Report "OFFICE COPY FPS2 2 -C2V/4'9 E EIVE /a5 5 ��Oleci5 Worldwide tqco DEC 14 2021 Contacts www.tyco-fire.com CITY OF TIGARD 3UILDINQ DIVISION Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General passed standard corrosion tests of the applicable approval agencies, this N �� testing is not representative of all pos- sible corrosive atmospheres. Conse q TYCO Series EC 11 and EC 14 fluently,it is recommended that the end ," i .T Extended Coverage Upright and user be consulted with respect to the ., Pendent Sprinklers are decorative suitability of these corrosion-resistant `' ` glass-bulb sprinklers designed for use coatings for any given corrosive envi in light or ordinary hazard occupancies. ronment. The effects of ambient tern- r„ They are intended for use in automatic perature, concentration of chemicals, T r . and gas/chemical velocity should be '�� i x sprinkler systems designed in rules considered, along with the corrosive f _= ,.. =y= dance with standard installation rules, nature of the chemical to which the such as NFPA 13,for a maximum cov- erage area of 400 ft2(37,2 m2)as corn sprinklers will be exposed. pared to the maximum coverage area of 130 ft2(12,1 m2)for standard cover- NOTICE age sprinklers used in ordinary hazard Series EC-11 and EC-14 Extended Cov- ,or' a occupancies, Series EC-11 and EC-14 erage Sprinklers described herein must Extended Coverage Sprinklers feature be installed and maintained in compli- a UL and C-UL Listing that permits their ance with this document, as well as fi, use with unobstructed or non-combus- with the applicable standards of the tible obstructed ceiling construction as NFPA, in addition to the standards of defined and permitted by NFPA 13, as any other authorities having jurisdiction. ' well as a specific application listing for Failure to do so may impair the perfor- use under concrete tees. mance of these devices. Series EC-11 and EC-14 Extended Coy- The owner is responsible for main- Technical erage Sprinklers have been fire tested taining their fire protection system Data . to compare their performance to that and devices in proper operating con- of standard coverage spray sprinklers. dition. Contact the installing contrac- These tests have shown that the pro- tor or product manufacturer with any Aprovals tectionprovided is equal to or more TYCO Series Coverage and EC 1d 4 questions. Extended Upright and effective than standard coverage spray Pendent Sprinklers are UL and C-UL sprinklers. P Sprinkler Listed. Refer to Table A for complete Corrosion-resistant coatings, where sprinkler approval information including applicable, help extend the life of Identification corrosion-resistant status.The approv- copper alloy sprinklers beyond that als apply to the service conditions indi- which occurs when exposed to Numbers cated in the Design Criteria section. corrosive atmospheres. Although corrosion-resistant coated sprinklers TY5137 Upright, 11.2K Series EC-11 and EC-14 Extended Cov TY5237 Pendent, 11.2K erage Sprinklers are FM Approved. TY6137 Upright, 14.0K Refer to Table A for complete sprinkler IMPORTANT approval information including corro- Refer to Technical Data Sheet TY6237 Pendent, 14.0K sion-resistant status. The approvals Refer 0 for warnings pertaining to TY5137 is a re-designation for C5137,G1894,and S2510 apply to the service conditions indi- TY5237 is a re-designation for C5237,G1893,and 82511 cated in the Design Criteria section. regulatory and health information. TY6137 is a re-designation for C6137,G1896,and S2610 TY6237 is a re-designation for C6237,G1895,and S2611 Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 OCTOBER 2018 TFP220 • TFP220 Page 2 of 8 WRENCH 3/4" ESCUTCHEON PLATE Components: FLAT NPT** SEATING SURFACE 1 1 - Frame 2 - Button zej‘l p ii —w,A� 3 - Sealing Assembly thlii �� 2 4 - Bulb 5 - Compression Screw ' 2-7/16" 6 Deflector • (61,9 mm) :II 0' I 3 UPRIGHT& Temperature rating is PENDENT I 1-11/16" ---- -- 4 indicated on Deflector. 