Report RECEIVED ,
P POTTER �� OP�AFC-50
The Symbol of Protection DEC 13 202� Fire Alarm Control Panel
LAiYOFTIGARD
'GILDING DIVISION —_
Features FR5202/-0 /1‘ QSSEM8�o
• 50 addresses available on this analog addressable system /4134f11 7Z
• Additional system capacity achieved via multi-point SLC modules •'2 yp•
• 99 software zones THe.
• NFPA 72 Compliant Smoke Sensitivity Test Built-In eromy
• System Operates as Class A or Class B for SLC,P-Link and NACs AFC-50
�n Nr,•Cm•q r"
• 5 Amp Power Supply,Expandable to 310 amps
• 2 NACS,Regulated,Rated at 3 Amps each,expandable to 188
• 2 Input/Output(I/O)Circuits for system flexibility rated at 1 Amp
each
• Strobe Synchronization and System Wide Sync for Gentexo,
AMSECO®,Cooper WheelockO and System Sensor®strobes
• Dedicated Alarm,Supervisory and Trouble Relays
• 4,000 Event History Buffer
• Optional two line DACT with UD-2000 that can report General,Zone
or Point Information
• Built in IP Communicator
• Ethernet Port for Programming and Network Connectivity
Nem
• E-Mail System Status,Reports and Event Information NYC Fire Dept.
• Product includes 5 year warranty. ® Certificate of Approval
APPROVED
6256 1,'.�.1 LISTED
7165-0328:0509 S735
Description Technical Specifications
The AFC-50 is an analog/addressable fire alarm system with a total system
capacity of 50 addresses.Additional capacity on the system is achieved Dimensions 16"W x 17"H x 3 7/s"D
using multi-point SLC modules.The control panel utilizes the exclusive 3.0 Amps @ 120 VAC 50/60 HZ
Potter protocol that includes a complete line of sensors and modules. AC Mains 2.0 Amps @ 240 VAC 50/60 HZ
Each SLC may be comprised of any combination of smoke sensor,heat
detectors or modules and allows for a total of 50 ohms of impedance and Enclosure 16 gauge cold rolled steel with removable
may use any wire compliant with the National Electrical Code(NEC). locked door with Lexan viewing window
The AFC-50 has a 5 Amp power supply with two Notification Appliance Standby Current-130 mA
Circuits(NACs)and two Input/Output(I/O)circuits.The NACs are rated at Alarm Current-200 mA
•
3 Amps each and the I/Os are rated at 1 Amp each.Each output is regulated 5 Amps power for NACs,I/O,and P-Link
•
and power limited.In addition,each output is uniquely programmable and Battery 3 Amps per NAC,regulated
•
may be configured for steady signal, strobe synchronization, constant 1 Amp per I/O circuit,regulated
• Battery Charger range 8-55 Ah
power, door holder power, or releasing. The strobe synchronization • Battery Charger voltage 27.3 VDC
includes Gentex,AMSECO, System Sensor and Cooper/Wheelock and • P-Link maximum current of 1 Amp
with the exclusive Quadrasync each output may have a unique brand and
all strobes will flash together. Temperature and 32°to 120°(0°C to 49°C)with a maximum
Humidity Range humidity of 93%non-condensing.
The NACs may be expanded using the PSN-1000 series intelligent power
supplies. Each PSN-1000 adds another 10 Amps of power,2 additional
input circuits and the AFC-50 will support up to 31 power supplies.The
system will synchronize the strobes system wide. In addition,the PSN-
1000E has space to allow the installation of up to six expansion cards.
The cards mount on a stacker bracket that allows access to all circuit
connections.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830133-REV E • 9/19 PAGE 1 OF 4
P POTTER AFC-50
The Symbol of Protection Fire Alarm Control Panel
SLC Loop Accessories
The control panel may be connected with up to 50 addressable devices or modules in any combination.The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Loop Devices
Device Description
PAD100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot.
PAD100-PHD Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent
obscuration and a fixed temperature 135°Fahrenheit heat detector.
PAD100-HD Analog Fixed(135d-185dF)or Rate-of-Rise Heat Detector(software selectable)
PAD100-DUCTR Addressable Duct Smoke Detector with Form C Relay.Addressable Duct Smoke Detector with Form C relay rated at 10a @
250/120VAC or 8amps at 30VDC.
PAD100-DUCT Addressable Duct Smoke Detector.
PAD 100-6B 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors.
PAD 100-4B 4"round base that may be mounted to an electrical box and wired for connection to the above sensors.
PAD 100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop.
PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC.Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC.
PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call.
PAD100-CD Addressable CO gas detector.
PAD 100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure.
PAD100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local,group and all
call. The LFSB complies with the Low Frequency Signal Requirements(520 Hz)
PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W.
Modules
Device Description
PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PAD100-PSSA Single Action Addressable Pull Station.
