Loading...
Report 2ci0CW Ott vtt4 12,4 COMcheck Software Version 4.1.0.0 V Envelope Compliance Certificate Section 1: Project Information Energy Code:2014 Oregon Energy Efficiency Specialty Code Project Title: Project Type: New Construction Envelope Compliance Method:Simplified Trade-Off Construction Site: Owner/Agent: Designer/Contractor: Building Location(for weather data): Adair Village,Oregon Climate Zone: 4c Vertical Glazing/Wall Area Pct.: 20% Elvflding_Wm;.At TYR° Floor Area 1-Retail:Nonresidential 4206 Section 2: Envelope Assemblies and Requirements Checklist Envelope PASSES --r In bode. Envelope Assemblies: Component Name/Description Gross Cavity Cont. Proposed Budget Area or R-Value R•Value U-Factor U-Factona: Perimeter Orientation:NORTH Exterior Wall 1:Wood-Framed,16"o.c.,[Bldg.Use 1-Retail] 957 21.0 0.0 0.062 0.064 Window 1:Metal Frame,Perf.Specs.:Product ID pending ID, 333 — 0.450 0 460 SHGC 0.40,[Bldg.Use 1-Retail](b) Orientation:EAST Exterior Wall 2:Wood-Framed.16"o.c.,[Bldg.Use 1 -Retail] 1449 21.0 0.0 0.062 0.064 Window 2:Metal Frame Curtain Wall/Storefront,Perf.Specs.: 591 — -- 0.450 0.450 Product ID pending ID,SHGC 0.40,[Bldg.Use 1-Retail](b) Orientation:SOUTH Exterior Wall 3:Wood-Framed,16"o.c.,[Bldg.Use 1-Retail] 957 21.0 0.0 0.062 0.064 Exterior Wall 4:Wood-Framed,16"o.c.,[Bldg.Use 1-Retail] 1290 21.0 0.0 0.062 0.064 Orientation:UNSPECIFIED ORIENTATION Roof 1:Insulation Entirely Above Deck,[Bldg.Use 1-Retail] 4206 — 38.0 0.026 0.348 (a)Budget U-factors are used for software baseline calculations ONLY,and are not code requirements. (b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in the plans/specs the requirement can be verified as being satisfied. Fenestration Product Rating: ® 1. U-factors of fenestration products(windows,doors and skylights)are determined in accordance with NFRC 100 by an accredited, independent laboratory,and labeled and certified by the manufacturer or are determined using the commercial size category values listed in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.4 and shall include the effects of the window frame. The temporary label afixed to the fenestration products must not be removed prior to inspection. Exception(s): ❑ Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills, center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be maintained on the jobsite and made available to the inspector. Plans reference page/section: A 1.0 Project Title: Report date: 10/17/18 Data filename; Untitled.cck Page 1 of 8 • a 2. Solar heat gain coefficient(SHGC)of glazed fenestration products(windows,glazed doors and skylights)shell be determined in accordance with NFRC 200 by an accredited,independent laboratory,and labeled and certified by the manufacturer or be determined using the Solar Heat Gain Coefficients(SHGC)in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.10.The overall values must consider type of frame material and operator for the SHGC at normal incidence. Exception(s): ❑ Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills, center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be maintained on the jobsite and made available to the inspector. Plans reference page/section: Al.0 Air Leakage, Insulation,and Component Certification: 3. Sealing of the building envelope.Openings and penetrations in the building envelope are sealed with caulking materials or closed with gasketing systems compatible with the construction materials and location,Joints and seams are sealed in the same manner or taped or covered with a moisture vapor-permeable wrapping material.Sealing materials spanning joints between construction materials allow for expansion and contraction of the construction materials. Plans reference page/section: A1.0 a 4. Window and door assemblies.The air leakage of window and sliding or swinging door assemblies that are part of the building envelope are determined in accordance with AAMAIWDMAlCSA 101/I.S.2/A440,or NFRC 400 by an accredited,Independent laboratory,and labeled and certified by the manufacturer. Exception(s): ❑ Site-constructed windows and doors that are weatherstripped or sealed in accordance with Section 502.4.3. Plans reference page/section: A1.0 Di 5. Curtain wall,storefront glazing and commercial entrance doors.Curtain wall,storefront glazing and commercial-glazed swinging entrance doors and revolving doors are tested for air leakage in accordance with ASTM E 283.For curtain walls and storefront glazing, the maximum air leakage rate is 0.3 cubic foot per minute per square foot of fenestration area.For commercial glazed swinging entrance doors and revolving doors,the maximum air leakage rate is 1.00 cfm/ft2 of door area, Exception(s): ❑ Requirement is not applicable. Plans reference page/section: A1.0 a 6. Building thermal envelope insulation.An R-value identification mark is applied(by manufacturer)to each piece of insulation 12 inches or greater in width.Alternately,the insulation installers have provided a signed,dated and posted certification listing the type, manufacturer and R-value of insulation installed.Refer to code section for blown or sprayed insulation installation/settling depths and marker requirements. (i 7. Insulation mark installation. Insulating materials are Installed such that the manufacturer's