . 162 [6.4] m 0 o d III 'STUB UP ° n AREA 41 o• * aCCO CD o c.n 12[.5] ► 9 ['4] 51 [2.0] y 162 [6.4] ► ,(79 *STUB-UP Q cci AREA REMOVABLE STUB-UP ACCESS COVER 1733 [68.2] ► 4 - 217 [8.5] (SHIPPED LOOSE WITH GENERATOR) TO BE INSTALLED DURING GENERATOR o A m TOP VIEW INSTALLATION y r 850 [33.5] N., co co co m = 116 [4.6] o c 25 - f'u 838 [33.0]TYP y c 50 TYP L.. 1750 [68.9]TYP - [1.0] MOUNTING CENTERSCP S'' [2.0] MOUNTING SLOTS TYP Co co 2 888 [35.0] CD -= '� 1 • 0 O CD °' 1950 [76.8] = CD i wpm • ' * REAR VIEW o or0C-71 = g 3• i LEFT SIDE VIEW CD CO00y m 3-. coo rn co) a rn CD W 000 N D N< 6 n o o: co Serie Protector® OS r c„„ GENERAC, 03 • y Protector® PROTECTOR® SERIE QS Serge QS Generatrices de secours Moteur a gaz refroidi par liquide �/9 COMPREND : Puissance nominale de secours • Controleur numerique multilingue Evolution' a Modele RG022 (aluminium - bisque) - 22 kW 60 Hz affichage a cristaux liquides de deux lignes (anglais/ Modele RG027 (aluminium - bisque) - 27 kW 60 Hz espagnol/franpais/portugais)avec fenetre externe pour Modele RG032 (aluminium - bisque) -32 kW 60 Hz observer facilement I'etat de la generatrice et la position Modele RG038 (aluminium - bisque) -38 kW 60 Hz des disjoncteurs. • Technologie electrique True Power'" • Regulateur de vitesse electronique isochrone • Enceinte a attenuation sonore • Recuperation de liquide de refroidissement en circuit ferme • Chargeur de batterie intelligent • Flexibles resistant aux UV et a('ozone • Regulation de tension a ±1 %pies imm■niamm.m • Fonctionne au gaz nature)ou au GPL • Garantie limitee 5 ans • Homologue UL 2200 • Homologue SwRi® (NFPA37, clause 4.1.4.1.2) c ETI/ us or) QUIET TEST La generatrice peut etre installee a une distance de 18 po (457 mm) minimum d'une paroi combustible* Conforme aux reglementations sur les emissions de l'EPA Modeles 22 et 27 kW conformes aux normes d'emissions du CA/MA *Uniquement si place a I'ecart des pones,des fenetres et des prises d'air ModeleS 32 et 38 kW non vendus au CA/MA frais et sauf prescriptions contraires de la reglementation en vigueur.Pour plus de details,consulter le guide d'installation. CARACTERISTIQUES O CONCEPTION INNOVANTE ET ESSAIS SUR PROTOTYPES sont des elements 0 REGULATION MICROELECTRONIQUE DE TENSION A FREQUENCE essentiels de I'approche de GENERAC a «AMELIORER L'ALIMENTATION COMPENSEE.Ce systeme de regulation de pointe a maximisation de la puissance ELECTRIQUE A DESSEIN». Mais ga ne s'arrete pas la. Notre approche exhaustive equipe de serie tous les modeles Generac. II fournit une REPONSE RAPIDE des essais de composants, essais de fiabilite, essais environnementaux, essais optimisee en fonction des variations des conditions de charge et une CAPACITE destructifs et de duree,en plus des essais plexus par CSA,NEMA,EGSA et d'autres MAXIMALE DE DEMARRAGE DU MOTEUR par asservissement electronique du normes,vous permet d'opter pour GENERAC POWER SYSTEMS avec('assurance de couple aux pointes de charge sur le moteur.Regulation numerique de la tension a resultats superieurs. ±1 %pres. O CRITERES D'ESSAI: 0 SERVICE APRES-VENTE A SOURCE UNIQUE par le reseau etendu de ✓ESSAIS DE PROTOTYPES v EVALUATION NEMA MG1-22 concessionnaires Generac, qui disposent des pieces et du savoir-faire pour ESSAIS DE TORSION DU SYSTEME CAPACITE DE DEMARRAGE l'entretien et les reparations de('ensemble de la machine,du moteur jusqu'aux plus DU MOTEUR petits composants electroniques. 