Loading...
Report �2�Zs� � I�ECEIVE� AC-1 & 2 RANI 2 5 21:122 Bard BARD FUSION-TECTM WALL-MOUNTT"'ITY OF TIGNRL niNee wia Free Cooling Economizer and Air Conditi l°Ivls. Climate Control Solutions oF FICE COPY Bard HR Series 11EER 3.5/5 Ton High Sensible Cooling System ,. The FUSION-TECTM has been designed specifically to optimize free cooling opportuni • - ties. By implementing a reverse-airflow design, productive outdoor air for free cooling is brought into the system from the lower portion of the chassis. The heat in the shelter is exhausted out of the top of the chassis which completely eliminates any possibility of recirculating hot exhaust into the cool air entryway.When outdoor air is not productive for free cooling, the FUSION-TEC system has a fully flexible mechanical cooling opera- tion that operates at an IPLV of 15.7, and also satisfies the D.O.E.'s 11.0 EER efficiency requirements. Engineered Features Dual Capacity: System fluctuates between two cooling capacities. The HR Series High Sensible system operates at ranges from 3.5 ton to 5 ton, based upon need and peak efficiency. Reverse Airflow: Peak performance low side air discharge directs the cooler air used for electronics and equipment cooling at floor level where it is needed. The heat from the shelter is pulled back into the FUSION-TEC from ceiling level to be exhausted to the outside, or integrated into the mechanical cooling system. Bard FUSION-TECTM Free Cooling Unit:All units are designed to optimize any free cooling outdoor air opportunities. Reverse Airflow Unit The FUSION-TEC features positive seal dampers to eliminate unwanted air migration. Peak operation is constantly monitored and deviations result in an alarm. (Free cooling may be disabled via software when needed.) As a safety design, an air quality switch has been integrated into the system to keep dirt and debris out of the building . Logic Board: System control panels are equipped with PLC Logic Boards that allow multiple unit operation with a single controller. Unit connection to the LV controller is accomplished with 2 wire shielded cable with drain (ground). Advanced Unit Diagnostics:Whether connected to the TEC-EYETM diagnostic tool, or just viewed from the shelter control,the system PLC Logic Board is able to display stored alarms and easy to read diagnostic information. Orphan Mode: System is designed to run independently if communication to the LV controller is Bard LV and RV lost, meaning that cooling can be provided even if the controller or wiring fails. Controllers Airflow Switch: All systems feature an airflow switch to monitor blower operation. Settings are field adjustable with alarm signal. Dirty Filter Switch:All systems include an airflow switch to monitor pressure drop across the unit filter. This will indicate when a filter change is needed. Settings are field adjustable with alarm AVM CERTIFIED- signal. An indicator light is located on the outside of the FUSION-TEC. . ..A Preee,re., Sngk Padape Vww/AC tnard High Pressure Transducer: A high pressure transducer is used for advanced diagnostic features NP" " including an alarm signal when condenser coil cleaning is needed. Low Pressure Transducer: A pressure transducer is used for advanced diagnostic features and indication of refrigerant loss. Combined with other sensors, the FUSION-TEC will constantlyus adisplay superheat readings. c High Efficiency Indoor Blower: Using the latest technology DEC Star®fan design, the FUSION- Intertek TEC achieves peak CFM airflow rates with the lowest energy usage possible. High Efficiency Outdoor Fan Motor:The FUSION-TEC uses a high efficiency ECM fan system to R-410A provide air through the condenser coil. By varying the fan speed, the system is able to provide the airflow needed at high and low outdoor temperature conditions. Security Features: By selecting the BardGuardTM option, electronic security features allow the system to sense coil and copper theft, and features multiple alarm options. An in-shelter disarm button allows authorized personnel to service the system. Form No. S3551.317 Supersedes NEW Page 1 of 34 Unit Nomenclature HH R 58 AP A OZ E P X X X X UNIT SERIES —1— MAXIMUM TOTAL CAPACITY 58-5 Ton 2 Stage Step Capacity REVISION A-Revision Level CONTROL LOGIC AND CLIMATE OPTIONS P-- Programmable Logic Board VOLTS&PHASE A-230/208/60/1 B-230/208/60/3 ELECTRIC HEAT "OZ" Okw with Circuit Breaker "01" 1.5kw with Circuit Breaker "05" 5kw with Circuit Breaker "MZ" Okw with Circuit Breaker and Inverter "M 1" 1.5kw with Circuit Breaker "M5" 5kw with Circuit Breaker and Inverter VENT PACKAGE E-Factory-Installed Economizer(All Units) FILTER — P-MERV8 Disposable Pleated Filter COLOR AND CABINET FINISH X-Beige Baked Enamel Finish 1-White Baked Enamel Finish 4-Buckeye Gray Baked Enamel Finish 5-Desert Brown Baked Enamel Finish 8-Dark Bronze Baked Enamel Finish PLACEHOLDER X- Future Use COIL AND UNIT COATING OPTIONS X-Copper/Aluminum Evaporator Coil, Copper/Aluminum Condenser Coil 1-Copper/Aluminum Evaporator Coil, AeroMarine Coated Condenser Coil 3-AeroMarine Coated Evaporator Coil, AeroMarine Coated Condenser Coil 4-Condenser Section Component Coating,AeroMarine Coated Evaporator Coil and Condenser Coil 5-Internal and External Cabinet Component Coating, AeroMarine Coated Evaporator Coil and Condenser Coil ACCESSORIES AND CONTROLS OPTIONS X-Standard accessories including airflow sensor,dirty filter sensor, pressure transducers, crankcase heater S-All standard accessories plus additional Bard Guarclim security features and security frame Note: Must order(1) BG1000 security controller for 1 to 4 units on the shelter. Form No. S3551-317 Supersedes NEW Page 2 o1 34 • FUSION-TECTM Unit Specifications Specifications HR58APA HR58APB Performance 5 Ton Full Load Total Cooling Capacity, BTUH 58,000 BTUH 5•1,000 BTUH 5 Ton Full Load EER 11 EER 11 EER 5 Ton Full Load CFM 1800 CFM 18110 CFM 3.5 Ton Part Load Total Cooling Capacity, BTUH 42,000 BTUH 42,100 BTUH 3.5 Ton Part Load EER 11.3 EER 11.3 EER 3.5 Ton Part Load CFM 1400 CFM 1400 FM IPLV (Integrated Part Load Value) 15.7 15.7 Rated Voltage 230/208 Volt 1 Phase 230/20: Volt 3 Phas• Compressor Operating Voltage Range 197V to 253V 197V to 3V Rated Load Amps 20.4/23.0 12.4/14.0 Branch Circuit Selection Current Amps 27.1 16.5 Locked Rotor Amps 152.9 110 Compressor Type 2 Stage Scroll 2 Stage Scrol Condenser Fan Motor Speeds and Type Variable ECM Variable ECM Condenser Fan and Motor Condenser Fan Motor Horsepower V2 HP 1/2 HP Condenser Fan Motor Amps 4.3 4.3 Condenser Fan Motor Min.