Report (2) g
+� .202.( - 00954_ RECEIVED
Li ('off F() y NOV 15 2021
1 T I G A R D A F C CITY OF TIGARD
BUILDING DIVISION
-MECHANICAL CUT SHEETS 11/09/2021
48TC-7.5T-E-3PH
NO EXCEPTIONS NOTED [) REJECTED [ ]
B ROA E 80 BSpec MAKE CORRECTIONS NOTED [ ] REVISE AND RESUBMIT [ ]
THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN
Carrier Thermostat CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS
NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN
REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF
ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE
E C D-S RT34CA-D 2 D H CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR
OR DEVIATION FROM CONTRACT DOCUMENTS.
CIDA
I M—PY4G-10 COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE
PORTLAND,OREGON
REVIEWED 11/09/2021,BY curtisg
model-5700-submittals-16982
model-7600-submittals-398
Project:
Tag: METALAIREn.
Engineer: OFFICE COPY
Contractor: ®T Submittal:b m itta I. 5700
Date: RECEIVED
Square Face Diffusers
2 Cone - Round Neck NOV 15 2021
Models: Steel Aluminized Steel Aluminum
❑5700-1 ❑5700-1 AS El 5700-1AL Surface Mount CITY OF TIGARD
05700-6 ❑5700-6 AS 0 5700-6 AL Lay in T-Bar BUILDING DIVISION
05700-6P 0 5700-6P AL Lay in T-Bar Panel
5700-7 5700-7 AS Concealed T-Bar
5700-9 5700-9 AS 5700-9 AL Bolt Slot/Donn Fineline (USG)Ceiling Grid
Models: 5700-1 (Steel-Surface Mount-24 x 24) Models: 5700-1 (Steel-Surface Mount-12 x 12)
_5700-1 AS (Aluminized Steel Surface Mount-24 x 24) _5700-1 AS (Aluminized Steel Surface Mount-12 x 12)
5700-1 AL (Aluminum-Surface Mount-24 x 24) _5700-1 AL (Aluminum-Surface Mount-12 x 12)
Neck Size-1 Neck Size-8 r 1Earthquake Tab 8 r 1 e _1
Latch Tabs 1 (4) 5700 Latches
2 3 \ 3 8 50
° } � 3 4
8 1 _}
} 1 4 r �.
_ Ceiling Opening=9}x 9} }
Ceiling Opening=21 4 x 21 4 Overall Diffuser=11 i x 11 a -
Overall Diffuser=23 4 x 23 4 For surface mount installations,use of plaster frame is recommended.
For surface mount installations,use of plaster frame is recommended. Available Neck Sizes 6&8
Available Neck Sizes 6,8,10,12,14,15
Models: _ 5700-6 (Steel-Lay in T-Bar-24 x 24) Models: _5700-6 (Steel-Lay in T-Bar-12 x 12)
5700-6 AS (Aluminized Steel Lay in T-Bar-24 x 24) 5700-6 AS (Aluminized Steel Lay in T-Bar-12 x 12)
— 5700-6 AL (Aluminum-Lay in T-Bar-24 x 24) _5700-6 AL (Aluminum-Lay in T-Bar-12 x 12)
t 1 Neck Size-g
Earthquake Tab Neck Size-3 7 1 e
Latch Tabs i 1 i }
I k 1 34
5 i
ZEZtair.____ ESSE --..,._
Overall Face Size=23 3 x 23 4 Overall Face Size=11 4 x 11 a
4
T-Bar Module=24 x 24 — T-Bar Module=12 x 12 —
Available Neck Sizes 6,8,10,12,14,15 Available Neck Sizes 6&8
Model 1J5700-6P (Steel-Lay in T-Bar Panel) Model: 1_5700-6P (Steel-Lay in T-Bar Panel)
5700-6P AL (Aluminum-Lay in T-Bar Panel) _5700-6P AL (Aluminum-Lay in T-Bar Panel)
Neck Size-8 — 1 Neck Size-1
8 1
I
ill r------." I �'8 r' I �'e
} }
Overall Face Size=234 x 234 — Overall Face Size=19-x 194
T-Bar Panel=24 x 24 — T-Bar Panel=20 x 20 —
Available Neck Sizes 6&8 Available Neck Sizes 6&8
Revision: G Date: 2/22/2019 Dimensions are in Inches Page: 1 of 2
Metal Industries,Inc. Clearwater,FL (727)441-2651 Fax(800)865 8383 www.metalaire.com sales@metalaire.com
Proj
Tag: METALAIREect: ,.
Engineer:Contractor: Submittal: 5700
Date:
Square Face Diffusers
2 Cone - Round Neck
Models: Steel Aluminized Steel Aluminum
—5700-7 —5700-7 AS Concealed T-Bar
_5700-9 _5700-9 AS ❑5700-9 AL Bolt Slot/Donn Fineline(USG) Ceiling Grid
Models: ❑5700-7 (Steel-Lay in T-Bar-24 x 24)
❑5700-7 AS (Aluminized Steel-Lay in T-Bar-24 x 24)
Neck Size-
Earthquake Tab
Latch Tabs ` I l it
1 ?? 32 41
2
Overall Face Size=23 a x 23
T-Bar Module=24 x 24
Available Neck Sizes 6,8,10,12,14,15
Models: 5700-9 (Steel-Lay in T-Bar-24 x 24)
—
5700-9 AS (Aluminized Steel-Lay in T-Bar-24 x 24)
—5700-9 AL (Aluminum-Lay in T-Bar-24 x 24)
Neck Size-g {
Earthquake Tab
Latch Tabs ( t
32 41
2
zzzef
23ax233
Overall Face Size=23 e x 23 e
T-Bar Module=24 x 24
Available Neck Sizes 6,8,10,12,14,15
Notes: ❑ (check if provided)
1.Available Finishes 2.Available Accessories 3.Available Options 4.Construction Details
Standard Finish: Accessories Shipped Unattached •Concealed Mount FMCC • Available Sizes Only as Listed
❑01 White — G3 Equalizing Grid • Available Neck Sizes as Listed
Optional Finish(extra charge): BDS Butterfly Damper
❑02 Satin Silver _RSD Radial Shutter Damper
03 Black ❑BAF Directional Baffles
28 Custom Color/Setup Charge Accessories Shipped Factory Installed
FGBP Factory Installed R6 Insulation
on Select Sizes and Models
Revision: H Date: 2/22/2018 Dimensions are in Inches Page: 2 of 2
Metal Industries,Inc. Clearwater,FL (727)441-2651 Fax(800)865 8383 www.metalaire.com sales@metalaire.com
Project: pin
Engineer: OFFICE COPY METALAIR ETM
Contractor: Submittal: 7600R RECEIVED
Date:
Perforated Return Diffuser - Round Neck NOV 15 2021
12 x 12 and 24 x 24 Module
Models:07600R-1 Steel Backpan & Face - Surface Mount CITY TIGARD
07600R-1 DFSteel Backpan & Face -Surface Mount- Drop Face BUILDINNGG DIVISION
07600R-1 AFSteel Backpan &Aluminum Face -Surface Mount
07600R-6 Steel Backpan & Face- Lay in T-Bar
07600R-6 AF Steel Backpan &Aluminum Face- Lay in T-Bar
07600R-6 AL Aluminum Backpan & Face- Lay in T-Bar
Models: 7600R-1 (Steel Backpan&Face-24 x 24 Surface Mount)
7600R-1 DF (Steel Backpan&Face-24 x 24 Surface Mount-Drop Face)
7600R-1 AF (Steel Backpan&Aluminum Face-24 x 24 Surface Mount)
Nominal Round Neck
O.D.-8
Back Pan
} 2 Concealed Spring Latches Earthquake Tab
38 I 2-Concealed Hinges
1 J - \\ Border 1 3
8 `Perforated Face Optional Drop Face B
(Border 1 DF)
Ceiling Opening=23 x 23
Overall Diffuser=25 8 x 25 8 -
Medm6: 7600R-1 (Ct..l Dackpai&rat=-12 x 12 Sarfac=M.,ld h)
7600R-1 DF (Steel Backpan&Face-12 x 12 Surface Mount-Drop Face)
7600R-1 AF (Steel Backpan&Aluminum Face-12 x 12 Surface Mount)
