Report Power Vented, Low Static, Axial Fan, Unit
REZNOWOFFICE ��� Heater for
ECEIVED
OCT 2 1 2021 Commercial/Ind
Use ustrial/Residential Utility
CITY OF TIGARD '� '�Z/ diDg6-4.
Model UDAP BUILDING DIVISION //2`/'/ 7�/}
acw ar,o . ES 16 s'
� CERf_
TIFIEd
a� a _ Wad?, TIF
ANSI Z83.8b CSA 2.6b
1
I The new V3 series unit heaters are designed to
provide all the features you expect in a Reznor®
Yt heater plus improved efficiency, easier installation and
a new look - both inside and out. Look for the unique
white unit with no visible front and bottom hardware,
deep red louvers, black side handle, and angled
corner to know you have a genuine Reznor unit by
Description : Thomas & Betts.
Reznor® V3 series model UDAP gas-fired
unit heaters are available in 14 sizes ranging Features:
from 30,000 to 400,000 BTUH gas input. Sizes • Sizes 30-125 certified for residential heating
30-125 are approved for residential application. application
All sizes are approved for commercial/industrial • Sizes 30-400 certified for commercial/industrial
installations. Model UDAP heaters are designed heating
application
for 82-83% thermal efficiency and are approved • 82-83% thermal efficient TOP in its class!
for installation in the United States and Canada • 50-60°F rise range
by the Canadian Standards Association(CSA). • NEW T-CORE2 ® design titanium stabilized steel
Reznor® V3 Series unit heaters have a heat exchanger (patent pending)
refreshing new appearance with a glossy white • NEW T-CORE2 ® design single burner combustion
cabinet finish, unique Reznor® mitered system including a one-piece burner assembly
corner and less visible hardware. Each size (patent pending)
cabinet is easily suspended from either 2 or 4 •Open fan motor with internal overload protection
suspension points, or an optional hanger kit for •Transformer for 24-volt controls
Iall sizes allows for ceiling mounting. The low • Integrated circuit board with diagnostic indicator
voltage terminal strip on the outside of the lights
cabinet makes connecting control wiring easy • Fan relay (included on the circuit board)
with no panels to remove. The addition of a "G" • Multi-try direct spark ignition with 100% lockout
terminal to the strip, along with the new design •Gas valve field adjustable for operation to 9,000 ft
of the circuit board, allows for fan only operation elevation
(without adding relays). All units have a factory •Vibration/noise isolated fan and venter motors
installed gas line nipple to the exterior of the designed for low noise operation
cabinet for easy gas service connection. • 2-pt and 4-pt suspension " standard on all sizes
• External terminal strip for 24-volt wiring
The preeminent new internal feature is the • External gas connection
T-CORE2 ® heat exchanger and single • Full fan guard — engineered for safety
burner combustion system. Other standard • Improved cabinet design with less visible hardware
features include a single stage gas valve, and a NEW Reznor appearance
multi-try direct spark ignition with 100% lockout, • Look for the white unit with the unique mitered
pressure switch to verify vent flow, resiliently corner
isolated venter motor, venter wheel with
improved housing, resiliently isolated axial fan
and motor assembly and a high temperature
limit control. Sizes 30-125 also include a flame Reviewed and approved by Owner:
rollout safety switch. Operation is controlled Greenburg Team One, LLC
through an integrated circuit board. The circuit By: Wyse Real Estate Advisors,
board monitors heater operation and has LED Managing Agent for Owner
diagnostic indicator lights to identify Jocelyn Burmester,
abnormalities in control functions. Associate VP, Wyse Real Estate Advisors
10/20/2021
Included Options
AA1: Unit equipped for natural gas
Natural gas is a naturally occurring gas mixture consisting primarily of methane and includes varying
volumes of alkanes, carbon dioxide, nitrogen, and hydrogen sulfide.
1 Therm = 100,000 BTU = 29.3 kWh
AG1: Gas controls designed for recirculating air heating application. Furnace has a 24 volt, single stage
combination gas valve which includes the electronic on-off valve controlled by a single-stage 24 volt
room thermostat, a pressure regulator, a safety pilot valve, and the manual shutoff valve.