PAD100-PSDA Dual Action Addressable Pull Station.
PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4"square electrical box.
PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD 100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel.Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125VAC.Also provides two contact inputs.
PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PAD 100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PAD100-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PAD100-RM Relay Module that provides one form C relay controlled by the control panel.Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.
PAD100-LED Module provides a single addressable LED that is controlled by the control panel.
PAD 100-SM Speaker Module provides switching for two audio channels.
PAD100-LEDK Addressable LED and key switch that mounts in a single gang box.
PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.For use with the PAD100-DUCTR only.
PAD 100-OROI One Relay One Input Module provides one form C relay and one input.The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830133-REVE • 9/19 PAGE2OF4
P POTTER AFC-50
The Symbol of Protection Fire Alarm Control Panel
SLC Features RA-6500R(F)—4 x 40 LCD annunciator with a key pad in a locked
The Potter protocol is a digital protocol with a proven design for metal enclosure.Flush mount version available.
reliability and noise immunity.The system does not require special LED-16(F)—16 LED annunciator with common indicators in a
cable or conductors for connection of the Signaling Line Circuit locked metal enclosure.Flush mount version available.
as long as the cable is compliant with NFPA 70 and NFPA 72. PSN-1000(E)—10 amp,remote intelligent power supply with
The system allows for Class A or Class B installations as well as 6 NACs,2 Inputs and a P-Link repeater.This panel is listed in
"T Taps",with a max wiring distance of 10,000 Ft. conjunction with the AFC-50 as releasing circuits.
Sensor Features CA-6075—Class A convertor that converts the SLC,NACs and
The sensors through the fire alarm control panel provide a real P-Link connection
time status as to the condition of the system.The smoke detector UD-2000—UL listed,Dual line telephone alarm communicator
sensitivity,heat detector temperature level and drift compensation DRV 50—LED driver expander,used to connect up to 50 LEDs in a
are all programmable options.The system also allows for a day/night graphic display
mode where the panel automatically adjusts the sensitivity depending FCB-1000—Fire communication bridge,provides remote mounting
on the time of day.To assist in the reduction of false alarms,the of the Ethernet connection
smoke detectors also have a maintenance warning that sends a trouble FIB-1000—Fiber interface module,used to extend P-Link to multi-
signal when a detector is dirty to the point that it can no longer mode fiber(2 required)
maintain the programmed sensitivity. RLY 5—Relay module,provides 5 form C relay contacts rated at 3.0
User Interface amps 24VDC/125AC
The fire alarm control panel has a 2 x 16 LCD display to provide SPG-1000—Serial parallel gateway,allows for the connection to a
information to the system status.The keypad has navigation keys serial or parallel printer
to allow manipulation of the Menu on board the panel.The panel is The FIB-1000,FCB-1000 and the SPG-1000 may be installed in the
shipped standard with the following LEDs: stacker bracket or ordered with the optional rack mount enclosure.
• AC Power-Green MC-1000 Multi-Connect allows up to sixty-three AFC series panels
• Alarm Red to share a single reporting technology.
IDC-6—Initiating device circuit provides 6 programmable inputs
• Earth Fault-Amber
AE-2—Two card expansion cabinet
• Supervisory Amber AE-8—Eight card expansion cabinet
• Silenced-Amber AE-14—Fourteen card expansion cabinet
• Trouble-Amber Ethernet/I.P. Connection
• Pre-Release-Amber The AFC-50 is shipped standard with an Ethernet connection.
• Release-Red This connection is the programming port and may be connected
to a building Wide Area Network(WAN)or Local Area Network
The common buttons include a Silence,Reset,Acknowledge,and (LAN).Once connected to the Internet,the panel may be selectively
Drill.All of the buttons are accessible once the locked door is programmed to e-mail alarm conditions,trouble conditions,
opened. supervisory conditions,test,Event History and detector status.An
P-Link e-mail may be sent to the panel and the panel will e-mail the event
The AFC-50 has a proprietary communication protocol that history,detector status,configuration file or server status to an
authorized E-mail account.In addition,reminders may be set to send
communicates through a RS-485 connection to field devices.Up
to 32 devices may be connected to a single P-Link connection.The an e-mail for service,testing or other conditions.
P-Link includes the communication terminals and regulated 24 VDC In addition,the Ethernet connection is UL listed as an IP
connection for the field devices.The field devices may be any of the communicator.The IP communicator is listed to report to the UL
following: listed Sur-Gard III IP receiver.The IP communicator replaces the
PAD100-SLCE-Analog/Addressable loop expansion module traditional less reliable alarm communicator transmitter that utilized
RA-6075R—2 x 16 LCD annunciator with a key pad in a locked telephone lines.The IP communicator is an active method of
metal enclosure. connection and communication to the monitoring station.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830133-REVE • 9/19 PAGE3OF4
W
P POTTER AFC-50
a The Symbol of Protection Fire Alarm Control Panel
Dimensions
0 0 1
TOP DEPTH=3.75"
J° O 0
a
DOOR= 16.07" I`
BACKBOX=15.77" DEPTH=3.84"
•
•
_ .o • •
•
cc,ul
o ( 0
0 " cc 0
o V
Q
- I
LEFT SIDE
RIGHT SIDE
BOTTOM
DWG W93-1
Ordering Information
Model Description Stock No.
