Report (3) t f(o y P/tG!FcC f7 NI &C2O22--o a O 2c,f
Unit Report For 48TC-7.5T-D-3PH RE
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
Go i
,$aARD
BURLDNG
Unit Parameters Dimensions (ft.in.)&Weight(Ib.)***
Unit Model. 48TCDDO8A2A5-0A0G0 Unit Length• 7'4.125"
Unit Size. 08(7.5 Tons) Unit Width. 4' 11.5"
Volts-Phase-Hertz. 208-3-60 Unit Height. 3'5.25"
Heating Type• Gas ••* Total Operating Weight. 870 lb
Duct Cfg• Vertical Supply/Vertical Return
Low Heat `'* Weights and Dimensions are approximate. Weight does
Round Tube Plate Fin Coils not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Gas Line Size- 1/2
Condensate Drain Line Size• 3/4
Return Air Filter Type• Throwaway
Return Air Filter Quantity 4
Return Air Filter Size• 16 x 20 x 2
Unit Configuration
Medium Static Option (Belt Drive)
Al/Cu -Al/Cu
Base Electromechanical Controls
Standard Packaging
2-Speed indoor fan motor controlled by VFD
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
• 10-Year heat exchanger-Aluminized(std.)
15-Year heat exchanger-Stainless Steel(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48TCDDO8A2A5-0A0G0 Rooftop Unit 1
Base Unit
Medium Static Option (Belt Drive)
Electromechanical control, No intake or exhaust option.
2 Speed Fan Controller (VFD)
Packaged Rooftop Builder 1.49n Page 1 of 7
Certified Drawing for 48TC-7.5T-D-3PH -
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
NOTES: UNITED P.O.BOY MBDB THIS DOCUMENT IS THE PROPERTY OF CARRIER CORPORATION
UNIT OUTDOOR 6 H TECHNOLOGIES SYRACUSE.NY AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE SUBMISSION OF THESE DRARIROS OR DOCUMENTS
1. DIMENSIONS ARE IN INCHES. DIMENSIONS COIL TYPE CONTENTS WILL MOT BE DISCLOSED OR USED WITHOUT CARRIER DOES NOT CONSTITUTE PART PENFODRANCf OR
IN [ I ARE IN MILLIMETERS. 41 1/4 33 15 1/8 CARRIER uzzl CORPORATION'S WRITTEN CONSENT.
ACC fPTAMCC OF COYTRACT.
2. CENTER OF GRAVITY 48TC-A08 RTPF [10481 [658] 14031
48TC-A09 RTPF 49 3/8 37 1/401 7/8 CONNECTION SIZES
[12531 [9461 [708) A 1 3/8' [351 DIA FIELD POWER SUPPLY HOLE
3. *DIRECTION OF AIR FLOW 40-3/8
4DEC-Al2 RTPF 49 3/B 37 114 15 7/B
[1253] [946] [403] [1026] B 2 1/Z' [61] DIA POWER SUPPLY KNOCKOUT
41 1/4 33 15 7/8
48TC-D08 RTPF C 1 3/4' [51] DIA GAUGE ACCESS PLUG
[1048] [6581 [4D3] , ,
IBTC-D09 RTPF 49 3/8 37 1/4 15 7/8 D 7/8' 1221 DIA FIELD CONTROL WIRING HOLE
[1253] [9461 1403]
20-3/4 E 3/1"-14 NPT CONDENSATE DRAIN
49 3/6 37 1// 15 7/B ECONOMIZER H000 F 1/2'-14 NPT GAS CONNECTION
48TC-D12 RIPE (12531 [9/61 [403] • (OPTIONAL) • [527] 3/4'-14 NPT GAS CONNECTION
48TC-008 NCH% 1 1/4 33 23
[14048] [6561 [584.2] G 2' [511 DIA POWER SUPPLY KNOCK-OUT