MODEL(S) U DAP D .
-UDAP 150
-UDAP 175
-UDAP 200
18' - 2511 -
•
816
1 1 1 8
I i
2216 I 3,-16 FEMALE THREAD I
-ALL SUSPENSION POINTS
I 1
II II
't t
OM BUSTION
AIR INLET
38 6 - 42 -
23 _g 8 DIA 5'CONNECTION
. .L
/////fC//�-,w,X\\\\l 1
Wire
rt THERMOSTATS
16 I ' ' ACCESS PANEL u CONNECTION 1 I /mm//,,��•\,\\\\\\\1
t��.`._..........
I /a ,•1.1 1.1 1!1 PP• •
1\\\\\`.\\\//I.'/////4/MMI V
�1 \\\\\`.�_\`J/i%/i//
7
_ r I
6 ___.
r
LINE VOLTAGE INLET - XTERNAL GAS
NOTES:
(CONNECTS AT CONNECTION
CIRCUIT BOARD) 4 DIA 2"
•SIZE SHOWN IS FOR GAS CONNECTION TO A SINGLE STAGE GAS VALVE,NOT SUPPLY LINE SIZE.
•25-11/16"AND 1-3/8"-HANGER DIMENSIONS FOR BOTH 2-PT AND 4-PT SUSPENSION.
'8.3/16"AND 22-3/16"-HANGER DIMENSIONS FOR 4-PT SUSPENSION.
'16-3/8"-HANGER DIMENSION FOR 2-PT SUSPENSION. ALL DIMENSIONS ARE IN INCHES
Page Number of
•
RENOR Throw/Floor Coverage
nnn
"Height measured from the floor to the
bottom of the unit heater.
H *Point where heated air from the heater
reaches the floor.
Point where heated air tends to rise
from the floor.
z Point where the air velocity drops be-
low 50 feet per minute(254 mm/sec).
X
4
Applies to both Model UDAS and Model UDAP
Dimension in feet
Size 30 45 60 75 100 125 150
Mounting Lvr. Lvr. Lvr. Lvr. Lvr. Lvr. Lvr.
Height X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle
5 6 14 30 -21' 7 16 40 -20' 8 18 45 -16' 9 20 57 -14' 9 20 59 -18' 10 22 65 -14 - -- --
8 7 13 26 -39' 9 16 37 -34" 10 18 42 -29' 12 22 54 -25" 11 21 56 -28' 12 23 63 -24' 13 24 73 -26`
10 6 11 22 -52' 9 15 33 -43' 10 17 39 -37' 12 22 52 -32' 12 20 52 -36' 13 24 60 -30' 14 24 69 -32
12 -- -- -- -- 8 12 27 -55` 10 16 34 -46' 12 21 48 -39" 11 19 47 -44' 14 23 57 -36" 14 24 64 -39"
14 -- -- -- -- -- -- -- -- 9 14 29 -56' 12 19 44 -46' 11 17 42 -51' 14 22 53 -43' 14 22 59 -45'
16 11 17 38 -54' 10 14 34 -58' 13 20 47 -50' 13 20 53 -51'
18 a 11 17 40 _ -57' 11 17 44 -58'
Size 175 200 225 250 300 350 400
Mounting Lvr. Lvr. Lvr. Lvr. Lvr. Lvr. Lvr.
Height X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle
8 15 28 90 -22' 16 30 93 -20" 14 27 86 -24' 16 29 93 -21' 15 28 94 -24' 17 31 105 -20' 18 34 113 -17'
10 17 29 87 -27' 17 31 91 -25' 15 27 82 -30' 17 30 90 -26" 16 28 89 -29' 18 32 103 -25' 20 35 110 -21'
12 18 29 84 -32' 18 31 88 -30' 16 27 78 -35' 18 30 87 -31' 17 28 85 -34' 19 32 98 -30' 21 36 108 -25'
14 18 28 79 -37' 19 30 84 -34" 16 26 73 -41' 18 30 83 -36' 17 27 80 -40' 20 32 95 -34' 23 35 105 -29'
16 18 27 74 -42' 19 29 79 -39' 16 24 67 -47' 19 28 78 -41' 17 25 74 -45' 21 31 90 -38" 23 35 101 -33'
18 17 26 68 -48' 19 28 74 -44' 14 22 60 -53' 18 27 72 -46' 16 24 66 -51' 20 30 85 -43" 23 35 97 -37'
Dimension in metric
•
Size 30 45 60 75 100 125 150
Mounting Lvr. Lvr. Lvr. Lvr. Lvr. Lvr. Lvr.
