Report •
OFFICE COPY ECEIVE
A 2� 5863 Lakeview Blvd.,Suite 100
MLake Oswego,OR 97035
Y OF TIGARD (503)627-0100
iffittif IJILDING DIVISION CCU 135901
R
fP.52O22-roo q 3
l'95 8 9 c�J ,ter
Zoom + Care
11958 SW Garden Place
Tigard, OR 97223
FIRE ALARM SYSTEM
I
re3
• Maki
5863 Lakeview Blvd.,Suite 100
Lake Oswego,OR 97035
(503)627-0100
CCB#135901
Flouts,
CORPORATION
TABLE OF CONTENTS
A. Fire Alarm System
1) System Sensor PC2WL, SCWL—Horn Strobe Ceiling Application 3
2) System Sensor SWL—Horn Strobe Wall Application 7
B. Shop Drawing 11
• f SYSTEM
$ SENSOR'
Indoor Selectable- 1
Output Strobes and jl = $ •
-
Horn Strobes for -. �
Ceiling Applications
•
System Sensor L-Series audible visible notification •
products are rich with features guaranteed to cut
aft
installation times and maximize profits with lower411,
current draw and modern aesthetics. ;
Features The System Sensor L-Series offers the most versatile and
• Plug-in design with minimal intrusion into the back box
easy-to-use line of horns,strobes,and horn strobes in the industry
with lower current draws and modern aesthetics.With white and red
• Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor
• Automatic selection of 12-or 24-volt operation L-Series can meet virtually any application requirement.
at 15 and 30 candela
• Field-selectable candela settings on ceiling units: The entire L-Series product line of ceiling-mount strobes and horn
15,30,75,95, 115, 150,and 177 strobes include a variety of features that increase their application
versatility while simplifying installation.All devices feature a plug-in
• Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations
• Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time-
consuming ground faults.
• Universal mounting plate for ceiling units
• Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal
before device installation mounting plate so installers can mount them to a wide array of back
• Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring,installers can test wiring
Advance devices continuity before the device is installed.
• Compatible with MDL3 sync module
Installers can also easily adapt devices to a suit a wide range of
• Listed for ceiling mounting only application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with two volume selections.
Agency Listings
S16NALIN6 T (•„ u4
(13
LISTED AP I
I -
S5512 FM approved except 7125-1653:0504
S4011 for ALERT models 7135-16530503
3057383
AVDS868-02.12/01/2017•Page 3
L-Series Specifications
Architect/Engineer Specifications
General
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-
• gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used
for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series
products,when used with the Sync•Circuit''Module accessory,shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150,and 177.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
• Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5'high(173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9'diameter x 3.4'high(175 mm diameter x 86 mm high)
(SBBCRL,SBBCWL)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd. 1
AVDS868-02.12/01/2017•Page 2
UL Current Draw Data
UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS)
8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC DC FWR Sound Pattern dB DC DC FWR
• Candela 15 87 41 60 Temporal High 39 44 54
Range 30 153 63 86 Temporal Low 28 32 54
75 N/A 111 142 Non-Temporal High 43 47 54
95 N/A 134 164 Non-Temporal Low 29 32 54
115 N/A 158 191 3.1 KHz Temporal High 39 41 54
150 N/A 189 228 3.1 KHz Temporal Low 29 32 54
177 N/A 226 264 3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54
UL Max.Current Draw(mA RMS),Ceiling Horn Strobe,Candela Range(15-177 cd)
8-1Z5 Volts 16-33 Volts
DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 103 167 71 90 143 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non Temporal High 106 173 71 90 141 165 187 230 273
Non-Temportal Low 95 166 54 71 124 161 170 216 258
3.1K Temporal High 111 164 69 94 147 163 184 229 257
3.1K Temporal Low 103 163 54 88 143 155 185 212 252
3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259
16-33 Volts
FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
•
Non-Temportal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 255 289
3.1K Temporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1K Non-Temporal Low 79 101 150 171 196 229 260
Horn Strobe Tones and Sound Output Data
Horn Strobe Output(dBA)
8-17.5 16-33
Switch Volts Volts
Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
' AVDS868-02•12/01/2017•Page 3
L-Series Dimensions
2.4T(62.7 mm) -
1.37'(34.8 mm) -- - 6.92'diam. -..- 2.5' -a-
6.83'dam.--, (175.77 mm) (64 mm)
(173 mm) \
ono*a �
f 0 / 1 I 1111i
ra
{' O
� 8 0 0 0 8 _----
` __
A0545-00 A0546-00
r Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box
s
\ / am
ftIo
I • 0a ego 4r � -
ocerma
qui op:
,
‘11P. I f ® , "
i
vr 8
r'- ` ,
!!" A0494.01 \\ A0531-01
2-Wire Ceiling Mount Horn Strobes 4-Wire Ceiling Mount Horn Strobes
with Ceiling Surface Mount Back Box with Ceiling Surface Mount Back Box
L-Series Ordering Information
Model Description Model Description
Ceiling Horn Strobes Ceiling Strobes
PC2RL 2-Wire,Horn Strobe,Red SCRL Strobe,Red
PC2WL 2-Wire,Horn Strobe,White SCWL Strobe,White
PC4RL 4-Wire,Horn Strobe,Red SCWL-CLR-ALERT Strobe,White,ALERT
PC4WL 4-Wire,Horn Strobe,White Accessories
TRC-2 Universal Ceiling Trim Ring Red
TRC-2W Universal Ceiling Trim Ring White
SBBCRL Ceiling Surface Mount Back Box,Red
SBBCWL Ceiling Surface Mount Back Box,White
For a ceiling-listed horn-only device,see AVDS865"Indoor Selectable-
Output Horns,Strobes,and Horn Strobes for Wall Applications".
