Loading...
Report RECEIVED N E-C2021-oOg64 Nov 23 2021 I 106— PA-ci p c L vU y CITY OF TIGARD sUIL DING AFC TIGARD - MECHANI( At TIGARD, OR STRUCTURAL CALCULATIONS DESIGN CRITERIA: DC1 ROOF FRAMING CHECK: RF1-RF3 CONDENSER UNIT ANCHORAGE: CU1-CU4 RTU ANCHORAGE: RTU 1-RTU3 (12 PAGES TOTAL INCLUDING COVER SHEET) ,:,t�c,i.u1 it s � November 19, 2021 ic— 3 E PROJECT NUMBER: 210085.01 .GUN 0,Tt A Icay�t7, ��y3`f /8 D. GN,/ z LEXPERES• 3 4 ':' -,'''; - ENC,INEI RING Pt A N N I N G IN 1 ER1IIis ! ANDS( APE 15895 SW 72ND AVE SUITE 200 PORTLAND,OR 97224 PHONE:503.226.1285 FAX:503.226.1670 INFO@CIDAINC.COM DC 1 ��4WE CAL SEA OSHPD AFC 11675 SW Pacific Hwy, Tigard, OR 97223, USA Latitude, Longitude: 45.43771719999999, -122.7562963 Hawthorne Villa ':• Green Light District sel Apartments .. Electric Lettuce Dispensary 9 Big 5 Sport, Goods -Tiga �. US Foods CHEF'STOREcp Carriage House Tigard Bowl1,0 P A artments Westside Christian High School Go,.,,gt Map data O2021 Date 7/20/2021,6:15:49 AM Design Code Reference Document ASCE7-16 Risk Category 11 Site Class D-Default(See Section 11.4.3) Type Value Description SS 0.867 MCER ground motion.(for 0.2 second period) Si 0.395 MCER ground motion.(for 1.0s period) SNAG 1.04 Site-modified spectral acceleration value 5M1 null-See Section 11.4.8 Site-modified spectral acceleration value SDS 0.694 Numeric seismic design value at 0.2 second SA SD1 null-See Section 11.4.8 Numeric seismic design value at 1.0 second SA Type Value Description SDC null-See Section 11.4.8 Seismic design category Fa 1.2 Site amplification factor at 0.2 second Fv null-See Section 11.4.8 Site amplification factor at 1.0 second PGA 0.394 MCEG peak ground acceleration FPGA 1.206 Site amplification factor at PGA PGA 0.475 Site modified peak ground acceleration TL 16 Long-period transition period in seconds SsRT 0.867 Probabilistic risk-targeted ground motion.(0.2 second) SsUH 0.977 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration SsD 1.5 Factored deterministic acceleration value.(0.2 second) S1RT 0.395 Probabilistic risk-targeted ground motion.(1.0 second) 51 UH 0.456 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration. S1D 0.6 Factored deterministic acceleration value.(1.0 second) PGAd 0.5 Factored deterministic acceleration value.(Peak Ground Acceleration) 15895 SW 72ND AVENUE,SUITE 200 \1 PORTLAND,OREGON 97224 TEL:503.226.1285 FAX:503.226.1670 0 E-MAIL:info@cidainc.com.c PR-"JECT NAME: _ �!.__. �'"��^- �_._._..._.___.__.... Pao).No.,.I00 V c, 0 I SHEET R F I U TiTim: *JJ BY: g/•i/l DATE: 1146/F'1 711:r7---t---1-1-letar--- ---r- ; 1 -1--7- i 7. 7 i ,1 i . i iii .- ..t.i I ! / 1�+R'T, Id., �..._. . Z 1` S �i f j2 Ci_f i rr 99 !! , 4-±-, , .4 4i Ji i u 4 , ` i _ Fie/50r Ie '. 1. f I g ' i I , f � Ir..±Lam_l_ i ' 1 1 i ; ; ! ' I i i i i 1 I t , til i P F, .. ., .m, .,..,; . ... .M _ • 'cif it,'�' exit ¢(1 ; I i 1 r ` ! , { { 1 1 > I _ mot , ! t { + t f z 1 1 1 ! _�, . f f 3 I jlm" i . 1 i ' . �_ �MN z _ ZEST �I� n�W .. I t , t 1 ( f { 1 iii f f Z 1 1 I I 1 I l i , 1 _ 1 , , , , , , , , e,,,,, , , , _...,„..4...,.....,„ .