Height X V Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle
1.5 1.8 4.3 9.1 -21' 2.1 4.9 12.2 -20' 2.4 5.5 13.7 -16' 2.7 6.1 17.4 -14' 2.7 6.1 18.0 -18' 3.0 6.7 19.8 -14' -- -- --
2.4 2.1 4.0 7.9 -39' 2.7 4.9 11.3 -34' 3.0 5.5 12.8 -29` 3.7 6.7 16.5 -25' 3.4 6.4 17.1 -28' 3.7 7.0 19.2 -24" 4.0 7.3 22.3 -26'
3.0 1.8 3.4 6.7 -52' 2.7 4.6 10.1 -43' 3.0 5.2 11.9 -37" 3.7 6.7 15.8 -32` 3.7 6.1 15.8 -36' 4.0 7.3 18.3 -30" 4.3 7.3 21.0 -32'
3.7 -- -- -- -- 2.4 3.7 8.2 -55' 3.0 4.9 10.4 -46' 3.7 6.4 14.6 -39' 3.4 5.8 14.3 -44" 4.3 7.0 17.4 -36" 4.3 7.3 19.5 -39-
.
4.3 -- -- -- -- -- -- -- -- 2.7 4.3 8.8 -56' 3.7 5.8 13.4 -46' 3.4 5.2 12.8 -51' 4.3 6.7 16.2 -43' 4.3 6.7 18.0 -45'
4.9 -- -- -- -- -- -- -- - -- -- -- -- 3.4 5.2 11.6 -54' 3.0 4.3 10.4 -58" 4.0 6.1 14.3 -50" 4.0 6.1 16.2 -51'
5.5 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 3.4 5.2 12.2 -57' 3.4 5.2 13.4 -58'
Size 175 200 225 250 300 350 400
Mounting Lvr. Lvr. Lvr. Lvr. Lvr. Lvr. Lvr.
Height X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle X Y Z Angle
2.4 4.6 8.5 27 4 -22' 4.9 9.1 28.3 -20' 4.3 8.2 26.2 -24' 4.9 8.8 28.3 -21' 4.6 8.5 28.7 -24' 5.2 9.4 32.0 -20' 5.5 10.4 34.4 -17"
3.0 5.2 8.8 26.5 -27" 5.2 9.4 27.7 -25` 4.6 8.2 25.0 -30' 5.2 9.1 27.4 -26' 4.9 8.5 27.1 -29" 5.5 9.8 31.4 -25' 6.1 10.7 33.5 -21"
3.7 5.5 8.8 25.6 -32' 5.5 9.4 26.8 -30' 4.9 8.2 23.8 -35' 5.5 9.1 26.5 -31' 5.2 8.5 25.9 -34" 5.8 9.8 29.9 -30' 6.4 11.0 32.9 -25'
4.3 5.5 8.5 24.1 -37' 5.8 9.1 25.6 -34' 4.9 7.9 22.3 -41' 5.5 9.1 25.3 -36' 5.2 8.2 24.4 -40' 6.1 9.8 29.0 -34' 7.0 10.7 32.0 -29'
4.9 5.5 8.2 22.6 -42" 5.8 8.8 24.1 -39' 4.9 7.3 20.4 -47' 5.8 8.5 23.8 -41' 5.2 7.6 22.6 -45' 6.4 9.4 27.4 -38" 7.0 10.7 30.8 -33'
5.5 5.2 7.9 20.7 -48" 5.8 8.5 22.6 -44" 4.3 6.7 18.3 -53' 5.5 8.2 21.9 -46' 4.9 7.3 20.1 -51' 6.1 9.1 25.9 -43' 7.0 10.7 29.6 -37'
Louver angle listed in the table is relative to the top of the unit heater.