1-Concealed Nominal Round Neck
Spring Clip -1 O.D.-8 Back Pan
4 / Earthquake Tab
2 1_ • �2-Concealed Hinges
ee
\Hinged,Removable Border 1 DF
Perforated Face Optional Drop Face
Ceiling Opening 11 x 11 4 -
Overall Diffuser 138-x 138-
Models: 7600R-6 (Steel Backpan&Face-24 x 24 Lay in T-Bar)
7600R-6 AF (Steel Backpan&Aluminum Face-24 x 24 Lay in T-Bar)
7600R-6 AL (Aluminum Backpan&Face-24 x 24 Lay in T-Bar)
7600R-6 DF (Steel Backpan&Face-24 x 24 Surface Mount-Drop Face)
Nominal Round Neck
O.D.-
a
II Back Pan
///
2 Concealed Spring Latches Earthquake Tab
381 ^ - 2-Concealed Hinges
e
Perforated Face
Optional Drop Face
(Border 1 DF)
Overall Diffuser=23 4 x 23 4
T-Bar Module=24 x 24 -
Models: 7600R-6 (Steel Backpan&Face-12 x 12 Lay in T-Bar)
7600R-6 AF (Steel Backpan&Aluminum Face-12 x 12 Lay in T-Bar)
Nominal Round Neck
1 Back Pan
O.D.-8
Earthquake Tab
2 2 Concealed Hinges
a
EME
Hinged,Removable
Perforated Face
Ceiling Opening 11 a x 11
T-Bar Module=12 x 12
IRevision: D I Date: 8/2016 I Dimensions are in Inches I Page: 1 of 2 I
Project:
Tag: METALAIRE�
Engineer:
Contractor: Submittal: 7600R
Date:
Perforated Return Diffuser - Round Neck
12 x 12 and 24 x 24 Module
Models:07600R-8 Steel Backpan & Face -Tegular T-Bar
07600R-8 AF Steel Backpan &Aluminum Face -Tegular T-Bar
07600R-8 AL Aluminum Backpan & Face-Tegular T-Bar
07600R-9 Steel Backpan & Face- Donn Fineline Ceiling Grid
07600R-9 AF Steel Backpan &Aluminum Face - Donn Fineline Ceiling Grid
Models: 7600R-8 (Steel Backpan&Face-24 x 24 Tegular T-Bar)
7600R-8 AF (Steel Backpan&Aluminum Face-24 x 24 Tegular T-Bar)
7600R-8 AL (Aluminum Backpan&Face-24 x 24 Tegular T-Bar)
Nominal Round Neck
O.D.
-i3 �Earthquake Tab
1 Concealed Back Pan
381 Spring Latches 2 Concealed Hinges
o
"" Removable Perforated Face 3
8
Overall Diffuser=234 x 234
T-Bar Module=24 x 24
Models: 7600R-8 (Steel Backpan&Face-24 x 24 Tegular T-Bar)
7600R-8 AF (Steel Backpan&Aluminum Face-24 x 24 Tegular T-Bar)
7600R-8 AL (Aluminum Backpan&Face-24 x 24 Tegular T-Bar)
Nominal Round Neck
O.D.-8 Back Pan
Earthquake Tab
Concealed Hinges
Removable Perforated Face 3-
114x114
Tegular T-Bar=12 x 12
8
Models: 7600R-9 (Steel Backpan&Face-24 x 24 Donn Fineline Ceiling Grid)
7600R-9 AF (Steel Backpan&Aluminum Face-24 x 24 Donn Fineline Ceiling Grid)
Nominal Round Neck
O.D.-$
Earthquake Tab
Concealed ,..,. Back Pan _2 Concealed Spring Latches
Spring Latches tttttt
38
Removable Perforated Face 3
8
Overall Diffuser=23 x 234
Module Size=24 x 24
Notes: ❑ (check if provided)
1.Available Finishes 2.Available Accessories 3.Available Options 4.Construction Details
Standard Finish: Round Necks: • Available only in listed sizes.
❑01 White. ❑ BDS-Butterfly Damper. • Seismic tabs standard on all units.
Optional Finish(additional charge): ❑ RSD-Radial Shutter Damper.
❑03 Black. Replacement Parts:
❑02 Satin Silver ❑ Replacement Steel Face Plates.
❑28 Custom Color. ❑ Replacement Aluminum Face Plate.
❑22(BBP)Black back pan/white face.
IRevision: C I Date: 8/2016 I Dimensions are in Inches I Page: 2 of 2 I
0 MICroMet1 Date: Weights: Units: 48TC D12 Part Number:
12/14/2018 701bs/31.75kg ECD-SRT34CA-D2DH
Submitted To: wbeck@airefco.com Job: Notes:
Economizer-Economizer-Ultra Low Leak Economizer,Vertical Orientation,Honeywell Jade W7220 Single/Multiple Speed Electromechanical Controller,Adjustable Dry Bulb Sensor,Honeywell
Actuator.Painted Rain Hood With Aluminum Filter,Barometric Relief,All Necessary Panels And Hardware Included. RECEIVED
NOV 152021
CITY OF TIGARD
BUILDING DIVISION
Economizer Harness ° Filter Access
=
with PL6 Plug Door Provided
,� on Unit
E
23 3116" Micrometl
j s Economizer ..........,,Filters
�r F4 22 3/S"
Communicating P ; '
Actuator / %%474.11, /r �a
� Barometric Relief 0 I
Damper /
�� r` Economizer ,
Outside Air Hood ,
j.% Sensor i i._
External Gear '111 — Knockouts for
Driven Dampers °Wiring for Optional Prop Side View
Power Exhaust
The Information contained in this drawing is the sole property of Micrometl Corporation.Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited.
Indianapolis_3035 N.Shadeland Ave.,Indianapolis,IN 46226_800.MMC.HVAC••Sparks_905 Southern Way,Sparks,NV 89431_800.884.4MMC••Longview_201 Kodak Blvd.,Longview,TX 75602_903.248.4800
Date: Weights: Units: 48TC D12 Part Number:
M i c ro M etl 12/14/2018 701bs/31.75kg
ECD-SRT34CA-D2DH
Submitted To: wbeck@airefco.com Job: Notes:
Economizer-Economizer-Ultra Low Leak Economizer,Vertical Orientation,Honeywell Jade W7220 Single/Multiple Speed Electromechanical Controller,Adjustable Dry Bulb Sensor,Honeywell
Actuator.Painted Rain Hood With Aluminum Filter,Barometric Relief,All Necessary Panels And Hardware Included.
Compliant Economizer:
1. Title 24:Economizers meet California Energy Commission Title 24-2013/2016 prescriptive section 140.4(damper leakage etc.),and mandatory section 120.2.i for Fault Detection
and Diagnostic controls(JADE HJW10).
2. ASHRAE 90.1:Economizers meet ASHRAE 90.1-2013/2016 damper leakage requirements,and meet 2016 Fault Detection and Diagnosis requirements.
3. IECC:Economizers meet IECC 2012,IECC 2015,and IECC 2018 for outside air,return air,and relief damper(when provided)leakage requirements,and IECC 2015 and IECC 2018
for Fault Detection and Diagnostic requirements.Note:IECC 2015 and IECC 2018 requires differential return air sensor,which is included in some models(i_e_D2XH)and must be
ordered separately on others(i.e.D2DH,D2ZH).
4. AMCA:Outside air and return air(volume)dampers are AMCA Class 1A rated at 1"w.g.Refer to MicroMetl NS1 catalog sheet on web site for details.Relief air dampers(when
provided)are also AMCA rated.Refer to GR1 series catalog sheet on web site for details.
Features:
• For single or 2 speed indoor fan units with Central Terminal Board(CTB)and Compressor Staging Board_Other control options available.