R-value mark is readily observable upon Inspection. a 8. Insulation product rating.The thermal resistance(R-value)of insulation has been determined in accordance with the U.S.FTC R-value rule. a 9. Installation.All material,systems and equipment are installed in accordance with the manufacturer's installation instructions and the International Building Code. 10.Outdoor air intakes and exhaust openings.Stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral to the building envelope shall be equipped with not less than a Class I motorized,leakage-rated damper with a maximum leakage rate of 4 cfm per square foot at 1.0 inch water gauge when tested in accordance with AMCA 500D.Stair and shaft vent dampers shall be capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection systems. Exception(s): ❑ Requirement is not applicable. Plans reference page/section: AI.5 ❑ 11.Loading dock weatherseals.Cargo doors and loading dock doors are equipped with weather seals to restrict infiltration when vehicles are parked in the doorway. Exception(s): Er Requirement is not applicable. Plans reference page/section: ❑ 12.Recessed lighting.Recessed luminaires installed in the building thermal envelope are sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires are IC-rated and labeled as meeting ASTM E 283.All recessed luminaires are sealed with a gasket or caulk between the housing and interior wall or ceiling covering. Exception(s): Q Requirement is not applicable. Project Title: Report date: 10/17/18 Dale filename: Untitled.cck Page 2 of 8 Plans reference page/section: ❑ 13.Vestibules.Doors that separate conditioned space from the exterior are protected with an enclosed vestibule,with all doors of the vestibule equipped with self-closing devices.Vestibules are designed so interior and exterior doors to not operate simultaneously. Exception(s): ❑ Doors not intended to be used as a building entrance door,such as doors to mechanical or electrical equipment rooms. ❑ Doors opening directly from a sleeping unit or dwelling unit. ❑ Doors that open directly from a space less than 3000 sq.ft.in area. ❑ Revolving doors. ❑ Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors. a Requirement is not applicable. Plans reference page/section: ❑ 14.'Other components have supporting documentation for proposed U-Factors. Exception(s): ® Requirement is not applicable. Plans reference page/section: Section 3: Compliance Statement Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications and other calculations submitted with this permit application.The proposed envelope system has been designed to meet the 2014 Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 4.1.0.0 and to comply with the mandatory requirements in the Requirements Checklist. Gary Womack-Abossein Enginering 10/17/18 Name-Title Signature Date Project Title: Report date: 10/17/18 Data filename: Untilled.cck Page 3 of 8 • v COMcheck Software Version 4.1.0.0 Mechanical Compliance Certificate Section 1: Project Information Energy Code:2014 Oregon Energy Efficiency Specialty Code Project Title: Project Type:New Construction Envelope Compliance Method:Simplified Trade-Off Construction Site: Owner/Agent: Designer/Contractor: Section 2: General Information Building Location(for weather data) Adair Village.Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity Spiker TypL&Description 1 HVAC System 1 (Single Zone):Single Package Heat Pump Healing Mode:Capacity=32600 kBtulh, Proposed Efficiency=3.60 COP.Required Efficiency=3.20 COP Cooling Mode:Capacity=57500 kBlulh,,Air Economizer Proposed Efficiency=12.50 EER,Required Efficiency: 9.50 EER +9.6 IPLV Fan System: None Section 4: Requirements Checklist In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section identifies where in the plans/specs the requirement can be verified as being satisfied. Requirements Specific To: HVAC System 1 : ❑ 1. Equipment meets minimum efficiency: Heat Pump: 3.20 COP 9.50 EER +9.6 IPLV ❑ 2. Energy recovery ventilation systems.Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. Exception(s): ❑ Where energy recovery systems are prohibited by the International Mechanical Code. • Systems serving spaces that are not cooled and are heated to less than 60°F. ❑ Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy. ❑ Type 1 kitchen exhaust hoods. • Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64°F(18°C). ❑ Systems requiring dehumidification that employ series-style energy recovery coils wrapped around the cooling coil when the evaporative coil is located upstream of the exhaust air stream. ❑ Systems exhausting toxic,flammable,paint exhaust,corrosive fumes,or dust. ❑ Laboratory fume hood systems that include qualifying features. Plans reference page/section: ® 3. Supply air economizers shall be provided on each cooling system and are capable of providing 100-percent outdoor air,even if additional mechanical cooling is required to meet the cooling load of the building.Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. Exception(s): ❑ Cooling equipment less than 54,000 Btu/hr total cooling capacity. Project Title: Report date: 10/17/18 Data filename. Untitled.cck Page 4 of 8 4. Plans reference page/section: Generic Requirements: Must be met by all systems to which the requirement is applicable: 41 1. Calculation of heating and cooling loads.Design loads are determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure. la 2. Equipment and system sizing.Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance with Section 503.2.1. Exception(s): ❑ Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. ❑ Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. Plans reference page/section: M1.0 a 3. HVAC Equipment Performance Requirements.Reported efficiencies have been tested and rated in accordance with the applicable test procedure.The efficiency has been verified through certification under an approved certification program or,if no certification program exists,the equipment efficiency ratings are supported by data furnished by the manufacturer. ut 4. Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that respond to temperature within the zone. Plans reference page/section: M2.0 ® 5. Heat pump supplementary heat.Heat pumps having supplementary electric resistance heat have controls that,except during defrost, prevent supplementary heat operation when the heat pump can meet the heating load. Plans reference page/section: MI.0 6. Set point overlap restriction.Where used to control both heating and cooling,zone thermostatic controls provide a temperature range or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum. Exception(s): ❑ Thermostats requiring manual change over between heating and cooling modes. Plans reference page/section: M1.0 ❑ 7. Optimum Start Controls.Each HVAC system has controls that vary the startup time of the system to just meet the temperature set point at time of occupancy. Plans reference page/section: ❑ 8. Off-hour controls.Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system. Exception(s): Zones that will be operated continuously. ❑ Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff switch. Plans reference page/section. ❑ 9. Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. Exception(s): a Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less. Plans reference page/section: ❑ 10.Freeze Protection and Snow melt system controls.Freeze protection systems,such as heat tracing of outdoor piping and heat exchangers,including self-regulating heat tracing,include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Plans reference page/section: ❑ 11.Zone Isolation Controls.A system serving multiple occupancies or floors in the same building is independently zoned and equipped with isolation devices. Plans reference page/section: u 12.Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions;or shall include supplementary control provisions so that the primary systems may be specifically controlled for comfort purposes only. Project Title: Report date: 10/17/18 Data filename: Untitled.cck Page 5 of 8 Exception(s): 0 [503.2.4.8+j Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. Plans reference page/section: ❑ 13.Humidity control.If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or zones,a humidity control device is provided. • Plans reference page/section: ❑ 14.Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative humidity in excess of 30 percent.Where a humidity control device is used for dehumidification,it is set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60 percent. Exception(s): ❑ Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity requirements outside this range. Plans reference page/section: Q 15.Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity where no active humidification or dehumidification takes place. Exception(s): ❑ Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in section 503.2.3,HVAC equipment performance requirements. Plans reference page/section: 16.Ventilation.Ventilation,either natural or mechanical,is provided in accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code. Plans reference page/section: M1.0 ❑ 17.Demand controlled ventilation(DCV).DCV is required for spaces larger than 500 fl2 for simple systems and spaces larger than 150(12 for multiple zone systems. Exception(s): ❑ Systems with energy recovery complying with Section 503.2.6 Li Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan off,closes the ventilation damper,or closes the zone damper when the space is unoccupied. Plans reference page/section: ❑ 18.Kitchen hoods.Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. Exception(s).' ❑ Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. ❑ Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. Plans reference page/section: ❑ 19.Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling automobiles employs automatic carbon monoxide sensing devices. Plans reference page/section: 20.Duct and plenum insulation end sealing.All supply and return air ducts and plenums are insulated with the specified insulation.When located within a building envelope assembly,the dud or plenum is separated from the building exterior or unconditioned or exempt spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams comply with Section 603.9 of the International Mechanical Code. Exception(s): ❑ When located within equipment. ❑ When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F(6°C). 