„1,, , 4. i , , It g Z. 190* ' 1 .I.,_ 1 ii. , E ` 1 ; 1 1 � s 7 E 1 4 � I ...,K.-. , ,,,,,,,,,,,,,.--4 y...,,, 1-- ItHH ' ' `4 ` @ L 3 ) �" I j ; S ! I 1 c I r... .4.._ I - - _ ; F.... I I I I s ` 1 I 1 , { 1 IfiHH + 1 f 1 1 15895 SW 72ND AVENUE,SUITE 200 q PORTLAND,OREGON 97224 TEL:503,226.1285 FAX:503.226.1670 E-MAIL:info@cidainc.com U , Prtca EcT NAME: Paot.No. SHUT / 2.. TtrtE:... >._,„.>�..>.,� .. o :.w.. BY: DATE: ...,...,......,«.............. .1:—alm" :r 1. *t**1-,4,17mk, obick e—fi-rtt . , 1 t a 1 _ 1. 1 s I 1 - %� r -7vlsrs Pie �0�' :Y/ar e.91-6, , i 1 ..___ . ..�. ....i ... . . w, V Y 101 - "....�.� _ y r i 7 v1Qa ,K }(/.z1 -T. 31 t 1/4 i , , > �� rah t 1 i , _ I 4 = i h_4_ € j i / I ; + I 1 I " i j � I 1 I I �,. ...t. ,. 4. et, ; i rV 1 ,--- -1-. .}-- a..�.. .._ .., ..__ __.,.,. ._,fit ._ t .. i i I P y 1j a d , ` I. IfIL L r 1 _.mow x P t 3 I i 1 A r._ . , w _a i ; . { 1._ ._ R .. . la4 1k/ _ ?_ ,c,-) 14 i ,_... t _. 1 ; _.... _., f 1 ._ . ..._. 1 f {�. .....yam ..,,,,, it , A f �., -�k..,.,,> ,,..,.� » ....,o..,+M .,gyp......_.., 11,h...,.<. ,A„ .. ., .,-.�.._._.. "..'*:I f .-- ...,.--,---�.. .i } r 1 a «. ,,. iei 1 do4 ,o/24 a �._ +, .r w wwF 1 ,i _...... . ..4. tj1 I, �ow/77e ;i ash L .1 i -1-----t. i i I I , T.; =I 1 o/2go,�d o u� I .._, i 1 I ' ' ZL/ � 41r'it-1 i, z. mm . . w., z , . ri y lgym „ �._ — , t .Ij j " f +!4 I + T _ {, .. i... i yam , //i },.w,,... .. .,.y.»„, ,..,,,...-F .,.,...::.„,. .,i..:W.. w.+.,w+.«...}—....,.,.wJ.,w..,:W,.» .., ,�.,,...w.....,,«-w,.....r F «.., 1 . a ''Cr JS, m, 1 ` I 1 { Projectngr:#le: Engineneer: Project ID: Project Descr: General Beam File:AFC Tigard remodel.ec6 Software cop d!ht ENERCALC,INC.1983-2020,Build:12.20.8.24 Lm.#:KW-06006865 CIDA INC. DESCRIPTION: RTU on joist with new post General Beam Properties Elastic Modulus 29,000.0 ksi Span#1 Span Length = 10.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 I04 Span#2 Span Length = 14.0 ft Area= 10.0 inA2 Moment of Inertia = 100.0 iO4 D(0,32) I 1 Df0.034 3(0.05) D_(0.034 S(0.05) _-. ca_.__._-.._- �' 6-..--._--_-___ X _s _._ S._ _..--______._.__. b X A, Abs Span=10.0ft Span= 14.0ft Applied Loads Service loads entered.Load Factors will be applied for calculations. Load for Span Number 1 Uniform Load: D=0.0170, S=0.0250 ksf, Tributary Width=2.0 ft Load for Span Number 2 1 Uniform Load: D=0.0170, S=0.0250 ksf, Tributary Width=2.0 ft i lj Point Load: 0=0.320 k @ 8.0 ft,(P) Pi1 DESIGN SUMMARY Maximum Bending= 2.209 k-ft Maximum Shear= 0.8748 k Load Combination +D+S Load Combination +D+S Span#where maximum occurs Span#2 Span#where maximum occurs Span#1 Location of maximum on span 7.969 ft Location of maximum on span 10.000 ft Maximum Deflection Max Downward Transient Deflection 0.008 in 21128 Max Upward Transient Deflection 0.000 in 0 Max Downward Total Deflection 0.021 in 8086 Max Upward Total Deflection -0.002 in 54970 Maximum Forces&Stresses for Load Combinations Load Combination Max Stress Ratios Summary of Moment Values (k-ft) Shear Values (k) Segment Length Span# M V Mmax+ Mmax- Ma-Max Mnx Mnx/Omega Cb Rm Va Max Vnx VnxlOmega Overall MAXimum Envelope Dsgn.L= 10.00 ft 1 0.26 -2.10 2.10 0.87 Dsgn.L= 14.00 ft 2 2.21 -2.10 2.21 0.87 +D+S Dsgn.L= 10.00 ft 1 0.26 -2.10 2.10 0.87 Dsgn.L= 14.00 ft 2 2.21 -2.10 2.21 0.87 Overall Maximum Deflections Load Combination Span Max.