't (42,7 mm) **Pipe thread connections per .�.�kio 5 ISO 7-1 can be provided on special request. 1/2"(12,7 mm) j 6* NOMINAL MAKE-IN CROSS UPRIGHT PENDENT SECTION FIGURE 1 SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS 11.2 K-FACTOR UPRIGHT(TY5137)AND PENDENT(TY5237) 14.0 K-FACTOR UPRIGHT(TY6137)AND PENDENT(TY6237) ASSEMBLY The Style 60 Two-Piece Flush Escutch- Dk es /�n •• Obstructed, non-combusti- eon(Figure 4)is UL Listed for use with 7 ble, ceiling construction with a the Series EC-11 and EC-14 Pendent Criteria deflector location below struc- Sprinklers. tural members of 1 to 6 in. Maximum Working Pressure TYCO Series EC-11 and EC-14 (25 to 150 mm) and a maximum 175 psi(12,1 bar) Extended Coverage Upright and deflector to ceiling/roof deck dis Pendent Sprinklers must only be tance of 22 in.(550 mm). Pipe Thread Connection installed in accordance with the appli- 3. Series EC-11 and EC-14 Extended 3/4 in. NPT cable UL and C-UL Listing or FM Coverage Sprinklers, specifically Discharge Coefficients Approval requirements as indicated tested and listed for non-combus- K= 11.2 GPM/psi!(161,3 LPM/bar%) below. Only Style 30 or 40 Recessed tible obstructed construction, are . K=14.0 GPM/psis(201,6 LPM/bar'/) Escutcheons are to be used for permitted to be used within truss- recessed installation, as applicable. es or bar joists having non-com- Temperature Ratings Refer to Tables A, B, and C, for more bustible web members greater Refer to Table A information. than 1 in. (25.4 mm) when apply- • Finish UL and C-UL ing the 4 times obstruction crite- Sprinkler: ria rule defined under "Obstruc- Refer to Table A Listing Requirements tions to Sprinkler Discharge Pattern 1. Series EC-11 and EC-14 Extended Development". Recessed or Flush Escutcheon: Coverage Sprinklers may be used White-Coated, Chrome-Plated, and for the coverage areas shown in 4. To prevent cold soldering, the Brass-Plated Table D, based on maintaining the minimum allowable spacing Physical Characteristics be- minimum specified flow rate as a tween Series EC-11 and EC-14 Ex- Frame Bronze function of coverage area and haz- tended Coverage Sprinklers is 8 ft Button Bronze and group for all sprinklers in the (2,4 m)for upright sprinklers and 9 ft Sealing Assembly .Beryllium Nickel w/TEFLON design area. (2,7 m)for pendent sprinklers. Bulb Glass(3 mm) 2. Series EC-11 and EC-14 Extended 5. Series EC-11 and EC-14 Extended Compression Screw Bronze Deflector Brass Coverage Sprinklers are permitted Coverage Sprinklers are to be in- to be used with unobstructed or stalled in accordance with all oth- Operation non-combustible obstructed ceil- requirements of NFPA 13 for ing construction as defined and extended coverage upright and The glass bulb contains a fluid that permitted by NFPA 13;for example: pendent sprinklers; For exam- expands when exposed to heat.When • Unobstructed, combustible or ple, obstructions to sprinkler dis- the rated temperature is reached, the noncombustible, ceiling con charge, obstructions to sprinkler fluid expands sufficiently to shatter struction with a deflector to pattern development, obstructions the glass bulb, which- then allows the ceiling/roof deck distance of to prevent sprinkler discharge from sprinkler to activate and flow water. 