—Max. RPM 300— 1200 RPM 300— 1201 RPM Condenser Fan Diameter/Rotation 24" CCW 24"CCW Condenser Fan CFM 3300 CFM Max. 3300 CF Max. Blower Motor and Indoor Airflow Blower Motor Speeds and Type Variable ECM Variabl: ECM Blower Motor Horsepower 3/4 HP 3/4 HP Blower Motor Amps 3.6 A 3.6 Blower Motor Max. RPM 1200 RPM 120n RPM 5 Ton Indoor Blower CFM © Estimated Static Pressure inch W. C. 1800 CFM @ 0.0 E.S.P. 1810 CFM @ 0.0 E.S.P. (Rated, wet coil) 3.5 Ton Indoor Blower CFM @ Estimated Static Pressure inch W. C. 1400 CFM @ 0.0 E.S.P. 1J 00 CFM @ 0.0 E.S.P. (Rated, wet coil) Filter Size—Number of filters 20 x 30 x 2—2 filters .0 x 30 x 2—2 filters Filter Rating(Disposable Filter) MERV8 ERV8 Form No. S3551-317 Supersedes NEW Page 3 of 34 Unit Specifications (continued) Specifications HR58APA 4R58APA Refrigeration System Refrigeration Flow Control Device Electronic Expansion Valve Electronic Expansion Valv- High Pressure Sensor 0-5V Analog Transducer 0-5 'nalog Transducer Low Pressure Sensor 0-5V Analog Transducer 0-5V •nalog Transduc: High Pressure Safety Switch Non-Adjustable NC Switch Non-Ad ustable NC S itch R410 Refrigerant Charge `* Air Pressure and Temperature Sensors Dirty Filter Indicator Switch Adjustable Pressure Switch Adjustable ' es re Switch Blower Airflow Indicator Switch Adjustable Pressure Switch Adjustable Pr•.sure Switch Outdoor Air Sensor 1OK Analog Sensor 10K Analog e.e .or Return Air Sensor 1OK Analog Sensor 1OK Analo: Sensor Supply Air Sensor 10K Analog Sensor 1OK Anal.: Senso Economizer Specifications Damper Motor 24VDC, Modulating(0-10y) 24VDC Modulating(1-1OV) Damper Blade Switch Magnetic NO/NC Switch Magm tic NO/NC Switc Outdoor Air Quality Sensor Adjustable Optical Sensor Adj .table Optical Sensor Unit Weight Specifications Estimated Unit Weight 547 lbs. 5,7 lbs. Estimated Unit Shipping Weight 577 lbs. .77 lbs. Form No. S3551-317 Supersedes NEW Page 4 0l 34 Product Design Features Counterflow HR Series in the Standard Wall Mount Footprint The FUSION-TECTM counterflow unit uses the advantages of having a high supply opening to draw heated air from the ceiling level, and discharge cooler air where it is needed the most, at equipment and floor level. This is done using the standard wall mount footprint that has been used for years in the shelter and equipment cooling industry and requires minimal or no wall modifications to replace existing wall mount cooling equipment. This is accomplished by reversing the airflow through the existing wall openings. An Energy Saving Economizer with Mechanical Cooling By design, the Bard FUSION-TECTM HR Series counterflow unit has a built-in free cooling economizer with separated intake and exhaust air paths. Using separate cold air intake and heated room air exhaust openings dramatically reduces the recirculation effect of room air being discharged from the unit and drawn back into the fresh air intake. This makes economizer operation as efficient as possible and allows for proper intake airflow temperature measurement. MECHANICAL COOLING ECONOMIZER MODE .h nifitli 4 .6 jej .. N i ., alli It t L ..„.,41, _ ►. ..._ , ' - Form No. S3551 317 Supersedes NEW Page 5 of 34 Unit Options Cabinet Finish Options All unit models are available in Beige, White, Buckeye Gray, Desert Brown and Dark Bronze. 11111 X= BEIGE 1 =WHITE 4 = BUCKEYE GRAY 5 = DESERT BROWN III 8 = DARK BRONZE Evaporator and Condenser Coil Coating Options All models utilize a copper/aluminum evaporator and condenser coil. An additional corrosion resistant AeroMarine coating may be ordered for the evaporator coil, condenser coil or both evaporator and condenser coils. \I\ '\ \\. Aluminum Fin AeroMarine Fin (standard evaporator) (optional coil coating) Condenser Section and Entire Unit Coating Options Bard recommends unit coatings be used near salt water coastal areas and areas that may be exposed to corrosive particulates in the airstream. Two options are available: Condenser section only (option 4*) includes coating the condenser section copper, condenser fan components, condenser coil header and end sheets. An entire unit coating (option 5*) includes components in the indoor and outdoor airstream including copper, filter/drier, compressor, and drain pan. °Refer to unit nomenclature for coating options. 1.. S Form No. S3551-317 Supersedes NEW Page 6 of 34 • Control Options Control Field- Module Installed Fits Models Listed Description Code Part# Standard control module package. It contains the following: t • Logic Control Board • Electronic Expansion Valve • High Pressure Transducer • Low Pressure Transducer • High Pressure Safety Switch • Dirty Filter Pressure Switch itIndoor Blower Operation Switch Return Air Temperature Sensor v• 'Supply Air Temperature Sensor • Outdoor Temperature and Humidity Sensor • Compressor Control Module • Economizer Intake Air Quality Sensor • Compressor Crankcase Heater • Phase Monitor(3 phase models only) Security control module package. It contains the standard options listed above and the following: • Heavy Duty Security Frame with Easy Service Access S N/A All Models • Panel Monitoring Devices • System Pressure Loss Switch • Speaker for Audible Alarm • Indoor Control Box with Arm and Disarm Hard start kit includes the following: N/A SK-118 All Models • Start Relay • Run Capacitor Form No. S355I317 Supersedes NEW Page 7 of 3°i • HR Series Units with LV Controller Unit Operation with LV Controller The HR Series counterflow unit is designed specifically for use with the LV Series lead/lag controller. Each HR unit contains a logic board that communicates with the LV controller using 18 gauge 2 wire shielded cable with drain. The LV controller uses a -48VDC power The LV controller communicates remotely using SNMP. supply for operation. By using battery SNMP requires a 3rd party program to access data points power, the controller is able to continue and communicate with the controller. to function during a power loss. LV Controller -48VDC SNMP Communication (RV1000 only) Power 66 Block Each unit has an 18 gauge 2 The LV controller wire shielded cable with drain to communicates alarms to communicate with the LV controller. the shelter 66 block with If communication is lost, the unit normally open/normally will operate in Orphan Mode. closed contact points. Q Unit 1 Unit 2 A 230 volt power is supplied 230VAC to each unit. Each Bard HR Power Series counterflow unit has circuit breaker protection built into the control panel. Farm No. 83551 317 Supersedes NEW Page 8 of 34 HR Series Orphan Mode Operation Orphan Mode Operation Each HR Series unit is equipped with an on-board return air temperature sensor and supply air temperature sensor. The programmable logic board in the unit allows for cooling functionality using these sensors when contact is lost with the LV controller. By running in continuous fan, return air temperature will be monitored and the FUSION-TECTM unit will use economizer free cooling and compressor cooling mode to maintain a indoor temperature of 74°F until communication is restored with the LV controller. LV Controller -48VDC SNMP Communication (RV1000 only) Power 66 Block Each unit has an 18 gauge 2 wire shielded cable with drain to communicate with the LV controller. , . . . If communication is lost, the unit will • ■ operate in Orphan Mode. -- s Unit 1 Unit 2 Runs in Orphan Mode Continues to run as lead unit connnected to LV controller 230VAC Power Four No. S3551-317 Supersedes NEW Page 9 of 34 HR Series Units with LV Controller One to Four Unit Operation with LV Controller One to four units may be connected to the LV controller to operate in a lead/lag configuration. Each unit requires an 18 gauge 2 wire shielded cable with drain to communicate with the LV controller. SNMP with traps (RV1000 only) LV Controller Ethenek Comm -48VDC Power to LV Power Shelter Alarms 66 Block 2 Wire for Comm. with Unit 1 2 Wire for Comm. with Unit 2 2 Wire for Comm. with Unit 3 2 Wire for Comm. with Unit 4 1 1 1 1 Unit 3 Unit 1 Unit 2 Unit 4 Unit 3 Power Unit 1 Power 23OVAC Unit 2 Power