Report OW2O2/-00z53
q1 % 141ti- IL-VD)/Oo
(1.4 COMcheck Software Version COMcheckWeb
Interior Lighting Compliance Cer '.; -
c5 <4. GINte ir
to
Project Information II 531` 1 P: ;
Energy Code: 90.1 (2019) Standard E , (I I
Project Title: T0345 TIGARD OR - ELECTRICAL COMPLIANCE 0'% 4)-09, ri.O Q,^
Project Type: Alteration 'pIALAN 1
10/05/2021
EXPIRES:12.31.2022
Construction Site: Owner/Agent: Designer/Contractor:
9009 SW HALL BLVD
TIGARD, Oregon 97223
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed
(ft2) Watts /ft2 Watts
1-ACC LOUNGE 189 (Common Space Types:Lounge/Breakroom) 150 0.59 88
2-ROOMS 127,190,191,192 (Common Space Types:Storage >=50- <=1000 1396 0.43 600
sq.ft.)
3-ROOMS 107,126,133,145,188(Common Space Types:Storage>=1000 14523 0.38 5519
sq.ft.)
4-ALL SALES FLOOR(Retail:Sales Area) 92875 1.05 97519
Allowance: Furniture, clothing, cosmetics highlighting/Fix. ID:Track 33800(a) 1.05 2400(b)
Allowance:Jewelry, crystal, china highlighting/Fix. ID: Track Lighting 830(a) 1.88 1560(b)
Allowance: Vehicles, sporting goods, small electronics highlighting/Fix. 8150(a) 0.45 3668(b)
ID: Al
5-COFFEE SEATING 178 (Common Space Types:Dining Area-General) 634 0.43 273
6-COFFEE 186,187 (Common Space Types:Food Preparation) 595 1.09 649
7-GUEST SVC 111 (Common Space Types:Lobby-General) 438 0.84 368
Supplemental Allowed Watts(null) = 1000
Total Allowed Watts = 113643
(a)Area claimed may exceed total floor area when Retail Merchandise Highlighting allowance(s) are specified.
(b)Allowance is (B x C) or the actual wattage of the fixtures g given in Proposed Power section, whichever is less.
(c)Supplemental watts must be associated with retail merchandise highlighting fixtures.
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp/Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
ACC LOUNGE 189 (Common Space Types: Lounge/Breakroom. 150 sq.ft.)
LED: A9L6: 4" OPEN RECESSED LINEAR, 6FT: Other: 1 3 33 99
ROOMS 127,190,191.192 (Common Space Types: Storage >=50 - <=1000 sq.ft.. 1396 sq.ft.)
Linear Fluorescent: C2: 4' STRIP, STOCK(ETR& RELO): 48"T8 32W: Electronic: 1 2 31 62
Linear Fluorescent: C3: 8' STRIP, STOCK(ETR& RELO): 48"T8 32W: Electronic: 2 10 59 590
LED: C2L: 4' LED STRIP(STOCK ROOMS): Other: 1 3 25 75
LED: C13: 4' LED WET LOCATION (WALK-INS): Other: 1 12 33 396
ROOMS 107,126,133,145.188 (Common Space Types: Storage >=1000 sq.ft., 14523 sq.ft.)