0 COMMUTATEURS DE TRANSFERT GENERAC. Durabilite et fiabilite sont synonymes de GENERAC POWER SYSTEMS.Lune des raisons de cette assurance est que la gamme de produits GENERAC est proposee avec ses propres dispositif et commandes de transtert,pour une compatibilite totale avec le systeme. GENERAC® !so 0GENERAC® GENERAC® y 22 • 27 • 32 • 38 donnees techniques et d'utilisation CARACTERISTIQUES DE LA GENERATRICE CARACTERISTIQUES DU MOTEUR:22,27,32 et 38 kW a; Type Synchrone c yp Marque Generac H(22 et 27 kW)ou Classe d'isolation du rotor Module En ligne F(32 et 38 kW) Cylindres 4 Classe d'isolation du stator H Cylindree(litres) 2,4 2/9 Facteur de perturbation telephonique(TIF) <50 Alesage(po/mm) 3,41/86,5 Conducteurs de sortie d'alternateur,monophase 4 conducteurs Course(po/mm) 3,94/100 Conducteurs de sortie d'alternateur,triphase 6 conducteurs Taux de compression 9,5:1 Roulements Etanches a billes Aspiration naturelle(22 et 27 kW) Accouplement Disque flexible ou Systeme d'admission d'air Turbo-com pression/post-ref ro id issement Systeme d'excitation Direct (32 et 38 kW) REGULATION DE TENSION Type de cames Hydrauliques Type Electronique Detection Monophase SYSTEME DE GRAISSAGE DU MOTEUR Type de pompe a huile Engrenages Regulation ±1% Type de filtre a huile Cartouche vissee a debit integral CARACTERISTIQUES DU REGULATEUR DE VITESSE Capacite d'huile du carter(pte/L) 4/3,8(22,27,32 et 38 kW) Type Electronique SYSTEME DE REFROIDISSEMENT DU MOTEUR Regulation de frequence Isochrone Type Ferme Regulation du regime permanent ±0,25% Pompe a eau Entraine par courroie SYSTEME ELECTRIQUE Vitesse du ventilateur(tr/min) 1980-22 et 27 kW 1500-32 et 38 kW Alternateur de charge de batterie 12 V 30 A 18,1/459,7(22 et 27 kW)ou Chargeur de batterie statique 2,5 A Diametre du ventilateur(po/mm) 22/558,8(32 et 38 kW) Batterie recommandee(batterie non fournie) Groupe 26(22,27,32 et 38 kW) Souftlant(22 et 27 kW)ou Mode de ventilateur Aspirant(32 et 38 kW) Tension du systeme 12 V CARACTERISTIQUES DE LA GENERATRICE CIRCUIT DE CARBURANT Type de carburant Gaz naturel,vapeur de propane Generatrice service intensif a champ tournant Accouplement direct au moteur Carburateur Inverse Montee de la temperature d'exploitation de 216°F(120°C)au-dessus dune ambiante de Vapo-detendeur secondaire De serie 104°F(40°C) Isolation de classe H conforme a NEMA Electrovanne de coupure de carburant De serie Isolation de classe F conforme a NEMA Pression de service du carburant 5 a 14 poH20/9 a 26 mmHg Taus les modeles soot entierement testes sur prototypes Pression de carburant GPL 11 a 14 poH20 CARACTERISTIQUES DE L'ENCEINTE Pression de carburant GN 5 a 14 poH20 Enceinte en aluminium a Assure la protection contre les elements. I'epreuve des intemperies Peinture epoxy texturee appliquee par poudrage electrostatique pour plus de durabilite. Silencieux interne de type Le silencieux tres peu bruyant de type critique est monte a critique l'interieur de l'enceinte pour Niter les blessures. Petit,compact,attrayant Permet une installation facile et visuellement attrayante. SAE L'enceinte a attenuation sonore assure un fonctionnement peu bruyant. (routes les caracteristiques nominales contormement a BS5514,IS03046,IS08528,SAE J1349 et D1N6271) . GENERAC`° 22 • 27 • 32 • 38 donnees d'exploitation ,y TENSION/PUISSANCE DE SORTIE DE LA GENERATRICE-60 Hz U . N O kW GPL A GPL kW Gaz nat. A Gaz nat. Dinjoncteur(A) (les deux) 120/240 V,mono,I.puiss.1,0 22 92 22 92 100 RG022 120/208 V,tri,f.puiss.0,8 22 76 22 76 80 3/9 120/240 V,tri,f.puiss.0,8 22 66 22 66 80 120/240 V,mono,f.puiss.1,0 27 113 25 104 125 RG027 120/208 V,tri,f.puiss.0,8 27 94 25 87 100 120/240 V,tri,t.puiss.0,8 27 81 25 75 90 120/240 V,mono,f.puiss.1,0 32 133 32 133 150 120/208 V,tri,I.puiss.0,8 32 111 32 111 125 RG032 120/240 V,tri,f.puiss.0,8 32 96 32 96 100 277/480 V,tri,f.puiss.0,8 32 48 32 48 60 120/240 V,mono,t.puiss.1,0 38 158 38 158 175 j RG038 120/208 V,tri,f.puiss.0,8 