• Gear driven design for trouble-free operation,eliminating slippage and binding associated with standard linkage_ rat!
• Includes assembled rainhood with aluminum water entrainment filters in the outside air section. OUR
▪ Rainhood is sloped for water run-off. tPfa of
• Built-in barometric relief damper provided.Power exhaust options available_ .411
111014111,11T\
• NC contest
All harnesses and plugs needed are provided.
uwamo.
Thies osm.mat
• Uses standard factory filter access door shipped with HVAC unit. MicroMetl Corporation
• If factory hinged access door option is installed on unit,an additional kit is required to seal hinged door properly. GR1 certifies and that
the
models
-OEM part no.CRPECONV004A00 or MicroMetl part number 0640-0200-HDANGL herein are licensed to bear
the AMCA Seal.
Notes: The ratings shown are
based on tests and
1. Control systems include Honeywell W7220 JADE controller,mixed(supply)air temperature sensor,OA sensor in description,and spring-return procedures performed in
accordance with AMCA
communicating actuator(some include differential return sensor as noted). Publication 511 and
2. JADE W7220 controller is field mounted in unit's control box_ comply with requirements
of the AMCA Certified
3. Mixed(supply)air sensor is field installed in indoor blower fan section. Ratings Programs.
The AMCA Certified
4. Differential return sensor(included in"-D2XH"and"-D2ZH"models or can be ordered separately-MicroMetl Part No.9901-2022-DIFF JC2)is field Ratings Seal applies
installed in return duct. to Air Leakage and Air
Performance ratings.
5. ASHRAE,IECC,and Title 24 require the economizer controller be capable of reporting faults to a fault management application accessible by
day-to-day operating or service personnel,or annunciated locally on zone thermostats or in some codes other devices are acceptable.Refer to
applicable code requirements and to MicroMetl instructions for suggestions.
6. For older single speed models without the Central Terminal Board the'`D2"part number is replaced by"-DJ' (See separate submittal).
The Information contained in this drawing is the sole property of Micrometl Corporation.Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited.
Indianapolis_3035 N.Shadeland Ave.,Indianapolis,IN 46226_800.MMC.HVAC••Sparks_905 Southern Way,Sparks,NV 89431_800.884.4MMC••Longview_201 Kodak Blvd.,Longview,TX 75602_903.248.4800
. RECEIVED
NOV 15 2021
TP—PAC, TP—PHP, TP—PRH ARD
TP—NAC, TP—NHP, TP—NRH VISION
Performance' Series Edge' Thermostat Clarrier)
turn to the experts
Product Data
• The Carrier Performance" Series Edge' thermostats consists of
programmable and non-programmable air conditioner,heat pump
I / and Thermidistat" controls. These units feature non-mercury,
l" non-lead based electronic controls built into a subtle,slim plastic
- #_ enclosure.
' ,1';' FEATURES/BENEFITS
0., - + Edge Programmable &Non-Programmable
t 1 • Outdoor Air Temperature(OAT)sensor option
• Auto changeover available
' • Battery free
i 13 t
'I.,.
L .f , ; i, • Non-volatile memory to retain settings during a power outage
• Keypad lockout
• English/Metric units selection
• Filter/UV light/Humidifier pad replacement indicators
• Continuous display hack-lighting configurable
• Hybrid Heat compatible
A07049 • RC/RH power compatible
Fig.1- Performance Series Programmable Thermostat • 2-wire communicating installation option
1
Edge Programmable models
• ExP" expansion port*for use with future enhancements and/or
features
• Programmable with personal computer**
• 7,5-2,All Days programmable
-7e • 4 or 2 periods per day programmability
[ l t • Programmable fan by period
• Vacation mode controls temperature and humidity
• Remote room sensor option
�;1 .t ►Adjusts automatically for Daylight Savings Time
Edge Non-Programmable models
• Touch ItGo programmability
Air Conditioner Control
• i-stage heat/1-stage cool
Heat Pump Control
• 3-stage heat/2-stage cool
A07049
Fig.2-Performance Series Non-programmable Thermostat Thermidistat Control
• Heat pump 2-stage or Hybrid Heat 3-stage heat/2-stage
US patents:US7287709 B2,US20080147242 Al,USD582800 SI,US20060165149 A1, cooling with humidity control
U96956463 B2.
• Humidity display
• Humidify output for direct control of humidifier
Designed and Assembled • Dehumidify output for variable-speed blowers
0 in the USA. • Hybrid Heat compatible
• ExP acracsory(expansion port and memory card)sold separately
** Requires ExP accessory
Ors `"'
jF r-
OFFICE Ct)1)y
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8
T P -- P A C 0 1
Product Packaged Quantity
T=Thermostat 01 =1 piece
Series Equipment Type
P=Performance AC=Air conditioning
HP=Heat pump
Not Defined RH=Relative humidity
- =Place Holder
Function Type
P=Programmable
cc N=Non-programmable
I
a.
I
Z DIMENSIONS
= 5.2 in. gin- ld N. 5.2 is .71n^ 37 IT
nj
1 [[1 ' -
Q 132.08111111 33 02 mini I ..___. p.m m
-228i ram I ' U5.09mm ' i
i
Z
IX 5.2 W S.z in
,132.08 fling I32.09 runt
I
a.
•
iJ
U
i_.__ Single Two
etSingle Two pi.,,, Yiece
a. Yi c Pie.
I
a
t-
A07137 A07138
Fig.3-Performance Series Programmable Thermostat Fig.4- Performance Series Non-programmable Thermostat
PRODUCT DATA INFORMATION Wiring Requirements
Physical Characteristics Standard 18 to 22 gauge,local wiring codes supersede
Dimensions: See drawing Accessories
Mounting: Vertical or horizontal J-box provisions PART NUMBER DESCRIPTION
Electrical TSTATXXSEN01-B* Outdoor air temperature sensor
Input volts/amps: 24VAC,3 VA,RC/RH compatible TP-EXP ExP Expansion Memory Port
Environment TX-LBP01 Large decorative backplate for TP-Pxx
and TP--Nxx
Operating temperature/Relative humidity: 32°F (0°C) to --
104°F(40°C),95%RH non-condensing EDGE-DR-ES05 Espresso Decorative Door
Storage temperature/Relative humidity: -40°F (-40°C) to EDGE-DR-GL05 Gold Luster Decorative Door
134°F(57°C),95%RH non-condensing EDGE-DR-NA05 Natural Grain Decorative Door
EDGE-DR-SB05 Saddlebrush Decorative Door
EDGE-DR-OX05 Onyx Decorative Door
EDGE-DR-QZ05 Quartz Decorative Door
TX-2WR05 2-wire harness
ZONECCORRSOI Remote room temperature sensor
* The outdoor air temperature sensor must be used with the Thermidistat
control in a Hybrid Heat system.
2
OPERATIONAL INFORMATION
Heating/Cooling Setpoints Auto Changeover
The heating/cooling setpoint range is from 50°F(10°C)to 90°F When Auto Changeover mode is selected, a change from heat to
(32°C). A selectable range of 1-6° is enforced between heating cool(or vice versa)will not occur until an opposite mode demand
and cooling desired temperatures. This is done by allowing one has existed for 20 minutes. When a setpoint is changed, Auto
setting to "push" the other, to maintain this difference. (This Changeover timing is ignored to allow the heating/cooling
difference is adjustable in Installer settings.) equipment to respond quickly. Auto Changeover mode can be
Humidify/Dehumidify Setpoint Range disabled.
The humidify setpoint range is from 10% to 46% RH in 2% RH Emergency Heat Mode
increments. The dehumidify setpoint range is from 46% to 66% When the thermostat is controlling a heat pump and emergency
RH in 2%RH increments. heat is selected, all Y signals are locked out, and W becomes
Five-minute Compressor Time Guard energized upon a call for heat.