48TC-D12 NCH% [1253 49 8 [946137 4 [279.41 '' '
I~ _S. THRU-THE-BASE CHART (FIELD INST)
RTPF-ROUND TUBE, PLATE FIN )COPPER/ALUM)
NCH-NOVATION [ALUM/ALUM/ \\\\\\\\ I THESE HOLES REQUIRED FOR USE WITH ACCY NITS:
I([IIIIf��( `111'1 [92518 �3zj/B 1M CRBTMPWROD4A01: GAS THRU CURB
CRBTMPWAOOIA01: GAS THRU BASEPAX
• w1 ���®� I RETURN AIR RETURN
1V �� _ _ .. AIR THREADED WIRE RED'D HOLE
__ \� � L CONDUIT1 SIZE USE SIZES (MAX./
D 11110 _ ��— W 1/2" ACC. 7/8' [22.2]
FILTER ACCESS PANEL % 1/2' 24V 7/8' [22.2]
(TOOL-LESS) n E ALT. ,
\ CONDENSATE Y 1 1/4" (002,0041 POWER 1 3/4" [44.4]
COIL ��% -\;\1`DAA IN OPENING 28-3/4
CONDENSER /jam'�\'; IN BASEPAX [7311 37-5/8 40-3/8 Z N (DOC 3/4' FPT GAS 1 3/4' [44.4]
• W SUPPLY [9551 [10271
1141i:1A m LY,lllill SEE THRU AIR (0021 PROVIDES 3/4' FPT THRU CURB
INDOOR COIL 1 - \\\\\\\_-- /i/////// % SUPPLY N
ACCESS PANEL \ ��,`=. � Y THE BASE AIR FLANGE 4 FITTING. HOLE SIZE: 2' [50.81
���� - A' CHART
BACK 18 6 ;` 2
14691 Ig12] tq 11 L -�- ____I THRU-THE-BASE CHART (FIOP)
[355]
4v 1218]
tr.'.v - —�- -{ - - UU N
tT[y F 1- ✓!R FOR 'THRU-THE-BASEPAN"FACTORY OPTION,A F FITTINGS FOR ONLY I. Y. 2 ARE PROVIDED. NN
• } FOR BELOW LISTED MODELS. A FIELD
L 6-1/4 SUPPLIED 1/2" ADAPTER IS REOUIRED
--29 SIB [100] LUE 74 [1591 WA BETWEEN BASE PAN FITTING AND GAS VALVE:
[7511 HOOD y 14 [831 48HCD,S008
[3561
TOP „25-1/2
[647]
H 1-1/4
[321 11-7/8
4-5l8 [302]
11181
1---i
LECTRICAL CONTROL BOX DISCONNECT E$TDI I TITER
IL A. �+� LOCATION ACCESS PANEL
CONDENSER G, I CONDENSATE
DRAIN
OPTIONAL ® ACCESSOO BLOWER
,I
11010 FACTORY _____
OPTIONAL •� INSTALLED
FACTORY 27-TIB 21_3/4 OUTSIDE
INSTALLED [1-1) • DISCONNECT \ AIR
CONVENIENCE C l.. F
HANDLE 13-1/8 [706] 26
OUTLET [334] - SUPPLY AIR [659]
•I HANDLE-�� J�s
-__-.-Eli _ II 6-5/B - __
"68] 1• ti 6 1/8 __ _•
�.
3-3/4 6-5/8 7
[951 59-1/2 2-5/8 8-3/B [1671 [177] 6-1/B /-3/8
[1510] [671
37 12141
TIP 37-7/8 [1551 [113]
[9401 [9621
42-3/8
LEFT WIDTTH 88-1/8 .. [10751 BAROMETRIC
[22381 SUPPLY * RETURN RELIEF
AIR AIR FLOW
FRONT RIGHT
INERT DATE SUPCRCEDES 48TC 08-12 SINGLE ZONE ELECTRICAL REV
48TM500985
1OF2 03-08-10 11-24-08 COOLING WITH GAS HEAT F
Packaged Rooftop Builder 1.49n Page 2 of 7
Certified Drawing for 48TC-7.5T-D-3PH
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
40 UNITED P.O.BOY 4800 THIS DOCUMENT IS THE PROPERTY Of CARRIE!CORPORATION SUBMISSION OF THESE DRAWINGS OR DOCUMENTS
TECHNOLOGIES SYRACUSE,n AND IS OE LIVERED UPON THE EIPAE3S CORGI TIOX THAT THE DOES NOT CONSTITUTE PART PERFORMANCE OR
STD. UNIT CORNER CORNER CORNER CORNER CARRIER 1322t CONTEXTS MIEE MDT BE 014CLOSFO OR USED YITNOUT CARRIER ACCEPTANCE Of CONTRACT.