i� SYSTEM ®2017 System Sensor.
3825 Ohio Avenue•St.Charles,IL 60174 Product specifications subject to change without notice.Visit systemse,sor cm
�.V SENSOR Phone:800-SENSOR2•Fax:630-377-6495 for current product Information.including the latest version of this data sheet.
AVDS86e42•12/01/2017
SYSTEM
�$ SENSOR' .1.41111I
ttl11111I
.1ti'i+�' F
Indoor Selectable- ,,
Output Horns, R
Strobes, and
Horn Strobes for
Wall Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut , • ' '` NIP Air*
installation times and maximize profits with lower w!
current draw and modern aesthetics.
,1
t
Features
• Updated Modern Aesthetics The System Sensor L-Series offers the most versatile and
• Small profile devices for Horns and Horn Strobes easy-to-use line of horns,strobes,and horn strobes in the industry
• Plug-in design with minimal intrusion into the back box with lower current draws and modern aesthetics.With white and red
• plastic housings,standard and compact devices,and plain,FIRE,
• Tamper-resistant construction and FUEGO-printed devices,System Sensor L-Series can
• Automatic selection of 12-or 24-volt operation at 15 and 30 meet virtually any application requirement.
candela
• Field-selectable candela settings on wall units: The L-Series line of wall-mount horns,strobes,and horn strobes
15,30,75,95, 110, 135,and 185 include a variety of features that increase their application versatility
• Horn rated at 88+dBA at 16 volts while simplifying installation.All devices feature plug-in designs
• Rotary switch for horn tone and two volume selections with minimal intrusion into the back box,making installations fast
and foolproof while virtually eliminating costly and time-consuming
• Mounting plate for all standard and all compact wall units ground faults.
• Mounting plate shorting spring checks wiring continuity before
device installation To further simplify installation and protect devices from construction
• Electrically compatible with legacy SpectrAlert and SpectrAlert damage,the L-Series utilizes a universal mounting plate for all
Advance devices models with an onboard shorting spring,so installers can test wiring
• Compatible with MDL3 sync module continuity before the device is installed.
• Strobes and Horn Strobes listed for wall mounting only
Installers can also easily adapt devices to a suit a wide range
• Horns listed for wall or ceiling use of application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with two volume selections.
Agency Listings
SIGNAUNG *� ,�
USTED APPROVED I. f
S5512 FM approved except 7125-1653:0504
S4011 for ALERT models 7135-1653:0503
3057383,3057072
AVDS865-05•2/22/2018•Page 1
L-Series Specifications
Architect/Engineer Specifications
General
L-Series standard horns,strobes,and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box,4 x 4 x 11/2-inch back box,4-inch
octagon back box,or double-gang back box.L-Series compact products shall mount to a single-gang 2 x 4 x 17/8-inch back box.A universal
mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be
used for mounting wall compact models.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series
products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 110, 135,and 185.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The
module shall synchronize Strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 4"/i6 x 4"/16 x 21/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 1.91'D(143 mm L x 119 mm W x 49 mm D)
Compact Wall-Mount Dimensions(including lens) 5.26"L x 3.46"W x 1.91"D(133 mm L x 88 mm W x 49 mm D)
Horn Dimensions 5.6"L x 4.7"W x 1.25"D(143 mm L x 119 mm W x 32 mm D)
Compact Horn Dimensions 5.25"L x 3.45"W x 1.25"D(133 mm L x 88 mm W x 32 mm D)
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.