Form RZ-C-UH(Version H)Page 25
Page Number of
REzNoR„ Installation Procedures
WARNING: Gas-fired appliances are not designed for use in hazardous atmospheres containing
flammable vapors or combustible dust, or atmospheres containing chlorinated or halogenated
hydrocarbons.
Installations in public garages or airplane hangars are permitted when in accordance with ANSI Z223.1 and
NFPA 54 codes or CAN1-B149 and enforcing authorities.
FOR YOUR SAFETY
What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch;do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier,immediately call your fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appli-
ance.
WARNING:Improper installation,adjustment,alteration,service,or maintenance can cause property
damage,injury,or death.Read the installation,operation,and maintenance instructions thoroughly
before installing or servicing this equipment.
Requirements for installation vary depending on the model of heater and the type of installation. Follow the
manufacturer's instructions and comply with all applicable codes.
Some venting requirements that apply to specific gas-fired models are shown on the following pages.
Pilot, Gas Control, and Air Control Descriptions Gas-Fired Unit Heaters
PILOT IGNITION SYSTEMS • Manual Pilot:Manual match lit pilots with 100%shutoff, pilot remains on 100%of time until pilot gas flow is
shut off(Models F&B Only).
• Intermittent Spark Pilot:Automatic lighting of pilot with an electronic spark on a call for heat. Pilot gas flow is
shutoff between heat cycles.Approved for use in the United States with the natural gas supply only on indoor
and outdoor units(Models F&B Only).
• Intermittent Spark Pilot with Timed Lockout:Automatic lighting of pilot with an electronic spark on a call for
heat. Pilot gas flow is shutoff between heating cycles. Locked device stops gas flow to the pilot if the pilot
fails to light in 120 seconds.Reset of lockout requires manual interruption of the thermostat circuit.Approved
for use in the Unites States and Canada with natural or propane gas on indoor and outdoor applications
(Models F&B Only).
• Direct Spark Ignition with Timed Lockout.Automatic lighting of the burner with an electronic spark on a call
for heat by the thermostat.There is no pilot.Trial for ignition is ten seconds after which,if flame is not sensed,
the unit tries for ignition again. If ignition is not proven after three attempts the unit will lockout and then au-
tomatically retry after a one hour down period(Models UDAP,UDAS,UDBP,UDBS&UEAS Only).
NOTE:When installing gravity vented appliances(Model F 8 B)check local and state codes for requirements.Some states require the
addition of spark pilot Option AH2 or AH3.
GAS CONTROL SYSTEMS • Single Stage:Single-stage gas valve which cycles on at 100%fire on a call for heat.
• Two-Stage:Two stage gas valve which fires at 100% or 50% on Models F & B; 100% or 70%on Models
UDAP, UDAS, UDBP& UDBS, as required by a remote two-stage thermostat. (Note:Two-Stage gas valve
not available on Models F& B [sizes 25&50 MBH]or Models UDAP, UDAS, UDBP& UDBS [sizes 30&
45 MBH])
AIR CONTROL SYSTEMS • Air Recirculation Kit(Single-stage units only): First stage control of thermostat energizes unit fan to recircu-
late warm stratified ceiling air. Second stage control of thermostat opens single-stage gas valve.
• Special Air Recirculation Kit(Single-stage units only): Same as the basic kit,with the addition of a manual
summer switch on thermostat for summer fan operation.
OPTIONAL POWER VENTING Use only the Reznor®power venter designed for the particular model and size of heater.
OF GRAVITY VENTED UNITS Understand the operation before installing.When a venter is used with a heater,the room thermostat turns the
-Models F and B venter on and off,and the venter turns the gas controls on and off. When the space calls for heat,the room
thermostat contacts close the circuit which starts the venter.When the venter starts,air from the venter blower
closes an air switch that is built into the venter.
Closing of the air flow switch sends an electric current to the burner controls, opening the gas valve and
sending gas to the burners.When the thermostat is satisfied,the thermostat turns off the venter and the gas
controls.As the venter blower stops,the airflow switch resets to the open position.