AFC-50 Fire Alarm Control Panel 3992752
Replacement Board AFC-50 3992756
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830133-REV E • 9/19 PAGE 4 OF 4
P POTTER u o-200o
The Symbol of Protection Digital Alarm Communicator
Features -o 7 ;Ek.4�,,
�
• Allows for communication to Monitoring Station
r. rr r
• Communicates using SIA-DCS or Ademco Contact ID Protocols r, <. .•" '•
• For use with IPA,AFC,and ARC series Addressable Panels and a `!
PFC-4064 Conventional Panel
t • Status LEDs indicate operation of DACT card
• Installs with ease behind main panel LCD display via User *
Interface bracket
F:. €-
• Device address is set internally to address 1 -
3
u • Includes two(2)RJ45 phone cords R "
r ,
F • •
• •
440.
:;,;;;' LISTED
Description Technical Specifications
The UD-2000 Digital Alarm Communicator Transmitter (DACT) Operating Voltage 22.0-24.0V
provides for up to two (2) phone lines for communication to a
monitoring station. The UD-2000 communicates using the SIA Standby Current 16mA
DCS or Ademco Contact ID protocols. When enabled, the DACT Alarm Current 23mA
automatically monitors each phone line or voltage and has the Max UD-2000s per panel 1
ability to seize the line and connect with a remote receiver.Once the
communication is complete,the DACT will hang up. Dimensions 4"W*6"H* 1 5/8"D
The DACT is provided with terminal blocks for each phone line and Operating Temperatures 0°C-49°C(32°F-120°F)
two RJ45 cords. In order for the DACT to work properly,it must be 10%-93%@ 30°C(86°F)
installed on a plain old telephone service (POTS) line or equivalent Operating Humidity Range (non-condensing)
deemed by the authority having jurisdiction. The DACT must be Mounting Options In FACP Behind keypad
installed before any other equipment to ensure it can seize the phone
line. Shipping Weight 0.47 lbs
Phone lines are high voltage and should be run in a separate conduit
from other circuits.The wire conductors connecting the DACT to the
phone system should be 26 AWG or larger.
Potter Electric Signal Company,LLC • St.Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com
8830146-REV B • 6/19 PAGE 1 OF 3
•
P POTTER UD-2000
The Symbol of Protection Digital Alarm Communicator
RJ31 X Phone Jack to UD-2000
Plain Old Telephone (POTS) lines
Tip(Brown) Ring(Grey)
Out to Premises Phones r Out to Premises Phones
Ring(Grey) Tip(Brown)
1-Grey �j LJ
7. 2-Tan �.
k�2 / 7Z 3-Black
4-Red
5-Green LI
6ll Y 6-Yellow�3 6�\ 3 - i 6
7-Blue
`` 8-Brown
416 Srv, u�4 5!V
Jl
Ring(Red) "U" ' "U" 'Tip(Green)
Line In From Telco Tip(Green) Ring(Red) Line In From Telco
Tel •2 one 2 Te •-. j 'hone 1
Ti, Ring Ti Ring Ti, Ring , Ring
i^ill inl i^i^l►,irrl
114 1, Li ir
UD-2000 Communicator
Telco Tip=Red
Telco Ring=Green
Phone Tip=Brown
Phone Ring=Grey
NOTICE
Install in accordance with compatible fire alarm control panel installation manual
Installation
The UD-2000 DACT is connected to the control panel using the provided four-wire cable connection(P/N 5210514)between P4 and UD-2000 P 1.The
connection is power limited and supervised.
1. Power system down.
2. Slide the UD-2000 into the card guides located under the User Interface bracket.
3. Secure the UD-2000 to the User Interface bracket using the provided#6-32x3/8"screw
4. Install the provided four-wire conductor jumper between UD-2000 P1 and P4.
Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com
8830146-REVB • 6/19 PAGE2OF3
P POTTER u D-2000
® The Symbol of Protection Digital Alarm Communicator
UD-2000 DACT Installation on UD-2000 DACT Installation on
Small Platform Panel Large Platform Panel
Fig 1 Fig 2
je i
° �-
\Eir,,,
0 00.1.11.2 1.1.0611101ff 0 0 0 0: = a
i MI 133 CD
CM COMVVV r
D
❑ Q
ra e
Zi a.
ea a - _
Screw R Q I 1 Slides in guides under main board.
