Report (2) g +� .202.( - 00954_ RECEIVED Li ('off F() y NOV 15 2021 1 T I G A R D A F C CITY OF TIGARD BUILDING DIVISION -MECHANICAL CUT SHEETS 11/09/2021 48TC-7.5T-E-3PH NO EXCEPTIONS NOTED [) REJECTED [ ] B ROA E 80 BSpec MAKE CORRECTIONS NOTED [ ] REVISE AND RESUBMIT [ ] THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN Carrier Thermostat CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE E C D-S RT34CA-D 2 D H CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR OR DEVIATION FROM CONTRACT DOCUMENTS. CIDA I M—PY4G-10 COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE PORTLAND,OREGON REVIEWED 11/09/2021,BY curtisg model-5700-submittals-16982 model-7600-submittals-398 Project: Tag: METALAIREn. Engineer: OFFICE COPY Contractor: ®T Submittal:b m itta I. 5700 Date: RECEIVED Square Face Diffusers 2 Cone - Round Neck NOV 15 2021 Models: Steel Aluminized Steel Aluminum ❑5700-1 ❑5700-1 AS El 5700-1AL Surface Mount CITY OF TIGARD 05700-6 ❑5700-6 AS 0 5700-6 AL Lay in T-Bar BUILDING DIVISION 05700-6P 0 5700-6P AL Lay in T-Bar Panel 5700-7 5700-7 AS Concealed T-Bar 5700-9 5700-9 AS 5700-9 AL Bolt Slot/Donn Fineline (USG)Ceiling Grid Models: 5700-1 (Steel-Surface Mount-24 x 24) Models: 5700-1 (Steel-Surface Mount-12 x 12) _5700-1 AS (Aluminized Steel Surface Mount-24 x 24) _5700-1 AS (Aluminized Steel Surface Mount-12 x 12) 5700-1 AL (Aluminum-Surface Mount-24 x 24) _5700-1 AL (Aluminum-Surface Mount-12 x 12) Neck Size-1 Neck Size-8 r 1Earthquake Tab 8 r 1 e _1 Latch Tabs 1 (4) 5700 Latches 2 3 \ 3 8 50 ° } � 3 4 8 1 _} } 1 4 r �. _ Ceiling Opening=9}x 9} } Ceiling Opening=21 4 x 21 4 Overall Diffuser=11 i x 11 a - Overall Diffuser=23 4 x 23 4 For surface mount installations,use of plaster frame is recommended. For surface mount installations,use of plaster frame is recommended. Available Neck Sizes 6&8 Available Neck Sizes 6,8,10,12,14,15 Models: _ 5700-6 (Steel-Lay in T-Bar-24 x 24) Models: _5700-6 (Steel-Lay in T-Bar-12 x 12) 5700-6 AS (Aluminized Steel Lay in T-Bar-24 x 24) 5700-6 AS (Aluminized Steel Lay in T-Bar-12 x 12) — 5700-6 AL (Aluminum-Lay in T-Bar-24 x 24) _5700-6 AL (Aluminum-Lay in T-Bar-12 x 12) t 1 Neck Size-g Earthquake Tab Neck Size-3 7 1 e Latch Tabs i 1 i } I k 1 34 5 i ZEZtair.____ ESSE --..,._ Overall Face Size=23 3 x 23 4 Overall Face Size=11 4 x 11 a 4 T-Bar Module=24 x 24 — T-Bar Module=12 x 12 — Available Neck Sizes 6,8,10,12,14,15 Available Neck Sizes 6&8 Model 1J5700-6P (Steel-Lay in T-Bar Panel) Model: 1_5700-6P (Steel-Lay in T-Bar Panel) 5700-6P AL (Aluminum-Lay in T-Bar Panel) _5700-6P AL (Aluminum-Lay in T-Bar Panel) Neck Size-8 — 1 Neck Size-1 8 1 I ill r------." I �'8 r' I �'e } } Overall Face Size=234 x 234 — Overall Face Size=19-x 194 T-Bar Panel=24 x 24 — T-Bar Panel=20 x 20 — Available Neck Sizes 6&8 Available Neck Sizes 6&8 Revision: G Date: 2/22/2019 Dimensions are in Inches Page: 1 of 2 Metal Industries,Inc. Clearwater,FL (727)441-2651 Fax(800)865 8383 www.metalaire.com sales@metalaire.com Proj Tag: METALAIREect: ,. Engineer:Contractor: Submittal: 5700 Date: Square Face Diffusers 2 Cone - Round Neck Models: Steel Aluminized Steel Aluminum —5700-7 —5700-7 AS Concealed T-Bar _5700-9 _5700-9 AS ❑5700-9 AL Bolt Slot/Donn Fineline(USG) Ceiling Grid Models: ❑5700-7 (Steel-Lay in T-Bar-24 x 24) ❑5700-7 AS (Aluminized Steel-Lay in T-Bar-24 x 24) Neck Size- Earthquake Tab Latch Tabs ` I l it 1 ?? 32 41 2 Overall Face Size=23 a x 23 T-Bar Module=24 x 24 Available Neck Sizes 6,8,10,12,14,15 Models: 5700-9 (Steel-Lay in T-Bar-24 x 24) — 5700-9 AS (Aluminized Steel-Lay in T-Bar-24 x 24) —5700-9 AL (Aluminum-Lay in T-Bar-24 x 24) Neck Size-g { Earthquake Tab Latch Tabs ( t 32 41 2 zzzef 23ax233 Overall Face Size=23 e x 23 e T-Bar Module=24 x 24 Available Neck Sizes 6,8,10,12,14,15 Notes: ❑ (check if provided) 1.Available Finishes 2.Available Accessories 3.Available Options 4.Construction Details Standard Finish: Accessories Shipped Unattached •Concealed Mount FMCC • Available Sizes Only as Listed ❑01 White — G3 Equalizing Grid • Available Neck Sizes as Listed Optional Finish(extra charge): BDS Butterfly Damper ❑02 Satin Silver _RSD Radial Shutter Damper 03 Black ❑BAF Directional Baffles 28 Custom Color/Setup Charge Accessories Shipped Factory Installed FGBP Factory Installed R6 Insulation on Select Sizes and Models Revision: H Date: 2/22/2018 Dimensions are in Inches Page: 2 of 2 Metal Industries,Inc. Clearwater,FL (727)441-2651 Fax(800)865 8383 www.metalaire.com sales@metalaire.com Project: pin Engineer: OFFICE COPY METALAIR ETM Contractor: Submittal: 7600R RECEIVED Date: Perforated Return Diffuser - Round Neck NOV 15 2021 12 x 12 and 24 x 24 Module Models:07600R-1 Steel Backpan & Face - Surface Mount CITY TIGARD 07600R-1 DFSteel Backpan & Face -Surface Mount- Drop Face BUILDINNGG DIVISION 07600R-1 AFSteel Backpan &Aluminum Face -Surface Mount 07600R-6 Steel Backpan & Face- Lay in T-Bar 07600R-6 AF Steel Backpan &Aluminum Face- Lay in T-Bar 07600R-6 AL Aluminum Backpan & Face- Lay in T-Bar Models: 7600R-1 (Steel Backpan&Face-24 x 24 Surface Mount) 7600R-1 DF (Steel Backpan&Face-24 x 24 Surface Mount-Drop Face) 7600R-1 AF (Steel Backpan&Aluminum Face-24 x 24 Surface Mount) Nominal Round Neck O.D.-8 Back Pan } 2 Concealed Spring Latches Earthquake Tab 38 I 2-Concealed Hinges 1 J - \\ Border 1 3 8 `Perforated Face Optional Drop Face B (Border 1 DF) Ceiling Opening=23 x 23 Overall Diffuser=25 8 x 25 8 - Medm6: 7600R-1 (Ct..l Dackpai&rat=-12 x 12 Sarfac=M.,ld h) 7600R-1 DF (Steel Backpan&Face-12 x 12 Surface Mount-Drop Face) 7600R-1 AF (Steel Backpan&Aluminum Face-12 x 12 Surface Mount) 1-Concealed Nominal Round Neck Spring Clip -1 O.D.-8 Back Pan 4 / Earthquake Tab 2 1_ • �2-Concealed Hinges ee \Hinged,Removable Border 1 DF Perforated Face Optional Drop Face Ceiling Opening 11 x 11 4 - Overall Diffuser 138-x 138- Models: 7600R-6 (Steel Backpan&Face-24 x 24 Lay in T-Bar) 7600R-6 AF (Steel Backpan&Aluminum Face-24 x 24 Lay in T-Bar) 7600R-6 AL (Aluminum Backpan&Face-24 x 24 Lay in T-Bar) 7600R-6 DF (Steel Backpan&Face-24 x 24 Surface Mount-Drop Face) Nominal Round Neck O.D.- a II Back Pan /// 2 Concealed Spring Latches Earthquake Tab 381 ^ - 2-Concealed Hinges e Perforated Face Optional Drop Face (Border 1 DF) Overall Diffuser=23 4 x 23 4 T-Bar Module=24 x 24 - Models: 7600R-6 (Steel Backpan&Face-12 x 12 Lay in T-Bar) 7600R-6 AF (Steel Backpan&Aluminum Face-12 x 12 Lay in T-Bar) Nominal Round Neck 1 Back Pan O.D.