Power Unit 4 Power Porn No. $3551.317 Supersedes NEW Page 10 of 34 • HR Series Units with -48VDC Power Inverter (Coming Soon!) Optional -48VDC Power Inverter All HR Series models have an option to order a -48VDC power inverter to allow unit operation when shore power is lost. During normal operation, the unit will operate on 230 volt AC power supplied locally. During a power outage, the indoor blower and economizer will operate on -48VDC power regardless of outdoor temp. and indoor humidity. This is accomplished by using an DC to AC power inverter located inside each unit. The power inverter contains circuit protection to avoid DC polarity issues if the + and — connections are reversed. Compressor cooling operation is disabled during -48VDC power inverter operation. -48VDC Power Inverter Operation LV Controller a -48VDC 230VAC 4 Power Power A • N 0 O U U CO N > p C = 230VAC P 0 o to Unit 1 E 230VAC I 0 Y(dr—C.)CN 0 _ C U U 230VAC to 230VAC to r Unit 1 Unit 2 Unit 1 Indoor Indoor Blower Blower and Econ. and Econ. 4 Form No. S3551 317 Supersedes NEW Page 11 of 34 HR Series Standard Components Programmable Logic Board Each unit uses a programmable logic board located in the unit control panel to communicate with the LV controller. By using a 2-wire connection, alarm functionality and unit operational commands are communicated. If communication is lost, the unit is able to run by using the logic in the unit controller in orphan mode. Wall-Mount Unit Control Board I) ro iOltr:,' i9t41kA5 zk 2te .0 e:NI -0e:Dl2 -0s:DD l� L7❑ O CI :e0. U e:Du Not :ea 0 e-DIS 6 °�$ — Not a ll 0 9-DI6 n;e 0 -0e-Dv -0 e=GND "1 II eclo _®�_ e:B2 egg C2 QB Dec B4 rIW:96 9<Bs — pp Nos ,6 o- 0 ec B6 O N06:Q o ec B7 m O O EY GND } 0 e se o9:Bs o I_ a' No7 re Cl C> -e O D NC7 0 {I .. 1= 0 0 O • Ir_ 0 ® ( 'R RA�� a' o 00 � la Power Supply Specifications: Other Specifications: 24VacNdc+10%/-15%50/60 Hz Environmental pollution degree: 3 Max power input:28 VA Index of protection: IP00 Insulation between power supply and instrument: Class according to protection against electric shock:to be incorporated • Mod.24Vac: reinforced ensured by the use of external safety into Class 1 and/or Class 11 appliances (class 2)transformer(mandatory) PTI of the insulating materials PCB:PTI 250' External fuse:3.15 AT(mandatory) insulation material: PTI 175 Minimum section of wires of all other connectors:0.5mm2 Period of stress across the insulating parts: long Product Specifications: Type of action: IC; lV for SSR versions Program memory(FLASH): 128MB Type of disconnection or micro interruption:micro interruption Data memory: 16MB/8 B category of resistance to heat and fire:Category D(UL94-VO) nternal clock precision: 100 ppm Immunity against voltage surges:Category III Battery type: Lithium button battery(removable), BR2032,3 Vdc Rated impulse voltage:4000V; Battery lifetime characteristics of removable battery; Min. 8 years Temperature for Ball Pressure Test: 125°C in normal operating conditions. Communication Lines Available: User Interface: • 1 shielded RJ45 Ethernet line.To the Ethernet port only one circuit type SELV CIRCUIT can be connections Type:all the pGD terminals with telephone connector J10, Maximum Ethernet port connection cable length: 100M CAT-5 STP th-Tune single unit controller with connector J 11/J12/J13 Operating Conditions: Storage:-40770°C,90%rH non-condensing Operating:-40T60°C,90%rH non-condensing Form No. S3551-317 Supersedes NEW Page 12 n1 34 HR Series Standard Components DEC Star'° Indoor Airflow System DEC Star is the first product to bring together a high efficiency blower (HEB) housing, axial flux (no shaft) BLAC motor, and variable speed ECM technology into one innovative assembly. The DEC Star blower system removes the motor from the blower inlet, eliminating restriction and improving system efficiency. *Used on HR58 units only. Specifications • High efficiency blower (HEB) housing and impeller driven by axial flux BLAC motor with full featured sinusoidal EON motor control technology • 10" diameter wheel • Two patents issued on the unique geometry blower. Other patents pending on the Halo motor system. • Operating speed range of 250 — 1400 rpm • 16-pin thermostat and PWM input to control • Variable speed, constant torque/constant airflow ECM • 120/240/277 and 120/240 VAC single-phase input, 50/60Hz • UL and cUL recognized system Electronic Expansion Valve (EEV) The valves are certified in accordance with the main national and international standards. Precise control is guaranteed by electronic controllers, designed especially to optimize management of air conditioning and refrigeration systems, with special focus on energy saving. In addition, highly precise control is also assured by the special shape of the movable elements, guaranteeing flow with an equal percentage characteristic; the stroke length, achieved by using stainless steel ball bearings; and the use of high precision mechanical components. Specifications • Power supply voltage 12V • Drive frequency 50 Hz • Phase resistance (25°C/77°F) 40 Ohm ± 10% • Index of protection IP67 • Step angle 7.5 ° • Linear advance/step 0.02 mm (0.001 inches) • Complete closing steps 500 • Control steps 480 Form No. S3551-317 Supersedes NEW Page 13 of 34 HR Series Standard Components Copeland UltraTech Compressor The Copeland Scroll UltraTech compressor offers a better means of powering air conditioning systems. Building on established scroll technology, the �} Copeland Scroll UltraTech compressor provides superior humidity control, greater efficiency and quieter operation, providing unsurpassed reliability and performance along with increased comfort and reduced energy bills. Modulating compressors provide precise temperature control, lower humidity and greater energy efficiency in comparison to fixed capacity compressors. , - The Copeland Scroll UltraTech compressor modulates between two capacity settings, 67% and 100%. Two internal bypass ports enable the compressor to run at 67% part-load capacity during times when only part-load cooling is needed. When demand increases, the modulation ring is activated, sealing the bypass ports and instantly shifting capacity to 100%. Running for longer periods at part-load capacity (67%) lowers the humidity inside the building and allows the HVAC system to operate more quietly. With the redesigned Copeland Scroll UltraTech compressor, the VA load is reduced to an expected range of 2-5 VA. EC Outdoor Fan Motor The EC outdoor fan motor maintains its high efficiency across a wide operating range. The result is a significant reduction in energy use when the motor is run at reduced speeds. Specifications • ECM Technology • Enclosed motor housing • Efficiencies up to 80% • Variable speed, constant torque, brush less DC motor • Single-phase input, 50/60Hz • Designed for direct-drive fan applications • Operating speed range of 200-1800 RPM • NEMA 48-frame • cURus recognized component • Single shaft with integrated control module Dirty Filter Switch All unit models utilize an adjustable dirty filter pressure switch to indicate when the filter needs to be changed. The dirty filter switch measures the pressure difference on both sides of the filter through tubing routed to the blower and vent areas of the unit. When pressure increases to a