® o o ri
0 q. O DWG*593-32A
0
il lilr".4. ''Fig .1 p
4.1
il 111 .. 0 E.
11 Ili
01cyl
�.
5cre
P Connector on '
small platform 11 R❑ �I
control panel Q ���
Q .-,
a Q` III®1 p a P Connector
Aim®®��3 on main board
Bi !�/L ain. . ill
�'I
.___-_-,-_,...1"_"4.r.,..,__;-_,.-f.,,,,...r.---,, . , Nu 11_55
Ordering Information
Model Description Stock No.
UD-2000 Digital Alarm Communicator 3992769
Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com
8830146-REV B • 6/19 PAGE 3 OF 3
x. ,. wglMrft#b/A{,fA/A/AH usws.,. .u:raa:.u..wruua..uuiHlsvrR&rl4st3t aRYlgtu4isuwuupkru......
►oi fr aes-corp.com
of SECURITY
CORPORATION INNO TION
Wireless Fire Alarm Canmurii Otot sJ or AFS ri el/Net
( Y
0.41�.
j[[
rt 4,4 �
7�t �.
f{ 4
FEATURES Advanced Wireless Alarm Monitoring
• UL Listed commercial fire As expensive dedicated landlines, required
alarm applications. for ULC S 559 compliance disappear, and
• ULC S 559/ULC S 304
p
• Direct reporting to AES the future of GSM for alarm transmission
receiver across AES-lntelliNet becomes increasingly uncertain, the AES
mesh radio network IntelliNet mesh radio network continues to
• Each Subscriber acts as
transmitter/receiver/repeater offer unmatched reliability and speed in
• Simple and fast activation .... 4' delivering wireless alarm signals to a central
on network "
•
On board status LEDs for station without any third-party fees or
easy setup reliance on networks operated by companies
i • 8 programmable zone • outside the alarm industry. The 7788F C
inputs w--
• Easy programming via AES ; Series Subscribers provide the wireless
sj
handheld programmer or PC communications link between the fire alarm
• Easy programming via AES panel and the central station receiver. Ideal
handheld programmer or PC
for most commercial fire alarm applications,
• Rugged metal housing ideal
for any commercial fire each 7788F-C Series Subscriber is housed
alarm application in a full-sized, red, locked steel cabinet and
• Narrowband compliant supports a range of alarm panel inputs,
including EOL fire, EOL supervised, and direct
MODELS voltage from the panel (non-fire applications).
7788F/7744F-ULP WITH
AES-INTELLIPRO FIRE
ALSO INCLUDES '1i= � 1 t{ flpei.atiori
• AES-IntelliPro Fire transmits AES Subscribers offer fully-supervised operation that includes monitoring of
full alarm data from virtually operating power(both primary AC and battery back-up) and the connection to
any fire alarm panel digital the mesh radio network. Each subscriber"checks-in"with the AES central station
communicator
• Alarm format support for receiver at least once every 24 hours.The supervision check-in time can be set to
Contact ID, Pulse, as well as as often as needed for the application, as appropriate for the network. Because
Bosch Modem lie and the central station operates the wireless network, there is no additional cost for air
Modem Illa
• Easy installation in AES time to transmit supervisory signals.
subscriber
• Operates in applications with
or without a phone line --r;-
(20 tr 51sA . (0). Net()ne
LISTED NIFPA® I._�� _.I
HOW TO ORDER Uf( Data Reporting from Alarm Panel Digital Dialel
Model Description Model 7788F-C-ULP comes equipped with an AES-IntelliPro Fire Full Data Module (AES
7744E 8 Zone Fire Alarm 7794)which enables reporting of full alarm data captured from the alarm panel's
Subscriber
digital communicator. AES-IntelliPro Fire supports most alarm communication formats
7788E-C-ULP 7744F Fire Alarm including Contact ID, Pulse, as well as Bosch Modem Ile and Modem II1a2 (when
Subscriber with converted to Contact ID format).