-8 Earthquake Tab 2 2 Concealed Hinges a EME Hinged,Removable Perforated Face Ceiling Opening 11 a x 11 T-Bar Module=12 x 12 IRevision: D I Date: 8/2016 I Dimensions are in Inches I Page: 1 of 2 I Project: Tag: METALAIRE� Engineer: Contractor: Submittal: 7600R Date: Perforated Return Diffuser - Round Neck 12 x 12 and 24 x 24 Module Models:07600R-8 Steel Backpan & Face -Tegular T-Bar 07600R-8 AF Steel Backpan &Aluminum Face -Tegular T-Bar 07600R-8 AL Aluminum Backpan & Face-Tegular T-Bar 07600R-9 Steel Backpan & Face- Donn Fineline Ceiling Grid 07600R-9 AF Steel Backpan &Aluminum Face - Donn Fineline Ceiling Grid Models: 7600R-8 (Steel Backpan&Face-24 x 24 Tegular T-Bar) 7600R-8 AF (Steel Backpan&Aluminum Face-24 x 24 Tegular T-Bar) 7600R-8 AL (Aluminum Backpan&Face-24 x 24 Tegular T-Bar) Nominal Round Neck O.D. -i3 �Earthquake Tab 1 Concealed Back Pan 381 Spring Latches 2 Concealed Hinges o "" Removable Perforated Face 3 8 Overall Diffuser=234 x 234 T-Bar Module=24 x 24 Models: 7600R-8 (Steel Backpan&Face-24 x 24 Tegular T-Bar) 7600R-8 AF (Steel Backpan&Aluminum Face-24 x 24 Tegular T-Bar) 7600R-8 AL (Aluminum Backpan&Face-24 x 24 Tegular T-Bar) Nominal Round Neck O.D.-8 Back Pan Earthquake Tab Concealed Hinges Removable Perforated Face 3- 114x114 Tegular T-Bar=12 x 12 8 Models: 7600R-9 (Steel Backpan&Face-24 x 24 Donn Fineline Ceiling Grid) 7600R-9 AF (Steel Backpan&Aluminum Face-24 x 24 Donn Fineline Ceiling Grid) Nominal Round Neck O.D.-$ Earthquake Tab Concealed ,..,. Back Pan _2 Concealed Spring Latches Spring Latches tttttt 38 Removable Perforated Face 3 8 Overall Diffuser=23 x 234 Module Size=24 x 24 Notes: ❑ (check if provided) 1.Available Finishes 2.Available Accessories 3.Available Options 4.Construction Details Standard Finish: Round Necks: • Available only in listed sizes. ❑01 White. ❑ BDS-Butterfly Damper. • Seismic tabs standard on all units. Optional Finish(additional charge): ❑ RSD-Radial Shutter Damper. ❑03 Black. Replacement Parts: ❑02 Satin Silver ❑ Replacement Steel Face Plates. ❑28 Custom Color. ❑ Replacement Aluminum Face Plate. ❑22(BBP)Black back pan/white face. IRevision: C I Date: 8/2016 I Dimensions are in Inches I Page: 2 of 2 I 0 MICroMet1 Date: Weights: Units: 48TC D12 Part Number: 12/14/2018 701bs/31.75kg ECD-SRT34CA-D2DH Submitted To: wbeck@airefco.com Job: Notes: Economizer-Economizer-Ultra Low Leak Economizer,Vertical Orientation,Honeywell Jade W7220 Single/Multiple Speed Electromechanical Controller,Adjustable Dry Bulb Sensor,Honeywell Actuator.Painted Rain Hood With Aluminum Filter,Barometric Relief,All Necessary Panels And Hardware Included. RECEIVED NOV 152021 CITY OF TIGARD BUILDING DIVISION Economizer Harness ° Filter Access = with PL6 Plug Door Provided ,� on Unit E 23 3116" Micrometl j s Economizer ..........,,Filters �r F4 22 3/S" Communicating P ; ' Actuator / %%474.11, /r �a � Barometric Relief 0 I Damper / �� r` Economizer , Outside Air Hood , j.% Sensor i i._ External Gear '111 — Knockouts for Driven Dampers °Wiring for Optional Prop Side View Power Exhaust The Information contained in this drawing is the sole property of Micrometl Corporation.Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited. Indianapolis_3035 N.Shadeland Ave.,Indianapolis,IN 46226_800.MMC.HVAC••Sparks_905 Southern Way,Sparks,NV 89431_800.884.4MMC••Longview_201 Kodak Blvd.,Longview,TX 75602_903.248.4800 Date: Weights: Units: 48TC D12 Part Number: M i c ro M etl 12/14/2018 701bs/31.75kg ECD-SRT34CA-D2DH Submitted To: wbeck@airefco.com Job: Notes: Economizer-Economizer-Ultra Low Leak Economizer,Vertical Orientation,Honeywell Jade W7220 Single/Multiple Speed Electromechanical Controller,Adjustable Dry Bulb Sensor,Honeywell Actuator.Painted Rain Hood With Aluminum Filter,Barometric Relief,All Necessary Panels And Hardware Included. Compliant Economizer: 1. Title 24:Economizers meet California Energy Commission Title 24-2013/2016 prescriptive section 140.4(damper leakage etc.),and mandatory section 120.2.i for Fault Detection and Diagnostic controls(JADE HJW10). 2. ASHRAE 90.1:Economizers meet ASHRAE 90.1-2013/2016 damper leakage requirements,and meet 2016 Fault Detection and Diagnosis requirements. 3. IECC:Economizers meet IECC 2012,IECC 2015,and IECC 2018 for outside air,return air,and relief damper(when provided)leakage requirements,and IECC 2015 and IECC 2018 for Fault Detection and Diagnostic requirements.Note:IECC 2015 and IECC 2018 requires differential return air sensor,which is included in some models(i_e_D2XH)and must be ordered separately on others(i.e.D2DH,D2ZH). 4. AMCA:Outside air and return air(volume)dampers are AMCA Class 1A rated at 1"w.g.Refer to MicroMetl NS1 catalog sheet on web site for details.Relief air dampers(when provided)are also AMCA rated.Refer to GR1 series catalog sheet on web site for details. Features: • For single or 2 speed indoor fan units with Central Terminal Board(CTB)and Compressor Staging Board_Other control options available. • Gear driven design for trouble-free operation,eliminating slippage and binding associated with standard linkage_ rat! • Includes assembled rainhood with aluminum water entrainment filters in the outside air section. OUR ▪ Rainhood is sloped for water run-off. tPfa of • Built-in barometric relief damper provided.Power exhaust options available_ .411 111014111,11T\ • NC contest All harnesses and plugs needed are provided. uwamo. Thies osm.mat • Uses standard factory filter access door shipped with HVAC unit. MicroMetl Corporation • If factory hinged access door option is installed on unit,an additional kit is required to seal hinged door properly. GR1 certifies and that the models -OEM part no.CRPECONV004A00 or MicroMetl part number 0640-0200-HDANGL herein are licensed to bear the AMCA Seal. Notes: The ratings shown are based on tests and 1. Control systems include Honeywell W7220 JADE controller,mixed(supply)air temperature sensor,OA sensor in description,and spring-return procedures performed in accordance with AMCA communicating actuator(some include differential return sensor as noted). Publication 511 and 2. JADE W7220 controller is field mounted in unit's control box_ comply with requirements of the AMCA Certified 3. Mixed(supply)air sensor is field installed in indoor blower fan section. Ratings Programs. The AMCA Certified 4. Differential return sensor(included in"-D2XH"and"-D2ZH"models or can be ordered separately-MicroMetl Part No.9901-2022-DIFF JC2)is field Ratings Seal applies installed in return duct. to Air Leakage and Air Performance ratings. 