UNIT OUTDOOR WEIGHT RNP WEIGHT IAl WEIGHT IBl WEIGHT ICI WEIGHT IDI C.G. COAPORAiIOX'3 RR[TTEN COXSCMi.
COIL TYPE LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z
48TC-A08 RTPF 780 354 118 81 158 72 209 95 236 107 41 1/2 [10541 33 7/8[8601 20 1/2 [521] vox STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
48TC-A09 RTPF 920 418 212 96 183 83 243 110 282 128 40 7/8[1038] 34 [864] 23 1/8 [587] FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
48TC-Al2 RTPF 930 422 216 98 196 89 _ 241 112 272 123.5 42 MOM 33 1/8[841] 24 1/4 [616]
48TC-D08 RTPF 835 379 164 74.5 110 77.2 255 115.8 246 111.7 44 7/8 [1140] 35 5/8[9051 19 3/8 [4921
48TC-009 RTPF 930 422 228 103.5 187 85 232 105.3 283 128.5 39 3/4 [10101 32 7/8[8351 18 5/8[473]
48TC-012 RTPF 940 421 231 104.9 189 85.8 234 106.2 286 129.8 39 3/4 11012] 33 [838] 18 1/2 [470]
48TC-008 MCHX 805 365.5 160 72.6 153 69.5 240 109 260 118 43[1092] 36 3/8 [9241 20 3/8 [517.7]
48TC-012 MCHX 895 406.3 185 84 176 79.9 260 118 214 124.4 42 7/8[10891 35 1/2 [9021 22 7/8[581]
RTPF -NCH% - ROUND TUBE,
IALUM/ALUMI B PLATE N (COPPER/ALUM) CORNER A
NOVA CORNER B
r .-....
•
Wiz,
R ..R
CORNER D _ CORNER C
TOP
- X
g •
pr.
O ED
Cj00 `='1' .. , ii : : 00
FRONT
SHEET DATE. SUPERCEOES 48TC 08-12 SINGLE ZONE ELECTRICAL REP
1 20F2 03-08-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F
Packaged Rooftop Builder 1.49n Page 3 of 7
Certified Drawing for 48TC-7,5T-D-3PH
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
Service Clearance
,Z
\s�/ i
1
C1124i
LOCATION DIMENSION CONDITION _
48-in(1219 mm) •Unit disconnect is mounted on panel
36-in(914 mm) •If dimension-8 is 12-in(305 mm)
A 18-in(457 mm) •No disconnect,convenience outlet option
•Recommended servicedearance(use electric screwdriver)
12-in(305 mm) •Minimum clearance(use manual ratchet screwdriver)
36-in(914 mm) •Unit has economizer
8 12-in(305 mm) •if dimension-A is 36-in(914 mm)
Special •Check for sources of flue products within 10-ft of unit fresh air intake hood _
C 36-in(914 mm) •Side condensate drain is used
18-in(457 mm( •Minimum clearance
48-in(1219 mm) •No flue discharge accessory installed,surface is combustible material
42-in(1067 mm) •Surface behind servicer Is grounded(e.g.,metal,masonry wall,another unit)
D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for adjacent units or!wilding fresh air intakes within 10-ft of this units
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
Packaged Rooftop Builder 1.49n Page 4 of 7
Performance Summary For 48TC-7.5T-D-3PH
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
Part Number:48TCDDO8A2A5-0A0G0
ARI EER. 11.00
IEER• 12.8
Base Unit Dimensions
UnitLength:_.........___.......___._.........__......._._.__._._......._........_...__.......__ 88.1 in
Unit Width _ _ _..................-•......--..........-•.... — ----- — 59.5 in
Unit Height• _ 41.3 in
Operating Weight
Base Unit Weight _.._...__._.__._.__ 835 lb
Medium Static Option (Belt Drive)• 15 lb
2 Speed Fan Controller (VFD)• _ 20 lb
Total Operating Weight _____ 870 lb
Unit
Unit Voltage-Phase-Hertz. 208-3-60
Air Discharge. Vertical
Fan Drive Type• Belt
Actual Airflow• _ — 3000 CFM