AES-/ntelliPro Fire
full data module
Optional Accessories Technical Specifications 7788F-C Series Subscriber
7041E Subscriber Handheld Dimensions
Programmer • 13.25"H x 8.5"W x 4.3"D Storage Temperature
•-10°to 60°C(14°to 140°F)
7794 AES-IntelliPro Fire Full Data (34cm H x 21.5cm W x 11cm D) Relative Humidity
Module Weight •0 to 85%RHC,Non Condensing
1640-C Plug-in Transformer: •Approx.7 pounds(3.2 kilograms),
16.5VAC,40VA excludes battery 7794 AES-IntelliPro Fire
Packaged with 7788F-C-ULP
Radio Frequency
•Standard Frequency Range:450-470MHz Input/Output Connections
A. f, t• t i to r) (others available in 400-512MHz range) • RJ11 connection to AES subscriber for module
Established in 1974,AES •Output Power-2 Watts data and power
Corporation empowers • RJ11 connector for Handheld Programmer/PC
Antenna programming
companies to grow profitable • Included 2.5 db tamper resistant antenna • RJ31X Telco connections-T and R both in and out
alarm monitoring businesses, mounts on enclosure via terminal strip and RJ45
and government agencies to • Multiple remote antenna options available •Alarm Panel digital communicator T and R both
enhance security anywhere Power Input •
in and out via termina strip and RJ45
in the world. Byprovidingp •Trouble output: Form C relay detects if
• 16.5VAC,40VA transformer(not included) Subscriber is off the network
the industry's only patented (ATC-Frost FPS 4016)
operator-owned and controlled
private wireless mesh networks, Backup Battery Alarm Formats
AES ensures superior reliability, •Will charge 12V battery up to 7.5 AH.Requires •Support for Contact ID and Pulse formats as well
low TCO and optimal RMR while 12VDC 7.5 AH battery for UL 864 as Modem Ile and Modem IIla2 converted to CID
reducing dependence on service Size
provider infrastructures. Alarm Signal Inputs(subscriber) •2.8 x 5.0 inches(7.1cm x 12.7cm)
The company's flagship •7788F-8 individually programmable zones
•7744F-4 individually programmable zones and Power Requirements
AES-IntelliNet systems are 4 reverse polarity inputs • 12 VDC nominal-primary and backup power
deployed in over a half million provided by the AES 7788E-C or other Subscriber
locations worldwide. ULC Standards
• CAN/ULC S 559-04
•CAN/ULC S 304
Antenna Cut/Communication
Trouble Output
• Form C relay;fail secure;rated for 24 VDC
1A resistive
Reset Button
• Located on main circuit board.
Operating Temperature
•0°to 50°C(32°to 122°F)
For more information, go to www.aes-corp.com or call
(800) 237-6387 or contact us at sales@aes-corp.com
(C Copyright 2014 AES Corporation AES-IntelliNet is a registered trademark of AES Corporation
P POTTER PAD 100-P D
The Symbol of Protection Photoelectric Smoke Sensor
Features `' SSeM9<Fo
• Low profile,less than 2 inches with the base �► �•
THE uSQ
• Wide selectable sensitivity range of 1.0 to 3.7%/foot •
• Sensor communicates sensitivity to control panel
• UL listed smoke calibration and sensitivity
• Optional locking tab to prevent unwanted removal
• Simple DIP switch address setting,no programming tool
required
• LED alarm indicator
• Product includes a 5 year warranty
• UUKL Listed for Smoke Control
ADO'
APPROVED 1 ► LISTED
Description Technical Specifications
The Photoelectric Smoke Sensor is a listed Analog Addressable smoke Operating Voltage 24 VDC
sensor compatible with fire alarm control panels that utilize the Potter
Addressable Device(PAD)protocol.The PAD100-PD is a low profile Detector Current Draw 300 µA
smoke sensor with a wide sensitivity range.The sensor and base(not Alarm indicator I LED
included)are made of a durable plastic in an off-white color to blend Alarm set-point range 1.0 to 3.7%/ft 3.6-12%/m
in with the ceiling.
Installation temperature 32 to 120°F/ 0 to 49°C
The PAD100-PD has a sensitivity range of 1.0 to 3.7%per foot and range
is UL. The PAD100-PD features drift compensation and has built in
dirty detector warning as well as. The PAD100-PD and the control Operating relative 0%to 93%(Non-condensing)
panel communicate over a proven and robust digital communication humidity range
path and the system analyzes the information at the particular device. Start-up time Max. 1 sec.
The total polling speed is less than five(5)seconds,well under the UL Maximum number of
requirements. addresses per loop 127
The sensor is compatible with any of the PAD series sensor bases and Maximum number of
simply twists on. The PAD100-PD is addressed using DIP switches lighted indicators in 30
in the rear of the sensor and can be easily programmed in the field alarm per loop.
without special tools. Color Eggshell White
Setting the Address Weight(without base) 101g(3.56oz)
Each addressable device on the SLC loop must have a unique address Dimensions(without Height: 1.35 in(34mm)
from 1 to 127 to function properly. The address is set using DIP base) Diameter:3.93 in(100 mm)
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device.Verify the
following:
1. Power to the device is removed
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830108-REV D • 12/18 PAGE 1 OF 2
P POTTER PAD100-PD
The Symbol of Protection Photoelectric Smoke Sensor
Air Velocity Ratings
The PAD100-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously.If the system already has 30 LEDs on,the PAD 100-PD will operate even
though the LED may not illuminate.
Operation
The PAD100-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled.The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is
in an active status.The polling LED can be turned off if desired for less conspicuous operation.
