Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report
OFFICE COPY fPS2022r- 000 f 3 llSG 4/2-6- -A/Re-4 Worldwide www.tyco-fire.com tqCO. RECEIVED JAN a 2922 Contacts y al or votio tuw 7.,IP1(3i or!lucti Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE a The TYCO Series TY-FRB Sprinklers Description described herein must be installed and maintained in compliance with The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the Upright (TY313) and Pendent (TY323) applicable standards of the National et •, Sprinklers described in this data sheet Fire Protection Association,in addition are quick response,standard coverage, to the standards of any other authori- ----- decorative 3 mm glass bulb-type spray ties having jurisdiction.Failure to do so •. sprinklers designed for use in light or may impair the performance of these ordinary hazard,commercial occupan- devices. � . cies such as banks, hotels, and shop The owner is responsible for main- . -- Z - ping malls. taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- applicable,is intended for use in areas tor or product manufacturer with any with a finished ceiling. This recessed questions. pendent sprinkler uses one of the following: Sprinkler k • A two-piece Style 15 Recessed Identification f�. - �, Escutcheon with recessed adjust 4 '4 .- ment up to 5/8 in. (15,9 mm) from '�, - .. �, the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT " c Escutcheon with recessed adjust ment up to 1/2 in. (12,7 mm) from TY323. . . .Pendent 5.6K, 1/2 in. NPT the flush pendent position. Technical The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Refer to Table A the rated temperature is reached, the Intermediate level versions of Series fluid expands sufficiently to shatter the TY-FRB Sprinklers are described in Maximum Working Pressure glass bulb, allowing the sprinkler to Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) activate and water to flow. kler guards and shields are described 250 psi(17.2 bar)* in Technical Data Sheet TFP780. .The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psi'%(80,6 LPM/bar'%) The TYCO Series TY-FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Always refer to Technical Data Finishes with the standard installation rules y Sprinkler:Refer to Table B recognized bythe applicable Listingor Sheet TFP700 for the "INSTALLER 9 PP WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and com- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations. to operate in a fire situation or cause Bulb Glass it to operate prematurely. Compression Screw Bronze Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 Page 2 of 4 9 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* I.'i7iT1 ii...` .\ 1\ 5 ���t [��. %/r//T T 1A1AC 7/16" Y I �s= (11,1 mm) pi 1fc4 NOMINAL 2" h MAKE-IN (50,8 mm) �, 2 oj 2" \I / 1-3/8" 3 �� (50,8 mm) 1 ) (I (34,9 mm) '�v / WRENCH 1 FLATS -_ r 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. - - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant �% applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the _ END"A") dance with this section. sprinkler fitting using only the W-Type '� General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE 2 Do not install any bulb-type sprin- erence to Figure 1,apply the W-Type 6 W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH a loss of liquid from the bulb.With the Torque sprinklers 7 to 14 lb-ft (9,5 to sprinkler held horizontally, a small air 19,0 N•m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor- 3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions. `�it temperature ratings. Step A. After installing the Style 15 A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the should be obtained by applying a sprinkler threads,and with pipe-thread minimum to maximum torque of 7 to sealant applied to the pipe threads, • t 14 lb-ft(9,5 to 19,0 N•m).Higher levels hand-tighten the sprinkler into the `�, of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairment Step B. Tighten the sprinkler into the PUSH WRENCH of the sprinkler. g p IN TO ENSURE sprinkler fitting using only the W-Type ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WRENCHING AREA eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m). W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and The Series TY-FRB Upright and finishing, slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. j pendent position. Install upright sprin- klers in the upright