This timer prevents the compressor from starting unless it has been Smart Recovery (Programmable models)
off for at least 5 minutes. It can be defeated for I cycle by With Smart Recovery selected, transition out of setback begins a
simultaneously pressing the FAN button and INCREASE fixed time period (Off, 30, 60, or 90 minutes selectable) before pc
TEMPERATURE(UP)button. selected recovery time and gradually adjusts room temperature so 2
Equipment on indicators that the desired temperature will be achieved at selected recovery I
time. O.When cooling equipment is ON, a COOL ON icon is displayed.
When heating equipment is ON, a HEAT ON icon is displayed. Room Temperature Offset
When auxiliary heating is ON(HP only), an AUX HEAT icon is Room temperature may be deliberately offset by up to 5° in either i
displayed. direction.
Humidify/Dehumidify Output On Indicators Programmable Fan(Programmable models)
(Thermidistat Control) This selection allows the homeowner to program the fan selection Z
to"Auto"or"Fan On"for each of the program schedule periods.
When the operating mode is heat and the HUM output is energized p g`
the"humidify"icon shall be displayed.When the operating mode I
is cool,the dry contact is configured as a DEHUM output and there
is a dehumidify demand or the cooling equipment is energized to I
satisfy a dehumidify demand, the "dehumidify" icon shall be
displayed. X
0
U
aa,
a
1-
3
40MB*D
Ducted Style Ductless System
Sizes 09 to 48 Carrie
turn`to the experts
°‘1 Installation Instructions
. _ 1 FAAGs- O� TABLE OF CONTENTS
O
PAGE
030) SAFETY CONSIDERATIONS 2
PARTS LIST 3
SYSTEM REQUIREMENTS 4
+3 i tt5 - 1, WIRING 4
DIMENSIONS 5
CLEARANCES 6
INSTALLATION LOCATION REQUIREMENTS 7
ii •!.1'iim
INDOOR UNIT INSTALLATION 7
i " FAN PERFORMANCES 9
ELECTRICAL DATA 17
CONNECTION DIAGRAMS 17
WIRELESS REMOTE CONTROL INSTALLATION 19
NOTE: Read the entire instruction manual before starting the START—UP 20
installation. TROUBLESHOOTING 21
NOTE: Images are for illustration purposes only.Actual models
may differ slightly.
NO EXCEPTIONS NOTED NI REJECTED I ]
MAKE CORRECTIONS NOTED [ ] REVISE AND RESUBMIT [ ]
THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN
CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS
NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN
REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF
ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE
CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR
OR DEVIATION FROM CONTRACT DOCUMENTS.
CIDA
COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE
PORTLAND,OREGON
REVIEWED 11/12/2021,BY curtisg
SAFETY CONSIDERATIONS A WA R N I N G
Installing, starting up, and servicing air—conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location(roofs,elevated structures,etc.). ELECTRICAL SHOCK HAZARD
Only trained, qualified installers and service mechanics should Failure to follow this warning could result in personal
install,start—up,and service this equipment. injury or death.
Untrained personnel can perform basic maintenance functions such Before installing,modifying,or servicing system,main
as cleaning coils. All other operations should be performed by electrical disconnect switch must be in the OFF
trained service personnel. position.There may be more than 1 disconnect switch.
When working on the equipment, observe precautions in the Lock out and tag switch with a suitable warning label.
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.Wear safety glasses and work gloves.Keep A WA R N I N G
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling,rigging,and setting bulky equipment. EXPLOSION HAZARD
Read these instructions thoroughly and follow all warnings or Failure to follow this warning could
cautions included in literature and attached to the unit.Consult result in death,serious personal injury,
local building codes and National Electrical Code(NEC)for and/or property damage.
special requirements.Recognize safety information.
Never use air or gases containing
This is the safety—alert symbol A.When you see this symbol on 4 oxygen for leak testing or operating
the unit and in instructions or manuals,be alert to the potential for refrigerant compressors. Pressurized
personal injury.Understand these signal words:DANGER, mixtures of air or gases containing
WARNING,and CAUTION.These words are used with the oxygen can lead to an explosion.
safety—alert symbol.DANGER identifies the most serious hazards
which will result in severe personal injury or death.WARNING CAUTION
signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage.NOTE EQUIPMENT DAMAGE HAZARD
is used to highlight suggestions which will result in enhanced Failure to follow this caution may result in equipment
installation,reliability,or operation. damage or improper operation.
Do not bury more than 36 in.(914 mm)of refrigerant pipe
in the ground.If any section of pipe is buried,there must be
a 6 in. (152 mm)vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried,refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start—up.
2
PARTS LIST
i
Table 1—Parts List
PART NO. NAME OF PART
1 AIR OUTLET
2 AIR INLET
3 AIR FILTER
4 ELECTRIC CONTROL CABINET
5 WIRED CONTROLLER
6 DRAIN PIPE(FIELD SUPPLIED)
7 WIRELESS REMOTE
ri
f •
a
•
f ,,,pool_.!
t 1 ea
f o 9 ill
r \ T
•
n
d
' 2 I I
O V
d
I.
1
I Fig.1 — Parts List
i Notes:
—If the outdoor unit is higher than the indoor unit,prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it
enters the wall to the indoor unit.This ensures that rain drips from the connection pipe before it enters the wall.
—Piping and the interconnecting wiring are field supplied.
I —The illustration above is only a sketch.Different models may be slightly different.
—Filter Standard on units produced after serial number 2815V10001
The following units are covered in these installation instructions.
I
Table 2—Indoor Units
kBTUh V—Ph—Hz ID Model No.
9 208/230-1-60 40MBQB09D--3
12 208/230-1-60 40MBQB12D--3
18 208/230-1-60 40MBQB18D--3
24 208/230-1-60 40MBQB24D--3
36 208/230-1-60 40MBQB36D--3
48 208/230-1-60 40MBQB48D--3
1 3
SYSTEM REQUIREMENTS WIRING
Allow sufficient space for airflow and servicing unit.See Fig.3 for All wires must be sized per NEC(National Electrical Code)or
minimum required distances between the unit and the walls or CEC(Canadian Electrical Code)and local codes.Use the
ceilings. Electrical Data table MCA(minimum circuit amps)and MOCP
Piping (maximum over current protection)to correctly size the wires and
the disconnect fuse or breakers respectively.
IMPORTANT: Both refrigerant lines must be insulated Per caution note,only stranded copper conductors with a 600 volt
separately. rating and double insulated copper wire must be used.The use of
• Minimum refrigerant line length between the indoor and outdoor BX cable is not recommended.
units is 10 ft.(3 m). Recommended Connection Method for Power and
• Table 3 lists the pipe sizes for the indoor unit.Refer to the Communication Wiring—Power and Communication Wiring:
outdoor unit installation instructions for other allowed piping The main power is supplied to the outdoor unit.The field
lengths and refrigerant information.
supplied 14/3 power/communication wiring from the outdoor unit
Table 3—Piping Lengths to the indoor unit consists of four(4)wires and provides the
9K 12K 18K 24K 36K a8K power for the indoor unit.Two wires are high voltage AC power,
Gas Pipe one is communication wiring and the other is a ground wire.
In 3/8 1/2 1/2 5/8 5/8 5/8
(size-connection Recommended Connection Method for Power and
(mm) (9.52) (12.7) (12.7) (16) (16) (16)
type) Communication Wiring(To minimize communication wiring
Liquid Pipe In 1/4 1/4 1/4 3/8 3/8 3/8 interference)Power Wiring:
(size—connection (mm) (6.35) (6.35) (6.35) (9.52) (9.52) (9.52)
type) The main power is supplied to the outdoor unit.The field
supplied power wiring from the outdoor unit to the indoor unit
consists of three(3)wires and provides the power for the indoor
unit.Two wires are high voltage AC power and one is a ground
ii
wire.
II To minimize voltage drop,the factory recommended wire size is
14/2 stranded with a ground.
Communication Wiring:
A separate shielded stranded copper conductor only, with a 600
1 volt rating and double insulated copper wire,must be used as the
q communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.
fi A CAUTION
1 EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
• Wires should be sized based on NEC and local codes.
• Use copper conductors only with a 600 volt rating and
double insulated copper wire.