5. ASHRAE,IECC,and Title 24 require the economizer controller be capable of reporting faults to a fault management application accessible by day-to-day operating or service personnel,or annunciated locally on zone thermostats or in some codes other devices are acceptable.Refer to applicable code requirements and to MicroMetl instructions for suggestions. 6. For older single speed models without the Central Terminal Board the'`D2"part number is replaced by"-DJ' (See separate submittal). The Information contained in this drawing is the sole property of Micrometl Corporation.Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited. Indianapolis_3035 N.Shadeland Ave.,Indianapolis,IN 46226_800.MMC.HVAC••Sparks_905 Southern Way,Sparks,NV 89431_800.884.4MMC••Longview_201 Kodak Blvd.,Longview,TX 75602_903.248.4800 . RECEIVED NOV 15 2021 TP—PAC, TP—PHP, TP—PRH ARD TP—NAC, TP—NHP, TP—NRH VISION Performance' Series Edge' Thermostat Clarrier) turn to the experts Product Data • The Carrier Performance" Series Edge' thermostats consists of programmable and non-programmable air conditioner,heat pump I / and Thermidistat" controls. These units feature non-mercury, l" non-lead based electronic controls built into a subtle,slim plastic - #_ enclosure. ' ,1';' FEATURES/BENEFITS 0., - + Edge Programmable &Non-Programmable t 1 • Outdoor Air Temperature(OAT)sensor option • Auto changeover available ' • Battery free i 13 t 'I.,. L .f , ; i, • Non-volatile memory to retain settings during a power outage • Keypad lockout • English/Metric units selection • Filter/UV light/Humidifier pad replacement indicators • Continuous display hack-lighting configurable • Hybrid Heat compatible A07049 • RC/RH power compatible Fig.1- Performance Series Programmable Thermostat • 2-wire communicating installation option 1 Edge Programmable models • ExP" expansion port*for use with future enhancements and/or features • Programmable with personal computer** • 7,5-2,All Days programmable -7e • 4 or 2 periods per day programmability [ l t • Programmable fan by period • Vacation mode controls temperature and humidity • Remote room sensor option �;1 .t ►Adjusts automatically for Daylight Savings Time Edge Non-Programmable models • Touch ItGo programmability Air Conditioner Control • i-stage heat/1-stage cool Heat Pump Control • 3-stage heat/2-stage cool A07049 Fig.2-Performance Series Non-programmable Thermostat Thermidistat Control • Heat pump 2-stage or Hybrid Heat 3-stage heat/2-stage US patents:US7287709 B2,US20080147242 Al,USD582800 SI,US20060165149 A1, cooling with humidity control U96956463 B2. • Humidity display • Humidify output for direct control of humidifier Designed and Assembled • Dehumidify output for variable-speed blowers 0 in the USA. • Hybrid Heat compatible • ExP acracsory(expansion port and memory card)sold separately ** Requires ExP accessory Ors `"' jF r- OFFICE Ct)1)y MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 T P -- P A C 0 1 Product Packaged Quantity T=Thermostat 01 =1 piece Series Equipment Type P=Performance AC=Air conditioning HP=Heat pump Not Defined RH=Relative humidity - =Place Holder Function Type P=Programmable cc N=Non-programmable I a. I Z DIMENSIONS = 5.2 in. gin- ld N. 5.2 is .71n^ 37 IT nj 1 [[1 ' - Q 132.08111111 33 02 mini I ..___. p.m m -228i ram I ' U5.09mm ' i i Z IX 5.2 W S.z in ,132.08 fling I32.09 runt I a. • iJ U i_.__ Single Two etSingle Two pi.,,, Yiece a. Yi c Pie. I a t- A07137 A07138 Fig.3-Performance Series Programmable Thermostat Fig.4- Performance Series Non-programmable Thermostat PRODUCT DATA INFORMATION Wiring Requirements Physical Characteristics Standard 18 to 22 gauge,local wiring codes supersede Dimensions: See drawing Accessories Mounting: Vertical or horizontal J-box provisions PART NUMBER DESCRIPTION Electrical TSTATXXSEN01-B* Outdoor air temperature sensor Input volts/amps: 24VAC,3 VA,RC/RH compatible TP-EXP ExP Expansion Memory Port Environment TX-LBP01 Large decorative backplate for TP-Pxx and TP--Nxx Operating temperature/Relative humidity: 32°F (0°C) to -- 104°F(40°C),95%RH non-condensing EDGE-DR-ES05 Espresso Decorative Door Storage temperature/Relative humidity: -40°F (-40°C) to EDGE-DR-GL05 Gold Luster Decorative Door 134°F(57°C),95%RH non-condensing EDGE-DR-NA05 Natural Grain Decorative Door EDGE-DR-SB05 Saddlebrush Decorative Door EDGE-DR-OX05 Onyx Decorative Door EDGE-DR-QZ05 Quartz Decorative Door TX-2WR05 2-wire harness ZONECCORRSOI Remote room temperature sensor * The outdoor air temperature sensor must be used with the Thermidistat control in a Hybrid Heat system. 2 OPERATIONAL INFORMATION Heating/Cooling Setpoints Auto Changeover The heating/cooling setpoint range is from 50°F(10°C)to 90°F When Auto Changeover mode is selected, a change from heat to (32°C). A selectable range of 1-6° is enforced between heating cool(or vice versa)will not occur until an opposite mode demand and cooling desired temperatures. This is done by allowing one has existed for 20 minutes. When a setpoint is changed, Auto setting to "push" the other, to maintain this difference. (This Changeover timing is ignored to allow the heating/cooling difference is adjustable in Installer settings.) equipment to respond quickly. Auto Changeover mode can be Humidify/Dehumidify Setpoint Range disabled. The humidify setpoint range is from 10% to 46% RH in 2% RH Emergency Heat Mode increments. The dehumidify setpoint range is from 46% to 66% When the thermostat is controlling a heat pump and emergency RH in 2%RH increments. heat is selected, all Y signals are locked out, and W becomes Five-minute Compressor Time Guard energized upon a call for heat. This timer prevents the compressor from starting unless it has been Smart Recovery (Programmable models) off for at least 5 minutes. It can be defeated for I cycle by With Smart Recovery selected, transition out of setback begins a simultaneously pressing the FAN button and INCREASE fixed time period (Off, 30, 60, or 90 minutes selectable) before pc TEMPERATURE(UP)button. selected recovery time and gradually adjusts room temperature so 2 Equipment on indicators that the desired temperature will be achieved at selected recovery I time. O.When cooling equipment is ON, a COOL ON icon is displayed. When heating equipment is ON, a HEAT ON icon