position. TFP172 Page 3 of 4 Care and _ 2-7/8" DIA. . (73,0 mm) Maintenance _ 2-1/4" DIA. _ The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. + \ FLUSH Before closing a fire protection system 3/8±5/16" 1`�7 L1` [I main control valve for maintenance (9,5±7,9 mm) work on the fire protection system } / that it controls, obtain permission to 1/8 MOUNTING j shut down the affected fire protection SURFACE (3,2 mm) systems from the proper authorities and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TY-FRB PLATE Absence of the outer piece of an FIGURE 4 escutcheon, which is used to cover a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only _ 2-7/8" DIA. _ cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER r 2-1/4" DIA. _ vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm) corrosion must be replaced. FLUSH Automatic sprinklers must never be ZZpainted, plated, coated, or other- wisewise altered after leaving the factory. } / /8" i Modified sprinklers must be replaced. MOUNTING (3,1 2 mm) Sprinklers that have been exposed to SURFACE corrosive products of combustion, but have not operated,should be replaced if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Limited Recessed Escutcheon be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has eon with(specify")finish,P/N(specify") lost liquid from its bulb. (Ref. Installa- Warranty Specify: Style 20 Recessed Escutch tion Section.) For warranty terms and conditions,visit eon with(specify")finish,P/N(specify") The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices Sprinkler Wrench in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order,indicate having jurisdiction.Contact the install- the full product name and Part Number ing contractor or product manufacturer (P/N). with any questions. Sprinkler Assemblies with NPT Automatic sprinkler systems are rec- Thread Connections ommended to be inspected, tested, Specify: Series TY-FRB Upright or and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN tion Service in accordance with local (specify), K=5.6, Quick Response, requirements and/or national codes. (specify) temperature rating, (specify) finish, P/N (specify,refer to Table A). A TFP172 Page 4 of 4 • SPRINKLER FINISH(See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY313) and 175°F(79°C) Yellow 1,2,3,4,5,6 PENDENT (TY323) 200°F(93°C) Green 5.6 286°F(141°C) Blue 1/2 in.NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4 (TY323) 175°F(79°C) Yellow Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable. c. Frame and Deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/Na 77 — XXX — X — XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS • 370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C) POLYESTER Notes: SIGNAL WHITE(RAL9003) a. Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C) 77-370-4-175-I 5 JET BLACK(RAL9005) 200 200°F 93°C POLYESTER ( ) 9 CHROME PLATED 286 286°F(141°C) Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 ,1►��� 02018 Johnson Controls.All rights reserved.All specifications and Other information shown were current as of document revision date and are subject to change without notice. Johnson ° NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Assocalion; Controls TEFLON is a registered trademark of DuPont f2S2022--0'0/ f(75Ce i w(4 RECEIVED tt.ICD JAN i 1 2922 Worldwide Fire Protection Contacts www.tyco-fire.com Cal Products BUIttnitiG D Ity.CN Series TY-B, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General NOTICE - The Series TY-B Sprinklers described '' -4--n Description herein must be installed and maintained ` " in compliance with this document, as The TYCO Series TY-B, 5.6 K-factor, well as with the applicable standards st Upright(TY315) and Pendent(TY325) of the National Fire Protection Associa- i Sprinklers described in this data sheet tion,in addition to the standards of any a are standard response,standard cover- other authorities having jurisdiction. age, decorative 5 mm glass bulb type Failure to do so may impair the perfor- spray sprinklers designed for use in mance of these devices. ""'` light, ordinary, or extra hazard, corn- mercial occupancies such as banks, The owner is responsible for maintain- hotels, shopping malls, factories, ing their fire protection system and -, -4= °& refineries,and chemical plants. devices in proper operating condition. The installing contractor or sprinkler The recessed version of the Series manufacturer should be contacted