pre-set measurement in the switch, an alarm signal is sent to the unit programmable logic board, then to the LV controller. The controller energizes a set of normally open contacts. A LED light is also installed on the exterior cabinet surface to indicate a filter change is required. Form No. S3551 317 Supersedes NEW Page 14 of 34 • HR Series Standard Components Filter Replacement Light A light is provided on the exterior of the unit that illuminates when the unit filter needs to be replaced. The light is located on the front left side of the cabinet. When the alarm signal for a dirty filter is reset through the LV1000 controller, the light will no longer be illuminated. Indoor Blower Operation Pressure Switch All unit models will utilize an indoor blower operation switch to indicate when blower airflow is not adequate for unit operation due to a failed , $4 - evaporator blower motor or other mechanical airflow issue. The switch f ° measures the pressure difference on both sides of the blower partition through tubing routed to the blower inlet and outlet areas of the unit. When pressure decreases below a pre-set measurement in the switch, an alarm signal is sent to the unit programmable logic board, then to the LV controller. The controller energizes a set of normally open contacts. Compressor Control Module A low voltage monitoring device is used to monitor power and indicate a low incoming voltage situation caused by inadequate shore power or generator operation. The monitoring device protects the unit against compressor contactor "chatter" and reverse compressor rotation during these situations. Return Air Temperature Sensor All unit models have a return air temperature sensor installed for operation in `orphan" mode. The return air temperature sensor is also used for indoor temperature averaging with the use of the LV controller. The return air sensor is located in the upper part of the return opening in such a way that it is exposed to the entering airstream. Information is received by the unit logic control board using a 10K resistance signal. An alarm will be sent to the LV controller if the return air temperature sensor is disconnected. Supply Air Temperature Sensor All unit models use a supply air temperature sensor. By monitoring the air temperature leaving the supply opening, the unit logic control board is able to monitor the air entering the shelter. Information is received by the unit logic control board using a 10K resistance signal. An alarm will be sent to the LV controller if the supply air temperature sensor is disconnected. Form No. S3551 317 Supersedes NEW Page 15 o1 34 HR Series Standard Components Outdoor Air Temperature and Humidity Sensor All unit models use a outdoor air temperature and humidity sensor. Using the sensor, the unit logic control board is able to monitor the outdoor air temperature, humidity and dew point. When conditions are acceptable for bringing in cooler outdoor air, the unit logic control board will allow economizer operation. The unit software can be set to operate economizer in Dry Bulb, Humidity %RH or dew point. An alarm will be sent to the LV 'w controller if the supply air temperature sensor is disconnected. Compressor Crankcase Heater All unit models have a crankcase heater installed as standard. The crankcase heater is a belly band style heater encircling the base section of the compressor housing. When the unit is not in operation, the crankcase 411111......11111111 heater is a precautionary measure to prevent compressor oil migration, deter oil and refrigeration from mixing and avoid refrigerant condensation. Care must be used when servicing the unit to avoid being burned by the belly band attached to the compressor base. Always disconnect power when servicing this area of the unit. Economizer Air Intake Quality Dust Sensor All unit models include a dust sensor to monitor the outdoor air quality r,, entering the economizer damper area. When conditions are unacceptable due to particulates in the air including farm field debris, highway dust and dirt, or other particulates, the economizer is disabled. The sensor monitors dust density by using an optical system The optical portion of the sensor uses a light-emitting diode and light detector. The sensor is shipped pre-set, but may be adjusted for less or more sensitivity. High Pressure Transducer All unit models have a high side pressure transducer. The transducer will be used for system monitoring of high side system pressures. This information will be used to indicate when outdoor coil cleaning is necessary based on outdoor conditions and system pressures. When high pressure increases beyond a pre-set measurement when compared to outdoor temperature stored in the unit programmable logic board, an alarm signal is sent from the unit programmable logic board to the LV controller. The controller energizes a set of normally open contacts to indicate abnormal high system pressure. The high pressure transducer also controls the outdoor condenser fan and motor to increase outdoor airflow during high outdoor ambient conditions. Superheat is displayed through the TEC-EYE diagnostic tool. Form Nu. S3561-31/ Supersedes NEW Page 16 of 34 HR Series Standard Components Low Pressure Transducer All unit models have a low side pressure transducer installed on the suction line between the evaporator coil and compressor. The transducer is used for system monitoring of low side system pressures. This information is used to indicate a loss of system refrigerant. When low pressure drops below a pre-set measurement stored in the unit programmable logic board, an alarm signal is sent from the unit programmable logic board to the LV controller. The controller energizes a set of normally open contacts to indicate1114.444111141 abnormal low system pressure. When a loss of charge is measured, the LV controller energizes a set of normally open contacts to indicate refrigerant loss and that the unit needs to be serviced. The low pressure transducer is also used for operation of the eletronic expansion valve (EEV). High Pressure Safety Switch All unit models have a high side pressure switch as a safety device. This device is connected to a safety rated set of contacts, and operates if high system pressures reach an unacceptable level. When activated, the unit will shut down compressor operation immediately. After a predetermined time, the unit will attempt to restart. If the switch is activated during the restart, compressor operation will lockout, and an alarm signal will be sent to the LV controller. This is a safety device that disables unit operation at a high refrigerant pressure. It is also used to protect unit components including the electronic expansion valve and compressor. Never disable the high pressure safety switch. Activation of the switch normally indicates the unit needs to be serviced. Field-Installed Hard Start Kit SK-118 (Optional) All unit models have a hard start kit available for field installation. The hard RNry azai-A start kit may be used to provide additional torque for compressor startup. --- A relay is provided to energize a start capacitor during the initial starting of Capacitor the compressor. When the starting winding voltage increases to a set value in the relay, the start capacitor is de-energized. Freeze Stat Evaporator Coil Protection All unit models include a freeze stat connected to the evaporator coil to avoid coil freeze up. This sensor, when activated, allows blower operation ,! without compressor cooling until coil temperatures are above freezing. Once below freezing, normal unit operation resumes. rap 1116. Form No. S3bb1-317 Supersedes NEW Page 17 of 34 V Un T G N 9 ry = x N y mT , _V� (,�(IQp„.,,,,!;;111)II1�11i - 'Condenser d Fan r. r 29.8 m.4 _ — TYP.