Linear Fluorescent: C2: 4' STRIP, STOCK(ETR& RELO): 48"T8 32W: Electronic: 1 5 31 155
Linear Fluorescent: C3: 8' STRIP, STOCK(ETR& RELO): 48"T8 32W: Electronic: 2 141 59 8319
LED: C1L: 4' LED STRIP(CONVEYORS): Other: 1 2 25 50
LED: C2L: 4' LED STRIP(STOCK ROOMS): Other: 1 1 25 25
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 1 of 7
COMcheck Software Version COMcheckWeb
Exterior Lighting Compliance Certificate
Project Information
Energy Code: 90.1 (2019) Standard
Project Title: T0345 TIGARD OR - ELECTRICAL COMPLIANCE
Project Type: Alteration
Exterior Lighting Zone 4 (High activity metropolitan commercial district (LZ4))
Construction Site: Owner/Agent: Designer/Contractor:
9009 SW HALL BLVD
TIGARD, Oregon 97223
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts / Wattage (B X C)
GPU 4' DRIVE UP DOOR(Drive-up windows/doors) 1 windows 200 No 200
Total Tradable Watts(a) = 0
Total Allowed Watts = 200
Total Allowed Supplemental Watts(b) = 900
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 900 watts may be applied toward compliance of both non-tradable and tradable
areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp/Wattage Per Lamp/ Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
GPU 4' DRIVE UP DOOR (Drive-up windows/doors. 1 windows or doors): Non-tradable Wattage
LED: H7: LED ARCH WALLPACK: Other: 1 1 45 45
Total Tradable Proposed Watts = 0
Exterior Lighting PASSES
Exterior Lighting Compliance
Statement
Compliance Statement: The proposed exterior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application.The proposed exterior lighting
systems have been designed to meet the 90.1 (2019)Standard requirements in COMcheck Version COMcheckWeb and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
L'i4v!/U i✓,<niv ' — zLecp"R1CA1 O/o„ "/= -o.2/
Name-Title rr4i) Signature Date
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 3 of 7
A B C D E
Fixture ID : Description / Lamp/ Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
LED: C3L: 8' LED STRIP(STOCK ROOMS): Other: 1 24 49 1176
ALL SALES FLOOR (Retail: Sales Area. 92875 sq.ft.)
Track Lighting: Track:A&A TRACK: Wattage based on circuit breaker capacity 0 0 2400 2400
(2e+01 amps x 1e+02 volts)
Track Lighting:A&A TRACK: Wattage based on circuit breaker capacity(2e+01 0 0 2400 2400
amps x 1e+02 volts)
Track Lighting:A&A TRACK: Wattage based on circuit breaker capacity (2e+01 0 0 2400 2400
amps x le+02 volts)
Track Lighting: A&A TRACK: Wattage based on circuit breaker capacity (2e+01 0 0 2400 2400
amps x 1e+02 volts)
Track Lighting:A&A TRACK: Wattage based on circuit breaker capacity (2e+01 0 0 2400 2400
amps x le+02 volts)
Track Lighting: A&A TRACK: Wattage based on circuit breaker capacity (2e+01 0 0 2400 2400
amps x 1e+02 volts)
Track Lighting: A&A TRACK: Wattage based on circuit breaker capacity(2e+01 0 0 2400 2400
amps x le+02 volts) 1
Track Lighting: A&A TRACK: Wattage based on circuit breaker capacity (2e+01 0 0 2400 2400
amps x le+02 volts)
Track Lighting: BEAUTY TRACK: Wattage based on circuit breaker capacity(2e+01 0 0 2400 2400
amps x 1e+02 volts)
Track Lighting: BEAUTY TRACK: Wattage based on circuit breaker capacity(2e+01 0 0 2400 2400
amps x le+02 volts)
LED: Sil: CUSTOM LED PENDANT: Other: 1 3 100 300
LED: D14: 6" LED DOWNLIGHT: Other: 1 11 49 539
LED: RP8: 8' DECO RING PENDANT: Other: 1 2 125 250
LED: RP12: 12' DECO RING PENDANT: Other: 1 1 188 188
LED: Al: 2x4 RECESSED LED RETROFIT(ETR):Other: 1 789 59 46551
LED: SP10: 6' BUSSTRUT LINEAR LED: Other: 1 6 16 96
LED: SP20: 20' PENDANT LINEAR LED, LUXBEAM: Other: 1 6 200 1200
LED: VL2: FOCAL DOWN FIXTURE: Other: 1 76 50 3800
LED: VL3: GONDOLA DOWN LIGHT FIXTURE: Other: 1 133 30 3990
LED: VL4: GONDOLA UP LIGHT FIXTURE: Other: 1 162 30 4860
LED: VL5: COOLER UP LIGHT FIXTURE: Other: 1 35 30 1050
Track Lighting: MARKET TRACK: Wattage based on circuit breaker capacity(2e+01 0 0 2400 2400
amps x le+02 volts)
COFFEE SEATING 178 (Common Space Types: Dining Area - General, 634 sq.ft.)