with TY-B Pendent Sprinkler, where appli- any questions. cable,is intended for use in areas with a ' 1 finished ceiling.This recessed pendent r�nkler sprinkler uses one of the following: Sp • A two-piece Style 15 Recessed Identification Escutcheon with recessed adjust- , t• , ,....,- ment up to 5/8 inch (15,9 mm)from Numbers (SINS) the flush pendent position. j • A two-piece Style 20 Recessed TY315 Upright 5.6K, 1/2"NPT \if Escutcheon with recessed adjust- TY325 Pendent 5.6K, 1/2"NPT ,;, ment up to 1/2 inch (12,7 mm) from the flush pendent position. Technical The adjustment provided by the Temperature Ratings Recessed Escutcheon reduces the Data 135°F(57°C) accuracy to which the fixed pipe drops 155°F(68°C) to the sprinklers must be cut. Approvals 175°F(79°C) UL and C-UL Listed 200°F(93°C) Intermediate level versions of Series FM, LPCB,and VdS Approved 286°F(141°C) TY-B Sprinklers are described in CE Certified 360°F(182°C)t Technical Data Sheet TFP352.Sprinkler guards and shields are described in Sprinklers with Polyester Finish are t UL,C-UL,and VdS Approved only Technical Data Sheet TFP780. UL and C-UL Listed as Corrosion- Resistant Sprinklers. Finishes Sprinkler:Refer to Table A Maximum Working Pressure Recessed Escutcheon:White Coated, 175 psi(12.1 bar) Chrome Plated,or Brass Plated 250 psi(17.2 bar)° *The maximum working pressure of 250 psi Physical Characteristics (17.2 bar)only applies to the listing by Un- Frame Bronze IMPORTANT derwriters Laboratories,Inc.(UL). Button Brass/Copper Always refer to Technical Data Discharge Coefficient Sealing Assembly Stainless Sheet TFP700 for the "INSTALLER g Steel w/TEFLON WARNING" that provides cau- K=5.6 GPM/psis 2(80,6 LPM/bars 2) Bulb Glass tions with respect to handling and Compression Screw Bronze installation of sprinkler systems and Deflector Bronze components. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP152 , TFP152 Page2of4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED - Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* I ter.... :'7;f1F PIO //rlrY m .:-. --- / �=5 7/16" Y �R- 5 �' - (11,1 mm) i•r 4 NOMINAL 12-11 2" ' , MAKE-IN (50,8 mm)IMF e P' �� 3 Aso 2" 1-3/8" �1 (50,8 mm) + (34,9 mm) `*' / ! ENCHATS 1/2"NPT** DEFLECTOR* F 2-7/8"(73,0 mm)DIA. . CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-B UPRIGHT(TY315)AND PENDENT(TY325)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE Operation Installation The glass bulb contains a fluid which The TYCO Series TY B, 5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY315)and Pendent(TY325) (USE ONLY the rated temperature is reached,the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss of SPRINKLER WRENCH Design liquid from the bulb.With the sprinkler held horizontally, a small air bubble WRENCH Criteria should be present.The diameter of the air bubble is approximately 1/16 inch RECESS The TYCO Series TY-B, 5.6 K-factor, (1,6 mm) for the 135°F(57°C) to 3/32 Upright(TY315)and Pendent(TY325) inch (2,4 mm) for the 360°F (182°C) �,� Sprinklers are intended for fire protec- temperature ratings. tion systems designed in accordance with the standard installation rules A leak tight 1/2 inch NPT sprinkler recognized by the applicable Listing joint should be obtained by applying a or Approval agency (e.g., UL Listing minimum-to-maximum torque of 7 to 14 Sr is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels �.., 13, and FM Approval is based on the of torque may distort the sprinkler inlet PUSH WRENCH requirements of the FM Loss Preven- and cause leakage or impairment of the tion Data Sheets). Only the Style 15 sprinkler. IN TO ENSURE or Style 20 Recessed Escutcheon,as ENGAGEMENT y Do not attempt to compensate for WITH SPRINKLER applicable, is to be used for recessed insufficient adjustment in the escutch- WRENCHING AREA pendent installations. eon plate by under-or over-tightening FIGURE 3 the sprinkler. Readjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-B Upright and Pendent Sprinklers must be installed in accor- dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position; install upright sprinklers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. { TFP152 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8" DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench (Figure 2). With reference to Figure 1,apply the W-Type 2-1/4" DIA. 6 Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm) Torque sprinklers 7 to 14 ft.