="Defl Location in Span Load Combination Max."+"Deft Location in Span S Only 0.0001._ ....__._._ 0.538 +0+S -0.0022 7.538 +D+S 2 0.0208 7.754 0.0000 7.538 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Support 3 0veralii to bnum 0.210 1.504 0.621 Overall MINimum +D+S 0.210 1.504 0.621 D Only 0.058 0.737 0.341 S Only 0.153 0.767 0.280 CU 1 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 MECHANICAL UNIT ATTACHMENT-LATERAL FORCES: CU AT WOOD BOX WP:= 1351b Weight of unit Ww:= 1001b Weight of box Wt := Wp+ Ww Wt= 235 lb L:= 37.24in Length of unit Le:= L+ 12in Length of wood box wm:= 15.85in Width of unit we:= wm + 12in Width of wood box hm := 31.89•in Height of unit he:= 12•in Height of Platform hme:= hm + he hme=43.89 in Total height of unit on Platform SEISMIC PARTS AND PORTIONS (TIGARD, OR) Site class=D Mapped SS:= 0.867 Adjusted Maximum Sms:= 0.395 Design SDs := 0.694 h := l3ft IP:= 1.0 ap:= 2.5 RP:= 6 z:= h Air side HVAC component 0.4.ap•SDs•Ip z FPunit 1 + 2•— •W F 46.84lb 0.7 F =32.79 lb ) punit = punit — 0.4•a •SDS•I z Fp := 1 + 2.—z •Wt Fp= 81.54 lb 0.7.Fp = 57.08 lb P P RP h WIND LOAD: BASED ON 2018 IBC/2019 OSSC Vas:= 98 Exposure B --Kd:= 0.85 Ki .= 0.7 Kzt:— 1.0 GCr.— 1.9 GCr vent•• 1.5 qz:= 0.00256•Kh•Kzt•Kd•V3s2•psf F:= GCr qz F=27.79 psf Pwind unit F•L•hm ''wind_unit=229.23 lb P F•L•h P 315.48 lb wind�— me wind= WIND LOAD: BASED ON 2018 IBC/ASCE7-16-VERTICAL Fvei. = gz'GCr vent Fvert=21.94 psf P F L•w P 89.941b wind unit vent ••—— very m wind unit vert —— Pvert unit ASD 0.6Wp—0.6Pwind unit vert Pvert unit ASD =27.03 lb >0,NO NET UPLIFT Pvert total_ASD 0.6Wt —0.6Pwind_unit_vert veil total ASD = 87.03 lb >0,NO NET UPLIFT E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\CU on wood box.mcd CU 2 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 OVERTURNING-UNIT TO UNISTRUT LC#7 0.6D+0.6W LC#8 0.6D+0.7E WIND-Overturning at unit to Unistrut SEISMIC-Overturning at unit to Unistrut / hm\ hm Mot wind unit Pwindunit' 2 / Mot_seismic_unit = t'Fpuni 2 Mot wind unit =304.6 lb ft Mot seismic unit =62.25 lb ft (0.6Mot_wind_unit) Pvert_unit_ASD (0•7'Mot_seismic_unit) (0.6—0.7.0.2•SDS)'wp Fup_wind_unit w — 2 Fup_seismic—unit w — 2 m m Fup_wind_unit = 124.84 lb Fup_seismic_unit =—0.95 lb 0.6 Pwind unit = 137.54 lb 0.7 Fpunit =32.791b WIND GOVERNS UNIT TO UNISTRUT ATTACHMENT Design attachment for 138 lb sliding and 125 lb tension at unit to Unistrut connection 0.6•Pwind unit = 137.54 lb Fup_wind_unit = 124.84 lb Try 3/8" DIAMETER BOLTS TO UNISTRUT: Fnt:= 45ksi Fnv:= 27ksi S2 := 2.0 Allowable loads-Bolts 2 it'bolt Dbolt := 0.375in Bolt diameter Abolt:= 4 Abolt =0.11 in2 Fnv'Abolt Vallow—bolt_allow 0 Vallow_bolt_al low= 1491.03 lb Fnt'Abolt Tallow_bolt_allow Tallow bolt_allow=2485.05 lb (0.6•P