1 to 12 in. (25 to 300 mm). reaching hazard and clearance to storage. TFP220 Page 3 of 8 Bulb Sprinkler Finish(See Note 5) Hazard Type Temperature Liquid Natural Chrome Lead Brass Plated Polyester' Coated 135°F(57°C) Orange Upright K=11.2(TY5137) 155°F(68°C) Red 1,2,3",4 Light Pendent 175°F(79°C) Yellow K=11.2(TY5237) 200°F(93°C) Green Table B describes K=14.0(TY6237) 1,2,4 1,2,4 UL and C-UL 286°F(141°C) Blue Sensitivity Rating 135°F(57°C) Orange Table C describes Recessed Pendent 1,2,3,4 FM K=11.2(TY5237) 155°F(68°C) Red Sensitivity Rating K=14.0(TY6237) 175°F(79°C) Yellow N/A With Style 30 200°F 200 93°C Escutcheon ( ) Green 1,2,4 286°F(141°C) Blue Upright 135°F(57°C) Orange K=11.2(TY5137) 155°F(68°C) Red 1,2,3,4 Ordinary K=14.0(TY6137) 175°F(79°C) Yellow 1,2,3,4 Pendent Table B describes K=11.2(TY5237) 200°F(93°C) Green 1,2,4 UL and C-UL K=14.0(TY6237) 286°F(141°C) Blue Sensitivity Rating Table C describes Recessed Pendent 135°F(57°C) Orange FM K=11.2(TY5237) 155°F(68°C) Red Sensitivity Rating K=14.0(TY6237) 1,2,4 N/A With Style 30 or 40 175°F(79°C) Yellow Escutcheon 200°F(93°C) Green NOTES 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL) 3. Approved by Factory Mutual Research Corporation(FM) 4. Approved by the City of New York under MEA 177-03-E 5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers N/A=Not Available Frame and Deflector only '*Pendent only TABLE A LABORATORY LISTINGS AND APPROVALS Light Hazard Ordinary Hazard Area ft x ft Style 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F (57°C) (68°C) (79°C) (93°C) (141°C) (57°C) (68°C) (79°C) (93°C) (141°C) Upright or Pendent - - - - - QR QR OR OR QR 14 x 14 Style 30 Recessed - - - - - OR QR QR OR QR Style 40 Recessed - - - - - QR QR QR OR OR Upright or Pendent QR* QR* QR* QR* QR* SR SR SR SR SR 16 x 16 Style 30 Recessed OR* QR* QR* QR* QR* SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent OR* QR* QR* QR* OR* SR SR SR SR SR 18 x 18 Style 30 Recessed QR* QR* QR* QR* QR* SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR Upright or Pendent QR* QR* QR* SR* SW SR SR SR SR SR 20 x 20 Style 30 Recessed QR* QR* OR* SR* SW SR SR SR SR SR Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR NOTES • OR=Quick Response • SR=Standard Response • N/A=Not Applicable 'Does not apply to Upright K=14.0 TABLE B SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS (REFER TO TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS) TFP22O Page 4 of 8 HC-1 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max Noncombustible Unobstructed,10 20 100 400 Up to 30 Noncombustible Obstructed,or 11.2 EC Pendent or14.0 EC Upright Combustible Unobstructed Noncombustible Unobstructed, Pendent 11.2 EC 10 20 100 400 Up to 30 Noncombustible Obstructed,or 14.0 EC Recessed Combustible Unobstructed Style 30 10 20 100 400 Up to 30 Combustible Obstructed 11.2 EC Pendent or 14.0 EC Upright Quick Pendent 11.2 EC 10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Recessed Style 30 10 20 100 400 Over and Noncombustible Unobstructed 11.2 EC Upright P 14.0 EC HC-2 Linear Spacing Area Spacing ft ft Ceiling Height ft Ceiling Type K-factor Style Response Min Max Min Max 10 20 100 400 Up to 30 11.2 EC Upright 10 20 100 400 Up to 30 14.0 EC Pendent or Noncombustible Unobstructed, Upright Quick Combustible Unobstructed 10 16 100 256 Over3 to 045 and 11.2 EC 14.0 Upright upEC HC-3 Linear Spacing Area Spacing ft ft Ceiling Height Ceiling Type K-Factor Style Response ft Min Max Min Max 10 16 100 256 Up to 30 11.2 EC Upright 10 20 100 400 Up to 30 14.0 EC Pendent or Noncombustible Unobstructed, Upright Quick Combustible Unobstructed 10 16 100 256 Over 30 and 11.2 EC, up to 45 14.0 EC Upright NOTES • The design for K 11.2 EC(K 160 EC)sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi(0,8 bar);similarly the design for K 14.0 EC(K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi(1,2 bar). • For flow criteria,refer to FM Loss Prevention Data Sheet 3-26. • Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations. TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS UL and C-UL Specific