� I = ' .••••n•••••••••••••• , ' •.••••••••••••••••••� �1.5 Condense re .•••••••••• •.•i••••• Condense 1 Section !i tesec iii••••••••••i : Section I 1 9.9 16.D Return Opening M Access •�trii•u••••••••n•••• P 9 t Condenser Air Intake••••:• Access I Low Volt. ::••4••••••••••••••i•••••••••••S Circuit Breaker h 29.9 —I i EleCirlcal/ •••••p••ua•••••ii Access Entrance '•••••••••o••••••���•�•�•�•�•�•••�•��f r` 6 i•••••••••••••••iii••••••i•••••64/ 3.6 16.0 76.0 Filter Filter ~ Access 0 , I • Access 31.2 1 29.9 CD i .i- iiiii ° 16.0 4z.o l ' • Supply y 39.7 -• I Opening 15.9 ti Hi Volt. 29.1 I—15.1—•- Electrical 16.0 ' N t i y Entrance 21.7 13.0 ¢ Evaporator f 41.9 r. and Blower Service PortCif Access CD Access 43.0 44.0 Dual C CD Evaporator I_ �� Dual Notes: Drains '�� Condenser 1. Filters and Condenser Section are accessible from Drains both sides. 10.9 Vent Air Intake :1 2. Condenser air enters the upper front section of the 1 unit and is discharged from the top. HR Series Unit Clearances Unit A C D H W X Y Z HR58 24" 15" from 30" 76" 42" 36" 20" 15" snowline Top View Shelter Shelter i Equipmen Equipmen Supply it //Q uupply'IAir 1 Dim.A ��‘�Il�u 11 '/�� kkW W)) DiTi A Dim.D aiml„ mil i'll" mrillV 11 Dim.D i \\,iii' I" Unit#1 Outdoor Clearance Area Unit#2 Dim.X Dim.X 1_— � L \ _ —0-II Dim.Y Dim.W— —Dim.Z --- Dim.W ► Dim.Y —.1— Side View Condenser Air Outlet i ] I I . .� / d Return Air Condenser / N -- J Air Inlet Dim.H Unit#1 . i , and#2 Supply Air! (‘s r 1 I E IS O - I a) d IC—_ I L = I Dim.C LwaJ f Dim.Ai "' Floor Outdoor Clearance Area / k-Dim.X -- Dim.D-I Form Nu. S355] 317 Supersedes NEW Page 19 0l 34 HR58 Mechanical Cooling Performance - 5 Ton Capacity (Full Load) Full Load Sensible Capacities Return Air Cooling 75 80 85 90 95 100 105 110 115 120 125 (DB/WB) Capacity 79/66* Sensible 46,900 45,700 44,600 43,500 42,500 41,600 40,700 39,900 39,100 38,400 37,700 75/61.1 Sensible 56,200 54,600 53,000 51,400 49,800 48,400 47,000 45,650 44,250 42,850 41,500 80/62.9 Sensible 55,300 53,750 52,150 50,600 49,000 46,250 43,500 40,750 38,000 35,250 32,500 85/64.7 Sensible 61,200 60,150 59,100 58,100 57,000 53,850 50,650 47,450 44,250 41,050 37,850 'Per NSTD standards for indoor shelter conditions. HR58 Mechanical Cooling Performance - 3.5 Ton Capacity (Part Load) Part Load Sensible Capacities Return Air Cooling 75 80 85 90 95 100 105 110 115 120 125 (DB/WB) Capacity 79/66* Sensible 35,800 34,600 33,500 32,400 31,400 30,500 29,600 28,800 28,000 27,300 26,600 75/61.1 Sensible 42,300 41,000 39,700 38,450 37,200 34,850 32,600 30,250 27,950 25,700 23,350 80;62.9 Sensible 42,050 40,750 39,500 39,200 38,900 35,800 34,700 33,550 32,450 31,300 30,200 85/64.7 Sensible 46,300 45,300 44,300 43,300 42,300 41,000 39,750 38,400 37,150 35,900 34,650 *Per NSTD standards for indoor shelter conditions. HR58 Free Cooling Economizer Performance Unit Model Indoor Airflow Outdoor Indoor Free Cooling Free Cooling Temperature Temperature Sensible Capacity EER HR58 1650 cfm 70°F 80°F 17,800 BTUH 36.3 HR58 1650 cfm 60°F 80°F 35,600 BTUH 72.7 HR58 1650 cfm 55°F 80°F 44,500 BTUH 90.9 HR58 1650 cfm 70°F 85°F 26,700 BTUH 54.5 HR58 1650 cfm 60°F 85°F 44,500 BTUH 90.9 HR58 1650 cfm 55°F 85°F 53,400 BTUH 109.1 Form No. S3551-317 Supersedes NEW Page 20 of 34 HR58 Electrical Specifications --_ Single Circuit O Model Rated Volts No. Field Minimum Maximum External Field Power & Phase Power Circuits Ampacity Fuse or Circuit Wire Size Ground Wire Breaker HR58AOZ 230Y208-1 1 43 60 8 10 114 A05 1 43 60 8 10 HR58BOZ 230/7.08-3 1 30 45 8 10 B05 1 , 30 45 8 10 O Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors. O Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. © These "Minimum Circuit Ampacity"values are to be used for sizing the field power conductors. Refer to the National Electrical code(latest version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway. IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes. HR58 Recommended Airflow HR58 Maximum ESP of Operation Electric Heat Only Nominal Rated CFM Nominal Rated ESP High Low Model Static Pressure* -AOZ .00"wc 1800 1400 .10 -A05 .00"wc .00"wc .00"wc HR58 Indoor Blower * Unit is rated for free blow non-ducted operation Performance with SGR-5W Supply Grille and RGR-5W Return Grille. Speed High Low ESP Dry Wet Dry Wet (Inch H20) Coil Coil Coil Coil 0.1 1885 1800 1470 1400 HR58 Electric Heating Performance Model kw Voltage Phase Amps @ 240V BTUH A05 5kw 230 Volt 1 20.8 17,065 805 5kw 230 Volt 3 12.0 17,065 Form No. S3551-317 Supersedes NEW Page 21 of 34 HR Series Dehumidification Operation The FUSION-TECTM HR Series unit is able to operate in a dehumidification mode when the humidity level reaches 80% RH. By running the unit at a lower blower speed, latent capacity is increased and water is removed from the shelter indoor air. HR58APA DEHUMIDIFICATION MODE PERFORMANCE Indoor OUTDOOR TEMPERATURE DB WB RH VALUE 60 65 70 75 80 85 90 95 100 105 110 115 Latent Btuh 39,200 38,200 37,250 36,250 35,300 34,300 33,150 32,000 30,850 29,700 28,550 27,400 80 76.4 85% #-H2o/Hr 36.98 36.04 35.14 34.20 33.30 32.36 31.27 30.19 29.10 28.02 26.93 25.85 Gallons/Hr 4.44 4.32 4.22 4.10 3.99 3.88 3.75 3.62 3.49 3.36 3.23 3.10 Latent Btuh 33,550 33,050 32,600 32,150 31,650 31,200 30,050 28,900 27,750 26,600 25,450 24,300 80 75.2 80% #-H2o/Hr 31.65 31.18 30.75 30.33 29.86 29.43 28.35 27.26 26.18 25.09 24.01 22.92 Gallons/Hr 3.80 3.74 3.69 3.64 3.58 3.53 3.40 3.27 3.14 3.01 2.88 2.75 Latent Btuh 27,900 27,900 27,950 28,000 28,050 28,100 26,950 25,800 24,650 23,500 22,400 21,250 80 73.9 75% #-H2o/Hr 26.32 26.32 26.37 26.42 26.46 26.51 25.42 24.34 23.25 22.17 21.13 20.05 Gallons/Hr 3.16 3.16 3.16 3.17 3.17 3.18 3.05 2.92 2.79 2.66 2.53 2.40 Latent Btuh 22,200 22,750 23,300 23,850 24,400 24,950 23,850 22,700 21,550 20,400 19,300 18,150 80 72.5 70% #-H2o1Hr 20.94 21.46 21.98 22.50 23.02 23.54 22.50 21.42 20.33 19.25 18.21 17.12 Gallons/Hr 2.51 2.57 2.64 2.70 2.76 2.82 2.70 2.57 2.44 2.31 2.18 2.05 Latent Btuh 16,550 17,600 18,650 19,750 20,800 21,850 20,700 19,600 18,450 17,350 16,200 15,050 80 71.2 65% #-H2o/Hr 15.61 16.60 17.59 18.63 19.62 20.61 19.53 18.49 17.41 16.37 15.28 14.20 Gallons/Hr 1.87 1.99 2.11 2.23 2.35 2.47 2.34 2.22 2.09 1.96 1.83 1.70 LatentBtuh 15,000 15,700 16,400 17,100 17,800 18,500 17,500 16,550 15,550 14,550 13,600 12,600 80 69.7 60% #-H2o/Hr 14.15 14.81 15.47 16.13 16.79 17.45 16.51 15.61 14.67 13.73 12.83 11.89 Gallons/Hr 1.70 1.78 1.86 1.93 2.01 2.09 1.98 1.87 1.76 1.65 1.54 1.43 Latent Btuh 13,500 13,800 14,150 14,500 14,800 15,150 14,300 13,500 12,650 11,800 11,000 10,150 80 68.3 55% #-H2O/Hr 12.74 13.02 13.35 13.68 13.96 14.29 13.49 12.74 11.93 11.13 10.38 9.58 Gallons/Hr 1.53 1.56 1.60 1.64 1.67 1.71 1.62 1.53 1.43 1.34 1.24 1.15 Latent Btuh 11,950 11,900 11,900 11,850 11,850 11,800 11,100 10,450 