wind unit) — Vapplied_bolt_ASD •= 4 Vapplied_bolt ASD =34.38 lb t = (Fup_wind—unit) T =62.42lb applied_bolt_ASD 2 applied_bolt_ASD Vapplied_bolt ASD Tapplied_bolt ASD Ubolt + Ubolt=0.05 <1.0,OK Vallow bolt allow Tallow bolt allow USE(4)3/8"DIAMETER BOLTS AT UNIT TO UNISTRUT CONNECTION E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\CU on wood box.mcd CU 3 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 ATTACHMENT-UNISTRUT TO WOOD BOX: Design attachment for 138 lb sliding and 125 lb tension at unit to Unistrut connection 0.6•Pwind_unit= 137.54 lb Fup_wind_unit = 124.84 lb Try#12x1-1/2"wood screws each end of Untrut.(2) brackets to resist uplft, (4)total nscrews_per_bracket = 1 0.6Pwind unit Fup_wind unit Vx:= Vx=34.38 lb Vy:_ V = 62.42 lb 4•nscrews_per bracket 2•nscrews per_bracket Vscrew J Vx2+ Vy2 Vscrew = 71.27 lb IV a := atan y a =61.15 deg Angle between grain and direction of loading \Vxi Screw Dimensions and Capacities: dscrew 0.216in Screw Diameter Lscrew := 1.5in Screw Length Lp := Lscrew —0.25in Lp = 1.25 in Screw length-Angle Thickness Lp C := C =0.58 p 10•dscrew P V'11:= 1.6.1161b•Cp V'11= 107.41 lb V'T:= 1.6.1161b•Cp V'T= 107.41 lb V'II\PT V'a, := V'a= 107.41 lb > Vscrew = 71.271b V'11•sin(a)2+ V'T•cos(a)2 Use(2)#12x1 1/2"wood screws at each bracket--(4)Brackets Minimum E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\CU on wood box.mcd CU 4 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 OVERTURNING-CURB TO ROOF LC#7 0.6D+0.6W LC#8 0.6D+0.7E WIND-Overturning at Box to Roof SEISMIC-Overturninq at Box to Roof ( hmc\ hmc Mot wind total 2 / Mot seismic_total FP' 2 Mot wind total =576.9 lb ft Mot seismic total = 149.13 lb ft (0.6Mot_wind_total) overt_total_ASD (0•7'Mot_seismic_total) (0.6—0.7.0.2•SDS)'wt Fup_wind_total = — Fup_seismic_total W — c 2 w c 2 Fup_wind_total = 105.64 lb Fup_seismic_total =—14.11 lb 0.6•Pwind= 189.29 lb 0.7•Fp = 57.08 lb WIND GOVERNS BOX TO ROOF ATTACHMENT Design attachment for 190 lb sliding and 106 lb uplift at Box to roof connection 0.6•Pwind= 189.29 lb Fup_wind_total = 105.64 lb Try Simpson HGA10 clips each side Vallow HGAI0 5001b Tallow HGAl0 6051b (O.6•Pwind) <1.0,OK Ushear Ushear= .19 2•V 0 allow HGA 10 (Fup_wind_total) <1.0,OK Utension Utension=0.17 Tallow HGA 10 USE(1)SIMPSON HGA10 CLIP EACH SIDE OF BOX TO ROOF--MIN.(4)TOTAL E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\CU on wood box.mcd RTU1 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU ROOFTOP UNIT ON CURB Wp:= 3201b Weight of unit We:= 951b Weight of curb Wt:= Wp+ We Wt=4151b L:= 48.1875in Length of unit Lc:= 46.1 in Length of Curb wm:= 32.625in Width of unit we:= 30.6in Width of curb hm:= 45.75•in Height of unit he:= 14•in Height of curb hme:= hm+ he hmc= 59.75 in Total height of unit on curb SEISMIC PARTS AND PORTIONS (TIGARD, OR) Site class=D Mapped Ss:= 0.867 Adjusted Maximum Sms:= 0.395 Design SDS := 0.694 h := 13ft Ip:= 1.0 ap:= 2.5 RP:= 6 z := h Air side HVAC component 0.4.a •SDS•I FPunit 1 F 111.04 lb 0.7 F 77.73lb P P Rp h P Punit = Punit= 0.4•ap•Sm.Ip Zl FPcurb