Scope of work is for the design of the connection of the sign to the existing canopy. RECEIVED See following pages for structural notes
Input Data:ASCE 7-16
• Maximum Height(h)= 15.00 ft(of sign)
DEC 2 2021
Wind Speed,V= 96 mph
Exposure Category= B �c10 PRO, 6, CITY OF TIGARD
Topo.Factor,Kzt= 1.00 �
Direct.Factor,Kd= 0.85 �G t N E NG DIVISION
Effective Area,Ae= 31.59 ft2 (Area Tributary to C&C) 7252 PE
Wall External Pressure Coefficients,GCp:
Corner Zone= No
GCp Zane 4 Neg._ -0.91 Fig.30.4-1
GCp Zone 5 Neg._ -1.10 Fig.30.4-1 N o
qz=0.00256`Kz`Kzt*Kd`V^2*0.6(allowable) �G Y 9 . QQ
Wall Pressures for Design: 0
Kz qz GCp F(psf) h Fs✓OSEPH l�P��
0.7 8.42 -0.91 = 9.6 0-15 ft
EXPIRES:12-31-2022
Overall Letter Width= 14.04 ft
Overall Height= 2.25 ft
Area= 31.59 ft2
Standoff= 0.00 in
Raceway Height= 6.50 in
Raceway Below Letters
Sian Area and Loadin! : Sign Above Canopy
Width,ft Height to Height to %solid Area,ft2 Wind Force,lb
bottom,ft top,ft load,psf
14.04 13.29 15.00 30% 7.20 9.6 69 letters
14.04 13.29 13.29 0% 0.00 9.6 0 standoff
14.04 12.75 13.29 100% 7.58 9.6 73 raceway
E= 142
V,= 69 lb
V2= 142 lb E
arm,= 10.26 in =(15'-13.29')/2*12 b MI
arm2= 3.24 in =(13.29'-12.75')/2"12 _ !2
MI= 708 in-lb =69*10.26"M2= 1392 in-lb =708in-Ib+(69*6.48+73*3.24") T_
2
Est.Dead Load= 61 lb (assumed at 4 psf)
Fastener Check: (raceway to supporting structure) RACEWAY
Fastener Type:Bolts
Kota'= 1392 in-lb _
V,otai= 142 lb
T,orai= 0 lb (sign is attached above structure) .-
Fastener Quantities: E .
Columns= 4 (min) (42"o.c.max)
Rows= 1
total fasterners= 4
couple distance= 0.50 in
T= 696 lb per fastener =(1392in-lb/0.5"+36)/(4)
V= 36 lb per fastener =1421b/(4) (E)Ct2x2o.?
Fastener into:Steel
Fastener Type:Bolts
Mat.Gauge:18 ga
Mat.Thickness:I 0.045 lin
Fastener Size: 0.25
Tc= 1378 lb
Vc= asa lb (4)1/4"DIA THRU BOLTS AT
0.58 <1.00 OK APPROX LOCATIONS
Use 0.25 Bolts at 42"o.c.max
Ic-0vr
Ir..
Ir
T H E ID)<''
® \
,rrp I � �
Project Name The Overland Canopy Sign Project# 211645
04 MILLER
CONSULTING Location 11930 SW 72nd Avenue, Tigard, OR
11111 ENGINEERS
Client Security Signs
9600 SW Oak St#400 1 503.246.1250 GSD ( 11/29/2021 1 of 3
Portland,OR 97223 miller-se.com By Ck'd Date Page
xanfl • • , -' nwL,a txAa`aaaxw •u...�, ••_ •"i •..•i6 w a w.. a wx.w.auaa xatsr + + t. A 6st6xb A F r I '• NTat'Rtb ..• + wra+nx...
GENERAL
THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND CORRELATION OF ALL ITEMS AND WORK NECESSARY
FOR COMPLETION OF THE PROJECT AS INDICATED BY THE CONTRACT DOCUMENTS. SHOULD ANY QUESTION ARISE
REGARDING THE CONTRACT DOCUMENTS OR SITE CONDITIONS, THE CONTRACTOR SHALL REQUEST
INTERPRETATION AND CLARIFICATION FROM THE ENGINEER BEFORE BEGINNING THE PROJECT. THE ABSENCE OF
SUCH REQUEST SHALL SIGNIFY THAT THE CONTRACTOR HAS REVIEWED AND FAMILIARIZED HIMSELF WITH ALL
ASPECTS OF THE PROJECT AND HAS COMPLETE COMPREHENSION THEREOF. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CONFORMANCE TO ALL SAFETY REGULATIONS DURING CONSTRUCTION.
THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS OTHERWISE
SPECIFICALLY NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OR CONSTRUCTION LOADS. ONLY
THE CONTRACTOR SHALL PROVIDE ALL METHODS, DIRECTION AND RELATED EQUIPMENT NECESSARY TO PROTECT
THE STRUCTURE, WORKMEN AND OTHER PERSONS AND PROPERTY DURING CONSTRUCTION. THE CONTRACTOR
SHALL, AT HIS OWN EXPENSE, ENGAGE PROPERLY QUALIFIED PERSONS TO DETERMINE WHERE AND HOW
TEMPORARY PRECAUTIONARY MEASURES SHALL BE USED AND INSPECT SAME IN THE FIELD.ANY MATERIAL NOT AS
SPECIFIED OR IMPROPER MATERIAL INSTALLATION OR WORKMANSHIP SHALL BE REMOVED AND REPLACED WITH
SPECIFIED MATERIAL IN A WORKMANLIKE MANNER AT THE CONTRACTOR'S EXPENSE.
THESE PLANS, SPECIFICATIONS, ENGINEERING AND DESIGN WORK ARE INTENDED SOLELY FOR THE PROJECT
SPECIFIED HEREIN. MILLER CONSULTING ENGINEERS DISCLAIMS ALL LIABILITY IF THESE PLANS AND
SPECIFICATIONS OR THE DESIGN, ADVICE AND INSTRUCTIONS ATTENDANT THERETO ARE USED ON ANY PROJECT
OR AT ANY LOCATION OTHER THAN THE PROJECT AND LOCATION SPECIFIED HEREIN. OBSERVATION VISITS TO THE
JOB SITE AND SPECIAL INSPECTIONS ARE NOT PART OF THE STRUCTURAL ENGINEER'S RESPONSIBILITY UNLESS
THE CONTRACT DOCUMENTS SPECIFY OTHERWISE.
NON STRUCTURAL PORTIONS OF PROJECT, INCLUDING BUT NOT LIMITED TO PLUMBING, FIRE PROTECTION, LAND
USE, SITE PLANNING, EROSION CONTROL, ELECTRICAL, MECHANICAL, FLASHING AND WATER-PROOFING ARE
BEYOND THE SCOPE OF THESE DRAWINGS AND ARE PROVIDED BY OTHERS. EXISTING STRUCTURAL ELEMENTS ARE
DESIGNED BY OTHERS. ANALYSIS FOR MOVEMENT DUE TO VORTEX SHEDDING OF WIND FORCES IS NOT INCLUDED
IN THE SCOPE OF WORK. IF MOVEMENT CAUSED BY VORTEX SHEDDING IS A CONCERN, WIND TUNNEL TESTING OR
OTHER ANALYTICAL MODELS SHALL BE UTILIZED TO EVALUATE THE STRUCTURE.
IN ACCORDANCE WITH SECTION 1704.2 EXECPTION 1, NO SPECIAL INSPECTIONS ARE REQUIRED FOR WELDS AS THE
LOADING IS A MINOR FRACTION OF THE CAPACITY OF THESE ELEMENTS.
CONTRACTOR TO VERIFY ALL CONDITIONS PRIOR TO FABRICATION OR INSTALLATION. ENGINEER OF RECORD FOR
THE PROJECT IS TO BE NOTIFIED IF CONDITIONS DIFFER FROM WHAT IS SHOWN ON THE DRAWINGS.
BUILDING CODE
ALL PHASES OF THE WORK SHALL CONFORM TO THE 2019 OREGON STRUCTURAL SPECIALTY CODE, BASED ON THE
2018 INTERNATIONAL BUILDING CODE, INCLUDING ALL REFERENCE STANDARDS, UNLESS NOTED OTHERWISE.
��GD t PROFFss4o
tci 7252 PE
'P di
e r '0N o
,10 O
��Fs/�Y 0 s .P�s)k.