LED: D14: 6" LED DOWNLIGHT: Other: 1 15 49 735
LED: D17: 6" LED DOWNLIGHT: Other: 1 1 26 26
COFFEE 186,187 (Common Space Types: Food Preparation. 595 sq.ft.)
LED: B2L: 2X4 RECESSED LED: Other: 1 5 40 200
LED: D17: 6" LED DOWNLIGHT: Other: 1 11 26 286
Track Lighting:T2H2 &Tl: STARBUCKS TRACK: Wattage based on 16 feet of track 0 0 480 480
GUEST SVC 111 (Common Space Types: Lobby - General. 438 sq.ft.)
LED: B2L: 2X4 RECESSED LED:Other: 1 6 40 240
LED: SR1B: 4" RECESSED LINEAR LED WALL WAS: Other: 1 3 40 120
Total Proposed Watts = 102258
Interior Lighting PASSES
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans,specifications, and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 90.1 (2019) Standard requirements in COMcheck Version COMcheckWeb and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
1)4 v/0 N4iv/vE - E tecrR/eq L
Name-Title LEAD Signature Date
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 2 of 7
COMcheck Software Version COMcheckWeb
Inspection Chec
Energy Code: 90.1 (2019) Standard klist
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.lD
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
8.4.1.1, calculations provide all information ODoes Not
8.4.1.2, with which compliance can be
8.7 determined for the electrical systems ONot Observable
[PR6]z and equipment and document where ONot Applicable
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
4.2.2, :Plans, specifications, and/or ❑Complies Requirement will be met.
9.4.3, 9.7 i calculations provide all information ❑Does Not
[PR4]1 ;with which compliance can be
determined for the interior lighting Not Observable
:and electrical systems and equipment ONot Applicable
and document where exceptions to
:the standard are claimed. Information
;provided should include interior
lighting power calculations, wattage of
;bulbs and ballasts,transformers and
i control devices.
9.7 Plans,specifications,and/or ❑Complies Requirement will be met.
(PR8]i calculations provide all information DDoes Not
;with which compliance can be
;determined for the exterior lighting ONot Observable
and electrical systems and equipment ONot Applicable
:and document where exceptions to
:the standard are claimed. Information
;provided should include exterior
lighting power calculations, wattage of
:bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 4 of 7
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
8.4.2 At least 50%of all 125 volt 15-and ❑Complies Exception: Space type is not private office, open office, or
[EL10]2 20-Amp receptacles are controlled by ODoes Not computer classroom.
an automatic control device.
,ONot Observable
❑Not Applicable
8.4.3 New buildings have electrical energy ❑Complies Exception: Requirement does not apply.
[EL11]2 use measurement devices installed. ❑Does Not
Where tenant spaces exist, each
tenant is monitored separately. In ONot Observable
buildings with a digital control system ONot Applicable
the energy use is transmitted to to
control system and displayed
graphically.
9.4.1.1 Automatic control requirements ❑Complies Requirement will be met.
[EL1]2 prescribed in Table 9.6.1,for the DDoes Not
appropriate space type, are installed. ONot Observable Location on plans/spec: See E161 for sensor types.Sales
Mandatory lighting controls(labeledfloor lighting controlled via EMS.
as'REQ')and optional choice controls ❑Not Applicable
(labeled as'ADD1' and 'ADD2') are
implemented.
9.4.1.1a Independent lighting controls installed ❑Complies 'Requirement will be met.
[EL2]2 per approved lighting plans and all ❑Does Not
manual controls readily accessible and
visible to occupants. ['Not Observable
ONot Applicable ,
9.4.1.1b No lighting shall be automatically DComplies Exception: Manual on function would endanger safety and
[EL2612 turned on-restriced to manual. ODoes Not security.
ONot Observable
ONot Applicable
9.4.1.1c <= 50%of general lighting power ❑Complies Requirement will be met.
[EL27]2 shall be allowed to be automatically ❑Does Not
turned on.
ONot Observable
ONot Applicable
9.4.1.1d Bilevel lighting control-<= 50%of ❑Complies Requirement will be met.