is displayed. Room Temperature Offset When auxiliary heating is ON(HP only), an AUX HEAT icon is Room temperature may be deliberately offset by up to 5° in either i displayed. direction. Humidify/Dehumidify Output On Indicators Programmable Fan(Programmable models) (Thermidistat Control) This selection allows the homeowner to program the fan selection Z to"Auto"or"Fan On"for each of the program schedule periods. When the operating mode is heat and the HUM output is energized p g` the"humidify"icon shall be displayed.When the operating mode I is cool,the dry contact is configured as a DEHUM output and there is a dehumidify demand or the cooling equipment is energized to I satisfy a dehumidify demand, the "dehumidify" icon shall be displayed. X 0 U aa, a 1- 3 40MB*D Ducted Style Ductless System Sizes 09 to 48 Carrie turn`to the experts °‘1 Installation Instructions . _ 1 FAAGs- O� TABLE OF CONTENTS O PAGE 030) SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 +3 i tt5 - 1, WIRING 4 DIMENSIONS 5 CLEARANCES 6 INSTALLATION LOCATION REQUIREMENTS 7 ii •!.1'iim INDOOR UNIT INSTALLATION 7 i " FAN PERFORMANCES 9 ELECTRICAL DATA 17 CONNECTION DIAGRAMS 17 WIRELESS REMOTE CONTROL INSTALLATION 19 NOTE: Read the entire instruction manual before starting the START—UP 20 installation. TROUBLESHOOTING 21 NOTE: Images are for illustration purposes only.Actual models may differ slightly. NO EXCEPTIONS NOTED NI REJECTED I ] MAKE CORRECTIONS NOTED [ ] REVISE AND RESUBMIT [ ] THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR OR DEVIATION FROM CONTRACT DOCUMENTS. CIDA COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE PORTLAND,OREGON REVIEWED 11/12/2021,BY curtisg SAFETY CONSIDERATIONS A WA R N I N G Installing, starting up, and servicing air—conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location(roofs,elevated structures,etc.). ELECTRICAL SHOCK HAZARD Only trained, qualified installers and service mechanics should Failure to follow this warning could result in personal install,start—up,and service this equipment. injury or death. Untrained personnel can perform basic maintenance functions such Before installing,modifying,or servicing system,main as cleaning coils. All other operations should be performed by electrical disconnect switch must be in the OFF trained service personnel. position.There may be more than 1 disconnect switch. When working on the equipment, observe precautions in the Lock out and tag switch with a suitable warning label. literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.Wear safety glasses and work gloves.Keep A WA R N I N G quenching cloth and fire extinguisher nearby when brazing. Use care in handling,rigging,and setting bulky equipment. EXPLOSION HAZARD Read these instructions thoroughly and follow all warnings or Failure to follow this warning could cautions included in literature and attached to the unit.Consult result in death,serious personal injury, local building codes and National Electrical Code(NEC)for and/or property damage. special requirements.Recognize safety information. Never use air or gases containing This is the safety—alert symbol A.When you see this symbol on 4 oxygen for leak testing or operating the unit and in instructions or manuals,be alert to the potential for refrigerant compressors. Pressurized personal injury.Understand these signal words:DANGER, mixtures of air or gases containing WARNING,and CAUTION.These words are used with the oxygen can lead to an explosion. safety—alert symbol.DANGER identifies the most serious hazards which will result in severe personal injury or death.WARNING CAUTION signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.NOTE EQUIPMENT DAMAGE HAZARD is used to highlight suggestions which will result in enhanced Failure to follow this caution may result in equipment installation,reliability,or operation. damage or improper operation. Do not bury more than 36 in.(914 mm)of refrigerant pipe in the ground.If any section of pipe is buried,there must be a 6 in. (152 mm)vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried,refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start—up. 2 PARTS LIST i Table 1—Parts List PART NO. NAME OF PART 1 AIR OUTLET 2 AIR INLET 3 AIR FILTER 4 ELECTRIC CONTROL CABINET 5 WIRED CONTROLLER 6 DRAIN PIPE(FIELD SUPPLIED) 7 WIRELESS REMOTE ri f • a • f ,,,pool_.! t 1 ea f o 9 ill r \ T • n d ' 2 I I O V d I. 1 I Fig.1 — Parts List i Notes: —If the outdoor unit is higher than the indoor unit,prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit.This ensures that rain drips from the connection pipe before it enters the wall. —Piping and the interconnecting wiring are field supplied. I —The illustration above is only a sketch.Different models may be slightly different. —Filter Standard on units produced after serial number 2815V10001 The following units are covered in these installation instructions. I Table 2—Indoor Units kBTUh V—Ph—Hz ID Model No. 9 208/230-1-60 40MBQB09D--3 12 208/230-1-60 40MBQB12D--3 18 208/230-1-60 40MBQB18D--3 24 208/230-1-60 40MBQB24D--3 36 208/230-1-60 40MBQB36D--3 48 208/230-1-60 40MBQB48D--3 1 3 SYSTEM REQUIREMENTS WIRING Allow sufficient space for airflow and servicing unit.See Fig.3 for All wires must be sized per NEC(National Electrical Code)or minimum required distances between the unit and the walls or CEC(Canadian Electrical Code)and local codes.Use the ceilings. Electrical Data table MCA(minimum circuit amps)and MOCP Piping (maximum over current protection)to correctly size the wires and the disconnect fuse or breakers respectively. IMPORTANT: Both refrigerant lines must be insulated Per caution note,only stranded copper conductors with a 600 volt separately. rating and double insulated copper wire must be used.The use of • Minimum refrigerant line length between the indoor and outdoor BX cable is not recommended. units is 10 ft.