R 1 + 2 h/•(Wp+ We) FPcurb= 144 lb 0.7•FPcurb= 100.81b WIND LOAD: BASED ON 2018 IBC/2019 OSSC Vas:= 98 Exposure B Kd:= 0.85 KI := 0.7 Kn:= 1.0 GCr:= 1.9 GCr vert:= 1.5 qZ:= 0.00256•Kh•K.t•Kd•V3S2•psf F:= GCr qZ F= 27.79 psf ''wind unit F•L•hm Pwind unit=425.53 lb Pwind_curb F L(hm+ hc) Pwind curb =555.74 lb WIND LOAD: BASED ON 2018 IBC/ASCE7-16-VERTICAL Fvert gz'GCr vent Fvert =21.94psf wind unit vert Fvert'L'win Pwind unit vert =239.56 lb P0.6W —0.6P overt 48.26 lb <0,Net Uplift vert_unit := p wind unit_vert unit = Pvert curb 0.6(Wp+ We) —0.6Pwind_unit_vert Pvert curb = 105.26 lb <0,Net Uplift E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structu ra I\Mech\RTU.mcd RTU 2 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 OVERTURNING-UNIT TO CURB LC#7 0.6D+0.6W LC#8 0.6D+0.7E WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb (1im\ ht" Mot seismic unit := FPunit• Mot wind_unit = Pwind_unit'2 - - 2 / M - 811.16 lb ft Mot seismic unit =211.67 lb ft of wind unit— - - Fup_wind_unit - (0.6Mot_wind_unit) - 1 vert_unit F - (0.7•Mot_seismic unit) (0.6-0.7.0.2•SDs)'wp - up_seismic_unit - W - c 2 we 2 Fup_wind_unit = 166.73 lb Fup_seismic_unit =-22.35 lb 0.6•Pwind unit =255.32 lb 0.7•Fpunit = 77.73 lb WIND GOVERNS UNIT TO CURB CONNECTION ATTACHMENT Design attachment for 256 lb sliding and 157 lb tension at unit to curb connection--18GA curb 0.6*Pwind_unit= 255.32 lb Fup_wind_unit = 166.73 lb Try 16GAx6"CLIPS WITH(4)#10 SCREWS TO UNITAND(4)#10 SCREWS TO CURB VCLIP:= 471 lb Per clip 0.6•Pwind_unit Ushear 2'VCLIP Ushear=0.271 Fup_wind unit Uuplift:= Uuplift= 0.35 1•VCLIP Use(1)16GAx6"clip per side with(4)#10 SMS to unit,and(4)#10 SMS to curb--(4)clips total E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\RTU.mcd RTU 3 CIDA AFC TIGARD RNH TEL: (503)226-1285 11/16/2021 FAX: (503)226 1670 OVERTURNING-CURB TO ROOF LC#7 0.6D+0.6W LC#8 0.6D+0.7E WIND-Overturning at curb to roof SEISMIC-Overturning at curb to roof hmc (hmc\ Mot wind curb := Pwind_curb'— Mot seismic c := FPcurb' 2 \ 2 Mot wind curb = 1383.56 lb ft Mot seismic c =358.51 lb ft (0.6Mot_wind_curb� 'avert_curb (0.7.Mot seismic_c) (0.6—0.7.0.2.SDS)'(Wt) Fup_wind_curb := — Fup—seismic_c := w — c 2 w c 2 Fup_wind_curb =272.91 lb Fup_seismic_c =—5.92 lb 0.6 Pwindcurb = 333.44 lb 0•7•FPcurb = 100.8lb WIND GOVERNS CURB TO ROOF ATTACHMENT Design attachment for 333 lb sliding and 273 lb uplift at curb to roof connection 0.6•Pwindcurb = 333.44 lb Fup_wind_curb =272.91 lb Try#10x3"WOOD SCREWS EACH SIDE--Long side to take tension, shortscies to take shear 'screw := 3 in length of screw LP := 'screw — in LP =2.38 in screw length-Sheathing-tapered tip 2 dthread:= 'screw 3 thread length dscrew := 0.19in Screw diameter LP Wthread:= 135•lb withdrawal capacity per inch Co:= C = 1.25 in • 10•dscrew Cp:= if(Cp> 1.0,1.0,Cp) C = 1 Vallow:= 1.6.901b•Cp Val low= 144 lb Tallow:= 1.6•dthread' 'thread Tallow=432 lb 0•6•Pwind_curb USHEAR:= USHEAR=O.579 4 Vallow Fup_windcurb UUPLIFT:= UUPLIFT=0.32 2•Tallow E:\adcadd\21\0085.01 AFC-Tigard Remodel\Structural\Mech\RTU.mcd