9,750 9,050 8,350 7,700 80 66.8 50% #-H2o/Hr 11.27 11.23 11.23 11.18 11.18 11.13 10.47 9.86 9.20 8.54 7.88 7.26 Gallons/Hr 1.35 1.35 1.35 1.34 1.34 1.34 1.26 1.18 1.10 1.02 0.94 0.87 Latent Btuh 10,400 10,000 9,600 9,250 8,850 8,450 7,900 7,350 6,800 6,300 5,750 5,200 80 65.3 45% #-H2o/Hr 9.81 9.43 9.06 8.73 8.35 7.97 7.45 6.93 6.42 5.94 5.42 4.91 Gallons/Hr 1.18 1.13 1.09 1.05 1.00 0.96 0.89 0.83 0.77 0.71 0.65 0.59 HR58APA DEHUMIDIFICATION MODE PERFORMANCE Indoor OUTDOOR TEMPERATURE DB WB RH VALUE 60 65 70 75 80 85 90 95 100 105 110 115 Latent Btuh 36,150 34,950 33,800 32,600 31,450 30,250 29,150 28,050 26,950 25,850 24,750 23,650 75 71.6 85% #-H2o/Hr 34.10 32.97 31.89 30.75 29.67 28.54 27.50 26.46 25.42 24.39 23.35 22.31 Gallons/Hr 4.09 3.95 3.82 3.69 3.56 3.42 3.30 3.17 3.05 2.93 2.80 2.68 Latent Btuh 32,550 31,450 30,350 29,300 28,200 27,100 26,050 25,000 23,950 22,950 21,900 20,850 75 70.4 80% #-H2o/Hr 30.71 29.67 28.63 27.64 26.60 25.57 24.58 23.58 22.59 21.65 20.66 19.67 Gallons/Hr 3.68 3.56 3.43 3.32 3.19 3.07 2.95 2.83 2.71 2.60 2.48 2.36 Latent Btuh 25,350 24,450 23,550 22,600 21,700 20,800 19,850 18,950 18,000 17,100 16,150 15,250 75 68 75% #-H2o/Hr 23.92 23.07 22.22 21.32 20.47 19.62 18.73 17.88 16.98 16.13 15.24 14.39 Gallons/Hr 2.87 2.77 2.66 2.56 2.46 2.35 2.25 2.14 2.04 1.93 1.83 1.73 Latent Btuh 21,750 20,950 20,100 19,300 18,450 17,650 16,800 15,900 15,050 14,150 13,300 12,450 75 66.7 70% #-H2o/Hr 20.52 19.76 18.96 18.21 17.41 16.65 15.85 15.00 14.20 13.35 12.55 11.75 Gallons/Hr 2.46 2.37 2.27 2.18 2.09 2.00 1.90 1.80 1.70 1.60 1.50 1.41 Latent Btuh 18,250 17,550 16,850 16,150 15,450 14,750 13,900 13,100 12,250 11,450 10,650 9,800 75 65.4 65% #-H2o/Hr 17.22 16.56 15.90 15.24 14.58 13.92 13.11 12.36 11.56 10.80 10.05 9.25 Gallons/Hr 2.07 1.99 1.91 1.83 1.75 1.67 1.57 1.48 1.39 1.30 1.21 1.11 LatentBtuh 14,800 14,200 13,600 13,000 12,400 11,800 11,050 10,250 9,500 8,750 8,000 7,200 75 64.1 60% #-H2o/Hr 13.96 13.40 12.83 12.26 11.70 11.13 10.42 9.67 8.96 8.25 7.55 6.79 Gallons/Hr 1.67 1.61 1.54 1.47 1.40 1.34 1.25 1.16 1.07 0.99 0.91 0.81 LatentBtuh 11,300 10,800 10,300 9,850 9,350 8,900 8,150 7,450 6,750 6,050 5,300 4,600 75 62.7 55% #-H2o/Hr 10.66 10.19 9.72 9.29 8.82 8.40 7.69 7.03 6.37 5.71 5.00 4.34 Gallons/Hr 1.28 1.22 1.17 1.11 1.06 1.01 0.92 0.84 0.76 0.68 0.60 0.52 Latent Btuh 7,800 7,450 7,050 6,700 6,300 5,950 5,300 4,650 3,950 3,300 2,650 2,000 75 61.1 50% #-H2o/Hr 7.36 7.03 6.65 6.32 5.94 5.61 5.00 4.39 3.73 3.11 2.50 1.89 Gallons/Hr 0.88 0.84 0.80 0.76 0.71 0.67 0.60 0.53 0.45 0.37 0.30 0.23 Latent Btuh 28,950 27,950 26,950 25,950 24,950 23,950 22,950 22,000 21,000 20,000 19,050 18,050 75 69.2 45% #-H2o/Hr 27.31 26.37 25.42 24.48 23.54 22.59 21.65 20.75 19.81 18.87 17.97 17.03 Gallons/Hr 3.28 3.16 3.05 2.94 2.82 2.71 2.60 2.49 2.38 2.26 2.16 2.04 Supersedes NEW Page 22 of 34 FUSION-TECTM Unit Controllers Controller Voltage Shipping Weight # of Units Wall-Mount Units Remote Communication 1111111111111111111111r-23' Ibs 1 to 4 Units FUSION-TECTN HTTP/IPV4/SNMP RV1000 -48VDC 25 lbs 1 to 4 Units FUSION-TECTM HTTPS/IPV6/SNMP LV1000 Multi-Unit Controller The LV Series unit controllers are designed to communicate with r one to four FUSION-TECTM wall mount units. Using a programmable logic board, the LV controller is able to operate all units in a lead/ lag configuration for equal unit run time. Normally open or normally closed dry contact points are available for unit and shelter alarming capability. A -48VDC power supply is used to ensure controller alarming is operational during a loss of shore power. RV1000 Multi-Unit Controller with IPV6 Communication The RV1000 has all of the features included with the LV1000 plus advanced remote communication features including IPV6 (Internet • Protocol Version 6) and SNMP (Simple Network Management Protocol Version 3). Form N . 53551-317 Supersedes NEW Page 23 01 34 FUSION-TECTM Accessories Supplied with LV Controller Part Number Description Quantity Supplied 8301-055 EMI Ferrite Filters 8403-079 Remote Indoor Temperature and Humidity Sensor 1 8301-059 TEC-EYETM Service Tool with 5 ft. Communication Cable EMI Ferrite Filters Part #8301-055 EMI (electromagnetic interference) ferrite filters are used to keep the communication wiring connecting the FUSION-TECTM units and the LV controller from acting as an antenna. As an antenna, the wire could receive electromagnetic interference from other electronic devices in the area. EMI ferrite filters are attached by forming a wire loop through the filter before connecting each unit. A typical two unit installation requires two filters (supplied with LV controller). A four unit installation will require four filters, and two additional filters will be required (sold separately). Wall-Mount Unit LV Controller •• JJ Filter 73 Filter - - Wall-Mount Unit Hon No. S3551 317 Supersedes NEW age 24 of 34 FUSION-TECTM Accessories Supplied with LV Controller Remote Indoor Temperature and Humidity Sensor Part #8403-079 The remote indoor temperature and humidity sensor is used to measure conditions inside the building. Connected with 18 gauge 5 wire shielded cable, the indoor sensor is able to communicate with the LV controller and decide when conditions warrant unit operation. Only one (1) temperature and humidity sensor is used for each LV controller. Up to two (2) optional temperature only sensors may be used (sold separately) for temperature averaging. Technical Specifications: Storage Temperature: -20°C to 70°C Temperature Sensor Range: -20°C to 70°C Humidity Output Signal Range: 0%RH to 100%RH Temperature Sensor Type: NTC 10K OHM at 25°C 1% Humidity Sensor Type: Capacitive Terminal Block Type: Screw terminals for cables, max. dia. 1.5mm min. 0 .5mm Maximum Wire Length: 1640 Ft. (500m) Temperature Tme Constant: In still air, 300s Humidity Time Constant: In still air, 60s. In moving air, 20s. Category of Resistance to Heat and Fire: Category D (for case and cover) Category of Immunity Against Voltage Surges: Category 2 Sensor Index of Protection: IP30 .86" or .86" or 22mm 22mm • 5" or 127mm - 3.26" or 83mm �► 1.73" or�� I 40mm 3.1 mm80mm in I1.73" or lem:171777 40m _,:r:f:f,f_f,fir,r,t,i,hrt�taaattk►,rt:�,!r�i r�i�. 