(3 m). Recommended Connection Method for Power and • Table 3 lists the pipe sizes for the indoor unit.Refer to the Communication Wiring—Power and Communication Wiring: outdoor unit installation instructions for other allowed piping The main power is supplied to the outdoor unit.The field lengths and refrigerant information. supplied 14/3 power/communication wiring from the outdoor unit Table 3—Piping Lengths to the indoor unit consists of four(4)wires and provides the 9K 12K 18K 24K 36K a8K power for the indoor unit.Two wires are high voltage AC power, Gas Pipe one is communication wiring and the other is a ground wire. In 3/8 1/2 1/2 5/8 5/8 5/8 (size-connection Recommended Connection Method for Power and (mm) (9.52) (12.7) (12.7) (16) (16) (16) type) Communication Wiring(To minimize communication wiring Liquid Pipe In 1/4 1/4 1/4 3/8 3/8 3/8 interference)Power Wiring: (size—connection (mm) (6.35) (6.35) (6.35) (9.52) (9.52) (9.52) type) The main power is supplied to the outdoor unit.The field supplied power wiring from the outdoor unit to the indoor unit consists of three(3)wires and provides the power for the indoor unit.Two wires are high voltage AC power and one is a ground ii wire. II To minimize voltage drop,the factory recommended wire size is 14/2 stranded with a ground. Communication Wiring: A separate shielded stranded copper conductor only, with a 600 1 volt rating and double insulated copper wire,must be used as the q communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire. fi A CAUTION 1 EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. • Wires should be sized based on NEC and local codes. • Use copper conductors only with a 600 volt rating and double insulated copper wire. 1 I t i r , 1 4 m: DIMENSIONS-INDOOR Air filter air inlet from rear side ,a‘K> '>. . < ' I irj-10''' ' .1. L B H2 4-install hanger H1 A Liquid side r' 0 1(25) o� MilF' Drain.i.e Gas side a � - 0 1(25) Test mouth&Test cover =F� Illo Drain.i.e - 0 U [aft, 7 C 1LIH 1(25)Drain connecting jpipe(for pump) 1' �t • Electric control box Outside Air Intake o E F imiumminnommiumm •liliiiii.M• coloommummicommii 1111 Air filter ic I. 7 I: Y .1111111111111 air inlet from bottom side Fig.2 - Indoor Unit Table 4-Indoor Unit UNIT:in(mm) OUTLINE AIR OUTLET AIR RETURN HANGER REFRIGERANT PIPE OPERATING DIMENSIONS OPENING SIZE OPENING SIZE BRACKERS LOCATIONS WEIGHT lb(kg) Size A B C D E F G H I J K L M H1 H2 W1 W2 9 27.6 8.2 25 22.4 2.5 19.4 1.3 4.6 23.4 7.8 3.1 29.1 13.8 4.7 5.6 3.7 5.9 39.9 (700) (210) (635) (570) (65) (493) (35) (119) (595) (200) (80) (740) (350) (120) (143) (95) (150) (18.1) 12 27.6 8.2 25 22.4 2.5 19.4 1.3 4.6 23.4 7.8 3.1 29.1 13.8 4.7 5.6 3.7 5.9 39.9 (700) (210) (635) (570) (65) (493) (35) (119) (595) (200) (80) (740) (350) (120) (143) (95) (150) (18.1) 18 36.2 8.2 25 22.4 2.5 28.07 1.3 4.6 32.0 7.8 3.1 37.8 13.8 4.7 5.6 3.7 5.9 50.7 (920) (210) (635) (570) (65) (713) (35) (119) (815) (200) (80) (960) (350) (120) (143) (95) (150) (23) 24 36.2 10.6 25 22.4 2.5 28.07 1.3 7.0 32.0 10.2 0.7 37.8 13.8 4.7 5.6 3.7 5.9 57.3 (920) (270) (635) (570) (65) (713) (35) (179) (815) (260) (20) (960) (350) (120) (143) (95) (150) (26) 44.8 10.6 30.5 27.9 2.5 36.7 1.3 7.0 40.7 10.2 0.7 46.5 19.3 4.7 5.6 3.7 5.9 77.1 36 (1140) (270) (775) (710) (65) (933) (35) (179) (1035) (260) (20) (1180) (490) (120) (143) (95) (150) (35) 47.2 11.8 34.1 31.4 3.1 38.1 1.5 8.0 43.0 11.3 1.7 48.8 19.7 6.9 7.8 6.1 8.3 99.2 48 (1200) (300) (865) (800) (80) (968) (40) (204) (1094) (288) (45) (1240) (500) (175) (198) (155) (210) (45) 5 urrrrrrrrrrrrr y . • CLEARANCES -INDOOR • INSTALLATION PLACE >11.8in(30cm) Strong aand durable ceilin Indoor unit >0.8in(2cm)I ICI ' Left Right 'I' side side 8 rn: • 1/ , l ��,v,, / �uii,- p >4in(10cm) >11.8in(30cm) - a.i Service access Ceiling A_ Floor iiiioiiaiiiaiiiiii//// MAINTENANCE SPACE A IService access COIL CONNECTION AREA CONDENSATE DRAIN PIPING AREA E V CONDENSATE PUMP SERVICE CLEARANCE SENSOR SERVICE CLEARANCE Filter service clearance Unit (only one side is required) A/2 I i 7 / A/2 I v ,AIO o G 7 / /lF---_i A >11.8in (30cm) Service access BLOWER/MOTOR SERVICE CLEARANCE PCB BOARD SERVICE CLEARANCE FILTER SERVICE CLEARANCE Fig.3 — Indoor Unit Clearances Table 5—Indoor Unit Clearance Capacity(Kbtu) A B C 9K 27.56 in.(70cm) 8.27 in.(21cm) 11.81 in.(30cm) 12K 27.56 in. (70cm) 8.27 in.(21cm) 11.81 in.(30cm) 18K 36.22 in.(92cm) 8.27 in.(21cm) 11.81 in.(30cm) 24K 36.22 in.(92cm) 10.63 in.(27cm) 11.81 in.(30cm) 36K 44.88 in.(114cm) 10.63 in. (27cm) 11.81 in. (30cm) 48K 47.24 in.(120cm) 11.81 in. (30cm) 15.75 in.(40cm) 6 38MARB Outdoor Unit Single Zone Ductless System Sizes 06 to 36 Carrier 51-, Product Data 0� �p INDUSTRY LEADING FEATURES / G\�p BENEFITS 6lOtio \\ A PERFECT BALANCE BETWEEN BUDGET �1 �,-�� LIMITS, ENERGY SAVINGS AND COMFORT. OlPr� ��t111111�����, \\\`�� --,-0- �t The 38MARB series ductless systems are a matched combination of jan outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires. r � The ductless system permits creative solutions to design problems such as: Fig. 1 —Sizes 06K-36K • Add-ons to current space(an office or family room addition) NOTE:Images are for illustration purposes only.Actual models may Special space requirements • differ slightly. • When changes in the load cannot be handled by the existing system TABLE OF CONTENTS • When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork PAGE • Historical renovations or any application where preserving the INDUSTRY LEADING FEATURES/BENEFITS 1 look of the original structure is essential. MODEL NUMBER NOMENCLATURE 3 STANDARD FEATURES AND ACCESSORIES 4 The ideal compliment to your ducted system when it is impractical or DIMENSIONS 5 prohibitively expensive to use ductwork. CLEARANCES 8 The compact indoor fan coil units take up very little space in the room SPECIFICATIONS 9 and do not obstruct windows.The fan coils are attractively styled to PERFORMANCE 10 COOLING PERFORMANCE-HIGH WALL 17 blend with most room decors.Advanced system components HEATING PERFORMANCE-HIGH WALL 20 incorporate innovative technology to provide reliable cooling COOLING PERFORMANCE-CASSETTE 23 performance at low sound levels. HEATING PERFORMANCE-CASSETTE 24 COOLING PERFORMANCE-DUCTED 25 HEATING PERFORMANCE-DUCTED 26 COOLING PERFORMANCE-CONSOLE 27 HEATING PERFORMANCE-CONSOLE 28 COOLING PERFORMANCE-AIR HANDLER 29 HEATING PERFORMANCE-AIR HANDLER 29 NO EXCEPTIONS NOTED [) REJECTED [ 1 APPLICATION DATA 30 MAKE CORRECTIONS NOTED [ 1 REVISE AND RESUBMIT [ ] WIRING 31 ELECTRICAL DATA 33 THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN CONNECTION DIAGRAMS 34 CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS NOT CLEARLY NOTED BY THE CONTRACTOR HAS NOT BEEN WIRING DIAGRAMS 35 REVIEWED. REVIEW SHALL NOT CONSTITUTE A COMPLETE CHECK OF GUIDE SPECIFICATIONS 39 ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR OR DEVIATION FROM CONTRACT DOCUMENTS. CIDA COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE PORTLAND,OREGON REVIEWED 11/12/2021,BY curtisg OFFICE COPY Specifications subject to change without notice. 