-lbs. (9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers \ _, i FLUSH The Series TY-B Recessed Pendent 3/8±5/16" Sprinklers must be installed in accor- (9,5±7,9 mm) ,1;%� .2 'r dance with the following instructions. ' �`�` OrStep A.After installing the Style 15 or MOUNTING 1/8 i _1i Style 20 Mounting Plate,as applicable, SURFACE (3,2 mm) over the sprinkler threads and with pipe-thread sealant applied to the pipe CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) threads,hand-tighten the sprinkler into TY-B PLATE 3/4"(19,1 mm) the sprinkler fitting. FIGURE 4 Step B.Tighten the sprinkler into the SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) sprinkler fitting using only the W-Type WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8" DIA. - sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After the ceiling is installed or SPRINKLER _ 2-1/4" DIA. - - the finish coat is applied, slide on the FITTING (57,2 mm) Style 15 or Style 20 Closure over the 5/16±1/4" Series TY-B Sprinkler and push the (7,9±6,4 mm) 1/2"(12,7 mm) Closure over the Mounting Plate until + FLUSH its flange contacts the ceiling. ,7- ✓' Care and -I / -Z-7 1/8" MOUNTING Maintenance SURFACE (3,2 mm) The TYCO Series TY-B, 5.6 K-factor, Upright(TY315) and Pendent(TY325) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-B PLATE 7/8'1(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) main control valve for maintenance WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. The owner is responsible for the system from the proper authorities Sprinklers that have been exposed to inspection,testing,and maintenance of and notify all personnel who may be corrosive products of combustion, but their fire protection system and devices affected by this action. have not operated,should be replaced in compliance with this document, as Absence of the outer piece of an if they cannot be completely cleaned by well as with the applicable standards escutcheon, which is used to cover wiping the sprinkler with a cloth or by of the National Fire Protection Associa- a clearance hole, can delay sprinkler brushing it with a soft bristle brush. tion (e.g., NFPA 25), in addition to the operation in a fire situation. Care must be exercised to avoid dam- standards of any other authorities hav- ing age to the sprinklers - before, during, jurisdiction. Contact the installing The owner must assure that the and after installation. Sprinklers dam contractor or sprinkler manufacturer sprinklers are not used for hanging aged by dropping, striking, wrench regarding any questions. any objects and that the sprinklers are twist/slippage, or the like, must be Automatic sprinklers are recommended only cleaned by means of gently dust replaced. Also, replace any sprinkler to be inspected,tested,and maintained ing with a feather duster; otherwise, that has a cracked bulb or that has lost by a qualified Inspection Service in non operation in the event of a fire or liquid from its bulb. (Ref. Installation accordance with local requirements inadvertent operation may result. Section.) and/or national codes. Sprinklers which are found to be leak Thereafter, annual inspections per ing or exhibiting visible signs of corro NFPA 25 are required;however, instead sion must be replaced. of inspecting from the floor level, a Automatic sprinklers must never be random sampling of close-up visual painted, plated, coated, or otherwise inspections should be made. altered after leaving the factory. TFP152 Page 4 of 4 P/N* 77 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 570 5.6K UPRIGHT(1/2-NPT) TY315 1 NATURAL BRASS 135 135°F(57°C) 571 5.6K PENDENT(1/2"NPT) TY325 3 PURE WHITE(RAL9010)" 155 155°F(68°C) POLYESTER Use suffix"I"for ISO 7-1 connection; SIGNAL WHITE(RAL9003) for example,77-570-4-175-I 4 POLYESTER 175 175°F(79°C) 9 CHROME PLATED 200 200°F(93°C) "Eastern Hemisphere sales only 286 286°F(141°C) 360 360°F(182°C) 000 OPEN*** "'OPEN indicates sprinkler assembly without Glass Bulb, Button,and Sealing Assembly TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-B Upright or Pen- dent(specify) Sprinkler,SIN (specify), K=5.6, Standard Response, (specify) temperature rating,(specify)finish, P/N (specify,refer to Table A) Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify')finish, P/N(specify*) Specify:Style 20 Recessed Escutcheon with(specify')finish, P/N(specify*) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. tycc TEFLON is trademark of The DuPont Corporation. Fire Protection Products