1 Wire } TB# Sensor Description Mark 1.18" or 30mm 18 B6 NTC OUT Indoor Remote Sensor(Zone 1) Zf 19 GND NTC OUT Ground 12 B2 OUT H Remote Indoor Humidity Sensor: 0-1 VDC(Zone 1) 13 GND M(GO) Ground 22 +VDC +(G) Power for B2 1111 , 0 a 0 Form No. S3551-317 Supersedes NEW Page 25 of 34 TEC-EYETM Service Tool Part #8301-059 The TEC-EYETM service tool is used to communicate with the FUSION-TECT"' unit logic board. By connecting directly to the logic board inside the unit control panel, it is possible to perform diagnostics on the unit, adjust certain settings and verify unit and economizer operation through a run test procedure. The TEC- EYEN service tool is required for unit setup and operation, and is supplied with the LV controller. Technical Specifications: Storage Temperature: -20°C to 70°C Operating Conditions: -20°C to 60°C Display Type: FSTN graphic Display Backlighting: LED Graphic Resolution: 132 x 64 pixels Size of Display Area: 72mm x 36mm Connector: RJ12 (phone connector) Maximum Wire Length: 50m, 164 ft. Category of Resistance to Heat and Fire: Category D and B Category of Immunity Against Voltage Surges: Category 2 Index of Protection: IP65, UL Type 1 TEC-EYET"Display ALARM KEY UP KEY A 10/24/16 Mon 13:5 _ -. bf .b f1DP: 46.E,b OAH 44.7: MENU KEY 0Blo 61ofx1er:4O FF DariFer: 0':F'P ENTER KEY Unit status: elOFF BY LC 7 BACK KEY _ DOWN KEY FUSION-TECTM Accessories Supplied with the Unit Top Rain Flashing Top rain flashing is supplied with each FUSION-TEC unit and must be used to avoid water intrusion between the wall and unit top. Follow all instructions for attaching and sealing the top rain angle provided in the FUSION-TEC installation instructions. Form No. 53551-317 Supersedes NEW Page 26 of 34 FUSION-TECTM Optional Accessories (Sold Separately) Part Number Description Quantity Supplied 8301 058 Additional Remote Indoor Temperature Sensor (18 gauge 2 wire shielded cable sold 1 separately) 8403-079 Additional Temperature and Humidity Sensor(18 gauge 5 wire shielded cable sold 1 separately) 8301-055 Additional EMI Ferrite Filters(Required for four units) 2 8301-053 Large Backlit Display Service Tool 1 2151-021 EEV Manual Adjustment Tool 1 113-140 Bottom Wall Mounting Bracket 1 2151-022 Tri-Groove Socket (Bard GaurdTm models only) 1 Remote Indoor Temperature Sensor Part #8301-058 Up to two (2) additional remote temperature sensors or two (2) additional remote temperature and humidity sensors may be connected to the LV controller to measure conditions inside the building. Connected with 18 gauge 2 wire shielded cable, the indoor temperature sensor is able to communicate with the LV controller and decide when conditions warrant unit operation. .86"or .86"or 22mm 22mm 5"or 127mm 3.26"or 83mm --111111 ' ii. , 40mm 3.14"or a (80mm u7 I 111 ® l 1.73"or ee40mm ]]nfl}I1�fA.LI�t.IJ.I.�:'aL _ I 1.18"or 30mm ,Illil�'I (i�,�:�1�1 4111 I, r11111 J Form No. 53551-317 Supersedes NEW Page 27 of 34 Large Display Service Tool Part #8301-053 The large display service tool is used to communicate with the FUSION-TECT"" unit logic board. Operation is identical to the TEC-EYETM, with a larger display and mechanical entry keys. By connecting directly to the logic board inside the unit control panel, it is possible to perform diagnostics on the unit, adjust certain settings and verify unit and economizer operation through a run test procedure. Technical Specifications: Storage Temperature: -20°C to 70°C t Operating Conditions: -20°C to 60°C } Display Type: FSTN graphic Display Backlighting: LED Graphic Resolution: 132 x 64 pixels Size of Display Area: 72mm x 36mm Connector: RJ12 (phone connector) Maximum Wire Length: 50m, 164 ft. Category of Resistance to Heat and Fire: Category D and B • Category of Immunity Against Voltage Surges: Category 2 Index of Protection: IP65, UL Type 1 EEV Manual Adjustment Service Tool Part #2151-021 The EEV manual adjustment tool allows for adjustment of the EEV (Electronic Expansion Valve) without the use of the unit logic board. The service technician can use this tool by removing the electronic head of the valve and attaching the adjustment tool. The tool houses magnets that interact with the valve to open or close the EEV for charging or evacuating the system without system power. Bottom Mounting Bracket Part #113-140 A bottom mounting bracket may be used to help support the unit during and after installation. The front lip of the bracket hooks underneath the unit base. This part is not supplied with the FUSION-TEC unit, but is available as an optioned accessory. Form No. S3551 317 Supersedes NEW Page 28 of 34 FUSION-TECTM Supply and Return Grilles (Sold Separately) Part Number Description Shipping Weight Quantity Supplied SGR-5W Supply Grille, 2' Wide Frame 6 pounds 1 RGR-5W Return Grille, 2"Wide Frame 12 pounds 1 16" x 30" Supply Grille, Wide Frame Part #SGR-5W The FUSION-TECTM unit requires a specially designed supply grille that allows for high velocity airflow through the unit supply opening. The grille finish is powder �a� -------- coated white. Wide frame grilles are used where wall hole sizes require a 2" wide grille flange to cover the wall opening. 10" x 30" Return Grille, Wide Frame Part #RGR-5W The FUSION-TECTM unit requires a specially designed return grille that allows for high velocity airflow through the unit return opening. Deflectors allow for air distribution at floor level, and are adjustable. The grille IM■■■■■■■■■■■■■■11111 finish is powder coated white. Wide frame grilles are immommommossommum used where wall hole sizes require a 2" wide grille flange Ismommommossomismo 9-5/8" to cover the wall opening. 11■■■■■■■■■■■■■■■■■ Ir4"H1-1/8" NOTE:90%FREE ARIA. ...1 41. — 29-5/8" Form No. S3551-317 Supersedes NEW Page 29 of 34 HR Series Field-Supplied Istallation Items, Wiring Component Reason for Use • Wiring— All Units x. •: This is required to communicate between each FUSION-TECTM unit and the LV controller. 18 Gauge 2 Wire Shielded Cable When calculating wire length that is needed, be sure to include routing distance to each unit, conduit requirements and a loop for an EMI ferrite filter inside each unit control panel. This is required to communicate between the indoor remote temperature and humidity sensor and the LV controller. When calculating wire length that is needed, be sure to include routing -.18 Gauge 5 Wire Shielded Cable distance between the sensor location and controller, conduit requirements and routing inside the LV panel to the terminal block. 18 gauge 6 wire shielded cable may be used if an extra conductor(wire) is desired. This is required to supply power to the unit for compressor, ventilation and electric heat operation. When calculating wire length that is needed, be sure to include routing distance Main Unit Power Wiring, 230VAC between the power source and the VAC circuit breaker inside the unit, and the conduit requirements. Be sure to follow all wire sizing and routing requirements supplied in this document and the installation manual. This is required to supply power to the LV controller. When calculating wire length that LV Controller Power Wiring, is needed, be sure to include routing distance between the power source and the VDC 48VDC connection point inside the LV controller, and the conduit requirements. Be sure to follow all wire sizing and routing requirements supplied in the LV specification sheet and the LV installation manual. This is optional to communicate between an additional indoor temperature sensor and the LV 18 Gauge 2 Wire Shielded Cable controller. When calculating wire length that is needed, be sure to include routing distance between the sensor location and controller, conduit requirements and routing inside the LV panel to the terminal block. Wiring—Unit With -48VDC Inverter This is required to supply-48VDC power to the inverter for blower and ventilation operation during a loss of 230VAC power. When calculating wire length that is needed, be sure to Main Unit Power Wiring, -48VDC include routing distance between the power source and the VDC circuit breaker inside the unit, and the conduit requirements. Be sure to follow all wire sizing and routing requirements supplied in this document and the installation manual. 18 Gauge 2 Wire Shielded Cable 18 Gauge 5 Wire Shielded Cable with Drain with Drain Where specified, this wire is 18/2 18 Gauge Copper Where specified, this wire is 18/5 18 Gauge Copper Conductor Stranded Shielded and a PVC jacket. Red Conductor Stranded Shielded and a PVC jacket. 