The PAD100-PD with the PAD100-4DB or PAD100-6DB has a low profile of less than two(2)inches to blend into the surrounding environment.The
sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector.
Sensor Sensitivity
The PADl00-PD and the compatible control panel work in tandem to keep the sensitivity consistent.As the sensor is installed over time,the sensor
compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty sensor.The sensor will then have to be cleaned
or replaced.
The PAD100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to
the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs.
NOTE:As required by NFPA,do not install the sensors until all construction is complete and the work area has been thoroughly cleaned.If the sensors
have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service.
Spacing
The PAD100-PD is UL listed with a recommended maximum spacing of 30 feet.Refer to NFPA 72 for specific information regarding detector spacing,
placement and special applications.
Compatible Bases
All bases will mount on a single gang,double gang,octagon,4"square or mud ring electrical box.
Device Description Stock No.
PAD 100-4DB 4"Standard Base 3992731
PAD100-6DB 6"Standard Base 3992732
PAD100-1B 6"base with an isolator module included. 3992730
PAD100-RB 6"base with one Form-C relay contact. 2A @ 30VDC,0.5A @ 125VAC 3992728
PAD100-SB 6"base with sounder module included.Sound pattern is provided from external source. 3992729
PAD 100-SPKB 6"base with speaker included 3992762
Ordering Information
Model Description Stock No.
PAD 100-PD Photoelectric Smoke Sensor 3992733
Potter Electric Signal Company, LLC • St. Louis, MO Phone: 800-325-3936 • www.pottersignal.com
8830108-REV D • 12/18 PAGE 2 OF 2
P POTTER PAD100-4DB/6DB
The Symbol of Protection 4 /6"Addressable Detector Base
Features Q,SEMB�o
•
• Terminals Marked with Polarity to assist with installation 3 a
• Duplicate terminals for in and out SLC wiring .may �'P•
• Terminals accept 22 to 12 AWG wire sizes / • '''
• Installs on single gang,double gang,octagon or 4"square boxr{�l�t' ,x'
rs ,
• Locking tab prevents unauthorized detector removal
• Product includes 5 year warranty ; � 4.51*0
® ` (1:111)
R
APPROVED I I LISTED
Application Technical Specifications
The Potter PAD100-6DB and PAD100-4DB detector bases are used Mounting Options Single gang, double gang, octagon, and 4"
to install Potter's addressable smoke and heat detectors.The PAD100- square box
6DB will mount on a single gang,double gang,octagon or 4"square Terminals Screw-Clamp Type
electrical box.
Wire Guage 22 to 12 AWG
Diameter:6.3 in(166 mm)
Description Dimensions
Height 0.72 in(18 mm)
The PAD100-6DB and PAD100-4DB are low-profile,surface mount Shipping Weight 87g(3.07 oz)
bases used with Potter's addressable detectors.The base uses screw-
clamp terminals that accept wire ranging from 22 to 14 AWG.When Material Durable Plastic
installed on recessed electrical boxes the PAD100-6DB is wide enough
to completely cover the back box and the immediate surrounding area.
The base is equipped with a locking tab to deter unauthorized removal
of the attached detector.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PRINTED IN USA 8830107-REV C • 12/18 PAGE 1 OF 2
P POTTER PAD100-4DB/6DB
The Symbol of Protection 4"/6"Addressable Detector Base
Locking Feature Wiring Diagram
The PAD100-6DB and PAD100-4DB include a locking feature that Fig.3
prevents removal of the detector without using a tool.
i
1.To eliminate this feature,break off the locking tab(refer to Figure
1),and then install the detector. b
s+. s+
Fig.1
To FA(P
First Detector Base Lust Ueteclor Buse
Loop(SL('
400 \,7 \ ® \
S-
�`
l , i� '
4:/ Break off tab(gray
area)in image to disable
locking feature. Ordering Information
Model Description Stock No.
2.To remove the detector from the base when the locking feature has PAD100-6DB 6"Sensor Base 3992732
been enabled, insert a small screw driver into the slot on the base to
push the plastic tab while simultaneously turning the detector head PAD 100-4DB 4"Sensor Base 3992731
counter-clockwise.