1
I
t
i
r
,
1
4
m:
DIMENSIONS-INDOOR
Air filter air inlet from rear side ,a‘K> '>. .
< ' I irj-10''' ' .1.
L B
H2
4-install hanger
H1 A Liquid side
r' 0 1(25) o�
MilF' Drain.i.e Gas side a
� - 0 1(25)
Test mouth&Test cover =F� Illo Drain.i.e
- 0 U
[aft, 7 C 1LIH 1(25)Drain connecting jpipe(for pump) 1' �t •
Electric control box Outside Air Intake
o E F
imiumminnommiumm
•liliiiii.M•
coloommummicommii
1111
Air filter
ic I.
7 I:
Y .1111111111111
air inlet from bottom side
Fig.2 - Indoor Unit
Table 4-Indoor Unit
UNIT:in(mm)
OUTLINE AIR OUTLET AIR RETURN HANGER REFRIGERANT PIPE OPERATING
DIMENSIONS OPENING SIZE OPENING SIZE BRACKERS LOCATIONS WEIGHT
lb(kg)
Size A B C D E F G H I J K L M H1 H2 W1 W2
9 27.6 8.2 25 22.4 2.5 19.4 1.3 4.6 23.4 7.8 3.1 29.1 13.8 4.7 5.6 3.7 5.9 39.9
(700) (210) (635) (570) (65) (493) (35) (119) (595) (200) (80) (740) (350) (120) (143) (95) (150) (18.1)
12 27.6 8.2 25 22.4 2.5 19.4 1.3 4.6 23.4 7.8 3.1 29.1 13.8 4.7 5.6 3.7 5.9 39.9
(700) (210) (635) (570) (65) (493) (35) (119) (595) (200) (80) (740) (350) (120) (143) (95) (150) (18.1)
18 36.2 8.2 25 22.4 2.5 28.07 1.3 4.6 32.0 7.8 3.1 37.8 13.8 4.7 5.6 3.7 5.9 50.7
(920) (210) (635) (570) (65) (713) (35) (119) (815) (200) (80) (960) (350) (120) (143) (95) (150) (23)
24 36.2 10.6 25 22.4 2.5 28.07 1.3 7.0 32.0 10.2 0.7 37.8 13.8 4.7 5.6 3.7 5.9 57.3
(920) (270) (635) (570) (65) (713) (35) (179) (815) (260) (20) (960) (350) (120) (143) (95) (150) (26)
44.8 10.6 30.5 27.9 2.5 36.7 1.3 7.0 40.7 10.2 0.7 46.5 19.3 4.7 5.6 3.7 5.9 77.1
36
(1140) (270) (775) (710) (65) (933) (35) (179) (1035) (260) (20) (1180) (490) (120) (143) (95) (150) (35)
47.2 11.8 34.1 31.4 3.1 38.1 1.5 8.0 43.0 11.3 1.7 48.8 19.7 6.9 7.8 6.1 8.3 99.2
48
(1200) (300) (865) (800) (80) (968) (40) (204) (1094) (288) (45) (1240) (500) (175) (198) (155) (210) (45)
5
urrrrrrrrrrrrr y .
•
CLEARANCES -INDOOR •
INSTALLATION PLACE
>11.8in(30cm)
Strong aand durable ceilin
Indoor unit >0.8in(2cm)I ICI '
Left Right 'I'
side side 8 rn:
•
1/ , l ��,v,, / �uii,- p
>4in(10cm) >11.8in(30cm) - a.i
Service access Ceiling
A_
Floor iiiioiiaiiiaiiiiii////
MAINTENANCE SPACE
A IService access COIL CONNECTION AREA
CONDENSATE DRAIN PIPING AREA
E V CONDENSATE PUMP SERVICE CLEARANCE
SENSOR SERVICE CLEARANCE
Filter service clearance
Unit
(only one side is required)
A/2 I i 7 / A/2 I
v
,AIO
o G
7 / /lF---_i A
>11.8in (30cm)
Service access
BLOWER/MOTOR SERVICE CLEARANCE
PCB BOARD SERVICE CLEARANCE
FILTER SERVICE CLEARANCE
Fig.3 — Indoor Unit Clearances
Table 5—Indoor Unit Clearance
Capacity(Kbtu) A B C
9K 27.56 in.(70cm) 8.27 in.(21cm) 11.81 in.(30cm)
12K 27.56 in. (70cm) 8.27 in.(21cm) 11.81 in.(30cm)
18K 36.22 in.(92cm) 8.27 in.(21cm) 11.81 in.(30cm)
24K 36.22 in.(92cm) 10.63 in.(27cm) 11.81 in.(30cm)
36K 44.88 in.(114cm) 10.63 in. (27cm) 11.81 in. (30cm)
48K 47.24 in.(120cm) 11.81 in. (30cm) 15.75 in.(40cm)
6
38MARB
Outdoor Unit Single Zone Ductless System
Sizes 06 to 36 Carrier
51-, Product Data
0� �p INDUSTRY LEADING FEATURES /
G\�p BENEFITS
6lOtio
\\ A PERFECT BALANCE BETWEEN BUDGET
�1
�,-�� LIMITS, ENERGY SAVINGS AND COMFORT.
OlPr� ��t111111�����,
\\\`�� --,-0- �t The 38MARB series ductless systems are a matched combination of
jan outdoor condensing unit and an indoor fan coil unit connected only
by refrigerant tubing and wires.
r � The ductless system permits creative solutions to design problems
such as:
Fig. 1 —Sizes 06K-36K • Add-ons to current space(an office or family room addition)
NOTE:Images are for illustration purposes only.Actual models may Special space requirements
•
differ slightly. • When changes in the load cannot be handled by the existing
system
TABLE OF CONTENTS • When adding air conditioning to spaces that are heated by
hydronic or electric heat and have no ductwork
PAGE • Historical renovations or any application where preserving the
INDUSTRY LEADING FEATURES/BENEFITS 1 look of the original structure is essential.
MODEL NUMBER NOMENCLATURE 3
STANDARD FEATURES AND ACCESSORIES 4 The ideal compliment to your ducted system when it is impractical or
DIMENSIONS 5 prohibitively expensive to use ductwork.
CLEARANCES 8 The compact indoor fan coil units take up very little space in the room
SPECIFICATIONS 9 and do not obstruct windows.The fan coils are attractively styled to
PERFORMANCE 10
COOLING PERFORMANCE-HIGH WALL 17 blend with most room decors.Advanced system components
HEATING PERFORMANCE-HIGH WALL 20 incorporate innovative technology to provide reliable cooling
COOLING PERFORMANCE-CASSETTE 23 performance at low sound levels.
HEATING PERFORMANCE-CASSETTE 24
COOLING PERFORMANCE-DUCTED 25
HEATING PERFORMANCE-DUCTED 26
COOLING PERFORMANCE-CONSOLE 27
HEATING PERFORMANCE-CONSOLE 28
COOLING PERFORMANCE-AIR HANDLER 29
HEATING PERFORMANCE-AIR HANDLER 29 NO EXCEPTIONS NOTED [) REJECTED [ 1
APPLICATION DATA 30 MAKE CORRECTIONS NOTED [ 1 REVISE AND RESUBMIT [ ]
WIRING 31
ELECTRICAL DATA 33 THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN
CONNECTION DIAGRAMS 34 CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS
NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN
WIRING DIAGRAMS 35 REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF
GUIDE SPECIFICATIONS 39 ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE
CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR
OR DEVIATION FROM CONTRACT DOCUMENTS.
CIDA
COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE
PORTLAND,OREGON
REVIEWED 11/12/2021,BY curtisg
OFFICE COPY
Specifications subject to change without notice.