(EL28]2 general lighting controlled with one ODoes Not
intermediate step between full off and
full on. ❑Not Observable
ONot Applicable
9.4.1.1e Automatic daylight responsive ❑Complies Exception: Retail lighting.
[EL29]2 controls for sidelighting >= 150 watts ODoes Not
controlled by photocontrols.
['Not Observable
O Not Applicable
9.4.1.1f Automatic daylight responsive ❑Complies Exception: Requirement does not apply.
[EL30]2 controls for toplighting >= 150 watts ODoes Not
controlled by photocontrols.
ONot Observable
❑Not Applicable
9.4.1.1g Automatic partial OFF: lighting shall ❑Complies Requirement will be met.
[EL31]2 be reduced >= 50%within 20 minutes ODoes Not
of zero occupancy.
ONot Observable
O Not Applicable
9.4.1.1h Automatic full OFF: lighting shall be ❑Complies Requirement will be met.
[EL32]2 shut off within 20 minutes of zero ODoes Not
occupancy.
[Not Observable
ONot Applicable
9.4.1.1i Scheduled shutoff: all lighting shall be ❑Complies Exception: Lighting in spaces where automatic shutoff would
[EL33]2 shut off when scheduled to be ODoes Not endanger the safety or security of the room or building
unoccupied. occupants.
❑Not Observable
ONot Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 5 of 7
.. w
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.lO
9.4.1.3 Separate lighting control devices for ❑Complies Requirement will be met.
[EL4]1 specific uses installed per approved `❑Does Not
lighting plans. ['Not Observable
DNot Applicable
9.4.1.4 Automatic lighting controls for exterior,❑Complies Requirement will be met.
[EL3]2 lighting installed. ❑Does Not
❑Not Observable
:0Not Applicable
9.6.2 Additional interior lighting power DComplies Requirement will be met.
[EL8]1 allowed for special functions per the ODoes Not
approved lighting plans and is
automatically controlled and ❑Not Observable
:separated from general lighting. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 6 of 7
a
Section
Final Inspection Complies? Comments/Assumptions
& Req.ID
8.7.1 Furnished as-built drawings for ❑Complies Requirement will be met.
[FI16]3 electric power systems within 30 days ❑Does Not
of system acceptance. ONot Observable
❑Not Applicable
8.7.2 Furnished O&M instructions for ;❑Complies Requirement will be met.
[FI17]3 systems and equipment to the ❑Does Not
building owner or designated ONot Observable
representative.
ONot Applicable
9.2.2.3 Interior installed lamp and fixture OComplies See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
?plans, demonstrating proposed watts ONot Observable
are less than or equal to allowed ONot Applicable
watts.
9.4.2 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[FI19)1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal ONot Observable
to allowed watts. ❑Not Applicable
I # 4
9.4.4 At least 75%of all permanently ❑Complies Exception: Requirement does not apply.
[FI20]1 installed lighting fixtures in dwelling ❑Does Not
units have>= 55 Im/W efficacy or a
>= 45 Im/W total luminaire efficacy. ONot Observable
ONot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: T0345 TIGARD OR-ELECTRICAL COMPLIANCE Report date: 10/05/21
Data filename: Page 7 of 7
•
11
lampert group
312.522.5835 www.lampertgroup.build
Transmittal 10/12/21
DECEIVE
D
OCT14z i
TO: City of Tigard ��y0FTID Planning & Building ;WOW
13125 SW Hall Blvd ODMSION
Tigard, OR 97223
From: Leif Erickson
Lampert Group LLC
10061 Riverside Dr. #760,
Toluca Lake, CA 91602
(312)956-4092
RE: Target - 9009 SW Hall Blvd
Tigard Planning and Building,
Please find the following plans and application for our project located at 9009 SW Hall
Blvd.
Quantity Item
6 i Complete set of Plans
2 Structural Calculations
1 Building permit application
1 Set of additional supporting documents
Should you have any questions or concerns, please feel free to contact me.
Sincerely,
Leif Erickson
LRE@Iampertgroup.build
(312)956-4092
Page 1 of 1