Form RZ-C-UH (Version H)Page 34
REZNOR® PRODUCT LIMITED WARRANTY
Thomas& Betts Corporation warrants to the original owner-user that this Reznor product will be free from defects in material or workmanship.
This warranty is limited to twelve (12)months from the date of original installation,whether or not actual use begins on that date,or eighteen
(18)months from date of shipment by Thomas& Betts Corporation,whichever occurs first.
EXTENDED WARRANTY
Models UEAS, UDAP, UDAS, UDBP, and UDBS—Extended nine (9)-year, non-prorated warranty on the heat exchanger, burners, and flue
collection box assembly. Extended four(4)-year,non-prorated warranty on all electrical and mechanical operating components(with the excep-
tion of blower belts on Models UDBP and UDBS).
Models F and B— Extended nine (9)-year, non-prorated warranty on the heat exchanger, burners, draft hood, and flue baffle assembly. Ex-
tended four(4)-year,non-prorated warranty on all electrical and mechanical operating components(with the exception of blower belts on Model
B).
Models OH—Extended four(4)-year,non-prorated warranty on the heat exchanger and combustion chamber.
Application NOTE: Extended four(4)-year warranty on electrical and mechanical operating components excludes any Reznor®HVAC equip-
ment installed in a corrosive or highly humid atmosphere such as a greenhouse.
LIMITATIONS AND EXCLUSIONS
Thomas&Betts Corporation's obligations under this warranty and the sole remedy for its breach are limited to repair,at its manufacturing facil-
ity,of any part or parts of its Reznor products which prove to be defective; or,in its sole discretion, replacement of such products.All returns
of defective parts or products must include the product model number and serial number, and must be made through an authorized Reznor
distributor or arranged through Reznor Customer Service.Authorized returns must be shipped prepaid. Repaired or replacement parts will be
shipped by Thomas& Betts F.O.B.shipping point.
1. The warranty provided herein does not cover charges for labor or other costs incurred in the troubleshooting, repair, removal, installation,
service or handling of parts or complete products.
2.All claims under the warranty provided herein must be made within ninety(90)days from the date of discovery of the defect. Failure to notify
Thomas& Betts of a warranted defect within ninety(90)days of its discovery voids Thomas& Betts's obligations hereunder.
3.The warranty provided herein shall be void and of no effect in the event that(a)the product has been operated outside its designed output
capacity (heating,cooling,airflow);(b)the product has been subjected to misuse, neglect,accident,improper or inadequate maintenance,
corrosive environments,environments containing airborne contaminants(silicone, aluminum oxide, etc.), or excessive thermal shock; (c)
unauthorized modifications are made to the product; (d) the product is not installed or operated in compliance with the manufacturer's
printed instructions;(e)the product is not installed and operated in compliance with applicable building,mechanical,plumbing and electrical
codes;or(f)the serial number of the product has been altered,defaced or removed.
4. The warranty provided herein is for repair or replacement only.Thomas& Betts Corporation shall not be liable for any loss, cost,damage,
or expense of any kind arising out of a breach of the warranty. Further,Thomas& Betts Corporation shall not be liable for any incidental,
consequential,exemplary,special,or punitive damages,nor for any loss of revenue,profit or use,arising out of a breach of this warranty or
in connection with the sale, maintenance, use,operation or repair of any Reznor product. In no event will Thomas& Betts be liable for any
amount greater than the purchase price of a defective product.The disclaimers of liability included in this paragraph 4 shall remain in effect
and shall continue to be enforceable in the event that any remedy herein shall fail of its essential purpose.
5.THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY FOR REZNOR PRODUCTS,AND IS IN LIEU OF ALL OTHER EXPRESS
AND IMPLIED WARRANTIES.THOMAS& BETTS CORPORATION SPECIFICALLY DISCLAIMS ALL OTHER EXPRESS AND IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO,ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PAR-
TICULAR PURPOSE. No person or entity is authorized to bind Thomas& Betts Corporation to any other warranty, obligation or
liability for any Reznor product. Installation, operation or use of the Reznor product for which this warranty is issued shall
constitute acceptance of the terms hereof.