38MARB:Product Data
Inverter Technology Fast Installation
The inverter driven compressor is designed to run at various input power This compact ductless system is simple to install.Only wires and piping
frequencies(Hz)which controls the compressor's motor speed. need to run between the indoor and outdoor units.These units are fast and
easy to install ensuring minimal disruption to customers in homes or the
Even Temperature—The control package,including the inverter, workplace.This makes the 38MARB systems the equipment of choice
monitors the outdoor and indoor temperatures as they relate to the for retrofit applications.
selected indoor set point and adjusts the compressor speed to match
the load and keep the system operating continuously rather than cycling Simple Servicing and Maintenance
and creating temperature swings.This translates to higher comfort levels Removing the top panel of the outdoor unit provides immediate access to
for the occupants. the control compartment,providing the service technician access to the
diagnostic LEDs to facilitate the troubleshooting process.In addition,the
Rapid Pull Down/Warm-Up—Comfort is increased by the inverter
draw-thru design of the outdoor unit means that dirt accumulates on the
system's ability to ramp up the compressor speed enabling the system to outside surface of the coil.Coils can be cleaned quickly from the inside
reach the user selected room temperature set point quicker. using a pressure hose and detergent.
Humidity Control—Running the system for longer periods and On the indoor units,service and maintenance expense is reduced due to
continuously varying the compressor speed enhances the humidity the permanent easy to clean filters.Also,error codes are displayed on the
control. front panel to alert the user to certain system malfunctions.
Individual Room Comfort Built-in Reliability
Maximum comfort is provided because each space can be controlled Ductless system indoor and outdoor units are designed to provide years of
individually based on the usage pattern. trouble-free operation.Both the indoor and outdoor units are well
protected.Whenever the microprocessor detects abnormal conditions,the
Low Sound Levels unit stops and an error code appears.
When noise is a concern,ductless systems are the answer.The indoor Inverter systems provide additional reliability due to the soft start.This
refers to the ability of the inverter to start the compressor motor using
units are whisper quiet.There are no compressors indoors,either in the
conditioned space or directly over it,and there is none of the noise reduced voltage and reduced current.This feature is beneficial from an
usually generated by air being forced through the ductwork. electrical standpoint(eliminates current spikes)as well as an overall
reliability standpoint due to reduced stress on all associated system
When sound ordinances and proximity to neighbors demand quiet components.
operation,the 38MARB unit is the right choice.With the inverter
technology,these units run at lower speeds most of the time resulting in Agency Listings
reduced sound levels. All systems are listed with AHRI(Air conditioning,Heating,and
Refrigeration Institute)and are UL certified per UL 60335-2-40
Inverter Technology—Enhanced Economical standard.
Operation
Ductless systems are inherently economical to operate.Individual rooms
are heated or cooled only when required,and since the air is delivered
directly to the space,there is no need to use additional energy to move the
air in the ductwork.This economical operation is enhanced further when
the inverter system output matches the load resulting in a more efficient
system.
Easy-To-Use Controls
The systems have microprocessor-based controls to provide the ultimate
in comfort and efficiency.The user friendly wired and wireless remote
controls provide the interface between the user and the unit.
Secure Operation
If security is an issue,outdoor and indoor units are connected only by
refrigerant piping and wiring to prevent intruders from crawling through
ductwork or wall openings.In addition,since the 38MARB can be
installed close to an outside wall,coils are protected from vandals and
severe weather.
Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations.
38MARB:Product Data
MODEL NUMBER NOMENCLATURE
OUTDOOR UNIT
38 MA R B Q 36 A 3
38=OUTDOOR UNIT
VOLTAGE
MA=MODEL 1=115-1-60
3=208/230-1-60
SYSTEM TYPE MAXIMUM NUMBER OF FAN COIL UNITS THAT
OUTDOOR CAN BE CONNECTED TO THE OUTDOOR UNIT
S-
B=1:1
MAJOR SERIES
NOMINAL CAPACITY
06-1/2 TON
09-3/4 TON
12-1TON
18-1-1/2 TONS
UNIT TYPE 24-2 TONS
Q=HEAT PUMP 30-2-1/2 TONS
36-3TONS
ti ma CERTIFIED.. ARS
M��r
Use of the AHRI Certified
TM Mark indicates a
manufacturer's
participation in the
program For verification
of certification for individual
products,go to
www.ahridirectory.org.
Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations.
38MARB:Product Data
STANDARD FEATURES AND ACCESSORIES
Outdoor Units
Ease Of Installation
Low Voltage Controls S Crankcase Unit
Comfort Features
Microprocessor Controls S The crankcase heater is standard on all unit sizes.Heater clamps must be
Auto Restart Function S placed around the compressor oil stump.
Auto Changeover S
Energy Saving Features Base pan Heater
Inverter Driven Compressor S The base pan heater is standard on all unit sizes.
46°F Heating Mode(Heating Setback) S
Safety And Reliability
3 Minute Time Delay For Compressor S
High Compressor Discharge Temperature S
Low Voltage Protection S
Compressor Overload Protection S
Compressor Over Current Protection S
IPM Module Protection S
Condenser High Temp Protection in Cooling Mode S
Aluminum Hydrophilic pre-coated fins S
Ease Of Service And Maintenance
Diagnostics S
Liquid Line Pressure Taps S
Application Flexibility
Crankcase Heater S
Base pan Heater S
Legend
• S-Standard
• A-Accessory
Accessories
Outdoor Unit Base Pan Base Rubber Quantity per Unit
Model Number Plugs RCD Part No.
38MARBQ12AA1
38MARBQ06AA3 12600801A00077 13
38MARBQ09AA3
38MARBQ12AA3
38MARBQ18AA3 12600801A00077 25
38MARBQ24AA3
38MARBQ30AA3 12600801A00117 5
38MARBQ36AA3
NOTE:The base pan is built in with multiple holes for proper draining
during the defrost process.For applications where it is required
to seal these holes,and re-direct the condensate drain,rubber
plugs are available through RCD.
Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations.
A
38MAR8:Product Data
DIMENSIONS
Air inlet
�. L1
(611 CON
H (00(((iffikil111))))))))) : D
L2
0 Ir\c==.3r
j u th==v'
Air outlet
W
Fig. 2-Outdoor Unit
UNIT SIZES 12K 6K 9K 12K 18K 24K 30K 36K
VOLTAGES 115V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
HEIGHT(H) IN(MM) 21.85(555) 21.85(555) 21.81(554) 21.81 (554) 26.50(673) 31.89(810) 31.89(810) 31.89(810)
WIDTH(W) IN(MM) 30.12(765) 30.12(765) 31.69(805) 31.65(805) 35.04(890) 37.24(946) 37.24(946) 37.24(946)
DEPTH(D) IN(MM) 11.93(303)) 11.93(303)) 12.99(330) 12.99(330) 13.46(342) 16.14(410) 16.14(410) 16.14(410)
L1 IN(MM) 17.81 (452) 17.81 (452) 20.10(511) 20.10(511) 26.10(663) 26.50(673) 26.50(673) 26.50(673)
L2 IN(MM) 11.25(286) 11.25(286) 12.50(317) 12.50(317) 13.70(347) 15.85(403) 15.85(403) 15.85(403)
OPERATING LBS(KG) 66.80(30.30) 63.71 (28.9) 74.10(33.60) 73.60(33.40) 101.0(45.80) 134.50(61) 141.80(64.3) 150.10(68.10)
WEIGHT
Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations.
RECEIVED
Unit Report For 48TC-7.5T-E-3PH NOV 15 2021
Project: Stock Units 2019 02/22/2019
Prepared By: CITY OF TIGARn 04:16PM
BUILDING DIVISION
Unit Parameters Dimensions (ft.in.)&Weight(lb.)***
Unit Model- 48TCEDO8A2A5-0A0G0 Unit Length• 7'4.125"
Unit Size. 08(7.5 Tons) Unit Width. 4' 11.5"
Volts-Phase-Hertz. 208-3-60 Unit Height. 3'5 25"
Heating Type• Gas **k Total Operating Weight 885 lb
Duct Cfg• Vertical Supply/Vertical Return
Medium Heat '*' Weights and Dimensions are approximate. Weight does
Round Tube Plate Fin Coils not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Gas Line Size- 3/4
Condensate Drain Line Size- 3/4
Return Air Filter Type• Throwaway
Return Air Filter Quantity 4
Return Air Filter Size• 16 x 20 x 2
Unit Configuration
Medium Static Option (Belt Drive)
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
2-Speed indoor fan motor controlled by VFD
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
15-Year heat exchanger-Stainless Steel(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48TCEDO8A2A5-0A0G0 Rooftop Unit 1
Base Unit
Medium Static Option (Belt Drive)
Electromechanical control, No intake or exhaust option.