38 132 38 132 150 120/240 V,tri,f.puiss.0,8 38 114 38 114 125 277/480 V,tri,f.puiss.0,8 38 57 38 57 60 CAPACITE DE SURINTENSITE CONSOMMATION DE CARBURANT DU MOTEUR Creux de tension<0,4 I.puiss. Gaz nature) Propane 15% 30% (pi3/h) (m3/h) (gal/h) (pi3/h) (I/h) 120/240 V,mono 55 135 Exercice d'entretien 42 1,2 0,44 16 1,7 RG022 120/208 V,tri 40 92 25%de la charge nominate 100 2,8 1,1 40 4,2 120/240 V,tri 35 80 RG022 50%de la charge nominate 190 5,4 2,1 75 7,8 120/240 V,mono 62 170 75%de la charge nominate 255 7,2 2,8 101 10,5 RG027 120/208 V,tri 70 120 100%de to charge nominate 316 9 3,4 125 13 120/240 V,tri 61 103 Exercice d'entretien 42 1,2 0,44 16 1,7 120/240 V,mono 75 180 25%de la charge nominate 108 3,1 1,2 43 4,5 120/208 V,tri 87 210 RG027 50%de la charge nominate 197 5,6 2,1 78 8,1 RG032 120/240 V,tri 75 182 75%de la charge nominate 287 8,2 3,1 114 11,8 277/480 V,tri 36 87 100%de la charge nominate 359 10,2 3,9 143 14,8 120/240 V,mono 75 180 Exercice d'entretien 79 2,2 0,8 30 3,2 120/208 V,tri 87 210 25%de la charge nominate 144 4,1 1,7 60 6,3 RG038 120/240 V,tri 75 182 RG032 50%de to charge nominate 226 6,4 2,7 97 10,3 277/480 V,tri 36 87 75%de la charge nominate 298 6,4 3,7 132 13,9 100%de la charge nominate 375 10,6 4,6 166 17,5 Remarque:La conduite de carburant dolt titre de section Exercice d'entretien 83 2,3 0,9 31 3,2 suftisante pour la pleine charge. 25%de la charge nominate 162 4,6 1,7 62 6,6 Pouvoir calorifique en BTU,multiplier pi3/h x 2520(GPL)ou pi3/h x 1000(GN) RG038 50%de la charge nominate 255 7,2 2,9 103 10,8 Pouvoir calorifique en MJ,multiplier m3/h x 93,15(GPL)ou m3/h x 37,26(GN) 75%de la charge nominate 345 9,8 4 142 15 Voir le debit maximal de carburant dans les«Fiches de donnees d'emissions»pour 100%de la charge nominate 437 12,4 5,2 185 19 les besoins des permis EPA et SCAQMD. , PUISSANCE NOMINALE DE SECOURS:Les puissances nominates de secours s'appliquent aux installations desservies par un reseau electrique fiable.La puissance nominale de secours pent etre appliquee a diverses charges pendant la duree dune coupure de courant.II n'y a pas de capacite de surcharge pour cette puissance nominate.Les caracteristiques nominates soot en conformite avec IS0-3046-1.La conception et les caracteristiques sont sujettes a modification sans preavis. GENERAC° ,y 22 • 27 • 32 • 38 donnees d'exploitation REFROIDISSEMENT DU MOTEUR cu 22kW 27kW 32et38kW d Debit d'air(admission dont air d'alternateur et de combustion,pi3/min et m3/min) 2400/68 2400/68 2200/62,3 Capacite du circuit de refroidissement(gal/L) 2,5/9,5 2,5/9,5 2,5/9,5 Rejet de chaleur dans liquide de refroidissement(BTU/h/MJ/h) 99 000/104,5 105 000/110,8 145 000/153 4 9 Temperature maximale d'exploitation de fair maximum sur le radiateur(°F/°C) 150/60 Temperature ambiante maximale(°F/°C) 140/50 EXIGENCES DE COMBUSTION Debit a la puissance nominate(pi3/min et m3/min) 68/1,9 68/1,9 106/3 EMISSIONS SONORES Niveau sonore en dB(A)a 23 pi(7 m)en mode d'exercice d'entretien` 61 61 58 Niveau sonore en dB(A)a 23 pi(7 m)en mode de fonctionnement a charge normale* 70 70 64 ECHAPPEMENT Debit d'echappement a la puissance nominate(pi3/min et m3/min) 165/4,7 180/5,1 300/8,5 Temperature d'echappement a la sortie du silencieux(°F/°C) 900/482 1000/538 1075/579 PARAMETRES DU MOTEUR Regime synchrone nominal(tr/min) 1800 AJUSTEMENT DE PUISSANCE EN FONCTION DES CONDITIONS AMBIANTES Reduction de charge en temperature 1,65%tous les 10°F au-dessus de 77°F ou 3%tous les 10°C au-dessus de 25°C Reduction de charge en altitude(22 et 27 kW) 3%tous les 1000 pi au-dessus de 600 pi ou 1 %tous les 100 m au-dessus de 183 m Reduction de charge en altitude(32 et 38 kW) 3%tous