Application depth of the concrete tees must not 3. When the sprinkler deflectors are Listing Requirements for exceed 30 in. (762 mm). The maxi- located higher than a horizontal Installation under Concrete Tees mum permitted concrete tee length plane 1 in. (25,4 mm) beneath the Series EC-11 and EC-14 Extended Coy- is 32 ft(9,8 m). However, where the bottom of the concrete tee stems, erage Upright and Pendent Sprinklers concrete tee length exceeds 32 ft the obstruction to sprinkler dis- (TY5137,TY5237,TY6137 and TY6237) (9,8 m), non-combustible baffles, charge criteria requirements of have a UL and C-UL Specific Applica- equal in height to the depth of the NFPA 13 for extended coverage Son Listing for use under concrete tees tees, can be installed so that the upright and pendent sprinklers when installed as follows: space between the tees does not applies. 1. Stems of the concrete tee con exceed 32 ft(9,8 m) in length. struction must be spaced at less 2. The sprinkler deflectors are to be than 7.5 ft (2,3 m) on center but located in a horizontal plane at or more than 3 ft(0,9 m)on center.The above 1 in. (25,4 mm) below the bottom of the concrete tee stems. TFP220 Page 5 of 8 Light Hazard Group I Group II Description Area 0.10 GPM/ft2 Ordinary Hazard Ordinary Hazard P ft x ft 0.15 GPM/ft2 0.20 GPM/ft2 GPM PSI GPM PSI GPM PSI 14 x 14 30 7.2 30 7.2 39 12.1 TY5137 16 x 16 30 7.2 39 12.1 51 20.7 (K=11.2)Upright 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 14 x 14 30 7.2 30 7.2 39 12.1 TY5237 16 x 16 30 7.2 39 12.1 51 20.7 (K=11.2)Pendent 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 14 x 14 N/A N/A 39 7.8 51 13.3 TY6137 16 x 16 N/A N/A 39 7.8 51 13.3 (K=14.0)Upright 18 x 18 N/A N/A 49 12.3 65 21.6 20 x 20 N/A N/A 60 18.4 80 32.7 14 x 14 37 7.0 39 7.8 51 13.3 TY6237 16 x 16 37 7.0 39 7.8 51 13.3 (K=14.0)Pendent 18 x 18 37 7.0 49 12.3 65 21.6 20 x 20 40 8.2 60 18.4 80 32.7 NOTES • 1 ft=0.3048 m • 1 ft2=0.093 m2 • • 1 GPM=3.785 LPM • 1 psi=0.06895 bar • 1 GPM/ft2=40.74 mm/mm TABLE D FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS 1 FM Approval Requirements eon Plate by under or over-tightening Series EC-11 and EC-14 Extended Installation the Sprinkler. Re-adjust the position of Coverage Upright and Pendent Sprin- TYCO Series EC 11 and EC 14 the sprinkler fitting to suit. klers are to be installed in accor- Extended Coverage Upright and 91. Install the sprinkler dance with the applicable Step nkler with the cable FM LP pp Loss Pendent Sprinklers must be installed deflector parallel to the mounting in buildings of specific roof construc in accordance with this section. surface. Install pendent sprinklers in tion and for the protection of certain General Instructions the pendent position; install upright specific ordinary hazard (non-storage Do not install any bulb-type sprinkler sprinklers in the upright position. and/or non-flammable or combustible if the bulb is cracked or there is a loss Step 2.After installing the Style 30,40, liquid) occupancies. Information pro- of liquid from the bulb. With the sprin- or 60 mounting plate(or other applica- vided in the FM Loss Prevention Data kler held horizontally,a small air bubble ble escutcheon)over the sprinkler pipe Sheets relates to, but is not limited to, should be present.The diameter of the threads and with pipe-thread sealant hydraulic design, ceiling slope, and air bubble is approximately 1/16 in. applied to the pipe threads, hand- obstructions, minimum and maximum (1,6 mm) for the 135°F (57°C) to tighten the sprinkler into the sprinkler allowable spacing, and deflector-to- 3/32 in. (2,4 mm)for the 286°F(141°C) fitting. ceiling distance. temperature ratings. Step 3. For upright or pendent sprin- These criteria may differ from UL A leak-tight 3/4 in. NPT sprinkler