2 Speed Fan Controller (VFD)
Packaged Rooftop Builder 1.49n Page 1 of 7
Certified Drawing for 48TC-7.5T-E-3PH
Project:Stock Units 2019 02/22/2019
Prepared By: 04:16PM
NOTES: ��II(({{ UNITED P.O.ROD 4805 THIS DOCUMENT IS TOE PROPERTY OF CARRIER CORPORATION SUBMISSION OF THESE DRAWINGS OR DOCUMENTS
UNIT OUTDOOR K H wry TECHNOLOGIES SYRACUSE.MI CON IS DELIVERED UPON THE OSEDAR CONDITION THAT RRF DOES NUT CONSTITUTE PART PERFORMANCE OR
1. DIMENSIONS ARE IN INCHES, DIMENSIONS COIL TYPE ••R�� CORPENTS MILL MOT RE DCONSENED OR URED N[TXOUT CHARIER
IN [ I ARE IN MILLIMETERS. 41 1/4 33 15 7/B CARRIER uzzl CORPORATION'S WRITTEN CONSENT. ACCEPTANCE OF CgITRA[T.
2. CENTER OF GRAVITY 48TC-A08 RTPF I10481 [658] [403]
49 3/8 37 1/4 27 7/8 CONNECTION SIZES
48TC-A09 RTPF [1253] [946] [708]
3.MO.DIRECTION OF AIR FLOW 49 3/8 31 1/4 15 1/8 A 1 3/8' [35] DIA FIELD POWER SUPPLY HOLE
48TC-Al2 RTPF 4D-3/B
[12531 [946] [403] I
Y� I10261 B 2 1/2' [64] DIA POWER SUPPLY KNOCKOUT
41 1/4 33 15 7/8 C 1 3/4' [51] DIA GAUGE ACCESS PLUG
48TC-D08 RTPF
[10481 [658] [403] ° °
48TC-D09 ROPE 49 3/8 31 1/4 15 7/8 i D 7/8' [22] DIA FIELD CONTROL WIRING NC".E1
[1253] [946] [403]
49 3/8 31 1/4 15 7/8 ECONOMIZER HOOD 20-3/4 E 3/4'-14 NPT CONDENSATE DRAIN
4BTC-D12 RTPF [1253] 19667 [603] (OPTIONAL( ] F
1/2'-14 NPT GAS CONNECTION
481C-D08 NCH% 41 1/4 33 23 3!1'-14 NPT GAS CONNECTION
[10481 [658] [584.2] G 2' [51] DIA POWER SUPPLY KNOCK-OUT
48TC-D12 NCH, 49 3/8 37 1/4 11 4� "e °
[12531 [946] [279.47 THRU-THE-BASE CHART (FIELD INST)
RTPF -ROUND TUBE, PLATE FIN (COPPER/ALUM) _ -- THESE ROLES REQUIRED FOR USE WITH ACCY KITS:
NCH% -NOVATION (ALUM/ALUM) •
�j� \\\\\\
I'I''"/� `'`111111 (92518 122/6 CRBTNPWR002AO1: GAS THRU CURB
\• CRBTNPWR004A01: GAS THRU BASEPAN
• p ® I RETURN AIR RETURN
' F,/i 1 I AIR THREADED WIRE REO'D HOLE
_ __ _ _ \ ;��� CONDUIT SIZE USE SIZES(MAX.)
//'E(T� W 1/2' ACC. 7/8' [22.2]
FILTER ACCESS PANEL 1110' `= y ^
% 1/2' 24V 1/8' [22.2]
(TOOL-LESS) E SAT.
CONDENSATE - • Y 1 1//' (002,004) POWER I 3/4' [44.4]
. ///�+ e �DAA IN OPENING 28-3/4
COONDENSER p/�p/�j� IN BASEPAN SUPPLY 37-5/8 40-3/8
11 f( Al 77317 [955] I1027] y 2 r 10041 3/4' FPT GAS 1 3/4° [41.4]
NMN1C\mL///47711 : % SEE THRU AIR (0021 PROVIDES 3/4"FPT THRU CURB
INDOOR COIL - AAG\VAAA�_U/�/////1 y - THE BASE SUPPLY 4 FLANGE 6 FITTING. HOLE SIZE: 2' [50.81
ACCESS PANEL ‘,„ j � CHART Y AIR
• BACK 8 16 E i
. [469][412] 14 11 L THRU-THE-BASE CHART (FIOP)
I [3551 [219]
1 I + I Ir .---- • I FOR 'THRU-THE-BASEPAN'FACTORY OPTION,
.N��- -- 1 c� FITTINGS FOR ONLY %, Y, d 2 ARE PROVIDED. or
( FOR BELOW LISTED MODELS. A FIELD
6-1/4 SUPPLIED 1/2' ADAPTER IS REQUIRED
-4 FLUE [159] 44 BETWEEN BASE PAN FITTING AND GAS VALVE:
29-S18 [100] '—3-1/4 48HCD,S408
[751] HOOD y 14 PF [831
[356]
TOP 25-1/2--
[641]
H 1-1/4
4-5/8 t321 8 13021
[1181
. . . /N .- "..
• H DISCONNECT I
-
CONTROL BOX • FILTER
COA, LOCATION ACCESS PANEL E STD.
COIL
G, : �� CONDENSATE
IN I
11 OPTIONAL INDOOR BLOWER •
•
M. FACTORY
ACCESS
OPTIONAL • • INSTALLED ----- I _
FACTORY 27-7/8 li
OUTSIDE
INSTALLED I DISCONNECT 27-1/< \ AIR
I:,
CONVENIENCE IN [7091 • FCs• i--HANDLE 13-t/6 -'— [106] 26
OUTLET C L`Jf/ I3341 SUPPLY AIR [659]
HANDLE—��
1I 6-5/6 .b • r. - 6-1/8
_a� _—_I
B ___ �B [166] R r100 I 1' f 1 00�% nsn _ -
3-3/4 2-5/8 —n 59-1/2 8-3/8 6-5/B °Mil 7[1611 [1711 4 6-1/8 4-3/8
[951 T15101 [67] 37 [214] 37-7/5 E1551 11131
TYP [940] [9621
CURB
LEFT WIDTH -• 88-1/8 - [107561 BAROMETRIC
[22381 SUPPLY 4
* RETURN RELIIEF
AIR
FRONT RIGHT
NETT DATE SUPERCEDES 48TC 08-12 SINGLE ZONE ELECTRICAL RE4
1 OF 03-08-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F
Packaged Rooftop Builder 1.49n Page 2 of 7
1
Certified Drawing for 48TC-7.5T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:16PM
UNITED P.D.BDN 48DN THIS DOCUMENT IS THE PROPERTI OF CARRIER CORPORATION SUBMISSION OF THESE 004050GS DR DOCUMENTS
STD. UNIT CORNER CORNER CORNER CORNER TECHNOLOGIES SYRACUSE,Nr CND IR DELIMERED UPON THE ERPRESS USEDITIDN OT C RRI DOES NOT CONSTITUTE PART PERFORMANCE OR
CONTEtlTS PILL XOi RE DISCLOSED DR USED VITNOUT CARRI EF
UNIT OUTDOOR WEIGHT PF• NEIGNT IA1 WEIGHT IBI HEIGHT(C) WEIGHT (DI C.G. CARRIER t3zn CORPORATION'S WRITTEN CONSENT. ACCEPTANCE of CONTRACT.