les 1000 pi au-dessus de 3000 pi ou 1 %tous les 100 m au-dessus de 915 m CARACTERISTIQUES DU CONTROLEUR Afficheur a cristaux liquifies a deux lignes de texte Interface utilisateur simple d'emploi. Commutateur de mode:Auto Demarrage automatique en cas de panne du reseau electrique.Exercice d'entretien 7 jours Off(Desactive) Met la generatrice a l'arret.Le courant est coupe.La commande et le chargeur continuent de fonctionner. Manual(Manuel) Demarrage par commande de demarreur,la generatrice reste en marche. En cas de panne de reseau,le transfert de charge s'effectue. Dalai de demarrage programmable de 10 a 30 secondes 10 s de serie Sequence de demarrage du moteur Cycle de lancement:16 s active,7 s de repos(duree maximale 90 s) Prechauffage du moteur 5 s Refroidissement du moteur 1 min Verrouillage du demarreur. Le demarreur ne peut pas etre relance pendant 5 s apres l'arret du moteur. Chargeur de batterie intelligent De serie Regulation de tension automatique avec protection contre les surtensions et les sous-tensions De serie Arret automatique pour basse pression d'huile De serie Arret pour surregime De serie,72 Hz Arret pour temperature elevee De serie Protection contre l'emballement De serie Fusible de securite De serie Protection contre les echecs du transfert De serie Protection batterie dechargee.. De serie Journal de fonctionnement 50 evenements De serie Systeme d'exercice d'entretien compatible futur groupe De serie Protection contre les cablages incorrects De serie Protection contre les defaillances internes De serie Capacite defaillances externes courantes De serie Protection contre les defaillances du regulateur de vitesse De serie GENERAC' 22 • 27 • 32 • 38 accessoires disponibles ti 7.2 0 N° de modele Produit Description 0 a a Le systeme Mobile Link de Generac permet de contrOler I'etat de la generatrice depuis Accessoire cellulaire tout endroit ayant acces a une connexion Internet a partir d'un ordinateur ou de tout G0071690 4G LTE Mobile Link® telephone intelligent.II permet mettle d'être notifie par courriel ou SMS de tout changement se produisant dans I'etat de la generatrice.Remarque:Necessaire 5/9 faisceau adaptateur requis.Propose aux Etats-Unis seulement. Necessaire adaptateur G006478 0 Mobile Link L/C(requis Le necessaire faisceau adaptateur est requis pour rendre les modeles refroidis par pour les series QT et liquide compatibles avec Mobile Link®. RG) Necessaire pour temps Si la temperature descend regulierement en dessous de 32°F(0°C),installer un G005630-1 -22,27,32 et 38 kW necessaires pour temps froid afin de maintenir la batterie a une temperature optimale. froid Le necessaire comprend un chauffe-batterie a thermostat integre dans l'enveloppe. G005616-0 22,27,32 et 38 kW Necessaire pour froid Recommande si la temperature descend regulierement en dessous de 32°F(0°C) extreme pendant des durees prolongees.Pour les modeles refroidis par liquide uniquement. G005651-0 Necessaire bouchons L'ajout de bouchons sur le socle de la generatrice permet d'empecher('intrusion de de socle saletes. Si l'enceinte de la generatrice est rayee ou endommagee,it est important de retoucher G005703 0 Bisque Necessaire de peinture la peinture pour la proteger contre la corrosion.Le necessaire de peinture comprend la peinture requise pour assurer un entretien ou une retouche correcte de l'enceinte de generatrice. G005656-0 22 et 27 kW Necessaire d'entretien Les necessaires d'entretien courants pour modeles refroidis par liquide comprennent G005984 0 32 et 38 kW courant tout le materiel necessaire pour effectuer des operations d'entretien completes sur les generatrices Generac refroidies par liquide. G006664 0 Systeme