klers, wrench-tighten using only the and/or NFPA criteria. Therefore, the joint should be obtained by apply- W-Type 3 (End A) Sprinkler Wrench. designer should review and become ing a minimum-to-maximum torque of For the pendent sprinkler installed familiar with FM requirements before 10 to 20 ft-lb(13,4 to 26,8 N•m). Higher with Style 30, 40, or 60 Escutcheon, proceeding with design. levels of torque may distort the sprin- wrench-tighten the sprinkler using only kler inlet with consequent leakage or the W-Type 22 Sprinkler Wrench. impairment of the sprinkler. Apply the wrench recess of the appli- Do not attempt to compensate for cable sprinkler wrench(Figure 5 and 6) insufficient adjustment in an Escutch- to the sprinkler wrench flats(Figure 1). TFP220 Page 6 of 8 2 7/8" DIA. 2 7/8"DIA. 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (12,7±3,2 mm) 2-1/4"DIA. _ 1/4"(6,4 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) FACE OF (57,2 mm) - FACE OF (57,2 mm) SPRINKLER 1/8" 8" • FITTING (3,2 mm) SPRINKLER FITTING (3,22 mm) / MOUNTING t \ v r SURFACE MOUNTING t PLATE MOUNTING MOUNTING CLOSURE r SURFACE PLATE CLOSURE 1-3/8"(34,9 mm) 1-3/8"(34,9 mm) 1-1/8"(28,6 mm) 7/8"(22,2 mm) FIGURE 2 FIGURE 3 SERIES EC-11 AND EC-14 RECESSED SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 1/2 IN. TOTAL ADJUSTMENT WITH TWO-PIECE 3/4 IN. TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON STYLE 40 RECESSED ESCUTCHEON 2-7/8" DIA. "FITTING SIDE" (73,0 mm) TOWARDS SPRINKLER 2 1/4" INTERNAL FITTING (57,2 mm)DIA. - DIMENSIONS OF STYLE 60 ESCUTCHEON ACCOMMODATE ..-0\ CLASS 150 MALLEABLE FACE OF IRON REDUCING / SPRINKLER FITTING: SPRINKLER FITTING WRENCH 3/8"(9,5 mm)ABOVE / TO 1/8"(3,2 mm)BELOW MOUNTING RECESS (END"A") 1/8" MOUNTING SURFACE SURFACE (3,2 mm) I FIGURE 5 W-TYPE 3 SPRINKLER ESCUTCHEON PLATE V WRENCH • SEATING SURFACE: CLOSURE 1/4"(6,4 mm)ABOVE 2-5/16"(58,7 mm) TO 1/2"(12,7 mm)BELOW 3/4"NPTWRENCH MOUNTING SURFACE; MOUNTING 1-13/16"(46,0 mm) RECESS 3/4"(19,1 mm)TOTAL PLATE ADJUSTMENT FIGURE 4 SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY , ft ., WITH 3/4 IN. TOTAL ADJUSTMENT STYLE 60 TWO-PIECE FLUSH ESCUTCHEON t ; 4• o WRENCH HEX FIGURE 6 W-TYPE 22 RECESSED SPRINKLER WRENCH TFP220 Page 7 of 8 P/N 51 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH1 RATING 893 11.2K Pendent TY5237 1 NATURAL BRASS 135 135°F(57°C) 894 11.2K Upright TY5137 4 SIGNAL WHITE 155 155°F(68°C) (RAL9003) POLYESTER 895 14.0K Pendent TY6237 JET BLACK(RAL9005) 175 175°F(79°C) 5 POLYESTER 896 14.0K Upright TY6137 200 200°F(93°C) 7 LEAD COATED 286 286°F(141°C) 9 CHROME-PLATED 000 OPEN2 NOTES: 1. Escutcheon ordered separately. 2. OPEN indicates the sprinkler assembly without glass bulb,button,and sealing assembly. TABLE E SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Care and be replaced.Also,replace any sprinkler Limited that has a cracked bulb or that has lost Maintenance liquid from its bulb. Refer to the Instal- lation section,for more information. TYCO Series EC-11 and EC-14 Frequent visual inspections are rec- For warranty terms and conditions,visit Extended Coverage Upright and ommended to be initially performed www.tyco-fire.com. Pendent Sprinklers must be maintained for corrosion resistant coated sprin- and serviced in accordance with this klers, after the installation has been Ordering section. completed,to verify the integrity of the Before closing a fire protection system corrosion resistant coating.Thereafter, Procedure main control valve for maintenance annual inspections per NFPA 25 should work on the fire protection system suffice; however, instead of inspecting Contact your local distributor for that it controls, obtain permission to from the floor level,a random sampling availability. When placing an order, shut