COIL TYPE LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z
48TC-A08 RTPF 780 354 178 81 158 72 209 95 236 107 41 1/2[10541 33 7/8[860] 20 1/2[5211 DFF STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
48TC-AD9 RTPF 92D 418 212 96 183 83 243 110 282 128 40 7/8[10381 34 [8641 23 1/8[5871 FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
48TC-Al2 RTPF 93D 422 216 98 196 89 247 112 272 123.5 42 11067] 33 1/8[841] 24 1/4[6161
48TC-008 RTPF 835 379 164 74.5 170 77.2 255 115.8 246 111.7 44 7/8[11401 35 5/8[905] 19 3/8 [4921
48TC-009 RTPF 930 422 228 103.5 187 65 232 105.3 283 128.5 39 3/4[10101 32 7/8 18351 18 5/8 [473]
48TC-012 RTPF 940 427 231 104.9 189 85.8 234 106.2 286 129.8 39 3/4[1010] 33[838] 18 1/2 [4701
48TC-008 MCHX 805 365.5 160 72.6 153 69.5 240 109 260 118 43[10921 36 3/8 [924] 20 3/8[517.7] 1
481C-D12 MCHX 895 406.3 185 84 176 79.9 260 118 274 124.4 42 7/8[10891 35 1/2 [902] 22 7/8[5811
RTPF - ROUND TUBE, PLATE FIN (COPPER/ALUM) CORNER A
MCHX - NOVATION !ALUM/ALUM CORNER B
'
170 n 11I1',1r //,. s
CORNER D _ CORNER C
TOP
x
•
•
Z a.
ED
i .
660 ; .,,. .,=. : • : 00
FRONT
SHEET DATE SUPERCEDES 48TC 08-12 SINGLE ZONE ELECTRICAL 48TM500985 REV
2OF2 03-08-10 11-24-08 COOLING WITH GAS HEAT F
Packaged Rooftop Builder 1.49n Page 3 of 7
Certified Drawing for 48TC-7.5T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:16PM
Service Clearance
p.
C11247
LOCATION DIMENSION CONDITION
48-in(1219 mm) •Unit disconnect is mounted on panel
36-in(914 mm) •If dimension-B is 12-in(305 mm)
A 18-in(457 mm) •No disconnect,convenience outlet option
•Recommended service clearance(use electric screwdriver)
12-in(305 mm) •Minimum clearance(use manual ratchet screwdriver)
36-in(914 mm) •Unit has economizer
8 12-in(305 mm) •If dimension-A is 36-in(914 mm)
Special •Check for sources of flue products within 10-ft of unit fresh air intake hood
C 36-in(914 mm) •Side condensate drain is used
18-in(457 mm) •Minimum clearance
48-in(1219 mm) •No flue discharge accessory installed,surface is combustible material
42-in(1067 mm) •Surface behind servicer is grounded(e.g.,metal,masonry wall,another unit)
D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for adjacent units or building fresh air intakes within 10-ft of this unit s
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
Packaged Rooftop Builder 1.49n Page 4 of 7
I
Performance Summary For 48TC-7.5T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:16PM
Part Number:48TCEDO8A2A5-0A0G0
ARI EER• _ - _ 11.00
IEER• _ _ 12.8
Base Unit Dimensions
Unit Length. - - . 88.1 in
Unit Width• 59.5 in
Unit Height •----- ______-__41.3 in
-- ----------
Operating Weight
Base Unit Weight 835 lb
Medium Heat 15 lb
Medium Static Option (Belt Drive). _ 15 lb
2 Speed Fan Controller (VFD)• 20 lb
Total Operating Weight 885 lb
Unit
Unit Voltage-Phase-Hertz. _ 208-3-60
Air Discharge. Vertical
Fan Drive Type• Belt
Actual Airflow. 3000 CFM
Site Altitude. _ 39 ft
Cooling Performance
Condenser Entering Air DB• - 90.0 F
Evaporator Entering Air DB• 78.0 F
Evaporator Entering Air WB• 64.4 F
Entering Air Enthalpy _ 29.49 BTU/lb
Evaporator Leaving Air DB• 56.2 F
Evaporator Leaving Air WB• - _ 54.6 F
Evaporator Leaving Air Enthalpy. 22.93 BTU/lb
Gross Cooling Capacity 88.40 MBH
Gross Sensible Capacity. 70.45 MBH
Compressor Power Input 5.97 kW
Coil Bypass Factor. 0.104
Mixed Air
Outdoor Air Airflow. ______________._._____-...__._._- 420 CFM
Outdoor Air DB _____ _ . .90.0 F
Outdoor Air WB• _ _ _-- 67.0 F
Outdoor Air Htg.Temp • 22.0 F
Return Air DB• - 76.0 F
Return Air WB• - _ 64.0 F
Return Air Htg.Temp • _ 70.0 F
Heating Performance
Heating Airflow. 3000 CFM
Entering Air Temp. 63.3 F
Leaving Air Temp. 109.0 F
Gas Heating Input Capacity. 120.0/180.0 MBH
Gas Heating Output Capacity' 98.0/ 148.0 MBH
Temperature Rise. 45.7 F
Thermal Efficiency(%)• 82.0
Supply Fan
External Static Pressure' 0.60 in wg
Fan RPM• _ 761
Fan Power. _ 1.64 BHP
NOTE. _ _ Selected IFM RPM Range: 733 -949
Packaged Rooftop Builder 1.49n Page 5 of 7
Performance Summary For 48TC-7.5T-E-3PH
Project: Stock Units 2019 02/22/2019
Prepared By: 04:16PM
Electrical Data
Voltage Range. 187 -253
Compressor#1 RLA. 13.6
Compressor#1 LRA• 83
Compressor#2 RLA. 13.6
Compressor#2 LRA• 83
Indoor Fan Motor Type- MED
Indoor Fan Motor FLA• 8.4
Combustion Fan Motor FLA(ea). 0.48
Power Supply MCA. 43
Power Supply MOCP(Fuse or HACR). 50
Disconnect Size FLA. 45
Disconnect Size LRA• 227
Electrical Convenience Outlet. None
Outdoor Fan [Qty/FLA(ea)]. 2/1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 98.2 95.2 85.8
125 Hz 91.4 86.0 84.3
250 Hz 77.9 73.0 80.5
500 Hz 70.7 66.3 78.7
1000 Hz 67.1 63.3 76.4
2000 Hz 65.7 58.5 72.7
4000 Hz 67.1 57.8 68.3
8000 Hz 69.3 57.4 65.1
A-Weighted 79.4 74.3 82.0
Advanced Acoustics
4II i 411) i
);
tit -aWe'l t
a-44
lob 0
Advanced Accoustics Parameters
1. Unit height above ground 30.0 ft
2. Horizontal distance from unit to receiver. 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction. 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Packaged Rooftop Builder 1.49n Page 6 of 7
Performance Summary For 48TC-7.5T-E-3PH
Project:Stock Units 2019 02/22/2019
Prepared By: 04:16PM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
A 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1 89.6 Lw
B 59.6 68.2 71.9 75.5 76.4 73.9 69.3 64.0 81.4 LwA
C 53.4 51.9 48.1 46.3 44.0 40.3 35.9 32.7 57.2 Lp
D 27.2 35.8 39.5 43.1 44.0 41.5 36.9 31.6 49.0 LpA
Legend
A Sound Power Levels at Units Acoustic Center, Lw
B A-Weighted Sound Power Levels at Units Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Fan Curve
2'0 0 RP,A 1000 FPM
1100 RP 1 0 RPM
1.8
800 RPM
1.6
1.4
- 700 RPM
c 1.2 500
!10
co0.8 WAIL\
) 500 RPM
0.6 Nworiv
400 RPM
0.4
3.00 BH"
2•!2HP
1.50 BHP
0.2 1.00 8HP -
_ 0.50 BH•
• 5 BHP
00 - I I I I I I I I I I I I I . I . . . I I , I I l . I . l I I
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4
Airflow(CFM-thousands)
RPM=761 BHP= 1.64 Maximum RPM= 1400 Maximum BHP=4.70
Note:Please contact application engineering for selections outside the shaded region.
SC-System Curve RP-Rated Point
Packaged Rooftop Builder 1.49n Page 7 of 7