AVOS865-05•2/22/2018•Page 2
e
UL Current Draw Data
• UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS)
8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC DC FWR Sound Pattern dB DC DC FWR
• Candela 15 88 43 60 Temporal High 39 44 54
Range 30 143 63 83 Temporal Low 28 32 54
75 N/A 107 136 Non-Temporal High 43 47 54
95 N/A 121 155 Non-Temporal Low 29 32 54
110 N/A 148 179 3.1 KHz Temporal High 39 41 54
135 N/A 172 209 3.1 KHz Temporal Low 29 32 54
185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54
UL Max.Current Draw(mA RMS),Wall Horn Strobe,Candela Range(15-185 cd)
8-17.5 Volts 16-33 Volts
DC input 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 98 158 54 74 121 142 162 196 245
Temporal Low 93 154 44 65 111 133 157 184 235
Non-Temporal High 106 166 73 94 139 160 182 211 262
Non-Temportal Low 93 156 51 71 119 139 162 190 239
3.1K Temporal High 93 156 53 73 119 140 164 190 242
3.1K Temporal Low 91 154 45 66 112 133 160 185 235
3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261
3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242
16-33 Volts
FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 83 107 156 177 198 234 287
Temporal Low 68 91 145 165 185 223 271
Non-Temporal High 111 135 185 207 230 264 316
Non-Temportal Low 79 104 157 175 197 235 283
3.1K Temporal High 81 105 155 177 196 234 284
3.1K Temporal Low 68 90 145 166 186 222 276
3.1K Non-Temporal High 104 131 177 204 230 264 326
3.1K Non-Temporal Low 77 102 156 177 199 234 291
Horn Tones and Sound Output Data
Horn and Horn Strobe Output(dBA)
8-17.5 16-33
Switch Volts Volts
Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
9" Coded High 85 90 90
10* 3.1 KHz Coded High 84 89 89
"Settings 9 and 10 are not available on 2-wire horn strobes.Temporal coding must
- be provided by the NAC.If the NAC voltage is held constant,the horn output remains
constantly on.
• AV05865-05.2/22/2018•Page 3
L-Series Dimensions
ur
^.-- 3.46•—.... 485 mm 80 mm _-; t25. ASr _ 1.55•
It)mm 125'
-r 32 mm 34 min (Al cm) MA cm)
Pil
133.9mm ur •i+au• MI sxl y bar
8 (13.7 an)
OC
i tilii—: 4 IIIIINom ,339mm , 8:4
40548-00 50547-00
A0557-00
Compact Strobe,Horn Strobe Compact Horn Compact Wall Surface Mount Back Box
SBBGRL,SBBGWL
-°--- 4.70" —ew
(11.94 cm) ter
(4!6 cle) 119 mm t25• --_— tar r) — _
135' 3Y mm (1224 an) (4.69 )
C 'N'a'"> ) f (3.16 MM) A ,("-
t ® nl
ll C
14.68 cm
(14.4 cm)
Y
1M mm 44' )
Strobe,Horn Strobe Aoss°-oo A054s 00 A0554-01
Horn Wall Surface Mount Back Box
SBBRUSBBWL
L-Series Ordering Information
. Model Description Model Description
Wall Horn Strobes Horns*
P2RL 2-Wire,Horn Strobe,Red HRL* Horn,Red
P2WL 2-Wire,Horn Strobe,White HWL* Horn,White
P2GRL 2-Wire,Compact Horn Strobe,Red HGRL* Compact Horn,Red
P2GWL 2-Wire,Comp 2 fils act Horn Strobe,White HOWL* Compact Horn,White
P2RL-P 2-Wire,Horn Strobe,Red,Plain Accessories
P2WL-P 2-Wire,Horn Strobe,White,Plain TR-2 Universal Wall Trim Ring Red
P2RL-SP 2-Wire,Horn Strobe,Red,FUEGO TR-2W Universal Wall Trim Ring White
P2WL-SP 2-Wire,Horn Strobe,White,FUEGO SBBRL Wall Surface Mount Back Box,Red
P4RL 4-Wire,Horn Strobe,Red SBBWL Wall Surface Mount Back Box,White
P4WL 4-Wire,Horn Strobe,White SBBGRL Compact Wall Surface Mount Back Box,Red
Wall Strobes SBBGWL Compact Wall Surface Mount Back Box,White
SRL Strobe,Red
SWL Strobe,White
SGRL Compact Strobe,Red
SGWL Compact Strobe,White
SRL-P Strobe,Red,Plain
SWL-P Strobe,White,Plain
SRL-SP Strobe,Red,FUEGO
SWL-CLR-ALERT Strobe,White,ALERT Notes:
All-P models have a plain housing(no"FIRE"marking on cover).
All-SP models have"FUEGO"marking on cover.
All-ALERT models have"ALERT"marking on cover.
*Horn-only models are listed for wall or ceiling use.
SYSTEM3825 Ohio Avenue•St.Charles,IL 60174 02018 System Sensor.
�$ SENSOR Phone:800-SENSOR2•Fax:630-377-6495 Product specifications subject to change wnntwtnotice.Visitsystems nsooctr
for current product information,including the latest version of this data sheet.
www.systemsensor,com AVBS865-05.2/22/2018