local de Aliments par batterie,le systeme de surveillance sans fil de Generac permet d'être surveillance sans fil informs en temps reel de l'etat de la generatrice sans jamais sortir de la maison. G006665 0 Faisceau de rallonge de Utilisation recommandee avec la telecommande sans fil sur les modeles jusqu'a telecommande sans fil 60 kW,obligatoire sur les modeles de 70 kW ou plus. Les modules de gestion intelligente s'utilisent en association avec le commutateur de G006873 0 Module de gestion transfert automatique pour renforcer ses capacites de gestion de I'energie.Its offrent intelligente(50 A) une souplesse supplementaire dans la gestion de l'energie sans egale parmi les autres systemes sur le marche. Interrupteur a bascule d d'urgence pour L'arret d'urgence permet de couper I'arrivee de carburant et d'arreter la generatrice G007993-0 installations residentielles selon immediatement en cas d'urgence. NEC2017 Interrupteur d'arret d'urgence rearmable L'arret d'urgence permet de couper l'arrivee de carburant et d'arreter la generatrice G006510-0 pour installations commerciales selon immediatement en cas d'urgence. NEC2020 Le contreleur de niveau de propane compatible Wi-Fi permet une surveillance en ContrOleur de niveau de continu du reservoir de propane liquide raccorde.La surveillance du niveau du reservoir G007005-0 est un moyen important d'assurer que la generatrice sera prete a l'emploi durant une propane liquide Wi Fi coupure de courant inattendue.Alerte d'etat au moyen d'une application gratuite pour vous avertir lorsqu'il faut refaire le plein du reservoir. 9 Protector® serie QS az o N C, N CD 0 o N co SERVICE ITEM 2.4L NOTES. N OIL FILL CAP EITHER SIDE RADIATOR/EXHAUST OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1092(43")WIDE X 1885(74.2")LONG. d:.0 DISCHARGE AIR AIR INTAKE OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. ^ (BOTH SIDES) (BOTH SIDES) OIL DRAIN HOSE LEFT SIDE 2 ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE BATTERY 12 - RADIATOR DRAIN LEFT SIDE AND APPLSCABLEING.NFPA 31S UNIT MUST BE INSTALLED IN 7 AND NFPA 70 STANDARDS AS WELL AS ANYEOTITH CURRENT HER FEDERAL, COOLANT RECOVERY BOTTLE LEFT SIDE i\ GRP 26 STATE,AND LOCAL CODES. V RADIATOR FILL CAP ROOFTOP IV NEGATIVE GROUND 3.CONTROL PANEL/CIRCUIT BREAKER INFORMATION CD AIR CLEANER ELEMENT LEFT SIDE PM:077483 -SEE SPECIFICATION SHEET OR OWNERS MANUAL CL REMOVE COVE' SPARK PLUGS LEFT SIDE -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. FOR ACCESS TO .-..,r" MUFFLER SEE NOTE II 4.REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS RADIATOR FILL CAP 1 11 „s /� '; DRNE BELT EITHER SIDE THE STUB-UP AREAS AS FOLLOWS: iI FAN BELT SEE NOTE 11 -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION 11 MI1 ,,, BATTERY LEFT SIDE NEUTRAL CONNECTION,BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. GI REFERENCE OWNERS MANUAL -LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. "' FOR PERIODIC REPLACEMENT 5.CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 427 [ ' PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND [16.8] RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. ,. 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 8.MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 (USE STANDARD SAE TORQUE SPECS) I -►141 9.MUST ALLOW FREE FLOW OF INTAKE AIR,DISCHARGE AIR AND EXHAUST.SEE SPEC - 629.9[24.8] SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. [5.6] CENTER OF GRAVITY 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE (SEE NOTE 5) AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. TOP VIEW 11.EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE, REMOVE FRONT PANEL TO ACCESS. EXHAUST MUFFLE' ENCLOSED WITHIN CIRCUIT BREAKE GENERATOR ENCLOSURE SEE NOTE 3 f 631 [24.8] DOOR TYP a- '-. tr" "5 �0 1� REAR ENCLOSURE -- C [ "` 1. 