21.Low-pressure duct systems.All longitudinal and transverse joints,seams and connections of tow-pressure supply and return ducts are securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or tapes installed in accordance with the manufacturer's installation instructions. Exception(s): ❑ Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification. Project Title: Report date: 10/17/18 Data filename: Untitled.cck Page 6 of 8 Plans reference page/section: ❑ 22.Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed in accordance with Section 503.2.7.Pressure classifications specific to the duct system are clearly indicated on the construction documents. Plans reference page/section: ❑ 23.High-pressure duct systems.Ducts designed to operate at high-pressure are insulated and sealed in accordance with Section 503.2.7. In addition,ducts and plenums are leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Plans reference page/section: 24.Air system balancing.Each supply air outlet and zone terminal device is equipped with means for air balancing in accordance with the requirements of IMC 603.17.Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable volume Fans with motors 10 horsepower. Plans reference page/section: MI.0 • 25.Manuals.The construction documents require that an operating and maintenance manual be provided to the building owner by the mechanical contractor.See long description for specifications. Plans reference page/section: M1.0 ❑ 26.Air System Design and Control.Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503.2.10.2. Plans reference page/section: B 27.Altowable fan floor horsepower.Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated In requirement details. Exception(s): ❑ Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. ❑ Individual exhaust fans with motor nameplate horsepower of 1 hp or less. Plans reference page/section: 28.Motor nameplate horsepower,For each fan,the selected fan motor is no larger than the first available motor size greater than the brake horsepower(bhp). Exception(s): ❑ For fans less than 8 bhp,where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp,selection of the next larger nameplate motor size is allowed. ❑ For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. Plans reference page/section: ❑ 29.Large Volume Fan Systems.Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve single zones reduce airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code,whichever is greater. Exception(s): ❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity levels or supplying an exhaust system. Plans reference page/section: ❑ 30.All air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than or equal to 110,000 6lu/h that serve single zones have their supply fan operation controlled according to code specific requirements. Excepton(s): ❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity levels or supplying an exhaust system. Plans reference page/section: ❑ 31.Series fan-powered terminal unit fan motors.Fan motors for series fan-powered terminal units are electronically-commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating conditions. Plans reference page/section: Project Title: Report date: 10/17/18 Data filename: Untitled.cck Page 7 of 8 a Section 5: Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications and ether calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2014 Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 4.1.0.0 and to comply with the mandatory requirements in the Requirements Checklist. Gary Womack-Abossein Engineering °Ytny � 10/17/18 Name-Title Signs re /'f QL fZI/L_Date Section 6: Post Construction Compliance Statement • HVAC record drawings of the actual installation,system capacities,calibration information,and performance data for each equipment provided to the owner. • HVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor. o Written HVAC balancing and operations report provided to the owner. The above post construction requirements have been completed. Principal Mechanical Designer-Name Signature Date � s Project Title: Report date: 10/17/18 Dale filename: Untitled cck Page B of 8 5291654-BIG-A-1116 1(/i'i/..ra .$a hij1)1 � !U„ �����\ % iiii�I COIL GUARD HIGH VOLTAGE \`\t. \� C HIGH VOLTAGE CONNECTION 7/8" � � v �� I iii/ CONNECTION 1-3/32" IIII �� i�C I HEAT EXCHANGER COMPRESSOR -pa- ACCESS PANEL ACCESS PANEL rill 1 CONDENSATE �� DRAIN BLOWER B ACCESS CONTROL ACCESS +. LOW VOLTAGE CONNECTION PANEL PANEL HomeDill UNIT DIMENSIONS Model Dimensions A B C PHE6B3631 51-1/4 45-3/4 49 1 PHE6B41331 51-1/4 45-3/4 53 j PHE6B6031 51-1/4 45-3/4 55 UNIT CLEARANCES Direction Distance(in.) Direction Distance(in.) Top1 36 Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom 2 3 1 1. Minimum Clearance of linch all sides of supply air duct for the first 3 foot of duct for 20&25 kW.,zero inches there after.For all other heaters,zero inch clearance all sides for entire length of duct. 2. Units must be installed outdoors.Over hanging structure or shrubs should not obscure outdoor air discharge outlet. 3. Units may be installed an combustible floors made from wood or class A,B or C roof covering materials. Note:For units applied with a roof curb,the minimum clearance may be reduced from 1 inch to 1/2 inch?between combustible roof curb material and this supply air duct. 14 Johnson Controls Unitary Products