Site Altitude. 39 ft
Cooling Performance
Condenser Entering Air DB• 90.0 F
" Evaporator Entering Air DB• _ 78.0 F
Evaporator Entering Air WB• 64.4 F
Entering Air Enthalpy. 29.49 BTU/lb
• Evaporator Leaving Air DB. 56.2 F
Evaporator Leaving Air WB• 54.6 F
Evaporator Leaving Air Enthalpy. 22.93 BTU/lb
Gross Cooling Capacity. 88.40 MBH
Gross Sensible Capacity. _ 70.45 MBH
Compressor Power Input _ 5.97 kW
Coil Bypass Factor• _ 0.104
Mixed Air
Outdoor Air Airflow• 420 CFM
Outdoor Air DB. _ 90.0 F
Outdoor Air WB. — 67.0 F
Outdoor Air Htg.Temp.: 22.0 F
Return Air DB• — 76.0 F
Return Air WB —__.______._ 64.0 F
Return Air Htg.Temp • 70.0 F
Heating Performance
Heating Airflow:__._______ 3000 CFM
Entering Air Temp• _ 63.3 F
Leaving Air Temp. 95.1 F
Gas Heating Input Capacity. — 125.0 MBH
Gas Heating Output Capacity. 103.0 MBH
Temperature Rise. — 31.8 F
Thermal Efficiency(%). 82.0
Supply Fan
External Static Pressure. _ 0.60 in wg
Fan RPM. 761
• Fan Power. 1.64 BHP
NOTE- Selected IFM RPM Range: 733-949
Electrical Data
Packaged Rooftop Builder 1.49n Page 5 of 7
Performance Summary For 48TC-7.5T-D-3PH
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
Voltage Range. 187-253
' Compressor#1 RLA:_________.__ 13.6
. Compressor#1 LRA• 83
Compressor#2 RLA• 13.6
Compressor#2 LRA• _ 83
Indoor Fan Motor Type• MED
Indoor Fan Motor FLA• 8.4
Combustion Fan Motor FLA(ea)• 0.48
Power Supply MCA• 43
Power Supply MOCP(Fuse or HACR)• 50
Disconnect Size FLA• 45
Disconnect Size LRA• 227
Electrical Convenience Outlet. None
Outdoor Fan [Qty/FLA(ea)]. 2/1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 98.2 95.2 85.8
125 Hz 91.4 86.0 84.3
250 Hz 77.9 73.0 80.5
500 Hz 70.7 66.3 78.7
1000 Hz 67.1 63.3 76.4
2000 Hz 65.7 58.5 72.7
4000 Hz 67.1 57.8 68.3
8000 Hz 69.3 57.4 65.1 I
•
A-Weighted 79.4 74.3 82.0
Advanced Acoustics
ti
t 0 i
O4., 0 i_
... 3.
0 1/4"
Advanced Accoustics Parameters
1. Unit height above ground. 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground- 5.7 ft
4. Height of obstruction• 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction- 0.0 ft
. Detailed Acoustics Information
• Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
Packaged Rooftop Builder 1.49n Page 6 of 7
Performance Summary For 48TC-7.5T-D-3PH
Project: Stock Units 2019 03/04/2019
Prepared By: 10:30AM
A 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1 89.6 Lw
B 59.6 68.2 71.9 75.5 76.4 73.9 69.3 64.0 81.4 LwA
C 53.4 51.9 48.1 46.3 44.0 40.3 35.9 32.7 57.2 Lp
D 27.2 35.8 39.5 43.1 44.0 41.5 36.9 31.6 49.0 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space,an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Fan Curve
2.0 0 RP,A 1000 PM
1100 RP 1 0 RPM
1.8 `\\
800 RPM
1.6
1.4
- 700 RPM
1.2 _ 5 on•,4=+
y 1.0
a_ -.0
AIL
41111111.11
500 RPM
0.6
-"111111
11WX-6\
400 RPM
0.4 -` 1 .
3.00 BH'
\2..
E0.2 1.50 ,
BHP `I .\
a BHP 5 BHP
00 I I III
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4
Airflow(CFM-thousands)
RPM=761 BHP= 1.64 Maximum RPM= 1400 Maximum BHP=4.70
Note:Please contact application engineering for selections outside the shaded region.
SC-System Curve RP-Rated Point
Packaged Rooftop Builder 1.49n Page 7 of 7