980 COVER PANEL . ' "1�- [38.6] SEE NOTE 4 T- VICE ACTION LATCH, RADIATORIEXHAUST _ 1 OVERALL ONE PER DOOR, DISCHARGE AIR • ', ,• HEIGHT - ' ONE LIFT OFF 1i § t USTOMER ACCESS 48 �. # ] ,,„„ ASSEMBLY,CONTROL 1.9 DOOR PER SIDE 3 `R - ' PANEL ACCESS, TY9] t�� +Mr " ."" OF GENERATOR - BATTERY CHARGER 11 CI • LOCATED WITHIN A O 1040 ...I I SEE NOTE 4 48 [40.9] 776 [30.6] ►II 45 ► 1490[58.7]TYP [1 9] FUEL LINE CONNECTION OVERALL WIDTH 1[1.B) . 1580[62.2] 3/4"NPT FEMALE COUPLING REAR VIEW TYP OVERALL LENGTH = LEFT SIDE VIEW WEIGHT DATA RIGHT SIDE VIEW CM ENGINE/KW ENCLOSURE WEIGHT WEIGHT SHIPPING WEIGHT GENSET ONLY SHIPPING SKID • KVA MATERIAL KG RBSI KG ABS] KG IL&S]1 = 0 2 PH 22KW SINGLE PHASE 7 IKVA1KVA(50HZ) AL 410.5]905] 30I661 MO I971] THREE PHASE 22 VA(50112) Q 2.4L 27KW(60HZ) m SINGLE PHASE 21.6KVA(50HZ) AL 4261940/ 30166] 456 HOW DIMENSIONS.MM[INCH) CD THREE PHASE 27KVA(50HZ) S. z CM .1 m 313 n 0 n • N CD 13.5 X 29.5 N MOUNTING SLOTS *NOTE-STUB-UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. y 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. ''::J•4::YpyN:� 674 .99999-55:99 [26.5] —104.5 StUi:vY [4.11] .� , (STUB-UP { AREA 28 —9 51 [1.1] 100 I [.4] [2.0] [3.9] 'STUB-UP AREA 1370[54.0] ► 210[8.3] REMOVABLE TOP VIEW STUB-UP COVER 735 [28.9]P1111111=1111111111111101 1 96 [3.8] 27 [1.0]--► 723 [28.5]TYP 1.145 ]1.8]TYP ► 1380[54.3]TYP '1 TYP MOUNTING SLOT CENTERS MOUNTING SLOT CENTERS 776 [30.6] ► 1580[62.2] LEFT SIDE VIEW REAR VIEW ort O' Y C m cn DIMENSIONS:MM[INCH] _ CD = m O m sal .7i xi 2 D n Protector® serie OS 10 Protector® serie QS un o cA3 CD N CO CD 0 CD w CO CO SERVICE ITEM 2.4L NOTES: rn RADIATOR/EXHAUST OIL FILL CAP EITHER SIDE co C DISCHARGE AIR AIR INTAKE OIL DIP STICK RIGHT SIDE 1.MINIMUM RECOMMENDED CONCRETE PAD SIZE:1194(47")WIDE X 2255(88.8")LONG. pp (BOTH SIDES) (BOTH SIDES OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. n OIL DRAIN HOSE RIGHT SIDE 2.ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE RADIATOR DRAIN HOSE LEFT SIDE AND SERVICING.THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT °- COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, co 768 [30.2]—I.- RADIATOR FILL CAP ACCESS ROOF TOP STATE,AND LOCAL CODES. Na — CENTER OF GRAVITY AIR CLEANER ELEMENT RIGHT SIDE 3.CONTROL PANEL/CIRCUIT BREAKER INFORMATION: 167 SEE NOTE 5 SPARK PLUGS LEFT SIDE -SEE SPECIFICATION SHEET OR OWNERS MANUAL MUFFLER SEE NOTE 11 -ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. [6.6) DRIVE BELT EITHER SIDE 4.REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS ` -,,,-.9. it` FAN BELT SEE NOTE 11 THE STUB-UP AREAS AS FOLLOWS: 4 w , >5 4 BATTERY LEFT SIDE -HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,NEUTRAL ; 535 CONNECTION,AND BATTERY CHARGER 120 VOLT AC(0.5 AMP MAX)CONNECTION. [21 1] I 1 sw REFERENCE OWNERS MANUAL -LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. FOR PERIODIC REPLACEMENT 5.CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. PART LISTINGS. 