down the affected fire protection of close-up visual inspections should indicate the full product name and Part systems from the proper authorities be made,so as to better determine the Number(P/N). and notify all personnel who may be exact sprinkler condition and the long S rinkler Assemblies with affected by this action. term integrity of the corrosion resistant p coating, as it may be affected by the NPT Thread Connections Sprinklers which are found to be corrosive conditions present. Specify: Series EC-11 or EC-14 leaking or exhibiting visible signs of (specify) Sprinkler, SIN (specify), corrosion must be replaced. The owner is responsible for the (specify) K-factor, Pendent or Upright inspection, testing, and maintenance (specify)Extended Coverage,(specify) Automatic sprinklers must never be of their fire protection system and temperature rating,(specify)finish,P/N painted, plated, coated, or other- devices in compliance with this doc- (from to Table E) wise altered after leaving the factory. ument, as well as with the applicable Modified sprinklers must be replaced. standards recognized by the Approval Recessed Escutcheon,Two-Piece Sprinklers that have been exposed to agency,such as NFPA 25,in addition to Specify: Style (30 or 40) Two-Piece corrosive products of combustion, but the standards of any authorities having Recessed Escutcheon with (specify) have not operated,should be replaced jurisdiction.Contact the installing con- finish, P/N (specify") if they cannot be completely cleaned tractor or product manufacturer with 'Refer to Technical Data Sheet TFP770 by wiping the sprinkler with a cloth or any questions. Flush Escutcheon,Two-Piece by brushing it with a soft bristle brush. Automatic sprinkler systems are rec- Specify: Style 60 Two-Piece Flush Care must be exercised to avoid ommended to be inspected, tested, Escutcheon with (specify) finish, P/N damage to the sprinklers before, and maintained by a qualified Inspec- (specify") during, and after installation. Sprin- tion Service in accordance with local -Refer to Technical Data SheetTFP778 klers damaged by dropping, striking, requirements and/or national codes. wrench twist/slippage,or the like,must Sprinkler Wrenches Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001 Specify:W-Type 22 Recessed Sprinkler Wrench, P/N 56-665-7-001 TFP220 Page 8 of 8 • 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 e 2010 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson IS{o11�v ,I NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls I l.fol5 TEFLON is a registered trademark of DuPont OFFICE COPY c y D Worldwide ContactsE VIED Fire Protection www.tyco-fire.com DEC I. 4 Girl Products VITY OF TIGARD Gem 7UILDING DIVISION Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers - f, '' Description described herein must be installed and ,.,1 ` , maintained in compliance with this doc- - The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable 1 Upright(TY313) and Pendent(TY323) standards of the National Fire Protec- ; Sprinklers described in this data sheet tion Association,in addition to the stan- are quick response,standard coverage, dards of any other authorities having tom" ' decorative 3 mm glass bulb-type spray jurisdiction. Failure to do so may impair sprinklers designed for use in light or the performance of these devices. "` - ordinary hazard,commercial occupan- : cies such as banks, hotels, and shop- The owner is responsible for maintain- k..,,` ping malls. ing their fire protection system and " ' T devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed p Escutcheon with recessed adjust- Identification ment up to 5/8 inch (15,9 mm) from "" > the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT ; ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT , the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) UL and C-UL Listed 200°F(93°C) TY-FRB Sprinklers are described in 286°F(141°C) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper *The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi112(80,6 LPM/barll2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- • age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. • 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* Iter,...., i 5-- .l 7/16" (11,1 mm) 4I NOMINAL 2" 0 _,0 MAKE IN (50,8 mm) v, 2 r a` 2" \�� `�/ 1-3/8" 3 I. f (50,8 mm) (34,9 mm) , WRENCH 1 7 t I FLATS 1/2"NPT** DEFLECTOR* --.-- 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE �, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to General Instructions FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air bub- WRENCH Criteria ble should be present. The diameter RECESS of the air bubble is approximately 1/16 The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) � ��—f Sprinklers are intended for fire protec- temperature ratings. • /F tion systems designed in accordance 714H with the standard installation rules rec A leak tight 1/2 inch NPT sprinkler joint should be obtained b a I in a min- ognized by the applicable Listing or y pp y g Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 L di e is based on the requirements of NFPA ft. lbs. (9,5 to 19,0 Nm). Higher levels .. 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).OnlyStyle 15 Style of the sprinkler. IN TO ENSURE the or y ENGAGEMENT 20 Recessed Escutcheon is to be used Do not attempt to compensate for WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch- WRENCHING AREA eon Plate by under-or over-tightening the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler • fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8" DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF — (57,2 mm) Torque sprinklers 7 to 14 ft.-lbs. (9,5 to SPRINKLER • 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers l 1 - FLUSH _ The Series TY-FRB Recessed Pendent 3/8±5/16" �` 1 Sprinklers must be installed in accor- (9,5±7,9 mm) % - '% dance with the following instructions. } / �, Step A.After installing the Style 15 or MOUNTING �'' 1/8" i Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread --_--- sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) sprinkler fitting. Step B.Tighten the sprinkler into the FIGURE 4 Step B. fitting using onin the in Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7spri Recessed Sprinkleruin Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8"DIA. - sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA. ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in + FLUSH contact with the ceiling. 1` -1 T 7 Care and t I + MOUNTING 1/8" Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) • Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. Absence of the outer piece of an if they cannot be completely cleaned by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, ii a clearance hole, can delay sprinkler and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like, must be replaced. with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2-NPT) TY313 3 PURE WHITE(RAL9010)** 155 155°F(68°C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 4 SIGNAL WHITE(RAL9003) 175 175°F 79°C POLYESTER* ( ) Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F for example,77-370-4-175-1 (93°C) Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6,Quick Response,(specify)tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N(specify*) Specify: Style 20 Recessed Escutch- • eon with(specify*)finish, P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 ' F GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Fire Protection Products