Fig.2
Insert small screwdriver l``l
into slot to remove /� ��
detector from base. 010
it
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PRINTED IN USA 8830107-REV C • 12/18 PAGE 2 OF 2
,
- - - _ -. -
PAD100-PSSA/PSDA
P POTTE][� Addressable Pull Station
® The Symbol of Protection Single/Dual Action
Features pSSEMB�Fo
• Single or Dual Action versions 2®Q'
• Durable die-cast construction T"E
• Reset key matches the fire alarm control panels
• Com atible with IPA Series anels M
• SLCC1assA ClassX&C1assB e � � ��� FIRELaR
• Product includes a 5 year warranty
• IJIJKL Listed for Smoke Control Li Pu�l ODwN
P�4� 1
� R ®rOTTER
APPROVED I"•� ..1
Description Technical Specifications
The PAD100-PSSA (Single Action) is activated by simply pulling Operating Voltage 24.0 VDC
the white "T" bar handle down. The PAD100-PSDA (Dual Action)
is activated by lifting the front cover and then pulling the white"T" Max SLC Standby Current 200uA
bar handle down.Once activated,the"T"bar cannot be reset without Max SLC Alarm Current 200uA
opening the front cover.Opening the front cover will also activate the 32°F-120°F(0°-49°C)
pull station.To reset the PAD100-PS Series,use the Potter WS-93 key Environmental Limitations
to unlock and open the front cover. Once the cover is open,push the Indoor Only
"T"bar back into the normal position and re-secure the front cover. Dimensions 4.75"H x 3.25"W x 1.75"D
Relative Humidity Range 0-93%(non-condensing)
Application Single gang box or
The PAD100-PSSA/PSDA is compatible with Potter's IPA and AFC/ Mounting Options potter P32-BB/DBB
ARC series addressable fire alarm control panels. It is a non-coded APS-SA-1.22lbs.
addressable pull station available in either a single or dual action Shipping Weight
model and installs on a single gang box or surface mounts using the APS-DA-1.46 lbs.
P32-BB or P32-DBB(deep)back box.
I
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830097-REV D • 12/18 PAGE 1 OF 2
PAD 100-PSSA/PSDA
P POTTER Addressable Pull Station
® The Symbol of Protection Single/Dual Action
Setting the Address
The PAD100-PS Series uses one SLC address assigned to the device.The address is set using the DIP switch located on the back of the PAD100-PS
device.
Pull Station Front View
Fig 1
0— - PR L ' I ZA o mm,
i -6 0--
1 II:;.
1 IPU!L pp�1.I PAL ��� 1jINIII
I =II D O
1
_II OUT o
Pun, e';.-- --'
L____________,:
®pow
PAD 100-PSDA
PAD100-PSSA
Pull Station Back View and Wiring
Fig 2
O
PPI Pl l'II�,
0
meonm&
O
il`G
I j1tl
ril_____A
FACTORY WIRED CONTACTS
FROM FACP OR
PREVIOUS DEVICE
TO NEXT DEVICE
Ordering Information
Model Description Stock No.
PAD100-PSSA Addressable Pull Station,Single Action 3992721
PAD100-PSDA Addressable Pull Station,Dual Action 3992720
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830097-REV D • 12/18 PAGE 2 OF 2
P POTTER PAD100-DIM
The Symbol of Protection Dual Input Module
Features ysEM
e<F
P • O
• Single module with dual contact monitoring inputs • ; • •
• Two(2)Class B or one(1)Class A monitoring inputs � �P.
• SLC Class A,Class X&Class B 2 THE uS
• Mounts in a standard 4"or double gang box
• Wiring terminals accessible when mounted in box
• All wiring terminals accept 22 to 12 AWG
Apo- ITER
• Product includes a 5 year warranty
• UUKL Listed for Smoke Control
NOTE:This addressable module does not support 2-wire smoke
detectors.
® to) UAPPROVED
Description Technical Specifications
The PAD100-DIM uses one (1) SLC loop address when monitoring Operating Voltage 24.0V
two(2)Class B circuits or one(1)Class A circuit.The module mounts
on either a 4" square or double gang box. The module is capable Max SLC Standby 240µA
of monitoring two (2) separate class B circuits making it ideal for
Current
monitoring sprinkler waterflow and valve tamper switches when they Max SLC Alarm 240µA
are located in the same proximity.The PAD100-DIM includes one red Current
LED to indicate the module's status. In normal condition, the LED Max Wiring Resistance 10052
flashes when the device is being polled by the control panel.When an of IDC
input is activated,the LED will flash at a fast rate. Max Wiring 1 F
Capacitance of IDC µ
Application EOLResistor 5.1K52
The PAD100-DIM is compatible with Potter's IPA and AFC/ARC Operating Temperature 32 to 120°F(0 to 49°C)
series addressable fire alarm control panels. The PAD100-DIM is an Range
interface module used to monitor dry contact devices such as sprinkler Operating Humidity 0 to 93%(non-condensing)
waterflow, valve tamper switches, or conventional pull stations. The Range
module is capable of monitoring two separate Class B or one Class A Max no.of Module Per 127 units
circuits. Loop
Settingthe Address Dimensions
4.17"(106mm)L x 4.17"
(106mm)W x 1.14"(29mm)D
Each addressable SLC device must be assigned an address. The Standard 4"Square or
address is set usingthe DIP switch located on the PAD100-DIM.When Mounting Options
Double Gang Box
the PAD100-DIM is used to monitor two individual Class B circuits
a single device address is assigned,each input is then identified as a Shipping Weight 0.61bs
sub-point of the module address.For example,if the address number
is assigned as "8", the first input will be "8.1"and the second input
will be"8.2".