6.BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND ' _ RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. g a 7.REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. i 8.MOUNTING BOLTS ORT STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 2.5"O.D.EXHAUST (USE STANDARD SAE TORQUE SPECS) OUTLET 4 . - 9.MUST ALLOW FREE FLOW OF INTAKE AIR,DISCHARGE AIR AND EXHAUST.SEE SPEC SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 10.GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE REMOVE COVE- TOP VIEW BATTERY 12V,GRP 26 AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. FOR ACCESS TO NEGATIVE GROUND 11.EXHAUST MUFFLER AND FAN BELT ARE ENCLOSED WITHIN GENERATOR ENCLOSURE, RADIATOR FILL CAP P/N:077483 REMOVE FRONT PANEL TO ACCESS. VICE ACTION LATCH, HAUST MUFFLER ONE LIFT DOOR, TEX ENCLOSED WITHIN CIRCUIT BREAKER ONE PER SEE NOTE 3 —759 [29.9]—i GENERATOR ENCLOSURE DOOR TYP OFF DOOR PER SIDE / OF GENERATOR „S ; , ,. eta - .e T ' s '* REAR ENCLOSURE - : ' -'- 'IP ' COVER PANEL -H,"lt„ a I.I x 1171[46.1] . .. SEENOTE4 * C7 OVERALL . RADIATOR/EXHAUST - <> -.a , - G DISCHARGE AIR HEIGHT USTOMERACCESS ASSEMBLY,CONTROL i ~: x_ `- PANEL ACCESS, ", c • • '� BATTERY CHARGER - = �' �` LOCATED WITHIN .. • SEE NOTE 4 CO C 50 [2.0] 1-4— —888 [35.0] ►1 47 1857 [73.1]TYP CD FUEL LINE CONNECTIO OVERALL WIDTH [1.8 . 58 3/4"NPT FEMALE COUPLING 1000 [39.4] J TYP] OVERALL LENGTH [TYP 0LEFT SIDE VIEW REAR VIEW CD LIFTING PROVISIONS RIGHT SIDE VIEW (4 PLACES) z SEE NOTES 5,7 AND -" CENTER OF GRAVITY DIMENSIONS WEIGHT DATA V) m WEIGHT WEIGHT ENCLOSURE SHIPPING WEIGHT . r ENGINE46N MATERIAL GENSET ONLY SHIPPING SKID KG RBS] KG[LBS] KG[LBS] 2.4L 32KW AL 556(1225] 44[98] 600[1323] DIMENSIONS:MM[INCH] 2.4L 38KW AL 560112351 44198] 605[1333] G) m C.,, Z N m CD D `13.5X29.5 CO MOUNTING SLOTS *NOTE-STUB-UP AREA FOR HIGH AND LOW VOLTAGE CONNECTIONS. 4X CIRCUIT BREAKER,NEUTRAL AND CUSTOMER CONNECTION OPENING. O N O_ m m m 786 ial o [30.9] o m m -162 [6.4] co - . STUB UP v AREA — 0 R. N o- C • • y N 9 [.4] -, al. 12 [.5] [ o. B 51 2.0] in 162 [6.4] ► m, *STUB-UP co c' AREA REMOVABLE STUB-UP ACCESS COVER m. • (SHIPPED LOOSE WITH GENERATOR) 1733 [68.2] "I ► 217 [8.5] TO BE INSTALLED DURING GENERATOR - cn INSTALLATION TOP VIEW T N wnco r 850 [33.5] 1 N.,E °; = 116 0 y' [4.6] L25 i 838 [33.0]TYP o v 50 TYP 1750 [68.9]TYP [1.0] MOUNTING CENTERS ;;• y [2.0] MOUNTING SLOTS TYP ^� m m 888 [35.0] - o 0 GI N°' 1950 [76.8] F. = = a,- * REAR VIEW c CAD m o a LEFT SIDE VIEW o rn� OD O co m O 1 C=D i iY m ° W O-p N XI N m. N O< O M. o m 0 0 IV = 0 iD Protector® serie OS ...... ................»......... .,...,,,.,,.,... . ..,....aw.»nevavrverv.:xvvar.afaxxxaf.rwwavvw.ulw+a fulsutwraaawawrfuaf..u....uv;r,a ... .,a f... .af raaa3r aw.awaau suwAw. ftuwiNAw6xLwtANd atsi4euat l4tutlwfi i 6Jae;Ywulauuatt n Site Selection and Preparation Fresh Air for Ventilation and Cooling Site Preparation Install unit where air inlet and outlet openings will not Generator Foundation become obstructed by leaves, grass, snow, etc. If prevail- ing winds will cause blowing or drifting, consider using a Install the generator on a concrete pad or base slab able windbreak at a safe distance to protect the unit. to support its weight and accessories. A correct founda- tion is needed to resist dynamic loading and reduce transmitted noise and vibration. The exact composition of Water Ingress Avoidance the mounting pad must follow standard engineering prac- • Select a location on high ground where water tices for the required loading and application. Securely levels will not rise and flood the generator. This unit fasten generator to the foundation using suitable should not operate in, or be subjected to, standing grade, size, and style fasteners. Holes are provided in water. the base frame for this purpose. • Install unit where rain gutter downspouts, roof run Concrete Pad off, landscape irrigation, water sprinklers, or sump pump discharge does not flood unit or spray Follow all federal, state, and local codes when designing enclosure, including any air inlet or outlet a concrete pad or base slab. openings. Seat concrete pad on a prepared solid subsurface and • Excess moisture can cause excess corrosion