38MARB:Product Data Inverter Technology Fast Installation The inverter driven compressor is designed to run at various input power This compact ductless system is simple to install.Only wires and piping frequencies(Hz)which controls the compressor's motor speed. need to run between the indoor and outdoor units.These units are fast and easy to install ensuring minimal disruption to customers in homes or the Even Temperature—The control package,including the inverter, workplace.This makes the 38MARB systems the equipment of choice monitors the outdoor and indoor temperatures as they relate to the for retrofit applications. selected indoor set point and adjusts the compressor speed to match the load and keep the system operating continuously rather than cycling Simple Servicing and Maintenance and creating temperature swings.This translates to higher comfort levels Removing the top panel of the outdoor unit provides immediate access to for the occupants. the control compartment,providing the service technician access to the diagnostic LEDs to facilitate the troubleshooting process.In addition,the Rapid Pull Down/Warm-Up—Comfort is increased by the inverter draw-thru design of the outdoor unit means that dirt accumulates on the system's ability to ramp up the compressor speed enabling the system to outside surface of the coil.Coils can be cleaned quickly from the inside reach the user selected room temperature set point quicker. using a pressure hose and detergent. Humidity Control—Running the system for longer periods and On the indoor units,service and maintenance expense is reduced due to continuously varying the compressor speed enhances the humidity the permanent easy to clean filters.Also,error codes are displayed on the control. front panel to alert the user to certain system malfunctions. Individual Room Comfort Built-in Reliability Maximum comfort is provided because each space can be controlled Ductless system indoor and outdoor units are designed to provide years of individually based on the usage pattern. trouble-free operation.Both the indoor and outdoor units are well protected.Whenever the microprocessor detects abnormal conditions,the Low Sound Levels unit stops and an error code appears. When noise is a concern,ductless systems are the answer.The indoor Inverter systems provide additional reliability due to the soft start.This refers to the ability of the inverter to start the compressor motor using units are whisper quiet.There are no compressors indoors,either in the conditioned space or directly over it,and there is none of the noise reduced voltage and reduced current.This feature is beneficial from an usually generated by air being forced through the ductwork. electrical standpoint(eliminates current spikes)as well as an overall reliability standpoint due to reduced stress on all associated system When sound ordinances and proximity to neighbors demand quiet components. operation,the 38MARB unit is the right choice.With the inverter technology,these units run at lower speeds most of the time resulting in Agency Listings reduced sound levels. All systems are listed with AHRI(Air conditioning,Heating,and Refrigeration Institute)and are UL certified per UL 60335-2-40 Inverter Technology—Enhanced Economical standard. Operation Ductless systems are inherently economical to operate.Individual rooms are heated or cooled only when required,and since the air is delivered directly to the space,there is no need to use additional energy to move the air in the ductwork.This economical operation is enhanced further when the inverter system output matches the load resulting in a more efficient system. Easy-To-Use Controls The systems have microprocessor-based controls to provide the ultimate in comfort and efficiency.The user friendly wired and wireless remote controls provide the interface between the user and the unit. Secure Operation If security is an issue,outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings.In addition,since the 38MARB can be installed close to an outside wall,coils are protected from vandals and severe weather. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 38MARB:Product Data MODEL NUMBER NOMENCLATURE OUTDOOR UNIT 38 MA R B Q 36 A 3 38=OUTDOOR UNIT VOLTAGE MA=MODEL 1=115-1-60 3=208/230-1-60 SYSTEM TYPE MAXIMUM NUMBER OF FAN COIL UNITS THAT OUTDOOR CAN BE CONNECTED TO THE OUTDOOR UNIT S- B=1:1 MAJOR SERIES NOMINAL CAPACITY 06-1/2 TON 09-3/4 TON 12-1TON 18-1-1/2 TONS UNIT TYPE 24-2 TONS Q=HEAT PUMP 30-2-1/2 TONS 36-3TONS ti ma CERTIFIED.. ARS M��r Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program For verification of certification for individual products,go to www.ahridirectory.org. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. 38MARB:Product Data STANDARD FEATURES AND ACCESSORIES Outdoor Units Ease Of Installation Low Voltage Controls S Crankcase Unit Comfort Features Microprocessor Controls S The crankcase heater is standard on all unit sizes.Heater clamps must be Auto Restart Function S placed around the compressor oil stump. Auto Changeover S Energy Saving Features Base pan Heater Inverter Driven Compressor S The base pan heater is standard on all unit sizes. 46°F Heating Mode(Heating Setback) S Safety And Reliability 3 Minute Time Delay For Compressor S High Compressor Discharge Temperature S Low Voltage Protection S Compressor Overload Protection S Compressor Over Current Protection S IPM Module Protection S Condenser High Temp Protection in Cooling Mode S Aluminum Hydrophilic pre-coated fins S Ease Of Service And Maintenance Diagnostics S Liquid Line Pressure Taps S Application Flexibility Crankcase Heater S Base pan Heater S Legend • S-Standard • A-Accessory Accessories Outdoor Unit Base Pan Base Rubber Quantity per Unit Model Number Plugs RCD Part No. 38MARBQ12AA1 38MARBQ06AA3 12600801A00077 13 38MARBQ09AA3 38MARBQ12AA3 38MARBQ18AA3 12600801A00077 25 38MARBQ24AA3 38MARBQ30AA3 12600801A00117 5 38MARBQ36AA3 NOTE:The base pan is built in with multiple holes for proper draining during the defrost process.For applications where it is required to seal these holes,and re-direct the condensate drain,rubber plugs are available through RCD. Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. A 38MAR8:Product Data DIMENSIONS Air inlet �. L1 (611 CON H (00(((iffikil111))))))))) : D L2 0 Ir\c==.3r j u th==v' Air outlet W Fig. 2-Outdoor Unit UNIT SIZES 12K 6K 9K 12K 18K 24K 30K 36K VOLTAGES 115V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V HEIGHT(H) IN(MM) 21.85(555) 21.85(555) 21.81(554) 21.81 (554) 26.50(673) 31.89(810) 31.89(810) 31.89(810) WIDTH(W) IN(MM) 30.12(765) 30.12(765) 31.69(805) 31.65(805) 35.04(890) 37.24(946) 37.24(946) 37.24(946) DEPTH(D) IN(MM) 11.93(303)) 11.93(303)) 12.99(330) 12.99(330) 13.46(342) 16.14(410) 16.14(410) 16.14(410) L1 IN(MM) 17.81 (452) 17.81 (452) 20.10(511) 20.10(511) 26.10(663) 26.50(673) 26.50(673) 26.50(673) L2 IN(MM) 11.25(286) 11.25(286) 12.50(317) 12.50(317) 13.70(347) 15.85(403) 15.85(403) 15.85(403) OPERATING LBS(KG) 66.80(30.30) 63.71 (28.9) 74.10(33.60) 73.60(33.40) 101.0(45.80) 134.50(61) 141.80(64.3) 150.10(68.10) WEIGHT Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. RECEIVED Unit Report For 48TC-7.5T-E-3PH NOV 15 2021 Project: Stock Units 2019 02/22/2019 Prepared By: CITY OF TIGARn 04:16PM BUILDING DIVISION Unit Parameters Dimensions (ft.in.)&Weight(lb.)*** Unit Model- 48TCEDO8A2A5-0A0G0 Unit Length• 7'4.125" Unit Size. 08(7.5 Tons) Unit Width. 4' 11.5" Volts-Phase-Hertz. 208-3-60 Unit Height. 3'5 25" Heating Type• Gas **k Total Operating Weight 885 lb Duct Cfg• Vertical Supply/Vertical Return Medium Heat '*' Weights and Dimensions are approximate. Weight does Round Tube Plate Fin Coils not include unit packaging. Approximate dimensions are provided primarily for shipping purposes.For exact dimensions and weights,refer to appropriate product data catalog. Lines and Filters Gas Line Size- 3/4 Condensate Drain Line Size- 3/4 Return Air Filter Type• Throwaway Return Air Filter Quantity 4 Return Air Filter Size• 16 x 20 x 2 Unit Configuration Medium Static Option (Belt Drive) Al/Cu-Al/Cu Base Electromechanical Controls Standard Packaging 2-Speed indoor fan motor controlled by VFD Warranty Information 1-Year parts(std.) 5-Year compressor parts(std.) 10-Year heat exchanger-Aluminized(std.) 15-Year heat exchanger-Stainless Steel(std.) No optional warranties were selected. NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 48TCEDO8A2A5-0A0G0 Rooftop Unit 1 Base Unit Medium Static Option (Belt Drive) Electromechanical control, No intake or exhaust option. 2 Speed Fan Controller (VFD) Packaged Rooftop Builder 1.49n Page 1 of 7 Certified Drawing for 48TC-7.5T-E-3PH Project:Stock Units 2019 02/22/2019 Prepared By: 04:16PM NOTES: ��II(({{ UNITED P.O.ROD 4805 THIS DOCUMENT IS TOE PROPERTY OF CARRIER CORPORATION SUBMISSION OF THESE DRAWINGS OR DOCUMENTS UNIT OUTDOOR K H wry TECHNOLOGIES SYRACUSE.MI CON IS DELIVERED UPON THE OSEDAR CONDITION THAT RRF DOES NUT CONSTITUTE PART PERFORMANCE OR 1. DIMENSIONS ARE IN INCHES, DIMENSIONS COIL TYPE ••R�� CORPENTS MILL MOT RE DCONSENED OR URED N[TXOUT CHARIER IN [ I ARE IN MILLIMETERS. 41 1/4 33 15 7/B CARRIER uzzl CORPORATION'S WRITTEN CONSENT. ACCEPTANCE OF CgITRA[T. 2. CENTER OF GRAVITY 48TC-A08 RTPF I10481 [658] [403] 49 3/8 37 1/4 27 7/8 CONNECTION SIZES 48TC-A09 RTPF [1253] [946] [708] 3.MO.DIRECTION OF AIR FLOW 49 3/8 31 1/4 15 1/8 A 1 3/8' [35] DIA FIELD POWER SUPPLY HOLE 48TC-Al2 RTPF 4D-3/B [12531 [946] [403] I Y� I10261 B 2 1/2' [64] DIA POWER SUPPLY KNOCKOUT 41 1/4 33 15 7/8 C 1 3/4' [51] DIA GAUGE ACCESS PLUG 48TC-D08 RTPF [10481 [658] [403] ° ° 48TC-D09 ROPE 49 3/8 31 1/4 15 7/8 i D 7/8' [22] DIA FIELD CONTROL WIRING NC".E1 [1253] [946] [403] 49 3/8 31 1/4 15 7/8 ECONOMIZER HOOD 20-3/4 E 3/4'-14 NPT CONDENSATE DRAIN 4BTC-D12 RTPF [1253] 19667 [603] (OPTIONAL( ] F 1/2'-14 NPT GAS CONNECTION 481C-D08 NCH% 41 1/4 33 23 3!1'-14 NPT GAS CONNECTION [10481 [658] [584.2] G 2' [51] DIA POWER SUPPLY KNOCK-OUT 48TC-D12 NCH, 49 3/8 37 1/4 11 4� "e ° [12531 [946] [279.47 THRU-THE-BASE CHART (FIELD INST) RTPF -ROUND TUBE, PLATE FIN (COPPER/ALUM) _ -- THESE ROLES REQUIRED FOR USE WITH ACCY KITS: NCH% -NOVATION (ALUM/ALUM) • �j� \\\\\\ I'I''"/� `'`111111 (92518 122/6 CRBTNPWR002AO1: GAS THRU CURB \• CRBTNPWR004A01: GAS THRU BASEPAN • p ® I RETURN AIR RETURN ' F,/i 1 I AIR THREADED WIRE REO'D HOLE _ __ _ _ \ ;��� CONDUIT SIZE USE SIZES(MAX.) //'E(T� W 1/2' ACC. 7/8' [22.2] FILTER ACCESS PANEL 1110' `= y ^ % 1/2' 24V 1/8' [22.2] (TOOL-LESS) E SAT. CONDENSATE - • Y 1 1//' (002,004) POWER I 3/4' [44.4] . ///�+ e �DAA IN OPENING 28-3/4 COONDENSER p/�p/�j� IN BASEPAN SUPPLY 37-5/8 40-3/8 11 f( Al 77317 [955] I1027] y 2 r 10041 3/4' FPT GAS 1 3/4° [41.4] NMN1C\mL///47711 : % SEE THRU AIR (0021 PROVIDES 3/4"FPT THRU CURB INDOOR COIL - AAG\VAAA�_U/�/////1 y - THE BASE SUPPLY 4 FLANGE 6 FITTING. HOLE SIZE: 2' [50.81 ACCESS PANEL ‘,„ j � CHART Y AIR • BACK 8 16 E i . [469][412] 14 11 L THRU-THE-BASE CHART (FIOP) I [3551 [219] 1 I + I Ir .---- • I FOR 'THRU-THE-BASEPAN'FACTORY OPTION, .N��- -- 1 c� FITTINGS FOR ONLY %, Y, d 2 ARE PROVIDED. or ( FOR BELOW LISTED MODELS. A FIELD 6-1/4 SUPPLIED 1/2' ADAPTER IS REQUIRED -4 FLUE [159] 44 BETWEEN BASE PAN FITTING AND GAS VALVE: 29-S18 [100] '—3-1/4 48HCD,S408 [751] HOOD y 14 PF [831 [356] TOP 25-1/2-- [641] H 1-1/4 4-5/8 t321 8 13021 [1181 . . . /N .- ".. • H DISCONNECT I - CONTROL BOX • FILTER COA, LOCATION ACCESS PANEL E STD. COIL G, : �� CONDENSATE IN I 11 OPTIONAL INDOOR BLOWER • • M. FACTORY ACCESS OPTIONAL • • INSTALLED ----- I _ FACTORY 27-7/8 li OUTSIDE INSTALLED I DISCONNECT 27-1/< \ AIR I:, CONVENIENCE IN [7091 • FCs• i--HANDLE 13-t/6 -'— [106] 26 OUTLET C L`Jf/ I3341 SUPPLY AIR [659] HANDLE—�� 1I 6-5/6 .b • r. - 6-1/8 _a� _—_I B ___ �B [166] R r100 I 1' f 1 00�% nsn _ - 3-3/4 2-5/8 —n 59-1/2 8-3/8 6-5/B °Mil 7[1611 [1711 4 6-1/8 4-3/8 [951 T15101 [67] 37 [214] 37-7/5 E1551 11131 TYP [940] [9621 CURB LEFT WIDTH -• 88-1/8 - [107561 BAROMETRIC [22381 SUPPLY 4 * RETURN RELIIEF AIR FRONT RIGHT NETT DATE SUPERCEDES 48TC 08-12 SINGLE ZONE ELECTRICAL RE4 1 OF 03-08-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F Packaged Rooftop Builder 1.49n Page 2 of 7 1 Certified Drawing for 48TC-7.5T-E-3PH Project: Stock Units 2019 02/22/2019 Prepared By: 04:16PM UNITED P.D.BDN 48DN THIS DOCUMENT IS THE PROPERTI OF CARRIER CORPORATION SUBMISSION OF THESE 004050GS DR DOCUMENTS STD. UNIT CORNER CORNER CORNER CORNER TECHNOLOGIES SYRACUSE,Nr CND IR DELIMERED UPON THE ERPRESS USEDITIDN OT C RRI DOES NOT CONSTITUTE PART PERFORMANCE OR CONTEtlTS PILL XOi RE DISCLOSED DR USED VITNOUT CARRI EF UNIT OUTDOOR WEIGHT PF• NEIGNT IA1 WEIGHT IBI HEIGHT(C) WEIGHT (DI C.G. CARRIER t3zn CORPORATION'S WRITTEN CONSENT. ACCEPTANCE of CONTRACT. COIL TYPE LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z 48TC-A08 RTPF 780 354 178 81 158 72 209 95 236 107 41 1/2[10541 33 7/8[860] 20 1/2[5211 DFF STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. 