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830082-REV D • 12/18 PAGE 1 OF 2
P POTTER PAD100-DIM
e The Symbol of Protection Dual Input Module
Installation Using Compatible Electrical Box
Fig 1
_i1.t - O
0---'----- 1,
O
k O
!arl.. 0
0 0 1! \11 .�:M y4�J'►
\_ \
Wiring Diagrams
PAD100-DIM With One Class A Circuit
Fig 2 MOVE THE"CL-A"DIP SWITCH
V TO"UP"POSITION
CD 0 c- FOR CLASS A WIRING
FROM FACP OR I 0 wr r_le,1e a 1 ,
PREVIOUS MODULE \ DPAR6iIQ 1
vl r
TO NEXT MODULE \ 71 �, o
iN
, ::t
T ® J - f�`
�— IZ Cyr o a
- - NOTE:
END-OF-LINE RESISTOR
/\ IS NOT REQUIRED
PAD100-DIM With Two Class B Circuits
Fig 3 MOVE THE'CL-A"DIP SWITCH
FOR CLASS WIRING
N
FOR CLASS B WIRING
00,
FROM FACP OR != &
PREVIOUS MODULE \ �'Iii itt-Ii
, TO NEXT MODULE \ .i i• 0
END-OF-LINE I CIII Ili 0
J
RESISTOR II�'�f�I
5.1KOHM>W J`L
Part#3005013 1011p�
®[pant 0
po Cp` r�o C� q
0
END-OF-LINE
RESISTOR — —
5.1K OHM XW
Part#3005013
Ordering Information
Model Description Stock No.
PAD100-DIM Dual Input Module 3992703
I
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 1
1
I
8830082-REV D • 12/18 PAGE 2 OF 2
P POTTER PAD100-SIM
e The Symbol of Protection Single Input Module
Features `,S�I04.,P
i ••� w
• One(1)Class B monitoring input • •••
• SLC Class A,Class X&Class B •� ��p•
0
• Mounts in a standard 4"or double gang box ti rHE 5
• Wiring terminals accessible when mounted in box
r
• All wiring terminals accept 22 to 12 AWG
• Product includes a 5 year warranty ®pow
• UKL Listed for Smoke Control ° " 'U
NOTE:This addressable module does not support 2-wire smoke •
detectors.
::. I.
APPROVED
Description Technical Specifications
The PAD100-SIM uses one(1)SLC loop addresses when monitoring Operating Voltage 24.0V
one(1)Class B circuit.The module mounts on either a 4"square or
double gang box.The module is capable of monitoring one(1)Class Max SLC Standby 240µA
B circuit. The PAD100-SIM includes one red LED to indicate the Current
module's status.In normal condition,the LED flashes when the device Max SLC Alarm 240µA
is being polled by the control panel.When the input is activated,the Current
LED will flash at a fast rate. Max Wiring Resistance 100 c
of IDC
Application Max Wiring 1 F
Capacitance of IDC µ
The PAD100-SIM is compatible with Potter's IPA and AFC/ARC
series addressable fire alarm control panels. The PADl00-SIM is an EOL Resistor 5.1K S2
interface module used to monitor dry contact devices such as sprinkler Operating Temperature 32 to 120°F(0 to 49°C)
waterflow, valve tamper switches, or conventional pull stations. The
module is capable of monitoring one Class B circuit. Operating Humidity 0 to 93%(non-condensing)
Range
Setting the Address Max no.of Module Per 127 units
Each addressable SLC device must be assigned an address.The address Loop
is set using the DIP switch located on the PAD100-SIM. 4.17"(106mm)L x 4.17"
Dimensions (106mm)W x 1.14"(29mm)D
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device: Mounting Options Standard 4"Square or
I. Power to the device is removed. Double Gang Box
2. Field wiring is correctly installed. Shipping Weight 0.61bs
3. Field wiring has no open or short circuits.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830083-REV D • 12/18 PAGE 1 OF 2
P POTTER PAD100-SIM
The Symbol of Protection Single Input Module
Installation Using Compatible Electrical Box
Fig]
I
MEM
0tl ® i___,
0
fE. 1
® 0
\ 0I „ _ r �11.
I � ,j � l Wiring Diagram
PAD200-SIM With Class B Circuit
Fig 2
FROM FACP OR '
PREVIOUS MODULE \ I'I _
\ - , °
TO NEXT MODULE �{��)
® °
END-OF-LINE RESISTOR — — °
S.IKOHM Y W CL______Th.„ o °
Part#3005013 • l -
CDl 0 CD 6)
Ordering Information
Model Description Stock No.
PAD100-SIM Single Input Module 3992704
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830083-REV D • 12/18 PAGE 2 OF 2