and use appropriate reinforcing bar or expanded wire mesh. decrease life expectancy of the unit. A common specification calls for 2,500 psi (17.24 MPa) concrete reinforced with 8 gauge wire mesh. Proximity to Utilities Dimensions • Contact local utility providers and verify proposed Extend concrete pad beyond the frame of the unit at least site selection meets all required utility placement 3 in (7.62 cm). A concrete pad extending 6 in (15.2 cm) requirements before installation. This could affect beyond the frame of the unit is suggested to provide a warranty coverage. mounting surface for fuel line support, and space for • Remember, laws and or codes may regulate maintenance and repair. distance and location of unit to specific utilities. The base pad must be: • It is recommended to pick a location where the • Capable of supporting 125% of the unit wet weight generator is as close as possible to the transfer for single unit applications. switch and the fuel supply, while verifying the site • Flat and level to within 0.5 in (13 mm). location conforms to the rest of the Site Selection section. • Capable of withstanding severe torque reactions. NOTE: Be aware one or both sides of generator may To calculate the depth of the concrete pad, the following need to be accessed in order to perform routine and peri formula may be used: odic maintenance. Depth of Base= Density x B x L Transportation Recommendations W=Total wet weight of generator set in pounds(kg) Use a suitable cart or equipment to carry generator, Density= Density of the concrete: including wooden pallet, to installation site. Place card- board between cart and generator to prevent any dam 150 pounds per cubic foot age or scratches to generator. • 2,400 kilograms per cubic foot Do not lift, carry, or move generator by grasping the B= Foundation width in feet(meters) louvers. Doing so may bend or damage the sheet L= Foundation length in feet(meters) metal. Suggested mixture of concrete (by volume) is 1:2:3 of cement, sand, and aggregate with a maximum 4 in (100 mm) slump with a 28 day compression strength of 3,000 psi (20.7 MPa). RECEIVED FEB 16 2022 CITY OF TIGARD BUILDING DIVISION Installation Guidelines For Spark-Ignited Stationary Generators 13 • Site Selection and Preparation Stub-Up Area Placement on Roofs, Platforms, and For load conduit, auxiliary power conduit (high voltage), Other Supporting Structures and control wiring conduit (low voltage), see unit installa- Where required to place generator on a roof, platform, tion drawings for location and dimensions of the stub-up deck, or other supporting structure and an oil contain- area. Figure 3-4 illustrates a typical stub opening (A). ment system consisting of a curb or dike shall be pro- vided in accordance with the requirements in NFPA 37 chapter 4.1.3 and chapter 6. Contact local building inspection department or fire department to determine which noncombustible materials are approved for instal- ' lation. In.(mm) 0 4.1(104.5) LI: u , 1.9(50)-► f 0.4(9) 2.0(51) 3.9 .44 (100) 002771 Figure 3-4. Installation Drawing Stub-Up Detail (Typical) Mounting Fixed Foundation Use mounting holes in the base frame to fasten unit to foundation. Always use hardware of a suitable grade, size, and style. Connections All electrical connections must have flexible sections to isolate vibration if they connect to the unit base rails. Cor- rectly support and secure all piping before installing the flexible connection. The surface beneath and beyond the engine and the oil containment system must be noncombustible to a mini- mum distance of 12 in (300 mm). 14 Installation Guidelines For Spark-Ignited Stationary Generators