OSEPH M
EXPIRES: 12-31-2022
Project Name The Overland Canopy Sign Project# 211645
Art MILLER
laCONSULTING Location 11930 SW 72nd Avenue, Tigard, OR
ENGINEERS
............................................................... Client Security Signs
9600 SW Oak St#400 I 503.246.1250 GSD 11/29/2021 2 of 3
Portland,OR 97223 i miller-se.com By _ Ck'd___ Date Page
DESIGN LOADS
THE FOLLOWING ARE THE DESIGN REQUIREMENTS:
STRUCTURAL DESIGN CRITERIA
RISK CATEGORY II
WIND DESIGN DATA
BASIC WIND SPEED(3 SEC GUST) 96 MPH
EXPOSURE B
STRUCTURAL STEEL
ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE ASTM A992 FOR W-SECTIONS AND ASTM A36 FOR ALL
OTHER SECTIONS, PLATES AND BARS. ALL RECTANGULAR HSS SECTIONS SHALL BE ASTM A500, GRADE B, FY=46000
PSI AND ALL ROUND HSS SECTIONS SHALL BE ASTM A500, GRADE B, FY = 42000 PSI. ALL STRUCTURAL STEEL PIPE
SHALL BE ASTM A53, GRADE B, TYPE E OR S, FY= 35000 PSI. ALL STEEL IN CONTACT WITH ALUMINUM TO BE HOT
DIPPED GALVANIZED OR HAVE A PROTECTIVE BARRIER TO PREVENT CORROSION.
UNLESS NOTED OTHERWISE, ALL BOLTS TO BE ASTM A307 AND ALL ANCHOR RODS TO BE ASTM F1554 GRADE 36,
WITH MATCHING NUTS. ALL FASTENERS IN CONTACT WITH ALUMINUM TO BE BE HOT DIPPED GALVANIZED WITH
MATCHING NUTS OR HAVE A PROTECTIVE BARRIER TO PREVENT CORROSION. NUTS SHALL BE TIGHTENED TO A
SNUG TIGHT CONDITION PER RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC) SPECIFICATION FOR
STRUCTURAL JOINTS, SECTION 8.1.
ALL STRUCTURAL STEEL SHALL HAVE ONE COAT OF PRIMER, EXCEPT SURFACES TO BE EMBEDDED IN CONCRETE
OR MASONRY. EMBEDDED SURFACES SHALL BE FREE OF CONTAMINANTS. ALL ZINC (GALV.) COATINGS ON IRON
AND STEEL PRODUCTS SHALL CONFORM TO ASTM A123. REPAIRS OF GALVANIZED COATINGS ARE TO CONFORM TO
ASTM A780. ALL EXPOSED STRUCTURAL STEEL TO HAVE ONE FINISH COAT OF RUST INHIBITING PAINT, COLOR BY
OWNER.
ALL WELDING SHALL CONFORM TO AMERICAN WELDING SOCIETY (AWS) D1.1 USING E70XX ELECTRODES. WELD
LENGTHS SHOWN ARE EFFECTIVE AS SPECIFIED PER THE SPECIFICATIONS OF THE AMERICAN INSTITUTE OF STEEL
CONSTRUCTION (AISC). WELDING SHALL BE PERFORMED BY AWS CERTIFIED WELDERS FOR WELD TYPES
SPECIFIED. WHERE WELD LENGTHS ARE NOT SHOWN, THE WELD SHALL BE FULL LENGTH OF MEMBERS BEING
JOINED. ALL BUTT WELDS SHALL BE FULL PENETRATION WELDS UNLESS NOTED OTHERWISE ON STRUCTURAL
DRAWINGS.ALL WELDS SHALL RECEIVE THE SAME FINISH COAT AS THE MEMBER BEING WELDED.
ccse PROFF
t
7252 PE c—
N o
6,2G V pt; • •Q
Fs✓OSEN 1\'�
EXPIRES:12-31-2022
' Project Name The Overland Canopy Sign Project# 211645
MILLER
CONSULTING Location 11930 SW 72nd Avenue, Tigard, OR
ENGINEERS
Client Security Signs
9600 SW Oak St#400 l 503 246.1250 GSD /�`( 11/29/2021 3 of 3