48TC-AD9 RTPF 92D 418 212 96 183 83 243 110 282 128 40 7/8[10381 34 [8641 23 1/8[5871 FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG. 48TC-Al2 RTPF 93D 422 216 98 196 89 247 112 272 123.5 42 11067] 33 1/8[841] 24 1/4[6161 48TC-008 RTPF 835 379 164 74.5 170 77.2 255 115.8 246 111.7 44 7/8[11401 35 5/8[905] 19 3/8 [4921 48TC-009 RTPF 930 422 228 103.5 187 65 232 105.3 283 128.5 39 3/4[10101 32 7/8 18351 18 5/8 [473] 48TC-012 RTPF 940 427 231 104.9 189 85.8 234 106.2 286 129.8 39 3/4[1010] 33[838] 18 1/2 [4701 48TC-008 MCHX 805 365.5 160 72.6 153 69.5 240 109 260 118 43[10921 36 3/8 [924] 20 3/8[517.7] 1 481C-D12 MCHX 895 406.3 185 84 176 79.9 260 118 274 124.4 42 7/8[10891 35 1/2 [902] 22 7/8[5811 RTPF - ROUND TUBE, PLATE FIN (COPPER/ALUM) CORNER A MCHX - NOVATION !ALUM/ALUM CORNER B ' 170 n 11I1',1r //,. s CORNER D _ CORNER C TOP x • • Z a. ED i . 660 ; .,,. .,=. : • : 00 FRONT SHEET DATE SUPERCEDES 48TC 08-12 SINGLE ZONE ELECTRICAL 48TM500985 REV 2OF2 03-08-10 11-24-08 COOLING WITH GAS HEAT F Packaged Rooftop Builder 1.49n Page 3 of 7 Certified Drawing for 48TC-7.5T-E-3PH Project: Stock Units 2019 02/22/2019 Prepared By: 04:16PM Service Clearance p. C11247 LOCATION DIMENSION CONDITION 48-in(1219 mm) •Unit disconnect is mounted on panel 36-in(914 mm) •If dimension-B is 12-in(305 mm) A 18-in(457 mm) •No disconnect,convenience outlet option •Recommended service clearance(use electric screwdriver) 12-in(305 mm) •Minimum clearance(use manual ratchet screwdriver) 36-in(914 mm) •Unit has economizer 8 12-in(305 mm) •If dimension-A is 36-in(914 mm) Special •Check for sources of flue products within 10-ft of unit fresh air intake hood C 36-in(914 mm) •Side condensate drain is used 18-in(457 mm) •Minimum clearance 48-in(1219 mm) •No flue discharge accessory installed,surface is combustible material 42-in(1067 mm) •Surface behind servicer is grounded(e.g.,metal,masonry wall,another unit) D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass) Special •Check for adjacent units or building fresh air intakes within 10-ft of this unit s flue outlet NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any application planning overhead obstruction or vertical clearances. Packaged Rooftop Builder 1.49n Page 4 of 7 I Performance Summary For 48TC-7.5T-E-3PH Project: Stock Units 2019 02/22/2019 Prepared By: 04:16PM Part Number:48TCEDO8A2A5-0A0G0 ARI EER• _ - _ 11.00 IEER• _ _ 12.8 Base Unit Dimensions Unit Length. - - . 88.1 in Unit Width• 59.5 in Unit Height •----- ______-__41.3 in -- ---------- Operating Weight Base Unit Weight 835 lb Medium Heat 15 lb Medium Static Option (Belt Drive). _ 15 lb 2 Speed Fan Controller (VFD)• 20 lb Total Operating Weight 885 lb Unit Unit Voltage-Phase-Hertz. _ 208-3-60 Air Discharge. Vertical Fan Drive Type• Belt Actual Airflow. 3000 CFM Site Altitude. _ 39 ft Cooling Performance Condenser Entering Air DB• - 90.0 F Evaporator Entering Air DB• 78.0 F Evaporator Entering Air WB• 64.4 F Entering Air Enthalpy _ 29.49 BTU/lb Evaporator Leaving Air DB• 56.2 F Evaporator Leaving Air WB• - _ 54.6 F Evaporator Leaving Air Enthalpy. 22.93 BTU/lb Gross Cooling Capacity 88.40 MBH Gross Sensible Capacity. 70.45 MBH Compressor Power Input 5.97 kW Coil Bypass Factor. 0.104 Mixed Air Outdoor Air Airflow. ______________._._____-...__._._- 420 CFM Outdoor Air DB _____ _ . .90.0 F Outdoor Air WB• _ _ _-- 67.0 F Outdoor Air Htg.Temp • 22.0 F Return Air DB• - 76.0 F Return Air WB• - _ 64.0 F Return Air Htg.Temp • _ 70.0 F Heating Performance Heating Airflow. 3000 CFM Entering Air Temp. 63.3 F Leaving Air Temp. 109.0 F Gas Heating Input Capacity. 120.0/180.0 MBH Gas Heating Output Capacity' 98.0/ 148.0 MBH Temperature Rise. 45.7 F Thermal Efficiency(%)• 82.0 Supply Fan External Static Pressure' 0.60 in wg Fan RPM• _ 761 Fan Power. _ 1.64 BHP NOTE. _ _ Selected IFM RPM Range: 733 -949 Packaged Rooftop Builder 1.49n Page 5 of 7 Performance Summary For 48TC-7.5T-E-3PH Project: Stock Units 2019 02/22/2019 Prepared By: 04:16PM Electrical Data Voltage Range. 187 -253 Compressor#1 RLA. 13.6 Compressor#1 LRA• 83 Compressor#2 RLA. 13.6 Compressor#2 LRA• 83 Indoor Fan Motor Type- MED Indoor Fan Motor FLA• 8.4 Combustion Fan Motor FLA(ea). 0.48 Power Supply MCA. 43 Power Supply MOCP(Fuse or HACR). 50 Disconnect Size FLA. 45 Disconnect Size LRA• 227 Electrical Convenience Outlet. None Outdoor Fan [Qty/FLA(ea)]. 2/1.5 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics Sound Power Levels, db re 10E-12 Watts Discharge Inlet Outdoor 63 Hz 98.2 95.2 85.8 125 Hz 91.4 86.0 84.3 250 Hz 77.9 73.0 80.5 500 Hz 70.7 66.3 78.7 1000 Hz 67.1 63.3 76.4 2000 Hz 65.7 58.5 72.7 4000 Hz 67.1 57.8 68.3 8000 Hz 69.3 57.4 65.1 A-Weighted 79.4 74.3 82.0 Advanced Acoustics 4II i 411) i ); tit -aWe'l t a-44 lob 0 Advanced Accoustics Parameters 1. Unit height above ground 30.0 ft 2. Horizontal distance from unit to receiver. 50.0 ft 3. Receiver height above ground. 5.7 ft 4. Height of obstruction. 0.0 ft 5. Horizontal distance from obstruction to receiver 0.0 ft 6. Horizontal distance from unit to obstruction. 0.0 ft Detailed Acoustics Information Packaged Rooftop Builder 1.49n Page 6 of 7 Performance Summary For 48TC-7.5T-E-3PH Project:Stock Units 2019 02/22/2019 Prepared By: 04:16PM Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1 89.6 Lw B 59.6 68.2 71.9 75.5 76.4 73.9 69.3 64.0 81.4 LwA C 53.4 51.9 48.1 46.3 44.0 40.3 35.9 32.7 57.2 Lp D 27.2 35.8 39.5 43.1 44.0 41.5 36.9 31.6 49.0 LpA Legend A Sound Power Levels at Units Acoustic Center, Lw B A-Weighted Sound Power Levels at Units Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. Fan Curve 2'0 0 RP,A 1000 FPM 1100 RP 1 0 RPM 1.8 800 RPM 1.6 1.4 - 700 RPM c 1.2 500 !10 co0.8 WAIL\ ) 500 RPM 0.6 Nworiv 400 RPM 0.4 3.00 BH" 2•!2HP 1.50 BHP 0.2 1.00 8HP - _ 0.50 BH• • 5 BHP 00 - I I I I I I I I I I I I I . I . . . I I , I I l . I . l I I 0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 Airflow(CFM-thousands) RPM=761 BHP= 1.64 Maximum RPM= 1400 Maximum BHP=4.70 Note:Please contact application engineering for selections outside the shaded region. SC-System Curve RP-Rated Point Packaged Rooftop Builder 1.49n Page 7 of 7