18/6 and black are the preferred wire colors. (6 wire) may be used in place of 18/5 (5 wire) if an extra conductor is desired. Form No. S3551 317 Supersedes NEW Page 30 0l 34 • HR Series Field-Supplied Installation Items, Unit Component Reason for Use Ten (10)cement fasteners, wall lag bolts or other fasteners are required to mount the Wall Fasteners for Unit FUSION-TECTM product to the wall structure. 0375 holes are provided in the wall mounting flange on each side of the FUSION-TECT" unit. Fasteners must be field specified based on the wall structure. Seven (7)cement or wood screws are required to mount the FUSION-TEC'' rain flashing to Wall Fasteners for Rain Flashing the wall structure. 0250 holes are provided in the top of the rain flashing. Fasteners must be field specified based on the wall structure. This is required to form a watertight seal between the FUSION-TEC'' unit and the wall. Exterior Silicone Caulk Choose an outdoor rated premium silicone caulk and follow all installation instructions provided with the FUSION-TEC'" unit. 23OVAC Main Unit Power Conduit This is required to supply power to the unit for compressor, ventilation and electric heat operation. 01.500 knockouts are provided on each side of the unit for 230V main power. Communication Wire Conduit This is required to supply communication to the unit logic control board. One (1) 0.875 knockout is provided on each side of the unit for the communication wire. Unit Installation-48VDC Inverter This is required to supply power to the unit for ventilation operation. 01.500 knockouts are -48VDC Main Unit Power Conduit provided on each side of the unit for-48VDC main power. 230VAC and -48VDC power must be separated as it enters the FUSION-TECT' unit. FUSION-TECTM Wall Mounting Holes FUSION-TECTM Electrical Entrances Five (5) 0.375 mounting holes are provided on each One (1) 0.875 and two (2) 01.093 entrances are side of the unit for attachment to the structure. provided on each side of the unit for wire routing. Form No. S3h21-31/ Supersedes NEW Page 3]o134 • HR Series Units with Bard GuardTM Security System Bard GuardTM Security System The Bard GuardTM Security System is comprised of the following parts: • Sensors and a speaker mounted in each unit. This is ordered by specifying "S" as the last digit in the unit model nomenclature. • The BG1000 Security Interface. This is sold separately and is installed inside the structure. Wires connect the BG1000 to the LV1000 controller. • A heavy duty hinged security frame that attaches to the unit. The security frame has four (4) locking nuts that require a special key to remove. The frame secures the front panels while allowing service access by removing the four (4) locking nuts and swinging the frame out of the way on four (4) provided hinges. This is ordered by specifying "Sr" as the last digit in the unit model nomenclature. Bard GuardTM Electrical Diagram LV 1000 -48VDC BG1000 fo Wire p Security ate or Power ow er toe Interface 2� 0m G1000 {pt 66 Block 4 Wire for Alarm and Speaker Unit 1 2 Wire for Alarm Unit 4 ► 4 4 Wire for Alarm and 2 Wire for Speaker Unit 2 Alarm Unit 3 Unit 4 Unit 1 Unit 2 Unit 3 Speaker Used Speaker Used P Speaker . • Speaker Not Used ip Not Used .,,,,,_ .. ..., _ .., t III,.. _ _ III 1111 ,„ OI ® ka is a . Unit 1 Unit 2 r Unit 3 Unit 4 Nt'r Form No. $3551-317 9rpersedes NEW Page 32 of 31 • HR Series Units with Bard GuardrM Security System Bard GuardTM Security Frame The Bard GuardTM Security frame provides a way to lock the front doors, unit top and condenser coil to deter theft of internal unit components. The frame is comprised of heavy duty steel angle iron and uses a hidden hinged system to allow easy access for servicing the unit. Four (4) locking nuts are provided to captivate the frame. A key is shipped with each unit to remove the locking nuts and provide access to internal components. •rtt Bard GuardTM Unit "S" Controls Option The Bard Guard "S" Controls option is used to order the FUSION-TECTM unit with all required tamper resistant door switches and the internal 80db audio warning speaker. A loss of refrigerant pressure also sends an alarm signal. All components are pre-wired from the factory, and a simple four (4) wire connection is used to connect the FUSION-TECTM unit security options to the BG1000 Security Interface. Up to four (4) units can be used with a single BG1000 by running two (2) wires to each additional unit. Power is supplied by the BG1000 to operate up to two (2) unit audio warning speakers. The audio warning is given in both English and Spanish. Bard GuardTM BG1000 Security Interface (Sold Separately) The Bard Guard security interface mounts to the wall inside the structure. -48VDC power is used to operate the security system. Two (2) indicator lights are provided to display "Armed" or "Disarmed". When armed, the system will apply power for up to 30 minutes to the unit speakers when unit system pressure is lost in any unit, or a door switch has been activated. An alarm signal will also be sent to the LV1000 controller. When disarmed, the system will remain inactive for up to 4 hours (user adjustable). Form Nu, S3551-31/ Supersedes NEW Page 33 of 34 • • Field-Supplied Installation Items, Bard GuardTM Component Reason for Use Wiring— All Units This is required to communicate between FUSION-TECTn' unit 1, unit 2 and the BG1000 18 Gauge 4 Wire Shielded Cable security interface. When calculating wire length that is needed, be sure to include routing with Drain distance to each unit and conduit requirements. 18 gauge 6 wire shielded cable may be used if extra conductors are desired. This is required to communicate between FUSION-TECTM unit 3, unit 4 and the BG1000 18 Gauge 2 Wire Shielded Cable security interface. When calculating wire length that is needed, be sure to include routing with Drain distance to each unit and conduit requirements. It is also required to communicate between the BG1000,the LV1000 and the 66 block NOC connection. This is required to supply power to the BG1000 security interface. When calculating wire LV Controller Power Wiring, length that is needed, be sure to include routing distance between the power source and the 48VDC VDC connection point inside the BG1000, and the conduit requirements. Be sure to follow all wire sizing and routing requirements supplied in the BG1000 specification sheet and the installation manual. 18 Gauge 2 Wire Shielded Cable 18 Gauge 4 Wire Shielded Cable with Drain with Drain Where specified, this wire is 18/2 18 Gauge Copper Where specified, this wire is 18/4 18 Gauge Copper Conductor Stranded Shielded and a PVC jacket. Red Conductor Stranded Shielded and a PVC jacket. 18/6 and black are the preferred wire colors. (6 wire) may be used in place of 18/4 (4 wire) if extra conductors are desired. 1 � Bard Manufacturing Company, Inc. Due to our continuous product improvement policy, Form No. Bard Bryan,Ohio 43506 all specifications subject to change without notice. S3551 www.bardhvac.com March 2017 Before purchasing this appliance, read important Climate control Solution energy cost and efficiency information available from Supersedes: NEW your retailer. Page 34 of 34